INSTALLATION, OPERATION, ANDMAINTENANCE MANUAL
“CMP & C” Series Custom Metered Series
CC ValveAUTOMATIC WATER
CONDITIONERS
1
“CMP & C” Series Automatic Water Conditioners
SPECIFICATION TABLE
NOTE:(1) Pressure drop not to exceed 15 psi.(2) Pressurevesselsareseamlessandmadeofreinforcedfiberglass,pressuretestedat300psi.(3) Brinetanksarefabricatedofseamless,rigid,tough,highimpact,non-toxicpolyethylene.(4) Productmaterialsandworkmanshipareprotectedwithawrittenwarranty.(5)Untreatedwaterprovidedduringallstepsofregeneration.(6)Wastewatervolumesbasedon“normal”lengthregeneration,15lb./cu.ft.saltdosage,50psiinletpressure.
Model Number Units CMP-22K CMP-22-C
Exchange Capacity
Kilograms
MAXMIDMIN
Salt PerRegenerationLbs. / Regen.
MAXMIDMIN
Max Service Flow (1) GPM 16.00 15.00 17.00 20.00 16.00 15.00
Pipe Size In - Out Drain
INSINS
1” 1” 1” 1” 1” 1”w w w w w w
Operating Pressure
RangePSI 30-125 30-125 30-125 30-125 30-12530-125
Maximum Operating
TemperatureDEG F 110 110 110 110 110 110
Mineral Tank Size
(Dia. x Ht.) (2)INS. 8 x 44 9 x 48 10 x 54 12 x 52 8 x 35 10 x 35
Brine Tank (Dia. x Ht. (3) INS. 18 x 33 18 x 33 18 x 40 18 x 40
Salt Storage LBS. 375 375 375 450 250 250
Resin Volume CU FT. 0.75 1.00 1.5 2.00 0.75 1.00
Electrical 120 Volts 60 Hz
Shipping Weight LBS. 72 105 119 137 77 91
Floor Space INS. 27 x 18 28 x 18 29 x 16 31 x 18 13.5 x 22.5 13.5 x 22.5Overall Ht. INS. 52 56 62 60 42 42Max. Drain
Flow DuringRegeneration
GPM 1.7 2.2 2.7 3.2 1.7 2.7
Regeneration Waste
Volume (6)GAL. 60 80 95 120 60 75
VOLT. / FREQ.
COLOR / CODEInjector Violet/C Red/D White/E Blue/F Violet/C White/E
CMP-30K CMP-40K
16.00
1”w
30-125
110
10 x 47
18 x 33
375
1.3
110
29 x 16
54
2.7
95
White/E
CMP-45K CMP-60K CMP-30-C
22,83619,509
14,514
30,44826,012
19,352
45,67239,018
29,028
60,89652,024
38,704
22,83619,509
14.514
30,44826,012
19,35211.258.004.00
15.0010.005.00
22.5015.008.00
30.0020.0010.00
11.258.004.00
15.0010.005.00
38,06032,515
24,19018.7513.006.00
2
Brin
e Ta
nkA
ssem
bly
Sof
tene
r Tan
kA
ssem
bly
San
itary
Dra
in, F
loor
Dra
in o
r La
undr
y Tu
bs a
re a
ccep
tabl
e.D
o no
t mak
e a
dire
ct c
onne
ctio
nto
the
drai
n. A
n ai
r gap
mus
t be
pre
sent
.
Brin
e Ta
nk O
verfl
ow d
rain
1/2
” di
amet
er m
inim
um s
ize
(gra
vity
flow
)
Col
d ha
rd w
ater
inle
t30
p.s
.i. m
inim
um p
ress
ure
1/2”
min
imum
pip
e si
ze
Max
imum
dra
in p
ipe
elev
atio
n ab
ove
drai
npo
rt is
5 ft
.
Hig
h P
ress
ure
War
ning
:If
feed
wat
er p
ress
ure
is k
now
n to
be
abov
e10
0 p.
s.i.
it is
stro
ngly
reco
mm
ende
d th
at a
pres
sure
redu
cing
val
ve b
e in
stal
led
at th
is p
oint
.
Har
d w
ater
to S
prin
kler
s an
d an
y de
rsire
d un
softe
ned
fixtu
res
Gro
und
Stra
p
Sof
tene
d W
ater
Out
let
Man
ual O
utle
t Val
ve(o
ptio
nal)
Brin
e Li
ne T
ubin
g
110-
125
Volt
Con
tinuo
us P
ower
Sup
ply
Tran
sfor
mer
Man
ual B
ypas
s Va
lve
(Nor
mal
ly C
lose
d)(o
ptio
nal)
Man
ual I
nlet
Val
ve(o
ptio
nal)
Dra
in P
ort
Dra
in li
ne 1
/2” d
iam
eter
m
inim
um s
ize
Con
nect
ion
to s
anita
ry s
ewer
line
(o
ptio
nal)
Air
gap
devi
ce
San
itary
sew
er li
ne
Dra
in T
rap
Dra
in
Typi
cal W
ater
Sof
tene
r Ins
talla
tion
“CMP & C” Series Automatic Water Conditioners
3
Installation Fitting Assemblies
Installationfittingsconnecttothecontrolvalveorthebypassvalveusing nuts that only require hand tightening. Handtightnutconnectionsbetweencontrolvalveandinstallationfittings,controlvalveandbypassvalve,andbypassvalveandinstallationfittingsallowforeaseserviceability.Donotuseapipewrenchtotightennutsoninstallationfittings.Hand tighten only.
Splitringretainerdesignholdsthenutonandallowsloadtobespreadovertheentirenutsurfaceareareducingthechanceforleakage.Thesplitringdesign,incorporatedintotheinstallationfittingsallowsapproximately2degreesoffaxisalignmenttotheplumbingsystem.Theinstallationfittingsaredesignedtoaccommodateminorplumbingmisalignmentsbutarenotdesignedtosupporttheweightofasystemortheplumbing.
Whenassemblingtheinstallationfittingpackage,connectthefittingtotheplumbingsystemfirstandthenattachthenut,splitringando-ring.Heatfromsolderingorsolventcementsmaydamagethenut,splitringoro-ring.Solderjointsshouldbecoolandsolventcementsshouldbesetbeforeinstallingthenut,splitringando-ring.Avoidgettingprimerandsolventcementsonanypartoftheo-ringsorsplitrings,bypassvalveorcontrolvalve.Solventcementsandprimersshouldbeusedinaccordancewiththemanufacturer’sinstructions.
Slipthenutontothefittingfirst,thenthesplitringsecondandtheo-ringlast.handtightenthenut.Ifthefittingisleaking,tighteningthenutwillnotstoptheleak.Removethenut,removethefitting,andcheckfordamageormisalignmentoftheo-ring.
Do notusethepipedopeorothersealantonthreads.Teflontapemustbeusedonthethreadsofthe1”NPTelbowandthe1/4”NPTconnectionandonthethreadsforthedrainlineconnection.Teflontapeisnotnecessaryonthenutconnectionorcapsbecauseofo-ringseals.
Do notuseVaseline,oilsorotherunacceptablelubricantsono-rings.Asiliconlubricantmaybeusedonblacko-rings.
Bypass Valve
Thebypassvalveeasilyconnectstothecontrolvalvebodyusingnutsthatonlyrequirehandtightening.Handtightennutconnectionsbetweencontrolvalveandfittings,controlvalveandbypassvalve,andbypassvalveandinstallationfittingsallowforeasyserviceability.Thesplitringretainerdesignholdsthenutonandallowsloadtobespreadovertheentirenutsurfaceareareducingthechanceforleakage.Thesplitringdesign,incorporatedintothebypass,allowsapproximately2degreesoffaxisalignmenttotheplumbingsystem.Thebypassisdesignedtoaccommodateminorplumbingmisalignmentsbutisnotdesignedtosupporttheweightofasystemortheplumbing.
Avoidgettingprimerandsolventcementsonanypartoftheo-ringsorsplitrings,bypassvalveorcontrolvalve.Donotusepipedopeorothersealantonthreads.Teflontapeisnotnecessaryonthecapsbecauseofo-ringseals.
DonotuseVaseline,oilorotherunacceptablelubricantsono-rings.Asiliconlubricantmaybeusedonblacko-rings.
“CMP & C” Series Automatic Water Conditioners
4
A. GENERAL
1. Shutoffallwateratmainsupplyvalve.2. Shutoffthefuelsupplytowaterheater.3. Openfaucets(hotandcold)nearestpumporwatermetertorelievepressureanddrainsystem.4. Movesoftenerintotheinstallationposition.Looselyattachallfittingstomeasureforbypassvalveas-
sembly(ifused),ormanualbypassvalve.5. Leveltheunit.Placeshimsundercabinetorbrinetankasneeded. (Do Notusemetalshims.)6. Cutthecoldwatersupplylineasrequired.7. Installthebypassvalveassemblyifused.
B. PLANNING INSTALLATION
1. Allinstallationproceduresmustconformtolocalplumbing,electricalandsanitationcodesandordinances.2. Itisrecommendedthatoutsidefaucetsforlawnservicebeonthehardwaterline,aheadofthesoftener,
toconservesoftenedwater,savesaltandpreventlawndamage.3. Ifthisisn’tpractical,usetheconvenientintegralbypassvalveassemblyduringirrigationflows. CAUTION: The inlet water temperature MUST NOT exceed 1200 F.4. Donotlocatesoftenerwhereambienttemperaturedropsbelow400 F.5. Allowspacearoundthesoftenerforeaseofservicing.6. Thesoftenerdrainlinesmustneverbesolidlyconnectedtothesewerline.(Alwaysprovideanairgapat
theENDofthedrainline).Valvedrainlinemustnotbeelevatedover5’fromthetopofthesofteneronwellsystems,andnotover8’onmunicipalwatersystems.
7. Thesaltstoragecabinetorbrinetankisagravitydrain,andthisdrainlinemustbelowerthanthedrainfittingonthesidewallofthecabinet.
8. Movethesoftenerintopositionandconnecttobypassassembly(ifused).Theintegralmanualbypassoptionisaconnectionwhicheliminatestheneedfora3-valvemanifold.Thismakesinstallationeasierandprovidesamoreconvenientmethodofbypassing.
9. IMPORTANT:Besurethatthewaterinletlineisconnectedtothe“inlet”sideofthebypassvalveortotheinletfitting.(Bypassvalvebothinlet/outletfittingsaremarked.)Ifwaterlinesarereverse,(inlet/out-let)resinmaybeforcedfromthewatersoftenerintothehouseholdplumbingsystem.Ifthisoccurs,householdplumbingsystemmustbeflushedclean.
C. CONNECT ALL FITTINGS (refer to previous page)
CAUTION: Care must be used when working with copper tubing. Do not allow the flame from torch to contact any portion of the Valve assembly.
1. Attach1/2”drainlinetodrainelbowwithinsertandnut.Useoptional3/4”drainfittingsifdrainrun exceeds 25 ft.
2. Donotelevatethedrainlineover5’abovethetopofthevalve(8’onmunicipalsystems)ortoexceed25’inlengthateitherheight.
CAUTION: An air gap must be provided upon sewer entry. (Conform to local plumbing and sanitation codes and ordinances).
3. Thesaltstoragecabinetorbrinetankprovidesanoverflow.Attach1/2”IDflexibleplastictubingtotheoverflowfittinganddirectittothedrain.DO NOTconnecttothemaindrainline.Useaseparategravityflowline.
“CMP & C” Series Automatic Water Conditioners
5
D. PRESSURE TEST THE INSTALLATIONTheplumbingsystemcannowbecheckedforanypossibleleaks1. Puttheunitintobackwash.Todothis,pushandholdtheREGENbuttonfor3-5seconds.Whenthe
Valvestopscycling,unplugtheunit.Withwatersupplyoff,putthebypassintotheserviceposition.2. Openwatersupplylinevalveveryslowly.Watershouldescapeslowlyfromthedrainline.Ifwaterenters
tooquickly,resinmaybelosttothedrain.3. Whenalloftheairhasbeenpurgedfromthemineraltank(waterflowssteadilyfromthedrain)openthe
mainsupplyvalvefully.4. Allow water to run to drain until clear. CHECK FOR LEAKS!5. Plugtheunitbackin.6. Manuallysteptheunitthroughtheremainingsteps,stoppingatthefillcycle(todothis,pushtheREGEN
button.TheunitwillsayBrineonthescreen).Oncethepistonhasstoppedmoving,pushtheREGENbuttonagaintothenextcycle.ContinueuntilFillappearsonthescreen.Theunitwillnowfillthebrinetanktotheappropriatelevel.(Thissequnceisforsoftenerswithpostfillbrine)
7. Allowcontroltoreturntothehomeposition.8. Checkforleaks!9. Makesurethepowercordispluggedintoaproperlygroundedwallreceptacle.
E. MANUAL REGENERATIONTheusercaninitiatemanualregeneration.Theuserhastheoptiontorequestamanualregenerationatthe delayedregenerationtimeortohavetheregenerationoccurimmediately:1. PressingandreleasingtheREGENbutton.“RegenToday”willflashonthedisplayandtheregeneration willoccuratthedelayedregenerationtime.Theusercancanceltherequestbypressingandreleasing
theREGENbutton.Thismethodofmanuallyinitiatingregenerationisnotallowedwhenthesystemissetto immediatelyregeneratewhenthegalloncapacityreacheszero.2. PressingandholdingtheREGENbuttonforapproximately3secondswillimmediatelystarttheregeneration Theusercannotcancelthisrequest.
NOTE: Program Timer “Lockout” Feature
TheProgramTimerisinitiallysettoallowaccesstoallProgramming,DiagnosticandHistoryscreens
TheInstallercanlimitaccessto(lockout)mostscreensbyactivatingtheLockoutFeature.
Activating“Lockout”allowstheusertoviewandchangeonlyWaterHardness,DaysOverride,TimeofRegenerationandTimeofday.
Activate “Lockout” Feature:PressthenNEXTthenthenSETCLOCKinsequence.LOCwillbrieflyappear inthedisplay.
De-activate “Lockout” Feature:PressthenNEXTthenthenSETCLOCK.UNLOCwillbrieflyappearin thedisplay.
Wheninoperationnormaluserdisplayssuchastimeofday,gallonsremainingordaysremainingbeforeregenerationareshown.Whensteppingthroughaprocedureifnobuttonsarepressedwithinfiveminutesthedisplayreturnstoanormaluserdisplay.Anychangesmadepriortothefiveminutetimeoutareincorporated.Theoneexceptioniscur-rentflowratedisplayunderthediagnosticprocedure.Thecurrentflowratedisplayhasa30minutetimeoutfeature.
“CMP & C” Series Automatic Water Conditioners
6
Control Valve Function and Cycles of Operation
ThisglassfilledNoryl1fullyautomaticcontrolvalveisdesignedastheprimarycontrolcentertodirectandregulateallcyclesofawatersoftenerorfilter.Whenthecontrolvalveissetupasasoftener,thecontrolvalvecanbesettoperformdownfloworupflowregenerationwiththeproperpiston.Whenthecontrolvalveissetupasafilter,thecontrolvalvecanbesettoperformdownflowregenerationorsimplybackwash.Thecontrolvalvecanbesettoregenerateondemand(consumptionofapredeterminedamountofwater)and/orasatimeclock(passageofaparticularnumberofdays).ThecontrolvalvecanbesetsothatthesoftenercanmeettheWaterQualityAssociation(WQA)orNSFInternationalefficiencyrating.
Thecontrolvalveiscompatiblewithavarietyofregenerantsandresincleaners.Thecontrolvalveiscapableofroutingtheflowofwaterinthenecessarypathstoregenerateorbackwashwatertreatmentsystems.Theinjectorregulatestheflowofbrineorotherregenerants.Thecontrolvalveregulatestheflowratesforbackwashing,rinsingandthereplenishingoftreatedwaterintoaregeneranttank,whenapplicable.
Thecontrolvalveisdesignedtodeliverhighservice(27gpm@15psig)andbackwash(27gpm@25psig)flowrateswhenthebypasshasstraightfittingsanda1.050”distributor.Thecontrolvalveusesnotraditionalfasteners(e.g.screws),insteadclips,threadedcaps,nutsandsnaptypelatchesareused.Capsandnutsonlyneedtobefirmlyhandtightenedbecauseradialsealsareused.Toolsrequiredtoservicethevalveincludeonesmallbladescrewdriver,pliersandapairofhands.Disassemblyforservicingtakesmuchlesstimethancomparableproductscurrentlyonthemarket.Controlvalveinstallationismadeeasybecausethedistributortubecanbecut1/2”aboveto1/2”belowthetopofthetankthread.Thedistributortubeisheldinplacebyano-ringsealandthecontrolvalvealsohasabayonetlockfeatureforupperdistributorbaskets.
Thetransformerpowerpackcomeswitha15-footpowercordandisdesignedforusewiththecontrolvalve.Thetransformerpowerpackisfordrylocationuseonly.Thecontrolvalveremembersallsettingsfortwohoursifthepowergoesout.Aftertwohours,theonlyitemthatneedstoberesetisthetimeofday;allothervaluesarestoredinthememory.Thecontrolvalvedoesnotneedbatteries.
Table3showstheorderofthecycleswhenthevalveissetupasasoftener.Whenthecontrolvalveisusedasadownflowsoftener,twobackwashesalwaysoccur.Whenthecontrolvalveisusedasanupflowsoftener,onlyonebackwashoccursafterbrining.Theinstallerhastheoptionofhavingtheregenerantrefillaftertherinsecycleorhavetheregenerantprefillbeforeregeneration.Iftheinstallerchoosestohavetheregenerantprefillbeforeregeneration,theprefillstartstwohoursbeforetheregenerationtimeset.Duringthe2-hourperiodinwhichthebrineisbeingmade,treated(softened)waterisstillavailable.Forexample:regenerationtime=2:00A.M.,prefilloptionselected,downflowsoftener.Filloccursat12:00A.M.,startofbackwashcycleoccursat2:00A.M.
1 - Noryl is a trademark of General Electric
Table 3Regeneration Cycles
1st Cycle: Backwash Normal2nd Cycle: Regenerate3rd Cycle: Backwash Normal5th Cycle: Rinse6th Cycle: Fill
“CMP & C” Series Automatic Water Conditioners
7
GeneralOperationWhenthesystemisoperatingoneoftwodisplayswillbeshown.PressingNEXTwillalternatebetweenthedisplays.Oneofthedisplaysisalwaysthecurrenttime ofdaywhichhastobeset(seepg.9).Capacityremainingisthenumberofgallonsthatwillbetreatedbeforethesystemgoesthrougharegenerationcycle.Theusercanscrollbetweenthedisplaysasdesired.Ifthesystemhascalledforaregenerationthatwilloccuratthepresettimeofregeneration,thewordsREGENTODAYwillappearonthedisplay.Whenwaterisbeingtreated(i.e.waterisflowingthroughthesystem)theword“Softening”or“Filtering”flashesonthedisplay.
User Displays/Settings
REGENTODAY
SOFTENING CAPACITY REMAINING
GAL
REGENTODAYwillshowifaregenerationisexpected“Tonight.”
TIME
650
REGENTODAY
SOFTENINGPM6:35
Installer Displays/SettingsSTEP 1-PressNEXTandsimultaneouslyfor3seconds.STEP 2-Hardness:Settheamountofhardnessingrainsofhardnessascalciumcarbonatepergallonusingtheorbuttons.Valuerangesfrom1to150in1grainincrements.Notethegrainspergalloncanbeincreasedifsolubleironneedstobereduced.Thisdisplaywillshow “-nA-”if“FILTER”isselectedorif‘AUTO’isnotselected.PressNEXTtogotostep3.PressREGENtoexitInstallerDisplays/Settings.STEP 3-DayOverride:Whengalloncapacityissettooff,setthenumberofdaysbetweenregenerations.WhengalloncapacityissettoAUTOortoanumber,setthemaximumnumberofdaysbetweenregenerations.Ifvaluesetto“oFF”regenerationinitiationisbasedsolelyongallonsused.Ifvalueissetasanumber(allowablerangefrom1to28)aregenerationinitiationwillbecalledforonthatdayevenifsufficientnumberofgallonswerenotusedtocallforaregeneration.SetDayOverrideusingorbuttons: • numberofdaysbetweenregeneration(1to28);or • “oFF”PressNEXTtogotostep4.PressREGENtoreturntopreviousstep.STEP 4-NextRegenerationTime(hour):Setthehourofdayforregenerationusingorbuttons.AM/PMtogglesafter12.Thedefaulttimeis2:00a.m.Thisdisplaywillshow“REGENon0GAL”if“on0”isselectedinbytheinstaller.PressNEXTtogotoStep5.PressREGENtoreturntopreviousstep.STEP 5-NextRegenerationTime(minutes):Settheminutesofdayforregenerationusingorbuttons.Thisdisplaywillnotbeshownif“on0”isselectedbytheinstaller(2a.m.isthefactorysetting).PressNEXTtoexitInstallerDisplays/Settings.PressREGENtoreturntopreviousstep.Toinitiateamanualregenerationimmediately,pressandholdthe“REGEN”buttonforthreeseconds.Thesystemwillbegintoregenerateimmediately.Thecontrolvalvemaybesteppedthroughthevariousregenerationcyclesbypressingthe“REGEN”button.
RETURN TO NORMAL MODE
REGEN
SET TIMEA.M.
REGEN
SET TIMEA.M.
REGENDAY
SET
SET CLOCK NEXT REGEN
Step 1
SET HARDNESS
Step 2
20
SET HARDNESS
Step 3
14
Step 4
2:00
Step 5
2:00
SET CLOCK NEXT REGEN
SET CLOCK NEXT REGEN
SET CLOCK NEXT REGEN
SET CLOCK NEXT REGEN
SET CLOCK NEXT REGEN
SET CLOCK NEXT REGEN
“CMP & C” Series Automatic Water Conditioners
8
RegenerationModeTypicallyasystemissettoregenerateatatimeoflowwaterusage.Anexampleofatimewithlowwaterusageiswhenahouseholdisasleep.Ifthereisademandforwaterwhenthesystemisregenerating,untreatedwaterwillbeused.
SetTimeofDayTheusercanalsosetthetimeofday.Timeofdayshouldonlyneedtobesetafterextendedpoweroutagesorwhendaylightsavingtimebeginsorendsandatthetimeofstart-up.Ifanextendedpoweroutageoccurs,thetimeofdaywillflashonandoffwhichindicatesthetimeofdayshouldbereset.STEP 1U - press SET CLOCK.STEP 2U-CurrentTime(hour):Setthehourofthedayusingorbuttons.AM/PMtogglesafter12.PressNEXTtogotostep3U.STEP 3U -CurrentTime(minutes):Settheminutesofthedayusingorbuttons.PressNEXTtoexitSetClock.PressREGENtoreturntopreviousstep.
Power LossIfthepowergoesoutforlessthantwohours,thesystemwillautomaticallyresetitself.Ifanextendedpoweroutageoccurs,thetimeofdaywillflashonandoffwhichindicatesthetimeofdayshouldbereset.Thesystemwillretaintheotherinformationenteredbytheinstaller.
Whenthesystembeginstoregenerate,thedisplaywillchangetoincludeinformationaboutthestepoftheregenerationprocessandthetimeremainingforthatsteptobecompleted.Thesystemrunsthroughthestepsautomaticallyandwillresetitselftoprovidetreatedwaterwhentheregenerationhasbeencompleted.ManualRegenerationSometimesthereisaneedtoregeneratethesystem,soonerthanwhenthesystemcallsforit,usuallyreferredtoasmanualregeneration.Theremaybeaperiodofheavywaterusagebecauseofguestsoraheavylaundryday.
Toinitiateamanualregenerationatthepresetdelayedregenerationtime,pressandrelease“REGEN”.Thewords“REGENTODAY”willflashonthedisplaytoindicatethatthesystemwillregenerateatthepresetdelayedregenera-tiontime.Ifyoupressedthe“REGEN”buttoninerror,pressingthebuttonagainwillcanceltherequest.Note:Iftheregenerationtimeoptionissetto“on0”thereisnosetdelayedregenerationtimeso“REGENTODAY”willnotactivateif“REGEN”buttonispressed.Toinitiateamanualregenerationimmediately,pressandholdthe“REGEN”buttonforthreeseconds.Thesystemwillbegintoregenerateimmediately.Therequestcannotbecancelled.Note:Forsofteners,ifbrinetankdoesnotcontainsalt,fillwithsaltandwaitatleasttwohoursbeforeregenerating.
ErrorMessageIftheword“ERROR”andanumberarealternatelyflashingonthedisplaycontacttheInstallerforhelp.Thisindicatesthatthevalvewasnotabletofunctionproperly.Referto“Troubleshooting”for“ERRORRESET”procedure.
P.M.
P.M.
REGENTODAYwillshowifaregenerationisexpected“Tonight.”
REGENTODAY
CAPACITY REMAINING
GAL
REGEN
BACKWASH
SET TIME
Step 2U
6:35
Step 3U
6:35SET TIME
Step 1U
Error 1003
2 8:22
320SET
CLOCK NEXT REGEN
SET CLOCK NEXT REGEN
SET CLOCK NEXT REGEN
SET CLOCK NEXT REGEN
“CMP & C” Series Automatic Water Conditioners
9
FLOW DIAGRAMSflowdiagram...service
SUPPLY WATER INLET
SUPPLY WATER TO TOP OF TANKCONDITIONED WATER
FROM DISTRIBUTOR
OUTLET PORT FOR SERVICE WATER
SUPPLY WATER
flowdiagram...backwashTO DRAIN
PISTON ROD ISBELOW 2nd STEP DOWN
SUPPLY WATER INLET
SUPPLY WATER TO DISTRIBUTOR
BACKWASH WATER TO DRAIN
OUTLET PORT FOR SERVICE WATER
SUPPLY WATER
PISTON ROD IS BOTTOMED OUTIN“HOME”POSITION
TO DRAIN
SUPPLY WATER INLET
SUPPLY WATER TO TOP OF TANK
CONDITIONED WATER FROM DISTRIBUTOR
OUTLET PORT FOR SERVICE WATER
SUPPLY WATER
flowdiagram...rinse flowdiagram...fill
CONDITIONED WATER TOREGENERANTTANK
SUPPLY WATER
OUTLET PORT FOR SERVICE WATER
CONDITIONED WATER FROM DISTRIBUTOR
SUPPLY WATER TO TOP OF TANK
SUPPLY WATER INLET
PISTON ROD ISBELOW 1st STEP DOWN
PISTON ROD IS4thSTEPDOWN
flowdiagram...downflowbrineTO DRAIN
PISTON ROD ISBELOW 3rd STEP DOWN
SUPPLY WATER INLET
SUPPLYWATERANDREGENERANTTO TOP OF TANK
WASTE WATER FROM DISTRIBUTOR
OUTLET PORT FOR SERVICE WATER
SUPPLY WATER
REGENERANTTRAVELSTHROUGHMANIFOLD
TO THE INJECTOR
REGENERANTIS SIPHONED IN
REGENERANTINMANIFOLD
“CMP & C” Series Automatic Water Conditioners
10
DIAGNOSTIC MODESupply
Water ExitsSupply
Water Enters
Figure 3
Diagnostic: Theinlethandlepointsinthedirectionofflowandtheoutlethandlepointstothecenterofbypassvalve,systemwaterpressureisallowedtothecontrolvalveandtheplumbingsystemwhilenotallowingwatertoexitfromthecontrolvalvetotheplumbing.
BYPASS OPERATION
NoWater Exits
SupplyWaterisshutofffrom the house and the
valve
SHUT OFF MODEFigure 4
ShutOff: Theinlethandlepointstothecenterofthebypassvalveandtheoutlethandlepointsinthedirectionofflow,thewaterisshutofftotheplumbingsystem.Ifwaterisavailableontheoutletsideofthesofteneritisanindicationofwaterbypassaroundthesystem(i.e.aplumbing connectionsomewhereinthebuildingbypassesthesystem).
“Untreated”Water Exits
SupplyWater Enters
Figure 2
Bypass: Theinletandoutlethandlespointtothecenterofthebypass,thecontrolvalveisisolatedfromthewaterpressurecontainedintheplumbingsystem.Untreatedwaterissuppliedtotheplumbingsystem.
NORMAL OPERATION“Treated”
Water ExitsSupply
Water Enters
Figure 1
Normal Operation: Theinletandoutlethandlespointinthedirectionofflowindicatedbytheengravedarrowsonthecontrolvalve.Waterflowsthroughthecontrolvalveduringnormaloperationandthispositionalsoallowsthecontrolvalvetoisolatethemediabedduringtheregenerationcycle.
Bypass ValveThebypassvalveistypicallyusedtoisolatethecontrolvalvefromtheplumbingsystem’swaterpressureinordertoper-formcontrolvalverepairsormaintenance.TheWS1bypassvalveisparticularlyuniqueinthewatertreatment industryduetoitsversatilityandstateoftheartdesignfeatures.The1”fullflowbypassvalveincorporatesfourpositionsincludingadiagnosticpositionthatallowsservicepersonaltoworkonapressurizedsystemwhilestillprovidinguntreatedbypasswatertothefacilityorresidence.Itscompletelynon-metallic,allplastic,designallowsforeasy accessandserviceabilitywithouttheneedfortools.
ThebypassbodyandrotorsareglassfilledNorylandthenutsandcapsareglassfilledpolypropylene.Allsealsare self-lubricatingEPDMtohelppreventvalveseizingafterlongperiodsofnon-use.Internalo-ringscaneasilybereplaced ifserviceisrequired.
Thebypassconsistsoftwointerchangeableplugvalvesthatareoperatedindependentlybyredarrowshapedhandles.Thehandlesidentifytheflowdirectionofthewater.Theplugvalvesenablethebypassvalvetooperateinfourpositions.
“CMP & C” Series Automatic Water Conditioners
11
DriveCa
pAs
sembly,Dow
nflow
Piston,
Rege
nera
nt P
isto
n an
d Sp
acer
Sta
ck A
ssem
bly
& Fr
ont C
over
and
Driv
e A
ssem
bly
t
t
t
tPa
rtofKit,O-ring(Item#51)
14
“CMP
& C
” Seri
es Au
tomati
c Wate
r Con
dition
ers
12
Front Cover and Drive AssemblyItemNo. PartNo. Description Quantity 7V3175CC-01 FrontCoverASSY 1 8V3107-01 Motor 1 9V3106-01 DriveBracket&SpringClip 1 10V3108 PCBoard 1 11V3110 DriveGear12x36 3 12V3109 DriveGearCover 1 13V3193-01 ServiceTool 1 14 V3186 Transformer110V-12V 1
DriveCapAssembly,DownflowPiston,UpflowPiston, Regenerant Piston and Spacer Stack Assembly
ItemNo. PartNo. Description Quantity 1 V3005 *SpacerStackAssemblywitho-rings 1 2 V3004 DriveCapAssembly 1 3 V3135 O-Ring228(useValveO-ringKit) 1 4 V3011 PistonDownflowAssembly 1 5 V3174 RegenerantPiston 1 6 V3180 O-Ring337(useValveO-ringKit) 1 15 V3105 O-Ring215(useValveO-ringKit) 1
t
tt
pV
VItem#5notusedwithBackwashOnlyfilterapplications.pItem#4identifiedwith“DN”code.
tSeepage20forValveO-ringKit.
“CMP & C” Series Automatic Water Conditioners
13
16
17
18
19
25a, 25b2423
22
20
30
2635
33
32
34
29
27
28
31
21�
�
�
Injector Cap, Injector Screen, Injector, Plug , O-Ring,RefillandRefillPortPlug, &Drain Line - 3/4”
Properflowwasherorientationdirectswaterflowtowardsthewasherfacewithroundededge.Flowwasherindentificationnumbersmustbevisibleafterinstallation.
t PartofKit,O-ring(Item#51,pg.20)
“CMP & C” Series Automatic Water Conditioners
14
DrawingNo. OrderNo. Description Quantity 21V3195-01 RefillPortPlugAssembly Thispartisrequiredforbackwashonlysystems 22H4615 ElbowLockingClip 1 23JCP-P-6 Polytubeinsert3/8 1 24JCPG-6PBLK Nut3/8 1 25aH4613 ElbowCap3/8(usew/3/8”tubing) 1 25bH4650 Elbow1/2”withnutandinsert(usew/1/2”tubing) Option 26V3163 O-Ring019(UseValveO-ringKit) 1 27V3165-01 RFCRetainerAssembly* 1 28 RFCBrineRefillFlowWasher 1*AssemblyincludesRFC.
RefillandRefillPortPlug
DrawingNo. OrderNo. Description Quantity 29H4615 ElbowLockingClip 1 30PKP10T58-BULK Polytubeinsert5/8 Option 31 V3192 Nut3/4DrainElbow Option 32 V3158-01 DrainElbow3/4MaleAssembly 1 33 V3163 O-Ring019(UseValveO-ringKit) 1 34 V3159-01 DrainFlowWasherRetainerAssembly 1 V3162-007 DrainFlowWasher0.7gpmfor3/4 V3162-010 DrainFlowWasher1.0gpmfor3/4 V3162-013 DrainFlowWasher1.3gpmfor3/4 V3162-017 DrainFlowWasher1.7gpmfor3/4 V3162-022 DrainFlowWasher2.2gpmfor3/4 V3162-027 DrainFlowWasher2.7gpmfor3/4 V3162-032 DrainFlowWasher3.2gpmfor3/4 V3162-042 DrainFlowWasher4.2gpmfor3/4 V3162-053 DrainFlowWasher5.3gpmfor3/4
35
OneDLFCmustbeusedif3/4fittingis
used
Drain Line - 3/4”
ItemNo. PartNo. Description Quantity 16 V3176 InjectorCap 1 17 V3152 O-Ring135(UseValveO-ringKit) 1 18 V3177 InjectorScreen 1 19V3010-1Z InjectorAssemblyZPlugSeenote 1 V3010-1A InjectorAssemblyABlack V3010-1B InjectorAssemblyBBrown V3010-1C InjectorAssemblyCViolet V3010-1D InjectorAssemblyDRed 20V3010-1E InjectorAssemblyEWhite V3010-1F InjectorAssemblyFBlue V3010-1G InjectorAssemblyGYellow V3010-1H InjectorAssemblyHGreen V3010-1I InjectorAssemblyIOrange V3010-1J InjectorAssemblyJLightBlue V3010-1K InjectorAssemblyKLightGreen
*Theinjectorplugandtheinjectoreachcontainone011(lower)and013(upper)o-ring.Note: Fordownflowbrine,injectorislocatedinthedownholeandinjectorplugintheuphole.
Forafilterthatonlybackwashesinjectorplugsarelocatedinbothholes.
1
Injector Cap, Injector Screen, Injector, Plug and O-Ring
t
t
t
“CMP & C” Series Automatic Water Conditioners
15
Parts Listing Part Number No. Description 1 Valve Metered (Complete - Specify Model) 2 Brine Tank w/ Cover 3 Brine Well 4 Brine Well Cap 5OverflowElbow 6 Brine Tube w/ Air Check 7 Brine Line Hose w/ Inserts 8 Brine Valve Safety 9 Brine Float -- Media (Specify Model) 11 Distributor Tube Assembly - Specify Model 12 Media Tank Jacket w/ cover - Optional 13 * Brine Valve Assembly - Complete - Includes #’s 6, 8, & 9 15 *Grid (Optional)
Brine Valve
AssemblyMedia Tank Jacketw/ Cover
Media TankBase
Media Tank
Valve (Metered Shown)
Brine Tank Cover
Brine Tank
Brine Grid(Optional)
Brine Tubew/ Air Check
Brine Well
Brine Line Hosing
Brine Well Caps
Brine Valve Safety
Overflow Drain
MediaDistributor Tubew/ Screen
1
2
2
11
10
10
15
12
3
5
8
6
7
4
“C” Series
9Brine Float
13
8
6 BrineTubew/Air Check
Brine ValveSafety
“CMP & C” Series Automatic Water Conditioners
16
ItemNo. PartNo. Description Quantity 36 V3151 Nut1”QuickConnect 1*37 V3003 MeterAssembly 1 38 V3118-01 TurbineAssembly 1 39 V3105 O-Ring215(UseValveO-ringKit) 1 40 V3003-01 MeterPlugAssembly(Timeclockoption) 1*Item#37includesItems#38'.
Water Meter and Meter Plug
t
39
40
37
36
38
t
PartofKit,O-ring(Item51,pg.20)
“CMP & C” Series Automatic Water Conditioners
17
(NotShown)DescriptionBypassVerticalAdapterAssembly
ItemNo. PartNo. Description Quantity 41 V3151 Nut1”QuickConnect 2 42 V3150 SplitRing 2 43 V3105 O-Ring215(Kitavailable-seeItem#10) 2 44 V3145 Bypass1”Rotor 2 45 V3146 BypassCap 2 46 V3147 BypassHandle 2 47 V3148 BypassRotorSealRetainer 2 48 V3152 O-Ring135(useBypassValveKit) 2 49 V3155 O-Ring112(useBypassValveKit) 2 50 V3156 O-Ring214(useBypassValveKit) 2
52 KITO-ringBypass (Incl. 2 ea. of items 43,48,49,& 50) 1 per valve Bypass Valve O-ring Kitl
l
l
l
l
lPartofKit,O-ringBy-Pass(Item52)
51 KITO-ring(contains1eachof3,6,15,17,26,&33)1pervalveValve O-ring Kits
53 A23540231 BypassValveComplete/LessConnectors 1 per valve Complete Assembly
46
4546
5
49
48
44
50
47
41
42
43
41
4243
47
50
44
48
49
l
l l
l
l l
l
l
53
“CMP & C” Series Automatic Water Conditioners
18
Order No: V3007 (Standard)Description: Fitting1”PVCMaleNPTElbowAssembly
DrawingNo.OrderNo. Description Quantity1 V3151 Nut1”QuickConnect 22 V3150 SplitRing 23 V3105 O-Ring215 24 V3149 Fitting1”PVCMaleNPTElbow 2
Order No: V3007-01 (Optional)Description: Fitting 3/4” & 1” PVC Solvent 900 Asy
DrawingNo.OrderNo. Description Quantity1 V3151 Nut1”QuickConnect 22 V3150 SplitRing 23 V3105 O-Ring215 24 V3189 Fitting3/4&1PVCSolvent90 2
Order No: V3007-03 (Optional)Description: Fitting3/4”BrassSweatAssembly
DrawingNo. OrderNo. Description Quantity1 V3151 Nut1”QuickConnect 22 V3150 SplitRing 23 V3105 O-Ring215 24 V3188-01 Fitting3/4”BrassSweat 2
Order No: V3007-02 (Optimal)Description: Fitting1”BrassSweatAssembly
DrawingNo. OrderNo. Description Quantity1 V3151 Nut1”QuickConnect 22 V3150 SplitRing 23 V3105 O-Ring215 24 V3188 Fitting1”BrassSweat 2
“CMP & C” Series Automatic Water Conditioners
19
Table 15Troubleshooting Procedures
Problem PossibleCause Solution
1. Timerdoesnotdisplaytimeofday
2. Timerdoesnotdisplaycorrecttimeofday
3. Nosoftening/filteringdisplaywhenwaterisflowing
4. Controlvalveregeneratesatwrongtimeofday
5.ERRORfollowedbycodenumber1001ErrorCode- Unabletorecognizestart ofregeneration1002ErrorCode- Unexpected stall1003ErrorCode- Motorrantolong,timed outtryingtoreachnext cycleposition1004ErrorCode- Motorrantolong,timedout tryingtoreachhome positionIfotherErrorCodesdisplaycontactthefactory
ERROR Reset Procedure: 1. Correct error condition.2.PressNEXTand REGENsimultaneously forthreeseconds.
a. Transformerunpluggedb. Noelectricpoweratoutletc. Defective transformerd. DefectivePCboarda. Switchedoutletb. Poweroutagec. DefectivePCboarda. Bypassvalveinbypasspositionb. Meterconnectiondisconnectedc. Restricted/stalledmeterturbine
d. Defective metere. DefectivePCboarda. Poweroutages
b. Timeofdaynotsetcorrectlyc. Timeofregenerationincorrectd. Controlvalvesetat“on0”
(immediateregeneration)e. Control valve set at NORMAL +
on0a. Controlvalvehasjustbeenser-
viced
b. Foreignmatterislodgedincontrolvalve
c. Highdriveforcesonpiston
d. Controlvalvepistonnotinhomeposition
e. Motornotinsertedfullytoengagepinion,motorwiresbrokenordisconnected,motorfailure
f. Drivegearlabeldirtyordamaged,missingorbrokengear
g. Drivebracketincorrectlyalignedtobackplate
h. PCboardisdamagedordefective
i. PCboardincorrectlyalignedtodrivebracket
a. Connect powerb. Repairoutletoruseworkingoutletc. Replace transformerd. ReplacePCboarda. Use uninterrupted outletb. Resettimeofdayc. ReplacePCboarda. Putbypassvalveinservicepositionb. ConnectmetertoPCboardc. Removemeterandcheckforrotation
orforeignmateriald. Replace metere. ReplacePCboarda. Reset control valve to correct time of
dayb. Resettocorrecttimeofday(a.m./p.m.)c. Resetregenerationtime(a.m./p.m.)d. Checkcontrolvalveset-upprocedure
regenerationtimeoptione. Checkcontrol.valveset-upprocedure
regenerationtimeoptiona. PressNEXTandREGENfor3
secondsorunplugpowersourcejack(blackwire)andplugbackintoresetcontrol valve
b. Checkpistonandspacerstackas-semblyforforeignmatter
c. Replace piston(s) and spacer stack assembly
d. PressNEXTandREGENfor3secondsorunplugpowersourcejack(blackwire)andplugbackintoresetcontrol valve
e. Checkmotorandwiring.Replacemotorifnecessary
f. Replaceorcleandrivegear(s)
g. Reseatdrivebracketproperly
h. ReplacePCboard
i. EnsurePCboardiscorrectlysnappedontodrivebracket
“CMP & C” Series Automatic Water Conditioners
20
Troubleshooting Procedures(continued)
Problem PossibleCause Solution
6. Control valve stalled in regeneration
7. Control valve does not regenerateautomaticallywhenREGENbuttonisdepressedandheld
8. Control valve does not regenerateautomaticallybutdoeswhenREGENbuttonisdepressed
9 Timeofdayflashesonandoff
a. Motornotoperatingb. Noelectricpoweratoutletc. Defective transformerd. DefectivePCboarde. Brokendrivegearordrivecap
assemblyf. Broken piston retainerg. Brokenmainorregenerantpistona. Transformerunpluggedb. Noelectricpoweratoutletc. Brokendrivegearordrivecap
assemblyd. DefectivePCboarda. By-passvalveinbypasspositionb. Meterconnectiondisconnectedc. Restricted/stalledmeterturbine
d. Defective metere. DefectivePCboardf. Set-up errora. Powerhasbeenoutmorethan
twohours,thetransformerwasunpluggedandthenpluggedbackintothewalloutlet,thetransformerplugwasunpluggedandthenpluggedbackintotheboardortheNEXTandREGENbuttonswerepressedtoresetthevalve.
a. Replace motorb. Repairoutletoruseworkingoutletc. Replace transformerd. ReplacePCboarde. Replacedrivegearordrivecapas-
semblyf. Replacedrivecapassemblyg. Replacemainorregenerantpistona. Connect transformerb. Repairoutletoruseworkingoutletc. Replacedrivegearordrivecapas-
semblyd. ReplacePCboarda. Put control valve in service positionb. ConnectmetertoPCboardc. Removemeterandcheckforrotation
orforeignmateriald. Replace metere. ReplacePCboardf. Checkcontrolvalveset-upprocedurea.. Resetthetimeofday