door fan test_fire new installers

99
High Value Enclosure High Value Enclosure Testing Testing by Colin Genge of Retrotec Inc by Colin Genge of Retrotec Inc [email protected] [email protected] www.retrotec.com www.retrotec.com 360 738 9835 ext 308 360 738 9835 ext 308 NFPA 2001 Appendix C & ISO 14520 Total Flooding Clean Agent Acceptance Procedure

Upload: hanlove

Post on 01-Jan-2016

39 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Door Fan Test_Fire New Installers

High Value Enclosure TestingHigh Value Enclosure Testingby Colin Genge of Retrotec Incby Colin Genge of Retrotec Inc

[email protected]@retrotec.com www.retrotec.comwww.retrotec.com360 738 9835 ext 308360 738 9835 ext 308

NFPA 2001 Appendix C

& ISO 14520

Total Flooding

Clean Agent Acceptance Procedure

Page 2: Door Fan Test_Fire New Installers

History Of Integrity TestingHistory Of Integrity Testing

Colin Genge first proposed using door fan tests to ensure passage of discharge in 1986

Several companies used door fans to find leaks. They all passed.

The next one wasn’t tested and it failed. 1988 NFPA hired Colin Genge to write the Appendix

on Door Fan testing. NFPA 2001 4-7.2.2.10 A discharge test is not

recommended…

Page 3: Door Fan Test_Fire New Installers

High ValueHigh Value Enclosure Testing Enclosure Testing High ValueHigh Value = High Risk = High Risk

facilities such as:facilities such as: Computer rooms, tape storage, battery rooms.

UPS rooms Pressurized control rooms Telecommunication centers Turbines, power generators Simulators Archives, Museums Clean Rooms, Operating rooms

Page 4: Door Fan Test_Fire New Installers

High Value High Value EnclosureEnclosure Testing Testing EnclosureEnclosure = walls, doors, = walls, doors,

windows, louvers, dampers, windows, louvers, dampers, connected ductsconnected ducts

Shots of dampers in fire barrier

Electronics enclosure

Page 5: Door Fan Test_Fire New Installers

High Value Enclosure High Value Enclosure TestingTesting TestingTesting=measuring:=measuring:

leakage areavent area

static pressures

Page 6: Door Fan Test_Fire New Installers

Function of the Enclosure Function of the Enclosure

Keep out: – fire, – smoke, – dust, – humidity, – pollutants, & corrosives

Maintain fire suppressant concentrationResist discharge pressure

Page 7: Door Fan Test_Fire New Installers

High Value Enclosure Testing High Value Enclosure Testing OutlineOutline

Preventing Enclosure Failure History, who tests, who accepts, why test Door Fan test equipment set up Enclosure design

Page 8: Door Fan Test_Fire New Installers

A. A. Preventing Enclosure FailurePreventing Enclosure FailureWhat do you think enclosure What do you think enclosure

failure is?failure is?________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

Page 9: Door Fan Test_Fire New Installers

59% failed to keep out fire 59% failed to keep out fire and smoke!and smoke!-1989 to 1999 study of clean agent systems indicated 59% failured

due to:

1st Enclosure leaks - design % lost too fast2nd No A/C shutdown - design % not achieved 3rd Electronic problem - didn’t detect fire4th Valve didn’t actuate - design % not achieved 5th Room size increased - design % not achieved 6th Wind losses - design % lost too fast7th Enclosure too tight - damage by discharge

Page 10: Door Fan Test_Fire New Installers

How we will address these How we will address these problems:problems:

All these problems are addressed by an Enclosure Integrity All these problems are addressed by an Enclosure Integrity door fan test upon installation and an annual re-test as door fan test upon installation and an annual re-test as recommended by NFPA.recommended by NFPA.

“Electronic problem, valve didn’t actuate”: addressed by “Electronic problem, valve didn’t actuate”: addressed by annual inspection but not covered in this presentation.annual inspection but not covered in this presentation.

Page 11: Door Fan Test_Fire New Installers

A. A. Preventing Enclosure Preventing Enclosure FailureFailure by: by:

1. Keeping out fire, smoke, dust, humidity, pollutants, dangerous compounds with well sealed enclosure. This is passive protection.

2. Passing NFPA 2001 or ISO 14520 standards to ensure the fire suppressant will put out the fire and prevent re-ignition.

3. Having sufficient vent area to prevent enclosure damage.

Page 12: Door Fan Test_Fire New Installers

A. 1. Preventing Enclosure A. 1. Preventing Enclosure Failure=Passive ProtectionFailure=Passive Protection

Keeping out fire, smoke, dust, humidity, pollutants, dangerous compounds

Page 13: Door Fan Test_Fire New Installers

A. 1. Passive Protection A. 1. Passive Protection assured by:assured by:

a) Inspect potential leakage sitesb) Locate leaks with smoke & door fanc) Seal leaksd) Inspect for continuous fire barrier

Page 14: Door Fan Test_Fire New Installers

A. 1. Passive Protection = Inspect A. 1. Passive Protection = Inspect potential leakage sitespotential leakage sites

Doors are a small leak compared to the huge leak hiding behind the rubber molding at floor level.

Page 15: Door Fan Test_Fire New Installers

A. 1. a) Inspect potential leakage A. 1. a) Inspect potential leakage sitessites

Large cable holes need to be sealed to keep agent in.

Page 16: Door Fan Test_Fire New Installers

A. 1. a) Inspect potential leakage A. 1. a) Inspect potential leakage sitessites

Cable penetrations

Page 17: Door Fan Test_Fire New Installers

A. 1. b) Passive Protection = A. 1. b) Passive Protection = Locate leaks with smokeLocate leaks with smoke

Locating leaks best done with smoke puffer with door fan supplying test pressure. A common slab-to-wall leak is identified as a definite big time leak with smoke puffer.

Page 18: Door Fan Test_Fire New Installers

A. 1. b) Locate leaks with A. 1. b) Locate leaks with smokesmoke

Cable conduits show up as huge leaks.

Page 19: Door Fan Test_Fire New Installers

A. 1. c) Passive Protection = Seal A. 1. c) Passive Protection = Seal leaksleaks

Door Fan measures leakage area Computer prints out

leakage report

Page 20: Door Fan Test_Fire New Installers

A. 1. c) Seal leaksA. 1. c) Seal leaks

Cables stopped with pillows don’t stop agent losses very well

This type of seal is needed.

Page 21: Door Fan Test_Fire New Installers

A. 1. c) Seal leaksA. 1. c) Seal leaks

Vertical cables properly sealed.

This is the type of seal needed on the wall-to-floor slab joint. Generous overlap.

Page 22: Door Fan Test_Fire New Installers

A. 1. c) Seal leaksA. 1. c) Seal leaks

Wall to upper deck being sealed.

This is the best type of seal. Flexible, fire rated, air and smoke tight.

Page 23: Door Fan Test_Fire New Installers

A. 1. d) Passive Protection = A. 1. d) Passive Protection = Continuous fire barrier?Continuous fire barrier?

Most common problem is where a suspended ceiling is used as fire barrier. It is NOT a fire barrier!

Ducts with remote dampers that are not in the same plane as the fire barrier is another example of a discontinuity because unprotected sheet metal duct has no fire rating.

Page 24: Door Fan Test_Fire New Installers

A. 1. d) Inspect for continuous A. 1. d) Inspect for continuous fire barrierfire barrier

Fire barrier is often missing under doors

Fire barrier caulked to the upper slab is good!

Page 25: Door Fan Test_Fire New Installers

A.A. 1. d) Inspect for 1. d) Inspect for continuous fire barriercontinuous fire barrier

Best solution is to have self contained air conditioning with all duct work inside the enclosure. This eliminates expensive duct and damper leakage problems.

Page 26: Door Fan Test_Fire New Installers

A. Preventing Enclosure A. Preventing Enclosure Failure=Failure=

1. Keeping out fire, smoke, dust, humidity, pollutants, dangerous compounds with well sealed enclosure. This is passive protection.

2. Passing NFPA 2001 or ISO 14520 standards to ensure the fire suppressant will put out the fire and prevent re-ignition.

3. Sufficient Vent area to prevent enclosure damage.

Page 27: Door Fan Test_Fire New Installers

A.A. 2. Preventing Failure= 2. Preventing Failure= Passing NFPA 2001 or Passing NFPA 2001 or ISO 14520 standardsISO 14520 standards

Passing NFPA 2001 Appendix C or ISO 14520 Annex standards will ensure the fire suppressant will put out the fire and maintain concentration to prevent re-ignition.

Page 28: Door Fan Test_Fire New Installers

A. 2. Passing NFPA 2001 or A. 2. Passing NFPA 2001 or ISO 14520 standardsISO 14520 standards

a) Measure static pressures with gauge & direction with smoke

b) Measure leaks with door fan

c) Determine agent mixing or descending interface using smoke

d) Use software to calculate retention time

e) Wind losses too

Page 29: Door Fan Test_Fire New Installers

A. 2. a) Measure static A. 2. a) Measure static pressures with gaugepressures with gauge

HVAC imbalance may cause air to dilute the agent.

Leaky Supply damper

Leaky Supply damper

Passivereturnleak

Page 30: Door Fan Test_Fire New Installers

A. 2. a) Measure static A. 2. a) Measure static pressures with gaugepressures with gauge

Adjacent pressurized rooms may create agent loss or push smoke into the protected enclosure.

Protected zone loses concentrationfrom air coming in from right + pressure

Page 31: Door Fan Test_Fire New Installers

A.A. 2. b) Measure leaks with door 2. b) Measure leaks with door fanfan

Door Fan measures leakage area

Computer prints out leakage report

Page 32: Door Fan Test_Fire New Installers

A. 2. c) Determine agent A. 2. c) Determine agent mixing or descending mixing or descending interface using smokeinterface using smoke

A neutral buoyancy smoke test will show whether continual mixing is occurring. If not then there will be a descending interface formed between the agent and the air coming in at ceiling level.

Page 33: Door Fan Test_Fire New Installers

A. 2. d) Use software to A. 2. d) Use software to calculate retention timecalculate retention time

Retention time calculation screen

Page 34: Door Fan Test_Fire New Installers

A.A. 2. e) Wind losses too2. e) Wind losses tooApplies more to enclosure exposed to wind.

Particularly remote telecom stations on hill tops or observatories on mountains.

Losses due to wind can easily be greater than gravity losses per NFPA or ISO

Page 35: Door Fan Test_Fire New Installers

A. Preventing Enclosure A. Preventing Enclosure Failure=Failure=

1. Keeping out fire, smoke, dust, humidity, pollutants, dangerous compounds with well sealed enclosure. This is passive protection.

2. Passing NFPA 2001 or ISO 14520 standards to ensure the fire suppressant will put out the fire and prevent re-ignition.

3. Provide sufficient Vent area to prevent enclosure damage.

Page 36: Door Fan Test_Fire New Installers

A. 3. Preventing A. 3. Preventing Failure=Failure=Provide sufficient vent Provide sufficient vent

areaareaa) Software calculates vent area needed to

prevent enclosure damage?

b) Door fan measures the effective area of the vent

c) Peak pressure predicted

Page 37: Door Fan Test_Fire New Installers

A. 3. a) Vent area needed?A. 3. a) Vent area needed?

Software calculates vent area needed to prevent enclosure damage based on various standards. Agent type, discharge time, concentration, and temperature are the major variables. The result is expressed in m2 or in2 of open free vent.

Page 38: Door Fan Test_Fire New Installers

A. 3. b) Vent area measuredA. 3. b) Vent area measured

Door fan measures actual installed capacity of vent. This can often be less than half the open area of the vent when louvers, screens, and attached duct is taken into account. The room leakage may be used as part of the vent or not in cases where room leaks do not vent to atmosphere.

Page 39: Door Fan Test_Fire New Installers

A. 3. c) Peak pressure A. 3. c) Peak pressure predictedpredicted

Peak pressure that will occur during the discharge is calculated based on the room and/or effective vent area that was measured with the door fan, agent type, concentration, discharge time and temperature.

Page 40: Door Fan Test_Fire New Installers

A. 3. Screen shows a)vent A. 3. Screen shows a)vent needed b) vent measured & c) needed b) vent measured & c)

peak pressurepeak pressure 0.15 m2 of

vent needed to keep pressure below 250 Pa.

vent measured at only 0.13 m2

Peak pressure will be 144 Pa

Page 41: Door Fan Test_Fire New Installers

High Value Enclosure Testing High Value Enclosure Testing OutlineOutline

A. Preventing Enclosure Failure

B. Who tests, who accepts, why test

C. Door Fan test equipment set up

D. Enclosure design

Page 42: Door Fan Test_Fire New Installers

B. Who tests – who acceptsB. Who tests – who accepts 500 installers use Retrotec equipment GM, Ford, IBM, Intel, Lockheed, GE, ATT, Texas Instruments,

AMEX, Exxon, Chevron, BP, DuPont, over 90% of the top 500 world corporations

Industrial Risk Insurers, Factory Mutual, Kemper

Insurance, Chubb Insurance Military forces 25 countries Research facilities: LBL, NASA, Sandia Labs, Jet Propulsion Labs,

NRC, Los Alamos

Page 43: Door Fan Test_Fire New Installers

B. 34 countries utilize door fan B. 34 countries utilize door fan teststests

Argentina

Bahrain

Belgium

Brazil

Canada

Chile

China

England

France

Germany

Grand Cayman

Holland

Hong Kong

Indonesia

Ireland

Italy

Jordan

Kuwait

Malaysia

New Zealand

Puerto Rico

Qatar

Saudi Arabia

Singapore

South Africa

South Pole

Spain

Sweden

Switzerland

Taiwan

Thailand

Trinidad

Turkey

UAE

USA

Page 44: Door Fan Test_Fire New Installers

B. Why test?B. Why test?

1. Passive protection

2. Initial acceptance

3. Annual re-test

Page 45: Door Fan Test_Fire New Installers

B. 1. Passive protectionB. 1. Passive protection

80% - chance fire or smoke event will occur outside the protected enclosure

Maximizes clean agent suppressionLo costWorks when power fails24 hours per day

Page 46: Door Fan Test_Fire New Installers

B. 2. New enclosures must be B. 2. New enclosures must be tested for acceptancetested for acceptance

NFPA2001 4-7.2.3“All total flooding systems must

have the enclosure examined and tested…”

$800 to $3500 initial test30 to 45 minutes test30 minutes report

Page 47: Door Fan Test_Fire New Installers

B. 3. Existing enclosures must B. 3. Existing enclosures must be checked annuallybe checked annually

NFPA2001 4-4Enclosure Inspection“Inspect at least every 12 months.If doubt, retest”

Non disruptive-operations can continue$250 to $1500 for re-test15 to 30 minutes to re-test

+ 15 minutes for report

Page 48: Door Fan Test_Fire New Installers

High Value Enclosure Testing High Value Enclosure Testing OutlineOutline

A. Preventing Enclosure Failure

B. History, who tests, who accepts, why test

C. Door Fan test equipment set up

D. Enclosure design

Page 49: Door Fan Test_Fire New Installers

C. Door fan test equipmentC. Door fan test equipment

1. Setting up door fan

2. CA2001 software calculates PASS or FAIL

3. Printout

4. Equipment cost and training

5. Specifying door fan tests

6. How to sell door fan tests

7. Benefits

Page 50: Door Fan Test_Fire New Installers

C. 1. C. 1. Setting Setting Up Door FanUp Door Fan

Tool case and calibrated blower are carried in first

35 + 20 lb

Page 51: Door Fan Test_Fire New Installers

Console set up and Lower panel removed from case

Page 52: Door Fan Test_Fire New Installers

Lower panel installs in seconds

Page 53: Door Fan Test_Fire New Installers

Middle panel expands sideways, up AND down!

Page 54: Door Fan Test_Fire New Installers

Upper panel installs in seconds

Page 55: Door Fan Test_Fire New Installers

Center panel expanded upwards

Page 56: Door Fan Test_Fire New Installers

Calibrated blower installed in panel

Page 57: Door Fan Test_Fire New Installers

Cable connected for:

Speed control signal to blower

Pressure across panel

Flow from blower

temperature

Page 58: Door Fan Test_Fire New Installers

Computer calculates maximum agent loss rate using data from digital gauges.

Retention time is calculated in 3 minutes.

If it fails, the room can be repaired and quickly re-tested.

Page 59: Door Fan Test_Fire New Installers

C. 2. CA2001 software C. 2. CA2001 software calculates PASS or FAIL for:calculates PASS or FAIL for:

Agent retention time &Maximum pressure created at discharge

Page 60: Door Fan Test_Fire New Installers

C. 3. C. 3. Page 1 Page 1

Door Fan Door Fan Test Test

PrintoutPrintout

Page 61: Door Fan Test_Fire New Installers

C. 3. C. 3. Page 3 Page 3

Door Fan Door Fan Test Test

PrintoutPrintout

Page 62: Door Fan Test_Fire New Installers

C. 3. Model 970hp Vs 902FC. 3. Model 970hp Vs 902F

Works, but not quite as impressive.Used by 2% of testers.

Impressive- tests all rooms. Used by 90% of testers.

Page 63: Door Fan Test_Fire New Installers

$3,000 to $12,00024 hr. tech support100% satisfactionCertification

availableDelivery immediate

Equipment and trainingEquipment and training

Page 64: Door Fan Test_Fire New Installers

C. 5. Specifying door fan testsC. 5. Specifying door fan tests

Under specifier’s article on www.retrotec.com

Page 65: Door Fan Test_Fire New Installers

C. 6. How to sell door fan C. 6. How to sell door fan teststests

Presentations to:•Authorities•Specifying Engineers and Architects•Fire Departments•End Users

Utilize Retrotec’s handouts, Windows software and videos on:• “How to Witness a Test”• Licensed CA2001 software users can give away copies to

AHJ, specifiers and fire departments.• “How to design an enclosure for clean agent”

Page 66: Door Fan Test_Fire New Installers

C. 6. How to sell testsC. 6. How to sell tests

1. Become enclosure experts. Show colorful example reports showing typical problems. Make it visible.

2. NFPA requires initial test and re-test yearly.

3. Show them list of world’s biggest who have tests done.

4. Use Retrotec’s specifier’s guide.

Page 67: Door Fan Test_Fire New Installers

Superior fire and smoke protection Saves energy Controls dust, noise and humidity Fast and easily repeated Profitable- $50,000 to $100,000 /year/system $500 to $3500 initial test, 30 to 45 minutes $300 to $1500 re-test, 15 to 30 minutes Non disruptive, allows operations to continue if

necessary. The A/C may need to be shut down for 10 minutes.

BenefitsBenefits

Page 68: Door Fan Test_Fire New Installers

High Value Enclosure Testing High Value Enclosure Testing OutlineOutline

A. Preventing Enclosure Failure

B. History, who tests, who accepts, why test

C. Door Fan test equipment set up

D. Enclosure design

Page 69: Door Fan Test_Fire New Installers

D. Enclosure designD. Enclosure design1. The 6 myths about clean agent enclosures

2. Common design problems

3. Design for maximum protection.

Page 70: Door Fan Test_Fire New Installers

6 clean agent enclosure 6 clean agent enclosure mythsmyths

1. Add more agent to account for leaks.

2. Inert gases don’t require door fan tests.

3. Suspended ceilings will contain agent.

4. Hazards at ceiling level can be protected.

5. Inert agents don’t need pressure vents.

6. Door fan gives longer retention times than a discharge test.

Page 71: Door Fan Test_Fire New Installers

Myth #1Myth #1Add more agent to account for leaks.Reality: beyond the extinguishing

concentration, more agent will decrease the retention time in most enclosures. More agent = more pressure = faster loss = shorter retention time.

Page 72: Door Fan Test_Fire New Installers

Myth #1Myth #1Agent leakage m2 retention minutes

38% INERGEN 0.06 14.7

50% INERGEN 0.06 13

More agent = more pressure

= faster loss = shorter retention time.

Page 73: Door Fan Test_Fire New Installers

Myth #1Myth #1Add more agent to account for leaks. Exception is where agent is continually

mixed by HVAC system. There more concentration DOES give longer retention.

Page 74: Door Fan Test_Fire New Installers

Myth #2Myth #2Inert gases don’t require door fan tests

because they are the same density as air and don’t leak out.

Page 75: Door Fan Test_Fire New Installers

Myth #2Myth #2Reality: all inert gases (except N2) are more dense than

air and leak out at the NFPA and ISO predicted rate. Halocarbons have four times the density difference which causes them to leak out at about half the rate of inerts.

Agent leakage retention density

38 % N2 0.03 m2 69 minutes 1.17kg/m3

(100% air) 1.2kg/m3

38% INERGEN 0.03 m2 29 minutes 1.3kg/m3

7% FM200 0.03 m2 14 minutes 1.6kg/m3

Page 76: Door Fan Test_Fire New Installers

Myth #3 Myth #3 Suspended Suspended ceilings will contain agent.ceilings will contain agent.

Often a suspended ceiling is used to contain clean agent. This practice reduces protection dramatically because it will still allow smoke to enter the room. Since a smoke event outside the enclosure is more likely than a fire within the enclosure, we recommend hard ceilings, sealing walls slab to slab and/or flooding the ceiling void for maximum protection.

Page 77: Door Fan Test_Fire New Installers

Myth #3 Myth #3 Unintentional Unintentional discharge due to excessive discharge due to excessive

leaksleaks

FM200air

7% FM20093% air

smokesmoke

i. Smoke enters via the above ceiling leaks.ii. The clean agent is discharged falsely.iii. As the agent runs out, it pulls in more smoke.

Page 78: Door Fan Test_Fire New Installers

Myth #3 Myth #3 Passive protection Passive protection of air seal protects enclosure of air seal protects enclosure

from smokefrom smoke

air

smoke smoke

Proper sealing at the top of the walls ensures smoke stays out of the protected enclosure.

Page 79: Door Fan Test_Fire New Installers

Myth #4 Myth #4 Hazards at ceiling Hazards at ceiling level can be protectedlevel can be protected

FM200

7% FM20093% air 7% FM200

93% air

100% air

i. Agent is dischargedii. The design concentration fills the roomiii. As the agent runs out, the upper part of the room loses concentration almost immediately.

Page 80: Door Fan Test_Fire New Installers

Myth #4 Myth #4 Hazards at ceiling Hazards at ceiling level can be protectedlevel can be protected

Only solution is to leave A/C running to continually mix the agent with incoming air.

Agent concentration must be increased by at least 25% because the concentration will drop over the retention time and must not go below a concentration that would allow the fire to re-ignite.

Page 81: Door Fan Test_Fire New Installers

Myth #5 Myth #5 Inert agents don’t Inert agents don’t need pressure vents.need pressure vents.

Reality: Manufacturers recommend vents for all enclosures. Room leaks CAN be used as the vent :

-maximum allowable pressure must be at least 500 Pa- but even then the leakage range allowable is very narrow. Typically 1.16 : 1

Agent minimum leakage for 10 min.retention

maximum leakage for 500 Pa venting

INERGEN 0.76 m2 0.88 m2

Page 82: Door Fan Test_Fire New Installers

Myth #5 cont’dMyth #5 cont’d the range for FM200 is 4.6 : 1 meaning that vents

are seldom needed.

Agent minimum leakage for 10 min.retention

maximum leakage for 500 Pa venting

INERGEN 0.76 m2 0.88 m2

FM200 0.12 m2 0.55 m2

Page 83: Door Fan Test_Fire New Installers

If a double door fan with flex duct is used to measure leak location, this narrow window can be widened.

Myth #5Myth #5

Page 84: Door Fan Test_Fire New Installers

Myth #6 Myth #6 Door fan gives Door fan gives longer retention times than longer retention times than

a discharge test.a discharge test.Main reason for this is

failure to measure leak location. This can be done with a door fan and flex duct. Then, the door fan test is very close to the discharge test.

Page 85: Door Fan Test_Fire New Installers

D. Enclosure designD. Enclosure design1. The 6 myths about clean agent enclosures

2. Common design problems

3. Design for maximum protection.

Page 86: Door Fan Test_Fire New Installers

D.2. D.2. Common design Common design problemsproblems

a) Ceiling too low decreases retention time.

b) Suspended ceiling used as fire barrier

c) Protection expected at the ceiling

d) Common sub-floor

e) External ductwork connected to building HVAC

f) Sub-floor air forced into exterior walls

g) Excess energy consumption

Page 87: Door Fan Test_Fire New Installers

D.2. a) Ceiling too low D.2. a) Ceiling too low decreases retention time.decreases retention time.

Suspended Minimum retention timeceiling height protected height

3.5 m 3 m 4.0 min.4 m 3 m 7.7 min.5 m 3 m 14.4 min.6 m 3 m 20.5 min.

For a hazard at 3 m, increasing the suspended ceiling height rapidly increases the protection.

Page 88: Door Fan Test_Fire New Installers

D.2. b) Suspended ceiling D.2. b) Suspended ceiling used as fire barrier.used as fire barrier.

Smoke and fire will pass these ceilings as if they were not there.

Worse, they disintegrate with time. Solution: install hard ceiling that is sealed

to the walls.

Page 89: Door Fan Test_Fire New Installers

D.2. c) Protection expected at D.2. c) Protection expected at the ceilingthe ceiling

Maximum Minimum retention time

agent height protected height

4 m 4 m 0.0 min.4 m 3.95 m 0.8 min.4m 3.75 m 3.3 min.4 m 3.5 m 6.9 min.4 m 3 m 14.4 min.

Page 90: Door Fan Test_Fire New Installers

D.2. c) Protection expected at D.2. c) Protection expected at the ceilingthe ceiling

Solution: increasing agent from 7% to the NOAEL of 9% and keeping A/C running to ensure continual mixing will provide 7% everywhere after 10 minutes. Since re-ignition will not occur till the concentration drops to 5.5%, this may be used as the lower limit after 10 minutes.

Initial Final retention time

agent % agent %

9 % 7 % 10.0 min.9 % 5.5% 18.6 min.

Page 91: Door Fan Test_Fire New Installers

D.2. d) Common sub-floorD.2. d) Common sub-floor

Typical sub-floor space that connects underneath an adjacent enclosure.

Page 92: Door Fan Test_Fire New Installers

D.2. d) Common sub-floorD.2. d) Common sub-floor

Separate zone #2 with common sub-floor

100% air

Zone #17% FM200

93% air

7% FM20093% air in sub-floor

Common sub-floor and zone #1 floods

Page 93: Door Fan Test_Fire New Installers

D.2. d) Common sub-floorD.2. d) Common sub-floor

Zone #2100% air

2 minutes later, the levels have equalized and protection is lost in Zone #1

Levels equalized between rooms7% FM200, 93% air

Zone #1100% air

sub-floor 7% FM200, 93% air

7% FM20093% air

Page 94: Door Fan Test_Fire New Installers

D.2. e) External ductwork D.2. e) External ductwork connected to building HVACconnected to building HVAC

Huge source of leaks. Hard to control over time.

Solution:

self contained A/C

Page 95: Door Fan Test_Fire New Installers

D.2. f) Sub-floor air D.2. f) Sub-floor air forced into exterior wallsforced into exterior walls

This wall to slab leak will cause air conditioned air to be pushed out by the sub-floor pressurization system to outdoors. In cold climates this will freeze and destroy the wall. In hot climates it will cool the wall and be dripping in condensation 24 hours per day.

Page 96: Door Fan Test_Fire New Installers

D.2. g) Excess energy D.2. g) Excess energy consumptionconsumption

Conditioned air losses through leaks are usually the largest part of the total heat load.

These exterior wall leaks were sealed with expanding foam to hold in the agent but the energy savings will pay back immediately.

Page 97: Door Fan Test_Fire New Installers

D. Enclosure designD. Enclosure design1. The 6 myths about clean agent enclosures

2. Common design problems

3. Design for maximum protection.

Page 98: Door Fan Test_Fire New Installers

D.3. D.3. Design for maximum protectionDesign for maximum protection

a) Slab to slab wallsb) Hard ceiling, no suspended ceilings!c) Maximize protected volumed) Large overlapping caulk bead on wall to lower

slab jointe) Minimize equipment heightf) Self contained A/C or damper at fire barrierg) Seal wall to ceiling with flexible sealh) Seal all cable bundles from inside the bundle

outwardsi) Automatic door closures to prevent door stops

from holding them open during discharge

Page 99: Door Fan Test_Fire New Installers

Conclusion:Conclusion: testing will ensure the enclosure testing will ensure the enclosure

will…will…keep out:

– fire, – smoke, – dust, – humidity, – pollutants, & corrosives

maintain fire suppressant concentration& resist discharge pressures