Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A, TDD1A060A9361A, TDD1B060A9361A, TDD1B080A9361A, TDD1B080A9451A TDD1B100A9451A, TDD1C100A9481A, TDD1C100A9541A TDD1C120A9541A, TDD1D120A9601A, TDD1D140A9601A Single-Stage Fan Assisted Combustion System

Upload: hathien

Post on 25-Sep-2018

285 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

Downflow/Horizontal Right or Downflow/Horizontal LeftInduced Draft Gas Furnace

PUB. NO. 22-1671-12

XR 80TDD1A060A9241A, TDD1A060A9361A, TDD1B060A9361A, TDD1B080A9361A, TDD1B080A9451A TDD1B100A9451A, TDD1C100A9481A, TDD1C100A9541ATDD1C120A9541A, TDD1D120A9601A, TDD1D140A9601A

Single-Stage Fan Assisted Combustion System

Page 2: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

© 2013 Trane All Rights Reserved 2 22-1671-12

General Features

Natural Gas ModelsCentral Heating furnace designs are certified by the American and Cana-dian Gas Associations for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

Safe OperationThe Integrated System Control has solid state devices, which continuously moni-tor for presence of flame, when the sys-tem is in the heating mode of operation. Dual solenoid combination gas valve and regulator provide extra safety.

Quick HeatingDurable, cycle tested, heavy gauge alu-minized steel heat exchanger quickly transfers heat to provide warm condi-tioned air to the structure.

BurnersMulti-port In-shot burners will give years of quiet and efficient service. All models can be converted to L.P. gas.

Integrated System ControlExclusively designed operational pro-gram provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self-diagnostics for ease of service. Also contains connec-tion points for E.A.C./humidifier.

Air DeliveryThe 4-speed, direct drive blower motor, has sufficient airflow for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed.

StylingHeavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel fin-ish for strength and beauty. The heat exchanger section of the cabinet is completely lined with foil faced fiberglass insulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

Features and General OperationThe XR 80 High Efficiency Gas Fur-nace employs an adaptive Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter b. Vent proving pressure switch.

Page 3: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

22-1671-12 3

Contents

General Features 2Features and Benefits 4

Standard Equipment 4Optional Equipment 5

General Data 6TDD1A060A9241A 6TDD1A060A9361A 6TDD1B060A9361A 6TDD1B080A9361A 7TDD1B080A9451A 7TDD1B100A9451A 7TDD1C100A9481A 8TDD1C100A9541A 8TDD1C120A9541A 8TDD1D120A9601A 9TDD1D140A9601A 9

Performance Data 10Electrical Data 12Field Wiring 14Dimensions 16

Page 4: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

4 22-1671-12

Features and Benefits

• Powersupply115/1/60

• Multi-portIn-shotburners

• Integratedsolidstatecontrolwithself-diagnostics

• SiliconNitridehotsurfaceigniterwithadaptive heat up

• Completefrontserviceaccess

• Heavygaugealuminizedsteelheatexchanger

• Slideoutblowerassembly

• Blowerdoorsafetyswitch

• Directdrive,4-speedmotor

• OptionalL.P.conversionkit

• Commonvent

• Leftandrightsideknockoutforventing

• Selectablecoolingfanoffdelayelimi-nates need for BAY24X045 time delay relay

• Quietslowopeninggasvalve

• Downflowconvertibletohorizontalonleft or right side

• Insulatedblowercompartment

• Accessoryhook-upcapability– Hum and EAC

• Quietinduceddraftblower

• Left/rightgasconnection

• 24voltfuse

• Manualresetflamerolloutswitches

XR 80 Downflow/Horizontal Right or LeftStandard Equipment

Page 5: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

22-1671-12 5

Features and Benefits

Optional EquipmentThermostat ............................................................................................................................................................... BAYSTAT388 [ ]Thermostat,Heating/CoolingSingleStage(MountsHorizontally) ...............................................................................AY28X092 [ ]Thermostat,Heating/CoolingSingleStage(MountsVertically) ................................................................................ BAYSTAT305 [ ]Thermostat, Electronic Programmable 1-Stage Heating/1-Stage Cooling ............................................................. TAYSTAT300C [ ]Propane Conversion Kit ......................................................................................................................................... BAYLPKT210A [ ]ElectronicAirFilter,“PerfectFit”HighEfficiency(14-1/2"WideGasFurnace) ......................................................TFM145A9FR1 [ ]ElectronicAirFilter,“PerfectFit”HighEfficiency(17-1/2"WideGasFurnace) ......................................................TFM175A9FR1 [ ]ElectronicAirFilter,“PerfectFit”HighEfficiency(21"WideGasFurnace) ............................................................TFM210A9FR1 [ ]ElectronicAirFilter,“PerfectFit”HighEfficiency(24-1/2"WideGasFurnace) ......................................................TFM245A9FR1 [ ] ElectronicAirFilter,“PerfectFit”StandardEfficiency(17-1/2"WideGasFurnace)..............................................TFP175A9FR01 [ ]ElectronicAirFilter,“PerfectFit”StandardEfficiency(21"WideGasFurnace) ....................................................TFP210A9FR01 [ ]ElectronicAirFilter,“PerfectFit”StandardEfficiency(24-1/2"WideGasFurnace)..............................................TFP245A9FR01 [ ]CoilEnclosure(14-1/2"WideCabinets) .........................................................................................................BAYCLE14A1422A [ ]CoilEnclosure(17-1/2"WideCabinets) ....................................................................................................... BAYCLE17A1722A [ ]CoilEnclosure(21"WideCabinets) .............................................................................................................. BAYCLE21A2130A [ ]CoilEnclosure(24-1/2"WideCabinets) ....................................................................................................... BAYCLE24A2430A [ ]Filter Access Door Kit .............................................................................................................................................. BAYFLTR206 [ ]Downflow Subbase .................................................................................................................................................. BAYBASE205 [ ]High Altitude Pressure Switch Kit .............................................................................................................................BAYHALT248 [ ]

Page 6: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

6 22-1671-12

General Data

Product Specifications 1MODEL

TYPE

RATINGS 2Input BTUHCapacityBTUH(ICS)3AFUETemp.rise(Min.-Max.)°F.

BLOWER DRIVEDiameter-Width(In.)No. UsedSpeeds(No.)CFM vs. in. w.g.Motor HPR.P.M.Volts/Ph/Hz

COMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLA

FILTER — Furnished?Type RecommendedHiVel.(No.-Size-Thk.)

VENT — Size (in.)

HEAT EXCHANGERType -Fired -UnfiredGauge(Fired)

ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSize

GAS VALVE

PILOT SAFETY DEVICEType

BURNERS — TypeNumber

POWER CONN. — V / Ph / Hz 4Ampacity(InAmps)Max.OvercurrentProtection(Amps)

PIPE CONN. SIZE (IN.)

DIMENSIONSCrated(In.)

WEIGHTShipping(Lbs.)/Net(Lbs)

TDD1A060A9241A

Downflow/Horizontal

60,00048,00080.0

35 - 65

DIRECT10 x 7

14

See Fan Performance Table1/5

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 14x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

3—453—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot3

115/1/605.515

1/2

H x W x D41 x 15-1/2 x 29-1/2

129 / 119

TDD1A060A9361A

Downflow/Horizontal

60,00048,00080.0

30 - 60

DIRECT11 x 7

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 14x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

3—453—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot3

115/1/6011.615

1/2

H x W x D41 x 15-1/2 x 29-1/2

129 / 119

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 ForU.S.applications,aboveinputratings(BTUH)areupto2,000ft.,derate4%per1,000ft.forelevationsabove2,000ft.abovesealevel. ForCanadianapplications,aboveinputratings(BTUH)areupto4,500ft.,derate4%per1,000ft.forelevationsabove4,500ft.abovesea

level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

TDD1B060A9361A

Downflow/Horizontal

60,00048,00080.0

30 - 60

DIRECT10 x 7

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 14x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

3—453—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot3

115/1/6011.615

1/2

H x W x D41 x 18-1/2 x 29-1/2

134 / 124

Page 7: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

22-1671-12 7

Product Specifications 1MODEL

TYPE

RATINGS 2Input BTUHCapacityBTUH(ICS)3AFUETemp.rise(Min.-Max.)°F.

BLOWER DRIVEDiameter-Width(In.)No. UsedSpeeds(No.)CFM vs. in. w.g.Motor HPR.P.M.Volts/Ph/Hz

COMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLA

FILTER — Furnished?Type RecommendedHiVel.(No.-Size-Thk.)

VENT — Size (in.)

HEAT EXCHANGERType -Fired -UnfiredGauge(Fired)

ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSize

GAS VALVE

PILOT SAFETY DEVICEType

BURNERS — TypeNumber

POWER CONN. — V / Ph / Hz 4Ampacity(InAmps)Max.OvercurrentProtection(Amps)

PIPE CONN. SIZE (IN.)

DIMENSIONSCrated(In.)

WEIGHTShipping(Lbs.)/Net(Lbs)

General Data

TDD1B080A9451A

Downflow/Horizontal

80,00064,00080.0

35 - 65

DIRECT10 x 8

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 16x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

4—454—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot4

115/1/609.815

1/2

H x W x D41 x 18-1/2 x 29-1/2

146 / 135

TDD1B080A9361A

Downflow/Horizontal

80,00064,00080.0

35 - 65

DIRECT10 x 7

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 14x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

4—454—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot4

115/1/609.015

1/2

H x W x D41 x 18-1/2 x 29-1/2

146 / 135

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 ForU.S.applications,aboveinputratings(BTUH)areupto2,000ft.,derate4%per1,000ft.forelevationsabove2,000ft.abovesealevel. ForCanadianapplications,aboveinputratings(BTUH)areupto4,500ft.,derate4%per1,000ft.forelevationsabove4,500ft.abovesea

level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

TDD1B100A9451A

Downflow/Horizontal

100,00080,00080.0

35 - 65

DIRECT10 x 8

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3200115/1/60

1.0

NoHigh Velocity

2 - 16x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

5—455—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot5

115/1/609.815

1/2

H x W x D41 x 18-1/2 x 29-1/2

156 / 145

Page 8: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

8 22-1671-12

General Data

Product Specifications 1MODEL

TYPE

RATINGS 2Input BTUHCapacityBTUH(ICS)3AFUETemp.rise(Min.-Max.)°F.

BLOWER DRIVEDiameter-Width(In.)No. UsedSpeeds(No.)CFM vs. in. w.g.Motor HPR.P.M.Volts/Ph/Hz

COMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLA

FILTER — Furnished?Type RecommendedHiVel.(No.-Size-Thk.)

VENT — Size (in.)

HEAT EXCHANGERType -Fired -UnfiredGauge(Fired)

ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSize

GAS VALVE

PILOT SAFETY DEVICEType

BURNERS — TypeNumber

POWER CONN. — V / Ph / Hz 4Ampacity(InAmps)Max.OvercurrentProtection(Amps)

PIPE CONN. SIZE (IN.)

DIMENSIONSCrated(In.)

WEIGHTShipping(Lbs.)/Net(Lbs)

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 ForU.S.applications,aboveinputratings(BTUH)areupto2,000ft.,derate4%per1,000ft.forelevationsabove2,000ft.abovesealevel. ForCanadianapplications,aboveinputratings(BTUH)areupto4,500ft.,derate4%per1,000ft.forelevationsabove4,500ft.abovesea

level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

TDD1C100A9481A

Downflow/Horizontal

100,00080,00080.0

35 - 65

DIRECT10 x 8

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 16x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

5—455—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot5

115/1/6011.615

1/2

H x W x D41 x 22 x 29-1/2

166 / 154

TDD1C100A9541A

Downflow/Horizontal

100,00081,00080.0

30 - 60

DIRECT11 x 10

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 14x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

5—455—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot5

115/1/6013.420

1/2

H x W x D41 x 22 x 29-1/2

167 / 155

TDD1C120A9541A

Downflow/Horizontal

120,00096,00080.0

35 - 65

DIRECT11 x 10

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 16x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

6—456—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot6

115/1/6013.420

1/2

H x W x D41 x 22 x 29-1/2

170 / 158

Page 9: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

22-1671-12 9

Product Specifications 1MODEL

TYPE

RATINGS 2Input BTUHCapacityBTUH(ICS)3AFUETemp.rise(Min.-Max.)°F.

BLOWER DRIVEDiameter-Width(In.)No. UsedSpeeds(No.)CFM vs. in. w.g.Motor HPR.P.M.Volts/Ph/Hz

COMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLA

FILTER — Furnished?Type RecommendedHiVel.(No.-Size-Thk.)

VENT — Size (in.)

HEAT EXCHANGERType -Fired -UnfiredGauge(Fired)

ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSize

GAS VALVE

PILOT SAFETY DEVICEType

BURNERS — TypeNumber

POWER CONN. — V / Ph / Hz 4Ampacity(InAmps)Max.OvercurrentProtection(Amps)

PIPE CONN. SIZE (IN.)

DIMENSIONSCrated(In.)

WEIGHTShipping(Lbs.)/Net(Lbs)

General Data

TDD1D140A9601A

Downflow/Horizontal

140,000113,000

80.045 - 75

DIRECT11 x 10

14

See Fan Performance Table3/4

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 16x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

7—457—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot7

115/1/6013.820

1/2

H x W x D41 x 25_-1/2 x 28

196 / 183

TDD1D120A9601A

Downflow/Horizontal

120,00096,00080.0

35 - 65

DIRECT11 x 10

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3000115/1/60

1.0

NoHigh Velocity

2 - 16x20 - 1in.

4 Round

AluminizedSteel-TypeI

20

6—456—56

Redundant - Single Stage

Hot Surface Ignition

Multi-port In-shot6

115/1/6013.420

1/2

H x W x D41 x 25-1/2 x 29-1/2

189 / 176

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 ForU.S.applications,aboveinputratings(BTUH)areupto2,000ft.,derate4%per1,000ft.forelevationsabove2,000ft.abovesealevel. ForCanadianapplications,aboveinputratings(BTUH)areupto4,500ft.,derate4%per1,000ft.forelevationsabove4,500ft.abovesea

level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

Page 10: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

10 22-1671-12

Performance Data

* May be "A" or "T"

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

*DD1A060A9241A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

12001025838722

1155988808689

1111951779656

1056905742618

1001859704579

924797646528

848735588478

774646502376

701558415275

*DD1A060A9361A

*DD1B060A9361A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

148013021115956

142912761100947

137512291070918

131811881035888

128211411000859

11001088965824

11121024918788

1029953859741

959882790682

*DD1B080A9361A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

152313171123942

149613071119943

146312611106931

142012421082920

136912231056898

131011751016868

12431122976833

11721060930795

11001000880760

*DD1B080A9451A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

1798138412101005

175013671150970

169213331108808

164213001075775

157512751042767

150012331008733

14251192967700

13251142925675

12251083867617

*DD1B100A9451A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

176713821130840

173113541138831

166913231115815

161512921085792

154612541054762

146912071015731

13921177977700

13001108938654

11461038877625

*DD1C100A9481A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

1965164514071202

1915162713981208

1865160513871205

1805157513751195

1740153513471166

1670148213181140

1587142112751105

1500133011901045

137012201095970

*DD1B100A9541A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

2165196217051492

2113192716881467

2060189116711442

1995183916361414

1929178616001385

1842172415471346

1755166214921307

1674158114351243

1593150013771179

*DD1C120A9541A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

2100191716721485

2049188716561478

1997185716391470

1958184216311448

1918182716231426

1852175115601388

1785167414961349

1695159414271278

1604151413581207

*DD1D120A9601A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

2241198117211476

2202196217051466

2163194216881456

2106190416711440

2049186616531423

1979180516111392

1908174315691361

1804168015151302

1700161714611243

*DD1D140A9601A

4 -3 -2 -1 -

HIGH - BlackMED - HIGH - BlueMED - LOW - YellowLOW - Red

2377211518061527

2321208117931507

2265204617791486

2199199217381473

2133193816961459

2050187216551422

1967180516141384

1877172715561329

1786164914971273

Page 11: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

22-1671-12 11

Performance Data

CFM VS. TEMPERATURE RISE

MODEL700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

*DD1A060A9241A 63 56 49 44 40

*DD1A060A9361A 56 49 44 40 37 34 32

*DD1B060A9361A 56 49 44 40 37 34 32

*DD1B080A9361A 59 54 49 46 42

*DD1B080A9451A 64 57 52 48 44 41

*DD1B100A9451A 62 57 53 49 46 44 41

*DD1C100A9481A 62 57 53 49 46 44 41 39 37

*DD1C100A9541A 62 57 53 49 46 44 41 39 37 35 34 32 31

*DD1C120A9541A 59 56 52 49 47 44 42 40

*DD1D120A9601A 59 56 52 49 47 44 42 40

*DD1D140A9601A 69 65 61 58 55 52 49 47 45

* First letter may be "A" or "T" From C341712 Sh. 1 Rev. 03

Page 12: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

12 22-1671-12

(continued on next page)

WIRING DIAGRAM

From Dwg. D342568P02

Page 13: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

22-1671-12 13

SCHEMATIC DIAGRAM

From Dwg. D342568P02

Page 14: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

14 22-1671-12

Field Wiring

FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING ONLY

FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING/COOLING(OUTDOOR SECTION WITHOUT TRANSFORMER)

From Dwg. 21B341437 Rev. 1

From Dwg. 21B341436 Rev. 1

Page 15: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

22-1671-12 15

Field Wiring

From Dwg. 21B341423 Rev. 1

From Dwg. 21B341422 Rev. 1

Page 16: Downflow/Horizontal Right or Downflow/Horizontal …€¦ · Downflow/Horizontal Right or Downflow/Horizontal Left Induced Draft Gas Furnace PUB. NO. 22-1671-12 XR 80 TDD1A060A9241A,

Trane 6200 Troup HighwayTyler, TX 75707www.trane.com

Since The Trane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.

Literature Order Number 22-1671-12

File Number 22-1671-12

Supersedes 22-1671-11

Date 04/13

From

Dw

g. 2

1C34

1700

Rev

. 0

TD

D1

OU

TL

INE

DR

AW

ING

(AL

L D

IME

NS

ION

S A

RE

IN IN

CH

ES

)

MO

DE

LD

IM "

A"

DIM

"B

"D

IM "

C"

DIM

"D

"

*DD

1A06

0A92

41A

*DD

1A06

0A93

61A

14-1

/2"

9-5/

8"13

-1/4

"13

"

*DD

1B06

0A93

61A

*DD

1B08

0A93

61A

*DD

1B08

0A94

51A

*DD

1B10

0A94

51A

17-1

/2"

9-5/

8"16

-1/4

"16

"

*DD

1C10

0A94

81A

*DD

1C10

0A95

41A

*DD

1C12

0A95

41A

21"

13-1

/16"

19-3

/4"

19-1

/2"

*DD

1D12

0A96

01A

*DD

1D14

0A96

01A

24-1

/2"

15-5

/16"

23-1

/4"

23"

* P

RE

FIX

LE

TT

ER

MAY

BE

"A

" O

R "

T"