Download - CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN
![Page 1: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/1.jpg)
CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN 23 & 24 AUGUSTUS 2016 – Patrick Hagen
![Page 2: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/2.jpg)
ECOLOGIE ECONOMIE HVAC-SECTOR
BUSINESS AS USUAL
Eu-richtlijnen, Ecodesign, EPB àverplichtingen, andere aanpak, nieuwe systemen
CONSUMENT
COMFORT OP DE EERSTE PLAATS
Duurzaamheid & ecologie = filosofie. Doet enkel verplichte investering.
GEBREK AAN OVERHEIDSINITIATIEVEN KORTE TERMIJN-DENKEN VERKEERDE PERCEPTIE
![Page 3: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/3.jpg)
Comfort
Budget
Duurzaamheid
![Page 4: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/4.jpg)
DUURZAAMHEID EFFICIENTIE COMFORT
HYDRAULISCH CONCEPT COMPONENTSELECTIE INREGELING HAALBARE BUDGETTEN
SYSTEEMOPTIMALISATIE
![Page 5: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/5.jpg)
DUURZAAM INGEREGELDE INSTALLATIES
HOOGST MOGELIJK COMFORT
LAAGST MOGELIJK VERBRUIK
HOOGST MOGELIJK RENDEMENT
![Page 6: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/6.jpg)
WAAROM INREGELEN?
INSTALLATIE IN ONBALANS • HOOG ENERGIEVERBRUIK • MOGELIJK KOUDE RUIMTES • SLECHT COMFORT
• LAAG ENERGIEVERBRUIK • HOOG COMFORT
NIET INGEREGELD
INGEREGELD
![Page 7: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/7.jpg)
SYSTEEMOPTIMALISATIE WHAT’S IN IT FOR YOU?
EINDGEBRUIKER
• COMFORT • DUURZAME EN EFFICIËNTE
INSTALLATIE • ZEER KORTE TERUGVERDIENTIJD • KLEINE INVESTERING
INSTALLATEUR
• SOLIDE BASIS VAN CONCEPT • COMPONENTSELECTIE IN DETAIL • MINIMALE FOUTMARGE • OPSPOORBARE STORINGEN
Systeemoptimalistie is beste oplossing naargelang de wens van de klant, volgens budget, waarbij foutenmarges in de uitvoering ervan geminimaliseerd worden.
![Page 8: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/8.jpg)
BASISTHEORIE INREGELEN
KV-WAARDE ▪ Geleidingsvermogen klep Kv-waarde ▪ Tegenovergestelde van weerstand
▪ Geeft het debiet aan waarbij een drukverschil van 100 kPa (1 bar) ontstaat
▪ Uitgedrukt in m3/h
▪ Temperatuur water: tussen 5°C en 40°C (gewoonlijk 15-16°C)
▪ Speciaal geval van Kv-waarde ▪ Geeft het debiet aan bij de volledig geopende klep
waarbij een drukverschil van 100 kPa (1 bar) ontstaat ▪ Uitgedrukt in m3/h
▪ Temperatuur water: tussen 5°C en 40°C (gewoonlijk 15-16°C)
KVS-WAARDE
G = [m3/h] Debiet Δp =[bar] Drukverschil Kvs = [m3/h] Hydraulische kenmerken van het ventiel
![Page 9: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/9.jpg)
![Page 10: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/10.jpg)
![Page 11: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/11.jpg)
BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // KV-WAARDE
![Page 12: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/12.jpg)
BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // CIRCUIT CURVE
![Page 13: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/13.jpg)
BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // KLEPKARAKTERISTIEK
Lineair gedrag indien Δpklep = constant
![Page 14: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/14.jpg)
BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // KLEPKARAKTERISTIEK
Lineair gedrag indien Δppomp = constant en ∆pklep ≠ constant klepautoriteit β (reactie debiet op gedrag van klep)
Stel: Klep sluit, debiet verkleint
∆Ppomp = ∆Prest + ∆P klep
cte ↘ ↗
![Page 15: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/15.jpg)
![Page 16: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/16.jpg)
BASISTHEORIE POMPGEGEVENS // VERSCHUIVING WERKINGSPUNT
![Page 17: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/17.jpg)
BASISTHEORIE POMPGEGEVENS // VERSCHUIVING WERKINGSPUNT
van A naar C
Sluiten van de klep (Kv1 < Kv)
Klep
sluit
van A naar B
Openen van de klep (Kv2 > Kv )
Klep
opent
![Page 18: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/18.jpg)
BASISTHEORIE POMPGEGEVENS // TOERENTALGEREGELDE POMP
![Page 19: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/19.jpg)
BASISTHEORIE POMPGEGEVENS // TOERENTALGEREGELDE POMP KENMERKEN
Automatische drukverschilregeling op Δp-c (drukconstant modus)
Opvoe
rhoo
gteH[m
]
VolumestroomV[m³/h]
nmax
1
2
nregel
3
1. Toerengeregelde pomp ingesteld op setpunt opvoerhoogte (punt 1).
2. De elektronica meet het verschil tussen het setpunt (punt 1) en actuele meetwaarde (punt 2).
3. De regelaar reduceert het toerental en brengt de opvoerhoogte weer op setpuntwaarde (punt 3).
H2
V2
nregel
nregel
nregel
nregel
V1
H1
![Page 20: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/20.jpg)
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
(Ventilator)convector nominaal debiet G 330 l/h
Drukverlies veroorzaakt bij nominaal debiet ΔP 1500 Pa
Lengte van de stijgleidingen – aansluitingen (ventilator)convectoren l 4 m
Bochten tussen stijgleidingen en (ventilator)convectoren nr. 2 (90°)
8 SECUNDAIRE CIRCUITS
![Page 21: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/21.jpg)
8 SECUNDAIRE CIRCUITS
Leidingen h8 790 Pa
Hulpstukken z8 960 Pa
Afgifte k8 1500 Pa
TOTAAL h8 3250 Pa = 3,25 kPa
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
![Page 22: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/22.jpg)
SECTIE VAN STIJGLEIDING 8 - 7
SECUNDAIR CIRCUIT 7
Leidingen h8-7 287 Pa
Hulpstukken z8-7 57 Pa
TOTAAL ∆P8-7 344 Pa
H8 3250 Pa
∆P8-7 344 Pa
DRUKVERLIES H7 3594 Pa = 3,59 kPa
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
![Page 23: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/23.jpg)
G7 = gebalanceerd debiet H7 = nieuw drukverlies van het circuit G8 = te balanceren debiet H8 = drukverlies van het te balanceren circuit
SECUNDAIR CIRCUIT 7
Debiet G7-8
Debiet 8 G8 330 l/h
Debiet 7 G7 348 l/h
TOTAAL G7-8 678 l/h
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
![Page 24: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/24.jpg)
SECTIE VAN STIJGLEIDING 7 - 6
Drukverlies ∆P7-8
Leiding h7-6 1096 Pa
Hulpstukken z7-6 250 Pa
TOTAAL ∆P7-6 1346 Pa = 1,37 kPa
SECUNDAIR CIRCUIT 6
H7 3250 Pa
∆P7-6 1350 Pa
DRUKVERLIES H6 4940 Pa = 4,94 kPa
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
![Page 25: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/25.jpg)
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN
VOLLAST
![Page 26: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/26.jpg)
G8 = 330 l/h Ø8 = ½” V8 = 0,44 m/s G7 = 330 l/h Ø7 = ½” V7 = 0,44 m/s G6 = 330 l/h Ø6 = ½” V6 = 0,44 m/s G5 = 330 l/h Ø5 = ½” V5 = 0,44 m/s G4 = 330 l/h Ø4 = ½” V4 = 0,44 m/s G3 = 330 l/h Ø3 = ½” V3 = 0,44 m/s G2 = 330 l/h Ø2 = ½” V2 = 0,44 m/s G1 = 330 l/h Ø1 = ½” V1 = 0,44 m/s
G8-7 = 330 l/h Ø8-7 = ¾” G7-6 = 660 l/h Ø7-6 = ¾” G6-5 = 990 l/h Ø6-5 = 1” G5-4 = 1320 l/h Ø5-4 = 1 ¼” G4-3 = 1650 l/h Ø4-3 = 1 ¼” G3-2 = 1650 l/h Ø3-2 = 1 ¼” G2-1 = 1980 l/h Ø2-1 = 1 ¼” G1-0 = 2310 l/h Ø1-0 = 1 ½”
VOLLAST
(Ventilator)convector nominaal debiet G 330 l/h Drukverlies veroorzaakt bij nominaal debiet ΔP 1500 Pa Lengte van de stijgleidingen – aansluitingen (ventilator)convectoren l 4 m
Bochten tussen stijgleidingen en (ventilator)convectoren nr. 2 (90°)
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
DEBIETBEREKENING
![Page 27: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/27.jpg)
SECUNDAIR CIRCUIT 8
Leidingen h8 790 Pa
Hulpstukken z8 960 Pa
Afgifte k8 1500 Pa
Inregelventiel ∆Pv8 1110 Pa
TOTAAL h8 4360 Pa = 4,36 kPa
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
![Page 28: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/28.jpg)
Inregelventiel ingesteld op POSITIE 6
SECUNDAIR CIRCUIT 8
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
![Page 29: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/29.jpg)
Sectie van stijgleiding 8 - 7
Debiet G8-7 = G8 = 333 l/h
Leiding h8-7 287 kPa
Hulpstukken z8-7 57 kPa
TOTAAL ∆P8-7 344 kPa
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
![Page 30: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/30.jpg)
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
3250 Pa SECUNDAIR CIRCUIT 7
Drukverlies
H8 4360 Pa
∆P8-7 344 Pa
H7 EFF 4704 Pa = 4,70 kPa
Inregelstand
H7EFF 4704 Pa
H8 3250 Pa
∆PREG.VENT 1454 Pa = 1,45 kPa
![Page 31: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/31.jpg)
Inregelventiel ingesteld op POSITIE 4.5
SECUNDAIR CIRCUIT 7
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
![Page 32: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/32.jpg)
![Page 33: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/33.jpg)
Statisch inregelen
Inregelventiel met debietmeter serie 132
Inregelventiel met venturi serie 130
Inregelventiel met flensaansluiting serie 130
Dynamisch inregelen
Drukonafhankelijk ventiel Flomatic® serie 145
Automatische debietregelaar Autoflow®
serie 121-126 serie 127 serie 120-125 serie 103
∆p regelen
Drukverschilregelaar serie 140
Inregelventiel met voorinstelling serie 142
Drukverschilregelaar serie 519
INREGELEN // toepassingen & componenten
![Page 34: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/34.jpg)
Statisch inregelen Dynamisch inregelen ∆P inregelen
Serie 130 Serie 132
Serie 145 Flomatic®
Serie 120 / 121 /125 / 126 / 107 / 103
Autoflow®
Serie 140 Serie 142 Serie 519
Solar Geothermie Tapwater
Radiatoren Vloerverwarming Satellietunit
Koelplafonds Luchtverhitter Stralingspanelen Convectoren Luchtgroep Cascade
INREGELEN // toepassingen
![Page 35: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/35.jpg)
INREGELEN // toepassingen RADIATOREN
![Page 36: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/36.jpg)
INREGELEN // toepassingen RADIATOREN
![Page 37: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/37.jpg)
INREGELEN // toepassingen VLOERVERWARMING
![Page 38: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/38.jpg)
INREGELEN // toepassingen VLOERVERWARMING
![Page 39: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/39.jpg)
INREGELEN // toepassingen VLOERVERWARMING
![Page 40: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/40.jpg)
INREGELEN // toepassingen DISTRIBUTIE-UNITS
![Page 41: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/41.jpg)
INREGELEN // toepassingen DISTRIBUTIE-UNITS
![Page 42: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/42.jpg)
INREGELEN // toepassingen DISTRIBUTIE-UNITS
![Page 43: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/43.jpg)
INREGELEN // toepassingen DISTRIBUTIE-UNITS
![Page 44: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/44.jpg)
INREGELEN // toepassingen VENTILOCONVECTOREN | KOELBALKEN | LUCHTVERHITTERS | STRALINGSPANELEN
![Page 45: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/45.jpg)
INREGELEN // toepassingen VENTILOCONVECTOREN | KOELBALKEN | LUCHTVERHITTERS | STRALINGSPANELEN
![Page 46: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/46.jpg)
INREGELEN // toepassingen LUCHTGROEPEN
![Page 47: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/47.jpg)
INREGELEN // toepassingen LUCHTGROEPEN
![Page 48: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/48.jpg)
INREGELEN // toepassingen LUCHTGROEPEN
![Page 49: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/49.jpg)
INREGELEN // toepassingen CASCADE
![Page 50: CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN](https://reader030.vdocuments.net/reader030/viewer/2022012103/616a065311a7b741a34dfaff/html5/thumbnails/50.jpg)
THANK YOU
CARE.CALEFFI.BE