division 15 - mechanical - miami-dade county public …facilities.dadeschools.net/planning/design...

67
Jan 04 Division 15 15 - 1 Issued Design Criteria M-DCPS DIVISION 15 - MECHANICAL I. GENERAL A. This division contains the following elements: 1. General Mechanical Requirements. 2. Mechanical Submittal Phasing Requirements. 3. General Plumbing Requirements. a. Plumbing Systems. b. Plumbing Drawings. c. Specific Room Plumbing Requirements. 1) Toilet Rooms and Group Showers. 2) Kitchens. a) General Requirements. b) Grease Interceptors. c) Floor Drainage. d) Dumpster Pads. e) Compactor. 3) Science, Art, and Photography Labs. 4) Equipment Rooms. d. Domestic Water. e. Drainage, Waste, and Vent Systems. f. Plumbing Fixtures. g. Fire Protection. h. Fuels and Energy Sources. i. Compressed Air. 4. Heating, Ventilating, and Air-conditioning. a. General. b. Life Cycle Cost Analysis (LCCA). c. HVAC System Selection. 1) General Requirements. 2) Specific Requirements. d. Heating Sources. e. Cooling Sources.

Upload: dangdat

Post on 07-Mar-2018

219 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 1 Issued Design Criteria M-DCPS

DIVISION 15 - MECHANICAL I. GENERAL

A. This division contains the following elements:

1. General Mechanical Requirements. 2. Mechanical Submittal Phasing Requirements. 3. General Plumbing Requirements.

a. Plumbing Systems. b. Plumbing Drawings. c. Specific Room Plumbing Requirements.

1) Toilet Rooms and Group Showers. 2) Kitchens.

a) General Requirements. b) Grease Interceptors. c) Floor Drainage. d) Dumpster Pads. e) Compactor.

3) Science, Art, and Photography Labs. 4) Equipment Rooms.

d. Domestic Water. e. Drainage, Waste, and Vent Systems. f. Plumbing Fixtures. g. Fire Protection. h. Fuels and Energy Sources. i. Compressed Air.

4. Heating, Ventilating, and Air-conditioning.

a. General. b. Life Cycle Cost Analysis (LCCA). c. HVAC System Selection.

1) General Requirements. 2) Specific Requirements.

d. Heating Sources. e. Cooling Sources.

Page 2: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 2 Issued Design Criteria M-DCPS

f. Design Considerations. g. Indoor Air Quality and Outside Air Requirements. h. Acoustical Considerations. i. Pumping and Piping Systems. j. Pipe Insulation. k. Equipment Selection.

1) Outdoor Air Louvers. 2) Air Filters. 3) Air-handling Units and Outside Air Supply Fans 4) Coils. 5) Air Duct Design. 6) Air Distribution Devices. 7) Return and Exhaust Air. 8) Cooling System. 9) Heating System. 10) Controls.

l. Existing School Retrofit.

B. Consider environmental hazards, safety, recycling, limited use, and handling of hazardous

materials in the selection of materials, equipment, and installations. C. Any equipment, device, system component, or part provided or installed by contractor

containing or using date processing shall be Year 2000 (Y2K) compliant. Specify the contractor to provide, before substantial completion, a manufacturer’s statement of Year 2000 compliance with a manufacturer’s and contractor’s warranty against date-related failures.

D. Provide utilities, chilled water piping, and HVAC central plant with added capacity suitable for a 10 percent building expansion. Capacity shall be in addition to standby or other requirements.

E. Chilled water piping serving HVAC equipment systems equipment and other piping and ducting shall not be located over wood floored stages, gymnasiums, or other similar spaces vulnerable to damage from condensation or leaks unless accepted by M-DCPS on a per condition basis using special insulation or auxiliary condensation drainage pan systems.

F. Provide accessibility for maintenance and replacement of equipment without removing adjacent equipment or piping causing disruption to facility functions.

1. Provide manufacturers' optional platforms and guardrails to service and maintain

equipment, including, but not limited to, cooling towers. Platform and guardrail omission may be accepted by M-DCPS on a per condition basis.

G. Installers, service personnel, and contractors for the following new or existing equipment

with refrigerant use shall comply with Environmental Protection Agency (EPA)

Page 3: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 3 Issued Design Criteria M-DCPS

regulations regarding technician certification and recycling or recovery equipment:

1. HVAC components including compressors, chillers, packaged units, heat pumps, room air-conditioners, heat pumps, dehumidifiers, thermal storage systems, and any other HVAC equipment with refrigerant use.

2. Refrigeration components including refrigerators, coolers, freezers, ice makers, vending machines, electric water coolers, and any other refrigeration equipment with refrigerant use.

H. Specify the contractor to provide at least 2 working day (48 hours) notice to the M-DCPS

project manager and M-DCPS Maintenance Operations, before starting any work involving existing refrigeration equipment or related components containing restricted refrigerants, to allow for M-DCPS attendance. The contractor shall comply with applicable code requirements for removing and disposing restricted refrigerants.

I. HVAC systems shall be operational and maintain 75 + 2 degrees F. and a constant 55 + 2 percent relative humidity for a period of at least 3 days (72 hours) before installation of specified interior finishes. These conditions shall be maintained at all times until interior finish installations are completed and accepted by M-DCPS. As specified, the contractor shall record conditions at least every 4 hours and provide supplemental temporary air-conditioning or dehumidification if HVAC is not operating at specified conditions. Exterior openings shall be kept closed during these periods by using temporary or permanent barriers.

II. GENERAL MECHANICAL REQUIREMENTS

A. Construction documents shall conform to requirements of Florida Department of Education, Office of Educational Facilities - State Requirements for Educational Facilities -1999 (SREF) and the following:

1. Florida Building Code (FBC). 2. Florida Building Code (FBC) - Plumbing. 3. Florida Building Code (FBC) - Mechanical. 4. Florida Building Code (FBC) - Gas. 5. NFPA 101 - 1997, Life Safety Code, except Sections 10-1.1.1, 10-1.4, 10-1.7, 10-

3.2.3, and Chapter 11. 6. Chapter 10D of the Florida Administrative Code. 7. Florida Department of Environmental Protection (DEP). 8. Florida Department of Environmental Resources Management (DERM). 9. Florida Department of Transportation (FDOT). 10. United States Environmental Protection Agency (EPA). 11. Florida Energy Efficiency Code for Building Construction (FEEC). 12. Accessibility requirements of applicable codes. 13. FPL Commercial/Industrial Energy Conservation Program Standards. 14. American Society of Civil Engineers (ASCE) 7-98.

Page 4: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 4 Issued Design Criteria M-DCPS

B. Design shall comply with nationally accepted engineering practices, both mandatory and

recommended, including, but not limited to, the following:

1. American Society of Heating, Refrigeration, and Air-conditioning Engineers (ASHRAE).

2. American Society of Plumbing Engineers (ASPE) Data Book. 3. Sheet Metal and Air Conditioning Contractors' National Association (SMACNA). 4. National Sanitation Foundation (NSF). 5. American Water Works Association (AWWA). 6. American Society of Sanitary Engineers (ASSE). 7. National Fire Protection Association (NFPA). 8. Insulation Contractors Association of South Florida. 9. Published recommendations of nationally recognized manufacturers.

C. See M-DCPS Educational Specifications for program requirements of a specific facility. D. Discrepancies among the preceding requirements, brought in writing to M-DCPS, will be

reviewed and clarified by the M-DCPS Facilities Design and Quality Control. E. A/E is responsible for obtaining the documents containing the preceding requirements. F. Equipment, parts, assemblies, and installations shall be certified for safety and

performance according to the standards of Underwriters Laboratories (UL), Air-conditioning and Refrigeration Institute (ARI), Factory Mutual (FM), or other M-DCPS accepted nationally recognized independent laboratories. M-DCPS will reject uncertified submittals, equipment, and construction.

G. Submit a summary of systems to FPL, if applicable, and M-DCPS during predesign program phase. M-DCPS may require written system descriptions or specifications before approval for A/E to proceed with design work. A/E may request data from M-DCPS Facilities Design and Quality Control of existing M-DCPS systems for evaluation.

H. M-DCPS special requirements and experiences with various types of materials, equipment, and system installations have led to adopted procedures and practices. Use of new products, procedures, or installations shall be justified to M-DCPS and have a proven track record in national, state, or local installations.

I. Systems shall be easy to operate, maintain, and allow for expansion. Expansion provision costs shall be itemized in Phase 1 and Phase 2 submittals.

J. New schools or renovation projects, when accepted by M-DCPS, shall receive energy management, fire, and security monitoring systems compatible with and connected to M-DCPS Energy/Communications.

K. Existing buildings with monitoring systems shall have new or renovated systems compatible with and connected to the existing monitoring system.

L. Piping, including domestic hot and cold water, shall be visibly field identified by legend, flow arrows, and color coding according to ANSI 13.1.

M. Provide for accessibility for maintenance and replacement required by plumbing and HVAC equipment without removing adjacent equipment or piping at locations including, but not limited to the, following:

Page 5: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 5 Issued Design Criteria M-DCPS

1. Mechanical equipment rooms. 2. Boiler or domestic water heater rooms. 3. Chiller rooms. 4. Cooling towers. 5. Air-handling equipment. 6. Dust collectors. 7. Air compressors. 8. Piping and ductwork. 9. Access panels. 10. Chases. 11. Fire dampers. 12. VAV boxes. 13. Roof fans. 14. Under counters. 15. Cleanouts.

N. M-DCPS supplied not in contract (NIC) equipment list will specify installation by

contractor or future installation by others and shall be so noted in construction documents. O. Contractor installed NIC equipment and equipment furnished by contractor, according to

construction documents, shall be set in place, installed, and connected to the necessary systems for proper operation and noted in construction documents.

P. Provide rough-in of necessary items for proper connection and operation of future or not in contract (NIC) equipment. Stub out floor and wall lines with rough-in flush to the walls and floors for future connections.

Q. Direct communication shall exist between M-DCPS Facilities Design and Quality Control reviewer and the A/E mechanical engineer.

1. Include the FPL account manager when FPL Commercial/Industrial Energy

Conservation Standards are available. 2. The M-DCPS project manager and A/E may be present or on a conference call and

shall be copied regarding correspondence and agreements. 3. Meetings requiring M-DCPS Facilities Design and Quality Control participation

shall take place on M-DCPS property.

R. M-DCPS will provide available documents of existing facilities for A/E use.

1. M-DCPS is not responsible for the completeness or accuracy of the documents. 2. Visit the site and verify existing conditions. 3. M-DCPS Facilities Design and Quality Control shall be notified by the A/E through

the M-DCPS project manager if discrepancies exist.

S. Before design, review M-DCPS requirements, policies, and standards. Obtain specifications and guidelines regarding safety and environmental issues from the M-

Page 6: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 6 Issued Design Criteria M-DCPS

DCPS project manager, M-DCPS Facilities Design and Quality Control, M-DCPS Asbestos Management, and M-DCPS Safety, Environment and Hazards Management.

T. Design requirement specifications shall not allow for interpretation. U. Locate equipment in mechanical rooms within the building where feasible and within

budget. Provide exterior access to mechanical rooms or access through corridors and not through instructional spaces or private offices.

V. Questions regarding design requirements or drawing preparation shall be referred to M-DCPS Facilities Design and Quality Control through the M-DCPS project manager.

W. Edit or delete applicable unused portions of M-DCPS Master Specification Guidelines to be applicable to the specific facility.

X. Design review by M-DCPS at each phase will request clarification, coordination, suggestions, or mandatory requirements of specific items. Immediate replies and revised drawings to each comment are required for inclusion in the next submittal phase.

Y. M-DCPS Facilities Design and Quality Control determines mechanical submittals to be adequate for phase reviews. M-DCPS will withhold A/E payment if A/E has not replied to comments, not complied with design standards, program requirements, previous design reviews, or has submitted insufficient design information to comply with phase submittal requirements.

Z. The A/E shall be responsible for an efficient, safe, maintainable, and working facility according to Florida Statutes and the Department of Professional Regulation.

AA. Building automation, automatic security monitoring, direct digital controls, and fire alarm systems will be reviewed by M-DCPS Energy/Communications.

BB. If roof mounted equipment is existing or accepted by M-DCPS on a per condition basis, provide at least minimum clearances between finished roof and bottom of equipment framing supports for roof mounted equipment and any other horizontal related items to allow roof or equipment maintenance according to related M-DCPS Master Specification Guidelines. Equipment exposed to the weather shall comply with ASCE 7-98.

III. MECHANICAL SUBMITTAL PHASING REQUIREMENTS

A. Comply with SREF for document and submittal requirements and the following:

1. Program Phase - Mechanical submittal for existing facility renovations only.

a. M-DCPS preprogramming shall be verified by A/E program phase submittal and include the following HVAC and plumbing system information.

1) Scope of work. 2) Preliminary construction cost estimates. 3) Description of A/E recommended additional work scope and related

probable cost not included in M-DCPS preprogramming package.

2. Phase 1 - Mechanical submittal.

Page 7: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 7 Issued Design Criteria M-DCPS

a. Provide an outline to include the following:

1) Scope of work including revisions and related costs to program requirements.

2) Preliminary HVAC system description with qualifications for FPL rebates/incentives, if applicable.

3) Identification of work in contract for contractor, M-DCPS, or outside contractors.

4) Description of connection points of gas, storm drainage, sanitary and domestic water systems, and chilled water.

b. Site plan drawings shall comply with SREF for Phase 1 Documents and provide

the following:

1) Identification of existing, new, or future buildings or additions. 2) Construction, demolition, or relocation status of portable classrooms. 3) Approximate location of existing and proposed boilers, water chillers,

cooling towers, storage tanks, pumps, and other major plumbing and HVAC equipment.

4) Indicate proposed routing of major exterior lines for plumbing and HVAC systems.

c. Floor plan drawings shall comply with SREF regarding Phase 1 Documents and

include the following:

1) Approximate location of air-handlers, chillers, pumps, boilers, tanks, and other major plumbing and HVAC equipment.

2) Plumbing fixture locations. 3) Group toilet locations. 4) Preliminary construction cost estimates with breakdowns regarding central

plant equipment, air-conditioning units, chilled water distribution, temperature controls, sanitary systems, domestic water systems, plumbing fixtures, domestic hot water generators, expansion provisions, and other major categories or items.

5) Applicable FPL rebates or incentives for replacement or new installation of energy efficient HVAC equipment.

3. Phase 2 - Mechanical submittal (33 percent completion).

a. Completed life cycle cost analysis (LCCA). See Heating, Ventilating, and Air-

conditioning, this division. b. Drawings shall comply with SREF for Phase 2 Documents and include the

following in addition to Phase 1 requirements.

Page 8: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 8 Issued Design Criteria M-DCPS

1) Revised drawings and written response to each Phase 1 review comment. 2) Air-conditioning cooling and heating loads. 3) Domestic hot water estimated loads. 4) Type, size, capacity, efficiency rating, and location of air-handlers, chillers,

pumps, cooling towers, boilers, tanks, and other major plumbing and HVAC equipment in equipment rooms noting ductwork and piping layouts.

5) Routing and location of major interior piping for plumbing and HVAC systems.

6) Duct layout at 1/8" scale floor plans with air quantities noted. 7) Double line duct layout showing supply air, return air, temperature sensors,

smoke detectors, outside air, and exhaust systems including air quantities at 1/4" scale floor plans of typical and specific rooms or areas.

8) Double line duct layout showing piping, grilles, temperature sensors, diffusers, equipment, air quantities, and sizes at 1/4" scale floor plans of typical and specific instructional spaces.

9) Double line layout of major ductwork with main runs and sizing completed.

10) Fire damper locations. 11) Typical and specific rooms or areas with locations of plumbing fixtures and

sanitary and domestic lines sized and noted at 1/4" scale floor plans. 12) Group toilets sanitary and domestic water line locations and sizes at 1/4"

scale floor plans. 13) Equipment room layouts identifying equipment and locations at 1/4" scale

plans. 14) Format schedules for HVAC and plumbing equipment. Include efficiency

ratings. 15) Detailed construction cost estimates. 16) Preliminary schedule of events if required due to site complexity.

4. Phase 3 - Mechanical submittals (50 percent stand-up review and 100 percent

completion).

a. Completed set of mechanical specifications. b. Completed detailed and itemized construction cost estimate according to

contract requirements, including any applicable rebates or incentives from FPL for energy efficient equipment.

c. Drawings shall comply with SREF for Phase 3 Documents and provide the following in addition to Phase 1 and 2 requirements.

1) Revised drawings and written response to each Phase 2 review comment. 2) Completed mechanical drawings coordinated with plans and specifications

of structural, architectural, electrical, civil, laboratory equipment supplier, kitchen equipment supplier work, and not-in-contract equipment to eliminate errors, conflicts, and omissions.

Page 9: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 9 Issued Design Criteria M-DCPS

3) Mechanical and electrical coordination shall include the following:

a) Equipment capacities, voltages, and phasing. b) Wiring diagrams and control sequence narrative. c) Additional materials and equipment furnished and installed by specific

trades. d) Plumbing and HVAC controls. e) Completed motor control component diagrams noting factory, and field

wiring. f) Completed temperature control component diagrams noting specific

contractor responsibility.

4) Completed HVAC air distribution system and equipment including valving, instrumentation, controls, temperature sensors, smoke detectors, humidistats, and other associated components.

5) Completed plumbing and HVAC piping system component diagrams including details of control and coil valving, strainers, thermometers, pressure gages with pressure snubbers, shut-off cocks, and other associated components.

6) Completed control diagrams for kitchen ventilation system including components.

d. Provide the following, but not limited to, drawings, details, and schedules:

1) HVAC schedules with reference flag notation to be used in equipment

rooms for identification. 2) Plumbing schedules. 3) Completed fan schedules including area served by type of fan, wheel,

arrangement, CFM, static pressures in inches w.g., maximum allowable brake horsepower, speed, voltage, phase, and sone ratings.

4) Roof curbs, flashing details, platforms, hanging and support methods, vibration isolators, housekeeping pads, and other equipment mounting details.

5) Duct and piping roof penetration details. 6) Ductwork flags indicating SMACNA pressure change construction

classifications. 7) Indicate insulation requirements at fringe areas to indicate interior, exterior,

exposed, or concealed. 8) Fire damper and fire/smoke damper mounting details. 9) Coil connections, water treatment, air compressor controls, expansion

tanks, duct fittings, branch takeouts, splinters, lab equipment, and other equipment or installation details required for clarity.

10) Vertical or horizontal duct, pipe, and insulation supports. 11) Architectural life safety plan indicating fire rated walls coordinated with

Page 10: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 10 Issued Design Criteria M-DCPS

mechanical and fire protection drawings. 12) Fire protection system layout if required including hydraulic calculations

according to NFPA. IV. GENERAL PLUMBING REQUIREMENTS

A. Plumbing Systems.

1. Plumbing drawings shall contain the following systems to the extent of 5 feet beyond the building perimeter:

a. Domestic water. b. Sanitary building drainage. c. Storm drainage, except gutters and downspouts. d. Liquefied petroleum gases (LPG) or compressed natural gas (CNG). e. Fuel oil (only at existing facilities). f. Acid resistant piping and dilution tank. g. HVAC condensate piping. h. Boilers and domestic hot water generators including boilers necessary for space

heating. i. Heating and domestic water heat exchangers and storage tanks. j. Compressed air, excluding HVAC controls. k. Steam and condensate return. l. Swimming pools.

m. Solar energy. n. Miscellaneous piping.

B. Plumbing Drawings.

1. Provide the following information in the following order:

a. Site plan, legends, abbreviations, schedules, and general notes. b. Floor plans. c. 1/4" or larger scale drawings including, but not limited to, the following

congested areas.

1) Group toilets. 2) Group showers. 3) Laboratories. 4) Kitchens. 5) Equipment rooms.

d. Sections and details. e. Sanitary riser diagrams.

Page 11: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 11 Issued Design Criteria M-DCPS

f. Domestic water riser diagrams. g. Storm drainage riser diagrams. h. Gas riser diagrams. i. Acid riser diagrams. j. Compressed air riser diagrams. k. Swimming pool equipment riser diagram. l. Solar energy system riser diagram.

m. Chiller equipment room riser diagram. n. Miscellaneous riser diagrams as requested by M-DCPS.

2. Plumbing and civil drawings shall have similar sheet size, column lines, and floor

plan scales as architectural drawings, minimum 1/8" equals 1 foot. Include the following:

a. Graphic scale, numerical scale, north arrow, and lettering size legible for record

drawings. b. Adjacent streets located and identified. c. Existing, new, and future construction located and identified including curbing,

fences, and gates. d. Finished NVGD elevations of existing and new construction to include finish

floors, walks, roadways, and landscaped or play areas. e. Plumbing legend and abbreviations. f. Correct job title. g. Locate and provide sizing, loads including fixture units, materials, maximum

and minimum pressures, slopes and inverts at building exit, obstructions or other lines, and points of connection within property lines of the following:

1) Sewer, drainage, gas, fuel oil, fire, and water lines. 2) Chilled water and heating lines. 3) Wells, manholes, tanks, catch basins, soakage pits, french drains, septic

tanks, and drain fields. 4) Potential hazards or obstructions for plumbing system installation created

by existing or new utilities or construction.

h. Each manhole shall have inlet and outlet invert noted and with a 0.1" difference of elevation.

i. Distance separation noted between building foundations and parallel pressure, sewer, or drainage lines to avoid pressure gradients and undermining conditions.

j. Drawings and specifications shall assign sole responsibility to the contractor:

1) For locating buried pipes and duct banks, with hand trenching as necessary. 2) To repair damage at the contractor's expense.

k. Extension of utilities to grassed areas to provide for future building connections.

Page 12: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 12 Issued Design Criteria M-DCPS

Provide line termination with cap or plug in valve boxes or valves at pressure lines if new construction is scheduled within 3 years.

l. Note on site plan "CONTRACTOR SHALL VERIFY DEPTHS AND LOCATIONS OF CONNECTION POINTS TO EXISTING PRESSURE LINES AND DRAINAGE LINES BEFORE STARTING WORK".

m. Minimum and maximum water pressures. n. At line connections and appropriate intervals, identify slopes and loads as

existing, capacity available, future, and maximum allowable. Loads shall be noted as follows:

1) Fixture units at supply lines and fixture units at sewer lines. Verify varying

water and sewer fixture unit values for the same fixture. 2) Square footage of roof and paved areas for storm drainage lines. 3) Tonnage on HVAC condensate lines. 4) Type, pressure, material, and cubic feet per hour of gas lines. 5) Gallons per minute at fire lines.

o. Locations, size, and identify adjacent and on-site domestic water lines, fire

lines, and facility water meters. p. A heating and air-conditioning site plan of large central systems. Small systems

may be shown on plumbing site plan if properly cross-referenced.

3. Plumbing floor plans shall include the following:

a. Plumbing connections of fixtures and equipment to the appropriate system. b. Fixture and equipment identification by the common name abbreviation and a

number of each different model of the same type on risers, details, and other drawing locations.

Examples:

WC-1 Water closet WC-2 Water closet, ADA accessible UR-1 Urinal UR-2 Urinal, ADA accessible L-1 Lavatory, wall hung L-2 Lavatory, counter top L-3 Lavatory, ADA accessible L-4 Lavatory with hot water SH-1 Shower, individual, ADA accessible SH-2 Shower, group, head only SK-1 Sink, stainless steel SK-2 Sink, enameled cast iron ARSK-1 Acid resistant sink

Page 13: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 13 Issued Design Criteria M-DCPS

EWC-1 Electric water cooler EWC-2 Electric water cooler, Hi-Lo ADA accessible PLSK-1 Plaster sink FD-1 Floor drain at finished areas FD-2 Floor drain at equipment rooms FD-3 Floor drain at kitchens FD-4 Floor drain at kitchen with funnel FS-1 Floor sink at kitchen

c. Routings shall generally parallel building walls. Standardized symbols and text

shall locate and identify lines rises, drops, valves, cleanouts, and other related items.

d. Locate plumbing lines at finished areas in chases. Lines routed in stud partitions shall be coordinated with electrical and other trades to insure adequate fit. Block walls shall not be cut to install vertical or horizontal lines.

e. Note elevations on floor plans of:

1) Sanitary lines above ceilings. 2) Domestic water lines being fed from below. 3) Aboveground horizontal lines 3 inches and larger.

f. Plumbing lines at obstructions, offsets at HVAC ducts, allowable beam

penetrations, and limited or congested areas shall be detailed separately or shown on 1/4" per foot minimum scale drawings.

g. Pressure lines, gravity lines, or systems grouped for compatibility at congested areas may be shown on separate drawings. Reference separated systems to a specific drawing.

h. Coordinate storm drainage system for roof material, roof assembly thickness, gutter, downspout sizes, and locations.

i. Insulation for condensation protection is not necessary for rain water leaders, domestic cold water lines, or other similar systems.

j. Field tag numbers of installed valves shall correspond to drawing valve number identification.

k. Reference line continuation at match lines or drawings of a different scale to a specific drawing.

l. Isometric drawings shall provide a north arrow and an ellipse at slab penetrations.

m. Identify and provide utilities to NIC equipment to be installed by contractor or for future installation by others with provision of utilities.

C. Specific Room Plumbing Requirements.

1. Toilet Rooms and Group Showers.

Page 14: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 14 Issued Design Criteria M-DCPS

a. Locate and identify plumbing fixtures, associated equipment, and lines. Reference line continuation to a specific drawing. Size main branches. Gravity lines shall note inverts and fixture units.

b. Plumbing fixture symbols shall be representative of the fixtures specified. c. Size chases to provide sufficient space for plumbing lines to cross behind floor

mounted fixture carriers, if used, and to conceal carrier feet within finished walls.

d. Provide 1 accessible loose-keyed hose bibb in each group toilet room. e. Floors at ADA accessible individual toilet rooms and group toilet rooms shall

slope 1/8" per foot down to at least 1 floor drain within the room.

1) Specify floor drains with reseals. 2) Reseals shall be fed by a water closet flush valve tailpiece or safewasted

from an electric water cooler or drinking fountain. 3) Resealers fed from lavatories or sinks shall only be used where no suitable

water closet, electric water cooler, or drinking fountain is within 30 feet. 4) Resealers fed from supply pipes are not allowed.

f. Provide flush valves with valve mounted or wall mounted push buttons at ADA

accessible water closets according to accessibility requirements. g. Provide accessibility according to ADA and SREF to group toilet rooms and

single station toilet rooms.

1) ADA accessible individual toilet rooms at pre-kindergarten shall receive a standard height toilet 14 to 15 inches high and a 22 inch high lavatory.

2) ADA accessible individual toilet rooms at kindergarten and grades 1-2-3 shall receive a standard height toilet 14 to 15 inches high and a 25 inch high lavatory.

3) ADA accessible individual toilet rooms at grades 4 and 5 shall receive a toilet with a seat 17 to 19 inches above finish floor and an ADA accessible lavatory.

4) Individual staff and individual public toilet rooms shall be ADA accessible and provided with a toilet having a seat 17 to 19 inches above finish floor and an ADA accessible lavatory.

5) Elementary group toilet rooms shall each have at least 1 ADA accessible stall with a toilet having a seat 17 to 19 inches above finish floor and an ADA accessible lavatory within the stall.

6) Each group toilet room serving grades 6-7-8-9-10-11-12, the staff, or the public shall have at least 1 ADA accessible stall with a toilet having a seat 17 to 19 inches above finish floor and an ADA accessible lavatory within the stall.

h. Provide hot water to kitchen staff toilet rooms. Hot water shall not be supplied

to public, student, or any other staff toilet rooms.

Page 15: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 15 Issued Design Criteria M-DCPS

i. Consider washfountains in place of groupings of 3 lavatories. j. Lavatory valves shall be slow acting and self-closing. k. Showers shall not be provided with individual shut-off controls, except as noted.

1) Centralized water controls for showerheads shall be provided by

combination thermostatic and pressure balancing mixing valves to provide water temperatures from 95 to 110 degrees F. at showerheads.

2) Shower rooms containing 30 or more showers shall be zoned for 1/3 and 2/3 of the available showers.

3) ADA accessible showers shall receive individual vandal resistant thermostatic and pressure balancing controls.

l. A 2.5 gpm flow restrictor shall be at each showerhead.

m. Electric water coolers shall be next to and not in toilet rooms.

1) Locate additional coolers according to program requirements. 2) Any arrangement where water falls back on the mouthpiece shall not be

used. 3) Comply with ADA accessible double configurations.

n. Fixture counts shall comply with SREF and FBC-Plumbing Table 403.1 -

Minimum Number of Plumbing Facilities.

1) "Potty Parity" fixture ratios are required at group toilets serving assembly occupancies for gatherings of 50 or more.

2) Assembly occupancies include, but not limited to, gymnasiums, auditoriums, media centers, multi-purpose rooms, cafeterias, and cafetoriums.

3) The fixture ratio of the number of water closets for women to the combined total of water closets and urinals for men shall be 3 to 2

o. Fixture mounting heights shall be coordinated and stated in fixture schedules

and interior elevations. See Plumbing Fixtures, this division, for mounting heights.

p. Shut-off valves, cleanouts, access panels, air chambers, and water hammer arrestors shall be identified and locations coordinated with architectural drawings.

2. Kitchens.

a. General Requirements.

1) Sanitary sewer lines, storm drains, or waste lines shall not be placed above

a kitchen, serving line, or cafeteria seating areas.

Page 16: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 16 Issued Design Criteria M-DCPS

2) Provide a kitchen fixture and equipment schedule to indicate required services, line sizes, and one of the following:

a) The specification division to furnish and install item. b) The item is M-DCPS supplied and installed by contractor. c) Rough-in only is required for future item.

3) Chemical sanitizing is used by M-DCPS for hand washing. Limit facility

hot water requirements to sinks at 110 degrees F. maximum according to SREF.

a) Maintain a domestic water heater serving multiple fixtures at a

temperature of approximately 130 degrees F. to prevent bacteria and virus growth. Provide the fixtures with accessible thermostatic mixing valves to limit water temperatures to 110 degrees F.

4) Provide overhead domestic water service distribution.

a) Water supply service drop to freestanding service lines or fixtures shall

be from the nearest wall for the shortest possible under slab run. b) At underground runs where allowed, provide a minimum 1/2" soft

temper Type "K" copper tubing, without joints, in a minimum 3 inch PVC sleeve with sealed ends.

c) Run PVC sleeves at least 4 inches below floor slab. d) Exposed ceiling drops are not allowed.

5) Food service area sinks shall have hot and cold water. Comply with current

requirements of the M-DCPS Food and Nutrition and the following:

a) Provide one 3 compartment vegetable sink. b) Provide one 3 compartment pot wash sink with overflow/scraping

compartment. c) Provide food preparation handwashing lavatory with hot and cold

water, gooseneck spout with aerator, and electronic proximity controls. d) Provide 2 worktables with built in sinks.

6) Two door separation is required between kitchen areas and staff toilet

rooms. Provide toilet rooms with hand washing signs. 7) Provide single door separation between kitchen areas and laundry room. 8) Provide a mop receptor and a can wash with hot and cold water. Fittings

shall have a threaded hose end.

a) Locate can wash area with exterior access next to an exterior kitchen door. There shall be no direct opening from this area to the kitchen,

Page 17: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 17 Issued Design Criteria M-DCPS

toilet rooms, or lockers. b) Locate the mop receptor in the vestibule between the kitchen and staff

toilet rooms. Lockers and the washer/ dryer shall also be in the vestibule.

9) Provide cooking exhaust hoods with UL Standard 300 listed wet chemical

automatic fire suppression extinguishing systems.

a) Manual or automatic activation shall shutdown kitchen main gas line, shutdown supply fan, deenergize underhood electrical appliances, and activate fire alarm system.

b) See Division 16 - Fire Alarm System.

10) Provide alkaline dry chemical portable fire extinguishers with at least a 20:BC rating next to cooking equipment.

b. Grease Interceptors.

1) Locate interceptors as close as feasible to a kitchen exterior wall. 2) Waste lines normally receiving grease waste shall be routed through the

interceptor. 3) Individual interceptor capacity shall be at least 750 gallons. 4) Maximum individual interceptor capacity shall not exceed 1,250 gallons. 5) Provide multiple 1,250 gallon capacity interceptors in series for required

capacities above 1,250 gallons. 6) Interceptor sizing and construction shall comply with Chapter 10D-6 and

10D-9 of the Florida Administrative Code. 7) Inlet and outlet inverts shall be noted for each interceptor. 8) Locate interceptors end to end to allow for straight line piping. 9) Slope lines into grease interceptors at 1/4" per foot.

c. Floor Drainage.

1) Provide kitchens, and related areas with floor drains having hinged

gratings, sediment buckets, and reseals. 2) Seal traps from wastelines of suitable fixtures. 3) Reseals, if used, shall be fed from a water closet flush valve tailpiece, an

electric water cooler, or drinking fountain if available. 4) Locate reseals in mechanical or custodial rooms if a water closet, electric

water cooler, or drinking fountain is not available. 5) Locate and select floor drains for easy dismantling and cleaning by the

custodial staff. 6) Floor drain interior shall be stainless steel or coated with acid resistant

enamel.

Page 18: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 18 Issued Design Criteria M-DCPS

7) Drains shall have a removable mesh lined sediment bucket. 8) Drain cover grates shall only be able to be installed with the sediment

bucket in place. 9) Drains shall have a double strainer. 10) Kitchen floor drains shall be located in accessible areas:

a) Near refrigerators, tilting or steam kettles, and large capacity sinks. b) In storage rooms, except dry storage. c) At low points of floor slopes and other programmed locations.

11) Kitchen trough, channel, or trench drains shall be located between cooking

equipment and production lines according to program requirements of M-DCPS Food and Nutrition.

12) Floor drains shall be in plain view and accessible for cleaning and maintenance.

13) Drips, drains, and wastes from ice bins, ice machines, or any other food service equipment shall be indirectly conveyed by air gaps to sanitary systems and received by floor drains equipped with grating-free funnels.

14) Provide 1/8" floor slope down to drains. 15) Floor sinks shall only be used as triple compartment drains and other M-

DCPS accepted locations.

d. Dumpster Pads.

1) Provide exposed dumpster pads within fenced service yards. 2) Do not provide enclosed dumpster locations or covered dumpster pads. 3) According to DERM, divert liquid waste, by providing pad with 1/8" slope,

directly to a suitable green space, enclosed by a 6 foot high fence, next to the dumpster pads. No other surfaces are allowed to be traversed.

4) Provide hose bibb within 25 feet of pad. 5) See General Considerations for dumpster pads.

e. Compactor.

1) Provide a M-DCPS accepted compactor for cafeteria and facility waste in

the cafeteria with a convenient route, not through the kitchen, to a service yard dumpster.

2) Food service pulpers and extractors will no longer be installed in new or renovation M-DCPS projects.

3) See Division 11 - Food Service Equipment for additional information. 4) See Division 16 - Power System Design for additional information.

3. Science, Art, and Photography Labs.

Page 19: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 19 Issued Design Criteria M-DCPS

a. Locate and identify plumbing fixtures, hoods, sinks, associated equipment, and lines, including acid resistant lines.

1) Reference line continuation to a specific drawing. 2) Size main branches. 3) Gravity lines shall note inverts and fixture units.

b. Provide a lab fixture and equipment schedule to indicate required services, line

sizes, and one of the following:

1) The specification division to furnish and install item. 2) The item is M-DCPS supplied and installed by contractor. 3) Rough-in only is required for future item.

c. Provide acid resistant piping systems at science and photography labs. See

Drainage Waste and Vent Systems, this division. d. Lines to cabinet fixtures or equipment shall be located in chases or partitions.

Limit cabinet lines to connection lengths required directly from chases or partitions. If partitions are not available, provide chases from ceiling to behind cabinets at appropriate intervals for plumbing vents, and gas and water lines.

e. Island vents are not allowed. Safewaste island sinks directly to a floor drain. f. Sink equipped freestanding instructor's desk shall be safewasted to a 3-inch

floor drain in the apron space. Coordinate desk and drain locations on drawings. Extend 3-inch drain line 15 feet or less to a vented line.

g. Labs shall receive acid resistant individually trapped and vented sinks. A vent stack 5 feet or less from fixtures may be shared.

h. Acid resistant sinks shall be epoxy bonded to acid resistant counter tops attached to transverse wood supports. Grid drains shall be epoxy bonded to sinks.

i. Provide a standpipe stopper with overflow at instructor desks and other non-student sinks designated by program requirements.

j. Hot water shall not be provided at student accessible lavatories or sinks. k. Science Lab Faucets:

1) Student Accessible: Epoxy coated and vandal resistant, equipped with

aerator and vacuum breaker. 2) Instructor�s Demo Desk: Epoxy coated and vandal resistant, equipped with

serrated tip and vacuum breaker. 3) Material Storage: Chrome plated and vandal resistant, equipped with

aerator and vacuum breaker, 4) Science lab faucets shall have color coding and lettered identification.

l. Gas cocks shall be scheduled and have a serrated tip, color coding, and lettered

identification. Backsplash mounted wall cocks are preferred to turret cocks.

Page 20: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 20 Issued Design Criteria M-DCPS

m. Gas, compressed air, or water service available to students shall be provided with clearly labeled master emergency shut-offs.

1) Use manual valves and switches operating energized open solenoids. 2) Manual valves shall have 1/4 turn shut-off handles. 3) Valves or switches shall be accessible and be located at or within 15 feet of

the instructor�s demo desk.

n. Each room or lab where students handle materials or chemicals potentially dangerous to human tissue shall be provided the following and without flow restrictions:

1) A drench hose at the instructor's demo table. 2) A dousing shower and an eyewash for emergency uses. 3) Locate the shower and eyewash away from egress routes and in a non-

curbed area with a floor drain.

o. See Domestic Water, this division, for supply to drench hoses, emergency showers, and eyewashes.

p. Art lab and art class sinks shall receive plaster interceptors at sinks designated by program requirements.

1) Interceptors shall be cast iron, undercounter, and have 2 inch inlets and

outlets with unions, a removable top, a nonmetallic strainer and an acid resistant enameled interior.

2) Provide accessibility to interceptor and cut cabinet bottom to receive and set interceptor on floor to gain maximum top access.

q. Photography lab sinks shall be provided with an exposed cartridge filter,

throttling valves, vacuum breakers, and a spray hose capable of reaching all points of the developing table.

1) Faucet, throttling valve, hose outlet, and vacuum breaker shall be

downstream of thermostatic valves and cartridge filter. 2) Photography lab sinks shall not be provided with chillers for additional

cold water use.

4. Equipment Rooms.

a. Locate and identify equipment and lines with standard symbols or text denoting rises, drops, valves, instrumentation, cleanouts, and other appurtenances. Note inverts or elevations at crossovers, obstructions, and aboveground horizontal lines 3 inches and larger.

b. Provide accessibility and clearances to allow equipment removal and

Page 21: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 21 Issued Design Criteria M-DCPS

maintenance according to manufacturer recommendations without removing adjacent equipment or piping.

c. Fasten equipment to 4 inch high minimum housekeeping concrete pads. Extend pad at least 6 inches from equipment outline. Vibration isolation requirements may require larger pads.

d. Provide vibration isolation at piping and under moving equipment. Increase noise isolation above occupied spaces with specified acoustical requirements. Provide piping support at units to relieve equipment from stresses.

e. Provide valving and disconnect flanges or unions at equipment to accommodate disconnections and repairs.

f. Provide pressure gages, temperature gages, flow meters, and other devices as required for proper equipment and systems monitoring.

g. In equipment rooms, provide frame protected drawings and schedules identifying valve tag numbers and equipment labels to show model numbers, capacities, SEER, accessories, and options.

1) Provide complete information in project specifications. 2) Equipment labels shall correspond to identified breakers or disconnects

unless located so purpose is evident. 3) Identify and label equipment by name or number to correspond to

construction documents. 4) Equipment cabinets shall receive engraved plastic with 1 inch high letters.

Provide appropriately sized and legible brass tags on equipment without cabinets.

h. Use of a centralized equipment room generating space heating shall be

minimized and a single centralized domestic hot water facility is not necessary if loads are remote from each other. Food service areas and group showers have the highest hot water demands.

i. Boilers:

1) Boilers shall comply with the Boiler Safety Act of 1987. 2) Boiler rooms shall comply with SREF.

j. Provide rated enclosures as required by SREF for fuel fired heaters or boilers. k. See Fuels this division for energy sources. l. Since chemical sanitizing is used for manual washing in M-DCPS kitchens, base

calculations and set controls for domestic hot water requirements to not exceed 110 degrees F.

1) Winter design cold water temperature shall be based on 70 degrees F. 2) Maintain a domestic water heater serving multiple fixtures at a temperature

of approximately 130 degrees F. to prevent bacteria/virus growth.

Page 22: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 22 Issued Design Criteria M-DCPS

a) Provide the fixtures with accessible thermostatic mixing valves to limit water temperatures to 110 degrees F.

3) Tankless water heaters, 9 KW minimum size, may be used at custodial

sinks and remote fixture locations requiring hot water. Hot water shall not exceed 110 degrees F.

4) Domestic hot water storage tanks, including electric water heaters may be used.

5) Provide domestic hot water recirculation systems at kitchens and other high hot water demand systems where piping runs exceed 60 feet.

m. Provide block flows, riser diagrams, and details for all systems. Show flow

rates, temperature differences, valving, and instrumentation. n. Flow diagrams shall be checked and coordinated with detail drawings. o. Determine domestic hot water system distribution temperatures and the

minimum insulation thicknesses required for recirculating or non-recirculating systems. Minimum insulation thickness for domestic hot water mains shall be 1 inch thick.

p. Verify insulation requirements for domestic hot water mains and branches. Hot water branches to single or double fixtures may be bare if allowable by conditions and accepted by M-DCPS.

q. Provide a dousing shower and an eyewash for emergency use at water treatment areas for chillers and other areas according to OSHA.

D. Domestic Water.

1. Service shall be extended underground from a water meter next to the property line,

to an adjacent fenced reduced pressure backflow preventer, and enter at an appropriate building mechanical equipment room or chase for overhead copper distribution.

a. The last 20 feet of exterior underground water service into the building shall be

bitumen coated type "K" copper pipe, for electrical grounding provisions. b. Domestic water service shall enter the building at an above slab location at an

exterior wall. c. Piping shall not be embedded in concrete slabs. d. Piping shall not be installed below interior slabs on fill, except to floor drain

reseals, demo desks, and other program required locations with island sinks. Use type "K" copper without any joints, coated with bitumen, and sleeved at slabs. Limit under slab distances to 10 feet or less.

2. Provide a duplex domestic water pump pressure booster system only if available

street pressure and oversize piping are insufficient to serve the plumbing fixture requirements.

Page 23: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 23 Issued Design Criteria M-DCPS

3. Water meter selection shall be based on a 5 to 8 psig pressure drop at peak design flows and not maximum capacity, regardless of pressure drop.

4. Establish water demand utilizing Hunter's Curve counting fixtures with flush valves and adding other fixed loads such as group showers, cooling tower make-up, and food preparation areas.

5. Size water line mains for a maximum velocity of 8 feet per second. Soft water branches and branches with a pH less than 6.9 shall be sized for a maximum velocity of 4 fps. Exterior underground PVC shall be sized for a maximum velocity of 5 fps.

6. Piping size shall be determined to accommodate pressure drops instead of velocity requirements at remote fixtures.

7. Peak design flow minimum pressure requirements at flush valve operated fixtures shall be according to fixture manufacturers' recommendations plus a 5 psig safety factor.

8. Locate an exterior master shut-off underground in a lockable valve box near each building served.

a. The distribution system shall contain shut-off valves for each floor, wing, or

appropriate zone. b. Valves shall be installed immediately adjacent to main or branch junctions. c. Major fixture groupings shall be valved. d. Locate toilet room valves above the nearest ceiling with lay-in tile. e. Aboveground valves shall be rising stem union bonnet gate valves for 2-1/2"

and smaller. Use iron body bronze mounted (IBBM) outside stem and yoke gate valves for valves greater than 2-1/2".

f. Use ball valves for only hot water system balancing and SREF required emergency 1/4 turn shut-offs. Ball valves shall be full ported.

g. Do not install valves in toilet room wall valve boxes. h. Provide services stops at each fixture. i. Equipment or hose bibbs typically not receiving service stops shall be provided

with valves. j. All valves shall be accessible.

9. Emergency Water Supply:

a. Water supplies for drench hoses at instructors' demo tables, emergency showers,

and eyewashes shall be from an independent secure source not prone to inadvertent shutoff.

1) Emergency water supplies shall connect upstream of both the instructor�s

room master control and the branch shutoff valve feeding the room. 2) The emergency water supply to each area or room shall be equipped with a

single, rising stem branch shutoff valve, chained and locked in the open position, labeled "EMERGENCY WATER SUPPLY".

Page 24: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 24 Issued Design Criteria M-DCPS

3) The emergency water supply piping shall be at least 1-1/2" diameter. 4) Emergency water supply shall not have additional valving or stops

downstream of the locked and labeled valve.

10. Provide properly sized air chambers to eliminate water hammer in cold water lines. Calculated air chambers requiring accessibility shall not be used. Water hammer arrestors may be used.

11. Domestic hot water lines serving multiple fixtures, quick closing valves, or other devices generating severe shock waves shall be protected only with accepted water hammer arrestors.

12. Exterior hose bibbs shall be loose keyed, flanged, chrome plated, independently valved, vacuum breaker equipped, and at the building perimeter or courtyards at intervals not to exceed 150 feet.

13. See Toilet Rooms and Group Showers in this division and program requirements for additional hose bibb requirements.

14. Underground exterior domestic water lines shall be as follows:

a. PVC with push-on joints for 3 inch diameter lines and larger. Provide thrust blocks for push-on joints.

b. PVC with socket welded joints for 2-1/2" diameter lines or less. c. Determine proper PVC type for intended use from Florida Building Code (FBC)

- Plumbing, Chapter 6 with their respective governing ASTM or other standards. d. Plumbing lines shall be buried a minimum of 24 inches for lines 2-1/2" or less

and a minimum of 36 inches for lines 3 inches and larger. e. Install lines with 6 inches of clean sand below and at sides of pipe and with a

minimum of 12 inches of clean sand backfill over pipe. f. PVC supply line velocities shall not exceed 5 fps. g. PVC lines shall have 2 inch wide metallic detection tape buried between 4 - 6

inches below finish grade.

15. Aboveground domestic water lines shall be type "L" copper for 4 inch diameter lines or less. Lines with larger than 4 inch diameters and lines of galvanized steel shall be avoided unless for absolutely necessary mains and only when accepted by M-DCPS on a per condition basis.

16. Domestic water system shall contain lead-free components. Lead-free solder, containing silver for easy flow, shall comply with federal specifications for potable water systems.

17. The plumbing contractor shall provide written certification of a completed lead free domestic water system from point of service complying with Florida DEP and the Federal EPA and Clean Drinking Water Act.

18. Domestic hot water shall be limited to 110 degrees F. maximum and mixing valves shall not be used.

19. Provide hot water at the following locations:

Page 25: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 25 Issued Design Criteria M-DCPS

a. Kitchens, can wash, laundry centers, showers, custodial sinks, clinics, and kitchen staff toilet rooms according to SREF.

b. See program requirements for additional hot water locations. c. Hot water shall not be supplied to individual or group public, student, or any

other staff toilet rooms, except as required by code.

20. Backflow preventors shall protect the domestic water system from cross connections.

21. Dielectric unions and flanges shall protect the domestic water system from dissimilar metal electrolysis.

E. Drainage, Waste, And Vent Systems.

1. Sanitary System.

a. Provide a gravity system to convey wastes through a sewer network to the

available public sanitary sewer system or a DERM approved disposal system. b. See Division 2 - Sanitary Sewer System for additional requirements. c. Specify installation of piping containing bells and spigots to begin at the most

remote downstream point.

1) Bells shall be laid upstream and spigots downstream for each length. 2) Spigots shall not be used for pushing.

d. Building drain piping shall comply with the following:

1) 4 inch diameter lines or larger shall be sized for 1/8" per foot minimum

slope. 2) Lines less than 4 inch diameter shall be sloped at 1/4" per foot minimum. 3) 1/16" per foot slope shall not be used. 4) Cleanouts shall be full sized up to 6 inches and at intervals not to exceed 50

feet. 5) Provide concrete protection doughnuts for cleanouts in landscaped areas.

e. Aboveground building drain lines may be PVC according to the Florida

Building Code (FBC) - Plumbing, Chapter 7 with their respective governing ASTM or other standards.

f. Building drain lines under slabs-on-grade shall be centrifugally spun cast iron. g. Underground exterior sanitary lines shall be as follows:

1) PVC with push-on joints for 3 inch diameter lines and larger. 2) PVC with socket welded joints for 2-1/2" diameter lines or less. 3) Determine proper PVC type for intended use from Florida Building Code

(FBC) - Plumbing, Chapter 7 with their respective governing ASTM or

Page 26: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 26 Issued Design Criteria M-DCPS

other standards. 4) Plumbing lines shall be buried a minimum of 24 inches for lines 2-1/2" or

less and a minimum of 36" for lines 3 inches and larger. 5) Install lines with 6 inches of clean sand below and at sides of pipe and with

a minimum of 12 inches of clean sand backfill over pipe. 6) PVC lines shall have 2 inch wide metallic detection tape buried between 4"

- 6" below finish grade.

h. Use wet venting, circuit venting, loop venting, and combination waste/vent systems to reduce pipe and fittings.

i. Minimum size of a soil line connection to a water closet shall be 4 inches. j. Provide an acid resistant piping system for science and photography labs

separate from sanitary waste and vent lines until neutralized by marble chips, limestone, or other forms of calcium carbonate chips, all sized between 2 to 3 inches. Acid resistant piping systems shall comply with the following:

1) Provide a single underground neutralization tank instead of multiple

undercounter tanks. 2) Provide venting for neutralization tanks according to Florida

Administrative Code 10D-9 and connect to the building�s acid resistant vent system.

3) High silica cast iron piping is allowed for use at any location. Connection to a different aboveground piping material shall be at least 6 inches above slab.

a) High silica cast iron piping shall have mechanical coupling joints

properly tightened to manufacturer's specifications or have bell and spigots with acid resistant packing.

4) Borosilicate glass piping is only allowed for aboveground use.

a) Borosilicate glass shall have mechanical coupling joints.

5) Thermoplastic piping is allowed for use at any location. Include metallic

detection tape for burial.

a) Thermoplastic pipe shall be flame retardant polypropylene with adequate rack support and installed with fusible seal fittings.

6) Sanitary lines from at least 2 water closets shall discharge into a

downstream line extended from a neutralization tank. Acid resistant piping shall continue from the neutralization tank to acid resistant fittings at the waste line from the 2 water closets.

7) See Science, Art, and Photography Labs for plaster interceptors.

Page 27: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 27 Issued Design Criteria M-DCPS

k. See Kitchen in this division for compactors and grease interceptors. l. Provide floor drains with reseals unless receiving safewastes.

m. See Kitchens and Toilet Rooms and Group Showers for additional floor drain requirements.

2. Septic Tank Abandonment.

a. An onsite sewage treatment and disposal system shall be abandoned within 90

days and any further use of the system for any purpose shall be prohibited whenever the use of the system is discontinued:

1) Following connection to a sanitary sewer. 2) Following condemnation, demolition, removal, or destruction of a building

or property, 3) When discontinuing the use of a septic tank and its replacement with

another septic tank.

b. A septic tank may not be abandoned if the Department of Environmental Protection or its designee approves the use of the retention tank where the tank is to become an integral part of a sanitary sewer system or storm water management system.

c. Abandonment of an onsite sewage treatment and disposal system may be performed by a local utility or local plumbing authority or the Board will apply for a permit from DEP to abandon the existing onsite sewage system and submit the required fee.

d. Abandonment shall include the following:

1) The tank shall be pumped out. 2) The bottom of the tank shall be opened or ruptured, or entire tank collapsed

so as to prevent the tank from retaining water.

e. The tank shall be filled with clean sand or other suitable material, and completely covered with soil.

3. Storm Drain System.

a. Drainage calculations shall be based on storm water management requirements

of FBC - Plumbing and FDOT Drainage Manual - Volume 2A. b. Roofs shall be provided with overflow scuppers, gutters, and downspouts

connected to a storm drain system and based on the FBC - Plumbing using a rainfall rate of 6 inches per hour.

1) Use ductile iron with push-on joints and accepted hangers or Schedule 80

Page 28: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 28 Issued Design Criteria M-DCPS

PVC for downspouts. 2) Install lines with 6 inches of clean sand below and at sides of pipe and with

a minimum of 12 inches of clean sand backfill over pipe. 3) PVC lines shall have 2 inch wide metallic detection tape buried between 4"

- 6" below finish grade. 4) Cleanouts are not required in storm drainage systems. 5) Maximum water runoff travel distance from remote roof surfaces to point

of drainage shall be 50 feet for single-ply membranes and 75 feet for built-up roofs.

6) Interior roof drains are not allowed. 7) Storm drain systems shall end at soakage pits or exfiltration trenches.

Disposal wells may be used if chlorine and salinity levels are allowable. Verify system requirements based on percolation tests and extent of construction.

8) Splash blocks at downspouts require M-DCPS acceptance on a per condition basis.

c. Design storm drain system to avoid "fountain" effect caused by piping

discharging into a catch basin. d. See Division 2 - Civil for additional storm drainage requirements. e. See Design Criteria, Division 7 for roof slopes.

4. Condensate Drainage System.

a. Provide traps at AHUs sized for static pressures used. b. PVC piping is allowed. c. Discharge to a catch basin or a properly sized drywell. d. Insulate lines with 1 inch foamed plastic at AHU rooms.

F. Plumbing Fixtures.

1. Plumbing fixtures shall be enameled cast iron except fixture types available only in

vitreous china. Enameled steel fixtures are not allowed. 2. Water Closets.

a. Use wall mounted water closets. Floor mounted toilets may only be used for

replacement of existing floor mounted toilets when using existing plumbing connections.

b. Provide elongated siphon jets having 1.6 gallon flush valve activation, a 1-1/2" top spud, 3 inch minimum water seal, and 2-1/4" diameter passageway.

c. Floor mounted carriers with carrier legs shall installed within chases. d. Water closet seats shall be commercial quality, solid plastic, open front,

coverless, and have stainless steel check hinges. Color shall be white if same price or less than black.

Page 29: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 29 Issued Design Criteria M-DCPS

3. Urinals.

a. Provide siphon jet wall hung urinals with 1.0 gallon flush valve activation and a

3/4" top spud. b. Urinals shall have an integral trap and visible standing water. c. Provide floor mounted fixture carriers with mechanical attachment.

4. Sinks/Lavatories.

a. Sink and lavatory faucets shall be equipped with aerators, unless otherwise

noted, and not exceed a 2 gpm flow. b. Wall hung and counter mounted lavatories shall be enameled cast iron with 4

inch center holes, 1-1/4" offset grid drain for HC and 1-1/2" grid drain for others, slow acting self-closing valves, a 1-1/2" diameter 17 gage chrome plated "P" trap, and with chrome plated extension to wall with an escutcheon.

c. Wall hung lavatories shall be a minimum size of 20 inches by 18 inches with a 4-inch high backsplash.

d. Provide floor mounted concealed arm carriers for wall hung lavatories. e. Counter mounted lavatories shall be self-rimming and a minimum size of 19

inches by 16 inches. Do not use in student or public toilet rooms. f. Lavatory fittings with mixing valves shall not be used. g. A cabinet mounted handwashing lavatory equipped with hot and cold water

shall be provided in the clinic with wrist blade handles and a gooseneck spout. h. The classroom service sink with a non-refrigerated drinking fountain, located

according to program requirements, shall be 25 inches by 17 inches, 18 gage stainless steel, single compartment, self rimming, and supplied with cold water only.

1) Provide, at opposite ends of the sink, a gooseneck faucet, and the drinking

fountain. 2) Bubblers, or any arrangement where water falls back on the mouthpiece

shall not be used.

i. Custodial service sinks shall be wall mounted, plain back, and have rim guards, plain back, and no legs. Provide fitting at wall above sink back with hot and cold water, shank stops, a vacuum breaker, a 30 inch long hose, and bucket hook.

j. Size photography lab developing sinks according to program requirements.

5. Electric Water Coolers/Drinking Fountains

a. Electric water coolers or non-refrigerated drinking fountains shall be at instructional spaces according to program requirements. Provide double height

Page 30: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 30 Issued Design Criteria M-DCPS

units to comply with accessibility requirements. b. Electric water coolers shall be wall hung at alcoves to maintain egress width

requirements or not intrude upon traffic circulation. Provide side clearances for ventilation and comply with accessibility requirements.

c. Water coolers at exterior program required locations shall have weatherized stainless steel finishes, secured remote chillers, vandal resistant components, and other security measures.

d. Locate electric water coolers next to group toilets, in administration areas, cafeterias, and other large assembly areas except the media center. Do not locate inside toilet rooms.

e. Drinking fountains and water coolers shall be safewasted to floor drains, if within 30 feet. Dry wells may be used for remote locations.

6. See program requirements and this division for Toilet Rooms and Group Showers,

Kitchens, and Science, Art & Photography Labs for additional fixture requirements. 7. See Science, Art and Photography Labs for emergency showers and eyewash

facilities. 8. Use the following fixture heights above finish floor per grade levels. See

accessibility requirements for additional information. FIXTURE Pre K K & 1-3 4-5 6-8 9-12 & Adult Toilet rim 14"-15" 14"-15" 14"-15" 14"-15" 14"-15" ADA toilet rim* 14"-15" 14"-15" - - - ADA toilet seat ** - - 17"-19" 17"-19" 17"-19" Urinal rim - - 16"-20" 20"-22" 22"-24" ADA urinal rim - - 17" 17" 17" Lav rim 24" 25" 27"-28" 29"-32" 31"-32" ADA lav rim 22" 25" - - - ADA lav rim 22" 25" - - - with clear side 48"Wx36"D 48"Wx36"D approach ADA lav rim (max) - - 34"/29" 34"/29" 34"/29" and clear height below apron

Page 31: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 31 Issued Design Criteria M-DCPS

Electric water 24"-26" 24"-27" 27"-30" 32"-36" 34"-36" cooler/non- refrigerated spout outlet Sink rim- 24"-26" 24"-27" 27"-28" 32" 36" general Sink rim - - 30" 30" 36" 36" science Sink rim with 24"-26" 24"-27" 27"-28" 32" 36" drinking fountain HC sink rim with 22" 25" - - - drinking fountain * Provide a standard height toilet seat according to M-DCPS Master Specification Guidelines. ** Provide a standard height toilet seat according to M-DCPS Master Specification Guidelines at

new ADA accessible toilets. Plastic seat lifts at existing standard height toilets are acceptable when complying with 19" high seat accessibility requirements.

G. FIRE PROTECTION

1. Fire sprinkler systems, when required, shall be wet pipe and hydraulically designed

for light hazard occupancy with equipment rooms, stages, and any other similar rooms designed for ordinary hazard occupancy. Comply with NFPA-13 and SREF fire sprinkler requirements.

2. Fire sprinkler system shall provide for 10 percent future building expansion. 3. Construction documents shall be prepared and sealed by a mechanical engineer with

a documented 10 years of fire protection experience or a fire protection engineer. Florida registration is required.

4. Provide at each floor an accepted water flow detector alarm device connected to activate the building fire alarm system. An alarm check valve may also be required.

5. Sprinkler heads shall be pendant type if not below minimum ceiling height. Provide concealed or wall mounted heads at spaces with ceilings of minimum height.

6. Provide high temperature heads to minimize water damage. 7. At sprinklered buildings, provide sprinkler heads with NFPA intermediate

temperature classification at kiln rooms. 8. Provide appropriate extra heads to M-DCPS upon completion and cabinet as

specified by NFPA-13.

a. Locate cabinet at the headend of the system. b. When used, provide an equal number of concealed type fire sprinkler heads and

Page 32: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 32 Issued Design Criteria M-DCPS

concealed cover plates.

9. Stages shall comply with SREF classifications of working stages, enclosed platforms, and platforms. Only working stages shall have a system of automatic sprinklers.

10. Provide sprinklers under bleachers and with protective covers if within 8 feet of finish floor.

11. Provide firehose cabinets with a UL listed semiautomatic hose rack with a 100 foot hose and plastic nozzle only at working stage sides to comply with NFPA-14. Include pressure reducing valve or orifice to angle supply as necessary to reduce pressure below 100 PSIG.

12. Six sprinkler heads may be connected to the domestic water supply for an isolated hazardous area when complying with NFPA.

13. Cooling towers, woodworking shops, and paint spray booths may require fire sprinkler systems and alarms to comply with SREF and NFPA.

14. UL Standard 300 listed wet chemical fire suppression (extinguishing) systems (AFSS) shall be provided at cooking exhaust hoods. See Kitchens, this division.

15. Thermoplastic, UL listed, post chlorinated polyvinyl chloride pipe (CPVC) in fire sprinkler systems is only allowed for horizontal runs in light hazard use.

a. Transitions from CPVC to other pipe shall be shown on drawings. b. See NFPA-13 for light, ordinary, and extra hazard definitions.

16. See Kitchens, this division, for additional kitchen fire protection requirements.

H. Fuels And Energy Sources.

1. Use natural gas or electric power. Diesel fuel oil is not accepted by M-DCPS for

new construction except when program required, see Division 16 for emergency power systems. Consider liquefied petroleum gases (LPG) or compressed natural gas (CNG) if natural gas service is unreliable or unavailable in the area.

2. Natural gas, when used, shall provide boilers, kitchen equipment, water heaters, laboratory outlets, and emergency generators with manufacturers' recommended operating pressures.

3. Gas line building entrance shall be at an above grade and above interior slab location to overhead distribution.

a. Concrete filled bollards shall protect regulator and entrance piping against

traffic hazards. b. Fencing shall be provided for exterior regulators and valves. c. Valves shall be lockable.

4. Gas lines shall not be installed underground below interior slabs unless written

acceptance is obtained from M-DCPS Facilities Design and Quality Control on a

Page 33: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 33 Issued Design Criteria M-DCPS

per condition basis and metal sleeving and exterior venting is provided.

a. Use wrought iron, cast iron, or steel pipe for underground sleeves or aboveground gas venting. PVC is not allowed for sleeves or gas venting

. 5. Gas piping shall not be embedded in slabs or in slab raceways. 6. Egress corridors and stairwells and surrounding wall and ceiling construction shall

not contain gas or flammable liquid piping or valves. 7. Low-pressure gas distribution shall be used inside buildings and sized to provide the

recommended operating pressures. 8. Gas pressure regulators at each major piece of equipment shall be provided by

equipment manufacturer or contractor. Regulator locations shall be noted on construction documents and have relief vent piping to exterior when required.

9. Provide gas valves with electrical shut-offs (energized open) and connect to the fire alarm system. Provide a manual reset for operation after power restoration, located near the related area. Electrical shut-off valves shall be brass or bronze, not aluminum, and at a weather protected exterior location.

10. See Science, Art and Photography Labs, this division, for additional gas shut-off valve requirements at student locations.

11. Fuel tanks shall be aboveground on-site tanks, protected with concrete filled bollards at new facilities. Comply with NFPA 58 for locations. See SREF for requirements at EHPAs.

a. Facilities requiring the replacement or relocation of fuel tanks, shall receive

aboveground fuel tanks. b. New underground or relocated underground fuel oil tanks are not allowed. c. Fuel oil tanks shall comply with Miami-Dade County 24-12, Florida DER. Code

17-61, and any other applicable codes. See Division 15. d. Coordinate with the latest M-DCPS Safety, Environment, and Hazards

Management guidelines for aboveground tank installations. See Division 15 for accepted fuels.

e. Locate fuel tanks as far as possible from student occupied areas. f. Aboveground fuel oil lines shall be painted.

12. See Division 16 for emergency power.

I. Compressed Air.

1. Air compressors required for shop and paint areas shall be located in a mechanical

equipment room. 2. See Equipment Rooms, this division, for mounting and vibration isolation. 3. Compressors shall be tank mounted and sized to accommodate student loads, tools,

or other diverse requirements. Compressor capacity shall be designated as having x scfm at y psig.

Page 34: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 34 Issued Design Criteria M-DCPS

4. Compressors 3 HP and larger shall be two stage. Water cooled or electric dryer operation shall not be provided.

5. Provide compressor airline with a regulator equipped with a globe valve bypass and a centrifugal filter water separator of at least 75 percent efficiency. Combination filter regulators are not allowed. Additional air outlet regulators are not required. Provide instrumentation.

6. Automatic water traps with shut-off valves and piped drains shall be provided at the following locations:

a. Airline exiting from the air compressor. b. Compressor storage tank. c. First air riser from the compressor and risers over 1 story in height. d. End of the main line branch. e. Provide a petcock at the bottom of piping riser/drops without an automatic water

trap, and at the bottom of each air outlet.

7. Water trap drain lines of different pressures shall not be combined except in infrequently used systems.

8. Provide 1 inch in 40 feet slope down in the airflow direction of airlines and avoid water collection pockets. Reverse slopes are not allowed. Air branch lines shall be taken from only the top of the main line.

V. HEATING, VENTILATING, AND AIR-CONDITIONING

A. General.

1. Design conditions shall be:

a. Cooling indoor design conditions: 77 Fdb/55 percent relative humidity. b. Heating indoor design conditions: 68 Fdb/40 percent relative humidity. c. Summer outdoor design conditions except for cooling towers and air- cooled

condensers: 91 Fdb/77wb.

1) Cooling tower outside design conditions: 91 Fdb/79 Fwb. 2) Air-cooled condenser outside design conditions: 95 Fdb/79Fwb.

d. Winter outdoor design conditions: 44 Fdb.

2. Load calculations and design of the building envelope, lighting, air- conditioning,

heating, and ventilation systems shall comply with, but not limited to:

a. SREF architectural and engineering design requirements. b. Florida Energy Efficiency Code (FEEC). c. An accepted life cycle cost analysis (LCCA).

Page 35: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 35 Issued Design Criteria M-DCPS

d. ASHRAE Handbook of Fundamentals. e. Air-conditioning and Refrigeration Institute (ARI) guidelines. f. Sheet Metal and air-conditioning Contractors National Association, Inc.

(SMACNA). g. FPL Commercial/Industrial Energy Conservation Program Standards.

3. The following definition of seasonal energy efficiency ratio shall supersede the ARI

definition.

SEER = Total BTU Total Energy Input in Watts

B. Life Cycle Cost Analysis (LCCA).

1. Life cycle cost analysis shall be provided for educational facilities with new HVAC

systems 30 tons or greater, as required by SREF. 2. Computer programs acceptable for life cycle cost studies shall comply with the

following.

a. Be commercially available, third party software. b. Use latest ASHRAE procedures (GRP 158 & TC 4.7). c. Use hourly calculations based on weather records for Miami-Dade County. d. Calculate annual energy consumption and annual energy costs based on current

FPL rates. e. Be of adequate size to model the total project. f. Provide software features to model systems needed to complete LCCA Data

Sheets 1, 2, and 3. See Design Criteria Appendix for blank forms.

3. The following, but not limited to, programs for small computers are acceptable, if suitable.

a. Carrier HAP. b. Trane Trace Ultra. c. Building Energy Analysis by Elite Software. d. SEA (Simplified Energy Analysis) by Ferreira and Kalasinsky Associates. e. MICRO-DOE 2 by Acrosoft, Inc.

4. Financial Analysis.

a. Life cycle costs shall be based on a 25 year term using cost escalation factors of

inflation and interest rates in formulas listed in latest ASHRAE Handbook - HVAC Applications, Chapter 33 - Owning and Operating Costs.

b. Use M-DCPS current maintenance contracted costs. c. The air-conditioning system with the lowest life cycle cost or another system

Page 36: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 36 Issued Design Criteria M-DCPS

within 4 percent of the lowest life cycle cost will be selected and accepted by M-DCPS, unless thermal storage payback is less than 10 years.

d. DOE approval of the life cycle cost analysis and choice of system is required before DOE accepting Phase 3 documents for review and acceptance.

e. Analysis shall include FPL rebates, design incentives, or any other rebate programs for replacements or new installations using energy efficient equipment or systems.

5. Submittals.

a. Life cycle cost analysis according to SREF shall be submitted with Phase 2

documents for review and acceptance. b. The submittal shall include the following.

1) Description of the project as new, remodeling, or an addition. 2) If an on-site central chilled water system exists. 3) Printouts of required computer program inputs including building data,

equipment, hours of use, and rates of energy. 4) LCCA Data Sheets 1, 2, and 3. See Design Criteria Appendix for blank

forms. 5) Computer printouts of energy consumption and energy costs by month and

total for a year. 6) Comparisons of different mechanical systems or schemes including central

chilled water systems, a thermal storage system, and DX, water cooled, or air-cooled systems.

7) Solar energy projects with hot water demand exceeding 1000 gallons per day shall be submitted separately from life cycle cost analysis.

c. Life cycle cost analysis shall include, but not limited to, the following:

1) Water-cooled versus use of air-cooled chillers or condensers of 150 tons or

more. 2) Heat recovery off chillers for domestic hot water at kitchens, showers, and

heated swimming pools or wading pools. 3) Outside air reduction to a value not below 7.5 cfm per person using

filtration allowed by ASHRAE to achieve indoor air quality versus introducing 15 to 20 cfm per person without filtration.

4) Solar heated domestic hot water when demand exceeds 1000 gallons per day or when heating swimming pools or wading pools.

5) Thermal energy storage for daytime use. 6) Use of flat plate heat exchangers. 7) Constant volume air systems versus variable air volume systems. 8) Refrigerants, if HCFC-22, HFC 134a, or HFC-410A are not used.

Page 37: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 37 Issued Design Criteria M-DCPS

a) Escalation costs of CFC-11, CFC-12, CFC-500, CFC-502 and other refrigerants due to regulations and shortages.

b) Equipment conversion costs of CFC-11 and CFC-12 to HCFC-22, HFC-134A, or HFC-410A.

c) Increased energy costs of operations after conversion to new refrigerants.

d. LCCA of constant volume air systems versus variable air volume air systems

may be omitted at classroom buildings. e. See Cooling Sources, this division for chillers and condensers. f. Low energy mechanical ventilation or economizer cycle may be omitted without

submitting an LCCA.

C. HVAC System Selection.

1. General Requirements.

a. HVAC systems shall be simple, easy to operate and maintain, use established design principles, be constructed of standard and proven materials, and be available at the lowest initial cost possible when compared against operating costs. Include FPL incentives.

b. Provide individual temperature controls to as many individual rooms as possible.

c. The energy efficiency ratio (EER) of HVAC equipment installed shall be the greater of minimum values stated in the FEEC and the minimum values required for FPL Commercial/Industrial Conservation Program Standards. Before installation, provide M-DCPS the manufacturer's literature verifying EER rating compliance.

d. Selection of one of the following systems shall be determined by LCCA and FEEC with parameters according to this division:

1) Unitary systems: Packaged single zone, factory assembled, self-contained

or split systems serving a single or multiple spaces. 2) Central systems: Cooling from a central source providing control zones and

serving multiple instructional spaces.

e. Exterior equipment and mountings shall withstand wind velocity pressures determined by American Society of Civil Engineers (ASCE) 7-98.

f. Wind loading design shall comply with American Society of Civil Engineers (ASCE) 7-98.

1) Provide calculations, signed and sealed by a Florida registered professional

engineer, establishing wind velocity pressure values for the specific project according to ASCE 7-98 using a wind speed of 146 mph.

Page 38: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 38 Issued Design Criteria M-DCPS

2) Use ASCE 7-98 Exposure Category "C" for wind design at M-DCPS additions and new construction.

3) According to ASCE 7-98 occupancy types, educational facilities are classified as Category 3 and shall have a wind load importance factor of 1.15.

4) SREF recommendations to use map wind speed plus 40 mph and a wind importance factor of 1.0 are not to be used.

g. Install condensate drains to drywells or a storm drain system. PVC piping as

specified for drainage may be used. Provide cleanouts and long radius elbows. h. The following, but not limited to, systems and components shall be used:

1) All air VAV systems for science labs, vocational labs, demonstration

rooms, music labs or rooms and any other room for student instruction. VAV systems shall use variable frequency drive fans. Variable inlet vanes are not allowed.

2) Single zone units for administration areas, gymnasiums, cafeterias, auditoriums, and any other large zones or areas, if determined by LCCA.

a) Single zone units shall receive face and bypass dampers.

3) Heating with electric strip heaters mounted at unit or in ducts. 4) Central plants of 50 tons or more shall consist of 2 centrifugal, rotary

screw, scroll, or reciprocating type chillers.

a) Size each chiller for approximately 60 percent of calculated peak cooling load on a primary loop.

b) Provide secondary chilled water loops at high schools. c) Provide loops with variable speed pumps. d) Chiller type shall be according to Cooling Sources in this Division.

i. Do not use a VAV system with DX units. j. Fan coil units, and VAV diffusers are not allowed for use. k. Unit ventilators are allowed for use as noted. l. Contractor shall verify components and systems are operational. Test and

balance services will be provided by a M-DCPS contracted firm. m. Fiberglass or any other material used for insulation or sound reduction shall be

separated by solid metal from the airstreams of ducts, outlets, air-handlers, VAV boxes, sound traps or any other HVAC equipment or components.

2. Specific Requirements.

a. Air-condition kitchen, kitchen offices, food storage, and other spaces according

to program requirements.

Page 39: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 39 Issued Design Criteria M-DCPS

1) Odor filled return air from cafeterias, home economics, and other similar

spaces shall not be mixed with and resupplied to other limited spaces or areas unless accepted odor filtration systems are used.

b. Kitchen dry storage rooms shall maintain at all times a temperature not to

exceed 75 degrees F. and relative humidity not to exceed 60 percent. See Design Considerations in this division.

c. Provide air-conditioning to electrical, main telephone/ communication room, switchgear, and air-handling unit rooms.

d. Cooking kitchen hood ventilation and exhaust:

1) Provide make-up type kitchen exhaust hood system. 2) Kitchen hood design shall extend 6 inches minimum beyond grease and

fume generating equipment and have fluorescent lighting with solid lens covers to maintain kitchen illumination requirements.

3) Hood shall be 18 gauge, Type 304 stainles steel. Exposed stainless steel shall have No. 4 finish. Galvanized, mild steel, or 400 series stainless steel are not allowed.

4) Design for low air velocities to minimize noise and to comply with ASHRAE Applications Handbook.

5) Hood system shall be UL listed, designed to comply with NFPA 96, and be NSF labeled.

e. Provide full width flystop air curtains with automatic door opening operation at

each exterior door of food service areas and dining rooms. Locate according to manufacturer�s recommendations for dust and insect control.

1) Provide weather resistant coatings and construction. 2) Provide a keyed cutoff switch. Push button switches are not allowed.

f. Maintain indoor air quality (IAQ) at instructional spaces, home economics,

darkrooms, shops, graphics, and science laboratories during experiments, dissections, and other odor producing activities with the use of additional ventilation, filtration, or exhaust.

1) Return air from odor producing areas shall not be combined with return air

from non-odor producing areas unless supply air is filtered using a M-DCPS accepted IAQ filter system.

2) Hoods required for these areas, except for home economics, shall be designed according to SMACNA.

3) Provide supplemental make-up air type fume hoods according to program requirements.

4) Provide one exhaust fan for each fume hood.

Page 40: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 40 Issued Design Criteria M-DCPS

5) Laboratory fume hood exhaust system shall be stainless steel. 6) Provide an emergency exhaust system at rooms with laboratory fume hoods

to comply with SREF. Emergency exhaust system may be galvanized steel.

a) When emergency exhaust fans are turned on, the fume hood exhaust fan shall remain in operation and the fume hood supply fan shall automatically shut down.

b) Include laboratory hood exhaust fans in the air change rate calculation when emergency exhaust fan is turned on and the laboratory hood supply air fans automatically shutdown.

g. Provide mechanical ventilation or mechanical exhaust at custodial closets with

service sinks and at storage rooms. Provide 1 CFM minimum per square foot mechanical ventilation for these rooms.

h. Do not air-condition or heat toilet rooms if conditioned air can be exhausted through the room. Exhaust slightly less than conditioned make-up air requirements from adjacent areas. Odor laden air shall not move through adjacent areas en route to exhaust. Provide 2 CFM minimum per square foot mechanical ventilation for toilet rooms.

1) Group toilet rooms shall have exhaust fans on continuously during

occupancy periods. Provide exhaust fans with a keyed switch and interlock with EMS for shut down and air-handling unit for start-up.

2) Individual toilet rooms shall have exhaust fan operation for 5 minutes after turning off lights.

i. Buildings shall be pressurized to maintain a 0.05" w.g. positive pressure.

1) The total return air and exhaust air volume from a space and the building

shall be 90 percent of the supply air volume. 2) At each AHU schedule, show the amount of outside air, supply air, return

air, and the percentage of the sum of the return and exhaust air to the supply air.

3) Provide air balance tables for corridors on the related floor plan sheets. 4) Note cfm per square foot for all areas.

j. HVAC piping or ducts shall not be located on top of walkway roofs or building

roofs. k. Equipment not feasible or not within budget to be located within the building

shall be at exterior ground floor locations. Roof mounted equipment requires acceptance by M-DCPS on a per condition basis.

1) Equipment at exterior ground floor locations shall receive a chain link roof

and 8'0" high minimum chain link perimeter fencing with lockable gates to

Page 41: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 41 Issued Design Criteria M-DCPS

deny unauthorized access. Pave the enclosed area and provide fencing clearances for equipment accessibility and maintenance. See Division 2 for additional fencing requirements.

2) Roof mounted equipment not intended for curb installation, shall be mounted on a structural framing system. a) Bottom of supports shall be at least the following heights above the

finished roof, to allow roof and equipment maintenance.

Width of Equipment ClearanceUp to 36" 18" Above 36" to 48" 24" Above 48" to 60" 30" Above 60" and wider 48"

b) Except at curbs and other roof mounted items designed to receive 8

inch high flashing, terminate other surfaces or pipes intersecting the roof plane at least 14 inches from the finished roof membrane.

c) Coordinate with Divisions 7 and 16. See Division 5 for equipment framing supports.

3) Roof mounted equipment, exhaust fans, exhaust and intake goosenecks,

and louvers shall be identified and labeled to correspond to construction documents unless specific purpose is readily evident.

l. Provide controls at direct expansion units to prevent freezing water resulting in

bursting pipes. m. Equipment rooms with refrigerant use shall comply with ASHRAE 15 and

provide the following:

1) Refrigerant sensors within 50 feet of refrigerant systems. 2) Equipment room alarm. 3) Forced mechanical ventilation for occupied and non-occupied conditions at

chiller room. 4) Self-contained breathing apparatus at equipment rooms. 5) Purge and relief valves piped to exterior. 6) Signage as required.

n. Note HVAC systems shall be in operation before installation of specific

finishes. o. Specify the contractor to maintain a repair log of equipment before M-DCPS

acceptance.

D. Heating Sources.

Page 42: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 42 Issued Design Criteria M-DCPS

1. Alternative heat sources shall be evaluated and decided by life cycle cost analysis

for Phase 2 submittal.

a. Provide electrical strip heat installed in HVAC ductwork or VAV boxes for space heating if economically feasible.

b. Use of existing, replacement, or future central boilers for space heating requires acceptance by M-DCPS on a per condition basis, due to extensive start-up and water system heating time.

1) Provide horizontal fire tube boilers with 5 square feet of heating surface per

horsepower with integral force draft burner, burner controls, boiler trim and refractory mounted on steel base frames.

2) Boilers shall comply with requirements of the Boiler Safety Act of 1987. 3) Boiler inspection is required by the M-DCPS insurance company. Schedule

with M-DCPS Risk Management before operation.

c. Individual gas fired furnaces, unit heaters, wall heaters, duct furnaces, or infrared heaters may be used at warehouses, shop buildings, and other similar small installations if economically feasible.

E. Cooling Sources.

1. Alternative cooling sources shall be evaluated and decided by life cycle costs for

Phase 2 submittal. 2. Chillers and condensers shall be the following for the total system capacity:

a. Up to + 25 tons - Reciprocating or scroll, air-cooled. b. + 25 tons to + 150 tons - Rotary screw, air-cooled. c. + 100 tons to + 800 tons - Rotary screw or centrifugal, water-cooled. d. + 800 tons and above - Centrifugal, water-cooled.

3. A central refrigeration plant shall be used for a cooling source if available for

present or future use. 4. Reciprocating and scroll refrigeration units shall be used for small loads. 5. Consider packaged condensing units with direct expansion coils with electric strip

heat for small installations. Combination heater and refrigeration packaged units may be used at small buildings. Heat pumps may be used for small individual instructional spaces on a per condition when accepted by M-DCPS.

6. Packaged air-cooled water chillers shall be used for loads less than 150 tons. 7. Manufactured packaged systems shall comply with the following consumption

limitations.

a. 1.26 maximum KW per ton for units with less than 20 ton capacity.

Page 43: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 43 Issued Design Criteria M-DCPS

b. 1.20 maximum KW per ton for units with greater than 20 ton capacity.

8. Water-cooled systems shall be used for systems over 100 tons. Investigate FPL incentive programs.

9. Direct expansion air-cooled systems shall be considered for cooling loads of 50 tons or less. Investigate FPL DX incentive programs.

F. Design Considerations.

1. The central chilled water plant shall be placed in an engineered driven location and

not based on aesthetics alone. 2. Provide a written estimate for approval during Phase 2 for interconnecting an

existing chiller plant with a new proposed separate chiller plant. 3. The central plant chilled water air-conditioning equipment shall be capable of

operating at reduced loads for off-hour use. 4. The following, but not limited to, spaces shall maintain design temperature and

relative humidity requirements of 77Fdb/55 percent RH during off-hours as required, except as noted. Use an independent AHU while operating the central chiller plant at a reduced capacity. If the central plant’s chillers cannot operate at the necessary reduced capacity, provide an independent refrigerant system with a local secure thermostat or a computerized start/stop/temperature controls.

a. Cafeteria/cafetorium dining areas. b. Auditoriums, stages, stage storage areas, and related spaces. c. Gymnasiums and physical education spaces. d. Band classrooms, vocal music classrooms, and related spaces.

1) Relative humidity at instrument storage rooms shall not exceed 55 percent

at all times. Provide a secure thermostat and a humidistat for controls.

e. Media center:

1) Relative humidity shall not exceed 50 percent at all times and 80 degrees F. during off-hours. Provide a secure thermostat and a humidistat for controls.

f. Administration area:

1) Provide an additional cooling load of at least 2.5 tons at administration

areas to account for computers, printers, TV sets, copying machines, vending machines, microwaves, and other NIC items.

5. Provide unit ventilators or other supplemental HVAC systems at the following

spaces to maintain specific temperatures and relative humidity requirements.

Page 44: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 44 Issued Design Criteria M-DCPS

a. Kitchen dry storage rooms:

1) Maintain at all times a temperature not to exceed 75 degrees F. and relative humidity not to exceed 60 percent.

b. Main telephone room and adjacent network server room:

1) Maintain at all times a temperature not to exceed 75 degrees F. and

relative humidity not to exceed 60 percent. 2) Design heat load will be approximately 10,000 BTU/Hour for the main

telephone room and 2,000 BTU/Hour for the network server room.

6. Childcare centers shall be individually and separately zoned. 7. Emergency rooms or a health occupational program with a clinic capable of being

used as a temporary emergency room shall be provided with adequate filtration and negative relative pressure.

8. Each instructional space shall receive temperature sensors to monitor and independently control air-conditioning. Adjacent offices may receive a single zone control at the most representative room temperature location.

a. Locate temperature sensors in return air ductwork and to be accessible from the

return air grille in the space.

G. Indoor Air Quality (IAQ) And Outside Air Requirements.

1. Outdoor air ventilation for appropriate indoor air quality shall be according to ASHRAE 62-1994.

2. Design supply air and ductwork according to ventilation effectiveness factors and Equation 6-1 of ASHRAE 62-1994.

3. At auditoriums and gymnasiums, provide outside air adjustments for full, reduced, and zero occupancy modes to reduce outside air quantities.

a. Provide automatic controls using carbon dioxide measuring, localized motion

detectors, or other M-DCPS approved devices for adjusting outside air quantities.

b. Provide manual overrides with timers to be easily accessible and in a secured location.

c. Controls, actuators, dampers, fans, and valves shall provide fast responses to rapidly changing trends or conditions.

d. Provide additional dedicated air handling units for outside air conditioning, not pre-treatment coils, for gymnasiums and auditoriums.

e. System shall maintain temperatures and relative humidities within M-DCPS required design conditions throughout the range of outside air variation.

Page 45: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 45 Issued Design Criteria M-DCPS

4. Select the lowest cost system based on a LCCA to maintain appropriate indoor air quality by one of the two following options. Exceptions would be based on odor considerations in this division.

a. Option 1: Providing 15 or 20 cfm of adequate outside air per occupant as

applicable, with the following:

1) Air-handling units shall have:

a) A dedicated outside air-cooling coil with a minimum of 6 rows. Each row shall have a maximum of 10 fins per inch. Provide a bypass factor of less than 0.10.

b) A sensible load cooling coil with a minimum of 4 rows. Each row shall have a maximum of 10 fins per inch. Provide a bypass factor of no more than 0.12.

2) Use of an approved enthalpy or desiccant wheel system for humidity

control with coils constructed as recommended by manufacturer requires M-DCPS written acceptance on a per condition basis.

3) Rooftop unit mounting is not allowed unless accepted in writing by M-DCPS, on a per condition basis.

a) When used, rooftop or exterior units shall have welded frame

construction, with proper casing and tie downs, complying with ASCE 7-98 and SREF.

4) Minimum acceptable AHU filter shall consist of a single 4 inch thick,

disposable, pleated particulate filter, ASHRAE Standard 52.1-92 rated at 40 to 45 percent atmospheric dust spot efficiency, located in filter box upstream of each AHU coil. Use a design pressure drop of 0.42 inches w.g. for these type filters in E.S.P. calculations.

5) Smoke detectors connected to the fire alarm system shall be provided in the return air ductwork, located before the mixing with outside air and in the supply air.

b. Option 2: Providing not less than 7.5 cfm of outside air per occupant and indoor

air quality (IAQ) filtration as allowed under Appendix "E" of ASHRAE 62-1994. IAQ filtration shall consist of the following:

1) Pre-filter: Minimum acceptable AHU pre-filter shall consist of a single 4

inch thick disposable, pleated particulate filter, ASHRAE Standard 52.1-92 rated at 40 to 45 percent atmospheric dust spot efficiency, located in filter box upstream of each AHU coil. Use a design pressure drop of 0.42 inches w.g. for these type filters in E.S.P. calculations.

Page 46: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 46 Issued Design Criteria M-DCPS

2) Gas Phase Filtration: Single pass gas chemical filter media, UL listed Class 1, non-toxic, nonflammable, not supporting mold or bacteria growth, disposable bulk media filters contained in rigid, 1/8" thick, water resistant cardboard frames. Chemical filter media shall contain not less than 4 cubic feet of media per 1,000 CFM of airflow. The maximum allowed velocity through the filter media shall be 450 fpm. Provide 2 sections.

a) The first bulk filter chemical media section shall have a thickness of at

least 12 inches of activated carbon granules impregnated with potassium hydroxide or other accepted equivalent chemical material designed to remove a variety of gaseous organic compounds. Each chemical pellet shall be 3 to 4 millimeters in diameter, in cylinders or spheres.

b) The second bulk filter chemical media section shall have a thickness of at least 12 inches of activated alumina impregnated in potassium permanganate granules or other accepted equivalent chemical material designed to remove a variety of sulfuric, nitric, and other gaseous compounds. Each chemical pellet shall be 3 to 4 millimeters in diameter, in cylinders or spheres.

c) The media chemical components may be combined in equal quantities inside the two 12 inch sections. Chemical media residence time shall be not less than 0.10 seconds at 450 fpm per chemical filter section.

d) The total design pressure drop, at 450 fpm, for the combination of both bulk chemical media filter beds shall not exceed 2.5 inches w.g. Use published pressure drop values at filter mid-life, not clean filter values.

e) The above specified chemical filter media shall provide for at least 1 year effective life in average school use.

3) Final Filter:

a) 12" thick disposable rigid pleated box type combination ASHRAE 90

to 95 percent average atmospheric dust spot percent efficiency, located downstream of the gas phase filter modules.

b) The design pressure drop for this type filter shall not exceed 0.77 inches w.g.

c) Use actual pressure drop values at filter mid-life, not clean filter values.

4) Provide a Life Cycle Cost Analysis between systems described for using outside air of 15 to 20 cfm or using 7.5 cfm with filtration and select lowest cost system. Exceptions would be based odor considerations in this division.

5) Gas phase filtration and final filter shall be placed in a metal housing fabricated by the gas phase filter manufacturer. Locate filter housing downstream of AHU, in supply air ductwork, and provide proper small

Page 47: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 47 Issued Design Criteria M-DCPS

angle sheet metal ductwork transitions complying with SMACNA Fig. 2-7. Filter housing shall be easily accessible and located inside AHU rooms.

a) Housing shall be not less than 16 gage galvanized steel with

appropriate frame structure, double walled, with minimum 1.5" thick, 3 pcf fiberglass insulation, sealed to allow less than I percent air leakage at design pressure. Provide proper gasketed tracks manufactured of extruded aluminum or nylon suitable for each filter width.

b) Provide filter housing with side accessible gasketed, double walled, and insulated doors. Doors shall have corrosion resistant stainless steel hinges and shall be provided with quick opening latches having progressive adjustment.

c) Provide a differential pressure switch across filter housing wired to the EMS system

6) Smoke detectors shall be provided upstream and downstream of the metal

filter housing, suitably separated from bends and transitions, and also in the return air ductwork before mixing with outside air

7) AHU cooling coil shall have at least 4 rows, each with a maximum of 10 fins per inch, and having a bypass factor not exceeding 0.12.

8) Supply air shall not bypass filters.

5. Reheat coils are accepted for use with the listed options to maintain appropriate indoor air quality.

6. Odor Considerations:

a. Use IAQ filtration at the following unless justification for other IAQ systems is accepted by M-DCPS:

1) Primary learning centers and other elementary schools where classroom or

multipurpose room eating is allowed. 2) Other schools where odor generating conditions are present and cannot be

economically self-contained.

a) Self-contained fan powered recirculating IAQ room air purifier having the same particulate and gas filter medias and stages as stated before, may be used in isolated areas, provided written permission is obtained from M-DCPS on a per condition basis.

7. Filters shall not contain fiberglass. 8. Outside air shall be ducted to the AHU.

a. Provide an appropriate air intake located at least 36 inches above the roof. b. Wall mounted intakes are not allowed.

Page 48: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 48 Issued Design Criteria M-DCPS

c. At installations requiring more than 5 cfm of outside air per occupant, outside air shall be introduced by using a dedicated fan.

1) If the system is VAV, provide a VAV box downstream of supply air fan, to

maintain a constant outside air volume. 2) Use a permanently installed air measuring station in outside air intake

system with the transducer wired to the EMS system to ensure minimum outside air volume and maintain building pressurization.

3) EMS system shall be capable of monitoring, recording, and modulating outside air through the O.A. motorized damper.

9. Roof mounted outside air intakes and exhausts shall be installed in properly flashed

curbs, having side mounted and caulked screws. Ductwork shall be counterflashed as necessary.

10. Return air shall be ducted to the AHU. Corridor return air is not allowed. An exception may be made for small administrative area alterations and renovations when accepted in writing by M-DCPS, on a per condition basis.

11. AHU rooms shall not serve as either an outside air or return air plenum. AHU rooms shall be provided with a supply air register and shall be air-conditioned.

12. AHU condensate drain pan shall be IAQ type.

a. Pan shall be sloped at least 1/4" per foot to drain with a double slope break in the metal, and shall be designed to drain dry with no standing water.

b. Pan shall extend horizontally at least 1/2 the height of the coil face drainage area.

c. Pan shall comply with IAQ requirements of ASHRAE Standard 62R, and have a level lip with at least a 4 inch depth.

13. Provide motorized dampers at all outside air intakes including locations where

supply air/outside air fans are installed.

a. Provide manual volume dampers with memory stops, downstream of motorized outside air dampers. Manual volume dampers are not needed in branch ductwork having supply/outside air fans.

b. Provide controls and actuators as required to interlock all supply/outside air fans, their motorized dampers, and exhaust air fans, with their corresponding AHU�s so no exhaust or supply/outside air is activated, and no outside air is introduced for a period of 30 minutes during start-up.

c. At each space with a fume hood, the emergency exhaust system shall consist of a supply fan and an exhaust fan.

1) The exhaust fan grille shall be located near and above the hood. Locate the

supply air outlet at the most remote location in the room from the exhaust fan grille, to completely swept the room of fumes.

Page 49: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 49 Issued Design Criteria M-DCPS

2) Provide a low leakage motorized damper for the supply and exhaust fans. 3) Provide a properly labeled single interlocked switch for both fans near the

exit door.

14. Buildings shall be pressurized by providing 10 percent more supply air than the sum of return and exhaust air.

15. Increase E.S.P. estimate by 10 percent to allow for contractor's field condition modifications to contract documents.

H. Acoustical Considerations.

1. Include passive measures to reduce noise transmitted to occupied spaces and areas,

since fiberglass, duct liners, and internal insulation are not allowed in contact with airstreams

2. The spectrum shape of the background noise shall approximate the appropriate ASHRAE Room Criteria (RC) curve over at least 3 contiguous octave bands without exceeding the limits defined by the specified RC curve, + 2 dB. The following limits shall be maintained:

a. Corridors and cafeteria: RC 40. b. Classrooms and offices: RC 35. c. Media center and music rooms: RC 30.

3. Evaluate systems and building components to comply with criteria. 4. Required design methods for reduction of sound transmitted by the HVAC system

to occupied spaces shall be according to 1991 ASHRAE Handbook, Applications, Chapter 42 recommendations and as follows:

a. Do not install air-conditioning equipment in equipment rooms with noisier

equipment. Do not locate air-handling unit (AHU) room near noise sensitive areas.

b. Provide AHU fans with internal isolators. Duct connections shall be by means of flexible connections. AHU or filter unit casing shall be isolated from structure by means of either rubber pads or spring isolators as required.

c. Select air-handling equipment for lowest practical sound generation and fan speeds. Show manufacturer's sound ratings of selected equipment in equipment schedules.

d. Use flexible duct connectors to diffusers, grilles, and other air distribution devices.

e. Make first duct branch connection or outlet location at a distance according to ASHRAE acoustical considerations from the air-handling unit, VAV boxes, or changes in direction.

f. Use ASHRAE and SMACNA recommended, not maximum allowed, velocities in duct systems and at air distribution devices to minimize air noise generation.

Page 50: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 50 Issued Design Criteria M-DCPS

1) Use of higher velocities require written M-DCPS acceptance on a per

condition basis. 2) Pressure loss through sheet metal duct downstream of any VAV box shall

not exceed 0.08" of water per 100 feet or 1" total pressure. 3) Use double thickness turning vanes at supply or return air

square/rectangular ducts changes in direction. 4) Low Velocity - 0.08 inches per 100 feet pressure drop max with maximum

velocity at 1,300 fpm. 5) Medium Velocity - 0.3 inches per 100 feet pressure drop max with

maximum velocity at 2,200 fpm.

g. Seal wall openings around duct perimeter and provide external acoustical treatment when penetrating equipment room walls to reduce any sound transmission via the duct or opening.

h. Provide spring or rubber mounts as required under vibrating pieces of equipment not factory isolated and provide flexible piping connections to them.

i. Install duct and piping at air-handling unit rooms using spring isolators. j. Install piping at chiller room using spring isolators. k. The sound generated by any outside chiller, air-cooled chiller condenser, or

cooling tower shall not exceed 70 dbA at a distance of 30 feet.

1) A sound barrier wall with chainlink and a 3 sided masonry wall shall surround the above equipment if 70 dBA is exceeded. See Division 2 for additional fencing requirements.

2) The masonry wall height shall be as tall as the top of the fan deck. 3) Locate equipment as far as possible from school buildings as well as

adjacent off-site construction.

l. Follow industry's recommended or required good engineering practices and standards.

I. Pumping And Piping Systems.

1. Provide manual chiller bypass piping when minimum chiller flow is within 10

percent of system demand. Provide control and isolation valves necessary to allow operation of any chiller with any chilled or condenser water pump and cooling tower.

2. Chilled water piping systems shall be ASTM A-53 Grade A or B, schedule 40, seamless, black steel pipe of domestic manufacture.

a. Piping 2-1/2" and larger shall be welded with flanges used for valves and other

similar appurtenances requiring disassembly for servicing. b. Piping less than 2-1/2" shall be screwed with unions instead of flanges.

Page 51: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 51 Issued Design Criteria M-DCPS

c. Victaulic or similar couplings are accepted for interior aboveground use. d. Condenser water piping may be same as for chilled water piping or may be

PVC. e. Determine friction drop values and velocity values using the Williams and

Hazen formula with C = 100 for "aged pipe". f. Size piping with diameters larger than 2 inches at friction loss equal to 4 feet

water head pressure loss per 100 feet of pipe. Steel pipe velocities shall not exceed 8 feet per second.

1) Size piping with diameters 2 inches or less at to not exceed 4 feet per

second. 2) Evaporator and condenser coil water velocities shall not exceed 9.0 feet per

second. Use an evaporator fouling factor of 0.0001 and a condenser fouling factor of 0.00025.

3) Provide isolated flanged connections for access and connection of relocatable chillers and relocatable cooling towers at single installations.

3. Pressure test all piping after installation. 4. Provide necessary accessories at both ends of each piece of equipment, such as flow

meters, isolation valves, balancing valves, control valves, flanges or unions, valved pressure gage wells, temperature wells, strainers, valved drains and air vents, dielectric fittings, and all other appurtenances necessary for balancing and maintaining the water side.

a. Major pieces of equipment shall be provided with permanent temperature and

pressure gauges. b. Smaller balancing valves may be circuit setter type with memory stops.

5. Balancing valves 2 inches and smaller shall be plug type equipped with memory

stop. Balancing valves 2-1/2" and larger shall be butterfly type equipped with memory stop. Ball valves are not allowed for use as balancing valves. Full ported ball valves are allowed as shutoff valves for sizes 2 inches and smaller.

6. Provide eccentric reducers at pumps suction and concentric at discharge. Provide non-slam check valves on discharge and strainers with blow-off at suction. Suction piping at pumps shall be designed for ease of priming and low net positive suction head (NPSH). Piping creating a high point at the suction side of the pump shall not be provided.

7. Provide spring or rubber mounts as required and flexible piping vibration isolators, placed in the horizontal position at all vibrating pieces of equipment.

8. Run horizontal piping above the ceiling space as high as possible or in unfinished areas and following the building lines. Underground piping shall be installed in landscaped or asphalted areas not scheduled for future construction. Pressure piping is not allowed under a slab on grade. Runs under courtyards or sidewalks require M-DCPS acceptance on a per condition basis.

Page 52: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 52 Issued Design Criteria M-DCPS

9. Isolate aboveground and underground piping systems with valves at branches 2 inches and larger.

10. Piping shall be suitably supported and allow for expansion and contraction of the installed piping, including surrounding insulation. Loops and anchors shall be provided, if necessary. Assume installation temperature to be 92 degrees F. dry bulb.

11. Vertical piping shall be installed in architecturally finished chases or in unfinished areas such as mechanical rooms. Walls shall not be channeled for installation of piping.

12. Provide automatic vents with shut-off valves at all chilled water piping high points where air will accumulate and not just the single highest point in the loop.

13. Provide spring hangers for piping inside air-handling unit rooms and in the chiller area.

14. Piping drops to chiller and pumps shall be supported from the floor and have floor vibration isolation. Piping drops to air-handling units shall be supported within one foot of the horizontal elbow before the drop.

15. Extraneous piping or equipment shall not be installed inside electrical rooms. 16. With 2 or more chillers, provide dedicated identical parallel chilled or condenser

water pumps, each having 100 percent of its chiller or compressor water capacity interlocked with its chiller or compressor.

a. Pump's operational points shall be selected so single pump operation shall allow

a minimum of 80 percent of the two chiller's maximum required flow. b. Provide a system friction curve and pump operating curves. c. Operating points with a single operational pump and with all pumps operating in

parallel shall be indicated in the curves. d. Pump motor shall be non-overloading at all curve points. e. Provide interlocked motorized butterfly valves to prevent chilled water flows

through any unused chiller. f. Variable speed drives may be used for installations larger than 10 horsepower.

17. Chilled water or condensing water pumps at independent chillers shall be piped to

allow either pump to be manually set to serve either chiller. 18. Provide pedestal mounted end suction pumps with mechanical seals and flexible

couplings or for large systems, horizontal split case, double suction pumps. 19. Bolt pumps directly to a concrete slab or an inertia anti-vibration base according to

this division. 20. Provide horizontal flexible piping connections. 21. Show on pump schedule, service, gpm, total dynamic head in feet of water, type of

pump, motor horsepower, phase, volts, motor efficiency, and RPM. 22. Pumps shall be bronze fitted. 23. Specifications shall include impeller and trim information complying with

Hydraulic Institute guidelines. 24. Provide a chemical feeder that serves the common system.

Page 53: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 53 Issued Design Criteria M-DCPS

25. Provide a gate valve, strainer, and eccentric reducer at suction side of each pump. 26. Provide a concentric reducer, check valve and a balancing cock on the discharge

side of each pump. 27. Pumps with flanges shall be drilled and tapped for gages. 28. Provide 2 parallel condenser water pumps with equal requirements listed for chilled

water pumps and the following:

a. Size piping using the Williams and Hazen formula with C = 100 for "aged pipe" to allow for corrosion.

b. Provide positive head at pump suctions by increasing tower height or increasing suction pipe size.

c. Verify required NPSH versus available.

29. Equipment installations shall comply with M-DCPS water treatment requirements. See Design Criteria Appendix - Water Treatment.

30. Pressure lines shall not be embedded in concrete slabs or below interior slabs on fill.

J. Pipe Insulation.

1. Chilled water piping shall be insulated using the thicknesses and materials as follows:

a. Interior Aboveground: Provide foamed plastic inserts every 40 feet and at

changes of direction with cellular glass insulation.

1) 1" and smaller: 1" foamed plastic. 2) 1-1/4" to 2": 1-1/2" cellular glass. 3) 2-1/2" to 6": 2" cellular glass. 4) 8" and larger: 2-1/2"cellular glass.

b. Exterior Aboveground: Increase interior aboveground insulation by one size. c. Exterior Underground:

1) 2" thick cellular glass: With expansion and contraction controls as needed. 2) All sizes: Urethane preinsulated piping system, with factory recommended

thicknesses and consisting of seamless black steel ASTM A-53 Grade B pipe, Schedule 40, with foamed-in-place closed cell polyurethane insulation and ASTM D-1784 outer jacket. Seal ends and couplings. Seal and protect piping and insulation against moisture intrusion during and beyond installation. Provide concrete anchors at elbows.

2. Provide jacketing for insulated pipe as follows:

a. Exterior Aboveground Jacketing: Finish with 0.016" thick sealed, aluminum

Page 54: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 54 Issued Design Criteria M-DCPS

Jacket, continuous over pipe, valves, and fittings. b. Exterior Underground Jacketing:

1) For all sizes of urethane piping, use PVC jacketing provided with

preinsulated pipe. 2) For all sizes of cellular glass piping, use factory applied jacket with field

installed joints.

c. Interior Aboveground Jacketing:

1) Concealed: Provide factory applied all service jacket (ASJ). 2) Exposed: In AHU rooms provide field applied fab and mastic finish

consisting of 10 x 10 glass fabric embedded in two coats of white breather weather barrier mastic.

3. Note on drawings the interior or exterior designation of piping installed at areas

subject to different interpretations.

a. Define interior and exterior design conditions and locations in contract documents to include interior corridor ceilings, exterior or walkway concealed overhangs, and other similar areas.

4. Fiberglass is not allowed for chilled water or similar cold piping insulation.

K. Equipment Selection.

1. Outdoor Air.

a. Locate outdoor air intakes on the upstream side, based on prevailing summer

southeast wind direction, of exhaust openings and separated by:

1) 10 feet minimum from kitchen exhausts and plumbing vents through roofs. 2) 25 feet minimum from process exhaust. 3) 36 inches minimum from the finished roof deck.

b. Intakes shall not exceed 550 fpm velocity through the net louver area at 100

percent fresh air to minimize noise pressure drops and rain carry over. c. At equipment rooms, provide ductwork from the outside air intake and return air

to the air-handling unit. Provide minimum of one floor drain next to air-handling units in each equipment room.

2. Air Filters.

a. Provide 4 inch thick throw-away type air filters with reusable metal frames at

Page 55: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 55 Issued Design Criteria M-DCPS

air-handling units.

3. Air-handling Units and Outside Air Supply Fans.

a. Air-handling units shall be floor mounted. Air-handling units supported from ceilings or roof structures or accessed by climbing over any equipment are not allowed.

b. Air-handling units shall be provided with manufacturer�s recommended access area fronting required maintenance areas and removable panels for maintenance access.

1) Show by dotted lines on drawings the clear space allotted for coil pull out. 2) Do not drop chilled water piping to AHU inside the coil pull out area,

c. Provide each AHU in a VAV system with a ducted outside air supply fan and

downstream VAV box to maintain a constant outside air supply throughout the full range of operation.

d. Air-handling units assembled with filter banks, coils, cabinet fans, plenums, and dampers shall be draw-through type with suction side coils.

e. Air-handling units shall be double wall construction. f. Condensate drain pans shall have slopes, drains, curb heights, and other indoor

air quality design features. g. Provide one of the following fan designs:

1) Non-overloading backward curved blade design selected on a stable point

of operation of the fan curve. 2) Forward curved fans for use in VAV systems.

h. Select fan motor sizes and speeds to provide an economical belt drive. i. Provide hot-dipped galvanized cabinets, fan wheel assemblies, and structural

supports. j. Provide fans with internal factory mounted vibration isolation. If factory

internal isolation is not available, provide field installed external floor mounted vibration isolation with adequate structural rigidity as follows:

1) Cabinet fans, centrifugal fans, and packaged air-conditioning units with fan

wheel diameters of less than 15 inches shall be hung or mounted using rubber-in-shear or spring mounted isolators.

2) Units with fan wheel diameters of 15 to 24 inches shall be mounted on spring isolator rails.

3) Units with fan wheel diameters over 24 inches shall be mounted on a concrete inertia base with spring isolators.

4) Units located on a slab with factory mounted internal vibration isolation do not need duplicate external vibration isolation.

Page 56: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 56 Issued Design Criteria M-DCPS

k. Select the proper fans for the required operating conditions, economical

operation and to minimize fan noise.

4. Coils.

a. Schedule heating and cooling coils on the appropriate drawings to include:

1) Service required. 2) Cubic feet of air per minute. 3) Maximum face velocity. 4) Maximum allowable air friction loss. 5) Entering and exiting air dry bulb and wet bulb temperature of heating and

cooling medium. 6) GPM. 7) Maximum pressure drop. 8) Minimum number of rows. See this division for indoor air quality and

outside air requirements. 9) Sensible heat ratio.

b. Any AHU otherwise meeting requirements for not being provided with a

dedicated outside air coil or preconditioned air, and having a sensible heat ratio of 0.70 or below, shall be provided with heat pipes or other M-DCPS accepted energy efficient re-heat method to maintain interior design conditions.

c. Cooling coils shall be designed for 45 degrees F. entering chilled water temperature and 55-57 degree F. leaving chilled water temperature. Higher temperature drops require M-DCPS written approval.

d. Air supply from chilled water coils shall be approximately 55 degrees F. e. Base direct expansion and chilled water cooling units use on a maximum of 500

fpm face velocity for the calculated quantity of air passing through the coil. f. Chilled water or refrigerant shall flow opposite to airflow with flow entrance at

the downstream airside of coil for flow through the rows, for the most efficient head transfer. Flow shall also enter at the bottom of coils and exit through the top connection to relieve possible air binding.

g. Provide the following for chilled water coil use:

1) Piping system with 3-way mixing valves capable of bypassing the coil upon reaching desired temperature. Variable speed pumps for flow controls and 2-way valves may be accepted by M-DCPS on a per condition basis.

2) Air vents at the top of the return riser. 3) Gate valves on the supply side of coil section. 4) Flow indicating balancing type lubricated plug valves with memory stops

on the return side of coil section. Ball valves are not acceptable for balancing.

Page 57: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 57 Issued Design Criteria M-DCPS

5) Thermometers as required by specifications. 6) Pressure gauges with 1/2" bottom connections, shut-off cocks, and

vibration snubbers. 7) 3/4" globe valve drain at system low point connected to a floor drain. 8) Water strainer upstream of control valve and gate, butterfly, or ball valves

in the main chilled water supply and return for shut-off and repair of control valve.

9) Diagrams showing airflow direction through coils. 10) Coil size based on a 10 to 12 degrees F. water temperature rise except

thermal storage or low temperature air requirements of a special system design.

11) Coil selection based on a 1 to 2 degrees F. higher supply water temperature than chiller set point capacity, but not higher than 45 degrees F.

12) Three-way valve sizes shall not be less than 1 size smaller than the coil�s size. Reduce piping at the 3-way valve, and increase immediately thereafter to reduce again at the coil. 3-way valve pressure drop shall not exceed 50 percent of the pressure drop of the branch or coil.

h. Provide the following for direct expansion coil use:

1) Life cycle cost analysis demonstrating worthwhile savings when compared

to chilled water systems. 2) Maximum steps of capacity controlled by solenoid valves if justified by

energy savings. 3) Individual suction risers with oil traps. 4) Stop valves, strainers, solenoid valves, and external equalizing thermal

expansion valves at liquid lines. 5) Sight glasses installed upstream of thermal expansion valves to observe

premature flashing conditions. 6) One row added to required row depth of cooling coils to allow for reduced

coil performance due to unequal air velocities through the coil, damage to coil fins, or dirt collection at coil fins.

i. Chillers shall be provided with manufacturer�s recommended access area

fronting required maintenance areas and removable panels for maintenance access.

1) Show by dotted lines on floor plans the clear space allotted for coil pull

out.

j. Heating coils shall be selected using standard guidelines. k. Provide manufacturer's recommended protective coating for exposed condenser

coils with a 5 year replacement warranty. l. Condenser coils shall be coated aluminum fins mechanically bonded to copper

Page 58: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 58 Issued Design Criteria M-DCPS

tubes. Evaporators shall receive copper tubes and aluminum fins.

1) Air-cooled condenser coils, sized for 2 tons and larger, shall have fins protected with a heresite or epoxy coating providing an extended fin life. Black fin coating or polycoat is not allowed.

m. Provide 10 fins maximum per inch at evaporator coils

5. Air Duct Design.

a. Supply, return, and outside air shall be ducted. Return or outside air plenums are

not allowed. Ductwork shall not be installed on outside walls or roofs of the building.

b. Ductwork shall be galvanized steel designed and constructed according to required or recommended SMACNA standards.

1) At all pressure classifications, seal seams at supply, return, exhaust, and

outside air ducts according to SMACNA Seal Class A using an accepted sealant.

2) Pressure indicating flags as required by SMACNA shall be used in the drawings.

3) Duct tape shall not be used as a sealant.

c. Use velocities and pressure drops as noted. d. Fiberglass liners are not allowed. See Acoustical Considerations, this division. e. Make all turns less than 6 inches with radius elbows. Rectangular elbows with

double thickness turning vanes may be used for ducts having both dimensions greater than 6 inches.

f. Provide opposed blade dampers at outlets and provide volume dampers for duct branches not having VAV boxes to allow for proper air balancing.

1) Dampers shall be stable under operating conditions. 2) Dampers shall be supplied with extensions to properly clear the 2 inch

thick insulation and be supplied with memory stops. 3) Provide medium duty quadrants. 4) Dampers at air-handling unit rooms, outlets, and branch ducts where the

total static pressure is more than 0.5 inches or with any dimension over 18 inches shall be opposed blade.

5) Damper stems shall be installed parallel to the duct run. 6) Splitter dampers are not allowed. 7) Provide access door for large opposed blade dampers.

g. Supply and return ductwork shall be sealed and insulated with 2 inch thick, 1-

1/2 pound density, or 2.2 inch 3/4 pound density, ductwrap blanket fiberglass

Page 59: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 59 Issued Design Criteria M-DCPS

insulation.

1) Provide kraft paper vapor barrier on the outside. 2) Insulation in mechanical or air-handling unit rooms shall be 2" thick

fiberglass board type 3 pound density finished with 10 x 10 glass fabric embedded in 2 coats of white breather weather barrier mastic.

3) Insulation shall be sealed to form a continuous vapor barrier to prevent moisture intrusion and condensation.

h. Branches shall not be designed or installed with extractors.

1) For rectangular ducts, provide for 45 degree entry tee according to Figure

N. Page 14.37 of the SMACNA HVAC Systems Duct Design 1990 - Third Edition.

2) For round ducts, or rectangular to round ducts, provide 45 degree conical wye similar to Figures J. & L. Page 14.36 of the SMACNA HVAC Systems Duct Design 1990 - Third Edition.

i. Design duct system for accessibility and ease of maintenance and balancing.

1) Provide adequate access doors to each damper and balancing device. 2) Access doors shall be hinged type with locking handle. 3) Access plates with sheet metal screws, or any access requiring disassembly

are not allowed.

j. Provide access doors for fire and balancing dampers only located in the bottom of the duct.

1) Recommended or required NFPA 90A sizing and accessibility

requirements shall be followed. 2) Access doors are required for fire dampers connected to flexible duct

connectors. 3) No accessibility claim shall be made for disconnection of flexible duct.

k. Mechanical equipment rooms are not required to have fire rated construction,

unless adjacent to fire rated conditions. There are no fire damper requirements for ductwork penetrating these walls, unless the walls, floor, or ceiling are required to be fire rated.

l. Fire dampers are required for ductwork penetrating fire rated assemblies. m. HVAC ductwork for M-DCPS projects, including portable classrooms, shall be

non-combustible metal. Solid metal shall separate insulation and vapor barriers from airstreams.

n. Ductwork shall be designed, fabricated, and installed to comply with ASHRAE and SMACNA recommended and not maximum allowed requirements.

Page 60: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 60 Issued Design Criteria M-DCPS

o. Fiberglass ductboard is not allowed and exposed, painted, or coated fiberglass is not allowed in contact with airstreams.

p. Provide round ductwork whenever possible. q. Rectangular ductwork velocities shall be less than 2200 feet per minute for

classrooms and administrative areas and less than 1000 feet per minute for media centers and auditoriums. Higher velocities require written M-DCPS acceptance on a per condition basis.

r. Size conditioned air ductwork using maximum recommended velocities, not maximum allowed velocities, according to SMACNA and ASHRAE. Design using a full one inch pressure drop from VAV box to supply air outlet.

s. Use minimum recommended velocity for TV studios, media centers, and other sound sensitive areas.

t. Comply with required room noise criteria curve requirements and provide means of sound reducing methods while maintaining a solid metal duct interior. See ASHRAE for additional guidelines. Electronic measures for sound wave cancellation are allowed.

u. Locate flags by SMACNA recommendations at pressure changes in ductwork to allow for economical duct fabrication.

v. Limit distances to 10 feet for flexible ducts. Avoid crimping and if necessary where space is limited provide a sheet metal elbow at the register.

w. Provide fire dampers in supply ductwork as required by NFPA 90A and SREF at the following, but not limited to, locations:

1) Vertical shafts. 2) Public corridors. 3) Exits. 4) Stairways. 5) Fire rated ceilings. 6) Penetrations through fire rated walls.

x. Locate fire damper access doors at the bottom of the ductwork for easy access. y. Design duct insulation to comply with SREF and FEEC, and to avoid

condensation. Provide minimum R-6 value. z. Ductwork shall be insulated except as follows:

1) Exhaust air ductwork. 2) Outside air ductwork, except the first 5 feet from the return air connection

shall be insulated.

aa. Ductwork located in mechanical equipment rooms and above ceilings shall be insulated and shall not be considered installed in air-conditioned spaces.

bb. Do not use exposed ductwork in student occupied spaces unless accepted by M-DCPS on a per condition basis.

cc. Provide accessible access doors in bottom of ductwork for maintenance of fire

Page 61: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 61 Issued Design Criteria M-DCPS

dampers and opposed blade dampers. dd. Provide opposed blade dampers at:

1) Air-handling rooms. 2) Dampers with a dimension greater than 18 inches. 3) Branches with a total pressure drop of more than 0.5". 4) Supply air outlets.

ee. Specify dampers with adequate extensions to avoid insulation compression and

maintain a depth of at least 2 inches of insulation.

6. Air Distribution Devices.

a. Select ductwork, devices, and insulation to reduce or eliminate entrained particles in supply air stream.

1) Exposed, painted or coated fiberglass shall not be in air streams.

b. Use accepted design practices to select supply grilles and diffusers to provide

adequate air distribution for an adequate learning environment. Coordinate grilles and diffusers locations with the lighting layout.

c. Registers serving VAV systems shall be limited to a maximum of 350 cfm each unless accepted in writing by M-DCPS on a per condition basis.

d. The use of perforated type diffusers is not allowed in VAV systems. Use louvered type.

e. Diffusers shall be sized 2' x 2' whenever a lay-in type ceiling is used.

7. Return and Exhaust Air.

a. Ductwork and Plenums:

1) Return air and make-up air shall be ducted to air-handling units. Size return ducts and shafts for a maximum 2200 feet per minute velocity.

2) Provide angle iron reinforcing midway between standing seams to prevent buckling due to negative pressure, at fan inlet side ducts over 150 feet long and with a dimension over 24 inches.

3) Return ceiling plenums and shafts are only allowed by M-DCPS on a per condition basis and shall comply with the following:

a) Verify return ceiling plenums for cross sectional areas, limit plenum

velocities to 800 fpm and provide clearances around supply ducts and other obstructions in the plenum. Return air plenums over egress corridors are not allowed.

Page 62: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 62 Issued Design Criteria M-DCPS

b) Return ceiling plenums shall not be shared by multiple room HVAC installations.

c) Limit use of plenum return shafts and limit shaft velocities to appropriate velocities. Unducted shafts shall not be used.

4) Prevent fan noise entering rooms by using ASHRAE guidelines between

fan and returns or use electronic sound wave cancellation, if feasible. 5) Fiberglass ductboard is not allowed and exposed, painted or coated

fiberglass shall not be in air streams.

b. Provide fire dampers in return ductwork as required by NFPA 90A and SREF at the following, but not limited to, locations:

1) Openings to return air shafts. 2) Ductwork connections through vertical fire partitions. 3) Penetrations through fire rated walls with ratings over 30 minutes.

c. Registers and grilles shall be sized for a velocity of 400 fpm.

1) Assuming 80 percent return of supply air, return registers and supply

registers will be of equal sizes. 2) Provide schedule with size, manufacturer, and type of return air registers. 3) Provide insulation at registers from attics or any other non-conditioned

locations subject to high temperatures and humidities.

d. Provide blower type exhaust fans to limit use of noise generating roof exhaust fans.

1) Fans exhausting from a ceiling plenum shall not have tip speed exceed

3000 fpm and shall have an inlet sound trap unless industrial type is specified.

2) Fans exhausting from ductwork shall not have tip speed exceed 3600 fpm and shall have a section of lined duct next to the fan and be adequate for static pressures up to 1/2" w.g.

3) For static pressures above 1/2" w.g., use blower type fans. 4) If lack of room exists for blower type fan specify roof fans with a 3 inch

high minimum spun inlet cone. 5) List appropriate data at supply fan schedule.

e. Provide backdraft dampers and bird screens at exhaust fans except at systems

with carbon monoxide, range hood exhaust, or at any other exhaust systems not required by code.

f. Special exhaust fan requirements shall comply with DOE, SREF, and other applicable codes and include the following:

Page 63: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 63 Issued Design Criteria M-DCPS

1) At kitchen hoods: Provide fan shaft seal and a special insulated plate for

motor and fan separation. 2) At science lab emergency exhaust: Provide galvanized ductwork. 3) At fume hoods: Provide stainless steel ductwork and fans and housings

with chemical resistant metals, plastics, or coatings. Emergency exhaust ductwork shall be galvanized steel.

4) At kilns: Provide fans with forced vented motor compartments and high temperature resistant construction.

5) At paint spray booths: Provide fans with non-sparking wheels and drives and explosion-proof motors.

6) At dust and sawdust collection systems:

a) Provide material handling fans and equipment with self-cleaning air-pulse filters.

b) Locate equipment in mechanical rooms or provide security fencing if at an exterior location.

c) Shaker type self-cleaning baghouse filters are not allowed. d) Do not connect collection systems to air-handlers. Exhaust to exterior

or have HEPA filtering before recirculating.

7) At clothes dryers:

a) Provide roof exhaust vents or wall exhaust vents, if not next to patios, walkways, or other circulation areas.

b) Provide full size exhaust kit for laundry dryer, complete with inline filter, flexible hose and painted metal weather resistant, wall or roof cap. Increase total exhaust run one pipe size for exhaust lengths of 16 feet to 25 feet or if more than two elbows are used. Lengths longer than 25 feet are not allowed.

8. Cooling System.

a. Refrigerant selection shall include environmental safety issues. Specify the

following M-DCPS accepted refrigerants or demonstrate benefits and costs of systems using any other regulated refrigerants:

1) HFC - 134a. 2) HCFC - 22. 3) HFC - 410A.

b. Direct expansion (DX) systems, consisting of an evaporator, a coil, a

compressor, evaporative valves, an air or water cooled condenser, accessories, and possibly a cooling tower shall not be used except for small systems.

Page 64: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 64 Issued Design Criteria M-DCPS

1) A multistage or infinitely variable compressor shall be used when

available.

c. Chilled water systems, easily adjustable for capacity control and consisting of centrifugal, screw, scroll, or reciprocating chiller compressors shall be used in the recommended load ranges in this division.

1) Provide integrated partial load performance evaluation. 2) Provide parallel flow piping.

d. Cooling Towers.

1) Cooling towers shall only be used for systems sized at 150 tons and larger.

Towers less than 150 tons may only be used for replacement of existing towers.

2) Tower manufacturer shall be a member of the Cooling Technology Institute (CTI) and tower thermal performance certified by CTI.

3) Cooling towers shall be of stainless steel construction. 4) Cooling tower sizes:

a) For 200 tons or less, use a single cooling tower. b) For 200 to 400 tons, use a multi-cell tower of two equal sized towers. c) For over 400 tons, use two equal sized towers.

5) Provide full sized flanges in the condenser water supply and return piping

between the cooling tower shut-off valves and the condenser water pump suitable for temporary emergency connection of a portable cooling tower at all single tower installations.

a) Flanged connections shall be accessible for hooking up to the hose or

temporary piping connections of the portable cooling tower.

6) The total tower capacity shall be 110 percent total of the sum of chiller net capacity plus 3,000 Btu/Ton compressor mechanical load.

a) Cooling towers rated for 200 tons or greater shall be direct drive. b) Cooling towers rated for less than 200 tons may be direct drive or belt

driven. c) Design for 79 degrees F. wet bulb conditions, 91 degrees F. dry bulb

and maximum 86 degrees F. condenser water supply to guarantee full capacity from the chiller at any wet bulb conditions and provide allowances for fouling.

Page 65: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 65 Issued Design Criteria M-DCPS

7) Install freeze protection when the heat or chilled water coil is located downstream of a direct expansion coil.

8) Cooling Tower Location:

a) Coordinate and integrate into the building design at a grade level location:

i) Locate tower at least 31 feet away from any buildings.

ii) Single flow crossflow cooling towers shall have air inlet oriented southeast, towards the prevailing summer breeze.

iii) Double flow crossflow cooling towers shall have shortest blank wall oriented southeast, towards the prevailing summer breeze.

iv) Counterflow cooling towers shall have shortest dimension oriented southeast, towards the prevailing summer breeze.

v) If cooling towers cannot be sited as described above, orient described walls towards best available summer winds at location.

vi) Fan discharge shall be at least 30 feet from any fresh air intake, including generator room.

vii) Provide tower with a louvered enclosure or a chainlink fencing and lockable gate at least 8 feet high and 10 feet away from the tower or any tower pump or accessory.

viii) Provide a separate chainlink fence under perimeter of tower to prevent storage underneath with a lockable access gate.

b) Locate away from standing water, rain water leaders, overflow

scuppers, drains, and any other possible sources of contaminants. c) Minimize noise to adjacent buildings with sound traps or distance

separation. d) Locate at least 100 feet away from parking areas to minimize staining. e) Consider leakage and windspray to minimize building staining.

9) As recommended by the cooling tower manufacturer, provide platforms

with guardrails, ladders, and safety cages necessary to access tower for equipment maintenance, unless deletion is accepted by M-DCPS on a per condition basis.

10) Connect cooling tower drain lines to the sanitary system according to DERM requirements.

11) A shut-off valve upstream of the balancing valve in single cell or multi-cell cooling towers is not required in crossflow cooling towers.

12) Painting is required for any metals not hot dipped galvanized after fabrication such as condenser water piping, domestic water piping, valving, piping supports, electrical conduits and boxes. Coordinate with Division 9 - Painting.

Page 66: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 66 Issued Design Criteria M-DCPS

e. Water Treatment (15545):

1) Provide condenser water treatment with a submerged sensor controlling bleed and chemical dosage into cooling tower water by measuring water conductivity and the following:

a) A cooling tower T.S. controller with a 0 to 90 minute timer. b) Flow controller. c) Biocide timer. d) Injection manifold. e) Chemical feed pumps. f) Bleed-off valve. g) Precleaning and cleaning of tower and chilled or hot water closed loop

systems as specified.

2) Provide chilled and heating hot water treatment with an all steel bypass pot type feeder using borate buffers and other corrosion inhibitors to prevent corrosion, scale and sludge buildup.

a) Chemical dosage treatment shall not produce a staining color to

construction in case of leakage.

3) Water treatment shall be provided for the full warranty period and not less than 1 year.

a) Review test results for approvals. b) Contact M-DCPS Facilities Operations for additional information and

see Design Criteria Appendix.

9. Heating System.

a. The following, but not limited to, equipment shall be considered for heating and as described in HVAC System Selection, this division.

1) All air VAV system with strip heaters. 2) Modified multi-zone or single zone units. 3) Strip heaters.

10. Controls.

a. Provide HVAC direct digital controls and HVAC automation according to M-

DCPS Energy/Communications requirements. b. See Operational Sequences in Division 13 for Energy Management System

(EMS) regarding lighting, HVAC and ventilation systems.

Page 67: DIVISION 15 - MECHANICAL - Miami-Dade County Public …facilities.dadeschools.net/planning/design criteria 2004... ·  · 2004-10-27DIVISION 15 - MECHANICAL ... American Society

Jan 04 Division 15 15 - 67 Issued Design Criteria M-DCPS

L. Existing School Retrofit.

1. Use of available chilled water for small air-handlers may be accepted at

instructional spaces by M-DCPS on a per condition basis.

a. Several instructional spaces may receive in order of preference, a VAV system, or constant volume system and a roof mounted unit.

b. Noise levels shall be according to acoustical consideration's paragraph in this division.

2. Instructional spaces and non-instructional areas may receive split direct expansion

or packaged DX units if chilled water is not available. Roof mounted DX package units may be used if approved on a per condition basis. DX units shall not be reverse cycle.

3. Provide heating with electric strip heaters mounted at unit, or in ducts, or at VAV boxes.

4. Non-instructional space areas shall receive central station single zone or multi-zone units with face and bypass dampers if chilled water is available. Roof mounted units shall be installed if equipment rooms are insufficient.

5. See this division for HVAC System Selection for central plant requirements. END OF DIVISION