Applications & Tools

Answers for industry.

Cover

Joint Configuration with WinCC (TIA Portal) and STEP 7 V5.x

WinCC Basic, Comfort, Advanced and STEP 7 V5.x

Application Description November 2013

Page 2: Applications & Tools - infoPLC

2 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

Siemens Industry Online Support This article is taken from the Siemens Industry Online Support. The following link leads you to the download page for this document: http://support.automation.siemens.com/WW/view/en/73502293 Caution: The functions and solutions described in this entry predominantly confine themselves to the realization of the automation task. Please furthermore take into account that corresponding protective measures have to be taken in the context of industrial security when connecting your equipment to other parts of the plant, the enterprise network or the Internet. For more information, please refer to entry ID 50203404. http://support.automation.siemens.com/WW/view/en/50203404

Page 3: Applications & Tools - infoPLC

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 3

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

s

SIMATIC WinCC (TIA Portal) and STEP 7 V5.x

Task 1

Solution 2

Configuration and Project Engineering

3

Literature 4

History 5

Page 4: Applications & Tools - infoPLC

Warranty and Liability

4 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

Warranty and Liability

Note The Application Examples are not binding and do not claim to be complete regarding the circuits shown, equipping and any eventuality. The application examples do not represent customer-specific solutions. You are responsible for ensuring that the described products are used correctly. These application examples do not relieve you of the responsibility to use safe practices in application, installation, operation and maintenance. When using these application examples, you recognize that we cannot be made liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these Application Examples at any time without prior notice. If there are any deviations between the recommendations provided in this Application Example and other Siemens publications – e.g. Catalogs – the contents of the other documents shall have priority.

We do not accept any liability for the information contained in this document. Any claims against us – based on whatever legal reason – resulting from the use of the examples, information, programs, engineering and performance data etc., described in this Application Example shall be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German Product Liability Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of fundamental contractual obligations (“wesentliche Vertragspflichten”). The damages for a breach of a substantial contractual obligation are, however, limited to the foreseeable damage, typical for the type of contract, except in the event of intent or gross negligence or injury to life, body or health. The above provisions do not imply a change of the burden of proof to your detriment. Any form of duplication or distribution of these application examples or excerpts hereof is prohibited without the expressed consent of Siemens Industry Sector.

Page 5: Applications & Tools - infoPLC

Preface

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 5

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

Preface Objective of the Application

The application describes how you can use STEP 7 V5.x and WinCC (TIA Portal) together to create a joint configuration.

Main topics of this application The following main topics are dealt with in this application: Data exchange between a project created with STEP 7 V5.x and an HMI operator panel created in the TIA Portal via…

– WinCC TagConverter – Source import – Project migration

Validity WinCC flexible 2008 SP3 STEP 7 V5.x From WinCC (TIA Portal) V12

Page 6: Applications & Tools - infoPLC

Table of Contents

6 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

Table of Contents Warranty and Liability ................................................................................................. 4 Preface .......................................................................................................................... 5 Table of Contents ......................................................................................................... 6 1 Task ..................................................................................................................... 7 2 Solution............................................................................................................... 9

2.1 WinCC TagConverter ........................................................................... 9 2.2 Source export and source import ....................................................... 10 2.3 Project migration ................................................................................ 11 2.4 Description of the core functionality ................................................... 12 2.5 Hardware and software components ................................................. 13

3 Configuration and Project Engineering ......................................................... 14 3.1 WinCC TagConverter ......................................................................... 14 3.1.1 General info ........................................................................................ 14 3.1.2 Create new converter template .......................................................... 16 3.1.3 Open existing converter template ...................................................... 18 3.2 Source export/source import .............................................................. 20 3.2.1 Preparatory actions ............................................................................ 20 3.2.2 Source export ..................................................................................... 20 3.2.3 Source import ..................................................................................... 26 3.3 Project migration ................................................................................ 33 3.3.1 Partial project migration ...................................................................... 33 3.3.2 Complete project migration ................................................................ 34

4 Literature .......................................................................................................... 40 5 History............................................................................................................... 40

Page 7: Applications & Tools - infoPLC

1 Task 2.1 WinCC TagConverter

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 7

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

1 Task Introduction

The TIA Portal offers the option to create the PLC program and the HMI configuration via software interface including all of the resulting advantages. However, in some cases, it is necessary to continue to create the PLC program with the “STEP 7 V5.x” software and the HMI configuration with the “WinCC (TIA Portal)” software due to technical or customer-specific reasons.

Overview of the automation task The figure below provides an overview of the automation task.

Figure 1-1

STEP 7 V5.x

TP1200 Comfort PanelWinCC (TIA Portal)

Tag handling?

Description of the automation task Case 1 The PLC program shall be created with the SIMATIC Software STEP 7 V5.x and the HMI project with the WinCC (TIA Portal) software. Data exchange between STEP 7 program and HMI operator panel is performed via “data blocks”. Tag handling shall be possible as in the case of a WinCC flexible project integrated in STEP 7.

Page 8: Applications & Tools - infoPLC

1 Task 2.1 WinCC TagConverter

8 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

Case 2 You have an existing STEP 7 project with an integrated MP277 Touch that was created with the WinCC flexible 2008 SP3 project. This MP277 Touch is to be replaced by a SIMATIC TP1200 Comfort Panel. Data exchange between STEP 7 program and HMI operator panel is performed via “data blocks”. Tag handling shall be possible as in the case of a WinCC flexible project integrated in STEP 7.

Page 9: Applications & Tools - infoPLC

2 Solution 2.1 WinCC TagConverter

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 9

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

2 Solution There are several options to implement the tasks.

2.1 WinCC TagConverter

Display An output file containing the selected STEP 7 tag is generated with WinCC TagConverter. This output file is imported into WinCC (TIA Portal). The imported STEP 7 tags can then be used in the usual way. Figure 2-1

Converter file

Import

WinCCTagConverter

WinCC (TIA Portal)

Page 10: Applications & Tools - infoPLC

2 Solution 2.2 Source export and source import

10 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

2.2 Source export and source import

Display Selected data blocks are merged in a file (STL source) → source export. Read-in of the file (STL source) into the TIA Portal → source import. Figure 2-2

Source export

Source import

STEP 7 V5.x

WinCC (TIA Portal)

The source export and source import always offers itself when you are using STEP 7 V5.x for the PLC program and WinCC (TIA Portal) for the HMI configuration. If you are making any changes to the data blocks in the STEP 7 project that concern the HMI operator panel, you can update these changes or expansions with the help of the “source export/source import” function with the WinCC (TIA Portal) project.

Page 11: Applications & Tools - infoPLC

2 Solution 2.3 Project migration

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 11

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

2.3 Project migration

Display Migration of a WinCC flexible 2008 SP3 project or migration of a STEP 7 V5.x project including HMI configuration into the TIA Portal. Figure 2-3

STEP 7 V5.x

TIA Portal V12

Migrate project

The project migration offers itself if you have an existing STEP 7 V5.x project including an integrated WinCC flexible 2008 SP3 configuration and you want to exchange the existing HMI operator panel, for example, for a SIMATIC Comfort Panel. The TIA Portal offers the option to migrate the STEP 7 V5.x configuration including the WinCC flexible 2008 SP3 configuration into the TIA Portal. Alternatively, you can also copy the existing WinCC flexible 2008 SP3 configuration from the STEP 7 project and subsequently migrate it to WinCC (TIA Portal). The STEP 7 V5.x project remains unchanged here. If any changes are subsequently performed in the STEP 7 V5.x project which concern the HMI operator panel, you have to make these changes “manually” in the WinCC (TIA Portal) project. Instead of a “manual” adjustment, it is recommended to use the “source export/source import” function. For this purpose, please refer to chapter 2.1.

Page 12: Applications & Tools - infoPLC

2 Solution 2.4 Description of the core functionality

12 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

Topics not covered This application does not include a description of… • the configuration interface of STEP 7 V5.x. • the configuration interface of TIA Portal. • the HMI operator panels used. Basic knowledge of these topics is assumed. If required, please refer to the appropriate manuals (see chapter 4).

Assumed knowledge For the implementation of the presented solutions, no particular knowledge is necessary. Basic knowledge of the configuration interface of STEP 7 V5.x and the TIA Portal is assumed.

2.4 Description of the core functionality

The core functionality is the description of how to use STEP 7 V5.x and the WinCC (TIA Portal) together. Various tag handling options are described here.

Note Generally, WinCC TagConverter provides the best tag handling option.

The following points are described in the application. • WinCC TagConverter

– Presentation of the WinCC TagConverter. Description of how to import tags of a STEP 7 V5.x project to WinCC (TIA Portal). A video entry on how to handle the TagConverter is also available under the following link http://support.automation.siemens.com/WW/view/en/56078300

• Source export / source import – Description of the individual steps in order to import the content of the data

blocks from the STEP 7 V5.x configuration into the TIA Portal. • Project migration

– Description of how you can migrate a STEP 7 V5.x project with integrated HMI operator panel into the TIA Portal.

Page 13: Applications & Tools - infoPLC

2 Solution 2.5 Hardware and software components

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 13

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

2.5 Hardware and software components

This application has been generated with the following components:

Hardware components Table 2-1

Component No. Order number Note

CPU S7-300 CPU 317-2 PN/DP

1 6ES7 317-2EK14-0AB0

MP 277 Touch 1 6AV6643-7CD00-0CJ1 TP1200 Comfort Panel 1 6AV2124-0MC01-0AX0

Standard software components Table 2-2

Component No. Order number Note

STEP 7 V5.5 1 6ES7810-4CC10-0YA5

Possible from STEP 7 V5.4 onward

WinCC flexible 2008 SP3

1 6AV6613-0AA51-3CA5

Possible from WinCC flexible SP2 onward.

WinCC V12 Advanced 1 6AV2102-0AA01-0AA5

From WinCC V12 Basic onward. Depending on the operator panel used.

STEP 7 Professional V12

1 6ES7822-1AA01-0AY5

From STEP 7 Basic V12 onward. Depending on the controller used.

WinCC TagConverter 1 Download http://support.automation.siemens.com/WW/view/en/56078300

Example file: The following list includes all files used in this example.

Table 2-3

Component Note

73502293_WinCC_TIA_STEP7_V5_DOKU_v20_en.pdf This document.

Page 14: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.1 WinCC TagConverter

14 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

3 Configuration and Project Engineering 3.1 WinCC TagConverter

Using the WinCC TagConverter, the data blocks or the system library required for data exchange between SIMATIC controller and HMI control panel are combined in a convertor file. The convertor file is then read via the integrated import function of WinCC (TIA Portal).

Note A video entry on how to handle the TagConverter is also available under the following link http://support.automation.siemens.com/WW/view/en/56078300

3.1.1 General info

Installation of the “TagConverters” Start the installation of “TagConverters” by double-clicking on the “setup.msi” file and follow the installation routine. In “Start > Siemens Automation > Options and Tools > HMI Tools >” you can the call up the TagConverter.

Start screen The two following functions can be executed via the screen. • Create new converter template • Open existing converter template Figure 3-1

Page 15: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.1 WinCC TagConverter

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 15

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

Create new converter template If you wish to import tags into WinCC (TIA Portal) from the used STEP 7 V5.x project for the first time, you use the “Create a new converter template” function.

Open existing converter template You have already created a converter file from the used STEP 7 V5.x project and then made changes in the STEP 7 project affecting the HMI operator panel. In this case, you use the “Open an existing converter template” function. Various basic settings, such as the previously selected STEP 7 project file, the task of the HMI connection name, etc. are in this case already preset and need not be assigned again.

Starting point • An existing STEP 7 V5.x configuration. • A WinCC (TIA Portal) configuration.

Page 16: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.1 WinCC TagConverter

16 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

3.1.2 Create new converter template

Table 3-1

No. Action Screens

1. Calling the functions • Start the TagConverter and, in the start screen, click on the “Create a new converter

template” button.

2. Select converter file

• Template

Create “template file”. The file saves the performed settings.

• Import file (Source data) Selection of the STEP 7 V5.x project file (*.s7p), from which the tag shall be imported into WinCC (TIA Portal).

• “Create” button This button is used for creating the “converter template”.

Page 17: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.1 WinCC TagConverter

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 17

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

3. Converter template • Selected objects

Here you select the controller(s). Select the tags of the marked controller to be exported.

• Conversion settings Here you enter the exact HMI connection name. The name must be identical with the connection created in WinCC (TIA Portal). – Optional: “Editing language in TIA Portal”

The language in which comments shall be imported into the WinCC project.

– Optional: “Include station name in tag/symbol name” When this option is activated, all exported symbols are preceded by the control name. This makes the symbols unique, even when different control systems are using identical symbol names.

• Output file (Output data) Specification of a storage path for the conversion file.

• “Convert” button

Pressing the button starts the conversion.

4. Importing data into WinCC (TIA Portal).

• In the WinCC (TIA Portal) configuration you open the tag editor (display all tags). • Click on the symbolic “Import” button and then select the previously saved “Conversion file”

via the dialog window. • Perform the “Import”.

Page 18: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.1 WinCC TagConverter

18 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

3.1.3 Open existing converter template

Table 3-2

No. Action Screens

1. Calling the functions • Start the TagConverter and, in the start screen, click on the “Open an existing converter

template” button. • Pressing the button opens a dialog screen which takes you to the stored “template file”.

Page 19: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.1 WinCC TagConverter

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 19

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

2. Converter template The “template file” enables you to call the previously made settings again. If necessary, adjust the settings (e.g. selecting or unselecting of marked tags in “Selected objects”. • “Convert” button

Pressing the button starts the conversion.

3. Importing data into WinCC (TIA Portal)

• In the WinCC (TIA Portal) configuration you open the tag editor (display all tags). • Click on the symbolic “Import” button and then select the previously saved “Conversion file”

via the dialog window. • Perform the “Import”.

Page 20: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

20 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

3.2 Source export/source import

During source export, data blocks from the STEP 7 program that are required for the data exchange between the SIMATIC controller and the HMI operator panel (STL source) are merged to one file.

3.2.1 Preparatory actions

• In order to insert the created file (STL source) into the WinCC (TIA Portal) configuration, the WinCC (TIA Portal) configuration has to include a SIMATIC controller. The SIMATIC controller (“dummy CPU”) has no other “jobs” Note: The CPU used, does not have to match the CPU used in STEP 7 V5.x.

• For the tag handling later on, a connection to the “dummy CPU” used should be configured in the WinCC (TIA Portal) project. The individual connection parameters should match the CPU used in STEP 7 V5.x.

3.2.2 Source export

Starting point

• An existing STEP 7 V5.x configuration. • A WinCC (TIA Portal) configuration that includes a SIMATIC controller.

Procedure

Table 3-3

No. Action Screens

1. STEP 7 V5.x project The screen shot shows the STEP 7 V5.x project with the three data blocks.

Page 21: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 21

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

2. Generate Source… Open any program or data block. In this example: data block “DB10” Note: Once you have processed “DB10”, save the changes first of all. Select the “File > Generate Source…” menu option in the opened “DB10”. A window opens up in which you specify the object name for the file to be generated (STL source).

Page 22: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

22 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

3. Window, specifying object name Specify an object name for the source to be created. In this example: “HMI_DataBlock” Confirm the entry with “OK”. A window opens up via which you can create a file (STL source). Note: If you have already carried out a “source export” in the project, you can use an existing object name another time. In this example: “HMI_DataBlock” The advantage is that the name of the file created later (STL source) stays the same. By confirming the entry with “OK”, a message is displayed that the object already exists. By confirming the message with “Yes” the window for creating file (STL source) opens up.

Page 23: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 23

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

4. Generating file (STL source) “Blocks not selected” box Several available program blocks are listed in the box. Select all data blocks that are to be “merged” as a file (STL source). In this example the data blocks “DB10” and “DB20” were selected. “Arrow button→” Via the “ → ” arrow button the selected data blocks are transferred into the “Blocks Selected” box. “Addresses” Select the “Symbolic” option here. Confirm the entries with “OK”.

Page 24: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

24 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

Note: Once you have selected a data block via which you have called the menu for generating the file (STL source) you will receive the following message. Please read the message. To continue the action, confirm the message with “Yes”. The file (STL source) is generated.

5. Viewing the created file (STL source)

The screen shot shows the created file (STL source) “HMI_DataBlock” under the “Sources” folder. “DB10” can be closed again.

Page 25: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 25

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

6. Storage path of the STL source In order to have the storage path of the STL source displayed, proceed as follows. Open the properties of the “HMI_DataBlock” file.

Select the “Source File” tab. The name of the file and the storage path are displayed. The default path is: …:\project file\s7asrcom\00000001 Tip: Select the complete storage path with the mouse and copy the name.

Page 26: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

26 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

3.2.3 Source import

Source import, example 1 Starting point • An existing TIA Portal configuration with an HMI project and a SIMATIC

controller (“dummy CPU” → see chapter 3). • In the “Program blocks” folder there are yet no data blocks that have been

updated with the existing data blocks in the STEP 7 V5.x project. (in contrast to “Source import, example 2”, were data blocks already exist).

Procedure

Table 3-4

No. Action Screens

1. Importing the STL source • Open the TIA Portal configuration • Open the STEP 7 project folder via the project navigation.

– Open the “External sources” folder. – By double clicking “Add new external file” a Window’s window is opened. – Navigate to the “STL source” window that you would like to import. Where the storage

path of the STL source is located, was described above →…:\project file\s7asrcom\00000001.

In this example the “00000002.AWL” file is selected. Tip: In the “file name” box you can paste the previously copied name of the “storage path” (in this example: E:\Project_\s7asrcom\00000001 You will then get directly to the folder that contains the STL source.

Page 27: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 27

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

2. Generating STL source The screen shot shows the imported “00000002.AWL” STL source. • Right click the file. A context menu opens. • Here, select the “Generate blocks from source” function. A message will appear once you

made your selection.

Message Please read the message. If the blocks are to be generated, click the “Yes” button.

Page 28: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

28 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

3. Viewing the generated data blocks The screen shot below shows the generated data blocks. If no data blocks with the same name existed before importing the tags in this case, only the name of the data blocks is adopted. The respective data block number has to be adjusted manually in this case. In this example the DB numbers “DB1” or “DB2” were automatically assigned to the data blocks.

4. Adjusting data block number

Adjust the DB number as follows. Open the properties of the data block and adjust the number according to the specifications from the “STEP 7 V5.x Project”. Confirm the entry with “OK”.

Page 29: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 29

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

5. HMI tag folder The PLC connection makes it possible to browse the tags of STEP 7 data blocks as usual.

Page 30: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

30 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

Source import, example 2 Starting point • An existing TIA Portal configuration with an HMI project and a SIMATIC

controller (“dummy CPU” → see chapter 3.1). • In the “Program blocks” folder already contains data blocks that are to be

updated with the existing data blocks in the STEP 7 V5.x project.

Procedure Table 3-5

No. Action Screens

1. Importing the STL source • Open the TIA Portal configuration • Open the STEP 7 project folder via the project navigation.

– Open the “External sources” folder. – By double clicking “Add new external file” a Window’s window is opened. – Navigate to the “STL source” window that you would like to import. Where the storage

path of the STL source is located, was described above →…:\project file\s7asrcom\00000001.

In this example the “00000002.AWL” file is selected. Tip: In the “file name” box you can paste the previously copied name of the “storage path” (in this example: E:\Project_\s7asrcom\00000001 You will then get directly to the folder that contains the STL source.

Page 31: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 31

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

2. Generating STL source The screen shot shows the imported “00000002.AWL” STL source. • Right click the file. A context menu opens. • Here, select the “Generate blocks from source” function. A message will appear once you

made your selection.

Message Please read the message. If the blocks are to be generated, click the “Yes” button.

Page 32: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.2 Source export/source import

32 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

3. Viewing the generated data blocks The screen shot below shows the existing data blocks The existing data blocks “DB10” and “DB20” have been replaced by the two generated data blocks 1:1.

4. HMI tag folder

The PLC connection makes it possible to browse the tags of STEP 7 data blocks as usual. If, for example, the addresses of the tags have changed they are automatically adjusted by the symbolic linking of the HMI tags.

Page 33: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.3 Project migration

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 33

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

3.3 Project migration

Depending on the initial situation, migrate the complete STEP 7 project including HMI configuration into the TIA Portal or only migrate the HMI configuration to WinCC (TIA Portal).

3.3.1 Partial project migration

In some cases it makes sense not to migrate the entire STEP 7 project including the HMI configuration into the TIA Portal. This may, for example, be the case when the hardware you use in the STEP 7 V5.x project is not supported by the TIA Portal. In cases like this it is advisable, for example, to only migrate the HMI configuration into the TIA Portal. Starting point • STEP 7 configuration with integrated WinCC flexible 2008 SP3 configuration

(e.g. MP 277 Touch project). • The WinCC flexible operator panel was copied from STEP 7 and

migrated into the TIA Portal. A detailed description can be found in entry ID 54695062.

Below is a brief description of how to proceed.

Brief description

Table 3-6

No. Action

1. WinCC Flexible Project migration Copy the WinCC flexible configuration from the STEP 7 V5.x project in the first step and subsequently only migrate the WinCC flexible 2008 SP3 configuration into the TIA Portal project.

2. Tag handling If you are performing any expansions or changes in the STEP 7 V5.x project that also affect the HMI operator panel than you can make the expansions or changes manually in the HMI project. Alternatively, use the “source export / source import” function (see chapter 3.1).

Page 34: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.3 Project migration

34 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

3.3.2 Complete project migration

The brief instruction describes how you can migrate a STEP 7 project with an integrated WinCC flexible 2008 SP3 project into the TIA Portal. Details on this issue can be found in entry ID 54695062. Starting point • STEP 7 configuration with integrated WinCC flexible 2008 SP3 configuration

(e.g. MP 277 Touch project). • The hardware used in the STEP 7 project is also available in the TIA Portal

hardware catalog. Table 3-7

No. Action Screens

1. STEP 7 V5.x project The screen shot shows the generated STEP 7 configuration with the data blocks and the HMI configuration.

Notes: • For this example, the project does not include a special STEP 7 program for controlling an

application. • For migrating the configuration into the TIA Portal, the application must be closed.

Page 35: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.3 Project migration

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 35

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

2. Migrating the STEP 7 V5.x project into the TIA Portal • Open the portal view of the TIA Portal. • Select the "Start > Migrate project" action (1) • Select the STEP 7 project that is to be migrated via the “source path” box. For this purpose,

open the respective project folder and select the file with the file ending “*. s7p” (2). • Select the “Include hardware configuration” option (3). • Enter a project name and a storage location (4). • Click the “Migrate” (5) button. The project is migrated into the TIA Portal.

12

5

3

4

Page 36: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.3 Project migration

36 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

3. Viewing migrated STEP 7 project The screen shot shows the migrated STEP 7 project with the MP 277 Touch.

4. Exchanging the operator panel

Preparing measures: Certain properties of the images can be preassigned under the “Оptions > Settings > Visualization > Resize screen” menu command. In this example: • Fit to height. • Align center. Information on the individual points can be found in the Online help. Search term: “Fit objects to contents” Further information can be found in the “Comfort Panels Migration Guide” manual under chapter “Switching screen from 4:3 to Widescreen”. The manual can be downloaded under the following entry ID. 49752044.

Page 37: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.3 Project migration

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 37

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

5. Changing the device version • Open the device configuration of the HMI operator panel in the project navigation via double

click (1). • Select one of the three buttons (2).

– Topology view – Network view – Device view

• Select the HMI object (3). • Select the “Properties” tab (4). • Under the “General” item you find the “Change device/version” button (5). Click the “Change device/version” button. The “Change device” dialog box is opened.

1

2

3

4

5

Page 38: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.3 Project migration

38 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

6. Dialog box: Change device • Current device (1): • New device: (2):

you can select an HMI operator panel or PC system via the drop-down menu. • Compatibility information (3):

output of compatibility information. Once you have selected the HMI operator panel, confirm the selection with the “OK” button. The device exchange is started. In this example the TP1200 Comfort was selected.

1

2

3

Page 39: Applications & Tools - infoPLC

3 Configuration and Project Engineering 3.3 Project migration

WinCC (TIA Portal) and STEP 7 V5.x V2.0, Entry ID: 73502293 39

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

No. Action Screens

7. Adjusting a name If required, adjust the name of the HMI operator panel to avoid possible confusion. Right click the name of the HMI operator panel in the project navigation. A context menu opens. Then select the “Rename F2” option. The device exchange is now completed.

8. WinCC flexible configuration in the STEP 7 V5.x project After successful migration of the STEP 7 V5.x project into the TIA Portal, the HMI project is no longer required in the existing STEP 7 V5.x project. The processing of the HMI configuration is now only in the TIA Portal. Make sure to avoid confusions regarding the HMI configurations.

Page 40: Applications & Tools - infoPLC

4 Literature

40 WinCC (TIA Portal) and STEP 7 V5.x

V2.0, Entry ID: 73502293

Cop

yrig

ht

Sie

men

s AG

201

3 Al

l rig

hts

rese

rved

4 Literature

Internet links This list is not complete and only represents a selection of relevant information Table 4-1

Subject Title

\1\ Reference to this document

http://support.automation.siemens.com/WW/view/en/73502293

\2\ Siemens Industry Online Support

http://support.automation.siemens.com

\3\ Software TagConverter for WinCC (TIA Portal) http://support.automation.siemens.com/WW/view/en/56078300

\4\ FAQ How to migrate a project integrated in STEP 7 from WinCC flexible to WinCC (TIA Portal)? http://support.automation.siemens.com/WW/view/en/54695062

\5\ Manual SIMATIC HMI operator panels migration guide Comfort Panels http://support.automation.siemens.com/WW/view/en/49752044

\6\ Manual WinCC Advanced V12.0 http://support.automation.siemens.com/WW/view/en/68075405

5 History Table 5-1

Version Date Modifications

V1.0 07/2013 First version V2.0 11/2013 TagConverter added


Top Related