division 18 operating controls_201212050944459666

Upload: ali-mukhtar-shigri

Post on 03-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    1/37

    UPDATELOGFORTECHNICALPROVISIONSDIVISION18

    Date Item(s)Changed Page#

    ChangeLegend:

    Added

    Strikeout

    10/1/12 TECHNICALPROVISIONS

    DIVISION18OPERATINGCONTROLS

    18.2 ProductsProduct Specifications

    18.2.1 Programmable Logic Controller (PLC) Control PanelDesign Standards

    All verbiage for the entire section 18.2.1 has been replaced with

    the following:

    Reference Attachment A, herein, titled Panel

    Design and Control Panel Component Selection

    Guide.

    ********************************************************

    18.2.2 Outdoor and Indoor RTU Enclosures

    Section 18.2.2 (Outdoor and Indoor RTU Enclosures) has beendeleted in its entirety.

    ***************************************************

    The following section has been renumbered:

    18.2.32 Instrumentation Equipment Specifications

    ***************************************************

    The following section has been renamed:

    18.3.2 Enclosure Signal and Control Circuit Wiring

    187

    187

    189

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    2/37

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    3/37

    [10/12]

    18-2

    8. National Electrical Code (NEC)

    9. Insulated Cable Engineers Association (ICEA)10. Local power and telephone companies

    11. Local authorities having jurisdiction over the work

    Where the requirements set forth in these specifications or on the drawings are greater or more rigidthan the mandatory requirements referenced above, the applicable specifications or drawings shall

    govern.

    In the case of conflict between any mandatory requirements and specifications or drawings, the

    mandatory requirements shall be followed in each case, but only after submitting such proposed

    changes to the Owner for approval.

    Nothing contained in these specifications or shown on the drawings will be so construed to conflict

    with any national, state, municipal, or local laws or regulations governing the installation of work

    specified herein, and all such acts, ordinances, and regulations, including the National Electrical

    Code, are hereby incorporated and made a part of these specifications. All such requirements willbe satisfied by the Contractor at no additional expense to the Owner.

    The drawings and specifications are complimentary to each other; what is called for by one shall be

    as binding as if called for by both. If a conflict between drawings and specifications is discovered,

    this shall be referred to the Owner as soon as possible for resolution. Should a conflict existbetween the drawings, specifications, and/or mandatory requirements (i.e., codes, ordinances, etc.),

    it will be assumed that the more expensive method has been estimated, unless such alternate has

    been agreed to prior to submission of bids.

    18.1.5 Contractor Submittals

    Shop Drawings: It is incumbent upon the Contractor to coordinate the work specified in these

    Sections so that a complete instrumentation, computer, and control system for the facility will be

    provided and will be supported by accurate shop and record drawings including an electronicversion in AutoCad, Landdesk Version 2005. Interface between existing instruments, existing

    control panels, motor control centers, starters, control valves, flowmeters, chemical feeders, and

    other equipment related to the instrumentation, control, and SCADA system shall be included in theshop drawing submittal.

    In these Contract Documents all systems, meters, instruments, and other elements are representedschematically and are designated by numbers, as derived from criteria in Instrument Society of

    America Standard ANSI/ISA S5.1. The nomenclature and numbers designated herein and on the

    drawings shall be employed exclusively throughout shop drawings, data sheets, and similarmaterials. Any other symbols, designations, and nomenclature unique to the manufacturer's

    standard methods shall not replace those prescribed above, used herein, and on the drawings.

    Should an error be found in a shop drawing during installation or start-up of equipment, thecorrection, including any field changes found necessary, shall be noted on the drawing and

    submitted finally "as-built" prior to acceptance of the project.

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    4/37

    [10/12]

    18-3

    Analog and SCADA System Hardware: This submittal shall be included in a singular, all-inclusive

    submittal which shall include but not be limited to:

    1. A complete index appearing in the front of each bound submittal volume. System

    groups shall be separated by labeled tags.

    2. A complete system block diagram.

    3. Loop Diagrams: Drawings showing definitive diagrams for every instrumentationloop system: These diagrams shall show and identify each component of each loop

    or system using method, legend, and symbols from ANSI/ISA S5.4, extending the

    format of ANSI/ISA S5.1 The loop diagram shall also show the spare loops and/orspare I/O.

    4. Loop description and/or facility operations descriptions.

    5. Installation, mounting, and anchoring details for all components and assemblies,including access requirements and conduit connection or entry details.

    6. Panel wiring and/or diagrams shall be prepared and the field wiring integrated. They

    shall include the following information:

    a. Name of panel

    b. Wiring and piping sizes and types

    c. Functional name and manufacturer's designation for items to which wiringand piping are connected

    d. Terminal strip numbers

    e. Electrical control schematics in accordance with ANSI standards

    7. Field wiring and piping diagrams shall be prepared and be integrated with the panelwiring diagram. They shall include the following information:

    a. Wiring and piping sizes and typesb. Conduits in which wiring is to be located

    c. Panel (e.g. RTUs, etc.) termination strip numbers

    d. Location, function name, and manufacturer's designation of items to whichwiring and piping are connected

    8. Drawings showing schematic diagrams for control circuits. Complete details on the

    circuit interrelationship of all devices within and outside each Control Panel shall besubmitted using schematic control diagrams. The diagrams shall show numbered

    terminals on components together with the unique number of the wire to be

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    5/37

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    6/37

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    7/37

    [10/12]

    18-6

    complete system calibration. Calibration shall be in accordance with subsection entitled

    "Calibration, Testing, and Start-up" under the "EXECUTION" portion of this specification section.

    Field Tests: The Contractors attention is directed to the article "EXECUTION" of this Sectionwhich delineates all the tests that are required to be performed in the field in order to demonstrate

    compliance with the Contract Documents.

    18.1.7 Storage and Handling

    All equipment and materials delivered to the job site shall be stored in a location which will not

    interfere with the operations of other contractors or the Owner. Storage and handling will beperformed in a manner that will afford maximum protection to the equipment and the materials. It

    is the Contractors responsibility to assure proper handling and on-site storage of instrumentation

    and control equipment in accordance with the System Supplier's recommendations.

    18.1.8 Environmental Conditions

    The instrumentation, controls, and SCADA systems shall be designed and constructed forsatisfactory operation and long, low maintenance service under the following environmental

    conditions:

    1. Central Computer System:

    a. Temperature range: 10 through 40 Celsius (50 through 104 Fahrenheit).

    b. Thermal shock: 0.55 Celsius (1.0 Fahrenheit) per minute maximumc. Relative humidity: 20% through 80% (non-condensing)

    2. Remote Site Equipment:

    a. Ambient temperature range: -18 through 60 Celsius (0 through 140

    Fahrenheit)b. Thermal shock: 1.0 Celsius. (1.8 Fahrenheit) per minute maximumc. Relative humidity: 100% maximum

    18.1.9 Service Requirements

    The Contractor shall provide jobsite visits and services of a manufacturer's technical field

    representative for calibration, testing, and startup of the following items.

    1. Level Transmitters2. Pressure Transmitters

    3. Chemical Analyzers and Feeders

    4. Flow Transmitters

    At no separate additional cost to the Owner, the Contractor shall include the following services of

    qualified technical representatives of the System Supplier (see Installation, Calibration, Testing, andStart-up herein):

    1. Supervise installation and connection of all instruments, elements, and componentsof every system, including connection of instrument signals to primary measurement

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    8/37

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    9/37

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    10/37

    [10/12]

    18-9

    Installation and Connection: The Contractor shall install and connect all field-mounted components

    and assemblies under the criteria imposed by these specifications and the System Supplier. Theinstallation personnel shall be provided with a final reviewed copy of the shop drawings and data.

    In building interior locations, conduits shall be surface-mounted on walls or ceilings wherever

    possible, and run parallel to building lines. Conduits shall not be routed on floors in areas subject to

    foot traffic. In exterior locations conduit shall be routed below grade. Where concrete or asphaltslabs exist, they shall be sawcut, conduits installed, and the cut repaired to original condition.

    Exposed conduits and/or raceway shall be installed perpendicular or parallel to building lines.

    Signal and low voltage wiring shall be run separately from power and 120-volt control wiring. All

    analog signal loops shall be fused.

    Bends shall be formed with proper tool and to uniform radii and shall be made without deforming or

    thinning the walls of the tubing. Plastic clips shall be used to hold individual plastic tubes parallel.

    Ends of tubing shall be square-cut and cleaned before being inserted in the fittings. Bulkheadfittings shall be provided at all panels requiring pipe and/or tubing entries.

    The Contractor shall have a technical field representative of the System Supplier instruct installationpersonnel on any and all installation requirements; thereafter, the technical field representative shall

    be readily available by telephone to answer questions and supply clarification when needed by theinstallation personnel.

    Final Checks: After all installation and connection work has been completed, the technical fieldrepresentative shall check it all for correctness, verifying polarity of electric power and signal

    connections, and all other similar details. The technical field representative shall certify in writing

    to the Contractor that for each loop or system checked out, all discrepancies have been corrected bythe installation personnel.

    Removal of Abandoned Equipment: All existing instrument and control equipment that is no longer

    required after the new system has been put into service shall be removed and delivered to the Ownerby the Contractor.

    18.3.2 Control Circuit Wiring

    Wiring Installation: All wires shall be run in plastic wireways except field wiring, wiring run

    between mating blocks in adjacent sections, wiring run from components on a swing-out panel to

    components on a part of the fixed structure, and wiring run to front panel-mounted components.Wiring run from components on a swing-out of front panel to other components on a fixed panel

    shall be made up in tied bundles. These bundles shall be tied with nylon wire ties and shall be

    secured to panels at both sides of the "hinged loop" so that conductors are not strained at theterminals. Signal and low voltage wiring shall be run separately from power and 120 volts control

    wiring.

    Wiring run to control devices on the front panels shall be tied together at short intervals with nylonwire ties and secured to the inside face of the panel using adhesive mounts with screws.

    Wiring to rear terminals on panel-mount instruments shall be run in plastic wireways secured tohorizontal brackets run above or below the instruments in about the same plane as the rear of the

    instruments.

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    11/37

    [10/12]

    18-10

    Conformance to the above wiring installation requirements shall be reflected by details shown on

    the shop drawings for the Owners review.

    Wire marking: Each signal, control, alarm, and indicating conductor connected to a given electricalpoint shall be designated by a single unique number which shall be shown on all shop drawings.

    These numbers shall be marked on all conductors at every terminal using white numbered wire

    markers which shall be plastic-coated cloth covered with clear heat shrink tubing or permanentlymarked heat-shrink plastic and must be durable, smudge and fade resistant.

    18.3.3 RTU I/O Configuration

    Listed References: A list of the I/O requirements (including used, future signals, and implemented

    spares) for each RTU is provided through the database list of the existing Central Computer System.

    Additional Requirements: Any power supplies, signal isolators, converters, interposing relays, etc.

    that are necessary to make existing signals and equipment compatible with the I/O cards shall be

    furnished and installed as a part of this Contract.

    The input/output signals to be connected to the new RTUs shall be only the existing input/output,

    plus any new instruments furnished under this contract, unless otherwise noted.

    18.3.4 Calibration, Testing, and Start-up

    Calibration: All instruments and systems furnished by the Contractor shall be calibrated after

    installation, in conformance with the component manufacturer's instructions. This shall provide thatthose components having adjustable features are set carefully for the specific conditions and

    applications of this installation and that the components and/or systems are within the specified

    limits of accuracy. Defective elements which cannot achieve proper calibration or accuracy, eitherindividually or within a system, shall be replaced. This calibration work shall be accomplished by

    the technical field representatives of the System Supplier whom the Contractor shall require tocertify in writing that for each loop of system, all calibrations have been made and that allinstruments are ready to operate.

    Proof of Conformance: The burden of proof of conformance to specified accuracy and performance

    is on the Contractor using its designated System Supplier. The Contractor shall supply necessary

    test equipment and technical personnel if called upon to prove accuracy and/or performance, at noseparate additional cost to the Owner, wherever reasonable doubt or evidence of malfunction or

    poor performance may appear.

    Testing: All systems shall be exercised through functional and operational tests in the presence of

    the Owner in order to demonstrate achievement of the specified performance. Operational tests

    depend upon completion of work specified elsewhere in these Contract Documents. The schedulingof tests shall be coordinated by the Contractor among all parties involved so that the tests may

    proceed without delays or disruption by uncompleted work.

    Start-up: When all equipment and systems have been assessed by the Contractor to have beensuccessfully carried through complete operational tests with not less than a minimum of simulation

    and the Owner concurs in this assessment, system start-up by the Owners operating personnel can

    follow.

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    12/37

    ATTACHMENT A

    Technical Provisions Division 18

    Operating Controls

    Panel Design and Control Panel Component

    Selection Guide

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    13/37

    Page 1of 25

    Panel Design and Control Panel

    Component Selection Guide

    (ATTACHMENT A TO TECHNICAL PROVISIONSDIVISION 18, OPERATING CONTROLS)

    Document Control Panel Design and Component Selection Guide

    Revision Number 2.00

    Effective Date Oct 2nd 2012

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    14/37

    Page 2of 25

    HistoryRevis ion Date Description of Change

    1.00 08/31/2012 Initial Release

    2.00 10/2/2012 Revisions

    Contents1 Introduction ............................................................................................................................ 42 Panel Design Requirements .................................................................................................. 4

    2.1 Design Cycle .................................................................................................................. 42.2 Panel Certification .......................................................................................................... 52.3 Environmental ................................................................................................................. 52.4 Panel Wiring ................................................................................................................... 5

    2.4.1

    Spare channels ....................................................................................................... 5

    2.4.2 IO Wiring ................................................................................................................. 52.5 Grounding ....................................................................................................................... 6

    2.5.1 Ground bus .............................................................................................................. 62.5.2 Components ............................................................................................................ 62.5.3 I/O DIN rails ............................................................................................................. 6

    2.6 Component Fastening .................................................................................................... 62.6.1 Backpanel direct mounted components .................................................................. 6

    2.7 Wire Duct ........................................................................................................................ 72.8 Labels ............................................................................................................................. 7

    2.8.1 Exterior enclosure label (on door) ........................................................................... 72.8.2 Interior enclosure labels (door) ................................................................................ 72.8.3 Backpanel component labels .................................................................................. 72.8.4 Terminal block labels ............................................................................................... 82.8.5 Wire labels ............................................................................................................... 8

    2.9 Spare Components Kit ................................................................................................... 82.9.1 Spare Parts ............................................................................................................. 8

    3 Enclosure ............................................................................................................................... 93.1 Enclosure ........................................................................................................................ 93.2 Laptop Shelf (Door) ........................................................................................................ 93.3 Fan ................................................................................................................................. 93.4 Cabinet Heater ............................................................................................................. 103.5 Heater Control .............................................................................................................. 103.6 Active Cooling ............................................................................................................... 103.7 Lighting ......................................................................................................................... 103.8

    Door Stops .................................................................................................................... 11

    3.9 Intrusion Switch ............................................................................................................ 114 Panel Power Distribution ..................................................................................................... 12

    4.1 Power Supply (24VDC) ................................................................................................ 124.2 UPS Controller .............................................................................................................. 124.3 Battery .......................................................................................................................... 134.4 DC Distribution Fuse .................................................................................................... 13

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    15/37

    Page 3of 25

    4.5 Analog I/O Fuses .......................................................................................................... 134.6 Circuit Breakers (branch protection) ............................................................................. 134.7 Circuit Breakers (supplementary) ................................................................................. 14

    4.8

    Surge Suppression ....................................................................................................... 145 Terminals ............................................................................................................................. 15

    5.1 Feed-Through Terminal Blocks .................................................................................... 155.2 Fused Terminal Blocks ................................................................................................. 155.3 Grounding Terminal Blocks .......................................................................................... 15

    6 Miscellaneous Backpanel Components ............................................................................... 166.1 DC Intermediate Relay ................................................................................................. 166.2 DC Intermediate Relay Socket ..................................................................................... 166.3 AC Intermediate Relay ................................................................................................. 166.4 AC Intermediate Relay Socket ..................................................................................... 176.5 Wire Duct ...................................................................................................................... 176.6 DIN Rail Standoffs ........................................................................................................ 17

    6.7

    120VAC Convenience Receptacles ............................................................................. 176.8 Signal Isolators / Converters ........................................................................................ 17

    6.9 Panel High Temperature Switch ................................................................................... 176.10 Low Water Cutoff Relay ................................................................................................ 186.11 Grounding Bars ............................................................................................................ 18

    7 PLC Components ................................................................................................................ 197.1 Processor ..................................................................................................................... 197.2 Rack ............................................................................................................................. 197.3 PLC Rack Power Supply .............................................................................................. 197.4 Discrete Input Module ................................................................................................... 197.5 Discrete Output Module .............................................................................................. 2007.6 Analog Input Module ..................................................................................................... 20

    7.7

    Analog Output Module .................................................................................................. 207.8 I/O Module Terminal Block (DI, DO, AI, AO) ................................................................ 20

    7.9 Expansion Rack Module ............................................................................................... 207.10 Expansion I/O Cable ..................................................................................................... 207.11 Expansion Terminator .................................................................................................. 21

    8 Networking ........................................................................................................................... 228.1 Ethernet Switch ............................................................................................................ 228.2 Ethernet Cables ............................................................................................................ 22

    9 Appendix A - Wiring Requirements .................................................................................... 23310 Appendix B - Large Backpanel Layout ................................................................................ 2411 Appendix C - Large Backpanel Layout.25

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    16/37

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    17/37

    Page 5of 25

    2.2 Panel Cert ification

    Certification Required

    UL508A listing

    2.3 Environmental

    Design Element Requirement

    Expected ambient temperature range 10 118F

    Panel fan (external air) Always required (unless otherwise specified)

    Heating Always required (for humidity control)

    Internal temperature range Internal panel temperature to be maintained between 45 115F

    2.4 Panel Wiring

    All internal panel wiring is to meet the standards as described in the RanchoCalifornia Water District Project Wire Requirements table in Appendix A of thisdocument.

    Specified wire gauge represents the minimum gauge for that conductor type; allconductors shall be sized appropriately for the electrical load they serve.

    In addition to this table, use of Telefast style, flying lead, or premade I/O module

    cables is not permitted.

    2.4.1 Spare channels

    Design Element Requirement

    I/O channels Provide a minimum of 4 spare points of each I/O type, includeadditional I/O modules as needed to meet this requirement

    Pre-wiring All spare points prewired to terminal blocks

    2.4.2 IO Wiring

    Design Element Requirement

    Digital input channels All to be 24VDC wired to terminal strips (unless specified otherwise)

    Digital output channels All to be 24VDC outputs individually wired to interposing relays (unlessspecified otherwise)

    Analog input channels All to be 24VDC 4-20mA individually fused and wired to terminal strips

    Analog output channels All to be 24VDC 4-20mA individually fused and wired to terminal strips

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    18/37

    Page 6of 25

    2.5 Grounding

    2.5.1 Ground bus

    Design Element Requirement

    Ground bus Two ground bus strips will be mounted directly to backpanel, bondground bus strips together with single conductor, at one end of stripsonly, with 12AWG (green wire)

    2.5.2 Components

    Design Element Requirement

    Enclosure door(s) Ground door(s) to backpanel ground bus bar with a single conductor of12AWG (green) wire

    Back panel Provided through ground bus bars mounted to back panel

    Components Each control component to have single conductor of appropriate sizerun to ground bus, do not ground control components to back panel

    2.5.3 I/O DIN rails

    Design Element Requirement

    AI/AO, DI, DO rail All I/O DIN rails to be isolated from backpanel with insulated DIN-railstandoffs as required per section 6.6

    Grounding Each I/O rail to have a single ground terminal block, directly connectedto the ground bus with a single conductor of 14AWG (green) wire

    2.6 Component Fastening

    Design Element Requirement

    Mechanical fastening Components mounted directly to back panel (e.g. wire ductrail, groundrails, etc.), to be fastened with machine screws by drilling and tappingthe panel

    Sheet metal and self-tapping tech screws are not permitted

    2.6.1 Backpanel direct mounted components

    Design Element Requirement

    PLC Direct mount to backpanel (no DIN rail)

    Power supply Direct mount to backpanel (no DIN rail)

    UPS Direct mount to backpanel (no DIN rail)

    Convenience receptacle Direct mount to backpanel (no DIN rail)

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    19/37

    Page 7of 25

    2.7 Wire Duct

    Design Element Requirement

    Size All duct to be sized to account for I/O quantity PLC rack is capable of(including existing spare channels and PLC rack capacity)

    Duct color Gray

    Voltage separation AC and DC wiring to be segregated as much as possible, especially foranalog I/O and network cables (refer to sample drawing in Appendix B)

    2.8 Labels

    2.8.1 Exterior enclosure label (on door)

    Design Element Requirement

    Type Black plastic (background) engraved with white lettering

    Format Text in all capitals

    Contents RCWD will define required door labels on a per panel basis (e.g.enclosure name, door lights, door push buttons, etc.)

    Fastening Mechanically fastened, corrosion resistant machine screw fasteners

    Sheet metal and self-tapping tech screws are not permitted

    2.8.2 Interior enclosure labels (door)

    Design Element Requirement

    Type Thermal transfer label, Hellermann Tyton 795 material or equivalent

    Contents Short circuit rating of panel

    Panel designer contact information

    Panel fabricator contact information

    2.8.3 Backpanel component labels

    Design Element Requirement

    Type Thermal transfer label, Hellermann Tyton 795 material or equivalent

    Format Text in all capitals

    Contents All standalone electrical components or assemblies (PLC rack, terminal

    busses, etc.) to have label on backpanel adjacent to component withcomponent number listed as seen on the electrical drawings (e.g.FU215)

    Alignment All labels applied cleanly:

    No bubbles, no ink smears

    Square relative to adjacent wire duct and components

    Consistent alignment

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    20/37

    Page 8of 25

    2.8.4 Terminal block labels

    Design Element Requirement

    Type White plastic, computer printed black text, mechanically affixed to theterminal (i.e. no stickers)

    Label on each side of the terminal

    Format Text in all capitals

    Contents Wire number for the circuit passing through the terminal block

    Orientation Numerically sequential - small to large:

    From left to right for horizontally mounted terminals

    From top to bottom for vertically mounted terminals

    2.8.5 Wire labels

    Design Element Requirement

    Label type Heat shrink, computer printed black text

    Format Text in all capitals

    Label application Each control wire or cable shall be assigned a unique identificationnumber

    All conductors of the same circuit shall have the same identificationnumber

    Numerical reservations Wire numbers:

    0-99 reserved for power distribution

    100-199 reserved for digital inputs

    200-299 reserved for analog inputs300-399 reserved for digital outputs

    400-499 reserved for analog outputs

    500-599 reserved for loop isolators and converters

    Location All wire labels visible, clear of wire duct and termination

    All wire labels aligned the same distance from termination, consistentrelative to all other wire labels

    All wire labels aligned so text is facing outwards (readable)

    2.9 Spare Components Kit

    2.9.1 Spare PartsDesign Element Requirement

    Fuses Vendor shall supply:

    Six spare fuses of each size

    1 spare relay for each type used in the panel

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    21/37

    Page 9of 25

    3 Enclosure

    3.1 Enclosure Required

    Rating, indoor non-corrosive environment: NEMA-12

    Rating, outdoor non-corrosive environment: NEMA-4

    Rating, corrosive environment: NEMA-4X

    Hazardous environment: Discuss classification with District

    Material: NEMA-12 / NEMA-4: Steel, NEMA-4X Stainless Steel

    Depth: 18 minimum

    Paint: White powder coat (indoor and outdoor enclosures)

    Latching: Screw clamps around door perimeter with padlock hasp

    Door: Preference, opens from right to left relative to facing front of enclosure

    Part/Model No: Hoffman (model line not specified)

    3.2 Laptop Shelf (Door) Required

    Type: Folding,18x18workingsurface,mountedtodoor

    Part/Model No: HoffmanAASHLF1818orapprovedequivalent

    3.3 Fan Required

    Type: Fan,roundACAxial,externalfanhoodwithremovablefiltercover

    Filters: (forexternal

    vent)

    Anti

    insect

    Part/Model No: Dayton4WT44orapprovedequivalent

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    22/37

    Page 10of 25

    3.4 Cabinet Heater Required

    Type: Radiant

    Voltage: 120VACinput

    Power: Sizeforrequiredheating

    Part/Model No: PfannenbergFLHlineorapprovedequivalent

    3.5 Heater Control Required

    Type: Integrated

    humidity

    and

    temperature

    control

    Voltage: Ratedfor120VACswitching,upto8Aresistive

    Part/Model No: HammondSKTH012009orapprovedequivalent

    3.6 Active Cooling When required per heat calculations

    Type: AirConditioner

    Part/Model No: DiscusswithDistrictifairconditionerrequired

    3.7 Lighting Required

    Type: Fluorescentbulbwithintegrateddoorswitch

    Type: Nooutlet,coolwhitebulbcolor

    Voltage: 120VACinput

    Size: 18or24long,usemaximumpermittedbyenclosuresize

    Part/Model No: SaginawSCELF16D18NOorapprovedequivalent,sizedasneeded

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    23/37

    Page 11of 25

    3.8 Door Stops Required

    Type: Holdsdoor

    open

    at

    90

    degrees

    Part/Model No: HoffmanALGDSTOP2orapprovedequivalent

    3.9 Intrusion Switch Required

    Type: Mechanicalrotarymicroswitch(notaplunger)

    Type: 1NO/1NCcontacts,adjustablerollerlever

    Wiring: Circuit

    closed

    when

    door

    closed,

    24VDC

    Part/Model No: Dayton4VZD3orapprovedequivalent

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    24/37

    Page 12of 25

    4 Panel Power Distribution

    4.1 Power Supply (24VDC) Required

    Type: Nonredundant,switching,DINrailmount

    Voltage: 120VACinput,24VDCoutput

    Capacity: Sizedsuchthatsupplyisnotmorethan75%loadedwithinitialdesign

    Ripple: Lessthan50mVpp

    Features: Alarmcontact,minimum90%typicalefficiency

    Part/Model No: PulsQS5.241orapprovedequivalent,sizedforcapacityasrequired

    4.2 UPS Controller Required

    Voltage: 24VDCpowerinput,12VDCbatterycharging,24VDCoutput

    Battery size: Sizedappropriatetochargebatterysizeused

    Battery: External

    Mount: DINrail

    Features: UPSenableinput,ready,onbattery,andbatteryqualitystatuscontacts

    Enable: Enabledwhenpanelmainbreakerison

    Part/Model No: PulsUB10.241orapprovedequivalent

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    25/37

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    26/37

    Page 14of 25

    4.7 Circuit Breakers (supplementary) Required

    Type: DINrail

    mounted

    miniature,

    UL1077

    compliant

    Ratings: Dprotectivecurve,standardboxterminals(norings)

    Size: Sizedappropriatelyforload

    Part/Model No: EatonWMZSseriesorapprovedequivalent

    4.8 Surge Suppression Required

    Type: Solid

    state,

    DIN

    rail

    mounted

    Protection: LinetoNeutral,LinetoGround,NeutraltoGround

    Voltage: 120VACoperating

    Current: 20Aoperating,30,000Atotalpeaksurgeperphase

    Other ratings: 4763Hzoperatingfrequency,compressionscrewterminals

    Features: FormCcontactforremotemonitoring(OKindication)

    Part/Model No: SolarSTFE200

    10N

    or

    approved

    equivalent

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    27/37

    Page 15of 25

    5 Terminals

    5.1 Feed-Through Terminal Blocks Required

    Type: Singlelevel,screwconnection

    Ratings: 8kVsurgevoltage,41Anominalcurrent,1000Vnominalvoltage

    Part/Model No: PhoenixContactUT63044131orapprovedequivalent

    5.2 Fused Terminal Blocks Required

    Type: Singlelevel,

    for

    glass

    6.3mm

    x32mm

    fuses

    (

    x1)

    Ratings: 6kVsurgevoltage,32Anominalcurrent,600Vnominalvoltage

    Part/Model No: PhoenixContactUT6HESI3046401orapprovedequivalent

    5.3 Grounding Terminal Blocks Required

    Type: Singlelevel,screwconnection

    Ratings: 8kVsurge

    voltage,

    57

    A

    Maximum

    current

    Part/Model No: PhoenixContactUT6PE3044157orapprovedequivalent

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    28/37

    Page 16of 25

    6 Miscellaneous Backpanel Components

    6.1 DC Intermediate Relay Required

    Type: Compactpowerrelay(icecube),

    Type: withintegratedindicatinglightandsuppressiondiode

    Ratings: Coil 24VDC,Contacts DPDT,10A@30VDC/110VAC

    Ratings: 50,000,000operationsmechanicallife,500,000operationselectricallife

    Part/Model No: IDECRH2BULDDC24Vorapprovedequivalent

    6.2 DC Intermediate Relay Socket Required

    Type: StandardDINrailmount

    Ratings: M3.5screwswithcaptivewireclamp,300V,10Arating

    Part/Model No: IDECSH2B05orapprovedequivalent

    6.3 AC Intermediate RelayRequired

    Type: Compactpowerrelay(icecube),

    Type: withintegratedindicatinglight

    Ratings: Coil 120VAC,Contacts DPDT,10A@30VDC/110VAC

    Ratings: 50,000,000operationsmechanicallife,500,000operationselectricallife

    Part/Model No: IDECRH2PULAC120Vorapprovedequivalent

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    29/37

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    30/37

    Page 18of 25

    6.11 Grounding Bars Required

    Type: 12screwlugs,14AWGto4AWGwirecopperwire

    Part/Model No: SchneiderElectricPK12GTAorapprovedequivalent

    6.10 Low Water Cutoff Relay Required when needed

    Type: Series16

    solid

    state

    plug

    in

    module

    Part/Model No: Warrick16DMB1B0

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    31/37

    Page 19of 25

    7 PLC Components

    7.1 Processor Required

    Type: Nonredundant

    Features: Level2processor,4MBmemory,12MBPCMCIAcard

    Ports: (3total):1xUSB,1xModbus/Serial,1xEthernetModBus/TCP

    Part/Model No: SchneiderElectricM340,BMXP342020

    7.2 Rack Required

    Type: 8or12slotrack(8minimum)

    Part/Model No: SchneiderElectricM340,BMXXBP0800orBMXXBP1200

    7.3 PLC Rack Power Supply Required

    Type: Nonredundant

    Voltage: 24VDCinput

    Output: 16.8Wmaximum(sumof3.3VDCand24VDCrackbuses)

    Rack output: Upto8.3Wat3.3VDCtorack,upto16.8Wat24VDCtorack

    Part/Model No: SchneiderElectricM340,BMXCPS2010

    7.4 Discrete Input Module Required

    Type: 24VDC,16isolatedinputs,currentsinking,1common,3.5mAperchannel

    Part/Model No: SchneiderElectricM340,BMXDDI1602

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    32/37

    Page 20of 25

    7.5 Discrete Output Module Required

    Type: Solidstate,

    24VDC,

    16

    outputs

    protected,

    1common,

    0.5A

    per

    channel

    Part/Model No: SchneiderElectricM340,BMXDDO1602

    7.6 Analog Input Module Required

    Type: 4inputs,highlevelisolated,420mAcapable,16bitresolution

    Part/Model No: SchneiderElectricM340,BMXAMI0410

    7.7 Analog Output Module Required when AOs present

    Type: 2outputs,highlevelisolated,420mAcapable,15bitresolution

    Part/Model No: SchneiderElectricM340,BMXAMO0210

    7.8 I/O Module Terminal Block (DI, DO, AI, AO) Required

    Type: 20wayremovableterminalblock,cageclampwithcaptivescrew

    Part/Model No: SchneiderElectricM340,BMXFTB2000

    7.9 Expansion Rack Module Required when expansion racks used

    Type: M340BusXrackexpansionmodule

    Part/Model No: SchneiderElectricM340,BMXXBE1000

    7.10 Expansion I/O Cable Required when expansion racks used

    Type: BusX,angledcable,2x9waySUBDconnector

    Part/Model No: SchneiderElectricM340,BMXXBC008K

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    33/37

    Page 21of 25

    7.11 Expansion Terminator Required when expansion racks used

    Type: BusX,

    line

    terminator,

    2x9way

    SUB

    D

    connector

    Part/Model No: SchneiderElectricM340,TSXTLYEX

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    34/37

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    35/37

    Page 23of 25

    9 Appendix A Wiring Requirements

    # DESCRIPTION

    WIRETAG

    PHASE/

    CODE

    LETTER

    WIRE

    COLOR

    NONFIELD

    INSULATION

    TYPE

    (CONTROL

    PANEL

    ENCLOSURE)

    FIELD

    INSULATION

    TYPE

    MINIMUM

    AWGSIZE

    (ALL

    STRANDED

    COPPER)

    INSULATION

    CLASS

    1480/277VAC,

    3PH

    A Brown

    MTWonly

    #4and

    largerXHHW

    #6and

    smaller

    THWN

    THHN

    PerN.E.C. 600V

    B Orange

    C Yellow

    N Gray

    G Green

    2208/110OR240

    VAC,3PH

    A Black

    MTWonly

    #4and

    largerXHHW

    #6and

    smaller

    THWN

    THHN

    PerN.E.C. 600V

    BRed,orange

    ifHileg

    C Blue

    N White

    G Green

    3110/220VAC,

    1PH

    L1 Black

    MTWonlyTHWN

    THHNPerN.E.C. 600V

    L2 Red

    N White

    G Green

    4110VACswitched

    controln/a Red MTWonly 16 600V

    5Analog

    input/outputn/a Violet MTWonly 18 600V

    6Discrete

    input/outputn/a Blue MTWonly

    18600V

    7

    D/Ointerposing

    relaycontact

    outputs

    n/a Yellow MTWonly

    18

    600V

    8 +24VDCpositive +24vBrown,blue

    switchedMTWonly

    18600V

    9 24VDCnegative 24v Orange MTWonly 18 600V

    10 +12VDCpositive +12v Red MTWonly 18 600V

    11 12VDCnegative 12v Black MTWonly 18 600V

    12 Shieldedpair+ Whiteorred 18

    600V Black 18

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    36/37

    Page 24of 25

    10 Appendix B - Large Panel Layout

  • 8/11/2019 Division 18 Operating Controls_201212050944459666

    37/37

    11 Appendix C - Small Panel Layout