    1 Introduction

    2 Step of Calculation1) The Dimension of the room and Indeks room (k)

    Formula for calculation of indeks room :

    where :p : Length [m]l : Width [m]

    H : height of working desk [m]t : height of the room from light to floor [m]h : height of lighted area (t - H) [m]

    2) Reflection factor

    Ceiling(rc) : 0.75Wall (cw) : 0.5Floor (cf) : 01

    3) Efficiency Armature

    where :d : diversity (maintenance factor)

    4) Intensity Illumination room (Flux)

    TECHNICAL SPESIFICATION FOR LIGHTING AND ELECTRICAL TERMINAL

    In this document, will be explain calculation for lighting and electrical terminal on the ship. The Calculation in the ship refer to book of the Electrical Installation ship, Sardono Sarwito 1995. The aspects that affect the type, number and type of lighting is the crew on ship, broad rooms and room types. Lighting is used when ship at sea or in port at night to do the activity. Placement of the lights should be in place in every deck that is used for crew activities, ex: gangways, stairways, room or storage. Every room have type of lighting according to its use. Socket or electrical terminal is used to supply power to electrical equipment in every room and the power shall be in accordance with the existing specifications. Type of socket are 2 ampere, 4 amper, 8 ampere, 10 amper accordance to the specification equipment.

    The dimensions of the rooms used are length, width, hight and the height of the room work areas in rooms,ex: galley, lavatories, pantry, gangway and areas that require lighting.

    Reflection factor is the index value and efficiency caused ceiling lighting, wall and floor. Index values k and the efficiency room that used to be known based on data.

    Based on the the value of the index the room and the efficiency of each index, it can be seen efficiency value interpolation (interpolation).

    Values obtained by the equation armature efficiently:

  • Intensity illumination is flux that required for the roomF = (E x A)/eff armatur

    ProjectDoc. NoRev. NoType

    where :E : Lighting Intensity (Lux)A

    5) Lumen Lumen values calculated using the equation :

    where:k : 125 for FL

    : 75 for IL

    6) Numer of lamp (n)n : Fluxs () / Fluxs (lumen)

    7) Determination number of socket

    8) Calculation of the Total Power Lighting

    where :N : number of armatureP : power the armaturea : size of the socket

    : 0.8

    CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    : Area ( p x l ) (m2)

    Type of Socket used size 2A, 4A, 6A, and 10A. Consideration in determining the amount of stop contact based equipment and needs required in a room.

    Calculation of the total lighting power is the power calculation armature used with power from stop contact. Power calculation in each room is shown in the following equation:

    Cos

  • : Desaign IV: 02- 42 12 140 - EL: 00: Philosophy

    In this document, will be explain calculation for lighting and electrical terminal on the ship. The Calculation in the ship refer to book of the Electrical Installation ship, Sardono Sarwito 1995. The aspects that affect the type, number and type of lighting is the crew on ship, broad rooms and room types. Lighting is used when ship at sea or in port at night to do the activity. Placement of the lights should be in place in every deck that is used for crew activities, ex: gangways, stairways, room or storage. Every room have type of lighting according to its use. Socket or electrical terminal is used to supply power to electrical equipment in every room and the power shall be in accordance with the existing specifications. Type of socket are 2 ampere, 4 amper, 8 ampere, 10 amper accordance to the

    The dimensions of the rooms used are length, width, hight and the height of the room work areas in rooms,ex: galley, lavatories, pantry, gangway and areas that require lighting.

    Reflection factor is the index value and efficiency caused ceiling lighting, wall and floor. Index values k and the efficiency room that used to be known based on data.

    Based on the the value of the index the room and the efficiency of each index, it can be

  • : Desaign IV: 02- 42 12 140 - BG: 00: Philosophy

    Type of Socket used size 2A, 4A, 6A, and 10A. Consideration in determining the amount of stop contact based equipment and needs required in a room.

    Calculation of the total lighting power is the power calculation armature used with power from stop contact. Power calculation in each room is shown in the following equation:

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    Formula :1. Area(A) = p x l where:

    p = Length (m)l = Width (m)

    2. Indeks (K) = p x l where:h (p + l) p = Length (m)

    l = Width (m)H = distance between lamp and work planh = t - height of work plant = height

    3. efficiency = eff 1 + ((k - k1) x (eff 2 - eff 1)/(k2 - k1))

    4. efficiency of armartur = d x eff (interpolation) whered = maintenance factor

    5. Flux (F) = (E x A)/eff armatur where:E = Lighting Intensity (Lux)

    6. Flux (lumen) = S x daya x 125 FL = 125 where:= S x daya x 75 IL = 75 S = Number of lamp in one armature

    7. n = Fluxs () / Fluxs (lumen)

    =(E x A)/eff armatur

    S x daya x 75

    A = Area (m2

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    MAIN DECK

    NO. RoomRoom Dimension

    KAType of Armature Faktor Refleksi

    (P) (L) (t) (H) (h) (A) Type daya ceiling wall floor

    1 Chef & Assist Cook 6.0 4.2 2.7 0.7 2.0 25.2 1.235 9 1 FL 20 0.75 0.5 0.12 Electrician & Oiler III 5.7 4.2 2.7 0.7 2.0 23.9 1.209 9 1 FL 20 0.75 0.5 0.13 Lavatory 6.3 5.4 2.7 0.7 2.0 34.0 1.454 4 1 FL 15 0.75 0.5 0.14 Hospital 5.6 5.0 2.7 0.7 2.0 28.0 1.321 10B 2 FL 20 0.75 0.5 0.15 Paint Store 3.6 2.6 2.7 0.7 2.0 9.4 0.755 13 1 FL 20 0.75 0.5 0.16 Gymnasium 5.0 3.5 2.7 0.7 2.0 17.5 1.029 9 1 FL 20 0.75 0.5 0.17 Recreation Room 5.25 4.5 2.7 0.7 2.0 23.6 1.212 10B 2 FL 20 0.75 0.5 0.18 Laundry & Dry Room 5.0 3.0 2.7 0 2.7 15.0 0.694 4B 2 FL 20 0.75 0.5 0.19 Pray Room 5.0 5.0 2.7 0.7 2.0 25.0 1.250 9 1 FL 20 0.75 0.5 0.1

    10 Dry Storage 4.3 3.6 2.7 0 2.7 15.5 0.726 4 1 FL 15 0.75 0.5 0.111 Cold Storage 4.6 3.5 2.7 0 2.7 16.1 0.736 4 1 FL 15 0.75 0.5 0.112 Galley 5.0 4.2 2.7 0 2.7 21.0 0.845 18 2 FL 20 0.75 0.5 0.113 Mess Room 5.4 4.2 2.7 0 2.7 22.7 0.875 10B 2 FL 20 0.75 0.5 0.114 Foreman & Wiper 5.7 4.2 2.7 0 2.7 23.9 0.896 9 1 FL 20 0.75 0.5 0.115 Oiler I & Oiler II 6.0 4.20 2.7 0 2.7 25.2 0.915 9 1 FL 20 0.75 0.5 0.116 Starway I 3.5 1.4 2.7 0 2.7 4.9 0.370 4 1 FL 15 0.75 0.5 0.117 Gang way 1 8.65 3.5 2.7 0 2.7 30.3 0.923 6 1 FL 20 0.75 0.5 0.118 Gang way 2 12.0 2.5 2.7 0 2.7 30.0 0.766 6 1 FL 20 0.75 0.5 0.119 Gang way 3 12.0 2.5 2.7 0 2.7 30.0 0.766 6 1 FL 20 0.75 0.5 0.120 Gang way 4 8.65 4.9 2.7 0 2.7 42.4 1.159 6 1 FL 20 0.75 0.5 0.121 Gang way 5 6.0 3.6 2.7 0 2.7 21.6 0.833 6 1 FL 20 0.75 0.5 0.122 Gang way 6 4.4 3.6 2.7 0 2.7 15.7 0.730 6 1 FL 20 0.75 0.5 0.1

    Indeks Room (k)

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    POOP DECK

    NO. Room Room Dimension KA Type of Armature Faktor Refleksi(P) (L) (t) (H) (h) (A) Type daya ceiling wall floor

    1 Quarter Master 1 3.5 3.0 2.5 0.7 1.8 10.5 0.897 9 1 FL 20 0.75 0.5 0.12 Seaman 2 3.5 3.0 2.5 0.7 1.8 10.5 0.897 9 1 FL 20 0.75 0.5 0.13 Serang 3.5 3.0 2.5 0.7 1.8 10.5 0.897 9 1 FL 20 0.75 0.5 0.14 Quarter Master 3 3.5 3.0 2.5 0.7 1.8 10.5 0.897 9 1 FL 20 0.75 0.5 0.15 Seaman 1 3.5 3.0 2.5 0.7 1.8 10.5 0.897 9 1 FL 20 0.75 0.5 0.16 Emergency Genset 2.0 3.0 2.5 0 2.5 6.0 0.480 13 1 FL 20 0.75 0.5 0.17 Lavatory 3.5 3.0 2.5 0 2.5 10.5 0.646 4 1 FL 15 0.75 0.5 0.18 CO2 Room 3.0 1.75 2.5 0 2.5 5.3 0.442 13 1 FL 20 0.75 0.5 0.19 AHU Room 3.0 1.75 2.5 0 2.5 5.3 0.442 13 1 FL 20 0.75 0.5 0.110 Pantry 3.0 1.8 2.5 0.7 1.8 5.3 0.619 4B 2 FL 20 0.75 0.5 0.111 Quarter Master 2 3.0 2.0 2.5 0.7 1.8 6.0 0.667 9 1 FL 20 0.75 0.5 0.112 Gang way 1 6.0 2.0 2.5 0 2.5 12.0 0.600 6 1 FL 20 0.75 0.5 0.113 Gang way 2 5.6 1.5 2.5 0 2.5 8.4 0.473 6 1 FL 20 0.75 0.5 0.114 Gang way 3 5.6 1.5 2.5 0 2.5 8.4 0.473 6 1 FL 20 0.75 0.5 0.115 Gang way 4 6.0 3.0 2.5 0 2.5 18.0 0.800 6 1 FL 20 0.75 0.5 0.116 Out Gangway 1 3.0 1.4 2.5 0 2.5 4.2 0.382 6 1 FL 20 0.75 0.5 0.117 Out Gangway 2 3.0 1.4 2.5 0 2.5 4.2 0.382 6 1 FL 20 0.75 0.5 0.118 Stairway 1 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.119 Stairway 2 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.120 Stairway 3 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.1

    Indeks Room (k)

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    Boat Deck

    NO. Room Room Dimension KA Type of Armature Faktor Refleksi(P) (L) (t) (H) (h) (A) Type daya ceiling wall floor

    1 Second Officer 3.5 3.0 2.5 0.7 1.8 10.5 0.897 9 1 FL 20 0.75 0.5 0.12 Second Engineer 3.5 3.0 2.5 0.7 1.8 10.5 0.897 9 1 FL 20 0.75 0.5 0.13 Third Engineer 3.5 3.0 2.5 0.7 1.8 10.5 0.897 9 1 FL 20 0.75 0.5 0.14 Third Officer 3.5 3.0 2.5 0.7 1.8 10.5 0.897 9 1 FL 20 0.75 0.5 0.15 Mess room 5.0 3.0 2.5 0.7 1.8 15.0 1.042 10B 2 FL 20 0.75 0.5 0.16 Lavatory 3.0 3.0 2.5 0 2.5 9.0 0.600 4 1 FL 15 0.75 0.5 0.17 Meeting Room 4.3 3.0 2.5 0.7 1.8 12.8 0.977 10B 2 FL 20 0.75 0.5 0.18 Pantry Room 3.0 2.0 2.5 0.7 1.8 6.0 0.667 4 1 FL 15 0.75 0.5 0.19 Gangway 1 3.0 1.4 2.5 0 2.5 4.2 0.382 6 1 FL 20 0.75 0.5 0.110 Gangway 2 6.0 3.0 2.5 0 2.5 18.0 0.800 6 1 FL 20 0.75 0.5 0.111 Gangway 3 3.0 1.4 2.5 0 2.5 4.2 0.382 6 1 FL 20 0.75 0.5 0.112 Gangway 4 6.4 1.5 2.5 0 2.5 9.6 0.486 6 1 FL 20 0.75 0.5 0.113 Gangway 5 6.4 1.5 2.5 0 2.5 9.6 0.486 6 1 FL 20 0.75 0.5 0.114 Stairway 1 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.115 Stairway 2 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.116 Stairway 3 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.1

    Indeks Room (k)

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    Brigde Deck

    NO. Room Room Dimension KA Type of Armature Faktor Refleksi(P) (L) (t) (H) (h) (A) Type daya ceiling wall floor

    1 Captain Bed room 5.0 3.0 2.5 0.7 1.8 15.0 1.042 9B 1 FL 20 0.75 0.5 0.12 Captain day room 3.0 2.1 2.5 0.7 1.8 6.3 0.686 9B 1 FL 20 0.75 0.5 0.13 Captain Office Room 3.0 2.1 2.5 0.7 1.8 6.3 0.686 9B 1 FL 20 0.75 0.5 0.14 Chief Eng. day room 3.0 2.1 2.5 0.7 1.8 6.3 0.686 9B 1 FL 20 0.75 0.5 0.15 Chief Eng. Bed room 5.0 3.0 2.5 0.7 1.8 15.0 1.042 9B 1 FL 20 0.75 0.5 0.16 Chief Eng. Office 3.0 2.1 2.5 0.7 1.8 6.3 0.686 9B 1 FL 20 0.75 0.5 0.17 KM. Chief engine 2.0 2.0 2.5 0 2.5 4.0 0.400 4 1 FL 15 0.75 0.5 0.18 KM. Capatin 2.0 2.0 2.5 0 2.5 4.0 0.400 4 1 FL 15 0.75 0.5 0.19 Chief off. Bed room 3.0 3.0 2.5 0.7 1.8 9.0 0.833 9B 1 FL 20 0.75 0.5 0.110 KM. Chief Off Room 2.0 2.0 2.5 0 2.5 4.0 0.400 4 1 FL 15 0.75 0.5 0.111 Gangway 1 6.0 1.4 2.5 0 2.5 8.4 0.454 6 1 FL 20 0.75 0.5 0.112 Gangway 2 5.4 1.5 2.5 0 2.5 8.1 0.470 6 1 FL 20 0.75 0.5 0.113 Gangway 3 5.4 1.5 2.5 0 2.5 8.1 0.470 6 1 FL 20 0.75 0.5 0.114 Gangway 4 6.0 1.0 2.5 0 2.5 6.0 0.343 6 1 FL 20 0.75 0.5 0.115 Stairway 1 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.116 Stairway 2 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.117 Stairway 3 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.1

    Indeks Room (k)

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    NAVIGATION DECK

    NO. Room Room Dimension KA Type of Armature Faktor Refleksi(P) (L) (t) (H) (h) (A) Type daya ceiling wall floor

    1 Wheelhouse 12.0 5.4 2.5 0.7 1.8 64.8 2.069 10B 2 FL 20 0.75 0.5 0.12 Radio Room 3.0 2.8 2.5 0.7 1.8 8.4 0.805 9B 1 FL 20 0.75 0.5 0.14 Lavatory 3.0 2.8 2.5 0 2.5 8.4 0.579 4 1 FL 15 0.75 0.5 0.15 ESEP Room 3.0 2.8 2.5 0 2.5 8.4 0.579 10B 2 FL 20 0.75 0.5 0.16 Operator Radio 4.3 2.8 2.5 0.7 1.8 12.0 0.942 9 1 FL 20 0.75 0.5 0.17 Stairway 3.0 1.3 2.5 0 2.5 3.8 0.353 4 1 FL 15 0.75 0.5 0.18 Chart Room 1.9 1.7 2.5 0 2.5 3.3 0.363 4 1 FL 15 0.75 0.5 0.1

    FORECASTLE DECK

    NO. Room Room Dimension KA Type of Armature Faktor Refleksi(P) (L) (t) (H) (h) (A) Type daya ceiling wall floor

    Indeks Room (k)

    Indeks Room (k)

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    1 Deck 8.1 2.5 3.0 0 3.0 20.3 0.637 40 1 IL 100 0.75 0.5 0.1

    ENGINE ROOM AND PLATFORM

    NO. Room Room Dimension KA Type of Armature Faktor Refleksi(P) (L) (t) (H) (h) (A) Type daya ceiling wall floor

    1 Tank Top 20.3 10.0 2.5 0 2.5 203.0 2.680 40 1 IL 100 0.75 0.5 0.12 Platform 1 20.3 10.0 2.5 0 2.5 203.0 2.680 14 2 FL 20 0.75 0.5 0.13 Platform 2 17.5 10.0 4.0 0 4.0 175.0 1.591 14 2 FL 20 0.75 0.5 0.14 Steering Gear Room 7.5 7.5 2.7 0 2.7 56.3 1.389 14 2 FL 20 0.75 0.5 0.17 Engine Control Room 8.0 2.8 4.0 0.7 3.3 22.4 0.629 14 2 FL 20 0.75 0.5 0.1

    Indeks Room (k)

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    No Deck Total PowerTotal of Stop Contact Point (A) Total of

    Light Point (W) 2 4 6 10 Load Point1 Main Deck 73 1760 13 8 0 0 102082 Poop Deck 34 735 9 0 0 0 31683 Boat Deck 30 635 12 0 0 0 42244 Capt. Bridge deck 42 795 9 0 0 0 31685 Forecastle Deck 2 200 0 0 0 0 06 Navigation Deck 14 385 3 0 0 0 10567 Engine Room 68 3860 0 0 0 0 0

    Jumlah total 263 8370 34 8 0 0 21824

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    S = Number of lamp in one armature

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    k1 eff 1 k2 eff 2 NO. eff intrpolasi eff arm Flux() Flux Lampu (Lumen) n

    1.000 0.350 1.250 0.379 1 0.377 0.7 0.2641059 100 9541.63 2500 3.81665111.000 0.350 1.250 0.379 2 0.374 0.7 0.2619782 100 9138.17 2500 3.65526621.250 0.452 1.500 0.487 3 0.481 0.7 0.3363769 50 5056.83 1875 2.69697451.250 0.382 1.500 0.405 4 0.389 0.7 0.2719566 200 20591.52 5000 4.11830410.600 0.329 0.800 0.407 5 0.389 0.75 0.2920403 50 1602.52 2500 0.64100741.000 0.350 1.250 0.379 6 0.353 0.7 0.2473882 100 7073.90 2500 2.82956061.000 0.353 1.250 0.382 7 0.378 0.7 0.2642769 250 22348.72 5000 4.46974330.600 0.285 0.800 0.322 8 0.302 0.7 0.2117306 50 3542.24 5000 0.7084476

    1.250 0.379 9 0.379 0.7 0.2653 100 9423.29 2500 3.76931780.600 0.295 0.800 0.368 10 0.341 0.7 0.2386262 50 3243.57 1875 1.72990250.600 0.295 0.800 0.368 11 0.345 0.7 0.241291 50 3336.22 1875 1.77931770.800 0.439 1.000 0.470 12 0.446 0.7 0.3122271 200 13451.75 5000 2.69034980.800 0.322 1.000 0.353 13 0.353 0.7 0.2471 250 22946.18 5000 4.58923510.800 0.314 1.000 0.350 14 0.350 0.7 0.245 100 9771.43 2500 3.90857140.800 0.314 1.000 0.350 15 0.350 0.7 0.245 100 10285.71 2500 4.1142857

    0.600 0.295 16 0.295 0.7 0.2065 50 1186.44 1875 0.63276840.800 0.190 1.000 0.220 17 0.220 0.7 0.154 50 9829.55 2500 3.93181820.600 0.150 0.800 0.190 18 0.190 0.7 0.133 50 11278.20 2500 4.51127820.600 0.150 0.800 0.190 19 0.190 0.7 0.133 50 11278.20 2500 4.51127821.000 0.220 1.250 0.250 20 0.250 0.7 0.175 50 12110.00 2500 4.8440.800 0.190 1.000 0.220 21 0.220 0.7 0.154 50 7012.99 2500 2.80519480.800 0.190 1.000 0.220 22 0.220 0.7 0.154 50 5084.42 2500 2.0337662

    Jumlah

    Dvrstas(d)

    intnstas (E) Lux

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    Jumlah Armature =Titik Beban Stop Kontak =

    Total Titik Beban =

    Total Daya =Total Beban Stop Kontak =

    Total daya dalam satu deck =

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    k1 eff 1 k2 eff 2 NO. eff intrpolasi eff arm Flux() Flux Lampu (Lumen) n

    0.800 0.314 1.000 0.350 1 0.332 0.7 0.2320769 100 4524.36 2500 1.8097450.800 0.314 1.000 0.350 2 0.332 0.7 0.2320769 100 4524.36 2500 1.8097450.800 0.314 1.000 0.350 3 0.332 0.7 0.2320769 100 4524.36 2500 1.8097450.800 0.314 1.000 0.350 4 0.332 0.7 0.2320769 100 4524.36 2500 1.8097450.800 0.314 1.000 0.350 5 0.332 0.7 0.2320769 100 4524.36 2500 1.809745

    0.600 0.329 6 0.263 0.7 0.18424 200 6513.24 2500 2.6052970.600 0.295 7 0.318 0.7 0.2223846 50 2360.77 1875 1.259080.600 0.329 8 0.242 0.75 0.1818158 200 5775.08 2500 2.310030.600 0.329 9 0.242 0.75 0.1818158 200 5775.08 2500 2.31003

    0.600 0.285 0.800 0.322 10 0.289 0.7 0.2019915 200 5268.34 5000 1.0536680.600 0.262 0.800 0.314 11 0.279 0.7 0.1955333 100 3068.53 2500 1.227412

    0.600 0.150 12 0.150 0.7 0.105 50 5714.29 2500 2.2857140.600 0.150 13 0.118 0.7 0.0828169 50 5071.43 2500 2.0285710.600 0.150 14 0.118 0.7 0.0828169 50 5071.43 2500 2.028571

    0.600 0.150 0.800 0.190 15 0.190 0.7 0.133 50 6766.92 2500 2.7067670.600 0.150 16 0.095 0.7 0.0668182 50 3142.86 2500 1.2571430.600 0.150 17 0.095 0.7 0.0668182 50 3142.86 2500 1.2571430.600 0.295 18 0.174 0.7 0.1214706 50 1543.58 1875 0.8232450.600 0.295 19 0.174 0.7 0.1214706 50 1543.58 1875 0.8232450.600 0.295 20 0.174 0.7 0.1214706 50 1543.58 1875 0.823245

    Jumlah

    Dvrstas(d)

    intnstas (E) Lux

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    Jumlah Armature = 34 Total Daya =Titik Beban Stop Kontak = 9 Total Beban Stop Kontak =

    Total Titik Beban = 43 pointTotal daya dalam satu deck =

    k1 eff 1 k2 eff 2 NO. eff intrpolasi eff arm Flux() Flux Lampu (Lumen) n

    0.800 0.314 1.000 0.350 1 0.332 0.7 0.2320769 100 4524.36 2500 1.8097450.800 0.314 1.000 0.350 2 0.332 0.7 0.2320769 100 4524.36 2500 1.8097450.800 0.314 1.000 0.350 3 0.332 0.7 0.2320769 100 4524.36 2500 1.8097450.800 0.314 1.000 0.350 4 0.332 0.7 0.2320769 100 4524.36 2500 1.8097451.000 0.353 1.250 0.382 5 0.358 0.7 0.2504833 250 14971.06 5000 2.994211

    0.600 0.295 6 0.295 0.7 0.2065 50 2179.18 1875 1.1622280.800 0.322 1.000 0.353 7 0.349 0.7 0.2446057 200 10424.94 5000 2.0849880.600 0.295 0.800 0.368 8 0.319 0.7 0.2235333 200 5368.33 1875 2.863108

    0.600 0.150 9 0.095 0.7 0.0668182 50 3142.86 2500 1.2571430.800 0.190 10 0.190 0.7 0.133 50 6766.92 2500 2.7067670.600 0.150 11 0.095 0.7 0.0668182 50 3142.86 2500 1.2571430.600 0.150 12 0.122 0.7 0.0850633 50 5642.86 2500 2.2571430.600 0.150 13 0.122 0.7 0.0850633 50 5642.86 2500 2.2571430.600 0.295 14 0.174 0.7 0.1214706 50 1543.58 1875 0.8232450.600 0.295 15 0.174 0.7 0.1214706 50 1543.58 1875 0.8232450.600 0.295 16 0.174 0.7 0.1214706 50 1543.58 1875 0.823245

    Jumlah

    Jumlah Armature = 30 Total Daya =Titik Beban Stop Kontak = 12 Total Beban Stop Kontak =

    Dvrstas(d)

    intnstas (E) Lux

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    Total Titik Beban = 42 pointTotal daya dalam satu deck =

    k1 eff 1 k2 eff 2 NO. eff intrpolasi eff arm Flux() Flux Lampu (Lumen) n

    1.000 0.350 1.250 0.379 1 0.355 0.7 0.248383 200 12078.11 2500 4.8312420.600 0.262 0.800 0.314 2 0.284 0.7 0.199102 200 6328.42 2500 2.5313660.600 0.262 0.800 0.314 3 0.284 0.7 0.199102 200 6328.42 2500 2.5313660.600 0.262 0.800 0.314 4 0.284 0.7 0.199102 200 6328.42 2500 2.5313661.000 0.350 1.250 0.379 5 0.355 0.7 0.248383 200 12078.11 2500 4.8312420.600 0.262 0.800 0.314 6 0.284 0.7 0.199102 200 6328.42 2500 2.531366

    0.600 0.295 7 0.197 0.7 0.137667 100 2905.57 1875 1.5496370.600 0.295 8 0.197 0.7 0.137667 100 2905.57 1875 1.549637

    0.800 0.314 1.000 0.350 9 0.320 0.7 0.224 200 8035.71 2500 3.2142860.600 0.295 10 0.197 0.7 0.137667 100 2905.57 1875 1.5496370.600 0.150 11 0.114 0.7 0.079459 50 5285.71 2500 2.1142860.600 0.150 12 0.117 0.7 0.082174 50 4928.57 2500 1.9714290.600 0.150 13 0.117 0.7 0.082174 50 4928.57 2500 1.9714290.600 0.150 14 0.086 0.7 0.06 50 5000.00 2500 20.600 0.295 15 0.174 0.7 0.121471 50 1543.58 1875 0.8232450.600 0.295 16 0.174 0.7 0.121471 50 1543.58 1875 0.8232450.600 0.295 17 0.174 0.7 0.121471 50 1543.58 1875 0.823245

    Jumlah

    Dvrstas(d)

    intnstas (E) Lux

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    Jumlah Armature = 42 Total Daya =Titik Beban Stop Kontak = 9 Total Beban Stop Kontak =

    Total Titik Beban = 51 point

    Total daya dalam satu deck =

    k1 eff 1 k2 eff 2 NO. eff intrpolasi eff arm Flux() Flux Lampu (Lumen) n

    2.000 0.433 2.500 0.465 1 0.437 0.7 0.30619 120 25396.02 5000 5.0792050.800 0.314 1.000 0.350 2 0.315 0.7 0.220379 180 6860.90 2500 2.7443590.600 0.295 0.800 0.368 4 0.287 0.7 0.201214 50 2087.33 1875 1.1132440.600 0.265 0.800 0.322 5 0.259 0.7 0.181372 100 4631.35 5000 0.9262710.800 0.314 1.000 0.350 6 0.340 0.7 0.237704 100 5065.12 2500 2.026047

    0.600 0.295 7 0.295 0.7 0.2065 50 907.99 1875 0.4842620.600 0.295 8 0.295 0.7 0.2065 100 1596.45 1875 0.851438

    Jumlah

    Jumlah Armature = 14 Total Daya =Titik Beban Stop Kontak = 3 Total Beban Stop Kontak =

    Total Titik Beban = 17 pointTotal daya dalam satu deck =

    k1 eff 1 k2 eff 2 NO. eff intrpolasi eff arm Flux() Flux Lampu (Lumen) n

    Dvrstas(d)

    intnstas (E) Lux

    Dvrstas(d)

    intnstas (E) Lux

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    0.600 0.195 0.800 0.268 1 0.208 0.65 0.135479 100 14946.96 7500 1.992929

    JumlahJumlah Armature = 2 Total Daya =

    Titik Beban Stop Kontak = 0 Total Beban Stop Kontak =Total Titik Beban = 2 point

    Total daya dalam satu deck =

    k1 eff 1 k2 eff 2 NO. eff intrpolasi eff arm Flux() Flux Lampu (Lumen) n

    2.500 0.427 3.000 0.456 1 0.437 0.65 0.284331 200 142791.31 7500 19.038842.500 0.793 3.000 0.814 2 0.801 0.75 0.600416 200 67619.80 5000 13.523961.500 0.671 2.000 0.729 3 0.682 0.75 0.511159 200 68471.83 5000 13.694371.250 0.626 1.500 0.671 4 0.651 0.75 0.48825 200 23041.47 3000 7.6804920.600 0.421 0.800 0.522 7 0.435 0.75 0.326547 100 6859.65 5000 1.371931

    Jumlah

    Jumlah Armature = 68 Total Daya =Titik Beban Stop Kontak = 0 Total Beban Stop Kontak =

    Total Titik Beban = 68 pointTotal daya dalam satu deck =

    Dvrstas(d)

    intnstas (E) Lux

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    Total of PowerLoad Point (KW)

    10208 11.9683168 3.9034224 4.8593168 3.963

    0 0.2001056 1.441

    0 3.86021824 30.194

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    N Daya (w)Stop Kontak (ampere) Total

    2 4 6 10 Watt

    4 80 1 352 4324 80 1 3523 45 04 160 1 3521 20 03 60 2 7044 160 3 10561 40 3 21124 80 1 3522 30 02 30 3 21123 120 1 2 17605 200 1 3524 80 1 3524 80 1 3521 15 04 80 05 100 05 100 05 100 03 60 02 4073 1760 13 8 0 0 10208

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    732194 point

    1760 Watt10208 Watt

    11968 watt

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    N Daya (w)Stop Kontak (ampere) Total

    2 4 6 10 Watt2 40 1 3522 40 1 3522 40 1 3522 40 1 3522 40 1 3523 60 01 70 02 40 02 40 01 40 3 10561 20 1 3522 40 02 40 02 40 03 60 01 20 01 20 01 15 01 15 01 15

    34 735 9 0 0 0 3168

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    735 Watt3168 Watt

    3903 watt

    N Daya (w)Stop Kontak (ampere) Total

    2 4 6 10 Watt2 40 2 7042 40 2 7042 40 2 7042 40 2 7042 80 1 3521 15 02 80 1 3523 45 2 7041 20 03 60 01 20 02 40 02 40 02 30 02 30 01 15 030 635 12 0 0 0 4224

    635 Watt4224 Watt

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    4859 watt

    N Daya (w)Stop Kontak (ampere) Total

    2 4 6 10 Watt5 100 2 7043 60 1 3523 60 1 3523 60 1 3525 100 2 7043 60 1 3522 30 02 30 03 60 1 3522 30 02 40 02 40 02 40 02 40 01 15 01 15 01 15 042 795 9 0 0 0 3168

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    795 Watt3168 Watt

    3963 watt

    N Daya (w)Stop Kontak (ampere) Total

    2 4 6 10 Watt5 200 03 60 2 7041 15 01 40 02 40 1 3521 15 01 15 0

    014 385 3 0 0 0 1056

    385 Watt1056 Watt

    1441 watt

    N Daya (w)Stop Kontak (ampere) Total

    2 4 6 10 Watt

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

    2 200 0

    2 200 0 0 0 0 0200 Watt

    0 Watt

    200 watt

    N Daya (w)Stop Kontak (ampere) Total

    2 4 6 10 Watt19 1900 025 1000 014 560 08 320 02 80 068 3860 0 0 0 0 0

    3860 Watt0 Watt

    3860 watt

  • CALCULATION FOR LIGHTING AND ELECTRICAL TERMINAL

    Doc. No : 02 - 42 12 140 - EL

    Jurusan Teknik Sistem Perkapalan FTK ITS

  • Pedoman Untuk Intensitas Iluminasi CahayaBiro Klasifikasi Indonesia

    JENIS RUANGANFLUKSI CAHAYA

    (Lux)

    Ruang palka

    20 sampai 40 luxRuang kerjaJalanLalu lintas diatas deck

    Lorong dan jalan masuk

    50 sampai 70 lux

    Tempat peluncuran sekociKamar kecilKamar mandiBioskopTerowongan poros

    Kamar Peta

    100 sampai 150 luxRuang kemudiKabin penumpangKabin awak kapal

    Ruang Mesin

    200 sampai 500 lux

    Ruang Komisaris/pemilikRuang istirahat

    Ruang duduk

    Ruang makan/minumPerpustakaan

    Rumah sakit 200 lux

  • Indeks :4

    Faktor (k)Ceiling 75 50Wall 50 30 10 50 30 10Floor 10 10

    Efisiensi Faktor Refleksi 0.60 (J) 0.295 0.246 0.213 0.283 0.250 0.211 0.80 (I) 0.368 0.314 0.283 0.350 0.301 0.272 1.00 (H) 0.406 0.357 0.327 0.390 0.345 0.317 1.25 (G) 0.452 0.408 0.368 0.421 0.378 0.346 1.50 (F) 0.487 0.439 0.393 0.452 0.413 0.374 2.00 (E) 0.538 0.488 0.461 0.503 0.460 0.421 2.50 (D) 0.588 0.523 0.475 0.507 0.496 0.456 3.00 (C) 0.608 0.556 0.493 0.566 0.521 0.418 4.00 (B) 0.650 0.596 0.554 0.603 0.553 0.525

    5.00 (A) 0.672 0.624 0.581 0.623 0.578 0.546

  • Indeks :4B

    30 0Faktor (k)

    Ceiling 75 5030 10 0 Wall 50 30 10 50 30

    10 0 Floor 10 10Faktor Refleksi Efisiensi Faktor Refleksi

    0.233 0.207 0.206 0.60 (J) 0.285 0.233 0.213 0.268 0.2350.296 0.267 0.252 0.80 (I) 0.322 0.294 0.278 0.315 0.2870.336 0.308 0.294 1.00 (H) 0.345 0.318 0.313 0.343 0.3210.367 0.336 0.378 1.25 (G) 0.382 0.353 0.340 0.369 0.3470.399 0.366 0.355 1.50 (F) 0.405 0.381 0.355 0.385 0.3660.438 0.304 0.400 2.00 (E) 0.433 0.412 0.590 0.419 0.4020.475 0.465 0.431 2.50 (D) 0.465 0.435 0.415 0.469 0.4340.499 0.468 0.461 3.00 (C) 0.481 0.454 0.414 0.461 0.4330.552 0.509 0.499 4.00 (B) 0.499 0.472 0.457 0.478 0.455

    0.549 0.582 0.527 5.00 (A) 0.511 0.486 0.469 0.491 0.464

    F L 2 0 w x 2 0 . 7

    0 1 2 3 4 512345

    4 0

    1 0

    3 0

    2 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • Indeks :18

    50 30 0Faktor (k)

    Ceiling 75 5010 30 10 0 Wall 50 30 10 50

    10 10 0 Floor 10 10Faktor Refleksi Efisiensi Faktor Refleksi

    0.213 0.230 0.209 0.239 0.60 (J) 0.359 0.314 0.288 0.3670.231 0.256 0.268 0.265 0.80 (I) 0.439 0.395 0.373 0.4210.305 0.318 0.302 0.282 1.00 (H) 0.470 0.462 0.420 0.4630.331 0.361 0.329 0.309 1.25 (G) 0.521 0.485 0.451 0.4970.349 0.394 0.367 0.329 1.50 (F) 0.556 0.520 0.483 0.5220.379 0.412 0.376 0.356 2.00 (E) 0.600 0.565 0.529 0.5730.408 0.417 0.405 0.585 2.50 (D) 0.645 0.595 0.361 0.6090.421 0.431 0.415 0.395 3.00 (C) 0.665 0.625 0.578 0.6290.444 0.454 0.437 0.457 4.00 (B) 0.694 0.652 0.626 0.658

    0.459 0.457 0.406 0.436 5.00 (A) 0.713 0.675 0.646 0.673

    F L 2 0 w x 2 0 . 7

    0 1 2 3 4 512345

    4 0

    1 0

    3 0

    2 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

    F L 2 0 w x 2 0 . 7

    0 1 2 3 4 512345

    3 5 0

    5 0

    3 0 0

    1 0 0

    1 5 0

    2 0 0

    2 5 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • Indeks :6

    50 30 0Faktor (k)

    Ceiling 7530 10 30 10 0 Wall 50 30 1010 10 0 Floor 10

    Faktor Refleksi Efisiensi Faktor Refleksi0.319 0.286 0.308 0.281 0.271 0.60 (J) 0.150 0.120 0.1000.383 0.363 0.380 0.352 0.363 0.80 (I) 0.190 0.160 0.1400.429 0.409 0.427 0.395 0.396 1.00 (H) 0.220 0.100 0.1700.485 0.439 0.456 0.433 0.435 1.25 (G) 0.250 0.220 0.2000.406 0.467 0.487 0.461 0.450 1.50 (F) 0.270 0.250 0.2200.540 0.510 0.523 0.496 0.688 2.00 (E) 0.300 0.280 0.2600.576 0.565 0.558 0.537 0.539 2.50 (D) 0.320 0.300 0.2800.597 0.566 0.575 0.556 0.566 3.00 (C) 0.330 0.310 0.3000.619 0.599 0.602 0.583 0.573 4.00 (B) 0.350 0.350 0.320

    0.640 0.615 0.618 0.602 0.591 5.00 (A) 0.370 0.350 0.350

    F L 2 0 w x 2 0 . 7

    0 1 2 3 4 512345

    3 5 0

    5 0

    3 0 0

    1 0 0

    1 5 0

    2 0 0

    2 5 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

    F L 2 0 w x 1 0 . 7

    0 1 2 3 4 512345

    4 0

    1 0

    3 0

    2 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • Indeks :9

    50 30 0Faktor (k)

    Ceiling 7550 30 10 30 10 0 Wall 50 30

    10 10 0 Floor 10Faktor Refleksi Efisiensi Faktor Refleksi

    0.140 0.120 0.100 0.110 0.100 0.100 0.60 (J) 0.262 0.2300.180 0.160 0.140 0.150 0.130 0.120 0.80 (I) 0.314 0.2910.210 0.180 0.160 0.180 0.160 0.150 1.00 (H) 0.350 0.3250.240 0.210 0.190 0.200 0.170 0.170 1.25 (G) 0.379 0.3550.260 0.230 0.220 0.220 0.210 0.190 1.50 (F) 0.407 0.3780.280 0.260 0.250 0.250 0.230 0.210 2.00 (E) 0.420 0.4070.300 0.280 0.270 0.270 0.250 0.230 2.50 (D) 0.460 0.4320.310 0.300 0.280 0.280 0.270 0.250 3.00 (C) 0.478 0.4510.330 0.320 0.310 0.300 0.290 0.270 4.00 (B) 0.496 0.469

    0.340 0.330 0.320 0.310 0.310 0.280 5.00 (A) 0.508 0.483

    F L 2 0 w x 1 0 . 7

    0 1 2 3 4 512345

    4 0

    1 0

    3 0

    2 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

    F L 2 0 w x 1 0 . 7

    0 1 2 3 4 512345

    4 0

    1 0

    3 0

    2 0

    5 0

    7 0

    6 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • Indeks :9B

    75 50 30 0Faktor (k)

    Ceiling 7510 50 30 10 30 10 0 Wall 50

    10 10 10 0 Floor 10Faktor Refleksi Efisiensi Faktor Refleksi

    0.210 0.255 0.232 0.210 0.227 0.206 0.186 0.60 (J) 0.2620.275 0.312 0.284 0.268 0.283 0.265 0.245 0.80 (I) 0.3140.310 0.340 0.318 0.302 0.315 0.299 0.279 1.00 (H) 0.3500.337 0.366 0.440 0.328 0.338 0.326 0.306 1.25 (G) 0.3790.352 0.382 0.363 0.346 0.361 0.345 0.326 1.50 (F) 0.4070.387 0.416 0.399 0.376 0.384 0.373 0.353 2.00 (E) 0.4200.412 0.445 0.421 0.405 0.414 0.402 0.382 2.50 (D) 0.4600.421 0.459 0.425 0.418 0.428 0.412 0.392 3.00 (C) 0.4780.454 0.475 0.442 0.441 0.443 0.434 0.416 4.00 (B) 0.496

    0.446 0.488 0.466 0.450 0.454 0.443 0.423 5.00 (A) 0.508

    F L 2 0 w x 1 0 . 7

    0 1 2 3 4 512345

    4 0

    1 0

    3 0

    2 0

    5 0

    7 0

    6 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

    F L 2 0 w x 1 0 . 7

    0 1 2 3 4 512345

    1 4 0

    2 0

    1 2 0

    4 0

    6 0

    8 0

    1 0 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • Indeks :10B

    75 50 30 0Faktor (k)

    Ceiling30 10 50 30 10 30 10 0 Wall10 10 10 0 Floor

    Faktor Refleksi Efisiensi0.230 0.210 0.255 0.232 0.210 0.227 0.206 0.186 0.60 (J)0.291 0.275 0.312 0.284 0.268 0.283 0.265 0.245 0.80 (I)0.325 0.310 0.340 0.318 0.302 0.315 0.299 0.279 1.00 (H)0.355 0.337 0.366 0.440 0.328 0.338 0.326 0.306 1.25 (G)0.378 0.352 0.382 0.363 0.346 0.361 0.345 0.326 1.50 (F)0.407 0.387 0.416 0.399 0.376 0.384 0.373 0.353 2.00 (E)0.432 0.412 0.445 0.421 0.405 0.414 0.402 0.382 2.50 (D)0.451 0.421 0.459 0.425 0.418 0.428 0.412 0.392 3.00 (C)0.469 0.454 0.475 0.442 0.441 0.443 0.434 0.416 4.00 (B)

    0.483 0.446 0.488 0.466 0.450 0.454 0.443 0.423 5.00 (A)

    F L 2 0 w x 1 0 . 7

    0 1 2 3 4 512345

    1 4 0

    2 0

    1 2 0

    4 0

    6 0

    8 0

    1 0 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

    F L 2 0 w x 2 0 . 7

    0 1 2 3 4 512345

    1 4 0

    2 0

    1 2 0

    4 0

    6 0

    8 0

    1 0 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • Indeks :13

    75 50 30 0Faktor (k)50 30 10 50 30 10 30 10 0

    10 10 10 0Faktor Refleksi Efisiensi

    0.265 0.233 0.213 0.258 0.235 0.213 0.230 0.209 0.179 0.60 0.322 0.294 0.278 0.315 0.287 0.271 0.286 0.268 0.247 0.80 0.353 0.318 0.313 0.343 0.321 0.305 0.318 0.302 0.282 1.00 0.382 0.352 0.340 0.369 0.347 0.331 0.341 0.329 0.309 1.25 0.405 0.381 0.355 0.385 0.366 0.369 0.364 0.348 0.329 1.50 0.433 0.412 0.390 0.413 0.402 0.379 0.392 0.376 0.356 2.00 0.465 0.435 0.415 0.448 0.424 0.408 0.417 0.405 0.385 2.50 0.481 0.454 0.474 0.461 0.438 0.421 0.431 0.415 0.395 3.00 0.499 0.472 0.457 0.478 0.455 0.444 0.444 0.437 0.417 4.00

    0.511 0.484 0.469 0.491 0.464 0.453 0.457 0.446 0.426 5.00

    F L 2 0 w x 2 0 . 7

    0 1 2 3 4 512345

    1 4 0

    2 0

    1 2 0

    4 0

    6 0

    8 0

    1 0 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

    F L 2 0 w x 1 0 . 7 5

    0 1 2 3 4 512345

    3 5 0

    5 0

    3 0 0

    1 0 0

    1 5 0

    2 0 0

    2 5 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • Ceiling 75 50 30 0Wall 50 30 10 50 30 10 30 10 0Floor 10 10 10 0

    Efisiensi Faktor Refleksi(J) 0.329 0.282 0.253 0.322 0.288 0.252 0.277 0.250 0.241(I) 0.407 0.357 0.330 0.392 0.347 0.322 0.347 0.317 0.308(H) 0.445 0.402 0.376 0.434 0.394 0.368 0.388 0.358 0.350(G) 0.489 0.447 0.412 0.466 0.428 0.398 0.421 0.343 0.388(F) 0.526 0.483 0.440 0.496 0.482 0.426 0.455 0.423 0.417(E) 0.573 0.529 0.487 0.546 0.509 0.472 0.493 0.461 0.452(D) 0.614 0.563 0.251 0.584 0.545 0.508 0.531 0.503 0.493(C) 0.640 0.594 0.539 0.608 0.568 0.532 0.552 0.525 0.515(B) 0.676 0.627 0.590 0.642 0.596 0.570 0.581 0.560 0.553

    (A) 0.696 0.653 0.615 0.659 0.619 0.590 0.599 0.581 0.592

    F L 2 0 w x 1 0 . 7 5

    0 1 2 3 4 512345

    3 5 0

    5 0

    3 0 0

    1 0 0

    1 5 0

    2 0 0

    2 5 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • Indeks :14

    Faktor (k)Ceiling 75 50 30Wall 50 30 10 50 30 10 30 10Floor 10 10 10

    Efisiensi Faktor Refleksi 0.60 (J) 0.421 0.359 0.312 0.412 0.361 0.311 0.342 0.713 0.80 (I) 0.522 0.440 0.620 0.508 0.647 0.410 0.446 0.413 1.00 (H) 0.574 0.518 0.679 0.559 0.547 0.475 0.500 0.469 1.25 (G) 0.626 0.572 0.536 0.603 0.558 0.520 0.521 0.575 1.50 (F) 0.671 0.614 0.584 0.639 0.576 0.553 0.583 0.550 2.00 (E) 0.729 0.679 0.626 0.703 0.657 0.614 0.641 0.608 2.50 (D) 0.793 0.725 0.678 0.754 0.707 0.671 0.693 0.667 3.00 (C) 0.814 0.761 0.714 0.780 0.735 0.697 0.719 0.688 4.00 (B) 0.860 0.805 0.765 0.821 0.773 0.749 0.758 0.736

    5.00 (A) 0.885 0.836 0.791 0.844 0.799 0.768 0.779 0.758

    F L 2 0 w x 2 0 . 7 5

    0 1 2 3 4 512345

    3 5 0

    5 0

    3 0 0

    1 0 0

    1 5 0

    2 0 0

    2 5 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • 000

    Faktor Refleksi0.2880.3880.4440.4900.5250.5830.6420.6630.711

    0.733

    Arus nominal dari kabel-kabel dengnan suhu penghantar yang diijinkan maksimum

    F L 2 0 w x 2 0 . 7 5

    0 1 2 3 4 512345

    3 5 0

    5 0

    3 0 0

    1 0 0

    1 5 0

    2 0 0

    2 5 0

    M o d e l J e n i s A r m a t u r d

    L u x

    ( m )

  • 1 2 3 4 5Pelayanan terus menerus

    mm A A A A

    Kabel-kabel berurat tunggal1.5 12 10 13 102.5 17 16 18 164 23 20 24 206 30 25 31 2510 41 36 43 3616 54 50 59 5025 71 63 80 8035 86 80 99 10050 106 100 125 12570 132 125 160 16095 160 160 200 200120 185 180 235 224150 211 200 280 250185 240 224 325 300240 280 250 395 355*)300 325 300 480 500*)

    Kabel-kabel berurat dua1.5 10 10 11 102.5 15 16 16 164 20 20 20 206 25 25 26 2510 35 36 34 3616 45 36 51 5025 59 50 69 63

    Kabel-kabel berurat tiga atau empat1.5 8 6 8.5 62.5 12 10 12 104 16 16 17 166 21 20 22 2010 28 25 32 2516 38 36 43 3625 50 50 61 6335 61 63 78 8050 74 63 100 10070 92 80 126 12595 112 100 161 160

    60oC padasuhu ruang 45oC

    Luas Penam-pang nominal dari penghan-tar

    tembaga

    Pelayanan waktu singkat 30 menit

    Arus mak- simum yang

    diijinkan

    Arus kerja pengaman lebur

    Arus mak- simum yang

    diijinkan

    Arus kerja pengaman lebur

  • 120 130 125 195 200Kabel-kabel berurat 5 sampai 24

    5 8 6 8.5 67 7 6 8 68 7 6 7 610 6.5 6 7 6

    14 6 6 6.5 6 12 5.5 6 6 6

    16 5 4 5 419 5 4 5 421 4.5 4 5 4

    24 4.5 4 4.5 4

    *) Pengaman lebur dengan arus kerja pengaman lebur yang lebih dari 320 Amp dan boleh digunakan hanya dengan persetujuan khusus

    x 1.5

  • Biro Klasifikasi Indonesia

    6 7

    A A

    Kabel-kabel berurat tunggal16 1022 2030 2540 3655 5075 63100 100124 125155 160194 200233 224278 250325 300370 350*)449 425*)503 500*)

    Kabel-kabel berurat dua12 1919 5025 5934 6545 5065 6688 59

    Kabel-kabel berurat tiga atau empat10 1017 1622 2029 2540 3555 5073 6991 80115 100144 125174 160

    Pelayanan memerlukan lama pembebanan di dalam periode

    penyedian total 10 menitArus mak- simum yang

    diijinkan

    Arus kerja pengaman lebur

  • 204 200Kabel-kabel berurat 5 sampai 24

    10 109 6

    8.5 68 6

    7.5 67 6

    6.5 66.5 66 6

    5.5 6

    *) Pengaman lebur dengan arus kerja pengaman lebur yang lebih dari 320 Amp dan boleh digunakan

  • DESIGN IV : MACHINERY AND ELEcTRICAL SYSTEMDEPARTMENT OF MARINE ENGINEERINGFACULTY OF MARINE TECHNOLOGY - ITS

    Doc. No. 02 - 42 12 140 - EL

    Rev Date Explanation Done By Sign Approved ByName SupervisorAtandho Gama M. Adi Kurniawan, ST, MT.

    TECHNICAL SPECIFICATION FOR LIGHTNING AND ELECTRICAL TERMINAL

  • DESIGN IV : MACHINERY AND ELEcTRICAL SYSTEMDEPARTMENT OF MARINE ENGINEERINGFACULTY OF MARINE TECHNOLOGY - ITS

    Approved By SignSupervisorAdi Kurniawan, ST, MT.

    TECHNICAL SPECIFICATION FOR LIGHTNING AND

  • IsiperhitunganintensitasSheet1Cover