Download - COMBUSTION SAFEGUARD Operates with FLAME ROD
SINGLE AND MULTI-BURNERSOLID STATE
BULLETIN P-24 R5
FORM 6642V
COMBUSTION SAFEGUARDOperates with FLAME ROD
and/orP-C II (Ultra-Violet) SCANNER
• Modularized Multi-BurnerControl
• Time Proven Plug-In Solid StateFLAME-PAK Amplifier.
• Plug-In, Interchangeable Relays
• Plug-In Power Transformer.
• Flame Rod and/or Ultra-VioletSensing. Independent orsimultaneously using sameFLAME-PAK Amplifier.
rotectofier
7317 N. LAWNDALE AVENUEP.O. BOX 287 • SKOKIE. ILLINOIS 60076·0287(847) 674·7676' CHICAGO PHONE: (773) 763-3110FAX: (847) 674·7009e-mail@proleclionconlrolsinc.comwww.proleclionconlrolsinc.com
SINGLE AND MULTI-BURNER
otecto ierCOMBUSTION SAFEGUARD
Operates with FLAME RODSand/or P-C IT (Ultra-Violet) SCANNERS
RELIABLE PERFORMANCE STANDARDS Solid state circuitry ... modular/plug-in con-struction ... automatic purge and ignition ... built-in flame-fault indication!
BASIC OPERATION
PROTECTOFIER monitors one or more burn-ers, and responds to the presence orabsence of flame via the rectification Winci-pIe. When using a FLAME ROD, the flameitself serves as a switch to open or close aD.C. circuit to FbAM~-PAK. Similarly, whenusing a P-C IT SCANN~R, a D.C. signal sourceis created by the ultra-violet sensitive tubec;mly when the flame is scanned. With eithersensing system, if the signal from flame toFLAME-PAK is interrupted (response time, 4seconds or less), the circuit to the safetyshut-off valve is broken, which automaticallyshuts down the complete system (and canalso energize circuit to alarm). The TELEFIERlight instantly indicates faulry Durner in amulti-burner system.
Single-Burner PROTECTOFIER
INSTALLATION DATAMOUNTING
PROTECTOF IERS can be mounted in any position andany practical distance from supervised burners. Open typescan be mounted in standard Control Panels. Separate en-closures, constructed of heavy gauge steel, are available.
WIRING
Wiring between the flame sensor(s) and the PROTECTOFIERshould be No. 14 gauge, type TW wire, insulated for 600 volts.All sensor wires may be run together in the same conduit.See Service Manual PSM-1187.
FLAME SENSORS PROTECTOFIERSare supplied for operation at 120V 50- 60Hz.
PROTECTOFIERS function with any commercial flame rodassemblies and/or with P-C II (Ultra-Violet) SCANNER-even in a single burner system. The Ultra-Violet Scannercan be used with either gas or oil flames.
INSTALLATION, OPERATION AND MAINTENANCESHAll CONFORM WITH NATIONAL FIRE PROTECTIONASSOCIATION STANDARDS, NATIONAL AND LOCALCODES, AND AUTHORITIES HAVING JURISDICTION.ANY MODIFICATION VOIDS APPROVALS.
PCI ADVANTAGESFLAME-PAK
Solid state module contains entire electronic circuit tosupervise one burner-no components under chassis! Com-pact units provide exceptionally reliable operation, longservice life, and are interchangeable for easy piug-in servicing.
TIMOFIEROptional control for automatic system purge and/or ignitiontrial timing. It actuates "flush-out" of combustible atmos-phere before start-up. Timing cycle is non-adjustable (specifyrange required}. Plug-in convenience permits easy servicingand inter-changing of TIMOFIERS with different timecycles.
TELEFIER
Built-in flame-fault indicator light for multi-burner systemsinstantly shows exact burner position causing shutdown-eliminates trouble-shooting steps and downtime.
(Available with readout extended to frontof Control Panel orenclosure.]
CONTROL MODULES
PROTECTOFIER Modules are teamed-up with the masterchassis to supervise multi-burner systems. Each modulecontains a FLAME-PAK, TELEFIER, TRANSFORMER andFLAME RELAY to supervise one burner. The plug-inFLAME RELAY insures that each pilot flame is establishedbefore main valve is energized.
P-C n (ULTRA-VIOLET) SCANNERS
For use with either gas or oil flames. Compact unitscontain only an ultra-violet sensing tube for direct 2-wireconnection to PROTECTOFIER. IMPORT ANT: Flame rodassembles and P-C II SCANNERS can be used simulta-neously in the same PROTECTOFIER System. P-C II W
U-V SCANNER, providedwith a 1/2" straight liquid-tite electrical connector andP-C IIWRA U-V SCANNER,provided with a 1/2" rightangle liquid-rite electricalconnector are also available.
THERMAL CIRCUIT BREAKER(Safety Lock-out Switch)
plug·inLOAD RELAY~
plug·inCHECK RELAY'
Five Burner PROiECiOFIER
(!lug-infLAME RELAY
t'Serves entire multi-burner system.
Two Burner
NON RE-LIGHT PROTECTOFIER (NR)
Single Burner
NON RE-LiGHT PROTECTOFIER (NR)
PROOFOFCLOSURE(~Form 6642VT and Form 6642VL T Models allow proof ofclosure contact on fuel valves to be interlocked before purgetimer initiates.
NON RE-LiGHT PROTECTOFIER (NR)Single and Multi-Burner Models
These "NR" Models are available to meet safety requirementsthat do not permit a re-light upon flame failure on certainautomatically operated burner installations. They have thesame built-in reliability and features of the standard Form6642V Series PROTECTOFIER, plus an additional plug-inACF relay and the necessary circuitry to prevent are-lightattempt upon a flame failure. "NR" Automatic Models areavailable with plug-in U-300A TIMOFIER to provide forpre-purge.
PROTECTorlERSINGLE BURNER WITHOUT TIMOFIER
FORM 6642VAGROUP M2101
FORM 6642VBGROUP M2101
TWO BURNER WITHOUT TIMOFIER
FORM 6642VLGROUP M3102
DONE BURNERGroup M21016-1/2" W x 8-1/2" H
FORM 6642VBLGROUP M3102
[]
TWO BURNERGroup M31029-3/4" W x 8-1/2" H
[ill THREE BURNERGroup M410313" W x 8-1/2" H
rno FOUR BURNERGroup M510416-1/4" W x 8-1/2" H
[[]] FIVE BURNERGroup M610519-1/2" W x 8-1/2" H
[
~ ~
SIX BURNERGroup M420614" W x 16" H
FORM 6642VCOMBUSTION SAFEGUARD
SINGLE BURNER WITH TIMOFIER
FORM 6642VT FORM 6642VBTGROUP MP3101 GROUP M31 01
TWO BURNER WITH TIMOFIER
FORM 6642VL TGROUP MP4102o ONE BURNER
Group MP31019-3/4" W x 8-1/2" H
FORM 6642VBL TGROUP M4102
M3101
M4102
THREE BURNERGroup MPS10316-1/4" W x 8-1/2" H
MS103
FOUR BURNERGroup MP610419-1/2" W xB-1/2" H
M6104
M420S
M4206
NOTE: PROTECTOFIERS are available to supervise any number of burners. See Price Bulletin 42.
"A" Indicates basic combustion safeguard model."8" (BREAKER) indicates lock-out switch model. Required for automatic-lighted installations. System "latches-out"
after failure to light within ignition trial time and cannot attempt re-start until switch is manually reset"L" (LOAD relay) All multi-burner models include load relay."T" (TIMER) indicates TIMOFIER model PLUG-IN, FIXED-TIME assembly. The TIMOFIER provides purge time and ignition trial time."P" (PROOF OF CLOSURE) in group number of VT and VLT models."NR" (NON-RELIGHT) PROTECTOFIER available in all automatic models.
[]]
TWO BURNERGroup MP410213" W x 8-1/2" H
DTI[0]
"~
J~
~ ~,
FIVE BURNERGroup MP420S14" W x 16" H
~.
~(
~ -
SIX BURNERGroup MP420614" W x 16" H
Printed in U.S.A. 6-08