DOSITEC
ENGLISH
INDEX
1.-GENERAL DESCRIPTION 4
2.-CARRIAGE AND MAINTENANCE 4
3.-TECHNICAL FEATURES 5
4.-OPERATION 6
5.- INSTALLATION 7Generalities 7Hydraulic connection 7Electric connection 9
6.- START UP 10DOSITEC - MP 12DOSITEC - MD 13DOSITEC - mA 14DOSITEC - Q 17
DOSITEC - PRC 20DOSITEC - MF 28
7.- MAINTENANCE List of parts 39
C.E APPROVAL DECLARATION 42
WARRANTY 42
SAFETY RULES
To avoid personal or environmental damages and to guarantee a proper operation of the equipment, the staff in charge of the installation, set up and maintenance of the equipment must follow the instructions of this manual, specially recommendations and warnings explicitly detailed. In additon, specific instructions for the chemical products to be dosed should be followed.
INDEX
1.-GENERAL DESCRIPTION 4
2.-CARRIAGE AND MAINTENANCE 4
3.-TECHNICAL FEATURES 5
4.-OPERATION 6
5.- INSTALLATION 7Generalities 7Hydraulic connection 7Electric connection 9
6.- START UP 10DOSITEC - MP 12DOSITEC - MD 13DOSITEC - mA 14DOSITEC - Q 17
DOSITEC - PRC 20DOSITEC - MF 28
7.- MAINTENANCE List of parts 39
C.E APPROVAL DECLARATION 42
WARRANTY 42
SAFETY RULES
To avoid personal or environmental damages and to guarantee a proper operation of the equipment, the staff in charge of the installation, set up and maintenance of the equipment must follow the instructions of this manual, specially recommendations and warnings explicitly detailed. In additon, specific instructions for the chemical products to be dosed should be followed.
1.- GENERAL DESCRIPTION
The dosing pumps DOSITEC are heavy duty, high precission, electric diaphragm pumps for dosing liquid products.
DOSITEC models:DOSITEC -MP: Manual Regulation from 0 to100% by potentiometerDOSITEC -MD: Manual Regulation from 0 to100% by keyboardDOSITEC - Q: Proportional regulationDOSITEC - mA: Analogic regulation by a current signalDOSITEC - PRC: Control PH or ORP(Redox)DOSITEC - MF: Multifuntion (Manual flow regulation / proportinonal /
Analogical 4-20mA / with timer)
DOSITEC dosing pumps are manufactured with materials that can resist most chemicals products, even acids. They are designed for all sorts of processes where it is necessary to dose a product into a hydraulic network, such as: food, textile, chemical industry, water treatments, etc. (See materials in Technical Features). In case there is any doubt about compatibility of materials with the products to be used please contact ITC S.L. Technical Service.
The metering pump has been designed to feed liquids with capacities from 0 to 20 l/h and pressures from 0 to 10 bar. They also include a conexion for a level switch..
2.- CARRIAGE AND MAINTENANCE
The original packing is thought so that the transport and the storage of the team can be made without causing damages to the team, provided they are made inside dry, aired spaces and far from sources of heat, always maintaining the bomb in vertical position.
Inside the packing it is included:
Dosing pump.1 semirigid PE hose, white, lenght 2m. 2 Flexible PVC hose transparent crystal type, lenght 2m.Injection valve 3/8” BSP-MFiltermanual of instructions
4
3.- TECHNICAL FEATURES
Maximum suction high: 2 mMínimum injection pressure: 0,5 bar
The products are manufactured according CE regulation.• IP 65 protection.• Plastic housing: Polypropylene.• Working temperature: 5-40 ºC• Standard power supply: 230 V (+/-10%) a.c.50 / 60 Hz single phase.• Optional power supply:120 V a.c. 50 / 60 Hz single phase. / 12V d.c.
LIQUID ENDS MATERIALS:
DIAPHRAGM: PTFE.PUMP HEAD: PVDFNIPPLES: PVDF.VÁLVES BODY: PVDFVALVES BALL: CeramicO-RINGS: FPM ( available in EPDM)SUCTION HOSE: PVC flexible.DISCHARGE HOSE : Polyethylene.FILTER: Polypropylene
FLOW-PRESSURE
bar2 64 8 10
l/h
10
6
2
14
12 1614 18 20
12
8
4
16
1 53 7 9 11 1513 17 19
9 l/h@10 bar
6 l/h@ 7 bar
2 l/h@ 20 bar
2,5 l/h@ 10 bar
5
Flowl/h2.5269
2.56
C/min
120120120120120120
Pressure
Bar10207
10107
Stroke length mm
0.81.01.01.40.81.0
PowerWatts
37 (0.16A)
58 (0.25A)
37 (0.16A)
58 (0.25A)
24 (2 A)
24 (2 A)
Power supply Volts
230V AC230V AC230V AC230V AC12V DC12V DC
WeightKg
33.83
3.833
Volumml/cycle
0.350.280.831.250.350.83
1.- GENERAL DESCRIPTION
The dosing pumps DOSITEC are heavy duty, high precission, electric diaphragm pumps for dosing liquid products.
DOSITEC models:DOSITEC -MP: Manual Regulation from 0 to100% by potentiometerDOSITEC -MD: Manual Regulation from 0 to100% by keyboardDOSITEC - Q: Proportional regulationDOSITEC - mA: Analogic regulation by a current signalDOSITEC - PRC: Control PH or ORP(Redox)DOSITEC - MF: Multifuntion (Manual flow regulation / proportinonal /
Analogical 4-20mA / with timer)
DOSITEC dosing pumps are manufactured with materials that can resist most chemicals products, even acids. They are designed for all sorts of processes where it is necessary to dose a product into a hydraulic network, such as: food, textile, chemical industry, water treatments, etc. (See materials in Technical Features). In case there is any doubt about compatibility of materials with the products to be used please contact ITC S.L. Technical Service.
The metering pump has been designed to feed liquids with capacities from 0 to 20 l/h and pressures from 0 to 10 bar. They also include a conexion for a level switch..
2.- CARRIAGE AND MAINTENANCE
The original packing is thought so that the transport and the storage of the team can be made without causing damages to the team, provided they are made inside dry, aired spaces and far from sources of heat, always maintaining the bomb in vertical position.
Inside the packing it is included:
Dosing pump.1 semirigid PE hose, white, lenght 2m. 2 Flexible PVC hose transparent crystal type, lenght 2m.Injection valve 3/8” BSP-MFiltermanual of instructions
4
3.- TECHNICAL FEATURES
Maximum suction high: 2 mMínimum injection pressure: 0,5 bar
The products are manufactured according CE regulation.• IP 65 protection.• Plastic housing: Polypropylene.• Working temperature: 5-40 ºC• Standard power supply: 230 V (+/-10%) a.c.50 / 60 Hz single phase.• Optional power supply:120 V a.c. 50 / 60 Hz single phase. / 12V d.c.
LIQUID ENDS MATERIALS:
DIAPHRAGM: PTFE.PUMP HEAD: PVDFNIPPLES: PVDF.VÁLVES BODY: PVDFVALVES BALL: CeramicO-RINGS: FPM ( available in EPDM)SUCTION HOSE: PVC flexible.DISCHARGE HOSE : Polyethylene.FILTER: Polypropylene
FLOW-PRESSURE
bar2 64 8 10
l/h
10
6
2
14
12 1614 18 20
12
8
4
16
1 53 7 9 11 1513 17 19
9 l/h@10 bar
6 l/h@ 7 bar
2 l/h@ 20 bar
2,5 l/h@ 10 bar
5
Flowl/h2.5269
2.56
C/min
120120120120120120
Pressure
Bar10207
10107
Stroke length mm
0.81.01.01.40.81.0
PowerWatts
37 (0.16A)
58 (0.25A)
37 (0.16A)
58 (0.25A)
24 (2 A)
24 (2 A)
Power supply Volts
230V AC230V AC230V AC230V AC12V DC12V DC
WeightKg
33.83
3.833
Volumml/cycle
0.350.280.831.250.350.83
130
100
5
172
4.- OPERATION
6
The metering pump is activated by a PTFE diaphragm mounted on a piston of an electromagnet.
When the piston of the electromagnet is attracted, a pressure is produced in the pump body with an expulsion of liquid from the discharge valve.Once the electric impulse is finished a spring brings the piston back to the initial position, with a recall of liquid through the suction valve.
As the operation is simple the pump does not need lubrication, therefore maintenance is reduced almost to zero.
The materials used for the construction of the pump make it particularly suitable for aggressive liquids.
DIMENSIONES
190
210
5.- INSTALATIÓN
GENERAL
7
HYDRAULIC CONNECTION
Properly design either in the suction and injection pipe is required, avoiding long lenght and bending pipes as much as possible.t
1
6
4
3
2
1
3
2
4
5
6
1
2
3
4
5
6PRIMING VALVE INJECTION VALVE
SUCTION PIPE COUNTER-PRESSURE VALVE
SUCTION FILTER INJECTION PIPE
Install the pump in a dry place and well away from sources of heat and, in any case, at environmental temperatures not exceeding 40°C. The minimum operating temperature depends on the liquid to be pumped,bearing in mind that it must always remain in a liquid state.
Carefully observe the regulations in force in the various countries as regards electrical installations.When the supply cable is devoid of a plug, the equipment should be connected to the supply mains by means of a single-pole circuit breaker having a minimum distance of 3 mm between the contacts. Before accessing any of the electrical parts, make sure that all the supply circuits are open.
130
100
5
172
4.- OPERATION
6
The metering pump is activated by a PTFE diaphragm mounted on a piston of an electromagnet.
When the piston of the electromagnet is attracted, a pressure is produced in the pump body with an expulsion of liquid from the discharge valve.Once the electric impulse is finished a spring brings the piston back to the initial position, with a recall of liquid through the suction valve.
As the operation is simple the pump does not need lubrication, therefore maintenance is reduced almost to zero.
The materials used for the construction of the pump make it particularly suitable for aggressive liquids.
DIMENSIONES
190
210
5.- INSTALATIÓN
GENERAL
7
HYDRAULIC CONNECTION
Properly design either in the suction and injection pipe is required, avoiding long lenght and bending pipes as much as possible.t
1
6
4
3
2
1
3
2
4
5
6
1
2
3
4
5
6PRIMING VALVE INJECTION VALVE
SUCTION PIPE COUNTER-PRESSURE VALVE
SUCTION FILTER INJECTION PIPE
Install the pump in a dry place and well away from sources of heat and, in any case, at environmental temperatures not exceeding 40°C. The minimum operating temperature depends on the liquid to be pumped,bearing in mind that it must always remain in a liquid state.
Carefully observe the regulations in force in the various countries as regards electrical installations.When the supply cable is devoid of a plug, the equipment should be connected to the supply mains by means of a single-pole circuit breaker having a minimum distance of 3 mm between the contacts. Before accessing any of the electrical parts, make sure that all the supply circuits are open.
8
PRIMINGVALVE
PRIMINGHOSE
Select the most appropiate injection point in the pipe to inject the product, and place there a 3/8” part to connect the Injection valve
INJECTIONHOSE
3/8”
To prime the pump, first connect the priming hose to the priming valve and drive the other side of the hose to a safety place to pour the air mixed with product.
Open the priming valve and start the pump at maximum flow until having only liquid in the priming outlet
Install a safety valve in a derivation as near as possible from the pump , in order to protect it and the wholeinstallation from possible over-pressures. This derivationMust derive the liquid to a safe place.
B C D
9
ELECTRIC CONNECTION
L1 (BLUE)L2 (BROWN)
YELLOW/GREEN
230V AC
1- 2-3- Pulse Input (+)4- Pulse Input (-)
1- Output relay.AL3. NO 2-3- Output relay (Com)4-
1- 2-3- Signal mA (+)4- Signal mA (-)
1- 2-3- Level switch4- Level switch
The electric protection of the motor must be installed and adjusted following its nominal intensity (overloaded switch disjuntor).
A disconnection dispositive must be installed in case of emergency.
The equipment must be protected to avoid untimely sudden starts.
1- 2-3- Level switch4- Level switch
1- Output mA (+)2- Output mA (-)3- Level switch4- Level switch
1- Pt1002- Pt1000 3- Common Pt1004- Common Pt1000
Connector BNCElectrode pHElectrode ORP (redox)
A
E
1- Output relay NO 2- Output relay NC 3- Output relay (Com)4-
1- 2-3- Level switch4- Level switch
MD Q mA PRC
1
2 3
4
A
B
C
D
E
1
2 3
4
1
2 3
4
1
2 3
4
MF
Output RS2321- Transmition2- Reception3- Ground4- Reset
1- Flow sensor2- Flow sensor3- Level switch (remote)4- Level switch (remote)
1- Output relay NO 2- Output relay NC 3- Output relay (Com)4-
1- 2- Signal Input mA (-)3- Pulse Input (+)4- Pulse Input (-)
Signal Input mA (+)
1 2 3 4
8
PRIMINGVALVE
PRIMINGHOSE
Select the most appropiate injection point in the pipe to inject the product, and place there a 3/8” part to connect the Injection valve
INJECTIONHOSE
3/8”
To prime the pump, first connect the priming hose to the priming valve and drive the other side of the hose to a safety place to pour the air mixed with product.
Open the priming valve and start the pump at maximum flow until having only liquid in the priming outlet
Install a safety valve in a derivation as near as possible from the pump , in order to protect it and the wholeinstallation from possible over-pressures. This derivationMust derive the liquid to a safe place.
B C D
9
ELECTRIC CONNECTION
L1 (BLUE)L2 (BROWN)
YELLOW/GREEN
230V AC
1- 2-3- Pulse Input (+)4- Pulse Input (-)
1- Output relay.AL3. NO 2-3- Output relay (Com)4-
1- 2-3- Signal mA (+)4- Signal mA (-)
1- 2-3- Level switch4- Level switch
The electric protection of the motor must be installed and adjusted following its nominal intensity (overloaded switch disjuntor).
A disconnection dispositive must be installed in case of emergency.
The equipment must be protected to avoid untimely sudden starts.
1- 2-3- Level switch4- Level switch
1- Output mA (+)2- Output mA (-)3- Level switch4- Level switch
1- Pt1002- Pt1000 3- Common Pt1004- Common Pt1000
Connector BNCElectrode pHElectrode ORP (redox)
A
E
1- Output relay NO 2- Output relay NC 3- Output relay (Com)4-
1- 2-3- Level switch4- Level switch
MD Q mA PRC
1
2 3
4
A
B
C
D
E
1
2 3
4
1
2 3
4
1
2 3
4
MF
Output RS2321- Transmition2- Reception3- Ground4- Reset
1- Flow sensor2- Flow sensor3- Level switch (remote)4- Level switch (remote)
1- Output relay NO 2- Output relay NC 3- Output relay (Com)4-
1- 2- Signal Input mA (-)3- Pulse Input (+)4- Pulse Input (-)
Signal Input mA (+)
1 2 3 4
10
6.- START UP AND REGULATION
STAND: Check that the pump is properly installed in its stand.
CHECKING OF HYDRAULIC CIRCUIT: Check that all valves are opened and that escapes from priming valves derive the liquid to a proper receptacle
CHECKING OF PUMP: Check visually/auditorilly the proper working of the pump.
OVER-PRESSURE PROTECTION: Adjust the safety valve over-pressure or relief to the wished pressure to protect the installation without exceeding the pump nominal pressure.
ELECTRIC PROTECTION: Adjust the electric dispositive of electric
In this case it is essential to bear in mind the following:
Replace PVC crystal suction hose with polyethilene discharge hose.
Empty any residual water from the pump head beforehand.
Warning: if the water mixes with sulphuric acid it can produce a large quantity of gas with consequent overheating of the area causing damage to valves and pump head.This operation can also be done with the pump disconnected from the plant by turning the pump upside-down for 15 to 30 seconds and without connecting the hose to the nipples; if impossible, dismount and remount the pump head using the four mounting screws.
HOW TO OPERATE WHEN DOSING SULPHURIC ACID
11
HOW TO OPERATE WHEN DOSING SODIUM HYPOCLORITE
Disconnect the pins from the mains or by means of a onnipolar switch with 3 mm minimum distance between the contact.
Disconnect discharge hose from process plant.
Remove the suction hose (with filter) from the tank and dip it into clean water.
Switch on the metering pump and let it operate with water for 5 to 10 minutes.
Switch OFF the pump, dip the filter into a hydrochloric acid solution and wait until the acid finishes cleaning.
Switch ON the pump again and operate it with hydrochloric acid for 5 minutes in a closed-circuit, with suction and discharge hose dipped into the same tank.
Repeat the operation with water.
Re-connect the metering pump to the process plant.
10
6.- START UP AND REGULATION
STAND: Check that the pump is properly installed in its stand.
CHECKING OF HYDRAULIC CIRCUIT: Check that all valves are opened and that escapes from priming valves derive the liquid to a proper receptacle
CHECKING OF PUMP: Check visually/auditorilly the proper working of the pump.
OVER-PRESSURE PROTECTION: Adjust the safety valve over-pressure or relief to the wished pressure to protect the installation without exceeding the pump nominal pressure.
ELECTRIC PROTECTION: Adjust the electric dispositive of electric
In this case it is essential to bear in mind the following:
Replace PVC crystal suction hose with polyethilene discharge hose.
Empty any residual water from the pump head beforehand.
Warning: if the water mixes with sulphuric acid it can produce a large quantity of gas with consequent overheating of the area causing damage to valves and pump head.This operation can also be done with the pump disconnected from the plant by turning the pump upside-down for 15 to 30 seconds and without connecting the hose to the nipples; if impossible, dismount and remount the pump head using the four mounting screws.
HOW TO OPERATE WHEN DOSING SULPHURIC ACID
11
HOW TO OPERATE WHEN DOSING SODIUM HYPOCLORITE
Disconnect the pins from the mains or by means of a onnipolar switch with 3 mm minimum distance between the contact.
Disconnect discharge hose from process plant.
Remove the suction hose (with filter) from the tank and dip it into clean water.
Switch on the metering pump and let it operate with water for 5 to 10 minutes.
Switch OFF the pump, dip the filter into a hydrochloric acid solution and wait until the acid finishes cleaning.
Switch ON the pump again and operate it with hydrochloric acid for 5 minutes in a closed-circuit, with suction and discharge hose dipped into the same tank.
Repeat the operation with water.
Re-connect the metering pump to the process plant.
12
DOSITEC MP
MANUAL REGULATION DOSING PUMP
Flow can be controlled manually by setting the pump pulse rate by means of a potentiometer. Possibility of a more precise flow rate setting at low frequencies through the two keys 20% and 100%.
1 3 4 2
5
6
7
8
9
1 START button2 STOP button3 20% flow scale read out button4 100% flow scale read out button5 Adjustment knob of injections/min (0-100%)6 Power LED 7 Pulse LED 8 20% flow scale read out LED9 100% flow scale read out LED
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
13
DOSITEC MD
Flow can be controlled manually by setting the pump pulse rate through the keypad from 0 to 100%.
2 3 1
4
5
6
1 Increasing value button2 Decreasing value button3 START /STOP button4 Display 5 Power LED6 Pulse LED
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
MANUAL REGULATION DOSING PUMP
12
DOSITEC MP
MANUAL REGULATION DOSING PUMP
Flow can be controlled manually by setting the pump pulse rate by means of a potentiometer. Possibility of a more precise flow rate setting at low frequencies through the two keys 20% and 100%.
1 3 4 2
5
6
7
8
9
1 START button2 STOP button3 20% flow scale read out button4 100% flow scale read out button5 Adjustment knob of injections/min (0-100%)6 Power LED 7 Pulse LED 8 20% flow scale read out LED9 100% flow scale read out LED
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
13
DOSITEC MD
Flow can be controlled manually by setting the pump pulse rate through the keypad from 0 to 100%.
2 3 1
4
5
6
1 Increasing value button2 Decreasing value button3 START /STOP button4 Display 5 Power LED6 Pulse LED
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
MANUAL REGULATION DOSING PUMP
14
DOSITEC mA
ANALOGIC 4-20mA DOSING PUMP
Microcontrolled dosing pump with a 4-20mA input for the flow regulation.
6 2 3 7
5
13
14
11
1
1 Display selector button (mA / pulse)2 Increasing values button3 Decreasing values button4 Function slection button5 Enter button6 Pulse displaying LED7 Manula function LED 8 LED SET POINT 2 / STOP9 LED SET POINT 1 / STOP10 Meter functionLED 11 mA displaying LED 12 Display13 Pulse LED 14 Level alarm LED
12 10
4 8 9
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
15
LEVEL CONTROL (UPON REQUEST)If the dosing pump is supplied with level control setting and upon request floating level switch. When the level of the additive is lower than the switch, level alarm goes ON, the display will show "FAO", the pump is off giving an optical and sound alarm. The level control alarm goes ON with 5 seconds delay.
Turning on the pump, the instrument switches automatically to the "METER" function.
Pressing button mA pulse will show the actual mA input signal. To go back to strokes/min press again.
In order to avoid programming and setting errors during the system functioning, the pump is programmed to automatically return to the Meter Mode each time the unit is switched OFF.
Switch to manual function and select a high frequency to prime the pump.
PROGRAMMING
SET POINT 1Mode Set 1 is used to select the mA input value/min. dosing pump flow and pulse frequency.
Press “F” button and Set 1 LED will switch on. The display will show the pulse frequency previously set. Select the minimum pump output required pressing “+/-” buttons. If the minimum output is zero set 000.
Press “mA/pulse” button, “mA” LED will switch on:
By pressing “+/-” buttons, you can select the mA input value corresponding to minimum pump output required.
Confirm with “Enter”.
STARTING THE PUMP
PRIMING
Press the “F” button to switch to MANUA function.Increase or decrease the injection/min through “+ /-” buttons (recomended about 75% of maximum frequency)
14
DOSITEC mA
ANALOGIC 4-20mA DOSING PUMP
Microcontrolled dosing pump with a 4-20mA input for the flow regulation.
6 2 3 7
5
13
14
11
1
1 Display selector button (mA / pulse)2 Increasing values button3 Decreasing values button4 Function slection button5 Enter button6 Pulse displaying LED7 Manula function LED 8 LED SET POINT 2 / STOP9 LED SET POINT 1 / STOP10 Meter functionLED 11 mA displaying LED 12 Display13 Pulse LED 14 Level alarm LED
12 10
4 8 9
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
15
LEVEL CONTROL (UPON REQUEST)If the dosing pump is supplied with level control setting and upon request floating level switch. When the level of the additive is lower than the switch, level alarm goes ON, the display will show "FAO", the pump is off giving an optical and sound alarm. The level control alarm goes ON with 5 seconds delay.
Turning on the pump, the instrument switches automatically to the "METER" function.
Pressing button mA pulse will show the actual mA input signal. To go back to strokes/min press again.
In order to avoid programming and setting errors during the system functioning, the pump is programmed to automatically return to the Meter Mode each time the unit is switched OFF.
Switch to manual function and select a high frequency to prime the pump.
PROGRAMMING
SET POINT 1Mode Set 1 is used to select the mA input value/min. dosing pump flow and pulse frequency.
Press “F” button and Set 1 LED will switch on. The display will show the pulse frequency previously set. Select the minimum pump output required pressing “+/-” buttons. If the minimum output is zero set 000.
Press “mA/pulse” button, “mA” LED will switch on:
By pressing “+/-” buttons, you can select the mA input value corresponding to minimum pump output required.
Confirm with “Enter”.
STARTING THE PUMP
PRIMING
Press the “F” button to switch to MANUA function.Increase or decrease the injection/min through “+ /-” buttons (recomended about 75% of maximum frequency)
16
To finish the programming procedure and modify the maximum output value, press “F” button which will automatically change to mode Set 2.
SET POINT 2
Mode Set 2 selects the mA input value/max. dosing pump flow and pulse/frequency.
Press “F” button and Set 2 LED wil switch on, the display will show the frequency previously set.
Press buttons “+/-” to set the desired imp/frequency at the maximum pump output required.
Press button “mA/pulse”, the display will show the value previously set.
Pressing “+/-” select the mA input value at the maximum pump output required.
Press Enter button.
Direct Functioning ModeDuring production the pumps are programmed for a 4-20 mA direct functioning curve. The pump will start every time the mA signal goes above 4 mA increasing the pulse frequency (and consequently the flow) proportionally to the mA input signal up to maximum imp/min frequency available. E.G. Set 1 minimum signal 4 mA, minimum output. Set 2 maximum signal 20 mA, maximum output.
Reverse Functioning ModeReverse functioning is when the mA signal increases and pump output proportionally decreases. Select the maximum mA signal required with mode Set 1 (in relation to the min. output). E.G. Set 1 maximum signal 20 mA, minimum output.Set 2 minimum signal 4 mA, maximum output.
WARNING: Reverse functioning can only be selected when mode Set 1 is always higher than the mA signal.
Example n° 1: DOSITEC-mA, 10 L/H, 5 BAR, SIGNAL 4-20 mA.Signal 4 mA = 0 l/h (0% pump flow rate)Signal 12 mA = 5 l/h (50% pump flow rate)Signal 20 mA = 10 l/h (100% pump flow rate)
Example n° 2: SAME MODEL , BUT WITH INVERSE SIGNAL: 20 - 4 mASignal 4 mA = 10 l/h (100% pump flow rate)Signal 12 mA = 5 l/h (50% pump flow rate)Signal 20 mA = 0 l/h (0% pump flow rate
17
DOSITEC Q
PROPORTIONAL DOSING PUMP
Microcontrolled dosing pump with a water counter input, for a proportional dosing. Possibility to set a proportion between the pulses from the water counter and the pulses of the dosing pump.
1 3 4 2
56
7
8
9
1 Decreasing values button2 Increasing values button3 Function selection button4 START / STOP button5 Display6 Power LED 7 Pulse LED 8 1xN LED / manual function9 1XN (M) LED10 1:N LED
10
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
16
To finish the programming procedure and modify the maximum output value, press “F” button which will automatically change to mode Set 2.
SET POINT 2
Mode Set 2 selects the mA input value/max. dosing pump flow and pulse/frequency.
Press “F” button and Set 2 LED wil switch on, the display will show the frequency previously set.
Press buttons “+/-” to set the desired imp/frequency at the maximum pump output required.
Press button “mA/pulse”, the display will show the value previously set.
Pressing “+/-” select the mA input value at the maximum pump output required.
Press Enter button.
Direct Functioning ModeDuring production the pumps are programmed for a 4-20 mA direct functioning curve. The pump will start every time the mA signal goes above 4 mA increasing the pulse frequency (and consequently the flow) proportionally to the mA input signal up to maximum imp/min frequency available. E.G. Set 1 minimum signal 4 mA, minimum output. Set 2 maximum signal 20 mA, maximum output.
Reverse Functioning ModeReverse functioning is when the mA signal increases and pump output proportionally decreases. Select the maximum mA signal required with mode Set 1 (in relation to the min. output). E.G. Set 1 maximum signal 20 mA, minimum output.Set 2 minimum signal 4 mA, maximum output.
WARNING: Reverse functioning can only be selected when mode Set 1 is always higher than the mA signal.
Example n° 1: DOSITEC-mA, 10 L/H, 5 BAR, SIGNAL 4-20 mA.Signal 4 mA = 0 l/h (0% pump flow rate)Signal 12 mA = 5 l/h (50% pump flow rate)Signal 20 mA = 10 l/h (100% pump flow rate)
Example n° 2: SAME MODEL , BUT WITH INVERSE SIGNAL: 20 - 4 mASignal 4 mA = 10 l/h (100% pump flow rate)Signal 12 mA = 5 l/h (50% pump flow rate)Signal 20 mA = 0 l/h (0% pump flow rate
17
DOSITEC Q
PROPORTIONAL DOSING PUMP
Microcontrolled dosing pump with a water counter input, for a proportional dosing. Possibility to set a proportion between the pulses from the water counter and the pulses of the dosing pump.
1 3 4 2
56
7
8
9
1 Decreasing values button2 Increasing values button3 Function selection button4 START / STOP button5 Display6 Power LED 7 Pulse LED 8 1xN LED / manual function9 1XN (M) LED10 1:N LED
10
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
18
LEVEL CONTROL (UPON REQUEST)If the dosing pump is supplied with level control setting and upon request floating level switch. When the level of the additive is lower than the switch, level alarm goes ON, the display will show "FAO", the pump is off giving an optical and sound alarm. The level control alarm goes ON with 5 seconds delay.
PROGRAMMING
MANUAL MODEIn manual mode select the desired injection frequency by pressing the arrow buttons, and starting with the “START/STOP” button.
PROPORCIONAL MODE
2)Select the desired proportion value by pressing buttons.3) Confirm value with button
Note: The injection velocity is selected in the manual mode
1001XN 1XN(M) FC tFF
MANUAL MODE PROPORTIONAL MODE
1XN ModeThe pump is operated by an impulse produced by an external device (e.g. pulse emitting water meter) and it supplies a number of injections equal to the value visualized on the display "N" (set by the operator). In case during the dosing of the "N strokes" other pulses arrive, these are neglected.
Example:- Pump set in water meter 1XN mode- Set value on "20"- At the time the water meter gives a pulse to the pump, it starts its 20 dosing injection strokes, if during this phase further shuts of the contact occur, these are neglected. Ended up the 20 injections, the pump is waiting for further pulses from the water meter to restart the dosing cycle.
1XN (M) MODELike in the 1XN mode but the microprocessor save in its memory all the received pulses.
ExampleThe pump receives the first contact and returns a string "N" injections to the maximum frequency (e.g. 120 imps./min).
To the arrival of the second contact, the pump computes the time "T" spent by the arrival of the first one and it returns a string of "N" injections not more to the maximum frequency but to that it allows to uniformly distribute them in the time "T".
If instead quick contacts goes to the condition N1>4 , the pump goes in alarm(AL3), the pump continues working, b
1:N MODEThe pump supplies an injection of chemical only when it has reached a number of pulses (contacts), equal to the value visualized on the display (set by the operator)
Example::- Pump set in water meter 1XN mode- Set value on "20”- At the time the water meter gives 20 pulses, the pump gives one pulse.
ut will miss the remaining injections.
19
100
1XN(M) FC t
1XN 1 1XN(M) MODE
1XN(M) 1
1:N MODE
1:N 1
FF
FF
4)Starting with the button.
STARTSTOP
1XN(M) FC t1XN 10
1)Select the desired injection frequency by pressing
2)Confirm by
3)Starting with the buttonSTARTSTOP
STARTSTOP
1XN MODEFF
STARTSTOP
1)Select the desired mode
18
LEVEL CONTROL (UPON REQUEST)If the dosing pump is supplied with level control setting and upon request floating level switch. When the level of the additive is lower than the switch, level alarm goes ON, the display will show "FAO", the pump is off giving an optical and sound alarm. The level control alarm goes ON with 5 seconds delay.
PROGRAMMING
MANUAL MODEIn manual mode select the desired injection frequency by pressing the arrow buttons, and starting with the “START/STOP” button.
PROPORCIONAL MODE
2)Select the desired proportion value by pressing buttons.3) Confirm value with button
Note: The injection velocity is selected in the manual mode
1001XN 1XN(M) FC tFF
MANUAL MODE PROPORTIONAL MODE
1XN ModeThe pump is operated by an impulse produced by an external device (e.g. pulse emitting water meter) and it supplies a number of injections equal to the value visualized on the display "N" (set by the operator). In case during the dosing of the "N strokes" other pulses arrive, these are neglected.
Example:- Pump set in water meter 1XN mode- Set value on "20"- At the time the water meter gives a pulse to the pump, it starts its 20 dosing injection strokes, if during this phase further shuts of the contact occur, these are neglected. Ended up the 20 injections, the pump is waiting for further pulses from the water meter to restart the dosing cycle.
1XN (M) MODELike in the 1XN mode but the microprocessor save in its memory all the received pulses.
ExampleThe pump receives the first contact and returns a string "N" injections to the maximum frequency (e.g. 120 imps./min).
To the arrival of the second contact, the pump computes the time "T" spent by the arrival of the first one and it returns a string of "N" injections not more to the maximum frequency but to that it allows to uniformly distribute them in the time "T".
If instead quick contacts goes to the condition N1>4 , the pump goes in alarm(AL3), the pump continues working, b
1:N MODEThe pump supplies an injection of chemical only when it has reached a number of pulses (contacts), equal to the value visualized on the display (set by the operator)
Example::- Pump set in water meter 1XN mode- Set value on "20”- At the time the water meter gives 20 pulses, the pump gives one pulse.
ut will miss the remaining injections.
19
100
1XN(M) FC t
1XN 1 1XN(M) MODE
1XN(M) 1
1:N MODE
1:N 1
FF
FF
4)Starting with the button.
STARTSTOP
1XN(M) FC t1XN 10
1)Select the desired injection frequency by pressing
2)Confirm by
3)Starting with the buttonSTARTSTOP
STARTSTOP
1XN MODEFF
STARTSTOP
1)Select the desired mode
20
DOSITEC PRC
PH, ORP (REDOX) DOSING PUMP
1 3 4 2
67
8
9
5
Microcontrolled dosing pump for PH or ORP(redox) control
1 Decreasing values button2 Increasing values button3 Escape button4 Cursor movement5 Enter button6 LCD display 7 Power LED 8 Pulse LED9 Alarm LED
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
21
DISPLAY DESCRIPTION
OVER Overdosing alarmDELAY Delay at powering onSET POINT Set point settingLEVEL Level alarmALARM Alarms settingMENU Menu selectionON-OFF ON-OFF functioning modePROP Proportional functioning modeHYST Hysteresis setting12 Calibration pointsCALIB Calibration menuSETUP General instrument settingSTARTUP Switching on delay settingINPUT MODE Level probe/flow sensor input activationRESET Reset activationDIRECTION Intervention selectionMAX Maximum pulses frequency based to maximum measuring value4 20 mA Output current settingsh:m:s Hours:minutes:secondsPH pH measureRx mV measure% Flow rate percentage
Password settingIntervention Alkaline/Oxidant/DirectaIntervention Acid/Reductive/Inversepulses/minuteFlow sensorNumeric values visualization
20
DOSITEC PRC
PH, ORP (REDOX) DOSING PUMP
1 3 4 2
67
8
9
5
Microcontrolled dosing pump for PH or ORP(redox) control
1 Decreasing values button2 Increasing values button3 Escape button4 Cursor movement5 Enter button6 LCD display 7 Power LED 8 Pulse LED9 Alarm LED
ACCESSORIES
- 1 flexible transparent PVC suction hose 2m- 1 semirig white PE injection hose 2m- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose.
21
DISPLAY DESCRIPTION
OVER Overdosing alarmDELAY Delay at powering onSET POINT Set point settingLEVEL Level alarmALARM Alarms settingMENU Menu selectionON-OFF ON-OFF functioning modePROP Proportional functioning modeHYST Hysteresis setting12 Calibration pointsCALIB Calibration menuSETUP General instrument settingSTARTUP Switching on delay settingINPUT MODE Level probe/flow sensor input activationRESET Reset activationDIRECTION Intervention selectionMAX Maximum pulses frequency based to maximum measuring value4 20 mA Output current settingsh:m:s Hours:minutes:secondsPH pH measureRx mV measure% Flow rate percentage
Password settingIntervention Alkaline/Oxidant/DirectaIntervention Acid/Reductive/Inversepulses/minuteFlow sensorNumeric values visualization
22
PARAMETERS AND FUNCTIONS LAYOUT
Selection measures to control pHSetpoint setting 7.2Hysteresis setting 0.1Choice of the type of intervention AcidON/OFF or Proportional intervention selection ON-OFFDefinition of beginning intervention value”PROP” Setpoint+1pHFirst point of calibration procedure ---Second point of calibration procedure ---Minimum alarm point 0.00Maximum alarm point 14.00Over-dosing alarm value 02:00 (h:m)Choise of the type of menu: BASE / FULL BASESix figures numerical pasword DisableDelay at powering on 00:03 (m:s)Delay exit calibration menu 05:00 (m:s)Calibration check 4 mA 4 mACalibration check 20 mA 20 mA
TYPICAL CHARACTERISTICS
Temperature 0-40ºCMax. Current relay output 6A (resisitve load) 1A ( inductive load)Current output 4-20mA (dynamic 0-500Ohm)PH measure 0-14 (0.01 pH) ORP (mV) mesure -1000 - +1400 (+/-1mV)
LEVEL CONTROL
PROGRAMATION
Press to enter in menus, and press you will scroll all 4 menus:
SETUP menu press to reach the desired menu BASE / FULL
Press to change the parameters of setup:
On the display will appear the set measure type pH or mV Change by means “+/-” and confirm through “ENT”:
DOSITEC PRC is supplied with level control setting.When the chemical tank is empty, on the display will appear LEVEL and the pump goes in stand by. The level control has 5 seconds of delay.
The first operation to do is to select the type of parameter (pH or Redox) that is intends to measure and to control.
The pump has turned on, on display it appears software revision then the type of controlled parameter that it flashes (default setting pH)Set measure type by means on the “+/-” and confirm through “ENT”
On display will show the measure's value.
23
ENT
SETUP
pH
pH
7.10
MENUSETPOINT
MENU
SETUP
MENU
CALIB
MENU
ALARM
MENU
SETUP
MENU
SETUP base
MENU
SETUP fullENT
SETUP
pH
ENT
22
PARAMETERS AND FUNCTIONS LAYOUT
Selection measures to control pHSetpoint setting 7.2Hysteresis setting 0.1Choice of the type of intervention AcidON/OFF or Proportional intervention selection ON-OFFDefinition of beginning intervention value”PROP” Setpoint+1pHFirst point of calibration procedure ---Second point of calibration procedure ---Minimum alarm point 0.00Maximum alarm point 14.00Over-dosing alarm value 02:00 (h:m)Choise of the type of menu: BASE / FULL BASESix figures numerical pasword DisableDelay at powering on 00:03 (m:s)Delay exit calibration menu 05:00 (m:s)Calibration check 4 mA 4 mACalibration check 20 mA 20 mA
TYPICAL CHARACTERISTICS
Temperature 0-40ºCMax. Current relay output 6A (resisitve load) 1A ( inductive load)Current output 4-20mA (dynamic 0-500Ohm)PH measure 0-14 (0.01 pH) ORP (mV) mesure -1000 - +1400 (+/-1mV)
LEVEL CONTROL
PROGRAMATION
Press to enter in menus, and press you will scroll all 4 menus:
SETUP menu press to reach the desired menu BASE / FULL
Press to change the parameters of setup:
On the display will appear the set measure type pH or mV Change by means “+/-” and confirm through “ENT”:
DOSITEC PRC is supplied with level control setting.When the chemical tank is empty, on the display will appear LEVEL and the pump goes in stand by. The level control has 5 seconds of delay.
The first operation to do is to select the type of parameter (pH or Redox) that is intends to measure and to control.
The pump has turned on, on display it appears software revision then the type of controlled parameter that it flashes (default setting pH)Set measure type by means on the “+/-” and confirm through “ENT”
On display will show the measure's value.
23
ENT
SETUP
pH
pH
7.10
MENUSETPOINT
MENU
SETUP
MENU
CALIB
MENU
ALARM
MENU
SETUP
MENU
SETUP base
MENU
SETUP fullENT
SETUP
pH
ENT
24
ENT
Will appear the protection password.OFF: password dissable
To enable the pasword mode press “+ / -” Set a password through “+/-” to increase or decrease value. Change digit through right arrow. Press “ENT”to confirm the password
After the password has been determined, it is possible to set up the type of sensor that is necessary to install the pump: When a level sensor is needed to be connected, the LEVEL warning will appear, when is necessary to connect a proximity sensor this icon will appear
On the display will appear the menu to select the time the pump will use to quite from calibration phase setting to come back to the main measuring display.Press ”+/-” to set the delay time and confirm with “ENT”
On the display will appear to set the delay time from pump switching-onPress “+/-” for change the time and “ENT” to confirm.
To solve the problem of inertia of someone electrodes or plant installation, the pump has the possibility to set de delay time from pump switching-on to the measuring and control moment.
CALIBRATION menu press set calibration
PH calibration:On the display will appear “POINT 1” Put the electrode in buffer solution pH7Adjust the value on the display up to reach 7.00 with “+/-” and press “ENT” to confirm
On the display will appear “POINT 2” Put the electrode after washing with tap water in the second buffer solution 4.00 or 9.00 pH Adjust the value on the display up to reach 4.00 or 9.00 with “+/-” and press “ENT” to confirm
MENU
SETUP offMENU
SETUP oooo
INPUT MODE
LEVEL
MENU
CALIB
DELAY h:m:s
10:00
DELAY h:m:sSTARTUP
00:03
MENU
CALIB
CALIB
pH
7.001POINT
CALIB
pH
4.002POINT
ORP (redox) calibration:POINT 1: put in short circuit the BNC connector . Using a metal wire, connected the core pin with the external cylinder part.Adjust the value on the display up to reach 0 using “+/-” and press “ENT” to confirm.Point 2: put the electrode in buffer solution (250, 475,650 mV)Adjust the value on the display up to reach the buffer solution value using “+/-” and press “ENT” to confirm.
SETPOINT menu press to change the set point
On display will appear the set point valueAdjust using “+/-”, and press “ENT” to confirm
On display will appear the menu to set if the pump has to dose above the set point or bellow this valueFor dosing an acid chemical select ” “ and for dosing alkaline chemical select “ “
Select with ”+/-” and press “ENT” to confirm
On display will appear the “HYSTERESIS” menu (only with ”FULL” menu) , this is the distance from the set point value, over this value the pump starts or stops it`s dosing Press ”+/-” to set the value and confirm with “ENT”
On display will appear to select the regulation mode:ON-OFF- when the pump has to dose it will run at flow rate selected by the user in Flow rate setting , and iit stops at the Setpoint.
PROP- when the pump will dose proportionality to the set point value. The pump star dosing over setpoint , increasing it’s speed up to the max frequency adjustment use will set.Press ”+/-” to select and confirm with “ENT”
25
MENUSETPOINT
ENT
SET pH
7.50POINT
SET
DIRECTION
POINT
HYST
0.05POINTSET
pH
MODE
SET
ON-OFF
POINT
MODE
SET
PROP.
POINT
24
ENT
Will appear the protection password.OFF: password dissable
To enable the pasword mode press “+ / -” Set a password through “+/-” to increase or decrease value. Change digit through right arrow. Press “ENT”to confirm the password
After the password has been determined, it is possible to set up the type of sensor that is necessary to install the pump: When a level sensor is needed to be connected, the LEVEL warning will appear, when is necessary to connect a proximity sensor this icon will appear
On the display will appear the menu to select the time the pump will use to quite from calibration phase setting to come back to the main measuring display.Press ”+/-” to set the delay time and confirm with “ENT”
On the display will appear to set the delay time from pump switching-onPress “+/-” for change the time and “ENT” to confirm.
To solve the problem of inertia of someone electrodes or plant installation, the pump has the possibility to set de delay time from pump switching-on to the measuring and control moment.
CALIBRATION menu press set calibration
PH calibration:On the display will appear “POINT 1” Put the electrode in buffer solution pH7Adjust the value on the display up to reach 7.00 with “+/-” and press “ENT” to confirm
On the display will appear “POINT 2” Put the electrode after washing with tap water in the second buffer solution 4.00 or 9.00 pH Adjust the value on the display up to reach 4.00 or 9.00 with “+/-” and press “ENT” to confirm
MENU
SETUP offMENU
SETUP oooo
INPUT MODE
LEVEL
MENU
CALIB
DELAY h:m:s
10:00
DELAY h:m:sSTARTUP
00:03
MENU
CALIB
CALIB
pH
7.001POINT
CALIB
pH
4.002POINT
ORP (redox) calibration:POINT 1: put in short circuit the BNC connector . Using a metal wire, connected the core pin with the external cylinder part.Adjust the value on the display up to reach 0 using “+/-” and press “ENT” to confirm.Point 2: put the electrode in buffer solution (250, 475,650 mV)Adjust the value on the display up to reach the buffer solution value using “+/-” and press “ENT” to confirm.
SETPOINT menu press to change the set point
On display will appear the set point valueAdjust using “+/-”, and press “ENT” to confirm
On display will appear the menu to set if the pump has to dose above the set point or bellow this valueFor dosing an acid chemical select ” “ and for dosing alkaline chemical select “ “
Select with ”+/-” and press “ENT” to confirm
On display will appear the “HYSTERESIS” menu (only with ”FULL” menu) , this is the distance from the set point value, over this value the pump starts or stops it`s dosing Press ”+/-” to set the value and confirm with “ENT”
On display will appear to select the regulation mode:ON-OFF- when the pump has to dose it will run at flow rate selected by the user in Flow rate setting , and iit stops at the Setpoint.
PROP- when the pump will dose proportionality to the set point value. The pump star dosing over setpoint , increasing it’s speed up to the max frequency adjustment use will set.Press ”+/-” to select and confirm with “ENT”
25
MENUSETPOINT
ENT
SET pH
7.50POINT
SET
DIRECTION
POINT
HYST
0.05POINTSET
pH
MODE
SET
ON-OFF
POINT
MODE
SET
PROP.
POINT
2626 27
When select ON-OFF, on the display will appears the maximum frequency adjustmentPress “+/-” to change and “ENT” to confirm
Only in ON-OFF mode it is possible to define the time delay before pump start -up, when going out of the setpoint Press “+/-” to change and “ENT” to confirm
When select PROP, on the display will appear the maximum measure value to which the pump has to dose at the maximum frequencyPress “+/-” to change and confirm with “ENT”
Only in PROP mode, on the display will appear the maximum frequency adjustment corresponding to the previous value.Press “+/-” to change and confirm with “ENT”
Only in PROP mode, on the display will appear frequency adjustment corresponding to the SetpointPress “+/-” to change and confirm with“ENT”
On the display will appear two measurers values that correspond to the 4-20mA outputPress “+/-” to set the value of the measure to which it has to correspond 4mA output, and confirm with “ENT”
Press “+/-” to set the value of the measure to which it has to correspond 20mA output, and confirm with “ENT”
ALARM menu press to enter in alarm mode
On the display will appear the MAXIMUM value of the measure, where the pump has to go in alarm mode.Press “+/-” to set the value and confirm with “ENT”
SET
ON-OFF
100POINT
%
SET
DELAY m:s
00.03POINT
SET 8.20POINT
PROP. MAX
pH
SET 100POINT
%
PROP. MAX
pH
SET 0POINT
%
PROP.
pH
min
SET
4 mA
0.00POINT
pH
SET
20mA
14.00POINT
pH
MENU
ENTALARM
ALARM
pH
MAX
14.00
On the display will appear MINIMUM value of the measure, at which the pump has to go in alarm mode.Press “+/-” to change the value and confirm with “ENT”
On the display will appear OVER DELAY ,which is the maximum time allowed to reach the set point value. Over this time, the pump will go in alarm modePress “+/-” to change the value and confirm with “ENT”. Press “ESC” to return in measure mode
RESET procedure (partial o total)Turn off and turn on the pump
Press press at the same time With this procedure a PARTIAL reset will be actived, the pump return to the default settings but all the calibration will be saved
Press twice then press will appear
With this procedure a TOTAL reset will be actived, the pump return to the default settings and all the calibration parameters will be lost.
Press twice then press will appear
With STANBD-BY procedure, the pump is put on stand by
Hold down at until a same time appears
In order to exit this mode, hold down keys “+ / -” at the same time.
ALARM
pH
min
0.00
ALARMOVER DELAY
pH
h:m
02:00
ENTMENUSETPOINT
RESET
RESET
RESET
2626 27
When select ON-OFF, on the display will appears the maximum frequency adjustmentPress “+/-” to change and “ENT” to confirm
Only in ON-OFF mode it is possible to define the time delay before pump start -up, when going out of the setpoint Press “+/-” to change and “ENT” to confirm
When select PROP, on the display will appear the maximum measure value to which the pump has to dose at the maximum frequencyPress “+/-” to change and confirm with “ENT”
Only in PROP mode, on the display will appear the maximum frequency adjustment corresponding to the previous value.Press “+/-” to change and confirm with “ENT”
Only in PROP mode, on the display will appear frequency adjustment corresponding to the SetpointPress “+/-” to change and confirm with“ENT”
On the display will appear two measurers values that correspond to the 4-20mA outputPress “+/-” to set the value of the measure to which it has to correspond 4mA output, and confirm with “ENT”
Press “+/-” to set the value of the measure to which it has to correspond 20mA output, and confirm with “ENT”
ALARM menu press to enter in alarm mode
On the display will appear the MAXIMUM value of the measure, where the pump has to go in alarm mode.Press “+/-” to set the value and confirm with “ENT”
SET
ON-OFF
100POINT
%
SET
DELAY m:s
00.03POINT
SET 8.20POINT
PROP. MAX
pH
SET 100POINT
%
PROP. MAX
pH
SET 0POINT
%
PROP.
pH
min
SET
4 mA
0.00POINT
pH
SET
20mA
14.00POINT
pH
MENU
ENTALARM
ALARM
pH
MAX
14.00
On the display will appear MINIMUM value of the measure, at which the pump has to go in alarm mode.Press “+/-” to change the value and confirm with “ENT”
On the display will appear OVER DELAY ,which is the maximum time allowed to reach the set point value. Over this time, the pump will go in alarm modePress “+/-” to change the value and confirm with “ENT”. Press “ESC” to return in measure mode
RESET procedure (partial o total)Turn off and turn on the pump
Press press at the same time With this procedure a PARTIAL reset will be actived, the pump return to the default settings but all the calibration will be saved
Press twice then press will appear
With this procedure a TOTAL reset will be actived, the pump return to the default settings and all the calibration parameters will be lost.
Press twice then press will appear
With STANBD-BY procedure, the pump is put on stand by
Hold down at until a same time appears
In order to exit this mode, hold down keys “+ / -” at the same time.
ALARM
pH
min
0.00
ALARMOVER DELAY
pH
h:m
02:00
ENTMENUSETPOINT
RESET
RESET
RESET
28
DOSITEC MF
MULTI-FUNCTION DOSING PUMP
Dosing pump controlled by a microprocessor that allows a manual flow regulation, which is proportional to an incoming pulse rate, 4-20 mA analogical external signal, or with timer.
1 3 4 2
67
8
9
1 Decreasing value button2 Increasing value button3 Previous program button4 Next program button5 START / STOP button6 Display7 Power LED 8 Injection sign LED9 Alarm sign LED
ACCESORIES
- 1 flexible transparent PVC suction hose of 2m (6.56 feet)- 1 semi rigid white PE injection hose of 2m (6.56 feet)- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose
5 MF
STARTSTOP
15:02120 P/MMAN.
29
ALARM LEVEL When the level sensor is connected to the dosing pump (D connector) and detects a lack of additive, stops the injection. This control level have a 5 minutes delay.
PROGRAMMINGFirst screens
Press START/STOP to confirm the value. It will start running automatically according to the selected frequency.
MENU SELECT
MANUALMENU SELECT
PULSE / MIN.
MENU SELECT
PULSE / HR.
MENU SELECT
PULSE / DAY
Select the pulse / minute value through
PULSE / MINUTE
120
Select the pulse / hour value through PULSE / HOUR
120
Select the pulse / day value through
PULSE / DAY
48
First step: define the dosing control mode - MANUAL / 1xN / 1xN(M) / 1-N / mA / PPM
MANUAL MODEThis method allows to operate the pump automatically, running a constant dosing. The pulse rate can be predetermine upon 3 different scales.
MAN. 120P/M
00:00
MENU SELECT
MANUALMENU SELECT
1xN
MENU SELECT
1xN(M)
MENU SELECT
mA
MENU SELECT
PPM
MENU SELECT
1-N
MENU SELECT
ALARM
MENU SELECT
REMOTE
MENU SELECT
BUZZERMENU SELECT
CLOCK
MENU SELECT
TIMER
MENU SELECT
LENGUAGE
28
DOSITEC MF
MULTI-FUNCTION DOSING PUMP
Dosing pump controlled by a microprocessor that allows a manual flow regulation, which is proportional to an incoming pulse rate, 4-20 mA analogical external signal, or with timer.
1 3 4 2
67
8
9
1 Decreasing value button2 Increasing value button3 Previous program button4 Next program button5 START / STOP button6 Display7 Power LED 8 Injection sign LED9 Alarm sign LED
ACCESORIES
- 1 flexible transparent PVC suction hose of 2m (6.56 feet)- 1 semi rigid white PE injection hose of 2m (6.56 feet)- 1 injection valve 3/8”- 1 filter- 1 instructions manual- 1 flexible transparent PVC priming hose
5 MF
STARTSTOP
15:02120 P/MMAN.
29
ALARM LEVEL When the level sensor is connected to the dosing pump (D connector) and detects a lack of additive, stops the injection. This control level have a 5 minutes delay.
PROGRAMMINGFirst screens
Press START/STOP to confirm the value. It will start running automatically according to the selected frequency.
MENU SELECT
MANUALMENU SELECT
PULSE / MIN.
MENU SELECT
PULSE / HR.
MENU SELECT
PULSE / DAY
Select the pulse / minute value through
PULSE / MINUTE
120
Select the pulse / hour value through PULSE / HOUR
120
Select the pulse / day value through
PULSE / DAY
48
First step: define the dosing control mode - MANUAL / 1xN / 1xN(M) / 1-N / mA / PPM
MANUAL MODEThis method allows to operate the pump automatically, running a constant dosing. The pulse rate can be predetermine upon 3 different scales.
MAN. 120P/M
00:00
MENU SELECT
MANUALMENU SELECT
1xN
MENU SELECT
1xN(M)
MENU SELECT
mA
MENU SELECT
PPM
MENU SELECT
1-N
MENU SELECT
ALARM
MENU SELECT
REMOTE
MENU SELECT
BUZZERMENU SELECT
CLOCK
MENU SELECT
TIMER
MENU SELECT
LENGUAGE
30
PROPORTIONAL MODEThis operation mode allows running a proportional dosing between the pulses emitted by the water meter, and the pump injections. (Socket B pin 3-4, see page 9)
1XN Function For every pulse received the pump will carry out a series of "N" injections, previously set by the operator, whom can also fix the frequency of the injection.
Example: - Pump set on 1XN function - Value set on: "20"- When the meter or any other element, shut off the contact, the pump starts dosing 20 injections. If there is a new shut off during this process, the pump will not take it in consideration until finishing the 20 injections, then it will restart this process again.
1XN (M) function This function its equivalent to the 1XN function, however in this function all the pulses received are saved at the microprocessor's memory.
Example: When the pump receives the first pulse or contact returns a series of "N" injections at the maximum frequency, for instance: 120 injections / minute.
When the pump receives the second pulse or contact starts computing the time “T” without exceeding the maximum frequency. When the remaining injections are bigger than 4XN an alarm (AL3) will go on. In that case, the pump will keep running however, the remaining injections will get lost.
MENU SELECT
1xN(M)
MENU1xN(M)
10
1xN(M) n=10
12:00
Through select the number of injections and press START /STOP to confirm
1x N n= 10
12:00
MENU SELECT
1xN
MENU 1xN
10
Through select the number of injections and press START /STOP to confirm
1:N functionFor each “N” pulses received the pump does one injection. The value of “N” can be set for the operator.
Example: - Pump set on 1:N function - Value set on "20”- When the meter shut off the contact 20 times, the pump does one injection.
1- N n= 10
12:00
MENU SELECT
1-N
MENU 1-N
10
mA (4-20mA) MODE
This operation mode allows the flow adjustment through a 4-20 mA analogical external signal. It allows setting the maximum and minimum injection speed, according to the 4-20 mA analogical signal. (Socket B pin 1-2, see page 9)
MENU SELECT
mA
SET mA (1)
4.0
SET mA (2)
20.0
PULSE / MIN (1)
0
PULSE / MIN (2)
120
BELLOW mA (1)
CONTINUE
BELLOW mA (1)
STOP
31
Through select the number of injections and press START /STOP to confirm
Through select the current value to indicate the minimum flow desired, and then confirm with
Through select STOP or CONTINUE the injection when the current is bellow the set one (SET mA), then confirm with
Through select the flow (injections/minute) corresponding to the maximum flow desired. Confirm with
Through select the current value to indicate the maximum flow desired, and then confirm with
Through select the flow (injections/minute) corresponding to the minimum current point. Confirm with
30
PROPORTIONAL MODEThis operation mode allows running a proportional dosing between the pulses emitted by the water meter, and the pump injections. (Socket B pin 3-4, see page 9)
1XN Function For every pulse received the pump will carry out a series of "N" injections, previously set by the operator, whom can also fix the frequency of the injection.
Example: - Pump set on 1XN function - Value set on: "20"- When the meter or any other element, shut off the contact, the pump starts dosing 20 injections. If there is a new shut off during this process, the pump will not take it in consideration until finishing the 20 injections, then it will restart this process again.
1XN (M) function This function its equivalent to the 1XN function, however in this function all the pulses received are saved at the microprocessor's memory.
Example: When the pump receives the first pulse or contact returns a series of "N" injections at the maximum frequency, for instance: 120 injections / minute.
When the pump receives the second pulse or contact starts computing the time “T” without exceeding the maximum frequency. When the remaining injections are bigger than 4XN an alarm (AL3) will go on. In that case, the pump will keep running however, the remaining injections will get lost.
MENU SELECT
1xN(M)
MENU1xN(M)
10
1xN(M) n=10
12:00
Through select the number of injections and press START /STOP to confirm
1x N n= 10
12:00
MENU SELECT
1xN
MENU 1xN
10
Through select the number of injections and press START /STOP to confirm
1:N functionFor each “N” pulses received the pump does one injection. The value of “N” can be set for the operator.
Example: - Pump set on 1:N function - Value set on "20”- When the meter shut off the contact 20 times, the pump does one injection.
1- N n= 10
12:00
MENU SELECT
1-N
MENU 1-N
10
mA (4-20mA) MODE
This operation mode allows the flow adjustment through a 4-20 mA analogical external signal. It allows setting the maximum and minimum injection speed, according to the 4-20 mA analogical signal. (Socket B pin 1-2, see page 9)
MENU SELECT
mA
SET mA (1)
4.0
SET mA (2)
20.0
PULSE / MIN (1)
0
PULSE / MIN (2)
120
BELLOW mA (1)
CONTINUE
BELLOW mA (1)
STOP
31
Through select the number of injections and press START /STOP to confirm
Through select the current value to indicate the minimum flow desired, and then confirm with
Through select STOP or CONTINUE the injection when the current is bellow the set one (SET mA), then confirm with
Through select the flow (injections/minute) corresponding to the maximum flow desired. Confirm with
Through select the current value to indicate the maximum flow desired, and then confirm with
Through select the flow (injections/minute) corresponding to the minimum current point. Confirm with
32
OVER mA (2)
CONTINUE
OVER mA (2)
STOP
When pressing START/STO the pump will start running according to the configuration set.
mA :00.0
12:00
PPM MODEThis operation mode allows dosing in Parts Per Million. page 9)
(Socket B pin 3-4, see
MENU SELECT
PPM
L/P W.METER
0.10
Through select the litter's value per each pulse from the flow meter (select it according to the meter) and confirm with
cc/ INJECTION
0,01
SOLUTION %
100
SET PPM
1.0
When pressing START/STO the pump will start running according to the configuration set.
PPM = 1.0
12:00
Through select STOP or CONTINUE the injection when the current is below the set one -SET mA (1). Confirm with
Through select the value in p.p.m (parts per million) that is required, (in a rank from 0.01 - 2000 p.p.m) and confirm with
Through select the concentration value (%) of the aditive that the pump needs to inject and confirm with
Through select the injection volumen for each cicle of the pump (see page 4) and confirm with
33
TELECONTROL (REMOTE)The pump can be activated and deactivated through an opening and closing contact located a 100 meters (maximum distance). There are two different operation modes: NORMAL or REVERSED
MENU SELECT
REMOTEMENU REMOTE
NORMAL
MENU REMOTE
REVERSED
ALARMS The pumps provided with flow sensor (which is optional) have a system that in case the pump stops injecting,according to the parameters set, due to any mechanical damage, a alarm goes on and stops the injections. (Socket C pin 1-2, see page 9)
MENU SELECT
ALARMREF. PULSES
0
MAX DIFF.
0
Note: the wires must be conected at the same connectors of the level probe (Socket C pin 3-4, see page 9)
NORMAL mode: Contact opened = pump activated Contact closed = pump in stand-by Through select the functionConfirm with
Through select the pulse rage value of reference and confirm with
Through select the maximum difference of pulses related to the reference ones, and confirm with
REVERSED mode: Contact opened = pump in stand-byContact closed = pump activatedThrough select the functionConfirm with
32
OVER mA (2)
CONTINUE
OVER mA (2)
STOP
When pressing START/STO the pump will start running according to the configuration set.
mA :00.0
12:00
PPM MODEThis operation mode allows dosing in Parts Per Million. page 9)
(Socket B pin 3-4, see
MENU SELECT
PPM
L/P W.METER
0.10
Through select the litter's value per each pulse from the flow meter (select it according to the meter) and confirm with
cc/ INJECTION
0,01
SOLUTION %
100
SET PPM
1.0
When pressing START/STO the pump will start running according to the configuration set.
PPM = 1.0
12:00
Through select STOP or CONTINUE the injection when the current is below the set one -SET mA (1). Confirm with
Through select the value in p.p.m (parts per million) that is required, (in a rank from 0.01 - 2000 p.p.m) and confirm with
Through select the concentration value (%) of the aditive that the pump needs to inject and confirm with
Through select the injection volumen for each cicle of the pump (see page 4) and confirm with
33
TELECONTROL (REMOTE)The pump can be activated and deactivated through an opening and closing contact located a 100 meters (maximum distance). There are two different operation modes: NORMAL or REVERSED
MENU SELECT
REMOTEMENU REMOTE
NORMAL
MENU REMOTE
REVERSED
ALARMS The pumps provided with flow sensor (which is optional) have a system that in case the pump stops injecting,according to the parameters set, due to any mechanical damage, a alarm goes on and stops the injections. (Socket C pin 1-2, see page 9)
MENU SELECT
ALARMREF. PULSES
0
MAX DIFF.
0
Note: the wires must be conected at the same connectors of the level probe (Socket C pin 3-4, see page 9)
NORMAL mode: Contact opened = pump activated Contact closed = pump in stand-by Through select the functionConfirm with
Through select the pulse rage value of reference and confirm with
Through select the maximum difference of pulses related to the reference ones, and confirm with
REVERSED mode: Contact opened = pump in stand-byContact closed = pump activatedThrough select the functionConfirm with
34
CLOCKThe pump features a clock with time. Some applications may request the activation or deactivation through this clock.
MENU SELECT
CLOCK
CLOCK SET
2007 JAN “01"
BUZZERThe pump features an acoustic alarm to warn us of any incidence.
MENU SELECT
BUZZERMENU BUZZER
ENABLED
MENU BUZZER
DISABLED
The function ENABLED indicates alarm on Through select functionConfirm with
CLOCK SET
“12:00" - MONThrough select the timeConfirm with
CLOCK SET
“2007" JAN 01
CLOCK SET
12:00 - “MON”
CLOCK SET
2007 “JAN” 01
The function ENABLED indicates alarm on Through select functionConfirm with
Through select the day of the weekConfirm with
Through select the year Confirm with
Through select the monthConfirm with
Through select the day Confirm with
TIMER
The timer menu carries out up to 8 different cycles of activation and deactivation in one day.
MENU SELECT
TIMERMENU TIMER
TIMER OFF
Function TIMER OFF deactivates the timer. Through select the function. Confirm with
SUNDAY SET1
ON 1:00
SUNDAY SET1
OFF 1:20
Repeat this operation according to the number of cycles (maximum 8) requested in one day.
MENU TIMER
WEEK SETS
MENU TIMER
DAYLY SETS
SET1
OFF 1:20
SET1
ON 1:00
Repeat this operation according to the number of cycles (maximum 8) requested in one day.
35
Function SET 1 OFF sets the timing to deactivate the pumpThrough select the function. Confirm with
Function SET 1 ON sets the timing to activate the pumpThrough select the function. Confirm with
Function DALY SETS set up to 8 different cycles of start and stop Through select the function. Confirm with
Function SUNDAY SET 1 OFF set the timing to deactivate the pump on Saturdays. Through select the function. Confirm with
Function WEEK SETS set up to 8 different cycles of start and stopThrough select the function. Confirm with
Function SUNDAY SET 1 ON sets the timing to activate the pump on Saturdays. Through select the function. Confirm with
34
CLOCKThe pump features a clock with time. Some applications may request the activation or deactivation through this clock.
MENU SELECT
CLOCK
CLOCK SET
2007 JAN “01"
BUZZERThe pump features an acoustic alarm to warn us of any incidence.
MENU SELECT
BUZZERMENU BUZZER
ENABLED
MENU BUZZER
DISABLED
The function ENABLED indicates alarm on Through select functionConfirm with
CLOCK SET
“12:00" - MONThrough select the timeConfirm with
CLOCK SET
“2007" JAN 01
CLOCK SET
12:00 - “MON”
CLOCK SET
2007 “JAN” 01
The function ENABLED indicates alarm on Through select functionConfirm with
Through select the day of the weekConfirm with
Through select the year Confirm with
Through select the monthConfirm with
Through select the day Confirm with
TIMER
The timer menu carries out up to 8 different cycles of activation and deactivation in one day.
MENU SELECT
TIMERMENU TIMER
TIMER OFF
Function TIMER OFF deactivates the timer. Through select the function. Confirm with
SUNDAY SET1
ON 1:00
SUNDAY SET1
OFF 1:20
Repeat this operation according to the number of cycles (maximum 8) requested in one day.
MENU TIMER
WEEK SETS
MENU TIMER
DAYLY SETS
SET1
OFF 1:20
SET1
ON 1:00
Repeat this operation according to the number of cycles (maximum 8) requested in one day.
35
Function SET 1 OFF sets the timing to deactivate the pumpThrough select the function. Confirm with
Function SET 1 ON sets the timing to activate the pumpThrough select the function. Confirm with
Function DALY SETS set up to 8 different cycles of start and stop Through select the function. Confirm with
Function SUNDAY SET 1 OFF set the timing to deactivate the pump on Saturdays. Through select the function. Confirm with
Function WEEK SETS set up to 8 different cycles of start and stopThrough select the function. Confirm with
Function SUNDAY SET 1 ON sets the timing to activate the pump on Saturdays. Through select the function. Confirm with
LANGUAGE
The language menu allows the selection between two languages.
MENU SELECT
LANGUAGESET LANGUAGE
ENGLISH
English menuThrough select language Confirm with
MENU LINGUA
ITALIANO
Italian menuThrough select language Confirm with
37
7.- MAINTENANCE
Before any maintenance operation we will check:
That the pump is stopped and disconnected from the electric supply.
There is no pressure neither inside the head nor in the impulsion pipe. It is advisable to empty the head before opening it.
The staff in charge of the maintenance will use the adequate protection means in order to manipulate the dosed liquid.
Periodically check the chemical tank level so as to avoid the pump operates without liquid. This would not damage the pump, but may damage the process plant due to lack of chemical. DOSITEC series dosing pumps are all supplied with level control setting. The level switch is not included therefore to be ordered separately.Level control stops pump operation once the level into the chemical is lower then the level switch,activating a L.E.D. on the pump .
Check the pump operating condition at least every 6 months, pump head position,screws, bolts and seals; check more frequently where aggressive chemicals are pumped, especially: - pulse and power L.E.D.; - the additive concentration in the process plant; a reduction of this concentration could be caused by the wearing of the valves, in which case they need to be replaced or by the clogging of the filter which then has to be cleaned as in point 3 here below.
36
LANGUAGE
The language menu allows the selection between two languages.
MENU SELECT
LANGUAGESET LANGUAGE
ENGLISH
English menuThrough select language Confirm with
MENU LINGUA
ITALIANO
Italian menuThrough select language Confirm with
37
7.- MAINTENANCE
Before any maintenance operation we will check:
That the pump is stopped and disconnected from the electric supply.
There is no pressure neither inside the head nor in the impulsion pipe. It is advisable to empty the head before opening it.
The staff in charge of the maintenance will use the adequate protection means in order to manipulate the dosed liquid.
Periodically check the chemical tank level so as to avoid the pump operates without liquid. This would not damage the pump, but may damage the process plant due to lack of chemical. DOSITEC series dosing pumps are all supplied with level control setting. The level switch is not included therefore to be ordered separately.Level control stops pump operation once the level into the chemical is lower then the level switch,activating a L.E.D. on the pump .
Check the pump operating condition at least every 6 months, pump head position,screws, bolts and seals; check more frequently where aggressive chemicals are pumped, especially: - pulse and power L.E.D.; - the additive concentration in the process plant; a reduction of this concentration could be caused by the wearing of the valves, in which case they need to be replaced or by the clogging of the filter which then has to be cleaned as in point 3 here below.
36
38
TROUBLE SHOOTING
MECHANICAL FAULTS
As the system is quite robust there are no apparent mechanical problems. Occasionally there might be a loss of liquid from the nipple because the tube nut has loosened, or more simply the discharge tubing-has broken.Very rarely there may be losses caused by the breakage of the membrane, or by the membrane seals in which case they have to be replaced by disassembling the four screws of the pump head, when re-mounting the pump head ensure that the screws are replaced properly, along with “O” ring.After repair, the metering pump will need to be cleaned of additive residues which can damage the pump casing.
PROBLEM
tThe pump gives pulses but doesn’t inject
The pump doesn’t give any pulse and LED are off
The pump gives only one pulse
The pump doesn’t give any pulse and green LED is on and red LED is off
Pump pulses are not constant
CAUSE
Valves not clean
Damaged valves
Filter not clean
Power supply failure
START failure
Power supply failure
SOLUTIÓN
Remove the suction and injection valves, clean them , and assemble them in the same position.
When the parts are swallen, check valve material against a chemical compatibility chart and fit the correct material.
Clean the filter
Chech the power supply. If it still doesn’t work contact with the Technical Service
Press START/STOP.If it still doesn’t work contact with the Technical Service.
Check the input voltageis within +/- 10% rated voltage
Disconnect the pump and contact immediately to the Technical Service
DOSITEC PARTS
39
5920059154 59300
5960559607
5915559311
59310
59213
59158
59209
59309
59308
59212
596105961159612
592035920459205
59210
59211
592065920759208
596135961459615
5920159202
59-050-F
59807-F
59809-F 59810-F
59303 59306
59303
59800-F
59302
59305
59157
59-862-F
59156-F
59805-F 59848
59307
59-863-F
59801-F
59849
38
TROUBLE SHOOTING
MECHANICAL FAULTS
As the system is quite robust there are no apparent mechanical problems. Occasionally there might be a loss of liquid from the nipple because the tube nut has loosened, or more simply the discharge tubing-has broken.Very rarely there may be losses caused by the breakage of the membrane, or by the membrane seals in which case they have to be replaced by disassembling the four screws of the pump head, when re-mounting the pump head ensure that the screws are replaced properly, along with “O” ring.After repair, the metering pump will need to be cleaned of additive residues which can damage the pump casing.
PROBLEM
tThe pump gives pulses but doesn’t inject
The pump doesn’t give any pulse and LED are off
The pump gives only one pulse
The pump doesn’t give any pulse and green LED is on and red LED is off
Pump pulses are not constant
CAUSE
Valves not clean
Damaged valves
Filter not clean
Power supply failure
START failure
Power supply failure
SOLUTIÓN
Remove the suction and injection valves, clean them , and assemble them in the same position.
When the parts are swallen, check valve material against a chemical compatibility chart and fit the correct material.
Clean the filter
Chech the power supply. If it still doesn’t work contact with the Technical Service
Press START/STOP.If it still doesn’t work contact with the Technical Service.
Check the input voltageis within +/- 10% rated voltage
Disconnect the pump and contact immediately to the Technical Service
DOSITEC PARTS
39
5920059154 59300
5960559607
5915559311
59310
59213
59158
59209
59309
59308
59212
596105961159612
592035920459205
59210
59211
592065920759208
596135961459615
5920159202
59-050-F
59807-F
59809-F 59810-F
59303 59306
59303
59800-F
59302
59305
59157
59-862-F
59156-F
59805-F 59848
59307
59-863-F
59801-F
59849
LIST OF PARTS
CODE DESCRIPTION UNITS59101 PLATE FOR LEVEL SENSOR STAND 159153 ELECTRIC CABLE 159154 CONNECTOR G4W1F 259155 CONNECTOR G4A5M 259156-F CYLINDER DIAPHAGM PVDF 159157 CYLINDER CAP 459158 DIAPHRAGM FLANGE 159200 PTFE DIAPHAGM 159201 LOWER LEXAN 159202 LOWER LEXAN STROKE REGULATION 159203 LEXAN MP 159204 LEXAN MD 159205 LEXAN Q 159206 LEXAN mA 159207 LEXAN MF 159208 LEXAN PRC 159209 CYLINDER COVER 159210 HYDRAULIC CASE 159211 ELECTRONIC CASE 159212 FLOW ADJUSTMENT KNOB 159213 CASE O-RING 159300 M4X8 INOX SCREW 459302 M4 6593 WASHER 459303 2087 O-RING FOR DRAIN VALVE 259304 LIP VALVE O'RING 159305 M4X35 DIN 912 INOX SCREW 459306 2819 O-RING FOR DRAIN VALVE 159307 2816 O-RING VITON 159308 SCREW 2.9X9.5 459309 SCREW 4X16 INOX 659310 SCREW 2.9X13 259311 CABLE CLAMP 159605 D 80 2-10 ELECTROMAGNET 159607 D 90 8-10 ELECTROMAGNET 159610 MP ELECTRONICA CARD 159611 MD ELECTRONICA CARD 159612 Q ELECTRONICA CARD 159613 mA ELECTRONICA CARD 159614 MF ELECTRONICA CARD 159615 PRC ELECTRONICA CARD 159800-F DRAIN CONNECTER PVDF 159801-F SEPARATOR OF INJECTION VALVE PVDF 159805-F 3/8" LIP VALVE GUIDE PVDF 159807-F DRAIN CONTROL PVDF 159808 O-RING 159809-F DRAIN SCREW PVDF 159810-F DRAIN ROD PVDF 159811 CYLINDER FOR INYECTION VALVE 159812 BODY OF INYECTION VALVE 159813 FOOT FILTER NET 159814 FOOT FILTER CONE 159-851-P 4x6 FOOT FILTER 1
ASSEMBLY59-080-F CYLINDER DOSITEC ASSEMBLY PVDF/ FPM 159-806 3/8” CHECK VALVE 159-851-P FOOT FILTER 4X6 159-862-F SUCTION CHECK VALVE BALL 4x6 PVDF/FPM 159-863-F DISCHARGE CHECK VALVE BALL4X6 PVDF / FPM 1
BALL VALVE 4x6 PVDF / FPM
FOOT FILTER 4X6
40
5981759802
5981359812
59824
59811
59-806 59-851-P
CHECK VALVE 4X6
Suction 59-862-F Discharge 59-863-F
1
2
3
4
6
5
13
12
10
11
9
8
9
7
10
8
7
1
2
3
4
6
5
13
12
10
11
7
8
7
9
10
8
9
LIST OF PARTS
CODE DESCRIPTION UNITS59101 PLATE FOR LEVEL SENSOR STAND 159153 ELECTRIC CABLE 159154 CONNECTOR G4W1F 259155 CONNECTOR G4A5M 259156-F CYLINDER DIAPHAGM PVDF 159157 CYLINDER CAP 459158 DIAPHRAGM FLANGE 159200 PTFE DIAPHAGM 159201 LOWER LEXAN 159202 LOWER LEXAN STROKE REGULATION 159203 LEXAN MP 159204 LEXAN MD 159205 LEXAN Q 159206 LEXAN mA 159207 LEXAN MF 159208 LEXAN PRC 159209 CYLINDER COVER 159210 HYDRAULIC CASE 159211 ELECTRONIC CASE 159212 FLOW ADJUSTMENT KNOB 159213 CASE O-RING 159300 M4X8 INOX SCREW 459302 M4 6593 WASHER 459303 2087 O-RING FOR DRAIN VALVE 259304 LIP VALVE O'RING 159305 M4X35 DIN 912 INOX SCREW 459306 2819 O-RING FOR DRAIN VALVE 159307 2816 O-RING VITON 159308 SCREW 2.9X9.5 459309 SCREW 4X16 INOX 659310 SCREW 2.9X13 259311 CABLE CLAMP 159605 D 80 2-10 ELECTROMAGNET 159607 D 90 8-10 ELECTROMAGNET 159610 MP ELECTRONICA CARD 159611 MD ELECTRONICA CARD 159612 Q ELECTRONICA CARD 159613 mA ELECTRONICA CARD 159614 MF ELECTRONICA CARD 159615 PRC ELECTRONICA CARD 159800-F DRAIN CONNECTER PVDF 159801-F SEPARATOR OF INJECTION VALVE PVDF 159805-F 3/8" LIP VALVE GUIDE PVDF 159807-F DRAIN CONTROL PVDF 159808 O-RING 159809-F DRAIN SCREW PVDF 159810-F DRAIN ROD PVDF 159811 CYLINDER FOR INYECTION VALVE 159812 BODY OF INYECTION VALVE 159813 FOOT FILTER NET 159814 FOOT FILTER CONE 159-851-P 4x6 FOOT FILTER 1
ASSEMBLY59-080-F CYLINDER DOSITEC ASSEMBLY PVDF/ FPM 159-806 3/8” CHECK VALVE 159-851-P FOOT FILTER 4X6 159-862-F SUCTION CHECK VALVE BALL 4x6 PVDF/FPM 159-863-F DISCHARGE CHECK VALVE BALL4X6 PVDF / FPM 1
BALL VALVE 4x6 PVDF / FPM
FOOT FILTER 4X6
40
5981759802
5981359812
59824
59811
59-806 59-851-P
CHECK VALVE 4X6
Suction 59-862-F Discharge 59-863-F
1
2
3
4
6
5
13
12
10
11
9
8
9
7
10
8
7
1
2
3
4
6
5
13
12
10
11
7
8
7
9
10
8
9
42
I.T.C. S.L. warrants the product specified in this document for a period of 2 years fromt he purchase date except for the wearing parts such as valves, seals, nipples, hoses and filter. This warranty obligation is limited to the free replacement of the damaged parts due to any material or manufacture defect. This warranty does not include periodic maintenance and damage resulting from misuse.
The equipment must be sent to I.T.C. S.L. Service Center with prepaid transport charges, and will be sent back with transport charges for customer’s account.
The warranty document with sales date and shop stamp or an invoice copy must be sent with the equipment.W
AR
RA
NT
Y
Date of sale and shop stamp
DATE:SERIAL #
MODEL
EC CONFORMITY DECLARATION
I.T.C S.L..Mar Adriàtic, 1Polígono Torre del Rector08130 Santa Perpètua de Mogoda
Declares that all models DOSITEC products, identified by a serial number and year of manufacture, strictly fulfill low voltages directives 73/23/CE and electromagnetic compatibility directives 89/336/CE, as long as installation, use and maintenance are carried out following the prevailing regulation and following the instructions contained in the handbook.
Antón PlanasManager
42
I.T.C. S.L. warrants the product specified in this document for a period of 2 years fromt he purchase date except for the wearing parts such as valves, seals, nipples, hoses and filter. This warranty obligation is limited to the free replacement of the damaged parts due to any material or manufacture defect. This warranty does not include periodic maintenance and damage resulting from misuse.
The equipment must be sent to I.T.C. S.L. Service Center with prepaid transport charges, and will be sent back with transport charges for customer’s account.
The warranty document with sales date and shop stamp or an invoice copy must be sent with the equipment.W
AR
RA
NT
Y
Date of sale and shop stamp
DATE:SERIAL #
MODEL
EC CONFORMITY DECLARATION
I.T.C S.L..Mar Adriàtic, 1Polígono Torre del Rector08130 Santa Perpètua de Mogoda
Declares that all models DOSITEC products, identified by a serial number and year of manufacture, strictly fulfill low voltages directives 73/23/CE and electromagnetic compatibility directives 89/336/CE, as long as installation, use and maintenance are carried out following the prevailing regulation and following the instructions contained in the handbook.
Antón PlanasManager
C/ Del Mar Adriàtic nº 1 Pol. Ind. Torre del RectorP.O. Box 6008130 STA. PERPETUA DE MOGODABARCELONA - SPAIN
Tel. 935 44 30 40 Fax 935 544 31 61e-mail: [email protected] www.itc.es
Ed: 01/10/2010-AN