A CPD Seminar by Vent-Axia

Domestic Indoor Air Qualityand Ventilation

Page 2: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Domestic Indoor Air Qualityand Ventilation

Agenda

• Why Ventilate?• Condensation and Indoor Air Quality• How to Reduce Humidity Levels• Building Regulations Part F• Low Carbon Energy Efficient Ventilation• Competent Persons Scheme• Building Regulations Part L – (the Relevant Parts)• Alternative Approach - PIV

Page 3: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Direction

• Energy is changing our industry

• 25% of total energy used in the UK is by HVAC within buildings

• Regulations drive our business and have a road map to deliver Low Carbon Homes from 2016 onwards and other buildings from 2020

Page 4: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Houses Lose HeatWhere does it go?

Page 5: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

• Tighter Modern Buildings

• Higher Humidity Levels

• CONDENSATION!

Why do we need Ventilation in our Homes?

Page 6: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Condensation

The ‘average’ family produces approximately15 litres of moisture per day – (about 27 pints in old money)

Your daily delivery of moisture looks like this!

Page 7: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Moisture Generation

• Asleep - 40cc/h per person

• Active - 55cc/h per person

• Cooking - 3000cc/day

Page 8: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Moisture Generation

• Dishwashing - 400cc/day

• Bathing - 200cc/day per person

• Drying clothes indoors -1500cc/day per person

Page 9: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

• Moisture generated by the previous activities will gravitate to a cold surface

• Walls, Ceiling, Floors & Soft furnishings quickly show signs of Black Mould:

• A Toxic Fungus: ‘Stachybotrys Chartarum’

What are the effects of Condensation ?

Page 10: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

What are the effects of Condensation ?

• Rooms subjected to long periods of high humidity levels (above 70%RH) will be affected

Page 11: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Health Issues

Condensation is not only damaging to the fabric of the building but also it’s occupants

Asthma and other respiratory diseases are on the increase in the UK with one in three families suffering

Page 12: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Volatile Organic

Compounds

Odours

Symptoms

Page 13: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Allergy

Symptoms

Asthma

Page 14: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

The Allergy TriggersHouse Dust Mite (HDM)

Dermatophagoides Pteronyssinus ‘Skin Eating Feather Mite’

• The droppings of the HDM contain the allergen DER P1

• A typical mattress can contain tens of thousands of dust mites

• Nearly 100,000 mites can live in one square yard of carpet

Page 15: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

How can we reduce Humidity Levels?

Three elements have to be in place

• Adequate Heating– Air is like a sponge - the warmer it is the more

moisture it will hold.

• Adequate Insulation– Prevents cold surfaces for moisture to condense

• Adequate Ventilation– Removes excess moisture & provides oxygen for

the occupants to live and breathe

Page 16: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Approved Document F

Page 17: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

New Structure 2010

Legalrequirements in

the Building Regulations and

Part F of Schedule 1

1st Tier

ApprovedDocument

F

2nd Tier

DomesticVentilation

Installation and Commissioning

Guide

3nd Tier

Industry, Guides, Good practice

Guides, Codes of practices and

standards

Both ADF and ADL refer to additional guides in the form of 2nd and 3rd tier documents

Page 18: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Compliance

Design Performance CriteriaMeans of ventilation and airflow rate based on dwelling permeability

Installation and CommissioningInstalled performance to be achieved through Competent Persons scheme

Operation and MaintenanceEnd user information to ensure effective use and maintenance

Page 19: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Design Performance• Dwelling Air

Permeability<5m3/(h.m2)@50Pa

Dwelling Air Permeability >5m3/(h.m2)@50Pa

Page 20: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

There are 4 Systems in Part F They work differently and vary in energy efficiencies:

1.Background ventilators and intermittent extract fans2.Passive Stack Ventilation3.Continuous Mechanical Extract 4.Continuous Mechanical Supply and Extract with Heat Recovery (MVHR)

Part F Ventilation Systems

Page 21: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Impeller Designs -2 Main Types:

Axial:• Ideal for through the wall or

window applications• Should not be used with

ducting longer than 3 metres

Centrifugal:• Ideal for ducted application• Good pressure development

• Both are used in ventilation systems in Part F

Page 22: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Part F System 1 Intermittent Extract Fans

Intermittent Extract Fans are normally Axial Flow

Page 23: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building
Page 24: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

What is Lo-Carbon?

• Energy efficient ventilation solutions• Lower energy consumption - up to 90% savings• Lower maintenance – 5 year motor life• Meets current and future energy targets• Meets environmental targets• Sustainable – longer service life• An affordable alternative to AC products

Page 25: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Lo-Carbon -100mm Axial Bathroom Fan

Applications: Panel or Wall

Models:Pull CordTimerHumidity

Sound AC: 32dBASound Lo-Carbon: 32dBA

Watts AC: 20 Watts Lo-Carbon: 5

Airflow AC: 90m³/hAirflow Lo-Carbon: 90m³/h

Specific Fan Power (SFP): 0.27

Page 26: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Lo-CarbonCentrifugal Bathroom Fan

Sound AC: 42dBASound Lo-Carbon: 42dBA

AC watts: 20 Lo-Carbon watts:5.3

Airflow AC: 90m³/hAirflow Lo-Carbon: 105m³/h

Specific Fan Power (SFP): 0.43

Applications: Panel or Wall

Page 27: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Tomorrows Solutions Today

Lo-Carbon 150 Axial Kitchen Fan

Applications: Panel or Wall

Available Summer 2009

Models:BasicTimerHumidity

Specific Fan Power (SFP): 0.15

Page 28: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Ventilation Energy Uses

• As well as heat loss, intermittent ventilation has other energy penalties:

– Over ventilation – Over use is often an issue (research showed Humidity sensors reduced running time by 40%)

– Motors – The motors use electricity to run

Page 29: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Part F System 3 MEV

Decentralised MEV(Axial Flow)

Centralised MEV(Centrifugal)

Page 30: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

The Next Generation

• The next generation of decentralised continuous systems

Page 31: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Lo-CarbonContinuous Running Fans

Page 32: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Continuous

Motor Consumption

Intermittent

Page 33: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Lo-CarbonContinuous Running

• Full range of controls– Timer– Humidity/Timer– Humidity Pull-Cord

• SELV versions– Timer– Humidity/Timer– Humidity/Pull-Cord

Page 34: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Ancillaries

• Window kit

• Conversion plate –150mm diameter to 100mm

Page 35: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Motor Consumption Comparison

Hours a Day

Motorconsumptionwatts

kW/h per year

Price per kW/h

Total cost per year

Kitchen*Lo-CarbonContinuous 23 1.4 11.75 0.12 £1.41

1 2.4 0.88 0.12 £0.11

Bathroom 24 1.4 12.26 0.12 £1.47

Continuous total £2.99

KitchenIntermittentCentrifugal 2 60 43.8 0.12 £5.26

Bathroom 2 29 21.17 0.12 £2.54

Intermittent total £7.80

*Kitchen fan running for 23 hours on trickle and 1 hour boost

Page 36: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Lo-CarbonSingle Room Heat Recovery

• A fan which recovers up to 80% of the heat from extracted air and puts it back into the fresh incoming air.

• The unique twin impeller design consumes as little as 2.0 Watts and operates almost silently on trickle setting.

• Complies with Part F, System 1 and may also be used in conjunction with System 3, continuous mechanical extract ventilation.

• Low energy consumption means the SRHR exceeds the energy saving requirements in Part L, Conservation of Fuel and Power.

• Switching from trickle to boost by switched Live, Pull cord or Humidistat. Overrun and delay start timer.

• The extract-only Summer Setting helps keep you cool by closing off the intake from outside, reducing the amount of warm air entering the dwelling.

Centrifugal Lo-Carbon

Page 37: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Features

Page 38: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Motor Consumption

SRHR Hours a Day

Motorconsumptionwatts

kW/h per year

Price per kW/h

Total cost per year

Kitchen* Trickle 23 2.0 16.79 0.12 £2.01

Boost 1 5.1 1.86 0.12 £0.22

Bathroom SRHR 24 2.0 17.52 0.12 £2.10

Continuous Total £4.33

KitchenCentrifugal

Kitchen 2 60 43.8 0.12 £5.26

BathroomCentrifugalBathroom 2 29 21.17 0.12 £2.54

Intermittent Total £7.80

*Kitchen fan running for 23 hours on trickle and 1 hour boost

Page 39: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Electrical Goods –Energy Consumption Comparison

Page 40: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Part F Ventilation SystemsSystem 4 MVHR

Mechanical Ventilation with Heat Recovery(Centrifugal)

Page 41: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

System 4 (MVHR Range)

MVHR units should be SAP Appendix Q Listed

Top performing MVHR SAP Q product will help with compliance

Various models to meet project requirements

Compact and light weight

Easy access filters for annual maintenance.

100% Speed Control for accurate site commissioning

User and Contractor friendly controls

Automatic Integral control options

Page 42: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Counter Flow Heat ExchangerThe Counterflow Heat Exchanger is the most efficient giving 90% Thermal Efficiency

How Does it Work?

Page 43: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

If the External Ambient is Zero Degrees

If Internal Temperatureis 20 degrees

Exhaust Temperature willbe 2 degrees

Supply temperature willbe 18 degrees

OUTSIDE

INSIDE

90%+ Efficiency

Counter Flow Heat Exchanger

Page 44: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Noise

• Continuous Mechanical ventilation systems should be below 35dBA on trickle speed

Page 45: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Main Changes - 2010 Edition

• Ventilation will become a controlled service needing sign off by a “competentperson”

• 2nd tier “Domestic Ventilation Installation and Commissioning Guide” with a sign off sheet

• All ventilation systems shall be commissioned (including Intermittent Fans and Cooker Hoods)

• Commissioning checklist to be passed to Building Control

Page 46: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Competent Persons Scheme

• BPEC have developed a Domestic Ventilation Systems 2010 course

• Aimed at installers of all ventilation systems

• Delivered by manufacturers, colleges and independent trainers

• If systems are installed by ‘Approved Installers’ SAP scores can be enhanced

Page 47: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Information for the Occupier

The owner/occupier shall be given sufficient information about the ventilation system and its maintenance requirements so that the ventilation system can be operated to provide adequate air flow. This should apply to natural and mechanical systems in new dwellings

Page 48: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Approved Document L

Page 49: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Part L1 - Domestic

Page 50: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Comparison Chart

Low Carbon Motors AC Motors

Product - Intermittent l/s Watts SFP (w/l/s) l/s Watts SFP (w/l/s)

100mm Bathroom Axial 25 6.5 0.26 25 15 0.60100mm SELV Bathroom Axial 25 6.5 0.26 21 16 0.76Slim Profile 100mm Bathroom Axial 24 6.5 0.27 26 16 0.62Slim Profile 100mm SELV Bathroom Axial 26 7.5 0.29 26 18 0.69Shower Fan 31 6.5 0.21 30 15 0.50Shower Fan and Light 31 6.5 0.21 31 40 1.29Centrifugal Bathroom Fan VAR VAR 0.50 VAR VAR 0.92Centrifugal Bathroom SELV Fan VAR VAR 0.50 n/a n/a n/a150mm Kitchen Axial 64 11.5 0.18 n/a n/a n/aSlim Profile 150 Kitchen Axial 67 8.2 0.12 67 20 0.30

Low Carbon Motors AC Motors

Product - Continuous l/s Watts SFP (w/l/s) l/s Watts SFP (w/l/s)

Continuous Axial VAR VAR 0.18 n/a n/a n/aContinuous Axial SELV VAR VAR 0.18 n/a n/a n/aContinuous Centrifugal VAR VAR 0.38 n/a n/a n/aContinuous Centrifugal SELV VAR VAR 0.38 n/a n/a n/a

Page 51: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Part L and Solar Gain

Criterion 3 –Limiting the Effects of Solar Gain

• 4.25 – If ventilation is provided using a balanced system, consideration should be given to providing a summer bypass function during warm weather so that the ventilation is more effective in reducing overheating.

Page 52: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Part L1 SummaryImportant Features of Part L

• TER 25% improvement over 2006

• SAP Q is retained

• Minimum Specific Fan Power across ventilation systems

• MVHR efficiency no less that 70%

Page 53: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Alternative ApproachPositive Input Ventilation

Page 54: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Positive Input Ventilation(PIV)

• Selectable air capacities to suit house volumes up to 400m³

• Lo Carbon Motor for very low running costs

• Ultra low sound level• EU4 Filter• Loft unit to be hung from rafters

or supported on AV mounts• Integral heater option • Integral time elapse meter• 5 year warranty

Positive Input Ventilation(PIV)

Page 55: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Positive Pressure –Loft Mounted

Page 56: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Positive Pressure –Flat Mounted

Page 57: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

Positive Pressure –Flat Mounted

• Selectable air capacities to suit house volumes up to 100m³

• Lo Carbon Motor for very low running costs

• Ultra low sound level• EU4 Filter• 6 speed capability; two speeds

selected on installation.• Integral heater option • Round to rectangular duct

connection included• 5 year warranty

Page 58: Domestic Indoor Air Quality and Ventilation · Domestic Indoor Air Quality and Ventilation. Domestic Indoor Air Quality and Ventilation Agenda ... damaging to the fabric of the building

The Future of Ventilation

• Lo-Carbon Technology is becoming standard• AC products are being phased out• Continuous Ventilation with or without Heat

Recovery in the Kitchen and Bathroom is becoming the system of choice

• Whole House Heat Recovery:The most efficient form of ventilation available for social housing on both refurbishment and new build