  • Design data Ammonia PumpRefrigerating plant

    Refrigerating capacity Q0 250.00 150.00 [kW] Circulation factor k: 4.0 4.0Pressure drop p 2,66 2,66 [bar]NPSH available (NPSHA): 2,50 2,50 [m]Operating point:Volume flow Qr: 3,91 3,91 [mc/h]Delivery head Hr: 40.00 40.00 [m]Net frequency fN: 50,00 50 [Hz]Nominal data: :

    Pump: CAM(R) 2/3 CAM(R) 2/3

    Stages: 3,00 3,00Impeller diameter D2: 114.0/130.0 [mm]Construction: Without inducerVolume flow Qopt : 10,77 10,77 [mc/h]Delivery head Hopt: 31.44 31.44 [m]Qmax orifice diameter D0: 13.9 10.4 [mm]Refrigerant: R717 (NH3) R717 (NH3)Evaporation temperature Top: -30.0 -30.0 [C]Density (Top): 0.678 0.678 [kg/l]Specific heat capacity Cp(Top):

    1,066 1,066[kcal/kg

    K]Vapour pressure pv(Top): 1,19 1,19 [bar]Equipment: Qmax orifice Qmax orificeDrive: AGX3.0 AGX3.0

    114.0/130.0 [mm]Without inducer

    Drive: AGX3.0 AGX3.0Rated power P1: 4,30 4,30 [kW]Shaft power P2: 3.00 3.00 [kW]Frequency fN: 50,00 50,00 [Hz]Rated speed n: 2.720,00 2.720,00 [min-1]Rated voltage UN: 40010% 40010% [V]Rated current lN: 7,50 7,50 [A]Starting current ratio lA/lN: 3,50 3,50Power factor cos : 0.83 0.83Insulation class: H HOperating range: Q min

    all Q r Q max

    all Q min

    all Q r Q max

    all Volume flow Q: 1.00 3,91 9,74 1.00 2.34 5.59 [m3/h]Delivery head H: 48,65 40 0 47.33 40 0 [m]Input power 1,56 1,77 2,02 1,56 1,66 1,85 [kW]NPSH required (NPSHR): 0,33 0,21 0,49 0,33 0,21 0,25 [m]Speed n: 2941 2930 2917 2941 2935 2926 [min-1]