DNP3 User Guide REVISION 1.2
DNP3 USER GUIDE 2
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
Contents DNP3 User Guide .................................................................................................................................. 1
Introduction: DNP3 ................................................................................................................................. 3
Configuring the Frontier ......................................................................................................................... 4
General ...................................................................................................................................................... 4
Master ....................................................................................................................................................... 4
Session ...................................................................................................................................................... 6
Events ........................................................................................................................................................ 8
Default Variations ..................................................................................................................................... 8
Files ......................................................................................................................................................... 10
Using the DNP3 Profile ........................................................................................................................ 12
Profile Section Overview ......................................................................................................................... 12
Section 5.1 – Binary Input Point List ....................................................................................................... 12
System ................................................................................................................................................. 13
Scan Status .......................................................................................................................................... 13
Battery Level Points ............................................................................................................................ 13
Other Alarms ....................................................................................................................................... 13
String Level Points ............................................................................................................................... 14
Channel Level Points ........................................................................................................................... 14
Jar Electrolyte Level Points ................................................................................................................. 15
Section 5.5 – Analogue Input Point List .................................................................................................. 15
Fixed Points ......................................................................................................................................... 15
String Points ........................................................................................................................................ 16
Channel Points .................................................................................................................................... 16
DNP3 USER GUIDE 3
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
Introduction: DNP3
Each version of Frontier after 3.10.0 is enabled for DNP3 communication. To communicate with a
Frontier using DNP3, the Frontier’s interface must be configured to point back to a DNP3 server. A
Primary Master is designated and a Secondary Master can also be set up on a separate network.
This document is intended to give the user a starting point for configuring DNP3 for use with the
Frontier system to monitor their battery. There are over 5000 potential points that can be monitored
with the Frontier system. This document describes some of the more common points and is not a
complete listing of every possible point.
It is important to note that each battery being monitored will have a different Battery Design which
will affect the DNP Profile for each system. The DNP Profile should be pulled from the Frontier after
the Battery Design is complete to get a true representation of the points available on that specific
system.
DNP3 USER GUIDE 4
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
Configuring the Frontier
Frontier supports the DNP3 (Distributed Network Protocol) communication standard for sending data
to a SCADA or other data acquisition system. To access DNP3 settings, choose DNP3 in the
Settings menu.
The DNP3 configuration page showing the General tab
General
To enable the DNP3 service, toggle the checkbox next to Enable DNP3 under the General tab.
Other configuration options under General include:
• Number of concurrent masters: Select how many master stations will connect to Frontier to
retrieve data. Frontier supports 1 or 2 master stations.
• Show advanced settings: To configure any “advanced” DNP3 settings, click the Show button to
display them.
To apply any changes to settings on this page, click the Save settings button. Modifying any DNP3
settings on this page will require a restart of the device.
Master
The Master tab contains options for configuring each specific master station (Primary and/or
Secondary), such as link and IP settings.
DNP3 USER GUIDE 5
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
The description for each option can be found in the table below.
Link Settings Description
Frontier link address
(Source address)
The local or “slave” DNP3 address of Frontier. The Frontier link
address should be unique on the user’s network. The address must
be from 0 to 65519.
Master link address
(Destination address)
The DNP3 address of the master station. The address must be
between 0 and 65519.
Validate master link
address
When enabled, only a master station indicating the Master link
address (Destination) may connect.
DNP3 USER GUIDE 6
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
Enable Frontier link self-
address
When enabled, Frontier will respond to DNP3 frames with
destination address 65532. This feature can be used to simplify
commissioning and troubleshooting, allowing the Master to
discover the Frontier’s true address and configure proper link
addresses accordingly. Frontier will reply with its own Link address
IP Settings Description
IP Mode The type of IP connection to establish with a master station.
Frontier presently supports TCP mode only.
TCP listen port The port to listen on for incoming TCP requests. The port must be
from 1025 to 65535.
Accept connections from
any IP address When enabled, accept incoming connections from any IP address.
Only accept connections
from the following IP
address
When Accept connections from any IP address is unchecked,
specify the IP address that can connect to Frontier. The entry box
will only appear when the checkbox is unchecked. If the same port
is specified for two masters, BOTH must have this entry.
To apply any changes to settings on this page, click the Save settings button. Modifying any DNP3
settings on this page will require a restart of the device. Note: it is only necessary to click "Save"
once all settings in all tabs have been made.
Session
The Session tab includes options for synchronizing time using DNP3 and various interval settings.
DNP3 USER GUIDE 7
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
The description for each option can be found in the table below.
Time Sync Description
Request sync time with
master
When enabled, request a periodic time synchronization from the
master station.
System clock renewal
period (minutes)
Specifies how long (in minutes) the system time will remain valid
until a time update request is sent. Note: Frontier only responds to
a Master Request with a Time Request flag when it boots, or when
the renewal period has passed and another communication with
the master occurs. Frontier never sends unsolicited messages
unless enabled by master.
Link Status Description
“Keep-alive” interval
(seconds)
The amount of time (in seconds) to keep connected sessions open.
Frontier will keep a session open for the specified amount of time
after losing connection with a master station.
Select/Execute Timer Description
Select-to-execute interval
(seconds)
The amount of time (in seconds) that a master station has to
perform an Execute operation following a Select operation on an
object index before the operation expires. Frontier always requires
DNP3 USER GUIDE 8
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
Select/Execute protocol when performing writes from the master.
This is a safeguard against accidental changes.
To apply any changes to settings on this page, click the Save settings button. Modifying any DNP3
settings on this page will require a restart of the device.
Events
The description for each option on the Events tab can be found in the table below.
Unsolicited Events Mask Description
Do not present or send
the following classes of
events
Select which classes (Class 1, Class 2, Class 3) to not send when
a class poll is requested by the master station. This feature is
included only for masters that do not automatically set the mask.
Event Class Queues
(Class 1, Class 2, Class 3) Description
Queuing Delay (seconds)
The number of seconds to hold an Event in the Unsolicited Event
queue before transmitting. This is the effective maximum delay
from occurrence to event transmission.
High Water (event
occurrences)
The maximum number of Events to collect in queue before
transmitting. If more than this number of events occurs within the
queuing delay period, they will be transmitted if enabled.
Otherwise any event(s) (even though fewer than this number,
including only one) will be transmitted (if enabled) by the end of the
queuing delay period.
To apply any changes to settings on this page, click the Save settings button. Modifying any DNP3
settings on this page will require a restart of the device.
Default Variations
The Default Variations tab contains fields allowing the user to configure the default variation used
when responding to class polls or reporting events to the master station.
DNP3 USER GUIDE 9
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
The description for each option can be found in the table below. These are Default Variations for
responses to Variation 0 Requests:
Object Type Description
Binary inputs
(1) packed format: Send binary inputs as a bit packed field of 8
Events. This may be more efficient for polling many Binary Inputs,
but does not include important information such as timestamp or
point status (offline, etc.)
(2) status with flags: Send binary inputs with status.
Binary input events
(1) without time: Send binary input change event without time.
(2) with absolute time: Send binary input change event with
absolute time.
(3) with relative time: Send binary input change event with
relative time.
Binary outputs (1) packed format: Send binary outputs as a packed bit field of 8
points.
DNP3 USER GUIDE 10
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
(2) status with flags: Send binary outputs with status.
Binary output events
(1) status without time: Send binary output change event without
time.
(2) status with time: Send binary output change event with time.
Binary command events
(1) command status without time: Send binary command event
without time.
(2) command status with time: Send binary command event with
time.
Analog inputs
(1) 32-bits with flag: Send analog inputs as 32-bits with flag. In
Frontier, most Analog Inputs are 16-bit numbers, but Currents are
signed 32-bit numbers.
(2) 16-bits with flag: Send analog inputs as 16-bits with flag.
(3) 32-bits without flag: Send analog inputs as 32-bits without
flag.
(4) 16-bits without flag: Send analog inputs as 16-bits without
flag.
Analog outputs
(1) 32-bits with flag: Send analog outputs as 32-bits with flag.
(2) 16-bits with flag: Send analog outputs as 16-bits with flag. In
Frontier, all points except Current Limits are 16-bits. An error will
be reported if a too-large number is requested in a smaller format.
To apply any changes to DNP3 settings, click the Save settings button. You may modify settings on
other DNP3 tabs before saving but be sure to save before navigating away from the DNP3
Configuration page. Modifying any DNP3 settings will require a restart of the device.
Files
The Files tab provides access to two files:
• DNP Profile: Industry standard file used to configure your master station. The DNP profile
describes the available data points on this device and must be re-generated when you change
your battery configuration. This is an XML-formatted file with a .xml file extension.
• DNP Configuration file: This is an NDSL proprietary format file used to restore the settings on
this device or clone them to another device.
DNP3 USER GUIDE 11
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
Important: Before downloading the profile, confirm that the battery design matches your physical
hardware. If you have changed any settings, ensure that DNP is enabled and the device has been
restarted so that the profile is correctly regenerated.
Note: Be sure to save any changes to DNP3 settings before downloading the DNP3 configuration
file.
Restoring a DNP3 settings file
To restore your previously saved DNP3 settings file click the Upload button. Once a valid DNP3
configuration file is selected, the file will be automatically uploaded and the configuration will be
applied. If the file selected is not a valid DNP3 configuration, an upload error will occur and DNP3
settings will remain unchanged.
Once the DNP3 configuration file is uploaded, Frontier will require a restart to apply the new
configuration to the device.
DNP3 USER GUIDE 12
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
Using the DNP3 Profile
After the Battery Design is completed on the system and a reboot has been performed, the DNP3
Profile can be downloaded. It is this profile that describes the available data points on your system.
A sample DNP3 Profile was generated for use as an example throughout this guide. Note that the
profile pulled from your system will likely be different.
Profile Section Overview
The profile document is broken out into sections. Section 1.1 describes device information including
the Device Name and DNP3 version number. Section 1.3 gives IP Networking information taken
from the Frontier’s Network Settings page. Section 1.4 reports Address information from the DNP3
Settings page on the Frontier along with port settings. Note you will only see the Primary Master’s
information in this section.
Section 3 identifies the capabilities and current settings for each of the DNP3 data types. Details of
the data points available in the device are shown in part 5 of the Device Profile.
Section 5.1 – Binary Input Point List
Section 5.1 provides a table defining the Binary Input data points available in the device. There is a
description of each point along with the name for the state when the value is 0, or 1. Class
information is also defined. The far-right column indicates if the point is included in Class 0 polls,
while the third column indicates if the point is assigned to Event Class 1, 2, 3 or more polls. Class 0
polls will get all significant measurement points defined in one operation (both Analogue and Binary
inputs). Event Class 1, 2, and 3 polls retrieve change events (mainly Binary Inputs, i.e. Frontier
alarm changes) that have occurred since previous polls. This is in lieu of master-enabled unsolicited
events, where each entry would represent one unsolicited event. When unsolicited events are
enabled, these Event Class 1, 2, and 3 polls are unnecessary and will always be empty. Note that
Event queues are finite in size, and if not polled periodically will overflow in favor of most recent
data. No errors will occur as a result of this overflow, only the oldest events themselves will be lost.
DNP3 USER GUIDE 13
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
System
Points 0-27 are System points. They indicate any alarms, alerts or failures within the system. For
example, if a cell on the battery were to trip a high voltage alarm in Frontier, index point 0 would
return a 1 value (Alarm). If there are no alarms for high voltage on the system at the time of the poll,
the returned value would then be 0. There are some System Reserved Alarm points listed, these
should not be used.
Points 0-18 will return a value on each Class 0 poll. These points can be used to provide a high-
level indication of any alarms, alerts or failures on the system. Further investigation may be needed
to determine which cell is in alarm, etc.
Scan Status
Points 28-45 can be used to monitor the system for scanning issues. A returned value of zero
indicates the last scan completed successfully. A returned value of 1 would indicate some error has
occurred. Note that points 37-45 are reserved and should not be used. Only the Probe Read Error
and Ohmic Delayed are included in Class 0 polls. When set, Ohmic Delayed indicates that a
scheduled Ohmic Testing has been held off due to system conditions. This is most often due to a
discharging event occurring less than one hour prior to scheduled testing.
Battery Level Points
Most Frontier systems will be configured to monitor a single battery. Points 46-152 indicate alarms
or failures on up to four batteries. Using the example from above, if our system has one battery and
a cell went into high voltage alarm, point 46 would return a 1 value. None of the points in this
section are included in a Class 0 poll. Also note the reserved alarms presently should not be used.
Other Alarms
Points 159-182 are reserved for alarms triggered from external ambient temperature probes, current
probes, or digital input bits. Each of these points (except for Thermal Watch) will return a value in a
Class 0, and Class 1 poll. It is possible that some of these points will not be used as not every
DNP3 USER GUIDE 14
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
system has the corresponding hardware connected. Thermal Watch indicates that a preset
temperature limit has been exceeded and may be part of a Thermal Runaway solution (not presently
supported in Frontier) which is mainly applicable to VRLA storage cells.
Points 0-182 are the group of Fixed Points on each system. These points will not vary even with
different hardware connected to the Frontier or with different battery designs. The remaining Binary
Input points are not fixed and will vary depending on the number of Strings, Channels and
Electrolyte detectors configured on the system.
String Level Points
Points 183-208 are reserved for alarms on String 1. If multiple strings are configured on the system
these data points (as defined for each battery) would duplicate starting with point 209. The number
convention for String 1.1 indicates Battery #1, String #1. String 1.2 would indicate Battery #1, String
#2, etc. If multiple Batteries are configured on the system, the naming would then move to String 2.1
and String 2.2. Points 183-199 are reserved for alarms or failures on the first string. Each of these
points would return a value in a Class 0 poll. All but the last two points (Detached ELD and Low
Float Logical Current Alarm) are included in Class 1 polls. There are also reserved points for each
string that should not be used.
There is a group of points reserved for temperature probes, digital input bits, High Ripple Alarm, etc.
Channel Level Points
Each channel configured in the battery design has a set of points associated with it. The channel
point list will enumerate based on the number of channels configured. In the image below, we are
looking at Battery #1, String #1, Channel #3. Each channel has a high/low Voltage Alarm, high/low
Ohmic Value Alarm, high/low Temperature Alarm, and then Thermal Runaway Watches/Alarm.
Note that some of these points will be unused depending on the hardware monitoring the battery.
Points other than Thermal Watch will return values in Class 0 and Class 1 polls.
DNP3 USER GUIDE 15
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
Jar Electrolyte Level Points
If equipped, the final group of Binary Input Points will be the Electrolyte Level points. Each level
detector will be enumerated based on the battery design and the number of detectors installed on
the system. On our sample system below, we have four jars with detectors. They are configured
for Battery #1, String #1, Jars #1-4. The Low Level Alarm points will return a zero if there is no
alarm and a one if there is an alarm. For each detector, there is a Low Level Alarm which indicates
the electrolyte level on that jar is low. The Trouble Alarm is triggered if any other alarm occurs on
that jar (ie. falloff, no response). Each of these points will return a value in Class 0 and Class 1
polls.
Section 5.5 – Analogue Input Point List
Section 5.5 provides a table defining the Analogue Input data points available in the device. These
are primarily the measurement data, updated with each cycle. There is a description of each point
along with the maximum and minimum values. If a multiplier or offset is needed those values are
also indicated. The table also defines the units for each point and the Event Class Assignment.
Class 0 polls will get all points defined in one operation (both Analogue and Binary inputs).
Fixed Points
Points 0-54 are fixed points and will be the same regardless of the size of the battery the system is
attached to. These are the values returned for the system. Those devices that are not used will not
return a value. Class 0 points in this group include the following:
• 11-TP1 Value
• 14-TP2 Value
• 17-TP3 Value
• 20-TP4 Value
• 23-26-Physical CT Values for CT1 through CT4
DNP3 USER GUIDE 16
T h i s a p p l i c a t i o n n o t e i s s u b j e c t t o c h a n g e w i t h o u t n o t i c e . V i s i t W W W . C E L L W A T C H . C O M f o r t h e l a t e s t c o n t a c t i n f o r m a t i o n f o r N D S L a n d C e l l w a t c h T e c h n i c a l S u p p o r t .
POWERING CONFIDENCE TM
String Points
Starting with point 55 you will see String level values. If multiple strings are connected you will see
them listed after the first string. The strings will enumerate beginning with String 1.1 (Battery 1,
String1). Data available in this section includes String Voltage Value, String Current Value, String
Ripple Value, etc. Note that Thermal Runaway is not yet supported in Frontier but is normally
important in VRLA installations.
Channel Points
After the points for each string the Channel Points will begin to enumerate. The size of this section
will be determined by the number of monitoring points on the system. This section uses a similar
numbering system (Channel 1.1.5 represents Battery #1, String #1, Channel #5). For each channel,
the values for Voltage, Ohmic, and Temperature are available.