1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Dana Hildebrand Avista Utilities Presented March 16 th , 2015 At the 32 nd Annual Hands-On Relay School Washington State University Pullman, Washington

Upload: iam-phil

Post on 08-Nov-2015

41 views

Category:

Documents


1 download

TRANSCRIPT

  • 1

    DISTRIBUTION PROTECTION OVERVIEW

    Kevin Damron & Dana Hildebrand

    Avista Utilities

    Presented

    March 16th, 2015

    At the 32nd Annual

    Hands-On Relay School

    Washington State University

    Pullman, Washington

  • 2

    Table of Contents

    System Overview .... 3

    Distribution (3-30MVA ) Transformer Protection ...... 12

    Relay Overcurrent Curves ... 19

    Symmetrical Components .... 23

    Distribution Fuse Protection .. 38

    Conductors ..... 28

    Coordinating Time Intervals . 43

    Transformer Relay Settings using Electromechanical Relays . 48

    IEEE Device Designations ... 51

    Electromechanical Relays used on Distribution Feeders.. 53

    Transformer & Feeder Protection using Microprocessor Relays . 57

    Transformer Differential Protection . 68

    Moscow 13.8kV Feeder Coordination Example . 71

  • 3

    System Overview - Distribution Protection

    Objective:

    Protect people (company personnel and the public) and equipment by the proper

    application of overcurrent protective devices.

    Devices include:

    Relays operating to trip (open) circuit breakers or circuit switchers, and/or fuses blowing

    for the occurrence of electrical faults on the distribution system.

    Design tools used:

    1 Transformer and conductor damage curves,

    2 - Time-current coordination curves (TCCs), fuse curves, and relay overcurrent

    elements based on symmetrical components of fault current.

    Documentation:

    1 - One-line diagrams and Schematics with standardized device designations as defined

    by the IEEE (Institute of Electrical and Electronics Engineers) keeps everyone on the

    same page in understanding how the system works.

    2 - TCCs

  • XFMR 12/16/20 MVA

    115/13.8kV

    115 kV SYSTEM

    13.8 kV BUS

    500A, 13.8 kVFDR #515

    DELTA/WYE

    LINE RECLOSER P584

    3 = 5158SLG = 5346

    3 = 3453SLG = 2762

    PT-2BPT-2A

    3 = 3699SLG = 3060

    PT-3B PT-3A PT-4

    #4 ACSR

    1 PHASE#4 ACSR #4 ACSR

    #4 ACSR

    #2 ACSR#4 ACSR

    2/0 ACSR#2 ACSR

    3 = 1907SLG = 1492

    3 = 322SLG = 271

    3-250 KVAWYE/WYE

    PT-865T

    A-172

    MOSCOW

    1 PHASE#4 ACSR

    3 = 558SLG = 463

    PT-3C

    PT-6BPT-6A

    PT-6C

    HIGH LEAD LOW

    3 = 1210SLG = 877

    PT-1

    PT-5

    PT-7

    FUSE

    556 ACSR

    556 ACSR

    13.8 kV FDR #512

    500 A FDR

    4

    System Overview Inside the

    Substation Fence

    Transformer

    relays

    Feeder relay

  • 5

    XFMR 12/16/20 MVA

    115/13.8kV

    115 kV SYSTEM

    13.8 kV BUS

    500A, 13.8 kVFDR #515

    DELTA/WYE

    LINE RECLOSER P584

    3 = 5158SLG = 5346

    3 = 3453SLG = 2762

    PT-2BPT-2A

    3 = 3699SLG = 3060

    PT-3B PT-3A PT-4

    #4 ACSR

    1 PHASE#4 ACSR #4 ACSR

    #4 ACSR

    #2 ACSR#4 ACSR

    2/0 ACSR#2 ACSR

    3 = 1907SLG = 1492

    3 = 322SLG = 271

    3-250 KVAWYE/WYE

    PT-865T

    A-172

    MOSCOW

    1 PHASE#4 ACSR

    3 = 558SLG = 463

    PT-3C

    PT-6BPT-6A

    PT-6C

    HIGH LEAD LOW

    3 = 1210SLG = 877

    PT-1

    PT-5

    PT-7

    FUSE

    556 ACSR

    556 ACSR

    13.8 kV FDR #512

    500 A FDR

    System Overview Outside the

    Substation Fence

    Midline

    recloser

    relay

  • XFMR 12/16/20 MVA

    115/13.8kV

    115 kV SYSTEM

    13.8 kV BUS

    500A, 13.8 kVFDR #515

    DELTA/WYE

    LINE RECLOSER P584

    3 = 5158SLG = 5346

    3 = 3453SLG = 2762

    PT-2BPT-2A

    3 = 3699SLG = 3060

    PT-3B PT-3A PT-4

    #4 ACSR

    1 PHASE#4 ACSR #4 ACSR

    #4 ACSR

    #2 ACSR#4 ACSR

    2/0 ACSR#2 ACSR

    3 = 1907SLG = 1492

    3 = 322SLG = 271

    3-250 KVAWYE/WYE

    PT-865T

    A-172

    MOSCOW

    1 PHASE#4 ACSR

    3 = 558SLG = 463

    PT-3C

    PT-6BPT-6A

    PT-6C

    HIGH LEAD LOW

    3 = 1210SLG = 877

    PT-1

    PT-5

    PT-7

    FUSE

    556 ACSR

    556 ACSR

    13.8 kV FDR #512

    500 A FDR

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

    For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 252 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    MIDLINE OCR

    MAXIMUM MIDLINE FUSE

    Fault I=5665.9 A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

    2

    2. IDR 252 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

    3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

    4

    4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

    5

    5f

    5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s

    6

    6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

    A

    A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

    FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

    6

    System Overview Each device has at least one curve plotted with current and time values

    on the Time Coordination Curve.

  • 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

    For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 252 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    MIDLINE OCR

    MAXIMUM MIDLINE FUSE

    Fault I=5665.9 A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

    2

    2. IDR 252 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

    3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

    4

    4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

    5

    5f

    5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s

    6

    6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

    A

    A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

    FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

    7

    System Overview

    Damage Curves:

    - transformer

    - conductor

    So, what curve goes where?

    What are the types of curves?

    Protective Curves:

    - relay

    - fuse

    Damage curves are at the top and to

    the right of the TCC.

    Protective curves lowest and to the

    left on the TCC correspond to those

    devices farther from the substation

    where the fault current is less.

  • 8

    Transformer Protection - Damage Curve ANSI/IEEE C57.109-1985

    The main damage curve line shows only the thermal effect

    from transformer through-fault currents. It is graphed

    from data entered below (MVA, Base Amps, %Z ):

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    T IME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. M15 P584 GND INST INST TD=1.000CTR=100 Pickup=3.A No inst. TP@5=0.048s

    A

    A. T ransf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.

    The dog leg on the curve is added to allow for additional

    thermal and mechanical damage from (typically more

    than 5) through-faults over the life of a transformer

    serving overhead feeders.

    Dog leg curve - 10 times base current at 2 seconds.

    Main curve - 25 times base current at 2 seconds.

    Time at 50% of the maximum per-unit

    through fault current = 8 seconds.

    Avista has Category III size (5-30MVA) Distribution Transformers in service per the above standard.

  • 9

    Copper Conductor Damage Curves ACSR Conductor Damage Curves

    (2/0 damage at 1500A @ 100sec.) (2/0 damage at 900A @ 100sec.)

    Conductor Damage Curves

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

    For ACSR Conductor Damage Curves No.

    Comment Date 12/13/05

    1

    1. M15-515 Phase INST INST TD=1.000CTR=160 Pickup=7.A No inst. TP@5=0.048s

    A

    A. Conductor damage curve. k=0.08620 A=355107.0 cmilsConductor ACSR336.4 ACSR

    B

    B. Conductor damage curve. k=0.08620 A=167800.0 cmilsConductor ACSR AWG Size 4/04/0 ACSR

    C

    C. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 2/02/0 ACSR

    D

    D. Conductor damage curve. k=0.08620 A=83690.0 cmilsConductor ACSR AWG Size 1/01/0 ACSR

    E

    E. Conductor damage curve. k=0.08620 A=52630.0 cmilsConductor ACSR AWG Size 2#2 ACSR

    FF. Conductor damage curve. k=0.08620 A=33100.0 cmilsConductor ACSR AWG Size 4#4 ACSR

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

    For Copper Conductor Damage Curves No.

    Comment Date 12/13/05

    1

    1. M15-515 Phase INST INST TD=1.000CTR=160 Pickup=7.A No inst. TP@5=0.048s

    A

    A. Conductor damage curve. k=0.14040 A=105500.0 cmilsConductor Copper (bare) AWG Size 2/02/0 Copper

    B

    B. Conductor damage curve. k=0.14040 A=83690.0 cmilsConductor Copper (bare) AWG Size 1/01/0 Copper

    C

    C. Conductor damage curve. k=0.14040 A=52630.0 cmilsConductor Copper (bare) AWG Size 2#2 Copper

    D

    D. Conductor damage curve. k=0.14040 A=33100.0 cmilsConductor Copper (bare) AWG Size 4#4 Copper

    EE. Conductor damage curve. k=0.14040 A=20820.0 cmilsConductor Copper (bare) AWG Size 6#6 Copper

  • 10

    Conductor Rating

    556 730

    336.4 530

    4/0 340

    2/0 270

    1/0 230

    #2 180

    #4 140

    ACSR

    Ampacity Ratings

    Conductor Rating

    2/0 360

    1/0 310

    #2 230

    #4 170

    #6 120

    Copper

    Ampacity Ratings

    Conductor Ampacities

    Conductor at 25C ambient taken from the Westinghouse Transmission & Distribution book.

  • 11

    Comparing a 140T fuse versus a

    #4 ACSR Damage curve.

    The 140T wont protect the

    conductor below about

    550 amps where the curves cross.

    Conductor Protection Graph

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kV#4 ACSR & 140T By Protection

    For Aspen File: HORS M15 EXP.olr No.

    Comment Date 3/06

    1

    1. Moscow 515 Kear 140T Kearney 140TTotal clear.

    A

    A. Conductor damage curve. k=0.08620 A=33100.0 cmilsConductor ACSR AWG Size 4

  • 12

    Transformer Protection using

    115 kV Fuses

  • 13

    Transformer Protection using

    115 kV Fuses

    Used at smaller substations up to 7.5 MVA

    transformer due to low cost of protection.

    Other advantages are:

    - Low maintenance

    - Panel house & station battery not required

    There are also several disadvantages to

    using fuses however which are:

    Low interrupting rating from 1,200A (for

    some older models) up to 10,000A at 115 kV.

    By contrast a circuit switcher can have a rating

    of 25KAIC and our breakers have normally

    40KAIC.

    The fuses we generally use are rated to blow

    within 5 minutes at twice their nameplate

    rating. Thus, a 65 amp fuse will blow at 130

    amps. This compromises the amount of

    overload we can carry in an emergency and

    still provide good sensitivity for faults.

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 KVROK 451R2 By JDH

    For ROK FDR 451, BUS FAULTS: 3LG=3580A, SLG=3782A, L-L=3100A No.

    Comment ASPEN FILE: ROK NEW XFMR (2005 BASE).OLR Date 2-13-07

    STATION TRANSFORMER PROTECTION

    FEEDER VCR PROTECTION

    MAXIMUM FEEDER FUSE

    1

    1. LAT RP4211 50N CO-11 INST TD=1.000CTR=500/5 Pickup=2.A No inst. TP@5=0.048s

    2

    2. SMD-2B 65E VERY SLOW 176-19-065Minimum melt. H=8.33

    3

    3. LAT RP4211 50P CO-11 INST TD=1.000CTR=500/5 Pickup=3.5A No inst. TP@5=0.048s

    4

    4. LAT RP4211 51P CO-11 CO-11 TD=2.000CTR=500/5 Pickup=3.A No inst. TP@5=0.5043s

    5

    5. LAT RP4211 51N CO-11 CO-11 TD=4.000CTR=500/5 Pickup=2.A No inst. TP@5=1.0192s

    6

    6. LAT RP4211 FUSE S&C Link 65TTotal clear.

    A

    A. Transf. damage curve. 7.50 MVA. Category 3Base I=313.78 A. Z= 7.3 percent.Rockford 13.8kV - ROCKFORD115 115.kV 1 T

  • 14

    The fuse time current characteristic (TCC) is fixed (although you can buy a standard, slow

    or very slow speed ratio which are different inverse curves).

    The sensitivity to detect lo-side SLG faults isnt as good as using a relay on a circuit

    switcher or breaker. This is because we use DELTA/WYE connected transformers so the

    phase current on the 115 kV is reduced by the 3 as opposed to a three phase fault.

    Some fuses can be damaged and then blow later at some high load point.

    When only one 115 kV fuse blows, it subjects the customer to low distribution voltages.

    For example the phase to neutral distribution voltages on two phases on the 13.8 kV become

    50% of normal.

    No indication of faulted zone (transformer, bus or feeder).

    Transformer Protection using 115 kV Fuses - continued

    A

    B

    C

    a

    b

    c

    1.0 PU

    0.5 PU0.5 PU

  • 15

    Transformer Protection using a Circuit Switcher Showing Avistas present standard using Microprocessor relays.

    13.8kV

    115kV

  • 16

    Transformer Protection using a Circuit Switcher Showing Avistas old standard using Electromechanical relays.

  • 17

    Transformer Protection using a Circuit Switcher

    Some advantages to this over fuses are:

    Higher interrupting.

    Relays can be set to operate faster

    and with better sensitivity than

    fuses.

    Three phase operation.

    Provide better coordination with

    downstream devices.

    Some disadvantages would be:

    Higher cost.

    Higher maintenance.

    Requires a substation battery, panel

    house and relaying.

    Transformer requires CTs.

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVIDR FEEDER 251 By JDH

    For Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 251 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    LO-SIDE CT'S

    MINIMUM FAULT TO DETECT:3LG=2460A, SLG=1833A, L-L=2130A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33

    2

    2. IDR A-777 51G 351 SEL-VI TD=1.000CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33

    3

    3. IDR A-777 51N 351 SEL-EI TD=5.700CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s

    4

    4. IDR A-777 51Q 351 SEL-EI TD=4.200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33

    5

    5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

    6

    6. IDR 251 50P 351S INST TD=1.000CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

    7

    7. IDR 251 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

    8

    8. IDR 251 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

    9

    9. IDR 251 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

    10

    10. IDR 251 51Q 351S SEL-EI TD=3.500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

    11

    11. 251 140T FUSE stn S&C Link140TTotal clear.

    A

    A. Conductor damage curve. k=0.08620 A=133100.0 cmilsConductor ACSR AWG Size 2/0FEEDER 251 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

  • 18

    Transformer Protection using a Breaker

    This is very similar to using a circuit switcher with a couple of advantages such as: Higher interrupting 40kAIC for the one shown below.

    Somewhat faster tripping than a circuit switcher (3 cycles vs. 6 8 cycles).

    Possibly less maintenance than a circuit switcher.

    The CTs would be located on the breaker so it would interrupt faults on the bus section up to

    the transformer plus the transformer high side bushings.

  • 19

    SEL Various Relay Overcurrent Curves.

    Extremely Inverse steepest

    Very Inverse

    Inverse

    Moderately Inverse

    Short Time Inverse least steep

    The five curves shown here have the same

    pickup settings , but different time dial

    settings.

    These are basically the same as various E-M

    relays.

    Avista uses mostly extremely inverse on

    feeders to match the fuse curves.

    Relay Overcurrent Curves

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. EXTREMELY INVERSE SEL-EI TD=15.000CTR=800/5 Pickup=6.A No inst. TP@5=4.0718s

    2

    2. INVERSE SEL-I TD=2.000CTR=800/5 Pickup=6.A No inst. TP@5=0.8558s

    3

    3. MODERATELY INVERSE SEL-2xx-MI TD=1.000CTR=800/5 Pickup=6.A No inst. TP@5=0.324s

    4

    4. SHORT TIME INVERSE SEL-STI TD=1.000CTR=800/5 Pickup=6.A No inst. TP@5=0.1072s

    5 5. VERY INVERSE SEL-VI TD=6.000CTR=800/5 Pickup=6.A No inst. TP@5=1.5478s

  • 20

    Time dial

    - at what time delay will the relay operate to

    trip the breaker

    - the larger time dial means more time delay

    - also known as lever from the

    electromechanical relay days

    - Instantaneous elements have a time dial

    of 1 and operate at 0.05 seconds.

    - Instantaneous curves are shown as a flat

    horizontal line starting at the left at the

    pickup value and plotted at 0.05 seconds.

    Relay Overcurrent Curves - Pickups & Time Dials

    Pickup

    - the current at which the relay will operate to trip the breaker.

    - also known as tap from the electromechanical relay days

    -expressed in terms of the ratio of the current transformer (CTR) that the relay is connected to,

    - e.g., a relay with a CTR of 120 and a pickup (or tap) of 4 will operate to trip the breaker at 480

    amps

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVIDR FEEDER 251 By JDH

    For Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 251 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    LO-SIDE CT'S

    MINIMUM FAULT TO DETECT:3LG=2460A, SLG=1833A, L-L=2130A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33

    2

    2. IDR A-777 51G 351 SEL-VI TD=1.000CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33

    3

    3. IDR A-777 51N 351 SEL-EI TD=5.700CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s

    4

    4. IDR A-777 51Q 351 SEL-EI TD=4.200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33

    5

    5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

    6

    6. IDR 251 50P 351S INST TD=1.000CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

    7

    7. IDR 251 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

    8

    8. IDR 251 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

    9

    9. IDR 251 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

    10

    10. IDR 251 51Q 351S SEL-EI TD=3.500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

    11

    11. 251 140T FUSE stn S&C Link140TTotal clear.

    A

    A. Conductor damage curve. k=0.08620 A=133100.0 cmilsConductor ACSR AWG Size 2/0FEEDER 251 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

  • 21

    Same Time Dial = 9

    Right curve picks up at 960 Amps

    Left curve picks up at 320Amps

    Relay Overcurrent Curves - Example of Different Pickup & Time Dial Settings

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. EXT INV 1 SEL-EI TD=15.000CTR=800/5 Pickup=6.A No inst. TP@5=4.0718s

    2 2. ~EXT INV 1 SEL-EI TD=12.000CTR=800/5 Pickup=6.A No inst. TP@5=3.2574s

    3

    3. ~EXT INV 2 SEL-EI TD=9.000CTR=800/5 Pickup=6.A No inst. TP@5=2.4431s

    4

    4. ~EXT INV 3 SEL-EI TD=6.000CTR=800/5 Pickup=6.A No inst. TP@5=1.6287s

    5

    5. ~EXT INV 4 SEL-EI TD=2.000CTR=800/5 Pickup=6.A No inst. TP@5=0.5429s

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. EXT INV 1 SEL-EI TD=9.000CTR=800/5 Pickup=6.A No inst. TP@5=2.4431s

    2

    2. ~EXT INV 1 SEL-EI TD=9.000CTR=800/5 Pickup=5.A No inst. TP@5=2.4431s

    3

    3. ~EXT INV 2 SEL-EI TD=9.000CTR=800/5 Pickup=4.A No inst. TP@5=2.4431s

    4

    4. ~EXT INV 3 SEL-EI TD=9.000CTR=800/5 Pickup=3.A No inst. TP@5=2.4431s

    5

    5. ~EXT INV 4 SEL-EI TD=9.000CTR=800/5 Pickup=2.A No inst. TP@5=2.4431s

    Same Pickup = 960 Amps

    Top curve Time Dial = 15

    Bottom curve Time Dial = 2

  • 22

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVINT 12F1 By JDH

    For Indian Trail feeder 12F1 in INT 2007base.olr No.

    Comment AT SUB: 3LG= 5719A, LL=4951A, SLG= 5880A Date 1-29-08

    TRANSFORMER PROTECTION

    STATION VCB 12F1 PROTECTION

    1 1. INT A-742 51P 351 SEL-VI TD=10.000CTR=600/5 Pickup=0.8A No inst. TP@5=2.5797s H=8.33

    2

    2. INT 12F1 51P 351S SEL-VI TD=1.800CTR=800/5 Pickup=3.A No inst. TP@5=0.4643s

    3

    3. INT 12F1 51G 351S SEL-VI TD=0.900CTR=800/5 Pickup=3.A No inst. TP@5=0.2322s

    4

    4. INT 12F1 51Q 351S SEL-VI TD=0.500CTR=800/5 Pickup=3.A No inst. TP@5=0.129s

    5 5. INT A-742 51G 351 SEL-VI TD=5.000CTR=600/5 Pickup=0.8A No inst. TP@5=1.2898s H=8.33

    6

    6. INT A-742 51Q 351 SEL-VI TD=3.000CTR=600/5 Pickup=0.8A No inst. TP@5=0.7739s H=8.33

    A

    A. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.4 percent.INDIAN TRAIL 12/16/20 MVA XFMR

    B

    B. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AAC556 kCMil AAC

    Microprocessor relays have different

    types of curves based on the type of

    fault current being measured:

    51P phase time overcurrent

    51N or 51G ground time overcurrent

    51Q negative sequence time overcurrent

    Transformer relay curves

    Feeder relay curves

    51P phase time overcurrent

    51N or 51G ground time overcurrent

    51Q negative sequence time overcurrent

    This brings us to a brief discussion of:

  • 23

    Symmetrical Components

    Symmetrical Components for Power Systems Engineering,

    J. Lewis Blackburn,

    There are three sets of independent components in a three-phase

    system: positive, negative and zero for both current and voltage.

    Positive sequence voltages (Figure 1) are supplied by generators

    within the system and are always present. A second set of balanced

    phasors are also equal in magnitude and displaced 120 degrees

    apart, but display a counter-clockwise rotation sequence of A-C-B

    (Figure 2), which represents a negative sequence. The final set of

    balanced phasors is equal in magnitude and in phase with each

    other, however since there is no rotation sequence (Figure 3) this is

    known as a zero sequence.

  • 24

    Symmetrical Components

    Three phase (3LG) fault - Positive sequence currents for setting phase elements in relays. Phase -Phase (L-L) fault - Negative sequence currents for setting negative sequence elements in relays. Single phase (1LG or SLG) fault - Zero sequence currents for setting ground elements in relays.

    Symmetrical Components Notation:

    Positive Sequence current = I + = I1

    Negative Sequence current = I - = I2

    Zero Sequence current = I 0 = I0

    Phase Current notation:

    IA High side Amps

    Ia Low side Amps

    8.33= 115/13.8 = transformer Voltage (turns) ratio

    Phasor diagram from Fault-study Software.

    Examples of three 13.8kV faults showing the current distribution through a Delta-Wye high-lead-low transformer bank :

  • 25

    Symmetrical Components Positive Sequence, 3LG 13.8 kV Fault You have only positive sequence voltage and current since the system is balanced.

    A

    B

    C

    a

    b

    c

    RR

    IA = 619 -88 Ia = 5158 -118

    IB = 619 152 Ib = 5158 122

    IC = 619 32 Ic = 5158 2

    Phase current = Sequence current

    That is; Ia = I+.

    Phase currents and voltages for the 115kV side.

    IA = Ia / 8.33 = 5158A / 8.33

    IA = 619A

  • 26

    Symmetrical Components Negative Sequence, L-L 13.8 kV Fault

    115kV side sequence currents and voltages

    13.8kV side sequence currents and voltages

    A

    B

    C

    a

    b

    c

    RR

    IA = 309 -28 Ia = 0 0

    IB = 619 152 Ib = 4467 152

    IC = 309 -28 Ic = 4467 -28

    3LG 13.8kV fault = 5158A,

    Ib=Ic=4467 A, 4467/5158 = 86.6%=3/2

    IB3LG = IBLL = 619A

    IA & IC = IB or Ia & Ic = Ib

    I2 = the phase current/3 = 4467/3 = 2579

    Digital relays 50Q/51Q elements set using 3I2.

    3I2 = Ib x 3 = 4467 x 1.732 = 7737,

  • 27

    Symmetrical Components Zero Sequence, 1LG 13.8 kV Fault

    115kV side sequence currents and voltages

    A

    B

    C

    a

    b

    c

    RR

    3I0 is the sum of the 3 phase currents and since Ib & Ic

    = 0, then 3I0 = Ia. This means the phase and ground

    overcurrent relays on the feeder breaker see the same

    amount of current.

    5346/(8.33*3) = 370 amps. So the high side phase

    current is the 3 less as compared to the 3 fault.

    Digital relays ground elements set using 3I0.

    13.8kV side sequence currents and voltages

    IA = 370 -118 Ia=3I0=5346 -118

    IB = 0 0 Ib = 0 0

    IC = 370 62 Ic = 0 0

    Ia = 3Va/(Z1 + Z2 + Z0)

  • 28

    Symmetrical Components - Summary of 13.8 kV Faults

    3LG positive sequence current

    SLG zero sequence current

    L-L negative sequence current

    IA = 619 Ia = 5158

    IB = 619 Ib = 5158

    IC = 619 Ic = 5158

    5158 / 8.33 = 619 Ia = 5158 = I1

    5346/(8.33x3) = 370 Ia = 5346 = 3I0

    If you have a Delta-Wye transformer bank, and you know the voltage ratio and secondary phase

    current values for 13.8kV 3LG (5158) and SLG (5346) faults, you can find the rest:

    IA = 309 Ia = 0

    IB = 619 Ib = 4467

    IC = 309 Ic = 4467

    5158 x 3/2 = 4467 Ib x 3 = 7737 = 3I2

    4467/(8.33x 3) = 309

    309 x 2 = 619

    IA = 370 Ia=5346

    IB = 0 Ib = 0

    IC = 370 Ic = 0

  • 29

    Symmetrical Components - Summary of 13.8 kV Faults

    Youve heard of a Line-to-Line fault, how about an Antler-to-Antler fault?

  • 30

    Electromechanical Relays

    used on Distribution Feeders

    Avistas standard distribution relay

    package (until the mid-1990s) included

    the following:

    3 phase 50/51 CO-11 relays,

    1 reclosing relay

    1 ground 50/51 CO-11 relay

    .

  • 31

    Objectives:

    - Protect the feeder conductor

    - Detect as low a fault current as

    possible (PU = 50% EOL fault amps)

    - Other than 51P, set pickup and time

    dial as low as possible and still have

    minimum Coordinating Time Interval

    (CTI) to next device. CTI is minimum

    time between operation of adjacent

    devices.

    - Carry normal maximum load (phase

    overcurrent only).

    - Pickup the feeder in a cold load

    condition ( 2 times maximum normal

    load) or pickup of the next feeder

    load

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 KV By

    For No.

    Comment Date

    TRANSFORMER PROTECTION

    FEEDER VCB PROTECTION

    MAXIMUM FEEDER FUSE

    1

    1. SMD-2B 65E VERY SLOW 176-19-065Minimum melt. H=8.33

    2

    2. LAT421 50P CO-9 INST TD=1.000CTR=600/5 Pickup=4.6A No inst. TP@5=0.048s

    3

    3. LAT421 51P CO-9 CO-9 TD=1.900CTR=600/5 Pickup=4.A No inst. TP@5=0.4618s

    4

    4. LAT421 50N CO-9 INST TD=1.000CTR=600/5 Pickup=3.A No inst. TP@5=0.048s

    5

    5. LAT421 51N CO-9 CO-9 TD=3.000CTR=600/5 Pickup=3.A No inst. TP@5=0.7228s

    6

    6. LAT421 FUSE S&C Link100TTotal clear.

    A

    A. Transf. damage curve. 7.50 MVA. Category 3Base I=313.78 A. Z= 6.9 percent.Latah Jct 13.8kV - LATAHJCT115 115.kV T

    B

    B. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 1/0

    Electromechanical Relays

    used on Distribution Feeders

  • 32

    13 kV BUS

    MIN FAULT3LG = 2000 A1LG = 1000 A

    FEEDER SETTINGS51P = 2000 / 2 = 1000 A51N = 1000 / 2 = 500 A

    Electromechanical Relays

    used on Distribution Feeders

    Pickup setting criteria of 2/1 ratio of end of line fault duty / pickup

    - ensures that the relay will see the fault and operate when needed.

  • 33

    13 kV BUS

    FAULT at MIDLINE3LG = 2000 A1LG = 1000 A

    FEEDER SETTINGS51P = 2000 / 2 = 1000 A51N = 1000 / 2 = 500 A

    MIN FAULT at END OF LINE3LG = 1000 A1LG = 500 A

    MIDLINE SETTINGS51P = 1000 / 2 = 500 A51N = 500 / 2 = 250 A

    Electromechanical Relays

    used on Distribution Feeders

  • 34

    Electromechanical Relays

    used on Distribution Feeders

    13 kV BUS

    500A FEEDER SETTINGS51P = 960 A51N = 480 A

    SECTION LOAD = 500 A

  • 35

    Electromechanical Relays

    used on Distribution Feeders

    13 kV BUS

    500A FEEDER SETTINGS51P = 960 A51N = 480 A N.O.

    SECTION LOAD = 250 A

    SECTION LOAD = 500 A

    SECTION LOAD = 250 A

  • 36

    Most overhead feeders also use reclosing capability to automatically re-energize the feeder

    for temporary faults. Most distribution reclosing relays have the capability of providing up to three

    or four recloses.

    -- Avista uses either one fast or one fast and one time delayed reclose to lockout.

    The reclosing relay also provides a reset time generally adjustable from about 10 seconds to

    three minutes. This means if we run through the reclosing sequence and trip again within the reset

    time, the reclosing relay will lockout and the breaker will have to be closed by manual means. The

    time to reset from the lockout position is 3 to 6 seconds for EM reclosing relays.

    -- Avista uses reset times ranging from 90 to 180 seconds.

    Lockout only for faults within the protected zone. That is; wont lockout for faults beyond

    fuses, line reclosers etc.

    Most distribution reclosing relays also have the capability of blocking instantaneous tripping.

    -- Avista normally blocks the INST tripping after the first trip to provide for a Fuse Protecting

    Scheme.

    Electromechanical Relays

    used on Distribution Feeders

    Reclosing

  • 37

    13 kV BUS

    RECLOSING SEQUENCE

    Closed

    Open

    0.5" 12" LOCKOUT

    RESET = 120"

    (INST Blocked during Reset Time)

    Electromechanical Relays

    used on Distribution Feeders

    Reclosing Sequence shown for a permanent fault

  • 38

    Distribution Fusing Fuse Protection/Saving Scheme

    Fault on fused lateral on an overhead feeder:

    - Station or midline 51 element back up fuse.

    - Station or midline 50 element protects fuse.

    During fault:

    Trip and clear the fault at the station (or line

    recloser) by the instantaneous trip before the fuse

    is damaged for a lateral fault.

    Reclose the breaker. That way if the fault were

    temporary the feeder is completely re-energized

    and back to normal.

    During the reclose the reclosing relay has to

    block the instantaneous trip from tripping again.

    That way, if the fault still exists you force the

    time delay trip and the fuse will blow before you

    trip the feeder again thus isolating the fault and

    re-energizing most of the customers.

    Of course if the fault were on the main trunk

    the breaker will trip to lockout.

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVM15 515 51N to 140T By Protection

    For Aspen File: HORS M15 EXP.olr No.

    Comment Date 3/06

    STATION FEEDER RELAYING

    MAXIMUM FEEDER FUSE

    1

    1. M15 515 GND TIME CO-11 TD=4.000CTR=160 Pickup=3.A No inst. TP@5=1.0192s

    2

    2. Moscow 515 Kear 140T Kearney 140TTotal clear.

    3

    3. M15 50N CO-11 INST TD=1.000CTR=160 Pickup=3.A No inst. TP@5=0.048s

  • 39

    Shows the maximum fault current for which

    S&C type T fuses can still be protected by a

    recloser/breaker instantaneous trip for

    temporary faults (minimum melt curve at 0.1

    seconds):

    6T 120 amps

    8T 160 amps

    10T 225 amps

    12T 300 amps

    15T 390 amps

    20T 500 amps

    25T 640 amps

    30T 800 amps

    40T 1040 amps

    50T 1300 amps

    65T 1650 amps

    80T 2050 amps

    100T 2650 amps

    140T 3500 amps

    200T 5500 amps

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. BR1 S&C 140T S&C Link140TMinimum melt.

    2

    2. ENDTAP S&C 40T S&C Link 40TMinimum melt.

    3

    3. M15 515 S&C 80T S&C Link 80TMinimum melt.

    Distribution Fusing Fuse Protection for Temporary Faults

  • 40

    NOTE: These values were taken from the S&C data bulletin 350-170 of March 28, 1988 based on no

    preloading and then preloading of the source side fuse link. Preloading is defined as the source side

    fuse carrying load amps equal to its rating prior to the fault. This means there was prior heating of

    that fuse so it doesnt take as long to blow for a given fault.

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. T FUSE S&C Link100TMinimum melt.

    2

    2. 251 140T FUSE stn S&C Link140TTotal clear.

    Distribution Fusing Fuse to Fuse Coordination

  • 41

    Typical continuous and 8 hour emergency rating of the S&C T rated silver fuse links plus the 140T

    and 200T.

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    T IME-CURRENT CURVES @ Voltage By

    For No.

    Comment Date

    1

    1. BR1 S&C 140T S&C Link140TMinimum melt.

    Distribution Fusing S&C T-Fuse Current Ratings

    General Rule: Fuse Blows at 2X Rating in 5 Minutes

  • 42

    Typical Coordinating Time Intervals (CTI)

    that Avista generally uses between protective

    devices.

    Other utilities may use different times.

    DEVICES: CTI

    (Sec.)

    Relay Fuse Total Clear 0.2

    Relay Series Trip Recloser 0.4

    Relay Relayed Line Recloser 0.3

    Lo Side Xfmr Relay Feeder Relay 0.4

    Hi Side Xfmr Relay Feeder Relay 0.4

    Xfmr Fuse Min Melt Feeder Relay 0.4

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

    For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 252 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    MIDLINE OCR

    MAXIMUM MIDLINE FUSE

    Fault I=5665.9 A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

    2

    2. IDR 252 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

    3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

    4

    4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

    5

    5f

    5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s

    6

    6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

    A

    A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

    FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

  • 43

    Typical Coordinating Time Intervals (CTI)

    that Avista generally uses between protective

    devices.

    Other utilities may use different times.

    DEVICES: CTI

    (Sec.)

    Relay Fuse Total Clear 0.2

    Relay Series Trip Recloser 0.4

    Relay Relayed Line Recloser 0.3

    Lo Side Xfmr Relay Feeder Relay 0.4

    Hi Side Xfmr Relay Feeder Relay 0.4

    Xfmr Fuse Min Melt Feeder Relay 0.4

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

    For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 252 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    MIDLINE OCR

    MAXIMUM MIDLINE FUSE

    Fault I=5665.9 A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

    2

    2. IDR 252 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

    3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

    4

    4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

    5

    5f

    5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s

    6

    6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

    A

    A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

    FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

  • 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVRAT 231 MID C390R By JDH

    For Huetter feeder 142 (2008) Rat feeder 231 (2009+) Midline Recloser C390R No.

    Comment Saved in: HUE142-RAT231 MID C390R 2007base.olr Date 2-25-08

    HUETTER FDR 142 PROTECTION

    RATHDRUM FDR 231 PROTECTION

    HUE 142 MID C270R PROTECTION

    MIDLINE 390R PROTECTION

    CALLED "HUE 142 LINE" IN POWERBASE

    RECLOSE IS 1SEC, 12SEC, LO, 120 SEC RESET

    RECLOSE IS 1SEC, 12 SEC, LO, 180 SEC RESET

    LARGEST DOWNSTREAM FUSE FROM 390R MIDLINE

    1

    1. C390R MID 51P CO-9 CO-9 TD=2.500

    CTR=300/5 Pickup=5.A No inst. TP@5=0.6037s

    2

    2. C390R MID 50P CO-9 INST TD=1.000

    CTR=300/5 Pickup=6.A No inst. TP@5=0.048s

    3 3. C390R MID 50N CO-9 INST TD=1.000

    CTR=300/5 Pickup=5.A No inst. TP@5=0.048s

    4

    4. C390R MID 51N CO-9 CO-9 TD=2.500

    CTR=300/5 Pickup=5.A No inst. TP@5=0.6037s

    5

    5. HUE 142 50P 251 INST TD=1.000

    CTR=160 Pickup=7.A No inst. TP@5=0.048s

    6

    6. HUE 142 51P 251 SEL-EI TD=1.500

    CTR=160 Pickup=6.A No inst. TP@5=0.4072s

    7

    7. HUE ML C270R 50P INST TD=1.000

    CTR=400/5 Pickup=8.1A No inst. TP@5=0.048s

    8

    8. HUE ML C270R 51P CO-11 TD=1.500

    CTR=400/5 Pickup=7.A No inst. TP@5=0.3766s

    9

    9. HUE 142 50N 251 INST TD=1.000

    CTR=160 Pickup=3.A No inst. TP@5=0.048s

    10

    10. HUE 142 51N 251 SEL-EI TD=4.000

    CTR=160 Pickup=3.A No inst. TP@5=1.0858s

    11

    11. HUE 142 51Q 251 SEL-EI TD=4.000

    CTR=160 Pickup=5.2A No inst. TP@5=1.0858s

    12

    12. HUE ML C270R 50N INST TD=1.000

    CTR=400/5 Pickup=3.A No inst. TP@5=0.048s

    13

    13. HUE ML C270R 51N CO-11 TD=7.000

    CTR=400/5 Pickup=3.A No inst. TP@5=1.8052s

    14

    14. RAT 231 50N CO-11 INST TD=1.000

    CTR=800/5 Pickup=3.A No inst. TP@5=0.048s15

    15. RAT 231 51N CO-11 CO-11 TD=5.000

    CTR=800/5 Pickup=3.A No inst. TP@5=1.3192s

    16

    16. RAT 231 50P CO-11 INST TD=1.000

    CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

    17

    17. HUE 142 FUSE S&C Link 65T

    Total clear.

    18

    18. RAT 231 FUSE S&C Link100T

    Total clear.

    19

    19. RAT 231 51P CO-11 CO-11 TD=1.800

    CTR=800/5 Pickup=6.A No inst. TP@5=0.4533s

    A

    A. Conductor damage curve. k=0.08620 A=133100.0 cmils

    Conductor ACSR AWG Size 2/0

    MIDLINE C390 FED FROM RAT 231 - MINIMUM CONDUCTOR TO PROTECT

    B

    B. Conductor damage curve. k=0.06710 A=556000.0 cmils

    Conductor AAC

    MIDLINE C390 FED FROM HUE 142 - MINIMUM CONDUCTOR TO PROTECT

    44

    Typical Coordinating Time Intervals (CTI)

    that Avista generally uses between protective

    devices.

    Other utilities may use different times.

    DEVICES: CTI

    (Sec.)

    Relay Fuse Total Clear 0.2

    Relay Series Trip Recloser 0.4

    Relay Relayed Line Recloser 0.3

    Lo Side Xfmr Relay Feeder Relay 0.4

    Hi Side Xfmr Relay Feeder Relay 0.4

    Xfmr Fuse Min Melt Feeder Relay 0.4

    Coordinating Time Intervals

  • 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVIDR FEEDER 251 By JDH

    For Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr No.

    Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

    TRANSFORMER PROTECTION

    STATION VCB 251 PROTECTION

    MAXIMUM FEEDER FUSE

    HI-SIDE CT'S

    LO-SIDE CT'S

    MINIMUM FAULT TO DETECT:3LG=2460A, SLG=1833A, L-L=2130A

    1

    1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33

    2

    2. IDR A-777 51G 351 SEL-VI TD=1.000CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33

    3

    3. IDR A-777 51N 351 SEL-EI TD=5.700CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s

    4

    4. IDR A-777 51Q 351 SEL-EI TD=4.200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33

    5

    5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

    6

    6. IDR 251 50P 351S INST TD=1.000CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

    7

    7. IDR 251 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

    8

    8. IDR 251 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

    9

    9. IDR 251 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

    10

    10. IDR 251 51Q 351S SEL-EI TD=3.500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

    11

    11. 251 140T FUSE stn S&C Link140TTotal clear.

    A

    A. Conductor damage curve. k=0.08620 A=133100.0 cmilsConductor ACSR AWG Size 2/0FEEDER 251 SMALLEST CONDUCTOR TO PROTECT

    B

    B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

    45

    Typical Coordinating Time Intervals (CTI)

    that Avista generally uses between protective

    devices.

    Other utilities may use different times.

    DEVICES: CTI

    (Sec.)

    Relay Fuse Total Clear 0.2

    Relay Series Trip Recloser 0.4

    Relay Relayed Line Recloser 0.3

    Lo Side Xfmr Relay Feeder Relay 0.4

    Hi Side Xfmr Relay Feeder Relay 0.4

    Xfmr Fuse Min Melt Feeder Relay 0.4

    Coordinating Time Intervals

  • 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 KV By

    For No.

    Comment Date

    TRANSFORMER PROTECTION

    FEEDER VCB PROTECTION

    MAXIMUM FEEDER FUSE

    1

    1. SMD-2B 65E VERY SLOW 176-19-065Minimum melt. H=8.33

    2

    2. LAT421 50P CO-9 INST TD=1.000CTR=600/5 Pickup=4.6A No inst. TP@5=0.048s

    3

    3. LAT421 51P CO-9 CO-9 TD=1.900CTR=600/5 Pickup=4.A No inst. TP@5=0.4618s

    4

    4. LAT421 50N CO-9 INST TD=1.000CTR=600/5 Pickup=3.A No inst. TP@5=0.048s

    5

    5. LAT421 51N CO-9 CO-9 TD=3.000CTR=600/5 Pickup=3.A No inst. TP@5=0.7228s

    6

    6. LAT421 FUSE S&C Link100TTotal clear.

    A

    A. Transf. damage curve. 7.50 MVA. Category 3Base I=313.78 A. Z= 6.9 percent.Latah Jct 13.8kV - LATAHJCT115 115.kV T

    B

    B. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 1/0

    46

    Typical Coordinating Time Intervals (CTI)

    that Avista generally uses between protective

    devices.

    Other utilities may use different times.

    DEVICES: CTI

    (Sec.)

    Relay Fuse Total Clear 0.2

    Relay Series Trip Recloser 0.4

    Relay Relayed Line Recloser 0.3

    Lo Side Xfmr Relay Feeder Relay 0.4

    Hi Side Xfmr Relay Feeder Relay 0.4

    Xfmr Fuse Min Melt Feeder Relay 0.4

    Coordinating Time Intervals

  • 47

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

    For M15 A-172 CS with fdr 515 with Kearney 140T Fuse No.

    Comment Three Phase Fault Date 12/12/05

    1

    1. Moscow 515 Kear 140T Kearney 140TMinimum melt.I= 5158.1A T= 0.10s

    2

    2. M15-515 Phase Time CO-11 TD=1.500CTR=160 Pickup=6.A No inst. TP@5=0.3766sI= 5158.1A (32.2 sec A) T= 0.33s

    3

    3. M15 A-172 Phase CO- 9 TD=1.500CTR=120 Pickup=2.A Inst=1200A TP@5=0.3605sI= 619.0A (5.2 sec A) T= 1.03s H=8.33

    FAULT DESCRIPTION:Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L 3LG

    3LG Fault Coordination

    Example:

    Top Ckt Swr w/ Phase E-M relay

    ----- 0.4 sec. ------

    Middle - E-M Phase relay for a 500

    Amp Feeder

    ----- 0.2 sec. ------

    Bottom 140T Feeder Fuse (Total

    Clear)

  • 48

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

    For Moscow CS with fdr 515 with 140T fuses No.

    Comment Single Line to Ground Fault Date 12/12/05

    1

    1. Moscow 515 Kear 140T Kearney 140TMinimum melt.I= 5346.4A T= 0.09s

    2

    2. M15 515 GND TIME CO-11 TD=4.000CTR=160 Pickup=3.A No inst. TP@5=1.0192sI= 5346.5A (33.4 sec A) T= 0.29s

    3

    3. M15-515 Phase Time CO-11 TD=1.500CTR=160 Pickup=6.A No inst. TP@5=0.3766sI= 5346.4A (33.4 sec A) T= 0.31s

    4 4. M15 A-172 GND TIME CO-11 TD=4.000CTR=240 Pickup=4.A No inst. TP@5=1.0192sI= 5346.5A (22.3 sec A) T= 0.83s

    FAULT DESCRIPTION:Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L 1LG Type=A

    SLG Fault Coordination

    Example:

    Top Ckt Swr w/ E-M Phase relay

    ----- 0.4 sec. ------

    Middle - E-M relays (Phase &

    Ground) for a 500 Amp Feeder

    ----- 0.2 sec. ------

    Bottom 140T Feeder Fuse (Total

    Clear)

  • 49

    Coordinating Time Intervals

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    2

    3

    45

    7

    10

    20

    30

    4050

    70

    100

    200

    300

    400500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

    For Moscow CS A-172 with fdr 515 with 140T Fuse No.

    Comment Line to Line Fault Date

    1

    1. Moscow 515 Kear 140T Kearney 140TMinimum melt.I= 4467.0A T= 0.12s

    2

    2. M15-515 Phase Time CO-11 TD=1.500CTR=160 Pickup=6.A No inst. TP@5=0.3766sI= 4467.0A (27.9 sec A) T= 0.43s

    3

    3. M15 A-172 Phase CO- 9 TD=1.500CTR=120 Pickup=2.A Inst=1200A TP@5=0.3605sI= 619.0A (5.2 sec A) T= 1.03s H=8.33

    FAULT DESCRIPTION:Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L LL Type=B-C

    L-L Fault Coordination

    Example:

    Top Ckt Swr w/ E-M relay

    ----- 0.4 sec. ------

    Middle - E-M (Phase) relay for a 500

    Amp Feeder

    ----- 0.2 sec. ------

    Bottom 140T Feeder Fuse (Total

    Clear)

  • 50

    The Final Product 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

    10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

    SECONDS

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    2

    3

    4

    5

    7

    10

    20

    30

    40

    50

    70

    100

    200

    300

    400

    500

    700

    1000

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    .01

    .02

    .03

    .04

    .05

    .07

    .1

    .2

    .3

    .4

    .5

    .7

    1

    TIME-CURRENT CURVES @ Voltage 13.8 kVINT 12F2 & MID 466R By JDH

    For Indian Trail feeder 12F2 and 12F2 Midline 466R in INT 2007base.olr No.

    Comment AT SUB: 3LG= 5719A, LL=4951A, SLG= 5880A Date 1-29-08

    TRANSFORMER PROTECTION

    STATION VCB 12F2 PROTECTION

    EAST BRANCH - FEEDER MAXIMUM FUSE

    FAULT DUTY AT 140T - WHEN FED FROM NORTH (N.O. PT)

    12F2 MIDLINE 466R PROTECTION

    WEST OR NORTH BRANCH - FEEDER MAXIMUM FUSE

    FAULT DUTY AT 150E; 3LG=2318, LL=2008, SLG=1684

    3LG=1932, LL=1673, SLG=1388

    FAULT DUTY AT 140T - WHEN FED FROM WEST MID 466R 3LG=2093, LL=1813, SLG=1520

    9&15

    11&4

    1

    1. INT A-742 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33

    2

    2. INT A-742 51G 351 SEL-VI TD=1.000CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33

    3

    3. INT A-742 51N 351 SEL-EI TD=5.600CTR=1200/5 Pickup=3.A No inst. TP@5=1.5201s

    4

    4. INT A-742 51Q 351 SEL-EI TD=4.200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33

    5

    5. INT F2 150E FUSE SMU-20_150ETotal clear.

    6

    6. INT 12F2 50P 351S INST TD=1.000CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

    7

    7. INT 12F2 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

    8

    8. INT 12F2 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

    9

    9. INT 12F2 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

    10

    10. INT 12F2 51Q 351S SEL-EI TD=3.500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

    11

    11. INT A-742 51Q 587 W2 SEL-EI TD=4.300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

    12

    12. F2 MID 466R 50P 351R INST TD=1.000CTR=500/1 Pickup=1.68A No inst. TP@5=0.048s

    13

    13. F2 MID 466R 51P 351R SEL-EI TD=2.300CTR=500/1 Pickup=1.44A No inst. TP@5=0.6243s

    14

    14. F2 MID 466R 50G 351R INST TD=1.000CTR=500/1 Pickup=0.89A No inst. TP@5=0.048s

    15

    15. F2 MID 466R 51G 351R SEL-EI TD=4.200CTR=500/1 Pickup=0.89A No inst. TP@5=1.1401s

    16

    16. F2 MID 466R 51Q 351R SEL-EI TD=3.800CTR=500/1 Pickup=1.54A No inst. TP@5=1.0315s

    17

    17. INT F2 140T FUSE stn S&C Link140TTotal clear.

    A

    A. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.4 percent.INDIAN TRAIL 12/16/20 MVA XFMR

    B

    B. Conductor damage curve. k=0.14040 A=52630.0 cmilsConductor Copper (bare) AWG Size 2NORTH BRANCH SMALLEST TRUNK CONDUCTOR

    C

    C. Conductor damage curve. k=0.04704 A=350000.0 cmilsCable XLPE 90C/250CEAST BRANCH SMALLEST TRUNK CONDUCTOR - 350 CN15

    D

    D. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 2/0WEST BRANCH SMALLEST TRUNK CONDUCTOR

    An example of a completed 13.8kV

    Feeder Coordination Study with 20

    Time-Current Curves representing:

    Instantaneous & Time-Delay Curves

    for the:

    - Transformer high side protection,

    - Transformer low side protection,

    - Station feeder breaker protection,

    - Midline feeder breaker protection.

    Two Fuses

    Transformer Damage Curve

    Three Conductor Damage Curves

  • 51

    2 Time delay relay.

    27 Undervoltage relay.

    43 Manual transfer or selective device.

    We use these for cutting in and out

    instantaneous overcurrent relays,

    reclosing relays etc.

    50 (or 50P) Instantaneous overcurrent

    phase relay.

    50N (or 50G) Instantaneous overcurrent

    ground (or neutral) relay.

    50Q Instantaneous Negative Sequence

    overcurrent relay.

    51 (or 51P) Time delay overcurrent phase

    relay.

    51N (or 51G) Time delay overcurrent

    ground (or neutral) relay.

    51Q Time delay Negative Sequence

    overcurrent relay.

    52 AC circuit breaker.

    IEEE Device Designations commonly used in Distribution Protection

    Avista sometimes adds letters to these such as F for feeders, T for transformers, B for bus and BF for

    breaker failure.

    52/a Circuit breaker auxiliary switch closed

    when the breaker is closed.

    52/b Circuit breaker auxiliary switch closed

    when the breaker is open.

    59 Overvoltage relay.

    62 Time Delay relay

    63 Sudden pressure relay.

    79 AC Reclosing relay.

    81 Frequency relay.

    86 Lock out relay which has several contacts.

    Avista uses 86T for a transformer lockout,

    86B for a bus lockout etc.

    87 Differential relay.

    94 Auxiliary tripping relay.

  • Danas Turn

    52

  • 53

    Criteria (for outdoor bus arrangement, not switchgear)

    Protect the Transformer from thermal damage - Refer to Damage Curves

    Backup feeder protection (as much as possible) - Sensitivity is limited because load is higher

    Coordinate with downstream devices (feeder relays)

    Carry normal maximum load (phase only)

    Pick up Cold Load after outages

    Distribution Transformer Electromechanical Relays

  • 54

    Relays:

    3 High Side Phase Overcurrent (with time and instantaneous elements) 1 Low Side Ground Overcurrent (with time and instantaneous elements) Sudden Pressure Relay

    Distribution Transformer

    Electromechanical Relays - Setting Criteria

  • 55

    Phase Overcurrent Settings Current measured on 115kV side

    51P Pickup (time overcurrent)

    Dont trip for load or cold load pickup (use 2.4 * highest MVA rating)

    Ends up being higher than the feeder phase element pickup

    Example: 12/16/20 MVA unit would use 2.4*20*5 = 240 amps (1940A low side)

    51P Time Lever (time dial)

    Coordinate with feeder relays for maximum fault (close in feeder fault)

    CTI is 0.4 seconds

    Worst coordination case: - on low side (discrepancy due to delta/wye conn.)

    Multiple feeder load can make the transformer relay operate faster

    50P Pickup (instantaneous overcurrent)

    Must not trip for feeder faults set at 170% of low side bus fault

    Accounts for DC offset

    Distribution Transformer

    Electromechanical Relays - Setting Criteria

  • 56

    Ground Overcurrent Settings Current measured on 13.8 kV side

    51N Pickup (time overcurrent)

    Set to same sensitivity as feeder phase relay (in case the feeder ground relay is failed)

    This setting is higher than the feeder ground, so we lose some sensitivity for backup

    51N Time Lever (time dial)

    Coordinate with feeder relays for ground faults

    CTI is 0.4 seconds

    50N Pickup (instantaneous overcurrent)

    DO NOT USE!!!!

    Distribution Transformer

    Electromechanical Relays - Setting Criteria

  • 57

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

    Advantages:

    More precise TAP settings

    More Relay Elements

    Programmable Logic / Buttons

    Lower burden to CT

    Event Reports!!!!!!!!!

    Communications

    Coordinate with like elements (faster)

    More Settings

    Microprocessor Relay

  • 58

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

    Elements We Set:

    51P 50P 50P2 (FTB) 51G 50G (115kV) 51N (13.8kV) 50N1 (FTB)

    FTB = Fast Trip Block (feeder relays must be Microprocessor)

  • 59

    Transformer Phase Overcurrent Settings - Current measured on 115kV Side

    51P - Phase Time Overcurrent Pickup

    Set to 240% of nameplate (same as EM relay)

    51P Time Dial

    Set to coordinate with feeders fastest element for each fault

    CTI is still 0.4 seconds

    50P1 Phase instantaneous #1 Pickup

    Direct Trip

    Set to 130% of max 13.8 kV fault (vs. 170% with EM relay)

    50P2 Phase instantaneous pickup for Fast Trip Block scheme

    Set above transformer inrush

    4 Cycle time delay

    Blocked if any feeder overcurrent elements are picked up

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 60

    Transformer Ground Overcurrent Settings - Current calculated from 115kV CTs

    51G - Ground Time Overcurrent Pickup

    Set very low (will not see low side ground faults due to transformer connection). Usually 120 Amps.

    51GTime Dial

    Set very low

    50G1 Ground Instantaneous #1 Pickup

    Set very low. Usually 120 Amps.

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

    Symmetrical

    Components!

  • 61

    Transformer Neutral Overcurrent Settings - Current measured by neutral CT or

    calculated from 13.8kV CTs.

    51N - Ground Time Overcurrent Pickup

    Set slightly higher than feeder ground pickup (about 1.3 times)

    51NTime Dial

    Set to coordinate with feeder ground

    CTI is 0.4 seconds

    50N1 Ground Instantaneous for Fast Trip Block

    Set slightly above the feeder ground instantaneous pickup

    Time Delay by 4 cycles

    Blocked if Feeder overcurrent elements are picked up

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 62

    Inrush The current seen when energizing a transformer.

    Need to account for inrush when using instantaneous elements (regular or FTB).

    Inrush can be approximately 8 times the nameplate of a transformer.

    Note that the microprocessor relay only responds to the 60 HZ fundamental and that this

    fundamental portion of inrush current is 60% of the total. So to calculate a setting, we could use

    the 8 times rule of thumb along with the 60% value. For a 12/16/20 MVA transformer, the

    expected inrush would be 8*12*5*0.6 = 288 amps. We set a little above this number (360 Amps).

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 63

    Transformer inrush UNFILTERED

    current. The peak current is about 1800

    amps.

    Transformer inrush FILTERED current

    (filtered by digital filters to show

    basically only 60 HZ). Peak is about

    700 amps.

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 64

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

    Microprocessor Feeder Relay

    Overcurrent Reclosing Fast Trip Block Output Breaker Failure Output

    Elements We Set:

    51P 50P 51G 50G 51Q

  • 65

    Feeder Phase Overcurrent Settings

    51P - Phase Time Overcurrent Pickup

    Set above load and cold load (960 Amps for 500 Amp feeder)

    Same as EM pickup

    51P Time Dial

    Same as EM relay (coordinate with downstream protection with CTI)

    Select a curve

    50P Phase instantaneous Pickup

    Set the same as the 51P pickup (960 Amps)

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 66

    Feeder Ground Overcurrent Settings

    51G - Phase Time Overcurrent Pickup

    Same as EM pickup which is 480 Amps

    51G Time Dial

    Same as EM relay (coordinate with downstream protection)

    Select a curve

    50G Phase instantaneous Pickup

    Set the same as the 51G pickup

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 67

    Feeder Negative Sequence Overcurrent Settings

    51Q - Negative Sequence Time Overcurrent Pickup

    Set with equivalent sensitivity as the ground element (not affected by load)

    Coordinate with downstream protection

    51Q Time Dial

    Same as EM relay (coordinate with downstream protection)

    Select a curve

    50Q Negative Sequence instantaneous Pickup

    DONT USE!!!!!

    Contributions from motors during external faults could trip this

    Distribution Transformer & Feeder Protection

    with Microprocessor Relays

  • 68

    87R1

    87OP

    87R2

    PRI I

    PRI I

    SEC I

    SEC I

    EXTERNAL FAULTTHE SECONDARY CURRENTS FLOW THROUGH BOTHRESTRAINT COILS IN THE SAME DIRECTION AND THENCIRCULATE BACK THROUGH THE CT'S. THEY DO NOTFLOW THROUGH THE OPERATE COIL

    CURRENT FLOW THROUGH AN E/M 87 DIFFERENTIAL RELAY FOR AN INTERNAL AND EXTERNAL FAULT

    BCT'S

    BCT'S

    CT POLARITY MARK

    Transformer Differential Protection External Fault

  • 69

    87R1

    87OP

    87R2

    PRI I

    PRI I

    INTERNAL FAULTTHE SECONDARY CURRENTS FLOW THROUGH BOTHRESTRAINT COILS IN OPPOSITE DIRECTIONS, ADD AND THEN FLOW THROUGH THE OPERATE COIL ANDBACK TO THE RESPECTIVE CT'S

    SEC I

    SEC I

    BCT'S

    BCT'S

    CT POLARITY MARK

    Transformer Differential Protection Internal Fault

  • 70

    The differential relay is connected to both the high and low side transformer BCTs.

    EM Differential Relay

    Since the distribution transformer is connected delta wye the transformer CTs

    have to be set wye delta to compensate for the phase shift.

    Transformer Differential Protection

  • 71

    GRAB YOUR HANDOUT!

    MOSCOW FEEDER 515 PROTECTION EXAMPLE

  • 72

    The Scenario

    A hydraulic midline recloser on a 13.8kV feeder in Moscow, ID is being replaced by a newer relayed recloser. The recloser is P584

    on feeder 515.

    The field engineer would like to replace the recloser in the existing location.

    Protection engineer must review the feeder protection and report back to the field engineer.

    NOTE: Avista designs for a fuse saving scheme with one instantaneous trip. The field engineers decide if they want to

    enable or disable the instantaneous tripping.

  • 73

    MOSCOW FEEDER 515 PROTECTION EXAMPLE

    Where do we start the protection design?

    1) Gather Information:

    Feeder Rating (expected load)

    Protective devices (Breakers, line reclosers, fuses)

    Fault Duty (at each protective device)

    Conductors to be protected

    Project deadline (tomorrow?)

  • 74

    How do we proceed?

    At each coordination point Loading

    Coordination What will coordinate with the downstream device

    Are we above the fuse rating

    Conductor Protection minimum conductor that can be protected by the feeder settings or

    fuse

    Fault Detection Can we detect the fault by our 2:1 margin

    Fuse Saving for Temporary faults What can a fuse be protected up to?

  • 75

    Begin at the END

    POINT 8: This is a customers load and we are using 3-250 KVA transformers to serve the load. The full load of this size of bank is 31.4

    amps. The Avista transformer fusing standard says to use a 65T on this

    transformer so thats what well choose.

  • 76

    FUSE - POINT 6B:

    What we know: 3 lateral feeding to a 65T at the end

    #4 ACSR conductor

    Fuse Selection: Loading Assume the load is all downstream of point 8, so a 65T or higher will

    still suffice.

    Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a

    100T or smaller fuse

    Fault Detection - Under the Relay Setting Criteria we want to detect the minimum

    line end fault with a 2:1 margin. The SLG is 463 so we calculate the max fuse as

    follows:

    463/2 (2:1 margin) = 231 amps. T fuses blow at twice their rating so divide

    by 2 again, with a result of 115. Fuse must be 100T or less.

    Coordination From Table 2, we see that we need an 80T or larger to coordinate

    with the downstream 65T fuse (at fault duties < 1400A w/preload)

    Fuse Saving - From Table 1 we see that an 80T fuse can be protected up to 2,050

    amps for temporary faults and the 3 fault is 1,907 amps so we could choose an

    80T or higher from that standpoint

  • 77

    Point 6B - So what fuse size should we use?

  • 78

    POINT 5 Midline Recloser

    What we know:

    Conductor to protect: #4 ACSR (can carry 140A load)

    Max fuse to coordinate with = 100T (FUTURE per distribution engineer)

    Maximum load (per engineer) = 84A

    Settings Considerations:

    Loading: Cold load would be 84*2 = 168 A, but the conductor can carry 140A max. Size for some

    load growth by setting at 2*conductor rating. 300 Amp phase pickup setting. NOTE: we dont design

    settings to protect for overload.

    Conductor Protection: From the table, Avistas 300A feeder settings can protect down to #2 ACSR, so 300A pickup is still acceptable. Review curves to confirm.

    Fault Detection: detect the minimum fault with a 2:1 margin. Here the min fault is at point 6

    1. The - fault at point 6 is 0.866*1907 = 1,651 so our margin to detect that fault would be 1651/300

    = 5.5:1 so no problem with the 300 amps PU from that standpoint (used - because its the

    minimum multi phase fault)

    2. The SLG at point 6 is 1,492 so we could set the ground up to 1492/2 = 745 amps and still detect the

    fault. However, our criteria says to set as low as possible and still coordinate with the largest

    downstream device and from above were trying to use a 100T. Based on curves, this is 300 amps

    (same as phase, which is unusual).

    Coordination: Based on fault study, set the time dial to coordinate with a 100T fuse with 0.2 second

    CTI.

    Fuse Saving: The fault duty at the recloser is 3453 3PH and 2762 1LG. An instantaneous trip will

    protect the 80T fuse if the fault duty is less than 2050 Amps. Some fuse protection is compromised but

    there is nothing we can do about it.

  • 79

    TRUNK FUSE - POINT 3C:

    What we know: #4 ACSR 3 trunk

    Load is 84 Amps

    Downstream protection is the midline recloser

    Fuse Selection: Loading Assume the load is the same as at the midline recloser. We set that at

    300A, and a 200T can carry 295 A continuous.

    Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a

    100T or smaller fuse.

    Fault Detection - Under the Relay Setting Criteria we want to detect the minimum

    line end fault with a 2:1 margin.

    SLG at midline is 2762 so even a 200T would provide enough sensitivity.

    Coordination PROBLEM! We have coordinated the midline with

    a 100T, so the upstream fuse must coordinate with that.

    Fuse Saving: As before, some fuse saving is compromised due to higher fault duty.

  • 80

    TRUNK FUSE Point 3C - Solutions?

  • 81

    TRUNK FUSE Point 3C - Solutions?

    Move Recloser

    Re-conductor

  • 82

    FEEDER BREAKER - POINT 1:

    What we know: This is a 500 amp feeder design. The load is 325 amps and cold load 650 per field engineer.

    Downstream protection is either the midline recloser or a 140T fuse.

    Settings Conside