distributed active filter systems (dafs): a new …...distributed active filter systems (dafs): a...

8
Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FOR ADVANCED POWER TECHNOLOGIES (CAPT) Department of Electrical Engineering National Tsing Hua University Hsin-Chu, 30013, TAIWAN email: [email protected]; [email protected] Abstract— This paper proposes a distributed active filter sys- tem (DAFS) for alleviating the harmonic distortion of power systems. The proposed DAFS consists of multiple active filter units installed on the same location or different locations within the power system. The active filter units of the proposed DAFS can cooperate, without any communication among them, to reduce the voltage harmonic distortion of the power lines. Each individual active filter unit functions like a harmonic conductance to reduce voltage harmonics. A droop relationship between the harmonic conductance and the volt-ampere of the active filter unit is programmed into the controller of each unit so multiple active filter units can share the workload of harmonic filtering. The slope of the droop is determined by the volt-ampere rating of the active filter unit in order to distribute the harmonic filtering workload in proportion to the rated capacity of each unit. The principle of operation is explained in this paper and test results based on computer simulation and laboratory test bench are provided to validate the functionalities of the proposed DAFS. I. I NTRODUCTION The proliferation of nonlinear loads in the power system has been growing in an unprecedented pace in recent years due to the advance of power electronics technologies. As a result, the harmonic pollution in the power system deteriorates significantly. Harmonic resonance which results in severe volt- age distortion has been reported. Previous literatures proposes installation of active filter at the end of radial lines to damp the harmonic resonance[1], [2]. However, depending on the magnitude of damping provided by the active filter, the level of harmonic distortion may become worse at certain locations along the radial line. Multiple installations of active filters have been presented in [2], but real-time communications among various units are required to coordinate the operations. A distributed active filter system (DAFS) is proposed in this paper to reduce voltage harmonic distortion of power systems. The proposed DAFS consists of several active filter units installed on various locations, and each unit operates as a harmonic conductance to reduce the voltage harmonics. The active filter units of the DAFS can share the harmonic filtering workload without any communications among them. This feature is accomplished by the droop relationship between the harmonic conductance and the volt-ampere of each active filter. The slope of the droop programmed into each active filter is determined by the volt-ampere rating of the active filter to ensure that the sharing of filtering workload is in proportion to the capacity of the active filter. Using the droop characteristic to share the current of a certain harmonic frequency has been presented in [3]. The proposed DAFS can share the harmonics within the operation bandwidth of the active filter units. II. PRINCIPLES OF OPERATION A simplified one-line diagram of the proposed DAFS is shown in figure 1. Several active filter units, including AF U x , AF U y , and AF U z , are installed along the line. All the active filter units operate as a harmonic conductance to reduce voltage harmonics. For example, the active filter unit AF U x performs as given: i x = G x · E x,h (1) where E x,h represents the harmonics components of the line voltage E x . The control of the active filter is implemented in the synchronous reference frame as illustrated in figure 1. The effectiveness of the synchronous reference frame transforma- tion has been proved by various motor drives applications and utility applications[4], [5], [6]. The three-phase line voltages E xa , E x b , and E xc are measured and transformed into E e xq and E e d in the synchronous reference frame. The ripples of E e xq and E e x d , which represent the line voltage harmonics, are extracted by high-pass filters (HPF). The voltage harmonics ˜ E e xq , ˜ E e x d are then multiplied by the conductance command G x to generate current commands i exq , i ex d of the active filter. The synchronous reference frame current commands are transformed back to three-phase current commands i xa , i x b , and i xc . Based on the current commands i xa , i x b , i xc , and the measured currents i xa , i x b , i xc , the current regulator calculates the voltage commands v xa , v x b , v xc as given: v xa = L x T (i xa i xa )+ E xa v x b = L x T (i x b i x b )+ E x b v xc = 1 · (v xa + v x b ) (2) where L x is the output inductor of the inverter, and T is the sampling period of the digital controller. The Pulse Width Modulator (PWM) then generates the corresponding gating signals so the active filter inverter produces the required 94 IAS 2004 0-7803-8486-5/04/$20.00 © 2004 IEEE

Upload: others

Post on 24-Mar-2020

15 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Distributed Active Filter Systems (DAFS): A new …...Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FORADVANCEDPOWER

Distributed Active Filter Systems (DAFS):A new approach to power system harmonics

Po-Tai Cheng Zhung-Lin LeeCENTER FOR ADVANCED POWER TECHNOLOGIES (CAPT)

Department of Electrical EngineeringNational Tsing Hua University

Hsin-Chu, 30013, TAIWANemail: [email protected]; [email protected]

Abstract— This paper proposes a distributed active filter sys-tem (DAFS) for alleviating the harmonic distortion of powersystems. The proposed DAFS consists of multiple active filterunits installed on the same location or different locations withinthe power system. The active filter units of the proposed DAFScan cooperate, without any communication among them, toreduce the voltage harmonic distortion of the power lines. Eachindividual active filter unit functions like a harmonic conductanceto reduce voltage harmonics. A droop relationship between theharmonic conductance and the volt-ampere of the active filterunit is programmed into the controller of each unit so multipleactive filter units can share the workload of harmonic filtering.The slope of the droop is determined by the volt-ampere rating ofthe active filter unit in order to distribute the harmonic filteringworkload in proportion to the rated capacity of each unit. Theprinciple of operation is explained in this paper and test resultsbased on computer simulation and laboratory test bench areprovided to validate the functionalities of the proposed DAFS.

I. INTRODUCTION

The proliferation of nonlinear loads in the power systemhas been growing in an unprecedented pace in recent yearsdue to the advance of power electronics technologies. As aresult, the harmonic pollution in the power system deterioratessignificantly. Harmonic resonance which results in severe volt-age distortion has been reported. Previous literatures proposesinstallation of active filter at the end of radial lines to dampthe harmonic resonance[1], [2]. However, depending on themagnitude of damping provided by the active filter, the levelof harmonic distortion may become worse at certain locationsalong the radial line. Multiple installations of active filters havebeen presented in [2], but real-time communications amongvarious units are required to coordinate the operations.

A distributed active filter system (DAFS) is proposed inthis paper to reduce voltage harmonic distortion of powersystems. The proposed DAFS consists of several active filterunits installed on various locations, and each unit operatesas a harmonic conductance to reduce the voltage harmonics.The active filter units of the DAFS can share the harmonicfiltering workload without any communications among them.This feature is accomplished by the droop relationship betweenthe harmonic conductance and the volt-ampere of each activefilter. The slope of the droop programmed into each active filteris determined by the volt-ampere rating of the active filter toensure that the sharing of filtering workload is in proportion to

the capacity of the active filter. Using the droop characteristicto share the current of a certain harmonic frequency has beenpresented in [3]. The proposed DAFS can share the harmonicswithin the operation bandwidth of the active filter units.

II. PRINCIPLES OF OPERATION

A simplified one-line diagram of the proposed DAFS isshown in figure 1. Several active filter units, including AFUx,AFUy, and AFUz , are installed along the line. All the activefilter units operate as a harmonic conductance to reducevoltage harmonics. For example, the active filter unit AFUx

performs as given:

ix = Gx · Ex,h (1)

where Ex,h represents the harmonics components of the linevoltage Ex. The control of the active filter is implemented inthe synchronous reference frame as illustrated in figure 1. Theeffectiveness of the synchronous reference frame transforma-tion has been proved by various motor drives applications andutility applications[4], [5], [6]. The three-phase line voltagesExa

, Exb, and Exc

are measured and transformed into Eexq

and Eed in the synchronous reference frame. The ripples of

Eexq

and Eexd

, which represent the line voltage harmonics, areextracted by high-pass filters (HPF). The voltage harmonicsEe

xq, Ee

xdare then multiplied by the conductance command

Gx to generate current commands ie∗xq, ie∗xd

of the activefilter. The synchronous reference frame current commands aretransformed back to three-phase current commands i∗xa

, i∗xb,

and i∗xc.

Based on the current commands i∗xa, i∗xb

, i∗xc, and the

measured currents ixa, ixb

, ixc, the current regulator calculates

the voltage commands v∗xa

, v∗xb

, v∗xc

as given:

v∗xa

=Lx

∆T(i∗xa

− ixa) + Exa

v∗xb

=Lx

∆T(i∗xb

− ixb) + Exb

v∗xc

= −1 · (v∗xa

+ v∗xb

)

(2)

where Lx is the output inductor of the inverter, and ∆Tis the sampling period of the digital controller. The PulseWidth Modulator (PWM) then generates the correspondinggating signals so the active filter inverter produces the required

94IAS 2004 0-7803-8486-5/04/$20.00 © 2004 IEEE

Page 2: Distributed Active Filter Systems (DAFS): A new …...Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FORADVANCEDPOWER

abcto

deqe

deqe

toabc

Exa, Exb

, Exc

ixa, ixb

, ixc

ixa, ixb

, ixc

Eexq

Eexd

Eexq

Eexd

Gx

Gx

Gx

Gx

Sx

Sx

ie∗xq

ie∗xd

i∗xa

i∗xb

i∗xc

v∗xa

v∗xb

v∗xc

HPF

HPFCurrent

Regulator PWM

AFUx

AFUy AFUz

Volt-AmpereCalculator

droop

Fig. 1. An active filter unit of the proposed Distributed Active Filter System and the associated control.

voltages. Conventional Sine/Triangle PWM or the space-vectorPWM can provide effective tracking of the current commandswith high dynamics[7], [8].

In order to share the harmonic filtering workload among theactive filter units of the proposed DAFS, a droop relationshipbetween the conductance command and the volt-ampere of theactive filter unit is programmed into the controller:

G1 = G10 + b1(S1 − S10); G2 = G20 + b2(S2 − S20);· · · · · · · · · Gx = Gx0 + bx(Sx − Sx0);Gy = Gy0 + by(Sy − Sy0); Gz = Gz0 + bz(Sz − Sz0)

(3)

where G1, G2, · · · , Gx, Gy, Gz are the conductance com-mands for the various active filter units of the proposed DAFS,G0 and S0 are the rated operation point of each active filterunit.

The conductance command Gx of AFUx is determined bythe volt-ampere consumption of this active filter unit. To obtainthe volt-ampere Sx of AFUx, the RMS values of voltage andcurrent associated with AFUx are calculated,

ExRMS=

√(Es

xq)2 + (Es

xd)2

dc

ixRMS=

√(isxq

)2 + (isxd)2

dc

Sx = ExRMS· ixRMS

where the dc values are extracted by low-pass filters. Esxq

and Esxd

are the stationary frame values of the line voltagesExa

, Exband Exc

, and isxqand isxd

are stationary frame valuesof the current ixa

, ixband ixc

.A simplified circuit given in figure 2 is to demonstrate

the effectiveness of G − S droop in distributing harmonicfiltering work load. The transmission parameters of section1 and section 2 of the transmission line are given as follows:

T1 =[

cosh(γ1l1) Zc1 sinh(γ1l1)1

Zc1sinh(γ1l1) cosh(γ1l1)

](4)

T2 =[

cosh(γ2l2) Zc2 sinh(γ1l2)1

Zc2sinh(γ2l2) cosh(γ2m2)

](5)

Line section 1 Line section 2

GxGy

ExEyVs

Fig. 2. A simplified circuit for evaluating the effectiveness of the G − Sdroop.

where γ1, γ2 are the propagation constants, Zc1 , Zc2 are thecharacteristic impedances, and l1, l2 are the length of the linesections.

The active filter units are also expressed in the format oftransmission parameters for convenience.

G1 =[

1 0G1 1

]; G2 =

[1 0

G2 1

](6)

Assuming the supply voltage Vs contains harmonics compo-nent Vsh, the voltage harmonics on bus x and bus y can becalculated as follows:

Ex,h = Vsh · 1[1 0

] · T1GyT2Gx

[10

]

Ey,h = Vsh ·[1 0

]T2Gx

[10

]

[1 0

] · T1GyT2Gy

[10

](7)

Assuming the active filter units have filtered down the har-monics so significantly that the RMS voltage at these busesis dominated by its fundamental voltage component. Thenthe volt-ampere associated with AFUx and AFUy can beexpressed as follows:

Sx = 3 · |Ex| · Gx|Ex,h| ≈ 3|Ex,f | · Gx|Ex,h|Sy = 3 · |Ey| · Gy|Ey,h| ≈ 3|Ey,f | · Gy|Ey,h|

(8)

The droop characteristics of both active filter units are given:

Gx = Gx0 + bx(Sx −Sx0); Gy = Gy0 + by(Sy −Sy0) (9)

95IAS 2004 0-7803-8486-5/04/$20.00 © 2004 IEEE

Page 3: Distributed Active Filter Systems (DAFS): A new …...Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FORADVANCEDPOWER

Based on equation (8) and equation (9), the relationshipbetween Sx and bx can be derived:

Sx = 3|Ex,f |(Gx0 + bx(Sx − Sx0))|Ex,h|→(1 − 3|Ex,f |bx|Ex,h|)Sx = 3|Ex,f |(Gx0 − bxSx0)|Ex,h|→Sx ≈ 3|Ex,f |(Gx0 − bxSx0)|Ex,h|

3|Ex,f |bx|Ex,h| =bxSx0 − Gx0

bx

(10)

Similarly,

Sy ≈ 3|Ey,f |(Gy0 − bySy0)|Ey,h|3|Ey,f |by|Ey,h| =

bySy0 − Gy0

by(11)

If the droop characteristics of the active filter units are assignedas follows:

Gx0 − bxSx0 = Gy0 − bySy0 (12)

Then by combining equation (10), equation (11), and equa-tion (12), one can conclude that the volt-ampere of the activefilter units will be approximately inversely-proportional to theslope of the droop:

bxSx ≈ bySy (13)

Previous derivations show that the slope of the droop shouldbe set in inverse-proportion to the volt-ampere rating of eachAFUs to achieve the desired load distribution. This can beextended to the case of multiple installations of active filterunits. The slopes of the droops are related to the volt-ampererating of corresponding active filter units as given,

b1S10 = b2S20 = · · · = bxSx0 = bySy0 = bzSz0 (14)

The above droop settings allow harmonic filtering workloadbeing shared in proportion to the volt-ampere rating of theactive filter units.

III. SIMULATION RESULTS

The proposed DAFS is applied a radial power distributionsystem to demonstrate its capability to share the harmonicfiltering workload among the various active filter units withG − S droop characteristics. The circuit model of the radialline is illustrated in figure 4(a) and figure 5(a). This model isused to demonstrate the harmonic amplification effect of longtransmission lines [1], [2]. Active filter units of the proposedDAFS and nonlinear loads will be placed at different busesalong the line to test the filtering capability. The parametersin the simulation are given as follows:

• Power system: 220 V (line-to-line), 60 Hz. The transmis-sion line parameters are L1 = 0.2mH, R1 = 0.05Ω,C1 = 150µF.

• Nonlinear loads: Two diode rectifiers with filter inductor,DC capacitor, and load resistor rated at 2760 VA and3348 VA are installed at bus 2 and bus 6 of the linerespectively.

• Active filters: Two active filter units, AFU1 and AFU2

are installed. Both active filter units are implementedby conventional hard-switching three-phase inverters asshown in figure 3. C = 4500µF, L = 1.0mH. Thefrequency of PWM operation is fpwm = 10 kHz. Thedroop parameters are G10 = G20 = 0.1Ω−1, b1 = b2 =−8 × 10−4 V−2, and S10 = S20 = 1.0 kVA.

AC

C

L

Fig. 3. The inverter of the individual active filter unit.

A. AFU1 and AFU2 at Bus 9

The diode-rectifier nonlinear loads are installed at bus 2 andbus 6, and the active filter units AFU1 and AFU2 are both atbus 9 as illustrated in figure 4(a). Voltage waveforms on buses1, 2, 4, 6, and 9 are shown in figure 4 to demonstrate the effec-tiveness of DAFS. Before the DAFS is started, the harmonicdistortion is very severe due to the harmonic amplificationalong the radial line. Table I shows that the voltage TotalHarmonic Distortion (THD) on these buses are significantlyreduced as the active filter units start operating. At steady state,AFU1 and AFU2 reaches G1 = G2 = 0.46Ω−1 based on thedroop characteristics, and both units absorb 2.02 A (RMS) ofharmonic current.

TABLE I

BUS VOLTAGE THDS WITH BOTH AFUS INSTALLED AT BUS 9.

Bus 1 Bus 2 Bus 4 Bus 6 Bus 9AFUs off 3.7% 5.9% 7.4% 3.7% 10.2%AFUs on 2.2% 3.4% 5.6% 4.7% 4.6%

B. AFU1 at Bus 9 and AFU2 at Bus 4

In this test, AFU1 is installed at bus 9, and AFU2 isinstalled at bus 4 while the nonlinear diode rectifier loadsremain at bus 2 and bus 6 as illustrated in figure 5(a). This ar-rangement is to test the sharing of harmonic filtering workloadand the overall filtering performances of the proposed DAFS.Figure 5 shows the voltage waveforms of various buses.

Figure 5(b) contains the waveforms when both active filterunits AFU1 and AFU2 operate with G1 = G2 = 0.5Ω−1.The voltage harmonic distortion is improved as the THDs arereduced by the filtering actions of the AFUs, but the sharingof filtering workload between AFU1 and AFU2 is not even.AFU1 filters 2.78 Arms of harmonic current, while AFU2

has only 2.40 Arms. The volt-ampere of AFU1 is 1303 VA,and AFU2 is 1061 VA, which also indicates un-even share ofworkload.

Figure 5(c) shows the waveforms when both active filterunits operate with droop characteristics. The voltage THDsare improved even further. AFU1 and AFU2 filters 2.01 Armsand 2.11 Arms respectively. The active filter units of theDAFS adjust the conductance command G1 and G2 basedon their own droop characteristics, and result in volt-ampereconsumption of 968 VA and 944 VA for AFU1 and AFU2,which indicates that the filtering workload is evenly sharedbetween the active filter units of DAFS.

In order to test the dynamic operation of the AFUs, theloading of diode rectifier on Bus 6 increases from 3348 VA to

96IAS 2004 0-7803-8486-5/04/$20.00 © 2004 IEEE

Page 4: Distributed Active Filter Systems (DAFS): A new …...Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FORADVANCEDPOWER

1 2 3 4 5 6 7 8 9

R1 L1C1

AFU1

AFU2

i1

i2

(a) Arrangement of nonlinear loads and DAFS in section III-A.

−500

0

500VTHD=3.7%

−500

0

500VTHD=5.9%

−500

0

500VTHD=7.4%

−500

0

500VTHD=3.7%

−500

0

500VTHD=10.2%

−20

0

20

0.21 0.22 0.23 0.24−20

0

20

i1

i2

Bus 1

Bus 2

Bus 4

Bus 6

Bus 9

(b) AFUs are off. X axis:sec..

−500

0

500VTHD=2.2%

−500

0

500VTHD=3.4%

−500

0

500VTHD=5.6%

−500

0

500VTHD=4.7%

−500

0

500VTHD=4.6%

−20

0

202.02A

1.11 1.12 1.13 1.14−20

0

202.02A

i1

i2

Bus 1

Bus 2

Bus 4

Bus 6

Bus 9

(c) AFU1 and AFU2 operate with G − S droop. Xaxis:sec..

Fig. 4. Simulation results of section III-A: AFUs are installed at the end of the power line; Voltage waveforms at Bus 1, 2, 4, 6, 9, and active filter currentsof AFU1 and AFU2.

TABLE II

BUS VOLTAGE THDS WITH AFUS INSTALLED AT DIFFERENT LOCATIONS.

Bus 1 Bus 2 Bus 4 Bus 6 Bus 9AFUs with constant gain 1.5% 2.3% 3.3% 3.3% 3.5%AFUs with droop control 1.3% 2.1% 2.8% 2.7% 4.2%

5709 VA at t = 4 s, and then the loading diode rectifier on Bus2 increases from 2760 VA to 4758 VA at t = 7 s. Figure 6(b)shows the volt-ampere associated with the AFUs grows asthe voltage harmonics build up along the line due to loadincrease. And then according to the droop characteristics ofthe AFUs, the conductance commands G1 and G2 will reduceas indicated in figure 6(a). Figure 6(c) shows that the realpower of the AFUs rises significantly in response to the loadincrease.

TABLE III

TRANSITION OF G, S AND P OF AFUS IN RESPONSE TO LOAD INCREASE.

t < 4 sec. 4 sec. < t < 7 sec. t > 7 sec.G1 0.31 Ω−1 0.26 Ω−1 0.19 Ω−1

G2 0.52 Ω−1 0.45 Ω−1 0.42 Ω−1

S1 969 VA 974 VA 980 VAS2 948 VA 955 VA 958 VA

P1 40 W 48 W 68 WP2 26 W 31 W 34 W

C. AFU1 and AFU2 of different VA ratings

Following the circuit arrangement in figure 5(a), the activefilter units AFU1 and AFU2 are installed on bus 9 and4 respectively, but their VA ratings are different, and thedroop slope of each AFU is inversely proportional to itsVA rating as suggested in equation (13). With the G − Sdroop characteristics, the harmonic filtering workload will bedistributed among the AFUs in proportion to their VA rating.

In figure 7(a), AFU1 is rated at 1.0 kVA, and AFU2 is ratedat 1.5 kVA. As the AFUs reaches steady state, AFU1 filters2.02 Arms at 959 VA. AFU2 filters 3.05 Arms at 1345 VA. Theratio of loading is approximately 1.40 (AFU2 : AFU1).

In figure 7(b), AFU1 is rated at 1.5 kVA, and AFU2 israted at 1.0 kVA. At steady state, AFU1 filters 2.97 Arms at1405 VA, and AFU2 filters 2.18 Arms at 953 VA. The ratio isapproximately 1.47 (AFU1 : AFU2).

IV. LABORATORY TEST RESULTS

A test bench illustrated in figure 8 is constructed to test theperformance of the proposed DAFS. The system parametersare as follows:

• The system voltage is 110 V(line-to-line), 60 Hz. L =0.2mH and C = 150µF are to amply harmonics alongthe line.

• Nonlinear diode rectifier loads are installed on bus 1(540 VA) and bus 3(630 VA).

97IAS 2004 0-7803-8486-5/04/$20.00 © 2004 IEEE

Page 5: Distributed Active Filter Systems (DAFS): A new …...Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FORADVANCEDPOWER

1 2 3 4 5 6 7 8 9

R1 L1C1

AFU1AFU2

i1

i2

(a) Arrangement of nonlinear loads and DAFS in section III-B.

−500

0

500VTHD1.5%

−500

0

500VTHD=2.3%

−500

0

500VTHD=3.3%

−500

0

500VTHD=3.3%

−500

0

500VTHD=3.5%

−20

0

202.76A

0.61 0.62 0.63 0.64−20

0

202.40A

i1

i2

Bus 1

Bus 2

Bus 4

Bus 6

Bus 9

(b) Both AFUs operate with G1 = G2 = 0.5Ω.X axis:sec..

−500

0

500VTHD=1.3%

−500

0

500VTHD=2.1%

−500

0

500VTHD=2.8%

−500

0

500VTHD=2.7%

−500

0

500VTHD=4.2%

−20

0

202.01A

1.11 1.12 1.13 1.14−20

0

202.11A

i1

i2

Bus 1

Bus 2

Bus 4

Bus 6

Bus 9

(c) AFUs operate with droop characteristics. X axis: sec..

Fig. 5. Simulation results of section III-B: AFUs are installed at different locations; Voltage waveforms at Bus 1, 2, 4, 6, 9, and active filter currents ofAFU1 and AFU2.

4 5 6 7 8 9 100

0.1

0.2

0.3

0.4

0.5

0.6

Con

duct

ance

Time

G1

G2

(a) Variation of G1 and G2. X axis: sec.;Y axis: Ω−1.

4 5 6 7 8 9 10900

950

1000

1050

App

aren

t pow

er

Time

S1

S2

(b) Variation of S1 and S2. X axis: sec.;Y axis: VA.

4 5 6 7 8 9 100

10

20

30

40

50

60

70

80

Rea

l pow

er

Time

P1

P2

(c) Variation of P1 and P2. X axis: sec.;Y axis: Watt.

Fig. 6. Transition of the AFUs operations in response to load increase.

• Active filter units AFU1 and AFU2 are installed on bus4 and bus 2 respectively. The switching frequency of theactive filter inverter is 10 kHz.

A. AFU1 and AFU2 of the same VA rating

In this test, AFU1 and AFU2 are both rated at 150 VA.The slope of the droop is b1 = b2 = −0.02V−2. Before theactive filter units are started, the line voltages on all 4 busesexhibit severe harmonic distortion as shown in figure 9(a). Thedistortion is significantly reduced as in figure 9(b) after the

AFUs start operation. The THDs of line voltages are givenin table V. The operation of AFU1 and AFU2 are givenin figure 10(a) and figure 10(b) respectively. At steady state,AFU1 absorbs S1 ≈ 137VA with G1 ≈ 0.29Ω−1, AFU2

absorbs S2 ≈ 139VA with G2 ≈ 0.31Ω−1. The filteringworkload is evenly distributed between AFU1 and AFU2 asthe test results indicate. Figure 11 shows the conductancecommand G1, G2 and the VA consumption S1, S2 of AFU1

and AFU2 respectively. AFU2 is started at t1, and AFU1

is engaged at t2. As both AFUs reach steady state between

98IAS 2004 0-7803-8486-5/04/$20.00 © 2004 IEEE

Page 6: Distributed Active Filter Systems (DAFS): A new …...Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FORADVANCEDPOWER

−500

0

500VTHD=1.2%

−500

0

500VTHD=1.9%

−500

0

500VTHD=2.4%

−500

0

500VTHD=2.6%

−500

0

500VTHD=3.5%

−20

0

202.02A

1.11 1.12 1.13 1.14−20

0

203.06A

i1

i2

Bus 1

Bus 2

Bus 4

Bus 6

Bus 9

(a) AFU1 rated at 1kV A, AFU2 rated at 1.5kV A. Xaxis: sec.

−500

0

500VTHD=1.5%

−500

0

500VTHD=2.4%

−500

0

500VTHD=3.6%

−500

0

500VTHD=3.5%

−500

0

500VTHD=3.5%

−20

0

202.97A

1.11 1.12 1.13 1.14−20

0

202.18A

i1

i2

Bus 1

Bus 2

Bus 4

Bus 6

Bus 9

(b) AFU1 rated at 1.5kV A, AFU2 rated at 1.0kV A.X axis: sec.

Fig. 7. Simulation results of section III-C: AFUs of different VA ratings are installed at different locations; voltage waveforms at Bus 1, 2, 4, 6, 9, andactive filter currents of AFU1 and AFU2.

TABLE IV

BUS VOLTAGE THDS WITH AFUS OF DIFFERENT RATINGS INSTALLED AT

DIFFERENT LOCATIONS.

Bus 1 Bus 2 Bus 4 Bus 6 Bus 91.2% 1.9% 2.4% 2.6% 3.5%

(a) AFU1 rated at 1.0 kVA, AFU2 ratedat 1.5 kVA.

Bus 1 Bus 2 Bus 4 Bus 6 Bus 91.5% 2.4% 3.6% 3.5% 3.5%

(b) AFU1 rated at 1.5 kVA, AFU2 ratedat 1.0 kVA

AFU1AFU2

i1i2Bus 1 Bus 2 Bus 3 Bus 4vs

Fig. 8. Laboratory test bench of the proposed DAFS.

t2 and t3, S1 ≈ 138VA and S2 ≈ 140VA indicate evendistribution of harmonic filtering workload. At t3, the loadingon the rectifier at bus 3 is reduced from 1.63 kVA to 0.3 kVA,and the reduction of harmonics distortion causes S1 and S2

of the AFUs to decrease slightly. Then the droop controllersraise the conductance commands G1 and G2 respectively asshown in figure 11 and table VI.

B. AFU1 and AFU2 of different VA rating

The volt-ampere rating of AFU1 and AFU2 are 200 VAand 150 VA respectively in this test. The droop slopes are alsoadjusted to b1 = −0.015V−2 and b2 = −0.02V−2. As both

(a) Before the AFUs are started.

(b) AFUs are in operation.

Fig. 9. Line voltages of all 4 buses. Top to bottom: bus 1, bus 2, bus 3, andbus 4. X axis: 4 ms/div; Y axis: 200 V/div.

99IAS 2004 0-7803-8486-5/04/$20.00 © 2004 IEEE

Page 7: Distributed Active Filter Systems (DAFS): A new …...Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FORADVANCEDPOWER

TABLE V

THDS OF LINE VOLTAGES.

Bus 1 Bus 2 Bus 3 Bus 4AFUs off 1.3% 5.4% 8.5% 9.8%AFUs on 0.9% 2.2% 3.9% 4.5%

i∗1

i1

Ebus4

(a) AFU1

i∗2

i2

Ebus2

(b) AFU2

Fig. 10. Operation of the AFU’s inverter. Top to bottom: inverter referencecurrent, inverter output current, inverter terminal voltage. X axis: 4 ms/div; Yaxis: 2 A/div or 200 V/div.

TABLE VI

OPERATION OF AFUS IN SECTION IV-A.

t1 < t < t2 t < t2 < t < t3 t > t3G1 0.152 0.162 0.214G2 (off) 0.312 0.372

t1 t2 t3

G2

S2

G1

S1

Fig. 11. G1, S1 and G2, S2 of active filter units. X axis: 4 s/div; Y axis:0.2 Ω−1/div or 200 VA/div.

AFUs reaches steady state between t2 and t3, S1 ≈ 187VAand S2 ≈ 136VA respectively. The AFUs share the filteringworkload in approximate proportion to their volt-ampere ratingas expected. The same load reduction as in section IV-A isintroduced at t3, S1 and S2 reduce slightly and the droopcontrollers of both units raise the conductance commands G1

and G2 in response as shown in figure 12 and table VII.

TABLE VII

OPERATION OF AFUS IN SECTION IV-B.

t1 < t < t2 t < t2 < t < t3 t > t3G1 0.24 0.25 0.32G2 (off) 0.36 0.40

t1 t2 t3

G2

S2

G1

S1

Fig. 12. G1, S1 and G2, S2 of active filter units. X axis: 4 s/div; Y axis:0.2 Ω−1/div or 200 VA/div.

V. SUMMARY

A distributed active filter system is proposed in this paper.The conductance-volt ampere (G − S) droop is developed inthe proposed DAFS to achieve even distribution of harmonicfiltering workload among various active filter units. Withproper settings of the droop slope as given in equation (12)and equation (13), each AFU within the DAFS can share the

100IAS 2004 0-7803-8486-5/04/$20.00 © 2004 IEEE

Page 8: Distributed Active Filter Systems (DAFS): A new …...Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FORADVANCEDPOWER

filtering workload based on its own VA capacity. Whetherthe active filter units are installed at the same location orat different locations, the G − S droop accomplishes thedistribution without any communications among AFUs, whichis a significant advantage in the deployment of the DAFS.

Computer simulation and laboratory test results validate theeffectiveness of the G − S droop characteristics in allocatingfiltering responsibility. The results also show that a distributeddeployment of active filter units can improve voltage THDsalong the power lines more effectively than installing activefilter at the end of the radial line. Figure 13 shows the THDsof bus voltages along the radial line of the simulation circuitmodel under different placements of nonlinear loads, and twoDAFS deployment configurations, AFU1, AFU2 both at bus9(∗ traces), and AFU1 at bus 9, AFU2 at bus 4( traces).If the DAFS is off ( traces), the harmonic amplification issevere along the line no matter where the nonlinear loads areas in figure 13. If both AFUs are installed at bus 9, the voltageTHD toward the end of line is reduced significantly, but theimprovement is not clear in the middle section of the line.With AFU1 at bus 9 and AFU2 at bus 4, the voltage THDsalong the entire line can be reduced.

The effectiveness of the proposed DAFS on radial trans-mission lines has been validated by previous simulation andlaboratory test results. As the proliferation of power electronicstechnologies continue to surge, the phenomena of harmonicresonance can occur at the industrial facility. The combina-tion of power factor correction capacitors and the systeminductance (power cables, transformers, etc) often result inresonant frequency in the 300-600 Hz range[9]. Most activefilter technologies, which focus on compensating harmoniccurrent of nonlinear loads, can not adequately address this is-sue. The proposed DAFS can deploy several small-rated activefilter units at various locations within the facility to damp theharmonic resonance. Compared to a centralized, large-ratedactive filter, the distributed, small-rated active filters of theDAFS can reduce harmonics in the power system or in amanufacturing facility with improved cost-effectiveness.

REFERENCES

[1] K. Wada, H. Fujita, and H. Akagi, “Considerations of a shunt active filterbased on voltage detection for installation on a long distribution feeder,”IEEE Transactions on Industry Applications, pp. 1123–1130, July/August2002.

[2] P. Jintakosonwit, H. Fujita, H. Akagi, and S. Ogasawara, “Implementationand performance of cooperative control of shunt active filters for harmonicdamping throughout a power distribution system,” IEEE Transactions onIndustry Applications, vol. 39, no. 2, pp. 556–564, March/April 2003.

[3] U. Borup, F. Blaabjerg, and P. N. Enjeti, “Sharing of nonlinar load inparallel-connected three-phase converters,” IEEE Transactions on Indus-try Applications, vol. 37, no. 6, pp. 1817–1823, November/December2001.

[4] P. T. Cheng, C. C. Huang, C. C. Pan, and S. Bhattacharya, “Design andimplementation of a series voltage sag compensator under practical utilityconditions,” IEEE Transactions on Industry Applications, vol. 39, no. 3,pp. 844–853, May/June 2003.

[5] P. T. Cheng, S. Bhattacharya, and D. Divan, “Experimental verificationof dominant harmonic active filter for high power applications,” IEEETransactions on Industry Applications, vol. 36, no. 2, pp. 567–577,March/April 2000.

[6] S. Bhattacharya, D. Divan, and B. Banerjee, “Synchronous frame har-monic isolator using active series filter,” in EPE ’91 Conference Record,1991, pp. 30–35.

0

Tot

al h

arm

onic

dis

tort

ion(

%)

No AFUsAFU1 & AFU2 @BUS9AFU1@BUS9 & AFU2@BUS4

1

2

2 3

4

4 5

6

6 7

8

8 9

(a) Nonlinear loads at bus 2 and bus 6.

0

Tot

al h

arm

onic

dis

tort

ion(

%)

No AFUsAFU1 & AFU2 @BUS9AFU1@BUS9 & AFU2@BUS4

1

2

2 3

4

4 5

6

6 7

8

8 9

(b) Nonlinear loads at bus 2 and bus 3.

0

Tot

al h

arm

onic

dis

tort

ion(

%)

No AFUsAFU1&AFU2 @BUS9AFU1@BUS9 & AFU2@BUS4

1

2

2 3

4

4 5

6

6 7

8

8 9

(c) Nonlinear loads at bus 5 and bus 6.

Fig. 13. Voltage THDs under different load and AFUs locations based onsimulation.

[7] T. G. Habetler, “A space vector-based rectifier regulator for ac/dc/acconverters,” IEEE Transactions on Power Electronics, vol. 8, no. 1, pp.30–36, January 1993.

[8] R. Wu, S. B. Dewan, and G. R. Slemon, “Analysis of a pwm acto dc voltage source converter under predicted current control withfixed switching frequency,” IEEE Transactions on Industry Applications,vol. 27, no. 4, pp. 756–764, July/August 1991.

[9] E. J. Currence, J. E. Plizga, and H. N. Nelson, “Harmonic resonanceat a medium-sized industrial plant,” IEEE Transactions on IndustryApplications, vol. 31, no. 3, pp. 682–690, May/June 1995.

101IAS 2004 0-7803-8486-5/04/$20.00 © 2004 IEEE