I400 (i4C, i4D, i4E, i4F, i4M, i4P, i4R, i4V, i4W Manual iSTAT I400 Standard Transducer Publication Reference: I400/EN/M/E I400/EN/M/E © 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. GRID

Upload: mehdimashayekhi172

Post on 01-Dec-2014

493 views

Category:

Documents


9 download

TRANSCRIPT

Page 1: Download Asset

I400 (i4C, i4D, i4E, i4F, i4M, i4P, i4R, i4V, i4W 

 

 

Manual iSTAT I400

Standard Transducer Publication Reference: I400/EN/M/E

I400/EN/M/E © 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither ALSTOM,  its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. 

GRID  

 

Page 2: Download Asset
Page 3: Download Asset

Service Manual I400/EN M/E

iSTAT I400

Page 1/58

HANDLING OF ELECTRONIC EQUIPMENT

A person’s normal movements can easily generate electrostatic potentials of several thousand volts. Discharge of these voltages into semiconductor devices when handling circuits can cause serious damage, which often may not be immediately apparent but the reliability of the circuit will have been reduced.

The electronic circuits of Alstom Grid products are immune to the relevant levels of electrostatic discharge when housed in their cases. Do not expose them to the risk of damage by withdrawing modules unnecessarily.

Each module incorporates the highest practicable protection for its semiconductor devices. However, if it becomes necessary to withdraw a module, the following precautions should be taken to preserve the high reliability and long life for which the equipment has been designed and manufactured.

1. Before removing a module, ensure that you are a same electrostatic potential as the equipment by touching the case.

2. Handle the module by its front-plate, frame, or edges of the printed circuit board. Avoid touching the electronic components, printed circuit track or connectors.

3. Do not pass the module to any person without first ensuring that you are both at the same electrostatic potential. Shaking hands achieves equipotential.

4. Place the module on an anti-static surface, or on a conducting surface that is at the same potential as you.

5. Store or transport the module in a conductive bag.

More information on safe working procedures for all electronic equipment can be found in BS5783 and IEC 60147-0F.

If you are making measurements on the internal electronic circuitry of equipment in service, it is preferable that you are earthed to the case with a conductive wrist strap.

Wrist straps should have a resistance to ground between 500k – 10M ohms. If a wrist strap is not available you should maintain regular contact with the case to prevent the build up of static. Instrumentation which may be used for making measurements should be earthed to the case whenever possible.

Alstom Grid strongly recommends that detailed investigations on the electronic circuitry, or modification work, should be carried out in a Special Handling Area such as described in BS5783 or IEC 60147-0F.

Page 4: Download Asset
Page 5: Download Asset

Service Manual I400/EN M/E

iSTAT I400

Page 3/58

1. SAFETY SECTION This Safety Section should be read before commencing any work on the equipment.

1.1 Health and Safety

The information in the Safety Section of the product documentation is intended to ensure that products are properly installed and handled in order to maintain them in a safe condition. It is assumed that everyone who will be associated with the equipment will be familiar with the contents of the Safety Section.

1.2 Explanation of symbols and labels

The meaning of symbols and labels may be used on the equipment or in the product documentation, is given below.

Caution: refer to product documentation Caution: risk of electric shock

Protective/safety *earth terminal Functional *earth terminal Note: This symbol may also be used for a protective/safety earth terminal if that terminal is part of a terminal block or sub-assembly e.g. power supply.

*NOTE: The term earth used throughout the product documentation is the direct equivalent of the North American term ground.

Page 6: Download Asset

Service Manual I400/EN M/E

iSTAT I400

Page 4/58

2. INSTALLING, COMMISSIONING AND SERVICING

Equipment connections

Personnel undertaking installation, commissioning or servicing work on this equipment should be aware of the correct working procedures to ensure safety. The product documentation should be consulted before installing, commissioning or servicing the equipment.

Terminals exposed during installation, commissioning and maintenance may present a hazardous voltage unless the equipment is electrically isolated.

If there is unlocked access to the rear of the equipment, care should be taken by all personnel to avoid electrical shock or energy hazards.

Voltage and current connections should be made using insulated crimp terminations to ensure that terminal block insulation requirements are maintained for safety. To ensure that wires are correctly terminated the correct crimp terminal and tool for the wire size should be used.

Before energising the equipment it must be earthed using the protective earth terminal, or the appropriate termination of the supply plug in the case of plug connected equipment. Omitting or disconnecting the equipment earth may cause a safety hazard.

The recommended minimum earth wire size is 2.5mm2, unless otherwise stated in the technical data section of the product documentation.

Before energising the equipment, the following should be checked:

− Voltage rating, frequency and polarity

− VT ratio and phase sequence

− CT circuit rating and integrity of connections;

− Protective fuse rating;

− Integrity of earth connection (where applicable)

− Supply voltage

Page 7: Download Asset

Service Manual I400/EN M/E

iSTAT I400

Page 5/58

3. EQUIPMENT OPERATING CONDITIONS The equipment should be operated within the specified electrical and environmental limits.

3.1 Current transformer circuits

Do not open the secondary circuit of a live CT since the high level voltage produced may be lethal to personnel and could damage insulation.

3.2 External resistors

Where external resistors are fitted to relays, these may present a risk of electric shock or burns, if touched.

3.3 Battery Replacement

Where internal batteries are fitted they should be replaced with the recommended type and be installed with the correct polarity, to avoid possible damage to the equipment.

3.4 Insulation and dielectric strength testing

Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each part of the test, the voltage should be gradually reduced to zero, to discharge capacitors, before the test leads are disconnected.

3.5 Insertion of modules and pcb cards

These must not be inserted into or withdrawn from equipment whist it is energised since this may result in damage.

3.6 Fibre optic communication

Where fibre optic communication devices are fitted, these should not be viewed directly. Optical power meters should be used to determine the operation or signal level of the device.

Page 8: Download Asset

Service Manual I400/EN M/E

iSTAT I400

Page 6/58

4. OLDER PRODUCTS Electrical adjustments

Equipment’s that require direct physical adjustments to their operating mechanism to change current or voltage settings should have the electrical power removed before making the change, to avoid any risk of electrical shock.

Mechanical adjustments

The electrical power to the relay contacts should be removed before checking any mechanical settings, to avoid any risk of electric shock.

Draw out case relays

Removal of the cover on equipment incorporating electromechanical operating elements, may expose hazardous live parts such as relay contacts.

Insertion and withdrawal of extender cards

When using an extender card, this should not be inserted or withdrawn from the equipment whilst it is energised. This is to avoid possible shock or damage hazards. Hazardous live voltages may be accessible on the extender card.

Insertion and withdrawal of heavy current test plugs

When using a heavy current test plug, CT shorting links must be in place before insertion or removal, to avoid potentially lethal voltages.

Page 9: Download Asset

Service Manual I400/EN M/E

iSTAT I400

Page 7/58

5. DECOMMISSIONING AND DISPOSAL

Decommissioning: The auxiliary supply circuit in the relay may include capacitors across the supply or to earth. To avoid electric shock or energy hazards, after completely isolating the supplies to the relay (both poles of any dc supply), the capacitors should be safely discharged via the external terminals prior to decommissioning.

Disposal: It is recommended that incineration and disposal to water courses is avoided. The product should be disposed of in a safe manner. Any products containing batteries should have them removed before disposal, taking precautions to avoid short circuits. Particular regulations within the country of operation, may apply to the disposal of lithium batteries.

Page 10: Download Asset

Service Manual I400/EN M/E

iSTAT I400

Page 8/58

6. TECHNICAL SPECIFICATIONS 6.1 Protective fuse rating

The recommended maximum rating of the external protective fuse for this equipment is 16A, Red Spot type or equivalent, unless otherwise stated in the technical data section of the product documentation.

Insulation class: IEC 61010-1 : 2002 Class II

EN 61010-1 : 2002 Class II

Insulation Category (Over voltage):

IEC 61010-1 : 2002 Category II (600V), III (300V) EN 61010-1 : 2002 Category II (600V), III (300V)

Environment: IEC 61010-1 : 2002 Pollution degree 2 (600V), 3 (300V)

EN 61010-1 : 2002 Pollution degree 2 (600V), 3 (300V)

Compliance is demonstrated by reference to generic safety standards.

Product Safety:

72/23/EEC & 2006/95/EC

EN 61010-1 : 2002

Compliance with the European Commission Low Voltage Directive.

Compliance is demonstrated by reference to generic safety standards.

Page 11: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 9/58

CONTENT

1. SAFETY SECTION 3

1.1 Health and Safety 3 1.2 Explanation of symbols and labels 3

2. INSTALLING, COMMISSIONING AND SERVICING 4

3. EQUIPMENT OPERATING CONDITIONS 5

3.1 Current transformer circuits 5 3.2 External resistors 5 3.3 Battery Replacement 5 3.4 Insulation and dielectric strength testing 5 3.5 Insertion of modules and pcb cards 5 3.6 Fibre optic communication 5

4. OLDER PRODUCTS 6

5. DECOMMISSIONING AND DISPOSAL 7

6. TECHNICAL SPECIFICATIONS 8

6.1 Protective fuse rating 8

7. INTRODUCTION 13

8. TECHNICAL DATA 14

8.1 Input Ratings – A.C. transducers 14 8.1.1 Voltage transducers 14 8.1.2 Current transducers 14 8.1.3 Frequency transducers 14 8.1.4 Watts, VArs, Phase Angle 15 8.1.5 Multi-function transducers 15 8.2 Input Ratings – D.C. transducers (i4D) 15 8.2.1 General 15 8.2.2 Tap Position Indicator 15 8.2.3 D.C. Voltage 15 8.2.4 D.C. Current 16 8.2.5 Resistance 16 8.2.6 Temperature (RTD) 16 8.3 Auxiliary Supply Input 17 8.3.1 Universal AC/DC auxiliary supply 17 8.3.2 AC auxiliary supply 17 8.4 Analogue Output Ratings – A.C. transducers 17

Page 12: Download Asset

I400/EN M/E Service Manual

Page 10/58

iSTAT I400 8.4.1 Output Ranges 17 8.4.2 Accuracy 17 8.5 Analogue Output Ratings – D.C. transducers 18 8.5.1 Output Ranges 18 8.5.2 Accuracy 18 8.6 Pulsed energy switches (I4E) 18 8.6.1 Output range 18 8.6.2 Accuracy 18 8.7 Communication ports 18 8.7.1 EIA232 Port 18 8.7.2 EIA485 Port 19 8.8 Electrical Environment 19 8.9 Environmental Conditions 19 8.9.1 Atmospheric environment 19 8.9.2 Construction 20

9. INSTALLATION 21

9.1 Dimensions 21 9.2 Mounting 21 9.3 Internal Jumpers 22

10. CONNECTIONS 23

10.1 Auxiliary Supply Connection 23 10.1.1 A.C. auxiliary supply 23 10.1.2 Universal auxiliary supply 23 10.2 Communications Connections 23 10.2.1 EIA232 port 23 10.2.2 EIA485 port 24 10.3 Input Connections 24 10.3.1 A.C. input transducers 24 10.3.2 D.C. input transducers 26 10.4 Output Connections 26

11. RELATED DOCUMENTS 27

12. MODBUS IMPLEMENTATION 28

12.1 TRANSACTIONS 28 12.1.1 Request 28 12.1.2 Response 28 12.1.3 Example of Request - Response cycle 28 12.2 FRAMING 29 12.2.1 RTU framing 29 12.3 SUPPORTED FUNCTIONS AND USAGE 29

Page 13: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 11/58

12.3.1 03 read from holding registers 30 12.3.2 04 read from input registers 30 12.3.3 06 write to a single holding register 31 12.3.4 16 (10 HEX) write to one or more registers 31 12.3.5 17 (11HEX) report slave id 32 12.3.6 77 (4D HEX) read measurement string 33 12.3.7 82 (52 HEX) re-read output buffer 35 12.4 ERROR RESPONSES 35 12.4.1 Exception codes 36

13. MODBUS ADDRESS MAP FOR AC MEASUREMENT TRANSDUCERS 37

14. MODBUS ADDRESS MAP FOR DC MEASUREMENT TRANSDUCERS 51

15. MODBUS DATA TYPES 55

Page 14: Download Asset

I400/EN M/E Service Manual

Page 12/58

iSTAT I400

BLANK PAGE

Page 15: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 13/58

7. INTRODUCTION iSTAT I400 digital transducers provide local and remote indication for precision electrical measurement and control when used with instruments, recorders, data loggers and SCADA (Supervisory Control and Data Acquisition) systems.

The I400 range contains the following type of devices:

(1) A.C. input transducers

• I4CA Mean-Sensing Current (single phase)

• I4VA Mean-Sensing Voltage (single phase)

• I4CD, I4CF RMS Current (single-, three-phase)

• I4VD, I4VF RMS Voltage (single-, three-phase)

• I4F Frequency

• I4P Phase Angle

• I4W Watts

• I4R VArs

• I4M Multi-function

• I4E Multi-function Energy

(2) D.C. input transducers

• I4DA Tap Position Indicator (T.P.I.)

• I4DB D.C. Voltage

• I4DC D.C. Current

• I4DF Resistance

• I4DG Temperature (RTD input)

(3) Ancillary Equipment

• I4X Communications Interfaces (separate manual)

Provision of both analogue outputs, pulsed electronic switches (I4E only) and MODBUS communication allows integration within existing sites and also in new facilities, where digital communications can be used.

The software package QDSP is used to program the I400 transducers. The ease of programmability of digital transducers is an important feature in the provision of cost effective system control. Systems can be easily changed or expanded as required. Scaling may be programmed on site, thereby avoiding costly project delays.

NOTE: When programming a transducer using the QDSP, it may additionally be necessary to physically change jumper positions within the transducer case. Refer to section 9.3 for further details.

Applications are found in electrical utilities, energy management systems, SCADA, building management and control systems, and process control environments.

Page 16: Download Asset

I400/EN M/E Service Manual

Page 14/58

iSTAT I400

8. TECHNICAL DATA 8.1 Input Ratings – A.C. transducers

8.1.1 Voltage transducers

Mean-sensing:

Nominal voltage (Un) 57.7V, 63.5V, 69.3V, 100V, 110V, 120V, 127V, 220V, 240V, 380V, 400V, 415V, 440V

Measuring range 10 to 120% Un

Burden 2 VA

Overload 1.2 x Un continuously 2 x Un for 1s

RMS:

Nominal voltage (Un) 50 – 500 V

Measuring range 0 to 120% Un

Burden 1mA x Un

Overload 1.5 x Un continuously 2 x Un for 1s

8.1.2 Current transducers

Mean-sensing:

Nominal current (In) 1A, 1.2A, 5A, 6A

Measuring range 0 to 120% In

Burden 2 VA

Overload 2 x In continuously 20 x In for 1s

RMS:

Nominal current (In) 0.5A - 5A

Measuring range 0 to 120% In

Burden 0.5 VA

Overload 2 x In continuously 20 x In for 1s

8.1.3 Frequency transducers

Nominal frequency (fn) 50Hz or 60Hz

Measuring range 45Hz to 65Hz

Burden (voltage circuit) 1mA x Un

Overload (voltage circuit) 1.2 x Un continuously 2 x Un for 1s

Page 17: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 15/58

8.1.4 Watts, VArs, Phase Angle

Nominal voltage (Un) 50 – 500V

Nominal current (In) 0.5A - 5A

Measuring range 0 to 120% In, 0 to 120% Un

Burden (voltage circuit) 1mA x Un

Overload (voltage circuit) 1.2 x Un continuously 2 x Un for 1s

Burden (current circuit) 0.5 VA

Overload (current circuit) 2 x In continuously 20 x In for 1s

8.1.5 Multi-function transducers

Nominal voltage (Un) 50 – 500V

Nominal current (In) 0.5A - 5A

Measuring range 0 to 120% In, 0 to 120% Un

Burden (voltage circuit) 0.2mA x Un

Overload (voltage circuit) 1.5 x Un continuously 2 x Un for 1s

Burden (current circuit) 0.01Ω x In 2

Overload (current circuit) 2 x In continuously 20 x In for 1s

8.2 Input Ratings – D.C. transducers (i4D)

8.2.1 General

Some of the DC Transducers are defined with different measurement ranges available. It is important that the correct range is selected when ordering as the top of the required measurement range cannot be set below the bottom of the unit’s range, i.e. if DC Voltage 1V to 50V unit is purchased the top of the configured range can not be set below 1V.

8.2.2 Tap Position Indicator

Nominal resistance (Rn) 100 Ω to 500k Ω

Number of steps 1 to 100

Minimum step value 30Ω

Measuring voltage <2.2V

Lead resistance <50Ω per lead

Burden <0.5 VA

8.2.3 D.C. Voltage

Nominal voltage (Un) ±50mV to ±300V programmable

Measuring ranges 50mV to 1V Input impedance >2.5MΩ 1V to 50 V Input impedance 250kΩ 50V to 300V Input impedance 2.5MΩ

Burden <0.5 VA

Overload 1.2 x Un continuously 2 x Un for 1s

Page 18: Download Asset

I400/EN M/E Service Manual

Page 16/58

iSTAT I400 8.2.4 D.C. Current

Nominal current (In) 0 – ±100mA (programmable)

Measuring ranges 1mA to 10mA Input impedance 100Ω 10mA to 100mA Input impedance 10Ω

Burden <0.5 VA

Overload 2 x In continuously 20 x In for 1s

8.2.5 Resistance

Nominal resistance (Rn) 10Ω to 50kΩ (programmable) 100Ω to 500kΩ (programmable)

Measuring voltage <2.2V

Lead resistance <10Ω per lead

Burden <0.5 VA

8.2.6 Temperature (RTD)

RTD sensor type Pt100, Pt1000, Ni100

Measuring method 2-wire, 3-wire or 4-wire

Measuring ranges -200°C to 850°C (Pt), -60°C to 250°C (Ni) (programmable)

RTD sensor limit values 20Ω to 10kΩ

Measuring voltage <2.2V

Lead resistance <10Ω per lead

Burden <0.5 VA

Page 19: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 17/58

8.3 Auxiliary Supply Input

8.3.1 Universal AC/DC auxiliary supply

Nominal voltage Operative range DC 24 V to 220 V 19 V to 300 V AC 50 V to 230 V (40…70 Hz) 40 V to 276 V (40…70 Hz) Burden <3VA

8.3.2 AC auxiliary supply

Nominal voltage (Ur) Operative range AC 57.7 V

63.5 V 69.3 V 100 V 110 V 115 V 120 V 208 V 230 V

80…120 % Ur

Frequency Range 45…65 Hz Burden <3VA

8.4 Analogue Output Ratings – A.C. transducers

8.4.1 Output Ranges

DC Current output

Nominal values 0..1mA, -1..0..1mA, 0..5mA, -5..0..5mA, 0..10mA, -10..0..10mA, 0..20mA, 4..20mA, -20..0..20mA

Compliance voltage 15V (10V for i4CA, i4VA)

Response time (0…99.5%) <300 ms

DC Voltage output

Nominal values 0..1V, -1..0..1V, 0..10V, -10..0..10V

Maximum current 20mA

Response time (0…99.5%) <300 ms

8.4.2 Accuracy

EN 60688 (analogue outputs) and via communications.

% of full scale unless otherwise stated.

Voltage (Mean Sensing/RMS) ±0.5%

Voltage (Suppressed Zero RMS) ±0.5% Un

Phase current ±0.5%

Neutral current ±1%

Power ±0.5%

Phase angle ±0.2°

Demand values ±1% Frequency ±0.1% (0.01% via communications) *

THD ±1%

* Accuracy of frequency is % of centre scale frequency

Page 20: Download Asset

I400/EN M/E Service Manual

Page 18/58

iSTAT I400 8.5 Analogue Output Ratings – D.C. transducers

8.5.1 Output Ranges

DC Current output

Nominal values 0..1mA, -1..0..1mA, 0..5mA, -5..0..5mA, 0..10mA, -10..0..10mA, 0..20mA, 4..20mA, -20..0..20mA

Compliance voltage 15V

Response time (0…99.5%) 500 ms

DC Voltage output

Nominal values 0..1V, -1..0..1V, 0..10V, -10..0..10V

Maximum current 20mA

Response time (0…99.5%) 500 ms

8.5.2 Accuracy

Analogue outputs and via communications.

% of full scale.

T.P.I. ±0.5%

DC Voltage ±0.5%

DC Current ±0.5%

Resistance ±0.5%

Temperature (RTD) ±0.5%

8.6 Pulsed energy switches (I4E)

8.6.1 Output range

Type Pulsed electronic switch

Pulse width 2 to 510 ms

Signal level 40V ac or dc maximum, 27mA maximum resistive load

8.6.2 Accuracy

Energy Active energy Class 1, Reactive energy Class 2 (EN61036 and EN61268)

8.7 Communication ports

8.7.1 EIA232 Port

Connection type Point to point

Signal levels EIA232

Cable type Screened multi-core

Maximum cable length 15m

Connector Screw terminals

Isolation 3.7kV rms for 1 minute between all terminals and all other circuits

Transmission mode Asynchronous

Protocol MODBUS RTU

Data rate 1200 to 115200 bits/s

Page 21: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 19/58

8.7.2 EIA485 Port

Connection type Multi-drop (32 connections per link)

Signal levels EIA485

Cable type Screened twisted pair

Maximum cable length 1000m

Connector Screw terminals

Isolation 3.7kV rms for 1 minute between all terminals and other circuits

Transmission mode Asynchronous

Protocol MODBUS RTU

Data rate 1200 to 115200 bits/s

8.8 Electrical Environment

Insulation

EN 61010-1: 1990 Insulation Class II (500V RMS) Tested at 3.7kV peak

EMC compliance

89/336/EEC & 2004/108/EC

The following generic standards were used to establish conformity.

EN 61326-1: 1997 Electrical equipment for measurement, control, and laboratory use.

EMC Requirements

Low Voltage Directive

73/23/EEC & 2006/95/EC

The following generic standards were used to establish conformity.

EN 61010-1: 2002 Electrical equipment for measurement, control, and laboratory use.

8.9 Environmental Conditions

8.9.1 Atmospheric environment

Temperature and humidity

EN 60688: 1992 Class 2

JVF (DIN 40 040)

Nominal range of operation -10°C to 55°C

Storage and transit -40°C to 70°C

Temperature coefficient (A.C. transducers) 0.02% / °C

Temperature coefficient (D.C. transducers) 0.05% / °C

Annual mean relative humidity ≤ 75%

Page 22: Download Asset

I400/EN M/E Service Manual

Page 20/58

iSTAT I400 8.9.2 Construction

Material Flammability protection UL 94 V-0

Enclosure protection IEC 60529: 1989 IP 50 (IP 20 for connection terminals)

Mounting EN 50022: 1978 DIN rail 35x15 mm

Dimensions 100mm Case 100x75x104.5 mm

45mm Case 45x75x104.5 mm

Weight AC auxiliary supply units <0.6kg

Universal aux. supply units <0.5kg

Page 23: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 21/58

9. INSTALLATION 9.1 Dimensions

104.5100

75

All dimensions in mmMaximum section of connection wires

< = 4.0mm² for one wire< = 1.5mm² for two wires

44.8 104.5

75

FIGURE 1 : I400 DIMENSIONS

Models with case width 44.8mm I4CA, I4VA, I4CD, I4VD, I4F and I4D

Models with case width 100mm I4P, I4W, I4R, I4M and I4E

9.2 Mounting

Mounting is at the rear of the unit, for 35x15 mm DIN rail according to EN 50022: 1978 .

Page 24: Download Asset

I400/EN M/E Service Manual

Page 22/58

iSTAT I400 9.3 Internal Jumpers

On programmable models of transducers, the analogue output values can be programmed using the QDSP software via the EIA232 or EIA485 communication port. However, before this is done, the hardware output range of each analogue output must be selected, on some versions (i4C, i4V, i4F, i4Dx) and on early models of other variants a physical jumper position on the output module within the transducer case needs to be changed. On later models (except i4C, i4V, i4F, i4Dx) the configuration is done completely using the configuration software and no physical changes will be required.

It is possible to choose between three hardware output ranges:

• 0…±5 mA

• 0…±20 mA

• 0…±10 V

By selecting one of these three hardware output ranges, it is possible to program any linear or multiple-slope (with maximum 5 break points) output characteristic using the QDSP setting software.

Caution: Electrical adjustments

Equipment that requires direct physical adjustments to their operating mechanism to change current or voltage settings, should have the electrical power removed before making the change, to avoid any risk of electrical shock.

Where the internal jumper needs to be set, the location of the jumpers is as shown in the diagram below. Single output transducers will have only Jumper 1 fitted.

FIGURE 2 : I400 JUMPER POSITIONS

For information, the QDSP setting software displays for each analogue output, on the Output graphical display in the Device Settings window, the positions to which the jumpers must be set to match the currently-selected output type.

If it is attempted in QDSP to select an output range which is not in the currently-selected hardware range, QDSP will display an error message, to indicate that the jumper positions must be physically changed.

Page 25: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 23/58

10. CONNECTIONS 10.1 Auxiliary Supply Connection

An auxiliary power supply is necessary for all I400 transducers, except for the self-powered mean sensing current and voltage transducers (I4CA and I4VA).

10.1.1 A.C. auxiliary supply

If the I400 transducer is fitted with an A.C. auxiliary supply, the terminal allocations are as follows:

Terminal Number Terminal Marking Description 13 ~ Live 14 ~ Neutral

10.1.2 Universal auxiliary supply

If the I400 transducer is fitted with a universal AC/DC auxiliary supply, the terminal allocations are as follows:

Terminal Number Terminal Marking Description 13 +/~ + / Live 14 – /~ Common / Neutral

10.2 Communications Connections

To be able to establish communication with an I400 unit, it has to be physically connected to the serial port of the computer or Remote Terminal Unit, etc.

I400 transducer connections are identified on the transducer label beside the screw terminals. In order to communicate with the device, auxiliary power must be applied to the device, and the communications connection must be correctly wired.

10.2.1 EIA232 port

If the I400 transducer is fitted with an EIA232 communications port, the terminal allocations are as follows:

RS232 9 pin connectionDescription I400 Terminal number Terminal

marking PC Terminal

Receive 21 (23 I4M4 only) Rx 3

Signal Ground 22 (24 I4M4 only) 5

Transmit 23 (25 I4M4 only) Tx 2

The EIA232 communications port is configured as a DTE (Data Terminal Equipment) device, which means that a crossover cable will be required to connect to a standard EIA232 serial port on a PC (also a DTE). The maximum connection length is 15 metres.

Page 26: Download Asset

I400/EN M/E Service Manual

Page 24/58

iSTAT I400 10.2.2 EIA485 port

If the I400 transducer is fitted with an EIA485 communications port, the terminal allocations are as follows:

Terminal Number Terminal Marking Description 21 (23 I4M4 only) A TxRxA (DATA+) 22 (24 I4M4 only) C No connection 23 (25 I4M4 only) B TxRxB (DATA-)

Two-wire EIA485 only is used. An EIA485 port will be required on the Master system and on any PC being used with QDSP an external EIA485 (2-wire) interface is required connected to the PC’s USB (or EIA232) port. The maximum connection length is 1000 metres. Conductors A and B should be terminated with a 120Ω terminating resistor.

10.3 Input Connections

10.3.1 A.C. input transducers

2 11

v

V

u

UL

N

Volts, frequency

1 3

LKL

N

Current

k l

LKL1

N

Power - single phase

k l

1 32 11

VU

u v

Power - 3 wire balanced

1 2 3 5 8

U V

u v

U VL1

L2

L3

k l

K L

Power - 3 wire unbalanced

1 2 3 5 7 8 9

U VL1

L2

L3

k l

K L k l

K L

Power - 4 wire balanced

LKL1

N

k l

1 32 11

VU

u v

L3

Page 27: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 25/58

Power - 4 wire unbalanced

L3

1 2 3 4 5 6 7 9 1111

L1

N

K LK L

k lk l

k l

u u u

Triple current

L3

1 3 4 6 7 9

L2L1

N

K LK L

K L

k lk l

k l

Triple voltage

L3

2 5 8 1111

L2L1

N

x x xx

NOTE: The diagrams referred to as ‘Power’ are applicable to Watt, VAr, Phase Angle and Multifunction transducers.

Page 28: Download Asset

I400/EN M/E Service Manual

Page 26/58

iSTAT I400 10.3.2 D.C. input transducers

1 2Ri

100% 0%Rx

3RuRu

4Ri

Tap Position Indicator

1+U -U

DC Voltage

33 3+I -I

DC Current

22

1Ri

Rx

Ri

Resistance, Temperature (RTD) - 2-wire

xx

44 1 2Ri

Rx

3RuRu

4Ri

Resistance, Temperature (RTD) - 3-wire

xx

1Ri

Rx

Ru4Ri

Resistance, Temperature (RTD) - 4-wire

xx

3

10.4 Output Connections

The I400 transducer output terminal allocations are as follows, where fitted:

Terminal Number Terminal Marking Description 15 + Output 1 + 16 – Output 1 – 17 + Output 2 + 18 – Output 2 – 19 + Output 3 + 20 – Output 3 – 21 (I4M4 only) – Output: 4+

22 (I4M4 only) – Output: 4 –

By default single output transducers always use Output 1 terminals (15 and 16).

I4M Multifunction transducers may be fitted with none, one, two, three or four outputs depending on order option.

I4E Multifunction energy transducers are always fitted with a pulse electronic switch on Output 1 terminals (15 and 16). If fitted, the other two outputs can be ordered as either additional electronic switches or analogue outputs.

All D.C. input transducers are single output transducers.

Page 29: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 27/58

11. RELATED DOCUMENTS

Ref Title

1 I400 Digital Transducers – Brochure

2 QDSP Technical Manual

3 Application Guide for Electrical Measuring Transducers

Page 30: Download Asset

I400/EN M/E Service Manual

Page 28/58

iSTAT I400

12. MODBUS IMPLEMENTATION 12.1 TRANSACTIONS

Communication operates on a master-slave basis where only one device (the master) can initiate transactions called 'Requests'. The other devices (slaves) respond by supplying the requested data to the master. This is called the 'Request - Response Cycle'.

Master to slave request:

Device address Function Code nx8 bit data bytes Error check

Slave to master response:

Device address Function Code nx8 bit data bytes Error check

12.1.1 Request

This Master to Slave transaction takes the form:

Device address:

Master addressing a slave (Address 0 is used for the broadcast address, which all slave devices recognise.)

Function code:

E.g. 03 asks the slave to read its Holding registers and respond with their contents.

Data bytes:

Tells the slave which register to start at and how many registers to read.

12.1.2 Response

This Slave to Master transaction takes the form:

Device address:

To let the master know which slave is responding.

Function code:

This is an echo of the request function code.

Data bytes:

Contains the data collected from the slave.

12.1.3 Example of Request - Response cycle

Input to I400 transducer: Van = 57.4 V 50Hz

Data held in Input Registers: 30057(10) & 30058(10) Starting register 30057(10) - 30000(10) offset = 57(10) = 00 39(16)

12.1.3.1 Request Frame

Starting Register Register Count CRC

Slave Address Function code HI LO HI LO LO HI

21 04 00 39 00 02

Page 31: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 29/58

12.1.3.2 Response Frame

Register Data CRC

Slave Address Function code Byte count HI LO HI LO LO HI

21 04 04 FD 00 E0 1F

Response register data, FD 00 E0 1F, is decoded as: Exponent (8 m.s.b., signed) = FD(16) = -3(10) Value (24 l.s.b., unsigned) = 00 E0 1F(16) = 57375(10) Complete number (decimal) = 57375 x 10-3 = 57.375 V

12.2 FRAMING

There are two types of message framing for Modbus serial communications, ASCII or RTU. The I400 family of transducers supports RTU framing only.

12.2.1 RTU framing

In RTU mode, messages start and end with a silent interval of at least 3.5 character times (t1-t2-t3-t4 as shown below).

The advantage of this mode of framing is that it enables a greater character density and a better data throughput. However, each message must be transmitted in a continuous stream. If a silent interval of more than 1.5 character times occurs before completion of the frame, the device flushes the incomplete message and assumes that the next byte will be the address field of a new message.

Start Address Function Data CRC Check End

t1-t2-t3-t4 8 bits 8 bits n x 8 bits 16 bits t1-t2-t3-t4

The Cyclic Redundancy Check (CRC) field is two bytes, containing a 16 bit binary value. The CRC value is calculated by the transmitting device, which appends the CRC to the message. The receiving device recalculates a CRC during receipt of the message, and compares the calculated value to the actual value it received in the CRC field. If the two values are not equal an error results. The CRC-16 calculation is an industry standard method used for error detection.

One frame is transmitted as 1 start bit, 8 data bits and 2 stop bit. If parity is selected then the frame is transmitted as 1 start bit, 8 data bits, and 1 stop bit.

Where n > 1 data is transmitted most significant byte first.

The CRC check is transmitted least significant byte first.

12.3 SUPPORTED FUNCTIONS AND USAGE

Code Code Function References

DEC HEX

3 03 to read from holding registers (4XXXX memory references)

4 04 to read from input registers (3XXXX memory references)

6 06 to write to a single holding register (4XXXX memory references)

16 10 to write to one or more holding registers (4XXXX memory references)

17 11 report slave ID 6 characters

77 4D read measurement string 1 byte value code (request)

82 52 re-read output buffer Use after broadcast request

Page 32: Download Asset

I400/EN M/E Service Manual

Page 30/58

iSTAT I400 12.3.1 03 read from holding registers

Reads the content of Holding Registers (4XXXX references) in the slave. Broadcast is also supported.

12.3.1.1 Request Frame

The query message specifies the starting register and quantity of registers (1 to 28) to be read. Registers are addressed starting at zero.

Here is an example of a request to read register 40043 “Connection Mode” from slave device 33 (=21(16) )

Starting Register Register Count CRC

Slave Address Function Code HI LO HI LO LO HI

21 03 00 2B 00 01

12.3.1.2 Response Frame

The register data in the response message is packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits.

Data is scanned in the slave at the rate of 28 registers maximum per scan. The response is returned when the data is completely assembled.

Here is an example of a response to the query:

Register Data CRC

Slave Address Function Code Byte Count HI LO LO HI

21 03 02 00 05

The contents of register 40043 is 00 05 (=’4u – 3 phase 4 wire unbalanced’).

12.3.2 04 read from input registers

Reads the content of Input Registers (3XXXX references) in the slave. Broadcast is also supported

Page 33: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 31/58

12.3.2.1 Request Frame

The query message specifies the starting register and quantity (1 to 28) of registers to be read. Registers are addressed starting at zero.

Here is an example of a request to read registers 30057 ... 30058 “U1” (=Van) from slave device 33:

Starting Register Register Count CRC

Slave Address Function Code HI LO HI LO LO HI

21 04 00 39 00 02

12.3.2.2 Response Frame

The register data in the response message is packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits.

Data is scanned in the slave at the rate of 28 registers maximum per scan. The response is returned when the data is completely assembled.

Here is an example of a response to the query:

Register Data Register Data CRC

Slave Address Function Code Byte Count HI LO HI LO LO HI

21 04 04 FD 00 E0 1F

The contents of registers 30036 ... 30037 are FD 00 and E0 1F hex.

12.3.3 06 write to a single holding register

Pre-sets a value into a single holding register (4XXXXX reference). When broadcast, the function pre-sets the same register reference in all attached slaves.

12.3.3.1 Request Frame

The query message specifies the register reference to be pre-set. Registers are addressed starting at zero; register 1 is addressed as 0.

Here is an example of a request to pre-set register 40010 “Active Access Level” to 00 02 hex (Level 2 access) in slave device 33:

Register Address Register Data CRC

Slave Address Function Code HI LO HI LO LO HI

21 06 00 0A 00 02

12.3.3.2 Response Frame

The normal response is an echo of the query, returned after the register contents have been pre-set. Here is an example of a response to the query:

Register Address Register Data CRC

Slave Address Function Code HI LO HI LO LO HI

21 06 00 0A 00 02 12.3.4 16 (10 HEX) write to one or more registers

Pre-sets values into a sequence of holding registers (4XXXX references). When broadcast, the function pre-sets the same register references in all attached slaves.

Page 34: Download Asset

I400/EN M/E Service Manual

Page 32/58

iSTAT I400 12.3.4.1 Request Frame

The query message specifies the register references to be pre-set. Registers are addressed starting at zero; register 1 is addressed as 0. Here is an example of a request to pre-set two registers starting at 40008 to 41 41 and 41 41 hex (Enter Level 2 Password AAAA), in slave device 33:

Slave Function Starting

Address

Register

Count

Byte

Count

Register

Data CRC

Address Code HI LO HI LO HI LO HI LO LO HI

21 10 00 08 00 02 04 41 41 41 41

12.3.4.2 Response Frame

The normal response returns the slave address, function code, starting address, and quantity of registers pre-set. Here is an example of a response to the query shown above.

Slave Function Starting Address Register Count CRC

Address Code HI LO HI LO LO HI

21 10 00 08 00 02

12.3.5 17 (11HEX) report slave id

Returns a description of the type of controller present at the slave address.

12.3.5.1 Request Frame

Here is an example of a request to report the ID of slave device 33:

CRC

Slave Address Function Code LO HI

21 11

12.3.5.2 Response Frame

The format of a normal response is shown below:

Slave Function Byte Register Data CRC

Address Code Count HI LO HI LO ….. LO HI

21 11 10 49 34 4D 20 20 20 54 72 61 6E 73 64 75 63 65 72

The string in the response is "I4M Transducer" (16 characters).

Page 35: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 33/58

12.3.6 77 (4D HEX) read measurement string

Reads the measurement value as an ASCII string. Broadcast is also supported.

The value codes are listed in the following table:

Value Value Byte Example

Code DEC Code HEX Measurement Value Count String Data

1 01 Frequency 7 "50.004 "

2 02 Frequency 1 7 "50.004 "

3 03 Frequency 2 7 "50.004 "

4 04 Frequency 3 7 "50.004 "

5 05 U1 7 "48.043k"

6 06 U2 7 "48.115k"

7 07 U3 7 "48.183k"

8 08 Uavg (phase to neutral) 7 "48.113k"

9 09 j12 (angle between U1 and U2) 7 "+000.00"

10 0A j23 (angle between U2 and U3) 7 "+000.02"

11 0B j31 (angle between U3 and U1) 7 "-000.02"

12 0C U12 6 "00.07k"

13 0D U23 6 "00.07k"

14 0E U31 6 "00.14k"

15 0F Uavg (phase to phase) 6 "00.09k"

16 10 I1 7 "079.94 "

17 11 I2 7 "080.58 "

18 12 I3 7 "080.40 "

19 13 IN 6 "240.9 "

21 15 Iavg 7 "080.31 "

22 16 Total I 7 "240.91 "

23 17 Active Power Total (Pt) 8 "+8147.3k"

24 18 Active Power Phase L1 (P1) 8 "+2697.6k"

25 19 Active Power Phase L2 (P2) 8 "+2724.2k"

26 1A Active Power Phase L3 (P3) 8 "+2725.1k"

27 1B Reactive Power Total (Qt) 12 "8225.8kvar L"

28 1C Reactive Power Phase L1 (Q1) 12 "2727.3kvar L"

29 1D Reactive Power Phase L2 (Q2) 12 "2750.8kvar L"

30 1E Reactive Power Phase L3 (Q3) 12 "2747.3kvar L"

31 1F Apparent Power Total (St) 7 "11.578M"

32 20 Apparent Power Phase L1 (S1) 7 "3836.0k"

33 21 Apparent Power Phase L2 (S2) 7 "3871.4k"

34 22 Apparent Power Phase L3 (S3) 7 "3869.6k"

35 23 Power Factor Total (PFt) 8 "+0.704 L"

36 24 Power Factor Phase 1 (PF1) 8 "+0.703 L"

37 25 Power Factor Phase 2 (PF2) 8 "+0.704 L"

38 26 Power Factor Phase 3 (PF3) 8 "+0.704 L"

Page 36: Download Asset

I400/EN M/E Service Manual

Page 34/58

iSTAT I400

Value Value Byte Example

Code DEC Code HEX Measurement Value Count String Data

39 27 Power Angle Total (atan2(Pt,Qt)) 7 "+045.27"

40 28 � (angle between U1 and I1) 7 "+041.46"

41 29 �2 (angle between U2 and I2) 7 "+041.05"

42 2A �3 (angle between U3 and I3) 7 "+041.24"

43 2B Internal Temperature 7 "+036.84"

44 2C U1 THD% 6 "002.81"

45 2D U2 THD% 6 "002.70"

46 2E U3 THD% 6 "002.70"

47 2F U12 THD% 6 "000.55"

48 30 U23 THD% 6 "000.55"

49 31 U31 THD% 6 "000.55"

50 32 I1 THD% 6 "034.91"

51 33 I2 THD% 6 "036.34"

52 34 I3 THD% 6 "035.65"

DYNAMIC DEMAND VALUES

53 35 I1 10 "I1=79.70 A"

54 36 I2 10 "I2=80.07 A"

55 37 I3 10 "I3=79.91 A"

56 38 Apparent Power Total (St) 11 "St=11.53MVA"

57 39 Active Power Total (Pt) - (positive) 11 "Pt=+8.051MW"

58 3A Active Power Total (Pt) - (negative) 11 "Pt=-0.000MW"

59 3B Reactive Power Total (Qt) - L 14 "Qt=8.253Mvar L"

60 3C Reactive Power Total (Qt) - C 14 "Qt=0.000Mvar C"

MAX DEMAND SINCE LAST RESET

61 3D I1 10 "I1=082.6 A"

62 3E I2 10 "I2=082.6 A"

63 3F I3 10 "I3=082.3 A"

64 40 Apparent Power Total (St) 11 "St=12.02MVA"

65 41 Active Power Total (Pt) - (positive) 11 "Pt=+08.29MW"

66 42 Active Power Total (Pt) - (negative) 11 "Pt=-00.00MW"

67 43 Reactive Power Total (Qt) - L 14 "Qt=08.71Mvar L"

68 44 Reactive Power Total (Qt) - C 14 "Qt=00.00Mvar C"

Page 37: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 35/58

12.3.6.1 Request Frame

The query message specifies the value code of the measurement to be read.

Here is an example of the query to read U1 (Van), value code 05, from slave device 33:

CRC Slave

Address

Function

Code

Value Code

LO HI

21 4D 05

12.3.6.2 Response Frame

The ASCII string in the response message is packed as data bytes. The quantity of data bytes depends on the value code.

Here is an example of a response to the query:

String Data CRC Slave

Address

Function

Code

Byte

Count 1. 2. 3. 4. 5. 6. 7. LO HI

21 4D 07 34 38 2E 30 34 33 6B

This reply is the ASCII string “48.043k”.

12.3.7 82 (52 HEX) re-read output buffer

This function should be used after the broadcast request. The addressed slave transmits the response frame of the previous request.

12.3.7.1 Request Frame

Here is an example of a request to re-read the output buffer of slave device 33:

CRC

Slave Address Function Code LO HI

21 52

12.3.7.2 Response Frame

The response to the query depends on the previous function code.

12.4 ERROR RESPONSES

When a slave detects an error other than a CRC error, a response will be sent to the master. The most significant bit of the function code byte will be set to 1 (i.e. the function code sent from the slave will be equal to the function code sent from the master plus 128). The following byte will be an exception code indicating the type of error that occurred.

The slave will ignore transmissions received from the master with CRC errors.

An example of an illegal request and the corresponding exception response is shown below. The request in this example is to read registers 0201H to 0209H. If these addresses are not supported in the slave then the following occurs:

Request Message

Starting Register Register Count

Address Function Code HI LO HI LO CRC

01 01 02 01 00 08 6D B4

Page 38: Download Asset

I400/EN M/E Service Manual

Page 36/58

iSTAT I400

Exception Response Message

Address Function Code Exception Code CRC

01 81 02 C1 91 12.4.1 Exception codes

Code Name Meaning

01 ILLEGAL FUNCTION The function code transmitted is not one of the functions supported by the slave.

02 ILLEGAL DATA ADDRESSES The data address received in the request is not an allowable value for the slave. Write to password protected registers.

03 ILLEGAL DATA VALUE The value referenced in the data field transmitted by the master is not within range for the selected data address. The register count is greater than 28 (functions 03 and 04).

06 SLAVE DEVICE BUSY The slave is engaged in processing a long duration program command. The master should re-transmit the message later when the slave is free.

Page 39: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 37/58

13. MODBUS ADDRESS MAP FOR AC MEASUREMENT TRANSDUCERS

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

30000 memory reference

SYSTEM DATA

04 30001 30008 Model Number T_Str16 Example: I4M3 Data

04 30009 30012 Serial Number T_Str8 Data

04 30013 Software Reference T1 Data 105

04 30014 Modbus Max. Register Read at Once

T1 Use 28 if (reg.30013) > 103 Data

04 30015 30018 Configuration Time Stamp

T_Time Data

04 30019 30022 Calibration Time Stamp

T_Time Data

04 30023 30024 Reserved Locations

04 30025 Hardware – I/O 4 T1 3 Jumperless Analog Output

04 30026 Hardware - I/O 1 T1 0 No I/O Data

1 Unipolar Analog Output

2 Bipolar Analog Output

3 Jumperless Analog Output

4 Pulse Output

5 Tariff Input

04 30027 Hardware - I/O 2 T1 see Hardware - I/O 1 Data

04 30028 Hardware - I/O 3 T1 see Hardware - I/O 1 Data

04 30029 Hardware - Communication Type

T1 0 No Communication Data

1 RS 232

2 RS 485

04 30030 Hardware Configuration

T1 Bit-0 External Auxiliary Supply Data

Bit-1 N - Neutral

Bit-2 Phase Voltage L1

Bit-3 Phase Voltage L2

Bit-4 Phase Voltage L3

Bit-5 Phase Current L1

Bit-6 Phase Current L2

Bit-7 Phase Current L3

04 30037 Energy Counter 1 Exponent

T2 Data

04 30038 Energy Counter 2 Exponent

T2 Data

04 30039 Energy Counter 3 Exponent

T2 Data

Page 40: Download Asset

I400/EN M/E Service Manual

Page 38/58

iSTAT I400

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

04 30040 Energy Counter 4 Exponent

T2 Data

AVAILABLE MEASUREMENTS

04 30041 Measurements Parameter 1

Data

Bit-0 Frequency

Bit-4 U1

Bit-5 U2

Bit-6 U3

Bit-7 Uavg (phase to neutral)

Bit-8 φ12 (angle between U1 and U2)

Bit-9 φ23 (angle between U2 and U3)

Bit-10 φ31 (angle between U3 and U1)

Bit-11 U12

Bit-12 U23

Bit-13 U31

Bit-14 Uavg (phase to phase)

Bit-15 I1

04 30042 Measurements Parameter 2

Data

Bit-0 I2

Bit-1 I3

Bit-2 IN

Bit-4 Iavg

Bit-5 � I

Bit-6 Active Power Total (Pt)

Bit-7 Active Power Phase L1 (P1)

Bit-8 Active Power Phase L2 (P2)

Bit-9 Active Power Phase L3 (P3)

Bit-10 Reactive Power Total (Qt)

Bit-11 Reactive Power Phase L1 (Q1)

Bit-12 Reactive Power Phase L2 (Q2)

Bit-13 Reactive Power Phase L3 (Q3)

Bit-14 Apparent Power Total (St)

Bit-15 Apparent Power Phase L1 (S1)

04 30043 Measurements Parameter 3

Data

Page 41: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 39/58

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

Bit-0 Apparent Power Phase L2 (S2)

Bit-1 Apparent Power Phase L3 (S3)

Bit-2 Power Factor Total (PFt)

Bit-3 Power Factor Phase 1 (PF1)

Bit-4 Power Factor Phase 2 (PF2)

Bit-5 Power Factor Phase 3 (PF3)

Bit-6 Power Angle Total (atan2(Pt,Qt))

Bit-7 φ1 (angle between U1 and I1)

Bit-8 φ2 (angle between U2 and I2)

Bit-9 φ3 (angle between U3 and I3)

Bit-10 Internal Temperature

Bit-11 U1 THD%

Bit-12 U2 THD%

Bit-13 U3 THD%

Bit-14 U12 THD%

Bit-15 U23 THD%

04 30044 Measurements Parameter 4

Data

Bit-0 U31 THD%

Bit-1 I1 THD%

Bit-2 I2 THD%

Bit-3 I3 THD%

Bit-8 Energy Counter 1

Bit-9 Energy Counter 2

Bit-10 Energy Counter 3

Bit-11 Energy Counter 4

04 30045 Measurements Parameter 5

Data

Bit-0 MD I1

Bit-1 MD I2

Bit-2 MD I3

Bit-3 MD St

Bit-4 MD Pt1

Bit-5 MD Pt2

Bit-6 MD Qt1

Bit-7 MD Qt2

Bit-8 MD Previous Period

Page 42: Download Asset

I400/EN M/E Service Manual

Page 40/58

iSTAT I400

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

Bit-9 MD Since Last Reset

MEASUREMENT

04 30049 30050 Frequency T5 Hz Data

04 30057 30058 U1 T5 V Data

04 30059 30060 U2 T5 V Data

04 30061 30062 U3 T5 V Data

04 30063 30064 Uavg (phase to neutral)

T5 V Data

04 30065 φ12 (angle between U1 and U2)

T17 deg Data -180.00 179.99 0.01

04 30066 φ23 (angle between U2 and U3)

T17 deg Data -180.00 179.99 0.01

04 30067 φ31 (angle between U3 and U1)

T17 deg Data -180.00 179.99 0.01

04 30068 30069 U12 T5 V Data

04 30070 30071 U23 T5 V Data

04 30072 30073 U31 T5 V Data

04 30074 30075 Uavg (phase to phase)

T5 V Data

04 30076 30077 I1 T5 A Data

04 30078 30079 I2 T5 A Data

04 30080 30081 I3 T5 A Data

04 30082 30083 IN T5 A Data

04 30086 30087 Iavg T5 A Data

04 30088 30089 ΣI T5 A Data

04 30090 30091 Active Power Total (Pt)

T6 W Data

04 30092 30093 Active Power Phase L1 (P1)

T6 W Data

04 30094 30095 Active Power Phase L2 (P2)

T6 W Data

04 30096 30097 Active Power Phase L3 (P3)

T6 W Data

04 30098 30099 Reactive Power Total (Qt)

T6 var L (if > 0) var C (if < 0) Data

04 30100 30101 Reactive Power Phase L1 (Q1)

T6 var L (if > 0) var C (if < 0) Data

04 30102 30103 Reactive Power Phase L2 (Q2)

T6 var L (if > 0) var C (if < 0) Data

04 30104 30105 Reactive Power Phase L3 (Q3)

T6 var L (if > 0) var C (if < 0) Data

04 30106 30107 Apparent Power Total (St)

T5 VA Data

04 30108 30109 Apparent Power Phase L1 (S1)

T5 VA Data

Page 43: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 41/58

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

04 30110 30111 Apparent Power Phase L2 (S2)

T5 VA Data

04 30112 30113 Apparent Power Phase L3 (S3)

T5 VA Data

04 30114 30115 Power Factor Total (PFt)

T7 Data

04 30116 30117 Power Factor Phase 1 (PF1)

T7 Data

04 30118 30119 Power Factor Phase 2 (PF2)

T7 Data

04 30120 30121 Power Factor Phase 3 (PF3)

T7 Data

04 30122 Power Angle Total (atan2(Pt,Qt))

T17 deg Data -180.00 179.99 0.01

04 30123 φ1 (angle between U1 and I1)

T17 deg Data -180.00 179.99 0.01

04 30124 φ2 (angle between U2 and I2)

T17 deg Data -180.00 179.99 0.01

04 30125 φ3 (angle between U3 and I3)

T17 deg Data -180.00 179.99 0.01

04 30126 Internal Temperature T17 deg C Data

ENERGY

04 30134 30135 Energy Counter 1 T3 Data -99999999

899999999

1

04 30136 30137 Energy Counter 2 T3 Data -99999999

899999999

1

04 30138 30139 Energy Counter 3 T3 Data -99999999

899999999

1

04 30140 30141 Energy Counter 4 T3 Data -99999999

899999999

1

DEMAND VALUES

DYNAMIC DEMAND VALUES

04 30175 30176 I1 T5 Data

04 30177 30178 I2 T5 Data

04 30179 30180 I3 T5 Data

04 30181 30182 Apparent Power Total (St)

T5 Data

04 30183 30184 Active Power Total (Pt) - (positive)

T6 Data

04 30185 30186 Active Power Total (Pt) - (negative)

T6 Data

04 30187 30188 Reactive Power Total (Qt) - L

T6 Data

Page 44: Download Asset

I400/EN M/E Service Manual

Page 42/58

iSTAT I400

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

04 30189 30190 Reactive Power Total (Qt) - C

T6 Data

MAX DEMAND SINCE LAST RESET

04 30207 30208 I1 T5 Data

04 30213 30214 I2 T5 Data

04 30219 30220 I3 T5 Data

04 30225 30226 Apparent Power Total (St)

T5 Data

04 30231 30232 Active Power Total (Pt) - (positive)

T6 Data

04 30237 30238 Active Power Total (Pt) - (negative)

T6 Data

04 30243 30244 Reactive Power Total (Qt) - L

T6 Data

04 30249 30250 Reactive Power Total (Qt) - C

T6 Data

THD HARMONIC DATA

04 30639 U1 THD% T16 Data

04 30640 U2 THD% T16 Data

04 30641 U3 THD% T16 Data

04 30642 U12 THD% T16 Data

04 30643 U23 THD% T16 Data

04 30644 U31 THD% T16 Data

04 30645 I1 THD% T16 Data

04 30646 I2 THD% T16 Data

04 30647 I3 THD% T16 Data

40000 memory reference

SYSTEM DATA

16 40001 40002 User Password (L1, L2)

T_Str4 A…Z Password to attempt user access level upgrade

Setting 41h 5Ah 1

16 40003 40005 Factory Password (FAC)

T_Str6 A…Z Password to attempt factory access level upgrade

Setting 41h 5Ah 1

16 40006 40007 Level 1 - User password

T_Str4 A…Z Setting 41h 5Ah 1

Page 45: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 43/58

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

16 40008 40009 Level 2 - User password

T_Str4 A…Z Setting 41h 5Ah 1

03, 06 40010 Active Access Level T1 0 Full protection Setting 0 3 1

1 Access up to level 1 user password

Data

2 Access up to level 2 user password

Data

3 Access up to level 2 (backup pass.)

Data

4 Factory access level Data

03, 06, 16

40012 40021 Description 1 T_Str20 Alphanum Setting 20h 7Eh 1

03, 06, 16

40022 40031 Description 2 T_Str20 Alphanum Setting 20h 7Eh 1

SYSTEM CONFIGURATION

03, 06 40032 "M" Function Mode T1 0 I400 order of measurements Setting 0 1 1

03, 06 40041 Pulse Length T2 ms Setting 2 510 2

03, 06 40042 Common Energy Counter Exponent

T2 Setting -3 9 1

03, 06 40043 Connection Mode T1 0 No mode Setting 0 5 1

1 1b - Single Phase

2 3b - 3 phase 3 wire balanced

3 4b - 3 phase 4 wire balanced

4 3u - 3 phase 3 wire unbalanced

5 4u - 3 phase 4 wire unbalanced

03, 06 40044 CT Secondary T4 mA Setting ? ? ?

03, 06 40045 CT Primary T4 A/10 Setting ? ? ?

03, 06 40046 VT Secondary T4 mV Setting ? ? ?

03, 06 40047 VT Primary T4 V/10 Setting ? ? ?

03, 06 40048 Calibration current T4 mA Setting ? ? ?

03, 06 40049 Calibration voltage T4 mV Setting ? ? ?

03, 06 40050 Current input/output range

T16 % of input range for 100% output

Setting 10 100 0.01

03, 06 40051 Voltage input/output range

T16 % of input range for 100% output

Setting 10 100 0.01

SYSTEM COMMANDS

06 40052 Reset command register

T1 Bit-0 Reset Energy Meter

Bit-1 Reset Demand

Page 46: Download Asset

I400/EN M/E Service Manual

Page 44/58

iSTAT I400

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

06 40053 Operator Command Register

T1 1 Save Settings Setting 1 2 1

2 Abort Settings

COMMUNICATION

03, 06 40055 Modbus Address T1 Setting 1 247 1

03, 06 40056 Baud Rate T1 0 Baud rate 1200 Setting 0 7 1

1 Baud rate 2400

2 Baud rate 4800

3 Baud rate 9600

4 Baud rate 19200

5 Baud rate 38400

6 Baud rate 57600

7 Baud rate 115200

03, 06 40057 Stop Bit T1 0 1 Stop bit Setting 0 1 1

1 2 Stop bits

03, 06 40058 Parity T1 0 No parity Setting 0 2 1

1 Odd parity

2 Even parity

03, 06 40059 Data Bits T1 0 8 bits Setting 0 1 1

1 7 bits

ANALOG OUTPUTS

OUTPUT 1

03, 06 40060 Output 1 Type T1 0 1 mA Setting 0 5 1

1 5 mA

2 10 mA

3 20 mA

4 1 V

5 10 V

03, 06 40061 Output 1 Parameter T1 0 No parameter Setting 0 255 1

1 Frequency

5 U1

6 U2

7 U3

8 Uavg (phase to neutral)

9 φ12 (angle between U1 and U2)

10 φ23 (angle between U2 and U3)

11 φ31 (angle between U3 and U1)

Page 47: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 45/58

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

12 U12

13 U23

14 U31

15 Uavg (phase to phase)

16 I1

17 I2

18 I3

19 IN

21 Iavg

22 ΣI

23 Active Power Total (Pt)

24 Active Power Phase L1 (P1)

25 Active Power Phase L2 (P2)

26 Active Power Phase L3 (P3)

27 Reactive Power Total (Qt)

28 Reactive Power Phase L1 (Q1)

29 Reactive Power Phase L2 (Q2)

30 Reactive Power Phase L3 (Q3)

31 Apparent Power Total (St)

32 Apparent Power Phase L1 (S1)

33 Apparent Power Phase L2 (S2)

34 Apparent Power Phase L3 (S3)

35 Power Factor Total (PFt)

36 Power Factor Phase 1 (PF1)

37 Power Factor Phase 2 (PF2)

38 Power Factor Phase 3 (PF3)

39 Power Angle Total (atan2(Pt,Qt))

40 φ1 (angle between U1 and I1)

41 φ2 (angle between U2 and I2)

42 φ3 (angle between U3 and I3)

43 Internal Temperature

44 U1 THD%

45 U2 THD%

46 U3 THD%

Page 48: Download Asset

I400/EN M/E Service Manual

Page 46/58

iSTAT I400

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

47 U12 THD%

48 U23 THD%

49 U31 THD%

50 I1 THD%

51 I2 THD%

52 I3 THD%

DYNAMIC DEMAND VALUES

53 I1

54 I2

55 I3

56 Apparent Power Total (St)

57 Active Power Total (Pt) - (positive)

58 Active Power Total (Pt) - (negative)

59 Reactive Power Total (Qt) - L

60 Reactive Power Total (Qt) - C

MAX DEMAND SINCE LAST RESET

61 I1

62 I2

63 I3

64 Apparent Power Total (St)

65 Active Power Total (Pt) - (positive)

66 Active Power Total (Pt) - (negative)

67 Reactive Power Total (Qt) - L

68 Reactive Power Total (Qt) - C

EXTENDED POWER FACTOR

69 CAP/IND P. F. Total (PFt)

70 CAP/IND P. F. Phase 1 (PF1)

71 CAP/IND P. F. Phase 2 (PF2)

72 CAP/IND P. F. Phase 3 (PF3)

Directional Currents

(= Ix * sign(Px))

73 Directional Iavg

74 Directional I1

75 Directional I2

76 Directional I3

Page 49: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 47/58

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

03, 06 40062 Output 1 Function Type

T1 0 linear Setting 0 1 1

1 quadratic

03, 06 40063 Output 1 Number of Breakpoints

T1 Setting 0 6 1

03, 06 40064 Output 1 Lower X Point (X0)

T17 % of parameter value Setting -300 300 0.01

03, 06 40065 Output 1 Lower Y Point (Y0)

T17 % of output type Setting -120 120 0.01

03, 06 40066 Output 1 X Breakpoint 1 (X1)

T17 % of parameter value Setting -300 300 0.01

03, 06 40067 Output 1 Y Breakpoint 1 (Y1)

T17 % of output type Setting -120 120 0.01

03, 06 40068 Output 1 X Breakpoint 2 (X2)

T17 % of parameter value Setting -300 300 0.01

03, 06 40069 Output 1 Y Breakpoint 2 (Y2)

T17 % of output type Setting -120 120 0.01

03, 06 40070 Output 1 X Breakpoint 3 (X3)

T17 % of parameter value Setting -300 300 0.01

03, 06 40071 Output 1 Y Breakpoint 3 (Y3)

T17 % of output type Setting -120 120 0.01

03, 06 40072 Output 1 X Breakpoint 4 (X4)

T17 % of parameter value Setting -300 300 0.01

03, 06 40073 Output 1 Y Breakpoint 4 (Y4)

T17 % of output type Setting -120 120 0.01

03, 06 40074 Output 1 X Breakpoint 5 (X5)

T17 % of parameter value Setting -300 300 0.01

03, 06 40075 Output 1 Y Breakpoint 5 (Y5)

T17 % of output type Setting -120 120 0.01

03, 06 40076 Output 1 X Breakpoint 6 (X6)

T17 % of parameter value Setting -300 300 0.01

03, 06 40077 Output 1 Y Breakpoint 6 (Y6)

T17 % of output type Setting -120 120 0.01

OUTPUT 2

03, 06 40080 Output 2 Type T1 See Output 1 Setting 0 5 1

03, 06 40081 Output 2 Parameter T1 See Output 1 Setting 0 255 1

03, 06 40082 Output 2 Function Type

T1 See Output 1 Setting 0 1 1

03, 06 40083 Output 2 Number of Breakpoints

T1 Setting 0 6 1

03, 06 40084 Output 2 Lower X Point (X0)

T17 % of parameter value Setting -300 300 0.01

03, 06 40085 Output 2 Lower Y Point (Y0)

T17 % of output type Setting -120 120 0.01

03, 06 40086 Output 2 X Breakpoint 1 (X1)

T17 % of parameter value Setting -300 300 0.01

03, 06 40087 Output 2 Y Breakpoint 1 (Y1)

T17 % of output type Setting -120 120 0.01

03, 06 40088 Output 2 X Breakpoint 2 (X2)

T17 % of parameter value Setting -300 300 0.01

Page 50: Download Asset

I400/EN M/E Service Manual

Page 48/58

iSTAT I400

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

03, 06 40089 Output 2 Y Breakpoint 2 (Y2)

T17 % of output type Setting -120 120 0.01

03, 06 40090 Output 2 X Breakpoint 3 (X3)

T17 % of parameter value Setting -300 300 0.01

03, 06 40091 Output 2 Y Breakpoint 3 (Y3)

T17 % of output type Setting -120 120 0.01

03, 06 40092 Output 2 X Breakpoint 4 (X4)

T17 % of parameter value Setting -300 300 0.01

03, 06 40093 Output 2 Y Breakpoint 4 (Y4)

T17 % of output type Setting -120 120 0.01

03, 06 40094 Output 2 X Breakpoint 5 (X5)

T17 % of parameter value Setting -300 300 0.01

03, 06 40095 Output 2 Y Breakpoint 5 (Y5)

T17 % of output type Setting -120 120 0.01

03, 06 40096 Output 2 X Breakpoint 6 (X6)

T17 % of parameter value Setting -300 300 0.01

03, 06 40097 Output 2 Y Breakpoint 6 (Y6)

T17 % of output type Setting -120 120 0.01

OUTPUT 3

03, 06 40100 Output 3 Type T1 See Output 1 Setting 0 5 1

03, 06 40101 Output 3 Parameter T1 See Output 1 Setting 0 255 1

03, 06 40102 Output 3 Function Type

T1 See Output 1 Setting 0 1 1

03, 06 40103 Output 3 Number of Breakpoints

T1 Setting 0 6 1

03, 06 40104 Output 3 Lower X Point (X0)

T17 % of parameter value Setting -300 300 0.01

03, 06 40105 Output 3 Lower Y Point (Y0)

T17 % of output type Setting -120 120 0.01

03, 06 40106 Output 3 X Breakpoint 1 (X1)

T17 % of parameter value Setting -300 300 0.01

03, 06 40107 Output 3 Y Breakpoint 1 (Y1)

T17 % of output type Setting -120 120 0.01

03, 06 40108 Output 3 X Breakpoint 2 (X2)

T17 % of parameter value Setting -300 300 0.01

03, 06 40109 Output 3 Y Breakpoint 2 (Y2)

T17 % of output type Setting -120 120 0.01

03, 06 40110 Output 3 X Breakpoint 3 (X3)

T17 % of parameter value Setting -300 300 0.01

03, 06 40111 Output 3 Y Breakpoint 3 (Y3)

T17 % of output type Setting -120 120 0.01

03, 06 40112 Output 3 X Breakpoint 4 (X4)

T17 % of parameter value Setting -300 300 0.01

03, 06 40113 Output 3 Y Breakpoint 4 (Y4)

T17 % of output type Setting -120 120 0.01

03, 06 40114 Output 3 X Breakpoint 5 (X5)

T17 % of parameter value Setting -300 300 0.01

03, 06 40115 Output 3 Y Breakpoint 5 (Y5)

T17 % of output type Setting -120 120 0.01

03, 06 40116 Output 3 X Breakpoint 6 (X6)

T17 % of parameter value Setting -300 300 0.01

Page 51: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 49/58

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

03, 06 40117 Output 3 Y Breakpoint 6 (Y6)

T17 % of output type Setting -120 120 0.01

DEMAND CALCULATIONS

03, 06 40123 Time constant T1 minutes (0=disabled) Setting 0 255 1

ENERGY COUNTER SETTINGS

Energy Counter 1

03, 06 40131 Energy Counter 1 Parameter

T1 0 No parameter Setting 0 3 1

1 Active Power

2 Reactive Power

3 Apparent Power

03, 06 40132 Energy Counter 1 Configuration

T1 Bit-0 Quadrant I Enabled Setting 0 63 1

Bit-1 Quadrant II Enabled

Bit-2 Quadrant III Enabled

Bit-3 Quadrant IV Enabled

Bit-4 Absolute Value

Bit-5 Invert Value

03,06 40134 Energy Counter 1 divider

T1 1, 10, 100, 1000, 10000 Setting

Energy Counter 2

03, 06 40135 Energy Counter 2 Parameter

T1 See Energy Counter 1 Parameter

Setting 0 3 1

03, 06 40136 Energy Counter 2 Configuration

T1 See Energy Counter 1 Configuration

Setting 0 63 1

03,06 40138 Energy Counter 2 divider

T1 See Energy Counter 1 divider

Setting

Energy Counter 3

03, 06 40139 Energy Counter 3 Parameter

T1 See Energy Counter 1 Parameter

Setting 0 3 1

03, 06 40140 Energy Counter 3 Configuration

T1 See Energy Counter 1 Configuration

Setting 0 63 1

03,06 40142 Energy Counter 3 divider

T1 See Energy Counter 1 divider

Setting

Energy Counter 4

03, 06 40143 Energy Counter 4 Parameter

T1 See Energy Counter 1 Parameter

Setting 0 3 1

03, 06 40144 Energy Counter 4 Configuration

T1 See Energy Counter 1 Configuration

Setting 0 63 1

Page 52: Download Asset

I400/EN M/E Service Manual

Page 50/58

iSTAT I400

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

03,06 40146 Energy Counter 4 divider

T1 See Energy Counter 1 divider

Setting

ANALOGUE OUTPUT 4

03, 06 40160 Output 4 Type T1 See Analogue Output 1 Setting 0 5 1

03, 06 40161 Output 4 Parameter T1 See Analogue Output 1 Setting 0 255 1

03, 06 40162 Output 4 Function Type

T1 See Analogue Output 1 Setting 0 1 1

03, 06 40163 Output 4 Number of Breakpoints

T1 Setting 0 6 1

03, 06 40164 Output 4 Lower X Point (X0)

T17 % of parameter value Setting -300 300 0.01

03, 06 40165 Output 4 Lower Y Point (Y0)

T17 % of output type Setting -120 120 0.01

03, 06 40166 Output 4 X Breakpoint 1 (X1)

T17 % of parameter value Setting -300 300 0.01

03, 06 40167 Output 4 Y Breakpoint 1 (Y1)

T17 % of output type Setting -120 120 0.01

03, 06 40168 Output 4 X Breakpoint 2 (X2)

T17 % of parameter value Setting -300 300 0.01

03, 06 40169 Output 4 Y Breakpoint 2 (Y2)

T17 % of output type Setting -120 120 0.01

03, 06 40170 Output 4 X Breakpoint 3 (X3)

T17 % of parameter value Setting -300 300 0.01

03, 06 40171 Output 4 Y Breakpoint 3 (Y3)

T17 % of output type Setting -120 120 0.01

03, 06 40172 Output 4 X Breakpoint 4 (X4)

T17 % of parameter value Setting -300 300 0.01

03, 06 40173 Output 4 Y Breakpoint 4 (Y4)

T17 % of output type Setting -120 120 0.01

03, 06 40174 Output 4 X Breakpoint 5 (X5)

T17 % of parameter value Setting -300 300 0.01

03, 06 40175 Output 4 Y Breakpoint 5 (Y5)

T17 % of output type Setting -120 120 0.01

03, 06 40176 Output 4 X Breakpoint 6 (X6)

T17 % of parameter value Setting -300 300 0.01

03, 06 40177 Output 4 Y Breakpoint 6 (Y6)

T17 % of output type Setting -120 120 0.01

Page 53: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 51/58

14. MODBUS ADDRESS MAP FOR DC MEASUREMENT TRANSDUCERS

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

30000 memory reference

SYSTEM DATA

04 30001 30008 Model Number T_Str16 Example: I4DB Data

04 30009 30012 Serial Number T_Str8 Data

04 30013 Software Reference T1 Data

04 30014 Modbus Max. Register Read at Once

T1 Use 28 if (reg.30013) > 103 Data

04 30015 30018 Configuration Time Stamp

T_Time Data

04 30019 30022 Calibration Time Stamp

T_Time Data

04 30023 30025 Reserved Locations

04 30026 Hardware - I/O 1 T1 0 No I/O Data

2 Bipolar Analog Output

04 30029 Hardware - Communication Type

T1 0 No Communication Data

1 RS 232

2 RS 485

MEASUREMENT

04 30126 Internal Temperature T17 Deg C Data

04 31501 31502 User Function T6 User Unit Data

04 31503 31504 DC Voltage T6 V Data

04 31505 31506 DC Current T6 A Data

04 31507 31508 Resistance T6 Ohm Data

04 31509 Temperature T19 Deg C Data

04 31511 Ratio T17 % Data

40000 memory reference

SYSTEM DATA

16 40001 40002 User Password (L1, L2)

T_Str4 A…Z Password to attempt user access level upgrade

Setting 41h 5Ah 1

16 40003 40005 Factory Password (FAC)

T_Str6 A…Z Password to attempt factory access level upgrade

Setting 41h 5Ah 1

16 40006 40007 Level 1 - User password

T_Str4 A…Z Setting 41h 5Ah 1

16 40008 40009 Level 2 - User password

T_Str4 A…Z Setting 41h 5Ah 1

03, 06 40010 Active Access Level T1 0 Full protection Setting 0 3 1

Page 54: Download Asset

I400/EN M/E Service Manual

Page 52/58

iSTAT I400

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

1 Access up to level 1 user password

Data

2 Access up to level 2 user password

Data

3 Access up to level 2 (backup pass.)

Data

4 Factory access level Data

03, 06, 16

40012 40021 Description 1 T_Str20 Alphanum Setting 20h 7Eh 1

03, 06, 16

40022 40031 Description 2 T_Str20 Alphanum Setting 20h 7Eh 1

COMMUNICATION

03, 06 40055 Modbus Address T1 Setting 1 247 1

03, 06 40056 Baud Rate T1 0 Baud rate 1200 Setting 0 7 1

1 Baud rate 2400

2 Baud rate 4800

3 Baud rate 9600

4 Baud rate 19200

5 Baud rate 38400

6 Baud rate 57600

7 Baud rate 115200

03, 06 40057 Stop Bit T1 0 1 Stop bit Setting 0 1 1

1 2 Stop bits

03, 06 40058 Parity T1 0 No parity Setting 0 2 1

1 Odd parity

2 Even parity

03, 06 40059 Data Bits T1 0 8 bits Setting 0 1 1

1 7 bits

ANALOG OUTPUTS

OUTPUT 1

03, 06 40060 Output 1 Type T1 0 1 mA Setting 0 5 1

1 5 mA

2 10 mA

3 20 mA

4 1 V

5 10 V

03, 06 40061 Output 1 Parameter T1 0 No parameter Setting 0 255 1

43 Internal Temperature

100 User Function

Page 55: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 53/58

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

101 DC Voltage

102 DC Current

103 Resistance

104 Temperature

106 Ratio

03, 06 40062 Output 1 Function Type

T1 0 linear Setting 0 1 1

1 quadratic

03, 06 40063 Output 1 Number of Breakpoints

T1 Setting 0 6 1

03, 06 40064 Output 1 Lower X Point (X0)

T17 % of parameter value Setting -300 300 0.01

03, 06 40065 Output 1 Lower Y Point (Y0)

T17 % of output type Setting -120 120 0.01

03, 06 40066 Output 1 X Breakpoint 1 (X1)

T17 % of parameter value Setting -300 300 0.01

03, 06 40067 Output 1 Y Breakpoint 1 (Y1)

T17 % of output type Setting -120 120 0.01

03, 06 40068 Output 1 X Breakpoint 2 (X2)

T17 % of parameter value Setting -300 300 0.01

03, 06 40069 Output 1 Y Breakpoint 2 (Y2)

T17 % of output type Setting -120 120 0.01

03, 06 40070 Output 1 X Breakpoint 3 (X3)

T17 % of parameter value Setting -300 300 0.01

03, 06 40071 Output 1 Y Breakpoint 3 (Y3)

T17 % of output type Setting -120 120 0.01

03, 06 40072 Output 1 X Breakpoint 4 (X4)

T17 % of parameter value Setting -300 300 0.01

03, 06 40073 Output 1 Y Breakpoint 4 (Y4)

T17 % of output type Setting -120 120 0.01

03, 06 40074 Output 1 X Breakpoint 5 (X5)

T17 % of parameter value Setting -300 300 0.01

03, 06 40075 Output 1 Y Breakpoint 5 (Y5)

T17 % of output type Setting -120 120 0.01

03, 06 40076 Output 1 X Breakpoint 6 (X6)

T17 % of parameter value Setting -300 300 0.01

03, 06 40077 Output 1 Y Breakpoint 6 (Y6)

T17 % of output type Setting -120 120 0.01

DC INPUT CONFIGURATION

03, 06 40200 Max. Voltage input range

T4c V Setting

03, 06 40201 Max Current input range

T4c A Setting

03, 06 40202 Max Resistance input range

T4 Ohm Setting

03, 06 40204 Voltage input/output range

T16 % of input range for 100% output

Setting 0.1 100 0.01

Page 56: Download Asset

I400/EN M/E Service Manual

Page 54/58

iSTAT I400

Code Address Contents Data Ind Values/Dependencies Type Min Max

Step

03, 06 40205 Current input/output range

T16 % of input range for 100% output

Setting 0.1 100 0.01

03, 06 40206 Resistance input/output range

T16 % of input range for 100% output

Setting 0.01 100 0.01

03,06 40207 Number of Quantization levels

T1 0 for continuous Setting 0 1000 1

03,06 40208 Resistance Connection Mode

T1 0 2-wire Setting 2 1 2

1 3-wire

2 4-wire

03, 06 40209 Offset Resistance T16 Terminal Wires Resistance (Ohms)

Setting 0 100 0.01

03,06 40210 Input Average Time Interval

T18 Seconds Setting 0.1 6 0.1

03,06 40211 Number of sliding windows for avg.

T1 Setting 1 10 1

LINEARISATION FUNCTION

03, 06 40230 Zero Input point (X=0) T17 % of input range for x=0 Setting -120 120 0.01

03, 06 40231 Unit Input point (X=1) T17 % of input range for x=1 Setting -120 120 0.01

03, 06 40232 Function Type T1 0 Linear Setting 0 10 1

1 User Function

2 Pt100

3 Ni100

03, 06 40233 User function Nominal Output Exponent

T2 Setting -15 15 1

03, 06 40234 User function Nominal Output Value

T1 Setting 1 65536 1

03, 06 40235 User function Polynomial level

T1 Setting 0 6 1

03, 06 40236 Polynom factor A0 T17 % Setting -327.68 327.67 0.01

03, 06 40237 Polynom factor A1 T17 % Setting -327.68 327.67 0.01

03, 06 40238 Polynom factor A2 T17 % Setting -327.68 327.67 0.01

03, 06 40239 Polynom factor A3 T17 % Setting -327.68 327.67 0.01

03, 06 40240 Polynom factor A4 T17 % Setting -327.68 327.67 0.01

03, 06 40241 Polynom factor A5 T17 % Setting -327.68 327.67 0.01

03, 06 40242 Polynom factor A6 T17 % Setting -327.68 327.67 0.01

Page 57: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 55/58

15. MODBUS DATA TYPES

Type Value / Bit Mask Description

T1 Unsigned Value (16 bit)

Example: 12345 stored as 12345 = 3039(16)

T2 Signed Value (16 bit)

Example: -12345 stored as -12345 = CFC7(16)

T3 Signed Long Value (32 bit)

Example: 123456789 stored as 123456789 = 075B CD 15(16)

T4 Short Unsigned float (16 bit)

bits # 15..14 Decade Exponent(Unsigned 2 bit)

bits # 13..00 Binary Unsigned Value (14 bit)

Example: 10000*102 stored as A710(16)

T5 Unsigned Measurement (32 bit)

bits # 31..24 Decade Exponent(Signed 8 bit)

bits # 23..00 Binary Unsigned Value (24 bit)

Example: 123456*10-3 stored as FD01 E240(16)

T6 Signed Measurement (32 bit)

bits # 31..24 Decade Exponent (Signed 8 bit)

bits # 23..00 Binary Signed value (24 bit)

Example: - 123456*10-3 stored as FDFE 1DC0(16)

T7 Power Factor (32 bit)

bits # 31..24 Sign: Import/Export (00/FF)

bits # 23..16 Sign: Inductive/Capacitive (00/FF)

bits # 15..00 Unsigned Value (16 bit), 4 decimal places

Example: 0.9876 CAP stored as 00FF 2694(16)

T8 Time stamp (32 bit)

bits # 31..24 Minutes 00 - 59 (BCD)

bits # 23..16 Hours 00 - 23 (BCD)

bits # 15..08 Day of month 01 - 31 (BCD)

bits # 07..00 Month of year 01 - 12 (BCD)

Example: 15:42, 1. SEP stored as 4215 0109(16)

T9 Time (32 bit)

bits # 31..24 1/100s 00 - 99 (BCD)

bits # 23..16 Seconds 00 - 59 (BCD)

bits # 15..08 Minutes 00 - 59 (BCD)

bits # 07..00 Hours 00 - 24 (BCD)

Example: 15:42:03.75 stored as 7503 4215(16)

T10 Date (32 bit)

bits # 31..24 Day of month 01 - 31 (BCD)

Page 58: Download Asset

I400/EN M/E Service Manual

Page 56/58

iSTAT I400

Type Value / Bit Mask Description

bits # 23..16 Month of year 01 - 12 (BCD)

bits # 15..00 Year (unsigned integer) 1998..4095

Example: 10, SEP 2000 stored as 1009 07D0(16)

T_Str4 Text String 4 characters

(T11) Two characters per 16 bit register

T_Str6 Text String 6 characters

(T12) Two characters per 16 bit register

T_Str8 Text String 8 characters

Two characters per 16 bit register.

T_Str16 Text String 16 characters

Two characters per 16 bit register.

T_Str20 Text String 20 characters

Two characters per 16 bit register.

T16 Unsigned Value (16 bit), 2 decimal places

Example: 123.45 stored as 123.45 = 3039(16)

T17 Signed Value (16 bit), 2 decimal places

Example: -123.45 stored as -123.45 = CFC7(16)

T18 Unsigned Value (16 bit), 1 decimal palce Example: 1234.5 stored as 1234.5 = 3039(16) T19 Signed Value (16 bit), 1 decimal palce Example: -1234.5 stored as -1234.5 = CFC7(16) T_Time Time and Date (64 bit)

bits # 63..56 1/100s 00 - 99 (BCD)

bits # 55..48 Seconds 00 - 59 (BCD)

bits # 47..40 Minutes 00 - 59 (BCD)

bits # 39..32 Hours 00 - 24 (BCD)

bits # 31..24 Day of month 01 - 31 (BCD)

bits # 23..16 Month of year 01 - 12 (BCD)

bits # 15..00 Year (unsigned integer) 1998..4095

Example: 15:42:03.75, 10. SEP 2000 stored as 7503 4215 1009 07D0(16)

T_TimeIEC Time and Date (64 bit) = IEC870-5-4 "Binary Time 2a"

bits # 63..55 Reserved

bits # 54..48 Years (0 .. 99)

bits # 47..44 Reserved

bits # 43..40 Months (1 .. 12)

bits # 39..37 Day of Week (1 .. 7)

bits # 36..32 Day of Month (1 .. 31)

bit # 31 Summer Time (0 .. 1): Summer time (1), Standard time (0)

bits # 30..29 Reserved

Page 59: Download Asset

Service Manual I400/EN M/E iSTAT I400

Page 57/58

Type Value / Bit Mask Description

bits # 28..24 Hours (0 .. 23)

bit # 23 Invalid (0 .. 1): Invalid (1), Valid (0)

bit # 22 Reserved

bits # 21..16 Minutes (0 .. 59)

bits # 15..00 Milliseconds (0 .. 59999)

Example: 15:42, 1. SEP stored as 4215 0109(16)

T_Data Record Data

Size and SubTypes depends on the Actual Memory Part

T4c Short Unsigned float (16 bit), 3 decimal palces bits # 15..14 Decade Exponent(Unsigned 2 bit) bits # 13..00 Binary Unsigned Value (14 bit) Example: 10.000*102 stored as A710(16)

Page 60: Download Asset

I400/EN M/E Service Manual

Page 58/58

iSTAT I400

BLANK PAGE

Page 61: Download Asset
Page 62: Download Asset

PXXX Product Description

GRID

Alstom Grid © - ALSTOM 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. Alstom Grid Worldwide Contact Centre www.alstom.com/grid/contactcentre/ Tel: +44 (0) 1785 250 070 www.alstom.com