Publication 11.2011

35-1150 kV

315-3500 A

Page 2: document-121-1358167669

"IZOLYATOR" PLANT performs design, manufacturing, warranty and post�warranty service of high�voltagebushings for various applications.

The enterprise is the main supplier of high�voltage bushings for power industry in Russia and CIS countries.

Hundreds of thousands of bushings were manufactured and are in operation now.

Production program:

bushings from 35 to1150 kV for powertransformers and shuntreactors

bushings from 110 to500 kV for cable con-nection of transformers

wall bushings from 66to 220 kV

high current bushingsfrom 20 to 35 kV fortransformers�to�busbarconnection

bushings from 35 to 220 kV for high voltage circuit�breakers

220 kV bushings for com-plete SF6 insulatedswitchgears

The bushings of any climatic�dependent design version are available.

All the bushings are interchangeable with manufactured previously in regard of overall dimensions and connectingdimensions.

Quality management sys-tem according to require-ments of internationals t a d a r d EN ISO 9001:2008 is oper-ating at the plant.

All the bushings are certi-fied for compliance withState Standard GOST10693�81 and other regula-tory documents of Russia'sGosstandard.The bushings also complywith Standard IEC 60137.

Page 3: document-121-1358167669

1

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

3Design of bushing with condenser � type RIP � insulation.

II TEST TAP (side view)

Kinds of insulation

High�voltage bushings for power trans-

formers and reactors are produced with

two kinds of internal condenser�type insu-

lation: RIP (Resin Impregnated Paper) and

OIP (Oil Impregnated Paper).

Design of the bushing withRIP�insulation

Internal RIP�insulation is the main

structural part of the bushing; it is the insu-

lating body formed by winding dielectric

paper divided by conductive grading layers

on the central tube (figure 1).

The grading layers serve for optimal

distribution of electric field in radial and

axial directions, providing the highest

dielectric strength values of both internal

and external insulation, including the lower

part of the bushing placed inside the

transformer or reactor.

RIP�insulation is manufactured by wind-

ing crepe paper produced by «Weidmann

Systems International AG» (Switzerland) or

«Karl Fislage GmbH & Co.

KG»(Germany), then the paper is impreg-

Figure 1

II

SHED PROFILE

Geometric dimensions may vary,providing required creepage dis-tance.

I

I

Page 4: document-121-1358167669

nated with epoxy compound under vacuum and

subsequently solidified under pressure.

RIP�insulation has practically no gas inclu-

sions.

After thermal treatment and varnishing of

external surface, the insulating body forms a

solid kernel, and a coupling is mounted on it

under press fit.

The main advantages of RIP�insulation are

high reliability and long service life performance

due to its low dielectric losses, low level of par-

tial discharges in the insulation, and high ther-

mal stability.

External insulation covers the upper part of

the insulating body located outside the trans-

former or reactor and is made of porcelain or

silicone rubber.

Porcelain insulation is the porcelain housing

with the flange mounted on its top. The joints

between the porcelain housing, connecting

sleeve and the upper flange are sealed by gas-

kets made of oil resistant rubber.

Compression of gaskets is provided by the

spring tightening device ensuring stable strain

in case of length change of the insulating body

and porcelain housing in the range from �60 to

+120°С.

The space between the insulating body and

porcelain housing is stuffed with filler for pro-

tection from moistering.

The design of the bushing ensures its

reliable leak�tightness.

Leak�tightness of the transformer is ensured

even in case of damaging the bushing's porce-

lain housing. The spring tightening device is

placed under the protective casing,

leak�tightness between the central tube and the

upper flange is provided by two rubber O�ring

gaskets.

Silicone rubber insulation is offered as an

alternative to porcelain insulation at bushings

with internal RIP � insulation (figure 2).

The bushings equipped with such insulation

have the following advantages:

absolutely dry, explosion�proof design requir-

ing no maintenance;

high tracking resistance, hydrophobic behav-

ior of external insulation preventing

flash�over without cleaning its surface, even

in case of simultaneous exposure to moisture

and contamination;

external insulation fins having constant or

varying spread, according to individual cus-

tomer's requirements;

seismic load resistance;

damage�proof external insulation made of

organic�silicon composition, reducing risk of

damage during transportation and mounting;

minimum weight;

environmental safety;

stability of properties during the whole oper-

ation life.

Silicone rubber insulation is moulded of

elastic material created on the basis of

proprietary organic�silicon compositions of

RTV�2 type by «Wacker Chemie GmbH»,

Germany.

Moulded and polymerization takes place

directly at the insulating body, thus completely

excluding usage of filler including the trans-

former oil. Besides, no spring tightening device

is needed.

Pressure compensator is intended for

compensating changes of oil volume caused by

temperature variations. It is used only in the

bushings with external porcelain insulation

where transformer oil is used as a filling materi-

al. The compensator is provided by the gas

cushion located in the upper part of the bush-

2

Page 5: document-121-1358167669

3

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

Figure 2

II

I

II TEST TAP(except ГКПТIII�90�110/2500)

I

Design of bushing with silicone rubber insulation.

ing.

Oil level is checked visually through the

oil�level sight glass at the protective housing.

Test tap connected to the last grading

layer of the insulating body serves for check-

ing the internal insulation. The test tap shall

be obligingly grounded when measurements

are not performed (figures 1,2).

The design of test tap equipped with

spring�loaded contact anticipates connection

of diagnostic tools during operation.

Transportation and storage of the bush-

ing require protection against moisture and

mechanical damage of the lower part of the

varnished surface of the body, submerged in

transformer oil during operation. Polyethylene

cover with silica gel desiccant and bakelite or

tin cylinder is used for this purpose.

Shield installed at the bottom part of the

bushing and intended for the electric field

compensation

SHED PROFILE

Geometric dimensions may vary,providing required creepage dis-tance.

Page 6: document-121-1358167669

4

Figure 3

I

I TEST TAP (side view)

Design of bushing with condenser�type OIP �insulation and gas cushion.

Design of the bushing with OIP�insulation

Internal OIP insulation is the main structuralpart of the bushing. It is the insulating body formedby winding dielectric paper divided by conductivegrading layers on the central or winding tube (fig-ure 3).

The grading layers serve for optimal distributionof electric field in radial and axial directions, provid-ing the highest dielectric strength values of bothinternal and external insulation, including the lowerpart of the bushing placed inside the transformer orreactor.

For bushings with pulled�through type connec-tion*, which have high current rating, winding ismade around a separate tube so that a channel isformed between the central tube and the windingtube, where oil circulates to cool and level the tem-perature of the insulation body during operation.

For bushings with other type of connection, theinside space of the central tube serves as such achannel.

In 750 kV bushings for reactors and 1150 kVbushings for transformers (figure 4), internal insu-lation is divided into two parts � the inner and theouter insulation, so that additional oil circulationchannel is formed to achieve better cooling.

Prior to assembly the frame is vacuum dried.After assembly the bushing is vacuum treated andimpregnated with transformer oil. Thermo�vacuumtreatment parameters ensure high reliability and

* See section "Connection".

Page 7: document-121-1358167669

5

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

Figure 4

1150kV bushing minus upper andbottom shield.

long�term performance of insulation during operation of the bushing.

External porcelain insulation consists of the upper and bottomhousings. Together with the coupling and the protective casing,they form a hermetically sealed oil�filled cavity where the insulationbody is placed.

The top and bottom butt ends of the cavity are covered byflanges. The joints between the porcelain housings, coupling andprotective casing are sealed by gaskets made of oil resistant rub-ber. Stable compression of gaskets is provided by spring tighteningdevice, compensating the length change of the parts when temper-ature varies in the range from �60 to +120°С. Compression of gas-kets sealing joints between the central tube and the flange isensured by bolts.

Pressure compensator is intended for compensation ofchanges of oil volume caused by temperature variations and islocated in the upper part of the bushing or in the external pressuretank mounted at the transformer tank lid.

Gas cushion or leak�proof metal bellows may be used as com-pensator.

Oil level in the bushings with gas cushion is checked visuallythrough the oil�level sight glass at the protective housing.

Leak�tightness of the bushing with bellows compensator ischecked by pressure indicator � manometer.

Test tap connected to the last grading layer of the insulatingbody serves for checking the internal insulation. The test tap shallbe obligingly grounded when measurements are not performed (fig.3).

The shield for leveling electric field is mounted in the lower partof the bushing, except the bushings for reactors and some types oftransformers which have the shield as integral part of the design.

The shield is not mounted at the upper part of the bushings(except 1150 kV bushings): special tests confirmed absence ofcorona discharge for voltage which is 10% higher than the highestoperating phase voltage.

ModificationEarthquake�resistant bushings marked with "C" letter were addi-

tionally tested for maintaining operability in case of earthquakeshaving magnitude up to 9 according to MSK�64 scale, and guaran-tee keeping of operating parameters in case of earthquakes.

High�altitude bushings marked with "в" letter are intended forusage at altitude over 1000 m above sea level.

Page 8: document-121-1358167669

6

Figure 5 Current�carrying system of pulled�through typebushings.

Kinds of bottom�connected bushings.Figure 6

Table 1

Rated current, A Cable cross�section, mm2

400 1 x 150500 1 x 185630 1 x 300800 1 x 300

1 х 5001000 2 х 300

3 х 1851250 3 х 2401600 4 х 3002000 4 x 4002500 4 х 500

ConnectionDepending on the method of connec-

tion to the transformer coil or reactor

coil, the bushings are classified as

follows.

1. Pulled�through type bushings,

which are connected by means of

pulling the copper cable of the tap (see

table 1) with soldered contact stud

through the central tube of the bushing

(figure 5).

The contact stud is supplied with the

bushing and is soldered to the tap at the

place of installation of the bushing.

2. The bottom�connected bushings,

featuring connection implemented by

clamping the tap cable with special bolts

(figures 6a, b) or nuts (figure 6c) at the

bottom contact tip of the bushing.

The bottom�connected bushings

with plug�in connector, featuring con-

nection implemented by inserting the

plug located at the bottom end of the

bushing into the socket at the end of the

tap (figure 6d).

In the first case, the tap cable from

the transformer winding serves as the

conductor, while in the second case �

the bushing's central tube.

а b

dc

BOTTOM PART OF PULLED-THROUGH

TYPE BUSHING

Page 9: document-121-1358167669

7

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

Figure 7 Kinds of termi-nal plates.

Figure 8 Key to bushing designationcode.

For connecting lead�in from the busbar, the terminal is

screwed to the threading of the upper contact stud (figure 7).

The terminal is supplied together with the bushing and is

fixed to the contact stud at the place of installation.

Technical dataThe main information for choosing the bushing is con-

tained in its code designation (figure 8).

Technical specifications, overall, fitting and connecting

dimensions of the bushings are presented at figures 5�7 and

in table 2.

а

b

c

d

e

в � High altitude

Г � Hermetic design version

Д � Extended lower part (standard length by default)

К � Internal RIP�insulation

М � Internal OIP�insulation

П � External silicone rubber insulation (porcelain by default)

Р � Bushing for shunt reactors

Т � Bushing for transformers (autotransformers)

III�60�220/2000Rated current, A

Rated voltage, kVLimit angle of vertical orientation, angular degree

External insulation category depending on ambient contamination, according to GOST 9920�89 and Standard IEC 60137

80

Page 10: document-121-1358167669

8

TOP VIEWEnlarged

Table 2. Part 1 of 7

Bushing typeDrawing No.

Test voltage, kV

1 m

inut

e, 5

0 Hz

Switc

hing

impu

lse

250

/250

0 μs

Rate

d vo

ltage

, kV

Phas

e to

ear

th v

olta

ge, k

V

Type

of i

nter

nal i

nsul

atio

n

Rate

d cu

rren

t, A

Cree

page

dis

tanc

e, m

m

Test

can

tilev

er lo

ad, N

Wei

ght,

kg

Conn

ectio

n ty

pe, f

igur

e N

o.

Ligh

tnin

g im

puls

e 1.

2/50

μs

Technical data of high voltage bushings.

40.5 kV bushings

ГКТIII-60-40,5/3500ИВУЕ.686351.154 RIP 40,5 25 3500 95 — 190 1160 3150 95 7e

36 kV bushings

ГКТIV-60-36/1250ИВУЕ.686351.168 RIP 72,5 42 1250 140 � 325 1800 2000 110 5,7e

52 kV bushings

ГКТIV-60-52/630ИВУЕ.686351.167 RIP 52 30 630 95 — 250 1900 1600 60 5

ГКТIV-60-52/800ИВУЕ.686351.167-01 RIP 52 30 800 100 — 250 1900 1250 60 5

ГКТПIV-90-52/2000ИВУЕ.686351.257 RIP 52 30 2000 70 — 170 1650 1250 50

72.5 kV bushings

ГКТIII-60-72,5/630ИВУЕ.686351.101 RIP 72,5 42 630 140 — 325 1810 1000 62 5,7а

ГКТПIII-90-72,5/630ИВУЕ.686351.201 RIP 72,5 44 630 140 — 325 1800 2000 29,5 5,7а

ГКТIII-60-72,5/2000ИВУЕ.686351.102 RIP 72,5 44 2000 140 — 325 1810 3150 143 5,7e

ГКТПIII-90-72,5/2000ИВУЕ.686351.202 RIP 72,5 44 2000 140 — 325 1800 3150 78 5,7e

126 kV bushings

ГКТIII�60�126/800ИВУЕ.686352.103 RIP 126 73 800 230 � 550 3150 1250 89 5,7а

ГКТПIII�90�126/800ИВУЕ.686352.203 RIP 126 73 800 230 � 550 3150 1250 42 5,7а

ГКТIII�60�126/800ИВУЕ.686352.303 RIP 126 73 800 230 � 550 3150 1250 86 5,7а

ГКТIII�60�126/800ИВУЕ.686352.103�01 RIP 126 73 800 230 � 550 3150 1250 87 5,7а

Page 11: document-121-1358167669

Dimensions, mm

Bushing typeDrawing No.

leng

th o

f bus

hing

leng

th o

f bot

tom

part

curr

ent t

rans

-fo

rmer

leng

thhe

ight

of c

entra

lfla

nge

arci

ng

dist

ance

trans

form

er ta

ple

ngth

hous

ing/

shie

lddi

amet

erm

ax.

pass

�thr

ough

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 lnholes n1holes

Overall, fitting and connecting dimensions of high voltage bushings.

Mounting flange* Pulled � throungh type connection

Bottomshield

9

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

40.5 kV bushings

ГКТIII-60-40,5/3500ИВУЕ.686351.154 1645 670 400 125 460 — 183 106 270 225 20/6 25 ― — — — — ― ―

36 kV bushing

ГКТIV-60-36/1250ИВУЕ.686351.168 1480 470 300 460 183 106 290 250 15/8 ― ― ― ― ― ― ―

52 kV bushings

ГКТIV-60-52/630ИВУЕ.686351.167 1360 550 300 125 620 1365 186 106 290 250 15/8 ― ― 50 80 30

ГКТIV-60-52/800ИВУЕ.686351.167-01 1400 315 125 620 1130 186 106 290 250 15/8 25 ― ― 5 36 50 80 30

ГКТПIV-90-52/2000ИВУЕ.686351.257 1385 500 250 115 560 ― 106 225 200 15/6 ― ― ― ― ― ― ―

72.5 kV bushings

ГКТIII-60-72,5/630ИВУЕ.686351.101 1360 315 125 620 1130 186 106 350 300 20/8 ― ― 30 36 50 80 30

ГКТПIII-90-72,5/630ИВУЕ.686351.201 1235 315 607 970 148 106 350 300 20/8 ― ― 30 36 50 80 30

ГКТIII-60-72,5/2000ИВУЕ.686351.102 1980 785 300 620 1643 255 165 528 480 24/9 60 165 32/4 89 ― ― ―

ГКТПIII-90-72,5/2000 ИВУЕ.686351.202 1825 785 500 598 1470 220 165 528 480 24/9 60 165 32/4 89 ― ― ―

126 kV bushings

ГКТIII�60�126/800ИВУЕ.686352.103 2080 660 200 125 1000 1850 186 106 350 300 24/8 25 � � 30 36 50 80 30

ГКТПIII�90�126/800ИВУЕ.686352.203 2030 660 200 125 1055 1770 106 350 300 24/8 25 � � 30 37 50 80 30

ГКТIII�60�126/800ИВУЕ.686352.303 2080 660 200 1000 1850 186 106 350 300 24/8 � � 30 36 50 80 30

ГКТIII�60�126/800ИВУЕ.686352.103�01 2190 770 300 125 1000 1960 186 106 290 250 15/8 25 � � 30 36 50 80 30

Page 12: document-121-1358167669

10

TOP VIEWEnlarged

Table 2. Part 2 of 7

Bushing typeDrawing No.

Test voltage, kV

1 m

inut

e, 5

0 Hz

Switc

hing

impu

lse

250

/250

0 μs

Rate

d vo

ltage

, kV

Phas

e to

ear

th v

olta

ge, k

V

Type

of i

nter

nal i

nsul

atio

n

Rate

d cu

rren

t, A

Cree

page

dis

tanc

e, m

m

Test

can

tilev

er lo

ad, N

Wei

ght,

kg

Conn

ectio

n ty

pe, f

igur

e N

o.

Ligh

tnin

g im

puls

e 1.

2/50

μs

Technical data of high voltage bushings.

126 kV bushings (continuation)

ГКТПIII�90�126/800ИВУЕ.686352.203�01 RIP 126 73 800 230 � 550 3150 1250 40 5,7а

ГКТIII�60�126/800ИВУЕ.686352.303�01 RIP 126 73 800 230 � 550 3150 1250 85 5,7а

ГКТIII�60�126/800ИВУЕ.686352.103�02 RIP 126 73 800 230 � 550 3150 1250 92 5,7а

ГКТПIII�90�126/800ИВУЕ.686352.203�02 RIP 126 73 800 230 � 550 3150 1250 44 5,7а

ГКТIII�60�126/800ИВУЕ.686352.303�02 RIP 126 73 800 230 � 550 3150 1250 88 5,7а

ГКТIII�60�126/800ИВУЕ.686352.103�03 RIP 126 73 800 230 � 550 3150 1250 102 5,7а

ГКТПIII�90�126/800 ИВУЕ.686352.203�03 RIP 126 73 800 230 � 550 3150 1250 55 5,7а

ГКТIII�60�126/800ИВУЕ.686352.303�03 RIP 126 73 800 230 � 550 3150 1250 98 5,7а

ГКТIV�60�126/800ИВУЕ.686352.103�04 RIP 126 73 800 230 � 550 3900 1250 112 5,7а

ГКТПIII�90�126/800 ИВУЕ.686352.203�04 RIP 126 73 800 230 � 550 3150 1250 41 5,7а

ГКТIII�60�126/800ИВУЕ.686352.303�04 RIP 126 73 800 230 � 550 3900 1250 100 5,7а

ГКТПIII-90-126/800ИВУЕ.686352.203-05 RIP 126 73 800 230 — 550 3150 1250 41 5,7а

ГКТПIII-90-126/800ИВУЕ.686352.203-06 RIP 126 73 800 230 — 550 3150 1250 39 5,7а

ГКТПIV-90-126/800ИВУЕ.686352.203-07 RIP 126 800

ГКТIV-60-126/800ИВУЕ.686352.303-05 RIP 126 73 800 230 — 550 3150 1250 98 5,7а

ГКТIII-60-126/2000ИВУЕ.686352.104 RIP 126 73 2000 230 — 550 3150 4000 155 5,7e

Page 13: document-121-1358167669

Dimensions, mm

Bushing typeDrawing No.

leng

th o

f bus

hing

leng

th o

f bot

tom

part

curr

ent t

rans

-fo

rmer

leng

thhe

ight

of c

entra

lfla

nge

arci

ng

dist

ance

trans

form

er ta

ple

ngth

hous

ing/

shie

lddi

amet

erm

ax.

pass

�thr

ough

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 lnholes n1holes

Overall, fitting and connecting dimensions of high voltage bushings.

11

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

126 kV bushings

ГКТПIII�90�126/800ИВУЕ.686352.203�01 2140 770 300 125 1055 1880 106 290 250 15/8 25 � � 30 37 50 80 30

ГКТIII�60�126/800ИВУЕ.686352.303�01 2190 770 300 1000 1960 186 106 290 250 15/8 � � 30 36 50 80 30

ГКТIII�60�126/800 ИВУЕ.686352.103�02 2390 970 500 125 1000 2160 186 106 290 250 15/8 25 � � 30 36 50 80 30

ГКТПIII�90�126/800ИВУЕ.686352.203�02 2340 970 500 125 1055 2080 106 290 250 15/8 25 � � 30 37 50 80 30

ГКТIII�60�126/800ИВУЕ.686352.303�02 2390 970 500 1000 2160 186 106 290 250 15/8 � � 30 36 50 80 30

ГКТIII�60�126/800ИВУЕ.686352.103�03 2390 970 200 125 1000 2160 186 106 535 480 24/9 25 � � 30 36 50 80 30

ГКТПIII�90�126/800 ИВУЕ.686352.203�03 2340 970 200 125 1055 2080 106 535 480 24/9 25 � � 30 37 50 80 30

ГКТIII�60�126/800ИВУЕ.686352.303�03 2390 970 200 1000 2160 186 106 535 480 24/9 � � 30 36 50 80 30

ГКТIV�60�126/800ИВУЕ.686352.103�04 2390 770 300 125 1200 2160 186 106 290 250 15/8 25 � � 30 36 50 80 30

ГКТПIII�90�126/800 ИВУЕ.686352.203�04 1980 610 300 125 1055 1715 106 290 250 15/8 25 � � 30 37 50 80 30

ГКТIII�60�126/800ИВУЕ.686352.303�04 2390 770 300 1200 2160 186 106 290 250 15/8 � � 30 36 50 80 30

ГКТПIII-90-126/800ИВУЕ.686352.203-05 1980 610 300 1055 1715 148 106 290 250 15/8 25 ― ― 30 37 50 80 30

ГКТПIII-90-126/800ИВУЕ.686352.203-06 1845 475 170 1055 1630 148 106 290 250 15/8 25 ― ― 30 37 50 80 30

ГКТПIV-90-126/800ИВУЕ.686352.203-07

ГКТIV-60-126/800ИВУЕ.686352.303-05 2280 660 200 1200 2050 186 106 350 300 24/8 ― ― 30 36 50 80 30

ГКТIII-60-126/2000ИВУЕ.686352.104 2275 720 400 960 1920 260 165 420 380 22/12 60 165 32/4 89 ― ― ―

Mounting flange* Bottomshield

Pulled � throungh type connection

Page 14: document-121-1358167669

12

TOP VIEWEnlarged

Table 2. Part 3 of 7

Bushing typeDrawing No.

Test voltage, kV

1 m

inut

e, 5

0 Hz

Switc

hing

impu

lse

250

/250

0 μs

Rate

d vo

ltage

, kV

Phas

e to

ear

th v

olta

ge, k

V

Type

of i

nter

nal i

nsul

atio

n

Rate

d cu

rren

t, A

Cree

page

dis

tanc

e, m

m

Test

can

tilev

er lo

ad, N

Wei

ght,

kg

Conn

ectio

n ty

pe, f

igur

e N

o.

Ligh

tnin

g im

puls

e 1.

2/50

μs

Technical data of high voltage bushings.

126 kV bushings (continuation)

ГКТПIII-90-126/2000ИВУЕ.686352.204 RIP 126 73 2000 230 — 550 3150 4000 85 5,7e

ГКТIII-60-126/2000ИВУЕ.686352.104-01 RIP 126 73 2000 230 — 550 3150 4000 165 5,7e

ГКТПIII-90-126/2000ИВУЕ.686352.204-01 RIP 126 73 2000 230 — 550 3150 4000 92 5,7e

ГКТIV-60-126/2000ИВУЕ.686352.104-02 RIP 126 73 2000 230 — 550 3900 4000 200 5,7e

ГКТПIV-90-126/2000ИВУЕ.686352.204-02 RIP 126 73 2000 230 — 550 3900 4000 94 5,7e

ГКТIV-60-126/2000ИВУЕ.686352.104-03 RIP 126 73 2000 230 — 550 3900 4000 205 5,7e

ГКТПIV-90-126/2000ИВУЕ.686352.204-03 RIP 126 73 2000 230 — 550 3900 4000 100 5,7e

ГКТIV-60-126/2000ИВУЕ.686352.104-04 RIP 126 73 2000 230 — 550 3900 4000 202 5,7e

ГКТПIV-90-126/2000ИВУЕ.686352.204-04 RIP 126 73 2000 230 — 550 3900 4000 95 5,7e

ГКТIII-60-126/2000ИВУЕ.686352.104-05 RIP 126 73 2000 230 — 550 3150 4000 172 5,7e

ГКТIII-60-126/2000ИВУЕ.686352.104-06 RIP 126 73 2000 230 — 550 3150 4000 182 5,7e

ГКТIII-60-126/2000ИВУЕ.686352.106 RIP 126 73 2000 230 —

ГКТIII-60-126/2000ИВУЕ.686352.107 RIP 126 73 2000 230 — 550 3150 1600 125 7e

ГКТПIII-90-126/2500ИВУЕ.686352.207 RIP 126 76 2500 230 — 550 3150 4000 75 7e

ГКТIII-60-126/2000ИВУЕ.686352.107-01 RIP 126 73 2000 230 — 550 3150 1600 130 7e

ГКТПIII-90-126/2500ИВУЕ.686352.207-01 RIP 126 76 2500 230 — 550 3150 4000 78 7e

ГКТIII-60-126/2000ИВУЕ.686352.150 RIP 126 2000 —

ГКТПIV-90-126/1250ИВУЕ.686352.208 RIP 126 1250 —

ГКТПIII-90-126/800ИВУЕ.686352.248 RIP 126 76 800 230 — 550 3150 3150 40 5,7а

Page 15: document-121-1358167669

Dimensions, mm

Bushing typeDrawing No.

leng

th o

f bus

hing

leng

th o

f bot

tom

part

curr

ent t

rans

-fo

rmer

leng

thhe

ight

of c

entra

lfla

nge

arci

ng

dist

ance

trans

form

er ta

ple

ngth

hous

ing/

shie

lddi

amet

erm

ax.

pass

�thr

ough

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 lnholes n1holes

Overall, fitting and connecting dimensions of high voltage bushings.

13

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

126 kV bushings

ГКТПIII-90-126/2000ИВУЕ.686352.204 2210 720 400 1045 1890 220 165 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТIII-60-126/2000ИВУЕ.686352.104-01 2575 1020 400 960 2220 260 165 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТПIII-90-126/2000ИВУЕ.686352.204-01 2510 1020 400 1045 2190 220 165 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТIV-60-126/2000ИВУЕ.686352.104-02 2620 720 400 1305 2265 260 165 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТПIV-90-126/2000ИВУЕ.686352.204-02 2460 720 400 1295 2140 220 165 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТIV-60-126/2000ИВУЕ.686352.104-03 2920 1020 400 1305 2565 260 165 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТПIV-90-126/2000ИВУЕ.686352.204-03 2760 1020 400 1295 2440 220 165 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТIV-60-126/2000ИВУЕ.686352.104-04 2670 770 400 1305 2315 260 165 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТПIV-90-126/2000ИВУЕ.686352.204-04 2510 770 400 1295 2190 220 165 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТIII-60-126/2000ИВУЕ.686352.104-05 2575 1020 400 960 2220 260 165 528 480 24/9 60 165 32/4 89 ― ― ―

ГКТIII-60-126/2000ИВУЕ.686352.104-06 2575 1020 400 960 2220 260 165 690 650 24/12 60 165 32/4 89 ― ― ―

ГКТIII-60-126/2000ИВУЕ.686352.106

ГКТIII-60-126/2000ИВУЕ.686352.107 2422 925 300 125 1000 ― 105 290 250 15/8 25 210 190 ― ― ― ― ―

ГКТПIII-90-126/2500ИВУЕ.686352.207 2360 925 300 1055 ― 105 290 250 15/8 210 190 ― ― ― ― ―

ГКТIII-60-126/2000 ИВУЕ.686352.107-01 2515 1020 500 125 1000 ― 105 290 250 15/8 25 210 190 ― ― ― ― ―

ГКТПIII-90-126/2500ИВУЕ.686352.207-01 2455 1020 500 1055 ― 105 290 250 15/8 210 190 ― ― ― ― ―

ГКТIII-60-126/2000ИВУЕ.686352.150

ГКТПIV-90-126/1250ИВУЕ.686352.208

ГКТПIII-90-126/800ИВУЕ.686352.248 2175 805 400 1055 1915 148 106 400 350 24/6 60 120 30

Mounting flange* Bottomshield

Pulled � throungh type connection

Page 16: document-121-1358167669

TOP VIEWEnlarged

Table 2. Part 4 of 7

Bushing typeDrawing No.

Test voltage, kV

1 m

inut

e, 5

0 Hz

Switc

hing

impu

lse

250

/250

0 μs

Rate

d vo

ltage

, kV

Phas

e to

ear

th v

olta

ge, k

V

Type

of i

nter

nal i

nsul

atio

n

Rate

d cu

rren

t, A

Cree

page

dis

tanc

e, m

m

Test

can

tilev

er lo

ad, N

Wei

ght,

kg

Conn

ectio

n ty

pe, f

igur

e N

o.

Ligh

tnin

g im

puls

e 1.

2/50

μs

Technical data of high voltage bushings.

145 kV bushings

ГКТIV-60-145/630ИВУЕ.686352.166 RIP 145 84 630 275 — 650 4495 3150 190 5

172 kV bushings

ГКТIII-60-172/800ИВУЕ.686352.109 RIP 172 100 800 275 — 650 3900 1250 190 5,7а

ГКТIII-60-172/800ИВУЕ.686352.109-01 RIP 172 100 800 275 — 650 3900 1250 195 5,7а

ГКТПIII-90-172/800ИВУЕ.686352.209 RIP 172 104 800 275 — 550 4250 4000 100 5,7а

ГКТIII-60-172/1000ИВУЕ.686352.111 RIP 172 104 1000 275 — 650 4250 4000 265 5,7c

ГКТIII-60-172/1000ИВУЕ.686352.111-01 RIP 172 104 1000 275 — 650 4250 4000 255 5,7c

ГКТIII-60-172/1000ИВУЕ.686352.112 RIP 172 104 1000 275 — 650 4250 4000 220 5,7c

ГКТIII-60-172/2000ИВУЕ.686352.110 RIP 172 104 2000 275 — 650 4320 5000 280 5,7e

ГКТПIII-90-172/2000ИВУЕ.686352.210 RIP 172 104 2000 275 — 650 4250 5000 160 5,7e

252 kV bushings

ГКТIII-60-252/1000ИВУЕ.686353.115 RIP 252 153 1000 460 — 1050 6300 1600 292 5,7b

ГКТIII-60-252/2000ИВУЕ.686353.114 RIP 252 146 2000 460 — 1050 6300 5000 455 5,7e

ГКТПIII-90-252/2000ИВУЕ.686353.214 RIP 252 146 2000 460 — 1050 6300 5000 270 5,7e

ГКТIII-60-252/2000ИВУЕ.686353.113 RIP 252 146 2000 460 — 1050 6300 4000 400 5,7e

ГКТПIII-90-252/2000ИВУЕ.686353.213 RIP 252 146 2000 460 — 1050 6300 5000 230 5,7e

ГКТПIV-90-252/2000ИВУЕ.686353.213-02 RIP 252 146 2000 460 — 1050 7900 5000 255 5,7e

ГКТIII-60-252/2000ИВУЕ.686353.113-01 RIP 252 146 2000 460 — 1050 6300 4000 427 5,7e

ГКТПIII-90-252/2000ИВУЕ.686353.213-01 RIP 252 146 2000 460 — 1050 6300 5000 250 5,7e

14

Page 17: document-121-1358167669

Hig

h v

olt

ag

e b

ush

ing

s fo

r p

ow

er

tra

nsf

orm

ers

an

d r

ea

cto

rs

Dimensions, mm

Bushing typeDrawing No.

leng

th o

f bus

hing

leng

th o

f bot

tom

part

curr

ent t

rans

-fo

rmer

leng

thhe

ight

of c

entra

lfla

nge

arci

ng

dist

ance

trans

form

er ta

ple

ngth

hous

ing/

shie

lddi

amet

erm

ax.

pass

�thr

ough

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 lnholes n1holes

Overall, fitting and connecting dimensions of high voltage bushings.

15

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

Mounting flange* Bottomshield

Pulled � throungh type connection

145 kV bushings

ГКТIV-60-145/630 ИВУЕ.686352.166 2640 800 300 1380 2385 260 165 350 310 16/12 ― ― 5 56 70 130 30

172 kV bushings

ГКТIII-60-172/800ИВУЕ.686352.109 2695 850 300 1363 2435 260 165 350 310 22/12 ― ― 30 56 70 130 30

ГКТIII-60-172/800ИВУЕ.686352.109-01 2695 850 400 1363 2435 260 165 400 350 24/6 ― ― 30 56 70 130 30

ГКТПIII-90-172/800ИВУЕ.686352.209 2575 850 300 1400 2265 220 165 350 310 22/12 ― ― 30 56 70 130 30

ГКТIII-60-172/1000ИВУЕ.686352.111 2920 1075 300 1380 2670 260 165 670 620 24/9 ― ― 19/4 56 70 130 40

ГКТIII-60-172/1000ИВУЕ.686352.111-01 2920 1075 450 1380 2670 260 165 530 480 24/9 ― ― 19/4 56 70 130 40

ГКТIII-60-172/1000ИВУЕ.686352.112 3030 1180 300 1325 2770 260 165 670 620 24/9 ― ― 28/3 85 130 40

ГКТIII-60-172/2000ИВУЕ.686352.110 3125 1000 500 1475 2765 300 198 420 380 22/12 60 165 32/4 89 ― ― ―

ГКТПIII-90-172/2000ИВУЕ.686352.210 2960 1000 500 1450 2460 270 198 420 380 22/12 60 165 32/4 89 ― ― ―

252 kV bushings

ГКТIII-60-252/1000ИВУЕ.686353.115 3805 1025 400 1960 3490 450 400 22/12 60 165 30 56 ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.114 4800 1905 1140 2025 4470 276 198 760 720 24/16 90 251 32/4 89 ― ― ―

ГКТПIII-90-252/2000ИВУЕ.686353.214 4530 1905 1140 2100 4025 760 720 24/16 91 251 32/4 89 ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.113 4275 1380 600 2025 3945 276 198 600 560 24/16 90 251 32/4 89 ― ― ―

ГКТПIII-90-252/2000ИВУЕ.686353.213 4005 1380 600 2100 3500 600 560 24/16 91 251 32/4 89 ― ― ―

ГКТПIV-90-252/2000ИВУЕ.686353.213-02 4505 1380 700 2600 4000 600 560 24/16 91 251 32/4 89 ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.113-01 4275 1380 600 2025 3765 276 198 760 720 24/16 90 251 32/4 89 ― ― ―

ГКТПIII-90-252/2000 ИВУЕ.686353.213-01 4005 1380 600 2100 3500 760 720 24/16 91 251 32/4 89 ― ― ―

Page 18: document-121-1358167669

416

TOP VIEWEnlarged

Table 2. Part 5 of 7

Bushing typeDrawing No.

Test voltage, kV

1 m

inut

e, 5

0 Hz

Switc

hing

impu

lse

250

/250

0 μs

Rate

d vo

ltage

, kV

Phas

e to

ear

th v

olta

ge, k

V

Type

of i

nter

nal i

nsul

atio

n

Rate

d cu

rren

t, A

Cree

page

dis

tanc

e, m

m

Test

can

tilev

er lo

ad, N

Wei

ght,

kg

Conn

ectio

n ty

pe, f

igur

e N

o.

Ligh

tnin

g im

puls

e 1.

2/50

μs

Technical data of high voltage bushings.

252 kV bushings (continuation)

ГКТIII-60-252/2000ИВУЕ.686353.116 RIP 252 153 2000 460 — 1050 6300 2500 370 7c

ГКТПIII-90-252/2000ИВУЕ.686353.216 RIP 252 146 2000 460 — 1050 6300 5000 190 7c

ГКТIII-60-252/2000ИВУЕ.686353.117 RIP 252 153 2000 460 — 1050 6300 5000 390 5,7e

ГКТIII-60-252/2000ИВУЕ.686353.118 RIP 252 146 2000 460 — 1050 6300 4000 320 6а,7b

ГКТIII-60-252/2000ИВУЕ.686353.119 RIP 252 146 2000 460 — 1050 6300 4000 310 6а,7e

ГКТIII-60-252/2000ИВУЕ.686353.119-01 RIP 252 146 2000 460 — 1050 6300 4000 315 6а,7e

ГКТIV-60-252/2000ИВУЕ.686353.119-02 RIP 252 146 2000 460 — 1050 7900 4000 365 6а,7e

ГКТIII-60-252/2000ИВУЕ.686353.119-03 RIP 252 146 2000 460 — 1050 6300 4000 320 6а,7e

ГКТIII-60-252/2000ИВУЕ.686353.122 RIP 252 2000

ГКТIII-60-252/3150ИВУЕ.686353.153 RIP 252 152 3150 425 — 950 6300 4000 490 6а

ГКТIII-60-252/2000ИВУЕ.686353.164 RIP 252 146 2000 460 — 1050 6300 4000 310 6а,7c

ГКТIII-60-252/2000ИВУЕ.686353.164-01 RIP 252 146 2000 460 — 1050 6300 4000 315 6а,7c

ГКТIV-60-252/2000ИВУЕ.686353.164-02 RIP 252 146 2000 460 — 1050 7900 4000 365 6а,7c

ГКТIII-60-252/2000ИВУЕ.686353.164-03 RIP 252 146 2000 460 — 1050 6300 4000 320 6а,7c

ГКТПIV-90-252/1600ИВУЕ.686353.223 RIP 252 1600 —

ГКТПIV-90-252/800ИВУЕ.686353.249 RIP 252 146 800 460 — 1050 7900 4000 282 5,7b

363 kV bushings

ГКТIII-60-363/1000ИВУЕ.686354.171 RIP 363 210 1000 510 950 1175 9050 2500 650 5,7b

ГКТПIII-90-363/1000ИВУЕ.686354.224 RIP 363 210 1000 510 950 1175 9050 2500 960 5,7b

Page 19: document-121-1358167669

Hig

h v

olt

ag

e b

ush

ing

s fo

r p

ow

er

tra

nsf

orm

ers

an

d r

ea

cto

rs

Dimensions, mm

Bushing typeDrawing No.

leng

th o

f bus

hing

leng

th o

f bot

tom

part

curr

ent t

rans

-fo

rmer

leng

thhe

ight

of c

entra

lfla

nge

arci

ng

dist

ance

trans

form

er ta

ple

ngth

hous

ing/

shie

lddi

amet

erm

ax.

pass

�thr

ough

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 lnholes n1holes

Overall, fitting and connecting dimensions of high voltage bushings.

17

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

Mounting flange* Bottomshield

Pulled � throungh type connection

252 kV bushings

ГКТIII-60-252/2000ИВУЕ.686353.116 4155 1535 600 1960 ― 165 670 620 24/16 175 ― ― ― ― ―

ГКТПIII-90-252/2000ИВУЕ.686353.216 4025 1535 600 2145 ― 225 165 670 620 24/16 70 175 ― ― ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.117 3965 1070 400 2025 3625 276 198 600 560 24/16 90 251 32/4 89 ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.118 3845 1225 300 1960 ― 238 165 450 400 22/12 230 239 ― ― ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.119 3760 1030 300 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.119-01 3860 1130 400 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―

ГКТIV-60-252/2000ИВУЕ.686353.119-02 4260 1130 400 2360 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.119-03 3960 1230 500 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.122

ГКТIII-60-252/3150ИВУЕ.686353.153 4330 1380 710 2025 ― 276 198 400 350 22/8 230 240 ― ― ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.164 3655 1030 300 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.164-01 3755 1130 400 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―

ГКТIV-60-252/2000ИВУЕ.686353.164-02 4155 1130 400 2360 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―

ГКТIII-60-252/2000ИВУЕ.686353.164-03 3855 1230 500 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―

ГКТПIV-90-252/1600ИВУЕ.686353.223

ГКТПIV-90-252/800ИВУЕ.686353.249 4990 1880 1045 2600 4690 270 210 550 500 24/12 120 251 30 89 ―

363 kV bushings

ГКТIII-60-363/1000ИВУЕ.686354.171 5815 2160 600 2770 5220 296 225 818 770 24/16 91 251 30/2 89 — — —

ГКТПIII-90-363/1000ИВУЕ.686354.224 5673 2160 600 2970 5220 270 240 818 770 24/16 91 251 30/2 89 — — —

Page 20: document-121-1358167669

4418

TOP VIEWEnlarged

Table 2. Part 6 of 7

Bushing typeDrawing No.

Test voltage, kV

1 m

inut

e, 5

0 Hz

Switc

hing

impu

lse

250

/250

0 μs

Rate

d vo

ltage

, kV

Phas

e to

ear

th v

olta

ge, k

V

Type

of i

nter

nal i

nsul

atio

n

Rate

d cu

rren

t, A

Cree

page

dis

tanc

e, m

m

Test

can

tilev

er lo

ad, N

Wei

ght,

kg

Conn

ectio

n ty

pe, f

igur

e N

o.

Ligh

tnin

g im

puls

e 1.

2/50

μs

Technical data of high voltage bushings.

363 kV bushings(continuation)

ГКТПIII-90-363/1000|ИВУЕ.686353.224-01 RIP 363 210 1000 510 950 1175 9050 2500 320 5,7b

ГКТIII-60-363/2500ИВУЕ.686354.125 RIP 363 210 2500 510 950 1175 8000 3150 620 5,7d

ГКТПIII-90-363/2500ИВУЕ.686354.225 RIP 363 210 2500 510 950 1175 9000 3150 300 5,7e

ГКТIII-60-363/1250ИВУЕ.686354.147 RIP 363 210 1250 510 950 1175 9050 2500 600 6а,7а

ГКТIII-60-363/1250ИВУЕ.686354.147-01 RIP 363 210 1250 510 950 1175 9050 2500 612 6а,7а

550 kV bushings

ГКТIII-60-550/800ИВУЕ.686355.128 RIP 550 334 800 680 1230 1550 13150 4000 1200 7а

ГКТIII-60-550/1600ИВУЕ.686355.173 RIP 550 300 1600 680 1230 1550 13150 5000 1900 7e

ГКТIII-60-550/630ИВУЕ.686355.173-01 RIP 550 303 630 680 1230 1550 13150 3150 1400 7e

ГКТIII-60-550/2500ИВУЕ.686355.172 RIP 550 303 2500 680 1230 1550 13150 2500 1230 5,7e

ГКТIII-60-550/2500ИВУЕ.686355.172-01 RIP 550 303 2500 680 1230 1550 13150 2500 1230 5,7e

ГКРIII-30-550/315ИВУЕ.686355.129 RIP 550 303 315 680 1230 1550 13735 2500 1150 5,7e

ГКТIII-60-550/1250ИВУЕ.686355.146 RIP 550 334 1250 680 1230 1550 15125 4000 1200 5,7e

ГКТIII-60-550/1251ИВУЕ.686355.146-01 RIP 550 334 1250 680 1230 1550 15125 4000 1180 5,7e

ГКТIII-60-550/1600ИВУЕ.686355.146-02 RIP 550 334 1600 680 1230 1550 15125 4000 1200 5,7e

600 kV bushings

ГКТПIII-90-600/800ИВУЕ.686355.262 RIP 600 800

800 kV bushings

ГМТII-30-750/1000ИВЕЮ.686345.011 OIP 800 462 1000 975 1550 2400 15750 2500 2750 5,7e

Page 21: document-121-1358167669

4

Hig

h v

olt

ag

e b

ush

ing

s fo

r p

ow

er

tra

nsf

orm

ers

an

d r

ea

cto

rs

Dimensions, mm

Bushing typeDrawing No.

leng

th o

f bus

hing

leng

th o

f bot

tom

part

curr

ent t

rans

-fo

rmer

leng

thhe

ight

of c

entra

lfla

nge

arci

ng

dist

ance

trans

form

er ta

ple

ngth

hous

ing/

shie

lddi

amet

erm

ax.

pass

�thr

ough

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 lnholes n1holes

Overall, fitting and connecting dimensions of high voltage bushings.

19

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

Mounting flange* Bottomshield

Pulled � throungh type connection

363 kV bushings

ГКТПIII-90-363/1000ИВУЕ.686353.224-01 5000 1490 600 2965 4550 225 450 400 22/12 91 251 30/2 89 ― ― ―

ГКТIII-60-363/2500ИВУЕ.686354.125 5290 1620 600 2770 4970 296 225 600 560 24/16 91 251 32/2 89 — — —

ГКТПIII-90-363/2500ИВУЕ.686354.225 5140 1615 600 2970 4820 270 240 600 560 24/16 90 250 32/4 89 — — —

ГКТIII-60-363/1250ИВУЕ.686354.147 4685 1155 300 2770 ― 296 225 450 400 22/12 230 239 ― ― ― ― ―

ГКТIII-60-363/1250ИВУЕ.686354.147-01 4885 1355 500 2770 ― 296 225 450 400 22/12 230 239 ― ― ― ― ―

550 kV bushings

ГКТIII-60-550/800ИВУЕ.686355.128 6462 1790 600 3670 ― 296 275 720 660 24/12 330 296 ― ― ― ― ―

ГКТIII-60-550/1600ИВУЕ.686355.173 7855 2750 1000 3955 ― 1200 1130 24/16 277 490 ― ― ― ― ―

ГКТIII-60-550/630ИВУЕ.686355.173-01 8665 3850 2000 3670 — 296 275 1200 1130 24/16 490 — — — — —

ГКТIII-60-550/2500ИВУЕ.686355.172 7470 2600 1000 3670 6520 296 275 1200 1130 24/16 175 282 28/4 89 — — —

ГКТIII-60-550/2500ИВУЕ.686355.172-01 7540 2670 1000 3670 6520 296 275 1200 1130 24/16 280 400 28/4 89 — — —

ГКРIII-30-550/315ИВУЕ.686355.129 7330 2205 700 3970 6625 296 320 1200 1130 24/16 30 — — —

ГКТIII-60-550/1250ИВУЕ.686355.146 7515 2080 900 237 4240 6980 296 275 720 660 24/12 37 190 290 20/4 69 ― ― ―

ГКТIII-60-550/1251ИВУЕ.686355.146-01 7215 1780 600 237 4240 6680 296 275 720 660 24/12 37 190 290 20/4 69 ― ― ―

ГКТIII-60-550/1600ИВУЕ.686355.146-02 7515 2080 900 237 4240 6980 296 275 720 660 24/12 37 190 290 24/4 69 ― ― ―

600 kV bushings

ГКТПIII-90-600/800ИВУЕ.686355.262

800 kV bushings

ГМТII-30-750/1000ИВЕЮ.686345.011 9430 2720 810 160 4900 7690 580 590 820 740 24/12 35 280 400 28/3 69 — — —

Page 22: document-121-1358167669

20

TOP VIEWEnlarged

Table 2. Part 7 of 7

Bushing typeDrawing No.

Test voltage, kV

1 m

inut

e, 5

0 Hz

Switc

hing

impu

lse

250

/250

0 μs

Rate

d vo

ltage

, kV

Phas

e to

ear

th v

olta

ge, k

V

Type

of i

nter

nal i

nsul

atio

n

Rate

d cu

rren

t, A

Cree

page

dis

tanc

e, m

m

Test

can

tilev

er lo

ad, N

Wei

ght,

kg

Conn

ectio

n ty

pe, f

igur

e N

o.

Ligh

tnin

g im

puls

e 1.

2/50

μs

Technical data of high voltage bushings.

800 kV bushings (continuation)

ГМТII-30-750/1000ИВЕЮ.686345.009 OIP 800 455 1000 975 1550 2400 15750 2500 2700 5,7e

ГМТII-30-750/1000ИВЕЮ.686345.011-01 OIP 800 462 1000 975 1550 2400 15750 2500 2840 5,7e

ГМТII-30-750/1000ИВЕЮ.686345.009-01 OIP 800 455 1000 975 1550 2400 15750 2500 2790 5,7e

ГМТII-30-750/1250ИВЕЮ.686345.010 OIP 800 462 1250 950 1550 2400 17700 2500 2800 6b,7d

ГМТII-30-750/1250ИВЕЮ.686345.013 OIP 800 462 1250 975 1550 2400 17700 2500 2580 6b,7d

ГМТII-30-800/1000ИВУЕ.686346.145 OIP 800 1000

ГМТII-30-800/1000ИВУЕ.686346.145-01 OIP 800 1000

ГКРII-60-800/315ИВУЕ.686356.165 RIP 800 486 315 950 1550 2100 15750 4000 2110 5,7e

1200 kV bushings

ГМТ-20-1150/12502ШЦ.800.119 OIP 1200 694 1250 1150 1900 2700 18000 2500 11690 5,7d

Page 23: document-121-1358167669

4

Hig

h v

olt

ag

e b

ush

ing

s fo

r p

ow

er

tra

nsf

orm

ers

an

d r

ea

cto

rs

Dimensions, mm

Bushing typeDrawing No.

leng

th o

f bus

hing

leng

th o

f bot

tom

part

curr

ent t

rans

-fo

rmer

leng

thhe

ight

of c

entra

lfla

nge

arci

ng

dist

ance

trans

form

er ta

ple

ngth

hous

ing/

shie

lddi

amet

erm

ax.

pass

�thr

ough

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 lnholes n1holes

Overall, fitting and connecting dimensions of high voltage bushings.

21

HIG

H V

OLT

AG

E B

US

HIN

GS

FO

R P

OW

ER

TR

AN

SF

OR

ME

RS

AN

D R

EA

CTO

RS

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

Mounting flange* Bottomshield

Pulled � throungh type connection

800 kV bushings

ГМТII-30-750/1000ИВЕЮ.686345.009 9430 2720 810 160 4900 7690 580 590 820 740 24/12 35 280 400 28/3 69 — — —

ГМТII-30-750/1000ИВЕЮ.686345.011-01 9430 2720 810 160 4900 7690 580 590 1200 1130 24/16 35 280 400 28/3 69 — — —

ГМТII-30-750/1000ИВЕЮ.686345.009-01 9430 2720 810 160 4900 7690 580 590 1200 1130 24/16 35 280 400 28/3 69 — — —

ГМТII-30-750/1250ИВЕЮ.686345.010 10080 2720 810 160 5525 — 580 590 820 740 32/12 35 280 400 — — — — —

ГМТII-30-750/1250ИВЕЮ.686345.013 9640 2410 810 160 5525 — 580 590 820 740 32/12 35 280 400 — — — — —

ГМТII-30-800/1000ИВУЕ.686346.145

ГМТII-30-800/1000ИВУЕ.686346.145-01

ГКРII-60-800/315ИВУЕ.686356.165 8515 2605 750 4900 7910 415 405 1200 1130 24/16 — — 30 72

1200 kV bushings

ГМТ-20-1150/12502ШЦ.800.119 11815 2855 800 230 7500 11063 530 850 1200 1130 25/16 31 — — 28/4 85 — — —

Page 24: document-121-1358167669

Nameplate.Figure 9

WEIGHT

DRAWING NUMBER

SERIAL NUMBER

DATE OF MANUFACTURE

BUSHING TYPE

NUMBER OF TECHNICAL SPECIFICATIONS

OR STATE STANDARD

Testing and operation

Every type of bushing passed accept-ance tests for compliance with all require-ments of State Standard GOST 10693�81and Standard IEC 60137.

Every manufactured bushing issubjected to hand�over tests for the purposeof checking its compliance with the require-ments in regard of the type and quality ofmanufacture, including test measurement ofpartial discharge level and tgδ of the insula-tion, according to the mentioned documents.

The advantage of the bushings with solidinsulation as compared to oil impregnatedpaper insulation is that oil contained in themis not intended for active insulation.Therefore, they need no regular conditionmonitoring. Technical maintenance requiresonly periodic (once in 4 years) measurementof tgδ of the bushing insulation.

Interchangeability

The range of products being manufac-tured includes not only the bushings cur-rently mounted on the newly made trans-formers and reactors, but also thosedesigned instead of the bushings manu-factured previously. In this case, adequa-cy of the submerged bushing parts andthe length of the pulled�through tap, aswell as fitting dimensions of the mountingflange, are observed; if necessary, this isco�ordinated with the transformer andreactor manufacturers.

22

Page 25: document-121-1358167669

23

NOTES

Page 26: document-121-1358167669

24

NOTES

Page 27: document-121-1358167669

HIGH QUALITY OF OUR PRODUCTS ENSURE LONG�TERM SAFE AND RELIABLE OPERATIONOF EQUIPMENT AT ELECTRIC POWER SUBSTATIONS UNDER ANY CONDITIONS AT THE MOST

IMPORTANT OBJECTS

750 kV bushings on the shunt reactors 110 MVA.

110 kV/630 A bushings on the 40 MVA power transformer. 220 kV/2000 A bushings on the 200 MVA power transformer.

330 kV bushings on the 125 MVA power transformer.

Page 28: document-121-1358167669

Massa Ltd. Company77 Lenina st., Pavlovskaya Sloboda village, Istra district,Moscow region 143581, RussiaTel.: +7 (495) 727 3311Fax: +7 (495) 727 3320E-mail: [email protected]

[email protected]. mosizolyator.com

«Izolyator» Plant reserves the right to make changes in the subsequent publications of the catalogue according to new developments, as well as Customer’s remarks and requests.