Enclosed ControlsProduct Catalog
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
2
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
MILBANKOVERVIEW
Milbank OverviewEnergy At Work since 1927
Milbank designs and manufactures electrical solutions that move and manage power for the residential, commercial, industrial, utility and transportation sectors. With more than 90 years of expertise in electrical engineering design and manufacturing, Milbank’s portfolio includes metering equipment, enclosures and enclosed controls. Founded in 1927, Milbank is a family-owned, American manufacturer headquartered in Kansas City, Mo. For more information, please visit milbankworks.com.
As a market leader in electrical metering equipment, Milbank has set the standard for quality since 1927. Hundreds of configurations are available, including many sizes, knockout configurations, terminal configurations, bypass options, hubs, locks and connectors. Milbank has the socket you need with thousands of active products to meet your utility’s requirements.
METERING
Milbank’s line of enclosures include commercial junction boxes, panel mount enclosures, transformer cabinets, wireway and troughs. Built with high-quality craftsmanship and materials which meet or exceed industry standards, Milbank enclosures are made to protect controls and equipment from dust, dirt and other harmful elements found in a wide variety of environments based on various NEMA ratings Milbank offers.
ENCLOSURES
Milbank doesn’t just build empty enclosures. We can deliver the entire package, complete with custom control equipment built to your exact specifications by our engineers. Milbank enclosed controls are an attractive, secure, easy to install and cost-effective solution when underground remote site power distribution and control equipment is required, replacing unsightly and inefficient strut and backboard structures.
ENCLOSED CONTROLS
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
3
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Table of ContentsTABLE OFCONTENTS
Enclosed Controls
Product Number Reference Guide ............................................................................................................................... 4-5Enclosed Controls Overview ......................................................................................................................................... 6-7Surface-Mount Enclosed Controls ..................................................................................................................................... 8Main Load Center Commercial Pedestals ......................................................................................................................... 9Switched Load Center Commercial Pedestals ................................................................................................................. 10400 Amps Commercial Pedestals .................................................................................................................................... 11Battery Backup Commercial Pedestals ............................................................................................................................ 12Power Transfer Commercial Pedestals ............................................................................................................................ 13CT Metered Commercial Pedestals ................................................................................................................................. 14Slimline Commercial Pedestals ....................................................................................................................................... 15 Electric Vehicle Charging ................................................................................................................................................ 16Accessories ..................................................................................................................................................................... 17Exterior Color Options .................................................................................................................................................... 18Detailed Drawings ..................................................................................................................................................... 19-30Application Examples ................................................................................................................................................ 31-43
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
4
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Catalog Number Logic1 2 3 4 5 6
CP3ACP3B
5. Service/Main Disconnect(Load centers use plug-in C/B’s; panelboards use bolt-on C/B’s)A = (2) 8 circuit load centers metered, (1) 8 circuit load center unmeteredB = (2) 24 circuit load centersD (1) 42 circuit panelboard (enclosure types H & K only )E =(1) 30 circuit panelboard (400A K or Q)F = (1) 18 circuit panelboardG = (1) 30 circuit load center (400A K or Q)H = (2) 12 circuit load centersJ = No interiors and no branch breakers (Main only)K = (1) 4 circuit load center metered, (1) 4 circuit load center unmeteredL = Distribution block(s) onlyM = (2) Distribution blocksN = Metered and unmetered lug to lug breakersP = Metered lug to lug breakersR = (1) 8 circuit metered, (1) 8 circuit unmetered, (1) 12 circuit meteredT = (1) 8 circuit load center
U = Unmetered lug to lug breakers (Type A)V = (1) 6 circuit plug-on breaker interiorW = (2) 6 circuit plug-on breaker interiorX = Non StandardY = (1) 42 circuit load center 30" tall deadfront1 = (1) 8 circuit load center metered, (1) 8 circuit load center unmetered2 = (2) 8 circuit load centers3 = (1) 12 circuit load center4 = (1) 12 circuit load center and (1) 8 circuit load center5 = (1) 16 circuit load center6 = Lug to lug main & branch breakers only7 = (1) 8 circuit load center, (1) 16 circuit load center8 = Fusible switch (Pullout)9 = (1) 24 circuit load center0 = (2) 16 circuit load centers
3. System Voltage0 = 120V, 1Ø, 2W (4 Jaw)1 = 120/240V, 1Ø, 3W (4 Jaw)2 = 208Y/120V, 1Ø, 3W (4 Jaw + 105J)3 = 240/480V, 1Ø, 3W (4 Jaw)4 = 480Y/277V, 1Ø, 3W (4 Jaw + 105J)5 = 208Y/120V, 3Ø, 4W (7 Jaw)6 = 240Δ/120V, 3Ø, 4W (7 Jaw)7 = 240ΔV, 3Ø, 3W (5 Jaw)8 = 480Y/277V, 3Ø, 4W (7 Jaw)9 = 480ΔV, 3Ø, 3W (5 Jaw)
A = No ratingB = 480Δ/240V, 3Ø, 4W (7 Jaw)C = 120/240V, 1Ø, 3W (5 Jaw)D = 240/480V, 1Ø, 3W (5 Jaw)E = 480V, 1Ø, 2W (4 Jaw)F = 1Ø, 3W, 120/240V, FORM 4S, (6 Jaw)G = NETWORK, 120/208V, 1Ø, 3W FORM 5S (8 Jaw)H = NETWORK, 277/480V, 1Ø, 3W FORM 5S (8 Jaw)I = 3Ø, 3W, Δ 240V, FORM 5S (8 Jaw)J = 3Ø, 3W, Δ 480V, FORM 5S (8 Jaw)
K = 3Ø, 4W, Δ 240V, FORM 8S (13 Jaw)L = 3Ø, 4W, Δ 480V, FORM 8S (13 Jaw)M = 3Ø, 4W, Y 120/208V, FORM 5S (8 Jaw)N = 3Ø, 4W, Y 277/480V, FORM 5S (8 Jaw)O = 3Ø, 4W, Y 120/208V, FORM 6S (13 Jaw)P = 3Ø, 4W, Y 277/480V, FORM 6S (13 Jaw)Q = 3Ø, 4W, Y 120/208V, FORM 9S (13 Jaw)R = 3Ø, 4W, Y 277/480V, FORM 9S (13 Jaw)S = 1Ø, 3W, 220/380V, (5 Jaw)
6. Enclosure Size CP3A (Slimline)A =12”W x 8.25”D x 63”H (Single)B = 20”W x 10.25”D x 63”H (Single)C = 20”Wx10.25”D x 52”H (Single)I = 12”W x 8.25”D x 50”H (Single)J = 20”W x 10.25”D x 50”H (Single)K = 12”W x 8.25”D x 63”H (Single) (Exposed Meter) L = 20”W x 10.25”D x 63”H (Single) (Exposed Meter) M = 12”W x 8.25”D x 50”H (Single) (Exposed Meter) N = 20”W x 10.25”D x 50”H (Single) (Exposed Meter)O = 12”W x 8.25”D x 43”H (Unmetered)P = 20”W x 10.25”D x 43”H (Unmetered)
CP3B - StandardA = 16”W x 17”D x 48”H (Single)B = 24”W x 17”D x 48”H (Double)C = 30”W x 24”D x 48”H or (54”H w/Sloped Top Only) D = 44”W x 24”D x 60”HE = 16”W x 17”D x 41”H (Unmetered, Low Profile)K = 32”W x 20”D x 60”HL = 36”W x 20”D x 60”HM = 24W” x 17”D x 41”H (Unmetered, Low Profile)P = 16”W x 17”D X 48”H (Exposed Meter)Q = 32”W x 20”D x 43.5”H (Unmetered) R = 4”W x 17”D x 48”H (Exposed Meter) S = 32”W x 20”D x 60”H (Exposed Meter)
CP3B Standard (cont.) X = 24”W x 24”D x 64”H ( CT Metered) Z = 32”W x 24”D x 64”H (CT Metered) T = 42”W x 27”D x 64”T (CT Metered) W = 46’W x 27” D x 64”T (CT Metered)
CP2B - Surface MountN = 14”W x 6”D x 39”HO = 35”W x 8”D x 48”H
1. Meter Sockets0 = No sockets1 = 1 ring type socket with test bypass facility2 = 2 ring type socket with test bypass facility3 = 1 ring type socket with, 1 without test bypass facilities4 = 1 ring type socket without test bypass facility5 = 1 ringless socket with lever test bypass facility6 = 2 ringless socket with lever test bypass facility7 = 1 ringless socket without test bypass facility
8 = 1 bolt-on meter with manual bypass facility9 = 1 ringless socket KK horn bypassA = 2 ringless sockets KK horn bypassB = 1 ring type socket with test switch, CT rated meter socketC = 1 ringless socket with test switch, CT rated meter socketD = 1 ring type socket with test bypass , U3504 meter socketE = 2 ring type sockets without test bypass
4. Service/Main Disconnect0 = No Main (Max 6 disconnect per unit)1 = (1) Circuit breaker main2 = (2) Circuit breaker mains
3 = (1) T-fuse pullout main4 = (3) Circuit breaker mains6 = (1) 4-pole main (100A Max.)
8 = (1) 4-pole 100A & (1) 2-pole 100AB = (2) Circuit breaker mains with interlockC = (2) T-Fuse pullout mains
2. Amps0 = No rating 1 = 100 Amps 2 = 200 Amps 3 = 125 Amps 4 = 400 Amps 6 = 600 Amps 8 = 800 Amps
REFERENCE GUIDE
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
5
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Catalog Number LogicReference for EXISTING Catalog Numbers Only
14 = 14K AIC22 = 22K AIC25 = 25K AIC30 = 30K AIC42 = 42K AIC
50 = 50K AIC65 = 65K AIC100 = 100K AIC(Short circuit rating)
AE = Alliant EnergyCE = Common Wealth EdisonCL = Copper NeutralCO = Colorado SpringsCOD = Colorado DOTCS = Cold SequenceCT = CaltransDP = Dayton Power & ElectricEM = Electrical MidwestIA = Iowa DOTID = Idaho DOTIL = Illinois DOTKC = Kansas CityKD = Kansas DOTKK = Horn BypassLA = Louisiana DOTLSMO = Lee’s Summit, MissouriLV = Las VegasLX = LenexaMA = MesaMO = MO DOTMN = Minnesota DOTNRG = NRG Electric LTDNV = Nevada DOTOP = Overland ParkPB = Penta Bolt SealingRI = Rhode Island DOTSL = Switched LoadSN = ShawneeTX = Texas DOT(Followed by pedestalType A, C, D or T)UD = Utah DOTWA = Washington DOTWE = Wisconsin ElectricXC = Xcel Energy
A = Aluminum (add color code)AL = Aluminum AnodizedAO = Aluminum UntreatedB = Brown (RAL 8011)BEB = Beige Brown (RAL 8024)BEG = Beige Green (RAL 1001)BG = Blue Green (RAL 6004)BK = Black (RAL 9004)BK1 = Poly Black (RAL 9005)BK2 = Ebony 334 Black (TCI 9210-90663)BK3 = Topeka BlackBKG = Black Green (RAL 6012)BR = Medium Brown (RAL 8017)BR1 = Brown (TCI 5084)BR2 = Brown (TCI 70-78815W)BR3 = Safari BrownBR4 = BR4 - Brown (FED SPEC 20122)BR5 = Brown (RAL 8008)BR6 = Brown (RAL 8003)BR7 = Western Reserve Pantone 326-1BR8 = Whiteman Brown (FED SPEC 20059)BRN = Brown (FED SPEC 20045)BRP = Brown Gray (RAL 7013)BU = Blue (RAL 5017)BWG = Boxwood Green (TIGER DRYLAC)BZ = Bronze Color (TIGER #39/60060)C = CaramelD = Dark Green #2 (KC)(#VFG505S9)DB = Dark Brown (RAL 8025)DBZ = Dark Bronze (KCMO)DG = Dark Green #1(RAL 8025)DG1 = Dark Green (FED SPEC 14052)DG2 = Dark Green #2 (RAL 6002)DG3 =Dark Green #3 (RAL 6029)DG4 = Dark Green #4 (FED SPEC 14062)DG5 = Franklin Green PGS8-90245 (Sherwin-Williams)DG6 = Dark Green #6 (FED SPEC 14066)DG7 = Dark Green #7 (RAL 6009)DP = Dark Gray (RAL 7036)DS = Desert Sand (Drylac #39/15020)DT = Desert Tan (RAL 9001)FB = Fawn BrownFBK = Flat BlackFST = Tan (FED SPEC 33617)G = Standard Mint Green (Use with AO and SS)G1 = Malaga GreenG2 = Light Green (RAL 6019)G3 = Green (FED SPEC 34424)GA = Green A (TIGER-DR 249/53120)GG = Green G (Grotto Green) (RAL 6007)GW = Gray-White (RAL 9002)LB = Light Brown (RAL 1019)LG = Light Green (FED SPEC 14672)MB = Mesa Brown (KELLY MOORE #183)MB1 = Mahogany BrownMG = Munsel GreenP = Gray (ANSI 61)P1 = Gray (ANSI 49)P2 = Gray (RAL 7038)P3 = Sky Gray (RAL 7001)P4 = Gray (RAL 7030)P5 = Pebble Gray (RAL 7032)P6 = Silk Gray (RAL 7044)P7 = Dove Gray (ANSI 70)PG = Pine Green (RAL 6020)R1 = Orient Red (RAL 3031)RFG = Rain Forest Green (4070)SB = Sepia Bronze (Sherwin-Williams)SC = Sail Cloth (Sherwin-Williams)SG = Summerland Grey (Gray Brown)SGN = Sage GreenSS = Stainless SteelSY = Sand Yellow (RAL 1002)T = Tan (RAL 1015)TB = Terra Brown (RAL 8028)TT = Telcom TanW = White (Exterior Paint) (VALSPAR PTW90005)W1 = Off WhiteWR = Wine Red (RAL 3005)
REFERENCE GUIDE
Note
New part numbers to be assigned by Milbank enclosed controls team.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
6
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
ENCLOSEDCONTROLS
Enclosed Controls Attractive | Easy to Install | Secure | Cost-Effective
Milbank Enclosed Controls are pad-mounted, weather-resistant electrical enclosures consisting of a utility pull section with optional meter socket and a customer section containing distribution and control equipment. Commercial pedestals are an attractive, secure, easy-to-install and cost-effective solution when underground remote site power distribution and control equipment is required, replacing unsightly and inefficient strut and backboard structures.
UL Listed as Industrial Control Equipment (File E113855)
Strut and backboard Commercial pedestal
• NEMA 3R rain-resistant, vandal-resistant cabinet of polyurethane powder coated steel (aluminum or stainless steel also available)• UL listed as enclosed industrial control equipment (UL508A)• Isolated lockable and sealable utility metering and lug landing sections• Lockable customer section for distribution and control equipment with internal deadfront• Print pocket inside customer section door contains wiring schematics and installation instructions• Load centers are UL listed for use with various manufacturers’ circuit breakers• All stainless steel external hardware (screws, bolts, hinges, handles, hasps and sealing screws)
Standard Features
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
7
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
ENCLOSED CONTROLS
Enclosed Controls Attractive | Easy to Install | Secure | Cost-Effective
These units are ideal for controlling, metering and power distribution of:• Traffic signals• Street lighting• Power distribution for electric vehicle charging stations• Communication equipment such as cell towers and telephone vaults• Event power for fairgrounds, swap meets, outdoor markets, portable offices,
holiday lights, etc.• Outdoor lighting for athletic fields, tennis and basketball courts,
parking lots, landscaping and subdivision entrances, etc.
• Meter sockets: ring type or ringless, up to 400 Amps• Main and branch breakers or T fuses• Distribution: copper load centers and panelboards• Clocks, timers and relays• Photoelectric cells and controls• Various power receptacles: pin and sleeve, twist lock or straight blade• Contactors: lighting, definite purpose, motor starters• Surge protection and lightning arresters• Generator inlets with interlocked breakers• Push button controls• Thermostat controls, fans and heating strips• Power blocks and terminal blocks• Steel, aluminum and plywood backboards• Transformers• Interlock devices for circuit breakers
Options
• Available in steel, aluminum (raw painted or anodized) or stainless steel construction with powder coated finish available in eight standard colors or special-ordered RAL colors
• Available for applications up to 400 Amps, 120V, 208V, 240V, 277V, 480V - 1Ø or 3Ø
Applications
Available Factory-Installed Options
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
8
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
SURFACE MOUNT
ENCLOSED CONTROLS
Enclosed ControlsSurface-Mount Compact Design
Features
• Easy installation• Overhead and underground entry and exit, all in one unit• Meter and components in one enclosure• UL508A & UL891 • Custom component configurations • UL listing covers all internal components• Can be mounted on multiple surfaces • Walls • Poles – narrow profile will have minimal extension past sides • H Frames (Strut)• Multiple bypass options available• Monitoring options available• Can be powder coated in any Milbank standard EC color or custom color.
Surface-Mount Enclosed Control Originally developed for small cellular communications, the surface-mount enclosed control offers the flexibility of larger enclosed controls products with a smaller footprint and several mounting options.
Benefits• Does not take up sidewalk space• Flood resistant• Eliminates need for connecting components: • Wire in - Wire Out
Communications Power
Distribution
StreetscapePower
Distribution
Lighting Control
Applications
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
9
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Main Load Center Commercial Pedestal1Ø3 wire 120/240V or 208Y/120VApplication: remote site service for multiple loadsMilbank Main Load Center Commercial Pedestals are designed to handle the vast majority of all requirements in a standard, stocked configuration. • All units feature a load center with a plug-on, back-fed main breaker. • Standard units are equipped with with a 16 circuit load center in
the 100 Amps or 24 circuit load center in 200 Amps models. • Sub-feed lugs allow feeding an external panel.
If your application requires turning loads on based on “dusk-to-dawn” requirements, be sure to see the Milbank Switched Load Center Commercial Pedestal products on the following page.
Standard PedestalsOptional Fifth Terminal Kit
Main CB Load Center Circuits
Meter Socket TypeAmps Spaces
CP3B11115A22 105J 100 1,2 16 Ring type with test/bypass blocks
CP3B12119A22 105J 200 1,2,3 4 24 Ring type with test/bypass blocks
CP3B51115A22 K3865 100 1,2 16 Ringless socket with lever bypass
CP3B52119A22 K3865 200 1,2,3,4 24 Ringless socket with lever bypass
MAIN LOAD CENTER
COMMERCIAL PEDESTAL
Enclosed ControlsMain Load Center Commercial Pedestals
Features
These units include everything required for remote site service: • Expandable: load centers allow for future expansion without costly
modifications.• All units feature a 200 Amps meter socket with optional field-
installable fifth terminal kit available.• 22K Amps interrupting capacity (AIC) standard.• Optional mounting base can be embedded in concrete for fast, easy
installation.• Separate sealable and lockable utility termination section.• Separate sealable and lockable metering section.• Separate sealable and lockable customer section with a load center
for “always on” loads that include a main circuit breaker, 16 circuit panel in 100 Amps model and 24 circuit panel in 200 amp model
Notes
• Chart shows standard, stocked items. Other options and features are available. Contact factory for options, details and availability.• May require customization based on regional requirements.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
10
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Standard PedestalsOptional Fifth Terminal Kit
Main CB Contactor Amperage
Meter Socket TypeAmps Spaces
CP3B11110A22SL1 105J 100 1,3 60 Ring type with test/bypass blocks
CP3B12110A22SL1 105J 200 1,2,3,4 100 Ring type with test/bypass blocksCP3B51110A22SL1 K3865 100 1,3 60 Ringless socket with lever bypassCP3B52110A22SL1 K3865 200 1,2,3,4 100 Ringless socket with lever bypass
SWITCHED LOAD COMMERCIAL PEDESTALS
Enclosed ControlsSwitched Load Center Commercial Pedestals
Notes
• Chart shows standard, stocked items. Other options and features are available. Contact factory for options, details and availability.• May require customization based on regional requirements.
Features
These units include everything required for remote site service: • Expandable: load centers allow for future expansion without costly
modifications.• All units feature a 200 Amps meter socket with optional field-installable fifth
terminal kit available.• 22K Amps interrupting capacity (AIC) standard.• Optional mounting base can be embedded in concrete for fast, easy
installation.• Separate sealable and lockable utility termination section.• Separate sealable and lockable metering section.• Separate sealable and lockable customer section with a control circuit including
PE receptacle, Lexan® window, glare shield, Hand-Off-Auto (HOA) switch, contactor controlling a 16 circuit load center for controlled loads, a pre-mounted DIN rail and pre-wired connector to add an optional “plug-and-play” time clock kit for PE on and TC off operation and a circuit directory to document configuration.
• A load center for “always on” loads that includes a main circuit breaker, a control power circuit breaker, a switched load center main breaker, nine (125 or 200 Amps model) or 11 (100 Amps model) blank breaker spaces and a circuit directory to document configuration. Ringless Lever Bypass shown
Traffic Signals Parking Lots Highways Athletic Field Lighting
Switched Load Center Commercial Pedestals1Ø3 wire 120/240V or 208Y/120V Designed not only to provide power for various loads, but also to switch specific loads on and off under certain conditions. A photoelectric cell is used for these controlled loads, and an optional time clock is also available.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
11
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
400 AMPSCOMMERCIALPEDESTALS
Enclosed Controls400 Amps Commercial Pedestals
Standard PedestalsOptional fifth Terminal Kit
Main CB Load Center Circuits Meter Socket Type
CP3B1411JB N/A 320 Amps (400 max) 0 Ring type with test/bypass studs
CP3B14120B N/A 2-200 Amps (2) 12 circuit Ring type with test/bypass studsCP3B54120B22 K3865 2-200 Amps (2) 12 circuit Ringless with lever bypass
CP3B5411JB22 K3865 320 Amps (400 max) 0 Ringless with lever bypass
Designed to provide a weather- and vandal-resistant metered enclosure for various loads and distribution, the 400 Amps Commercial Pedestal (in bold) can handle a wide range of applications using standard, stocked configurations.• Choice of a single main breaker or twin service disconnect
breakers gives flexibility to the pedestal design. • Optional distribution with feed-through lugs below the service
disconnect breakers allows the pedestal to handle numerous applications.
• Typical applications include remote homes where the metering is best located at the curbside or other remote area. The pedestal can also provide power to a secondary residence, on-site business, workshop, irrigation, lighting, security or other secondary load.
• Refer to page 18 for color options.
Features
These units include everything required for remote service:• Main circuit breaker or dual service disconnects• Expandable: load center units allow for future expansion without
costly modifications• Optional mounting base can be embedded in concrete for
fast, easy installation• Separate sealable and lockable utility termination section with lug
termination• Separate sealable and lockable metering section • Separate sealable and lockable customer section with a circuit
directory and a print pocket to hold all documentation• Meter socket options include ring type with bypass studs, ringless
with heavy duty lever bypass, or K Type bolt-on
Notes
• Chart shows standard, stocked items. Other options and features are available. Contact factory for options, details and availability.
• Stud utility landing is standard. Lug kits are available from factory.
• Units with load centers have (2) #6-250 sub-feed lugs on each load center. (Each load center is 200 Amps rated and UL listed with: Siemens, General Electric and Cutler-Hammer plug-in style circuit breakers.)
• May require customization based on regional requirements.
Commercial Job Sites Remote Site for Residential &
Commercial Job Sites
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
12
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Designed to provide battery backup power for various loads and to switch specific loads on and off under certain conditions; as an example, the pedestal could use a photoelectric cell or time clock to control lighting circuits. Metered and unmetered power distribution options are available. The backup power pedestal is designed to handle the vast majority of today’s backup power requirements. By using a 19-inch rack design, shelves can be adjusted to accommodate the required batteries and manufacturers’ DC to AC inverters, transfer switches and other related equipment. This design gives the user a wide range of design and configuration options. Complete turnkey, ready to power-up pedestals are offered along with basic units ready to accept batteries and inverters supplied by others.Features
• 100 through 320 Amps meter socket with the option of either a ring type socket (conforms to EUSERC 308) with or without test/bypass blocks or a heavy duty ringless socket with lever bypass
• Separate sealable utility termination compartment• An isolated separate customer section with service disconnects,
power distribution options and power control • 19-inch wide rack in customer compartment for easy layout of
equipment• Battery trays• Thermostat with cooling fan• Filtered louvers for heat rise flow through ventilation• Three-point door latch (key or padlockable)
BATTERY BACKUPCOMMERCIALPEDESTALS
Enclosed ControlsBattery Backup Commercial Pedestals
Options
• Manual bypass switch• Transfer switch for generator power
backup• Generator inlet receptacles 30 Amps
through 200 Amps• Padlockable provision for receptacles• Police access door
• Metered load center distribution• Unmetered load center distribution• Photo electric controls (for street
lighting)• Time clocks• HOA switches• Contactors
• GFCI duplex receptacles• Thermostat for heating control• Heating pads or elements• Roll out shelves for batteries• Surge arresters and lighting arresters
Note
• May require customization based on regional requirements.
Traffic Signals Parking LotsCommunications Power Distribution
Camera & SecurityLocations
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
13
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
POWER TRANSFERCOMMERCIALPEDESTALS
Enclosed ControlsPower Transfer Commercial Pedestals
Providing metered or unmetered AC power, distribution, surge suppression, mechanical interlock and standby generator receptacle — all in a neat, compact pedestal.
Features
• 120/240V 1Ø3W through 277/480V 3Ø4W ratings• Metered or unmetered units• Choice of EUSERC ring type or ringless meter sockets• 60 Amps through 400 Amps ratings • Padlockable, isolated utility compartments• 20 Amps GFCI convenience receptacle• Lockable recessed generator receptacle door • Utility and generator indicator light options• All stainless steel hardware• Galvanized steel, aluminum or stainless steel cabinet options• Custom designs available
Note
• May require customization based on regional requirements.
Traffic SignalsCommunications
Power DistributionPump & LiftStations
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
14
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
CT METEREDCOMMERCIALPEDESTALS
Enclosed ControlsCT Metered Commercial Pedestals
Designed to be used where a smaller service package would be a better choice over larger switchgear equipment, these pedestals have amperage ratings of 400 to 800 Amps at voltages up through 480V three phase.
Features
• Up to 800 Amps• A low profile CT pedestal• All utility equipment is isolated in separated
padlockable and sealable compartments • Separate customer compartment designed to hold
distribution and control equipment• Dead front customer protection• Optional mounting base• Optional construction in steel, aluminum and
stainless steel• Refer to page 18 for color options
Note
• May require customization based on regional requirements.
Pump & LiftStations
Water Treatment Plants
Commercial &Industrial Control
Systems
Electric VehicleCharging Stations
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
15
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
SLIMLINE COMMERCIALPEDESTALS
Enclosed Controls Slimline Commercial Pedestals
Provides a sleeker, smaller footprint, with wireway access on the side of the unit rather than the back, allowing maximum flexibility to place the pedestal anywhere physical space is at premium.
Providing unmetered AC power, distribution, surge suppression, mechanical interlock and standby generator receptacle — all in a neat, compact pedestal.
Features• 100 or 200 Amps• Vandal-resistant, secure and attractive design• Customer compartment with distribution and control equipment with swing deadfront door,
secured with both a hasp/latch and draw latch outer door• Utility metering compartment protected with a hinged hood, increasing resistance to
meter vandalism• Small footprint• Wireway located on left side of pedestal for utility incoming wire, allowing pedestal to be
mounted with back as close as 14 inches to walls or structures• Available in 12- and 20-inch widths and 50- and 63-inch (metered) and 43-inch (unmetered) heights• Includes a print pocket for plans and drawings• Voltage range: 120V–480V• Compatible with both ringless and ring type meter sockets, 4–7 terminals
• Refer to page 18 for color options• Pedestal mounting base option saves time and labor to install on a cement pad—no anchor bolts required• Powder coated G90 galvanized steel or aluminum; raw, anodized or powder coated, as well as stainless steel
exterior options
Note
• May require customization based on regional requirements
Direct bury pedestals offer many advantages. With no need to coordinate, buy or wait for concrete, installation time can be cut down to less than an hour. Traditional direct bury pedestals are awkward to transport and handle and can only be used in a direct bury application. Milbank’s modular design offers flexibility and convenience for distributors
and contractors alike. It’s constructed with 14-gauge steel and only available for 12-inch pedestals.
Water Treatment Plants
Highways Parks &Landscaping
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
16
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Enclosed ControlsPower Distribution Pedestal for Electric Vehicle Charging
ELECTRIC VEHICLE
CHARGING
Milbank is a pioneer with EV charging distribution pedestals. With the increased emphasis on electric vehicles and the need to build infrastructure to support these vehicles, Milbank has been there from the beginning. Ranging from small charging station installations to multi-unit fast-charge arrays, Milbank has the solution.
Standard Features
• Metered and unmetered• 200-800 Amps• 120/208V or 120/240V or 277/480V• Predesigned shells• Predesigned interiors• Separate sealable utility termination compartment Customizable Features
• Color• Meter type/form• Utility landing format• 480V for fast charging applications• Filtered louvers for heat rise flow through ventilation• Interiors that will accept site-specified breaker quanities
and sizes• Multiple latching and locking options available
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
17
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
ENCLOSED CONTROLS
ACCESSORIES
Enclosed ControlsAccessories
105JFifth terminal kit for use with
ring type meter sockets
K3865Fifth terminal kit for use with ringless lever bypass meter
sockets
CP-ABK5/8Anchor bolt kit (includes four
5/8-13" x 18" anchor bolts)
CP-TC7D7-day time clock kit
CP-TC24H24-hour time clock kit
CP-TCWIREMale 4-pin connector and wiring harness for use with
time clocks other than shown
CP-PE-TYP5-2POSTwo position PE control kit
CP-PE-HOA-3POSHOA (Hand-Off-Auto) switch
for field installation
CP-16PDMNT-CALT - 16" pedestal mounting base
CP-24PDMNT-CALT - 24"pedestal mounting base
CP-32PDMNT - 32"pedestal mounting base
The Milbank mounting base is a standalone foundation system that doesn’t need to be used in conjunction with anchor bolts. The base is intended to be encased in concrete up to the top flange while leaving the mounting hardware intact. Once the concrete has cured, the mounting bolts can be removed and reused to secure the pedestal.
Bases available for all Milbank enclosed controls.All bases include mounting hardware.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
18
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
Additional Colors
Additional colors are available at the customer’s request. Please note: any deviation from the standardized colors can affect the overall price and manufacturing time. Be sure to contact your sales representative for more information.
EXTERIORCOLOR CHART
Enclosed ControlsExterior Color Options
Available Colors
Milbank offers standardized colors to all customers at no additional cost. Below are close approximations of the colors available. Please note: the color chips below may vary slightly in color or gloss from actual coatings due to the effects of heat, light and the manufacturing process. Please contact your sales representative for more information.
Mint Green(EUSERC territory standard)
Black Desert Tan Dark Green
Summerland GrayGray(Non-EUSERC territory standard)
WhitePine Green
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
19
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
SURFACE-MOUNTDRAWING
Enclosed ControlsSurface-Mount Compact Enclosed Control
“N” Style Surface-Mount Enclosed Control
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
20
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
ENCLOSED CONTROLS DRAWING
Enclosed Controls16" Metered & Unmetered Commercial Pedestal Drawings
17"ENCLOSURE
DEPTH
ALL SIDES. 6" REC.FOUNDATION EXTENSION
RECOMMENDED MIN.3"
REQUIRED PERN.E.C 110-16
TYPICAL
36" MIN.CLEARANCE
FRONT & BACK
42"
23.5" UTILITYTERMINATIONLANDING MIN.
MOUNTING BASE MOUNTING BASE
ANCHOR BOLT
MOUNTING HOLES
MOUNTING BASE DETAIL
MOUNTING HOLESPEDESTAL
9 3/4"
15"16"
14 1/2"
12 1/4"16"14 1/2"
13"
6 3/4"UTILITYSECTION
CUSTOMERSECTION
WITH COVER
WINDOW
HINGEDDEMANDMETERRESET
HINGED EXTERIOR DOORWITH DOOR STOP TO HOLDDOOR IN OPEN POSITION
48"
HINGEDDEADFRONT
SECURITY
(IF APPLICABLE)
LIFT-OFF
PHOTO CELL WINDOW
FOR
WITH SHIELD
DOOR
COVER
SERVICECOVER
FULLY HINGED
THROUGH
METER SECTION
PADLOCKBRACKETEXTENDS
REMOVEABLETEST BYPASSBLOCK COVER
(IF APPLICABLE)
Pad-mount Base or (4) 5/8-11 X 18" Anchor Bolts Recommended
CP-16PDMNT-CALTCP-16PDMNT-CALT
23 7/8" UTILITYTERMINATIONLANDING MIN.
N.E.C 110-16TYPICAL
FRONT & BACK
MINIMUM DEPTH.ALL SIDES. 6" REC.
FOUNDATION EXTENSION RECOMMENDED MIN.3"
36" MIN.CLEARANCE
REQUIRED PER
17"ENCLOSURE
DEPTH
CP-16PDMNT-CALTMOUNTING BASE
POCKETPRINT
HINGEDEXTERIORDOOR
40 1/2"
32 1/4"
Pad-mount Base or (4) 5/8-11 X 18" Anchor Bolts Recommended
WITH SHIELD(IF APPLICABLE)
COVERSERVICELIFT-OFF
SECURITYDOOR FOR THROUGH
LATCH HASPEXTENDS
PHOTO CELL WINDOW
HINGEDDEADFRONT
CP-16PDMNT-CALTMOUNTING BASE
MOUNTING HOLES
SECTION
UTILITY
MOUNTING BASE DETAIL
CUSTOMER
MOUNTING HOLESANCHOR BOLT
SECTION
PEDESTAL
14 1/2"12 1/4"
9 3/4"
16"15"
14 1/2"
13"
16"
6 3/4"
“A” Style 16" Metered Commercial Pedestal
“E” Style 16" Unmetered Commercial Pedestal | Low Profile
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
21
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
METERED ENCLOSEDCONTROLSDRAWING
Enclosed Controls16"- 24" Metered Commercial Pedestal Drawings
CLEARANCEREQUIRED PER
N.E.C 110-16
DEPTHENCLOSURE
17"
TYPICALFRONT & BACK
36" MIN.
3" RECOMMENDED MIN.FOUNDATION EXTENSIONALL SIDES. 6" REC.MINIMUM DEPTH.
23.5" UTILITYTERMINATIONLANDING MIN.
42"
MOUNTING BASE
UTILITY
SECTION
SECTION
CUSTOMER
PEDESTALMOUNTING HOLES
MOUNTING BASE DETAIL
12 1/4"14 1/2"
22 1/2"
21"
23"
24"
6 3/4"
9 3/4"16"
MOUNTING BASE
DEADFRONT
THROUGH
SECURITY
(IF APPLICABLE)
COVER
HINGED
PHOTO CELL WINDOW
FULLY HINGED
WITH SHIELD
FOR
METER SECTION
24" COMMERCIAL PEDESTAL
COVERSERVICELIFT-OFF
DOOR
PADLOCKBRACKETEXTENDS
REMOVEABLETEST BYPASSBLOCK COVER
(IF APPLICABLE)
WINDOWWITH
COVER
HINGEDDEMANDMETERRESET
HINGED EXTERIOR DOORWITH DOOR STOP TO HOLDDOOR IN OPEN POSITION
48"
“B” Style 24" Metered Commercial Pedestal
3" RECOMMENDED MIN.FOUNDATION EXTENSION
ALL SIDES. 6" REC.MINIMUM DEPTH.
36" MIN.CLEARANCE
REQUIRED PERN.E.C 110-16
TYPICALFRONT & BACK
17"ENCLOSURE
DEPTH
WITH SHIELD(IF APPLICABLE)
PHOTO CELL WINDOW
SEALABLEPAD LOCKABLEMETER COVER
48"
16"
40"
MOUNTING BASE
FOR SECURITY
(EXPOSED METER)16" COMMERCIAL PEDESTAL
COVERSERVICELIFT-OFF
PADLOCKBRACKETEXTENDSTHROUGH
DOOR
HINGEDDEADFRONT
23.5" UTILITYTERMINATIONLANDING MIN.
17"
MOUNTING BASE
UTILITY
MOUNTING BASE DETAIL
SECTION
PEDESTALMOUNTING HOLES
CUSTOMERSECTION
9 3/4"
16"15"
14 1/2"
13"
16"14 1/2"
12 1/4"
6 3/4"
“P” Style 16" Metered Commercial Pedestal
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
22
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
UNMETERED ENCLOSED CONTROLSDRAWING
Enclosed Controls24" Unmetered & Metered Commercial Pedestal Drawings
22 1/2"UTILITY
TERMINATIONLANDING
3" RECOMMENDED MIN.FOUNDATION EXTENSIONALL SIDES. 6" RECOMMENDEDMINIMUM DEPTH.
CUSTOMERSECTION
MOUNTING BASE DETAIL
“M” Style 24" Metered Commercial Pedestal
LIFT-OFFSERVICECOVER
PADLOCKBRACKETEXTENDSTHROUGH
DOORFOR
SECURITY
PHOTO CELL WINDOWWITH SHIELD
(IF APPLICABLE)
HINGEDDEADFRONT
PRINTPOCKET
HINGED EXTERIOR DOORWITH DOOR STOP TO HOLDDOOR IN OPEN POSITION
MOUNTING BASE MOUNTING BASE
UTILITY TERM.SECTION
36" MIN.CLEARANCE
REQUIRED PERN.E.C 110-16
TYPICALFRONT & BACK
21 1/2"
12 1/4"
15 3/8"
17"
""
6 1/2"
14 1/4"
24"
22 1/2"
1 7/8"1 1/2"
21"
Pad Mount Base or (4) 5/8-11 X 18" Anchor Bolts Recommended
CP-24PDMNT-CALTCP-24PDMNT-CALT
“M” Style 24" Unmetered Commercial Pedestal
“R” Style 24" Metered Commercial Pedestal
3" RECOMMENDED MIN.FOUNDATION EXTENSION
ALL SIDES. 6" REC.MINIMUM DEPTH.
36" MIN.CLEARANCE
REQUIRED PERN.E.C 110-16
TYPICALFRONT & BACK
17"ENCLOSURE
DEPTH
MOUNTING BASEMOUNTING BASE
SERVICECOVER
LIFT-OFF
SECURITYFOR
PADLOCKBRACKETEXTENDSTHROUGH
DOOR
HINGEDDEADFRONT
TERMINATION23.5" UTILITY
LANDING MIN.
17"
MOUNTING BASE DETAIL
SECTIONUTILITY
PEDESTALMOUNTING HOLES
CUSTOMERSECTION
12 1/4"
24"
23"
22 1/2"
21"
16"14 1/2" 9 3/4"
6 3/4"
WITH SHIELDPHOTO CELL WINDOW
(IF APPLICABLE)
SEALABLEPAD LOCKABLEMETER COVER
40"
48"
24"
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
23
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
UNMETERED & METERED
DRAWINGS
Enclosed Controls32" Unmetered & Metered Commercial Pedestal Drawings
“K” Style 32" Metered Commercial Pedestal
CLEARANCEREQUIRED PER
N.E.C 110-16
DEPTHENCLOSURE
17"
TYPICALFRONT & BACK
36" MIN.
3" RECOMMENDED MIN.FOUNDATION EXTENSIONALL SIDES. 6" REC.MINIMUM DEPTH.
POCKETPRINT
COVER
DOOR IN OPEN POSITION
WINDOW
HINGED EXTERIOR DOORWITH DOOR STOP TO HOLD
WITH
HINGEDDEMANDMETERRESET
RINGLESSMETER
SOCKET
53.0
6
8.043
DEADFRONT
THROUGH
COVERMETER SECTION
SECURITY
(IF APPLICABLE)
HINGED
PHOTO CELL WINDOW
FULLY HINGED
WITH SHIELD
FOR
COVERSERVICELIFT-OFF
DOOR
PADLOCKBRACKETEXTENDS
REMOVEABLETEST BYPASSBLOCK COVER
(IF APPLICABLE)
SECTION
MOUNTING BASE DETAIL
UTILITY
SECTIONCUSTOMER
PEDESTALMOUNTING HOLES
CUSTOMERSECTION
14 1/4"16 1/2"
30 1/2"
21"
31"
32"
7 3/4"
11 3/4"18"
MOUNTING BASEMOUNTING BASE
“Q” Style 32" Unmetered Commercial Pedestal
17"
TYPICALFRONT & BACK
N.E.C 110-16REQUIRED PER
CLEARANCE
ENCLOSUREDEPTH
36" MIN.
3" RECOMMENDED MIN.FOUNDATION EXTENSIONALL SIDES. 6" REC.MINIMUM DEPTH.
22 1/2"UTILITY
TERMINATIONLANDING
COVERSERVICE
Milbank Mounting Base
BACK VIEW
CP-32PDMNT
Recommended:
FRONT VIEW
LIFT-OFF
PRINTPOCKET
HINGED EXTERIOR DOORWITH DOOR STOP TO HOLDDOOR IN OPEN POSITION
34.4
4
43.5
"
0"
"30
32"
MOUNTING BASE MOUNTING BASE
CUSTOMER
UTILITYSECTION
SECTION
MOUNTING BASE DETAIL
PEDESTALMOUNTING HOLES
CUSTOMERSECTION
11 3/4"14 1/4"
16 1/2"
30 1/2"
29"
31"
32"
7 3/4"
18"
REAR DOORCUSTOMER
PAD LOCKABLE
UTILITYDOOR
(IF APPLICABLE)
SECURITY
WITH SHIELD
DOORFOR
PADLOCKBRACKETEXTENDSTHROUGH
PHOTO CELL WINDOW
HINGEDDEADFRONT
RIGHT VIEW
20"
8.98 ID
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
24
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Enclosed Controls32" Metered Commercial Pedestal Drawings
METERED DRAWINGS
3" RECOMMENDED MIN.FOUNDATION EXTENSION
ALL SIDES. 6" REC.MINIMUM DEPTH.
DEPTHENCLOSURE
17"
REQUIRED PERN.E.C 110-16
TYPICAL
36" MIN.CLEARANCE
FRONT & BACK
PHOTO CELL WINDOWWITH SHIELD
(IF APPLICABLE)
SEALABLEPAD LOCKABLEMETER COVER
"52
"32
60"
SECTION
CUSTOMER
UTILITY
SECTION
MOUNTING BASE DETAIL
PEDESTALMOUNTING HOLES
UTILITYSECTION
14 1/4"
32"31"
30 1/2"
29"
18"16 1/2" 11 3/4"
7 3/4"
MOUNTING BASEMOUNTING BASE
SERVICECOVER
LIFT-OFF
SECURITYFOR
(2)PADLOCKBRACKETSEXTENDSTHROUGH
DOOR
HINGEDDEADFRONT
TERMINATIONLANDING MIN.
23.5" UTILITY
20"
“S” Style 32" Metered Commercial Pedestal (with one or two meters)
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
25
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Enclosed Controls32"- 42" CT Rated Commercial Pedestal Drawings
CT RATED METERED
DRAWINGS
“Z” Style 32" Metered Commercial Pedestal - CT Rated
“T” Style 42" Metered Commercial Pedestal - CT Rated
3.00 RECOMMENDED MIN.FOUNDATION EXTENSIONALL SIDES. 6" RECOMMENDEDMINIMUM DEPTH.
POCKETPRINT
8.00" x 8.00"VIEWING WINDOW
(INSIDE)
HINGED EXTERIOR DOORWITH DOOR STOP TO HOLDDOOR IN OPEN POSITION
42.00"
"40
.53
64.
00
C C N.E.C. 110-6
FRONT & BACK
REQUIRED PERCLEARANCE
TYPICAL
MOUNTING DETAIL
36" MIN.
MOUNTING BASECP-42X27PDMNT
CHECK WITH LOCAL UTILITYTO DETERMIND IF LUGS ORSTUDS ARE REQUIRED FOR FIELD WIRING.
handle
HINGED
THROUGH
LIFTING EYESMETER SECTION
COVER
DOOR
SECURITYFOR
DEADFRONT
PADLOCKBRACKETEXTENDS
Padlockable 1/4 turn
FULLY HINGED
9.3127
15.19
STUD
DOOR IDTO
" DEEP
7.33 "
43.64"TO BOTTOM
OF LUG
SECTION C-C
UTILITYSECTION
CUSTOMERSECTION
13 3/4"
21.
50
40 1/2"
27" ENCLOSURE
DEPTH
42.00"
3.00 RECOMMENDED MIN.FOUNDATION EXTENSIONALL SIDES. 6" RECOMMENDEDMINIMUM DEPTH.
FRONT & BACK
METER SECTION
MOUNTING DETAIL
36" MIN.
REQUIRED PER
TYPICAL
CLEARANCE
COVER
N.E.C. 110-6
MOUNTING BASECP-32X24PDMNT
FULLY HINGED
DESCRIPTION
SCALE 1 : 12SECTION C-C
SECTIONUTILITY
CUSTOMERSECTION
.7530 9/16"32 1/8"
1 1/2"
19 1/4"
13 3/4"
1 7/8"
24" ENCLOSURE
DEPTH
PRINTPOCKET(INSIDE)
COVERWITH
WINDOW
HINGEDDEMANDMETERRESET
HINGED EXTERIOR DOORWITH DOOR STOP TO HOLDDOOR IN OPEN POSITION
32.00"
"40
.53
64.
00
CC
THROUGH
PADLOCKABLE 1/4 TURN HANDLE
DEADFRONT
SEALING PROVISION PROVIDED ON EACH UTILITY DOOR
SECURITYFOR
WIRE SUPPORT
SINGLE STUD LANDING
DOOR
PADLOCKBRACKETEXTENDS
HINGED
LIFTING EYES
24
9.31
12.00
CONNECTOR
" DEEP
15.11
OF
42.00"TO BOTTOM
4.00"STUDTO
DOOR ID
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
26
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Enclosed Controls46" CT Rated Unmetered Commercial Pedestal Drawings
CT RATEDUNMETERED DRAWINGS
“W” Style 46" Metered Commercial Pedestal - CT Rated
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
27
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Enclosed Controls44" Unmetered Commercial Pedestal Drawings
UNMETEREDDRAWINGS
“D” Style 44" Unmetered Commercial Pedestal
AA
DESIGN FOR 19”RACK MOUNTABLEEQUIPMENT
WITH DOOR STOP TO HOLDDOOR IN OPEN POSITION
POCKETPRINT
HINGED EXTERIOR DOOR
3-POINT CAM LATCHPADLOCK-ABLE
44”
FRONT
5/8 ANCHOR BOLT PLACEMENT
BACK
60”
24”
SECTIONUTILITY
SECTIONCUSTOMER
SCALE 1 : 14SECTION A-A
CUSTOMERSECTION
16.000
21.5
31
16.00
39.50
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
28
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Enclosed Controls12" & 20" Slimline Pedestal Drawings
SLIMLINEDRAWINGS
“B” Style 20" Covered Metered Commercial Pedestal - Slimline
“A” Style 12" Covered Metered Commercial Pedestal - Slimline
3"RECOMMENDED MIN.
FOUNDATION EXTENTIONALL SIDES. 6" RECMINIMUM DEPTH
36" MIN.CLEARANCE
REQUIRED PERN.E.C. 110-16
TYPICALFRONT & BACK
20.00"PEDESTAL WIDTH
10.25"ENCLOSURE
DEPTH
58.624"
SECTIONCUSTOMER
BASE DETAIL
SCALE 1 : 12
MOUNTING
SECTION C-C
UTILITYSECTION
5.250"
16.00"
8.0
0
7.0
0
14.438"
LEFT-OFFSERVICECOVER
SERVICETERMINATIONLINE/LOAD350-#6
42.
734"
26.00" UTILITYTERMINATIONLANDING MIN.
12.
00"
CP-20-PADPART NUMBER
MOUNTING BASEAND HARDWARE
Wednesday, September 02, 2015 10:02:13 AM tbennett
Shear/Die No.:
TB
B-Size CP3A Outline
Paint Qty.:
LBS. EA.
TB
X.XXXX
STEEL
**
GRAMS
TB1 of 2
B-Size CP3A Outline
Material:
Finish:
Catalog No.:
Title:
Customer:
Drawing No.:
KANSAS CITY, MO
GALVANIZED, 14 GA STAINLESS
METERED SLIM LINE
02-15-13 Sheet:
Tolerances:
2DESCRIPTION
X.XX.XX
USA
Drawn By:
Scale: NTSDate:
.125 ALUMINUM, 14 GA
.015
.03
.1
Third Angle
Checked By:
Part Wt.:
DATE BY
A02-15-1309/02/15
FIRST RELEASEMAKE 2 INCHES DEEPER
Unless Specified Otherwise
B-SIZE, 63T x 20W x 10.25W,
Approved By:
REV. ECO No.
20" COMMERCIAL PEDESTAL
FOR
BRACKET
DRAW LATCH
DOOR
FULLY HINGED
WINDOW
HINGED DEAD FRONT
SECURITY
EXTENDS
METER SECTION
THROUGH
PADLOCKABLE
SLIM LINE 63 INCH TALL
WITH SHIELD
COVER
(IF APPLICABLE)
(1.75")
PADLOCK
PHOTO CELLKNOCKOUT
REMOVEABLETEST BYPASSBLOCK COVER(IF APPLICABLE)
C C
WINDOWWITH
HINGEDDEMANDMETERRESETCOVER
PRINTPOCKET
21.125"
20.00"
63.00"
3"RECOMMENDED MIN.
FOUNDATION EXTENTIONALL SIDES. 6" RECMINIMUM DEPTH
36" MIN.CLEARANCE
REQUIRED PERN.E.C. 110-16
TYPICALFRONT & BACK
12.00"PEDESTAL WIDTH
8.25"ENCLOSURE
DEPTH
LIFT-OFFSERVICECOVER
SERVICETERMINATIONLINE/LOAD350-#6
42.
734"
26.00" UTILITYTERMINATIONLANDING MIN.
12.
00"
BASE DETAILMOUNTING
SCALE 1 : 12
CUSTOMERSECTION
SECTION C-C
UTILITYSECTION
5.078"
8.00"
6.0
0
5.0
0
6.610"
BLOCK COVER(IF APPLICABLE)
(1.75")WINDOW
HINGED
SLIM LINE 63 INCH TALL12" COMMERCIAL PEDESTAL
SECURITYFOR
DOORTHROUGHEXTENDSBRACKET
(IF APPLICABLE)
FULLY HINGED
WITH SHIELD
COVERMETER SECTION
DEAD FRONT
PADLOCK
PHOTO CELLKNOCKOUT
REMOVEABLETEST BYPASS
PADLOCKABLEDRAW LATCH
C C
MOUNTING BASE AND HARDWAREPART NUMBERCP-12-PAD2
A-Size CP3A Outline
A-Size CP3A Outline
2
Material:
Finish:
Catalog No.:
Title:
Ref:
Drawing No.:
General Offices:
Drawn By:Scale: NTS
Date: Sheet 1 of 10-10-12
Kansas City, MO
Tolerances:Unless Specified OtherwiseX.XX.XXX.XXXX 2
.015
.03
.1
Third Angle
Projection
Checked By:Approved By:
SLIM LINE PEDESTAL
04-14-13 *
FIRST RELEASE 10-10-12 TB
TB FIRST DRAFT
**
A-Size, 63T x 12W x 8.25W12" WIDE METERED
WITHWINDOW
HINGEDDEMANDMETERRESETCOVER
PRINTPOCKET
13.13"
12.00"
63.00"
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
29
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Enclosed Controls12" & 20" Exposed Meter Slimline Pedestal Drawings
“L” Style 20" Exposed Meter Commercial Pedestal - Slimline
“K” Style 12" Exposed Meter Commercial Pedestal - Slimline
SLIMLINEDRAWINGS
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
30
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
FOUNDATION EXTENTION
20.00"PEDESTAL WIDTH
MINIMUM DEPTHALL SIDES. 6" REC
3"RECOMMENDED MIN.
10.25"ENCLOSURE
DEPTH
LBS. EA.
GRAMS
P-Size CP3A Outline
Material:
Finish:
Catalog No.:
Title:
Customer:
Paint Qty.:
USA
Drawn By:
Scale: NTS Drawing No.:
KANSAS CITY, MO
GA STAINLESS STEEL
CP3A P-SIZE
Sheet: 1 of 108/13/15
Tolerances:Unless Specified Otherwise
X.XX.XX
Date:
X.XXX
.125 ALUMINUM, 14 GA STEEL, 14
P-Size CP3A OutlineX 2.015.03.1
Third Angle
Checked By:
Approved By:
Part Wt.:
REV. DATE DESCRIPTION BY
**A
10-15-1310/12/15
FIRST RELEASE2 INCHES DEEPER
TBTB
Monday, October 12, 2015 4:05:02 PM tbennett
Shear/Die No.:
TB
ECO No.
CP-20-PADPART NUMBER
MOUNTING BASEAND HARDWARE
DEAD FRONT
SECURITY
HINGED
NON METERED SLIM LINE 43" TALL20" COMMERCIAL PEDESTAL
THROUGHDOORFOR
(IF APPLICABLE)WITH SHIELD
EXTENDSBRACKETPADLOCK
PHOTO CELLKNOCKOUT(1.75")WINDOW
PADLOCKABLEDRAW LATCH
C CSERVICECOVER
LEFT-OFF
SERVICETERMINATIONLINE/LOAD350-#6
42.
734"
26.00" UTILITYTERMINATIONLANDING MIN.
12.
00"
SCALE 1 : 12
CUSTOMER
BASE DETAILMOUNTING
SECTION
SECTION C-C
UTILITYSECTION
7.0
0
5.250"
16.00"
8.0
0
14.438"PRINTPOCKET
43.
00"
20.00"
Enclosed Controls12" & 20" Unmetered Slimline Pedestal Drawings
“P” Style 20" Unmetered Commercial Pedestal - Slimline
“O” Style 12" Unmetered Commercial Pedestal - Slimline
SLIMLINEDRAWINGS
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
31
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
ENCLOSED CONTROLS
APPLICATIONEXAMPLES
Enclosed Controls Application Examples
Location: Skykomish, WA
Description: EV charging station at Stevens Pass Ski Resort. Mountain pass is on WA Highway 2, which connects Seattle to Wenatchee.
Location: Kansas City, MO
Description: Demonstrating one of the 500 plus utility-sponsored
installations of electric vehicle charging stations in Kansas City, Mo.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
32
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Enclosed Controls Application Examples
Location: North Carolina
Description: 12-inch exposed meter pedestal used for traffic applications.
Location: North Carolina
Description: Another 12-inch exposed meter slimline pedestal.
Location: Atlanta, GA
Description: Intersection near the Atlanta Braves stadium in Atlanta, Ga. uses 16-inch exposed meter pedstal to manage the intersection traffic control.
APPLICATIONEXAMPLES
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
33
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Enclosed Controls Application Examples
Location: Sandusky, OH
Description: Customer had a dilapidated, unsafe wood backboard system with meter sockets, CT rated meter socket and several disconnects.
Milbank installed a secure pedestal with breakers inside. The system powers the lights and supports power to the concession stand and scoreboard.
Due to original service being overhead, the customer decided to keep the overhead service with a cost-effective termination box to feed the enclosed controls cabinet, rather than replacing the entire system. The results are safe, secure and aesthetically pleasing.
BEFORE
AFTER
APPLICATIONEXAMPLES
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
34
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed Controls Application Examples
Location: Huntington Beach, CA
Description: This Milbank pedestal supplies power for the Wells Fargo ATM parking lot kiosk, the irrigation controller and overhead lighting. In addition to the power distribution equipment, the pedestal has an isolated compartment for phone company lines. The Telco 24V equipment must be kept separate from the high voltage 120V equipment. Steel powder painted.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
35
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed ControlsApplication Examples
Location: Mission Viejo, CA
Description: The Milbank pedestal is supplying power for the irrigation and pump control to its left. Also includes walkway lighting control equipment. Anodized aluminum.
Location: Costa Mesa, CA
Description: Milbank commercial pedestal
supplying power for an underground telephone equipment vault. Meter
socket, generator receptacle and surge
protection are all installed inside this pedestal.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
36
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed ControlsApplication Examples
Location: Lacy, WA
Description: A traffic signal control cabinet stands next to
a Milbank power supply and street lighting control pedestal.
Mounted on a raised pad for winter snow conditions.
Anodized aluminum.
Location: Cleveland, OH
Description: Milbank pedestals were supplied for Rapid Transit Bus Stops to provide security and normal lighting. Pedestals looped together for efficiency.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
37
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed ControlsApplication Examples
Location: Interstate 70, MO
Description: Milbank pedestal providing remote distribution for Dynamic Message Signs along I-70 between Kansas City and St. Louis, Mo. Operated through MoDOT, these stationary traffic control devices provide travelers with real-time traffic-related messages.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
38
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed ControlsApplication Examples
Location: Manchester, TN
Description: Milbank pedestals used for annual outdoor music and arts festival. Operating in remote farmland, multiple pedestals provide temporary power receptacles for organizer’s use. Shown with in-use cover, which allows for security and safety for receptacles in use.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
39
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed ControlsApplication Examples
Location: Rio Rancho, NM
Description: Battery backup pedestal that contains an inverter and batteries providing uninterrupted power to traffic signals at a busy intersection in the event of utility power failure. The Milbank pedestal supplies power for the intersection signal heads and the control cabinet using utility power and, if necessary, a backup system. The batteries can run the entire intersection traffic lights for four hours in full operation mode and an additional four hours in flashing mode. Aluminum powder painted tan.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
40
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed ControlsApplication Examples
Location: Anaheim, CA
Description: Disneyland parking lot lighting and control. Two pedestals were provided as customer required both 120V and 480V. Steel painted green.
Location: Dubuque, IA
Description: Parking lot lighting power and control application.
Steel painted black.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
41
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed ControlsApplication Examples
Location: Kansas City, MO
Description: Multiple pedestal locations throughout the Zona Rosa Shopping Center provide street lighting and traffic signal distribution.
Location: Atlanta, GA.
Description: Right outside the Atlanta Falcons arena
stands a Milbank exposed meter lighting pedestal.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
42
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must
comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed ControlsApplication Examples
Location: Kansas City, MO
Description: Multiple pedestal locations at Kansas City International Airport provide lighting distribution for rental car facility parking lot.
Location: Anaheim, CA
Description: Milbank pedestal supplying power for the traffic signal cabinet (seen in picture).
Pedestal also holds the control equipment for the intersection and roadway street lighting.
Anodized aluminum.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
43
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility, and may require local electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
APPLICATIONEXAMPLES
Enclosed ControlsApplication Examples
Location: Louisville, KY
Description: The Parklands of Floyd’s Fork multi-phase park project. Provides power and automated controls for area and walkway lighting. Includes receptacles for temporary power for concerts, festivals and other events.
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com ENCON 2/20