The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
EXSULATION® L5000Lamella Non Combustible EIFS
DSC5002
Exsulation L5000System Installation Details
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Exsulation® L5000 Table of Contents
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
NOTEDRYVIT MAKES NOREPRESENTATION REGARDINGCONFORMITY OF ITSSUGGESTIONS TO APPLICABLEBUILDING CODES, ENGINEERINGCRITERIA, SPECIFICAPPLICATIONS OR PROJECTLOCATIONS. ALL COMPONENTSINDICATED IN ILLUSTRATIONS, ASWELL AS OTHERS THAT MAY BEREQUIRED FOR THE INTEGRITYOF THE SYSTEM SHALL BEDESIGNED, DETAILED ANDENGINEERED BYREPRESENTATIVES OF THEARCHITECT, OWNER ORCONTRACTOR TO BE INCONFORMANCE WITH MODELCODES, ARCHITECTURAL ANDENGINEERING REQUIREMENTSPERTAINING TO SPECIFICBUILDING PROJECTS.
DRYVIT MAKES NO WARRANTY,EXPRESSED OR IMPLIED, AS TOTHE ARCHITECTURAL DESIGN,ENGINEERING, OR WORKMANSHIPOF PROJECTS UTILIZING DRYVITSYSTEMS OR PRODUCTS.
THE LIABILITIES OF DRYVIT SHALLBE AS STATED IN THEEXSULATION L5000 LIMITEDCOMMERCIAL WARRANTY.CONTACT DRYVIT FOR A FULLAND COMPLETE COPY OF THEWARRANTY.
DETAIL
EXL.0.0.01 NORMAL AND HIGH IMPACT
EXL.0.0.02 LAMELLA SLAB LAYOUT
EXL.0.0.03 FOUNDATION WITH DRAINAGE STRIP - EXTENDED 2D VIEW
EXL.0.0.04 HEAD/SILL
EXL.0.0.05 HEAD/SILL FOR SELF FLASHING WINDOW OPTIONS
EXL.0.0.06 PROTECTION OF ROUGH OPENINGS
EXL.0.0.07 ROUGH OPENING AND SILL PREPARATION - AQUAFLASH ® SYSTEM
EXL.0.0.08 JAMB
EXL.0.0.09 PARAPET - CAP FLASHING
EXL.0.0.10 PARAPET/ WALL TERMINATION
EXL.0.0.11 PARAPET - SOLID SUBSTRATE
EXL.0.0.12 SOFFIT/FASCIA INTERSECTION
EXL.0.0.13 SOFFIT - UNINSULATED
EXL.0.0.14 INSIDE/OUTSIDE CORNERS
EXL.0.0.15 OUTSIDE CORNER - HIGH IMPACT
EXL.0.0.16A FLOORLINE DETAIL - APPLICATION SEQUENCE
EXL.0.0.16B HORIZONTAL SLIP JOINT - EXTENDED 2D VIEW
EXL.0.0.17 HORIZONTAL SLIP JOINT
EXL.0.0.18 TWO-STAGE JOINT - EXTENDED 2D VIEW
EXL.0.0.19 STRUCTURAL EXPANSION JOINTS
EXL.0.0.20 PENETRATIONS
EXL.0.0.21 WALL PENETRATIONS
EXL.0.0.22 SIGN ATTACHMENT
EXL.0.0.23 AESTHETIC REVEALS
EXL.0.0.24 HORIZONTAL JOINT AT STONE VENEER
EXL.0.0.25 SOFFIT VENT
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Exsulation® L5000 EXL.0.0.01
Normal and High Impact
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposedto abnormal stress, hightraffic, or deliberateimpact have the basecoat reinforced withPanzer® 15 or 20 Meshprior to Standard PlusMesh. Location of highimpact zones should beindicated in contractdrawings.
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
NORMAL IMPACT
HIGH IMPACT
Primus® DM Adhesive ribbons
Dryvit Secondary Barrier
Approved mechanical fastener
Lamella (6" strips)
Primus DM Basecoat
Dryvit reinforcing mesh
Primus DM Basecoat
Dryvit finish
Backwrap
Dryvit Secondary Barrier
Approved mechanical fastener
Lamella (6" strips)
Primus DM Basecoat
Dryvit reinforcing mesh
Primus DM Basecoat
Dryvit finish
Backwrap
Primus DM Basecoat
Dryvit reinforcing mesh
Substrate
Primus DM Adhesive ribbons
Substrate
152.
4mm
(6")
152.
4mm
(6")
R-002-07-08
EXL.0.0.02
Lamella Slab Layout
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:
1. Fasteners required inconjunction with adhesiveon first row and everyfourth row thereafter asshown.
2. Standard PB fastener andwasher required.
Exsulation® L5000
Approvedmechanicalfastener andplate
Substrate
Ensure thatfibre orientationis perpendicularto the substrate
90°
Substrate
Fibre
R-002-07-08
Exsulation® L5000 EXL.0.0.03
Foundation with Drainage Strip - Extended 2d View
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
610
mm
(2'-0
") m
ax. (
see
note
2)
200m
m (8
") m
in.
Dryvit water-resistivebarrier coating
Dryvit adhesive in verticalnotched trowel configuration
applied to lamella
Slope grade away fromfoundation wall
Dryvit basecoat
Dryvit reinforcing mesh
Dryvit finish
Dryvit Backstop™ NT overGrid Tape
Dryvit Drainage Strip adhered withdabs of AP Adhesive (see note 3)
Dryvit Detail Mesh™ wrappedto backside of lamella min.63.5 mm (2 12")
Dryvit Aquaflash® applied overDryvit water-resistive barriercoating at foundation (see note 2)
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 Mesh prior toStandard Plus Mesh.Location of high impactzones should be indicatedin contract drawings.
2. Expansion joint is requiredalong top of foundation if610mm (2'-0") dimension isexceeded.
3. Ensure bottom edge ofDrainage Strip is left free todrain.
4. Notched trowel sizeminimum of 12" x 12", bymaximum 2" on centre.
5. Adhesive applied to thelamellas.
Lamella
Sheathing
R-002-07-08
Exsulation® L5000 EXL.0.0.04
Head/Sill
Sill Pan Flashing Detail
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:1. Dryvit recommends that ground floor applications
and all facades exposed to abnormal stress, hightraffic, or deliberate impact have the base coatreinforced with Panzer® 15 or 20 mesh prior toStandard Plus mesh. Location of high impactzones should be indicated on contract drawings.
DRYVITEXSULATIONL5000 SYSTEM
BY OTHERS
Approved substrate
Dryvit water-resistive barrier coating
Dryvit adhesive in vertical notched trowelconfiguration applied to lamella
Lamella insulation notched to accommodateDrainage Strip, flashing, and AquaFlash® System
Wrap Dryvit Detail Mesh wrapped tobackside of lamella min. 63.5 mm (2 12")
Dryvit Demandit™ or ColorPrime™ on surface(s) to receivesealantDryvit compatible sealant with closed cell backer-rodand weep tubes every 600 mm (24"), by others
19 mm (3/4") min.
Continuous flashing, by others
Fillet caulk with bond breaker, by others
Dryvit AquaFlash System
Wrap Dryvit Detail Mesh™ wrapped tobackside of lamella min. 63.5 mm (2 12")
Continuous pan flashing with end dams, byothers, see detail below
Dryvit compatible sealant, by others
Dryvit Drainage Stripset in dabs of AP Adhesive
See Protection of RoughOpening as per EXS.0.0.06
and EXS.0.0.07
Provide air seal,by others, aroundinterior of window
per windowmanufacturer's
requirements
38mm(1-1/2") min.
Dryvit reinforcing mesh embedded in base coatDryvit finish
R-002-07-08
Exsulation® L5000 EXL.0.0.05
Head/Sill for Self Flashing Window Options
Notes:1. Dryvit recommends that ground floor
applications and all facades exposed toabnormal stress, high traffic, or deliberateimpact have the base coat reinforced withPanzer® 15 or 20 mesh prior to Standard Plusmesh. Location of high impact zones should beindicated on contract drawings.
2. Additional head flashing may be necessary forwindows that are not self flashing. Drainable Sill Option
Approved substrateDryvit water-resistive barrier coatingDryvit adhesive in vertical notched trowelconfiguration applied to lamellaLamella insulation notched to accommodateDrainage Strip, flashing, and AquaFlash®
Dryvit Demandit™ or Color Prime™ onsurface(s) to receive sealant
Dryvit compatible sealant with closed cell backer-rodand weep tubes every 600 mm (24"), by others
19 mm (3/4") min.
Window integral flashing
Dryvit compatible sealant, by others
Dryvit Demandit or Color Prime onsurface(s) to receive sealant
Wrap Dryvit Detail Mesh 63.5 mm (2 12")min. at backside of lamella
Dryvit Drainage Strip set indabs of AP Adhesive
Dryvit AquaFlash meshembedded in Dryvit AquaFlash
Liquid lapped over window flange
19 mm (3/4") min.
Provide air seal, by others,around interior of window
per window manufacturer'srequirements
Wrap Dryvit Detail Mesh™ 63.5 mm (21
2") min. at backside of lamella
Dryvit AquaFlash System
DRYVIT EXSULATIONL5000 SYSTEM
BY OTHERS
Sill pan flashing, by others
Dryvit water-resistivebarrier coating
Dryvit AquaFlash
Transition flashing
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Dryvit reinforcing mesh embedded in base coatDryvit finish
See Protection of Rough Openingas per EXS.0.0.06 and EXS.0.0.07
R-002-07-08
Exsulation® L5000 EXL.0.0.06
Protection of Rough Openings
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Application Sequenceand Notes:
1. Apply WRB over sheathingand into rough opening.
2. Embed Detail Mesh™ intoWRB, stopping at sill.Embed diagonal mesh asshown at all corners.
3. Once embedment iscomplete, apply WRB overremainder of the substrateas illustrated.
4. Apply AquaFlash® andAquaFlash mesh as perDSC196 - Sills only if WRBis applied around thebalance of the roughopening.
AquaFlash is applied using abrush or deep-nap roller. EmbedAquaFlash Mesh into wetAquaFlash and allow to set.
Apply second coat fully coveringthe AquaFlash Mesh.
Alternatively, Dryvit's Flashing tape or EIFS tape maybe used and is applied aroundthe entire rough opening, but notreturning to the header. Seeillustration below.
* Water-resistive barrier to beapplied over EIFS tape with apositive lap of 2" minimum.
2
63.5mm(2 12") min.
63.5mm (2 1 2") min.
Substrate andsheathing assembly
3Dryvit
AquaFlashSystem
4
1
EIFS Tape Application
Apply 1st
2nd3rd
4th*(See Note)
R-002-07-08
Exsulation® L5000 EXL.0.0.07
Rough Opening and Sill Preparation - AquaFlash System
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:
1. The AquaFlash System is acombination of AquaFlashLiquid used in conjunction withAquaFlash Mesh to sealsubstrates around windows,doors and other openings.
2. Install AquaFlash System(including diagonal "butterflies")onto sill and allow to dry.
3. Alternatively, Dryvit FlashingTape or EIFS tape may beused.
Step #1 Step #2
Step #4
Install AquaFlash®System at sill (seenote 2)
Step #3
Step #5
Install DryvitAquaFlash Meshembedded inAquaFlash at headand over upturnedpan flanges
63.5mmmin.
Install sill panflashing
Install DryvitAquaFlash Meshembedded inDryvit water-resistivebarrier coating atjambs.
Installflashingsat head
Refer to EXS.0.0.08for jamb detail
Apply AquaFlashMesh and
AquaFlash overFlashing
R-002-07-08
Exsulation® L5000 EXL.0.0.08
Jamb
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
DRYVITEXSULATION
L5000 SYSTEM
Dryvit water-resistivebarrier coating
Dryvit Grid Tape inDryvit water-resistivebarrier coating
Continuous Dryvitcompatible sealant andclosed cell backer-rod,by others
Dryvit Demandit™ orColor Prime™ on surfacesto receive sealant
Dryvit adhesive invertical notched trowelconfiguration applied atbackside of lamella
Wrap Dryvit Detail Mesh™63.5 mm (2 12") min. atbackside of lamella
Dryvit reinforcing meshembedded in base coat
19 mm(3/4") min.
BY OTHERS
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer®15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
Lamella
Dryvit finish
ApprovedSubstrate
Air Seal
R-002-07-08
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
Exsulation® L5000 EXL.0.0.09
Parapet - Cap Flashing
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
BY OTHERS
Roofassembly
Metal cap flashing, by others
Dryvit AquaFlash® system
Dryvit compatible sealantwith bond breaker, by others(see note 2)
DRYVIT EXSULATIONL5000 SYSTEM
63.5 mm (2-1/2") min.
Wrap Dryvit Detail Mesh™63.5 mm (2 12") min. atbackside of lamella
Approved substrate
Dryvit water-resistivebarrier coating
Dryvit adhesive in verticalnotched trowel configurationapplied to lamella
Lamella
Dryvit reinforcing meshembedded in base coat
Dryvit finish
Framing
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposedto abnormal stress, hightraffic, or deliberateimpact have the basecoat reinforced withPanzer® 15 or 20 meshprior to Standard Plusmesh. Location of highimpact zones should beindicated on contractdrawings.
2. Ensure parapet capping iswater tight if sealant is tobe applied here. Otherwiseextend capping overlap asrequired to avoid moisturemigration behind system.
Parapetcap sheet
R-002-07-08
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
EXL.0.0.10
Parapet/Wall Termination
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Exsulation® L5000
Parapet/Wall Termination
Notes:1. Dryvit recommends that ground floor applications and all façades exposed to abnormal stress, high traffic, or deliberate
impact have the base coat reinforced with Panzer ® 15 or 20 mesh prior to Standard Plus mesh. Location of high impactzones should be indicated on contract drawings.
2. Lap all flashing and water-resistant barriers in shingle fashion.3. Use Dryvit AquaFlash System at wall/sleeve transition.
Roofing System
Aluminium reglet
Dryvit Exsulation L5000 System
Metal copingflashing
at parapet wall
Flashing sleeveshown in exploded
view
Lamella
Dryvit AquaFlash® System
Dryvit Drainage Strip
Dryvit compatible sealant w/ closedcell backer rod and weep tubesevery 600 mm (24") by others.
Roof flashing and counterflashing, by others
4" (102mm)
6" (153mm)
6" (153mm)
4"(102mm)
R-002-07-08
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
Exsulation® L5000 EXL.0.0.11
Parapet - Solid Substrate
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
2. If system on back ofparapet exceeds 610mm(2'-0") in height, provisionsfor drainage are requiredalong wall base.
3. Ensure parapet capping iswater tight if sealant is tobe applied here. Otherwiseextend capping overlap asrequired to avoid moisturemigration behind system.
4. Install mechanical fixingsas per EXL.0.0.02.
BY OTHERS
Metal cap flashing(by others)
Wrap Dryvit Detail Mesh 63.5mm (2 12") min. at backside
of lamella
Dryvit compatiblesealant (by others)
Roof flashing andcounter flashing, by
others
Approved substrate
Roof assembly
200
mm
(8")
min
.
DRYVIT EXSULATIONL5000 SYSTEM
Dryvit AquaFlash® Mesh embeddedin AquaFlash Liquid as water-resistivebarrier coating
Wrap Dryvit Detail Mesh™63.5 mm (2 12") min. atbackside of lamella
Dryvit water-resistivebarrier coating
Dryvit adhesive in verticalnotched trowel configurationapplied to lamella
Dryvit compatiblesealant, by others(see note 3)
Lamella
Dryvit reinforcing meshembedded in base coat
Dryvit finish
63.5 mm (2-1/2") min.
Approved mechanicalfastener
Parapetcap sheet
R-002-07-08
Exsulation® L5000 EXL.0.0.12
Soffit/Fascia Intersection
19 mm (3/4") min.
DRYVIT EXSULATIONL5000 SYSTEMBY OTHERS
Approved substrate
Dryvit water-resistivebarrier coating
Dryvit adhesive invertical notched trowelconfiguration applied tolamella
LamellaDryvit reinforcing meshembedded in base coat
Dryvit finish
Dryvit reinforcing meshembedded in Dryvitwater-resistive barriercoating
Dryvit Drainage Strip
Wrap Dryvit Detail Mesh™63.5 mm (2 12") min. atbackside of lamella. Do notblock Drainage Strip withbase coat.
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
2. Bottom edge of DryvitDrainage Strip shall bemasked during installationto prevent clogging ofdrainage channels.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Approved mechanical fixing
R-002-07-08
Exsulation® L5000 EXL.0.0.13
Soffit - Uninsulated
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
2. Soffits without insulationrequire expansion jointsevery 6 m (20 ft).
3. Refer to Dryvit publicationDSC173 for specificrequirements for soffitareas.
4. Bottom edge of DryvitDrainage Strip shall bemasked during installationto prevent clogging ofdrainage channels.
Approved substrate
Dryvit water-resistivebarrier coatingDryvit adhesive in verticalnotched trowel configurationapplied to lamellaLamella
Dryvit reinforcing meshembedded in base coatDryvit finish
Wrap Dryvit Detail Mesh™63.5mm (2 12") min. atbackside of lamellaDryvit Drainage Strip™
25 mm (1") max.
Approved mechanical fixing
DRYVIT EXSULATIONL5000 SYSTEMBY OTHERS
Dryvit Detail Mesh embedded inDryvit water-resistive barrier coating
Dryvit reinforcing meshembedded in base coat
R-002-07-08
Exsulation® L5000 EXL.0.0.14
Inside/Outside Corners
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Approved substrate
Dryvit water-resistivebarrier coating
Dryvit adhesive invertical notched trowelconfigurationLamella
Reinforcing meshembedded in base coat
Dryvit finish
200mm (8") min.(see notes 2 and 3)
200mm (8") min.(see notes 2 and 3)
Must overlap 200 mm(8") min. See above andnotes 2 and 3
Approved substrate
Dryvit water-resistivebarrier coating
Lamella
Dryvit reinforcing meshembedded in base coat
Dryvit adhesive invertical notched trowelconfiguration
DRYVIT EXSULATIONL5000 SYSTEM
BY OTHERS
Dryvit reinforcingmesh embedded in
Dryvit water-resistivebarrier coating
Dryvit reinforcing meshembedded in Dryvitwater-resistive barriercoating
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
2. Double wrap outsidecorners with reinforcingmesh or use CornerMesh™.
3. Do not lap reinforcing meshwithin 200mm (8") of acorner.
R-002-07-08
Exsulation® L5000 EXL.0.0.15
Outside Corner - High Impact
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposedto abnormal stress, hightraffic, or deliberateimpact have the basecoat reinforced withPanzer® 15 or 20 meshprior to Standard Plusmesh. Location of highimpact zones should beindicated on contractdrawings.
200 mm(8") min.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Approved substrate
Dryvit water-resistivebarrier coatingDryvit adhesive in verticalnotched trowel configurationapplied to lamellaDryvit reinforcing meshembedded in Dryvitwater-resistive barrier coatingLamella
Dryvit base coat
Dryvit Panzer®reinforcing mesh
Dryvit base coat
Dryvit corner mesh
Dryvit Standard or StandardPlus reinforcing meshoverlap min. 200 mm (8") atcorner
Dryvit base coat
Dryvit finish
Corner render profile (optional)
R-002-07-08
Exsulation® L5000 EXL.0.0.16A
Floorline Detail - Application Sequence
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposedto abnormal stress, hightraffic, or deliberateimpact have the basecoat reinforced withPanzer® 15 or 20 meshprior to Standard Plusmesh. Location of highimpact zones should beindicated on contractdrawings.
Apply coat of Dryvitwater-resistive barrieronto substrate
2 Dryvit Aquaflash®System applied overDryvit water-resistivebarrier coating atfloorline joint
1
3 Apply Detail Mesh™at system terminationso to extend fullybehind insulation63.5 mm (2 12")
Dryvit base coat
Dryvit Mesh embeddedin base coat
Dryvit base coat
Lamella
Approved substrate
4Apply Dryvitadhesive to lamellain vertical notched
trowel configurationand allow to dry.
Closed-cellbacker-rod
Approved mechanical fixing
R-002-07-08
Exsulation® L5000 EXL.0.0.16B
Horizontal Slip Joint - Extended 2d View
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
2. Install fastener on first rowextending above slab. Usesupport/spacer block on firstrow until adhesive sets.
Approved substrate
Dryvit water-resistivebarrier coating
Dryvit Detail Mesh™ prewrappedand embedded in base coat
Dryvit base coat
Dryvit adhesive in verticalnotched trowelconfiguration applied tolamella
Dryvit mesh embeddedin base coat
Dryvit base coat
Dryvit finish
Slope bottom surfacefor positive drainage
Dryvit AquaFlash System lapped onto lowersection and terminating at sealant bond line.
Dryvit Drainage Strip adheredin dabs of AP Adhesive
Dryvit AquaFlash System
Closed cell backer-rod
Lamella insulation notchedto accomodate DrainageStrip and AquaFlash®System.
Approved mechanical fixing
Temporary spacer block
R-002-07-08
Exsulation® L5000 EXL.0.0.17
Horizontal Slip Joint
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Slip typeconnection
Approved substrate
Dryvit water-resistivebarrier coating
Dryvit adhesive in verticalnotched trowel configurationapplied to lamella
Lamella
Dryvit reinforcing meshembedded in base coatDryvit Drainage Strip
Dryvit finish
Dryvit compatible sealant withclosed cell backer-rod, by others
Slope bottom surface forpositive drainage
19 mm(3/4") min.
Dryvit Demandit™ or ColorPrime™ on surfaces to receivesealantWrap Dryvit Detail Mesh™63.5 mm (2 12 ") min. atbackside of lamella
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
2. Expansion joint in theExsulation L5000 System isnecessary where significantdifferential movement isexpected at floor lines.
3. Locate external sealant jointwithin 50 mm (2") of breakin sheathing.
4. Apply Dryvit AquaFlashSystem over prepared jointat change in substrate
Closed cellbacker-rod
DRYVIT EXSULATIONL5000 SYSTEM
BY OTHERS
Dryvit AquaFlash®System
Dryvit AquaFlash System appliedover top of previous coat and
extended towards bottom slopedsurface for drainage
Approved mechanical fixing
R-002-07-08
Exsulation® L5000 EXL.0.0.18
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Two-Stage Joint - Extended 2d
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposedto abnormal stress, hightraffic, or deliberateimpact have the basecoat reinforced withPanzer® 15 or 20 meshprior to Standard Plusmesh. Location of highimpact zones should beindicated on contractdrawings.
Sealant andbacker-rod
Exterior faceof system
Drain opening
Approved Substrate
Lamella
Backer-rod
Drainagespace
AquaFlash®System
Dryvit waterresistivebarrier coating50.8mm
(2") min.
25.4mm(1") min.
R-002-07-08
Exsulation® L5000 EXL.0.0.19
Structural Expansion Joints
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:1. Dryvit recommends that ground floor applications and all façades exposed to abnormal stress, high traffic, or deliberate
impact have the base coat reinforced with Panzer ® 15 or 20 mesh prior to Standard Plus mesh. Location of high impactzones should be indicated on contract drawings.
2. Sealant should not be in direct contact with the AquaFlash System.3. Apply water-resistive barrier over remainder of wall surface.
Interior seal, by others
Dryvit AquaFlash®System (see note 2)
Approved substrate
Dryvit water-resistivebarrier coatingDryvit adhesive in verticalnotched trowel configuration
Lamella
Dryvit finish
Lamella
Dryvit adhesive in verticalnotched trowel configuration
Dryvit compatible sealant withclosed cell backer-rod, by others
Dryvit Demandit™ or Color Prime™on surfaces to receive sealant
Dryvit AquaFlash System (see note 2)
Dryvit reinforcing meshembedded in base coat
Wrap Dryvit Detail Mesh 63.5 mm (212")
min. at backside of insulation slab
19 mm(3/4") min.
19 mm (3/4") min.
Dryvit compatiblesealant withclosed cellbacker-rod, by others
Dryvit Demandit® or Color Prime™on surfaces to receive sealant
Wrap Dryvit Detail Mesh™63.5 mm (21
2") min. atbackside of insulation slab
Dryvit reinforcing meshembedded in base coat
Interior seal,by others
BYOTHERS
DRYVITEXSULATION
L5000 SYSTEM
Dryvit water-resistivebarrier coating
R-002-07-08
Exsulation® L5000 EXL.0.0.20
Penetrations
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Approved substrate
Dryvit water-resistive barriercoating
Dryvit Demandit™ or ColorPrime™on surfaces to receivesealant
Dryvit compatible sealant withclosed cell backer-rod, by others
19 mm (3/4") min.
19 mm (3/4") min.
Wrap Dryvit Detail Mesh™63.5 mm (2 12 ") min. atbackside of lamella
Dryvit adhesive in verticalnotched trowel configuration
Lamella
Dryvit reinforcing meshembedded in base coat
Dryvit finish
DRYVIT EXSULATIONL5000 SYSTEM
BY OTHERS
AquaFlash® System
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposedto abnormal stress, hightraffic, or deliberateimpact have the basecoat reinforced withPanzer® 15 or 20 meshprior to Standard Plusmesh. Location of highimpact zones should beindicated on contractdrawings.
Dryvit Demandit orColor Prime
on surfaces toreceive sealant
Secondaryseal, by others
R-002-07-08
Exsulation® L5000 EXL.0.0.21
Wall Penetrations
Wrap insulation slab withDryvit Detail ReinforcingMesh
Dryvit Detail Reinforcing Mesh240 mm (9 1/2") x 300 mm (12")(typ.)
Lamella
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
2. Locate lamella slabs suchthat slab edges do not alignwith corners of penetration.
3. Apply a piece of 240 mm (91/2") x 300 mm (12") detailreinforcing mesh diagonallyat each corner.
R-002-07-08
Exsulation® L5000 EXL.0.0.22
Sign Attachment
13 mm (1/2") min.
DRYVIT EXSULATIONL5000 SYSTEM
Dryvit water-resistivebarrier coating
Dryvit adhesive in verticalnotched trowel configurationapplied to lamella
Lamella
Dryvit reinforcing meshembedded in base coatScrew/bolt attachment tobuilding framing/ blocking
Neoprene washer
Sign fixture
Dryvit compatible sealantand bond breaker tape, byothersSealant with bond breakertape between sleeve andDryvit water-resistive barriercoating, by others
Dryvit finish
BY OTHERS
Approvedsubstrate
Framingmember
Non-corrosivepipe sleeve
Blocking(secure to
framing)
BY OTHERS
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
InstallationInstructions:
1. Pre-drill through EIFSstopping at water-resistivebarrier (WRB).
2. Cut sleeve to equal depth ofsystem from WRB tooutside face.
3. Gun neutral cure siliconesealant into hole and insertsleeve.
4. While sealant is wet, installfastener and tool sealantaround edges as shown.
R-002-07-08
Exsulation® L5000 EXL.0.0.23
Aesthetic Reveals
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
19 mm (3/4") min.
Framingmember
BY OTHERS
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
2. Slope bottom edge of revealfor positive drainage.
3. EPS can be used at reveallocation. This must bepre-approved by designauthority.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Approved substrate
DRYVIT EXSULATIONL5000 SYSTEM
63.5 mm (2 1/2")
Dryvit water-resistivebarrier coating
Dryvit adhesive invertical notched trowelconfiguration
Dryvit Detail Mesh™embedded in base coat
Dryvit reinforcing meshembedded in base coat
Dryvit finish
LamellaEPS (Seenote 3)
R-002-07-08
Exsulation® L5000 EXL.0.0.24
Horizontal Joint at Stone Veneer
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
DRYVIT EXSULATIONL5000 SYSTEM
BY OTHERS
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposedto abnormal stress, hightraffic, or deliberateimpact have the basecoat reinforced withPanzer® 15 or 20 meshprior to Standard Plusmesh. Location of highimpact zones should beindicated on contractdrawings.
Approved substrate
Dryvit water-resistive barrier coating
Dryvit adhesive in verticalnotched trowel configuration applied tolamella
Lamella notched to accommodateDryvit Drainage Strip, flashing, andDryvit AquaFlash® System lappedover flashing
Dryvit finish
Dryvit reinforcing meshembedded in base coat
Wrap Dryvit DetailMesh™ 63.5 mm (2 12 ")min. at backside oflamella
Dryvit Demandit™ or Color Prime™on surface(s) to receive sealant
19 mm (3/4") min.
Dryvit compatible sealant with closedcell backer-rod and weep tubes every600 mm (24"), by others
Continuous flashing, by others
Sealant with bond breaker, by others
Secondary barrier extendedbehind flashing, by others
Stone veneer system, by others
Dryvit DrainageStrip
Dryvit AquaFlashSystem
R-002-07-08
Exsulation® L5000 EXL.0.0.25
Soffit vent
Soffit vent by others
VARIES
VARIES
VARIES
VARIES
Uninsulated
The architecture, engineering and design of the project using the Dryvit products is theresponsibility of the project's design professional. All systems must comply with localbuilding codes and standards. This detail is for general information and guidance onlyand Dryvit Systems Canada specifically disclaims any liability for the use of this detailand/or for the architecture, design, engineering or workmanship of any project. Thedesign professional determines, at its sole discretion, whether this detail or a functionallyequivalent alternative is best suitedfor the project. Use of a functionally equivalent detaildoes not violate Dryvit's warranty. This detail is subject to change without notice.Contact Dryvit Systems Canada to ensure you have the most recent version.
129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA129 Ringwood Drive PO Box 1268Stouffville, Ontario L4A 8A2800-263-3308www.dryvit.com
®
DRYVIT SYSTEMS CANADA
Notes:
1. Dryvit recommends thatground floor applicationsand all facades exposed toabnormal stress, hightraffic, or deliberate impacthave the base coatreinforced with Panzer® 15or 20 mesh prior toStandard Plus mesh.Location of high impactzones should be indicatedon contract drawings.
2. Caulk all butt joints,intersections, and end ofvents.
Substrate
Dryvit finish
Dryvit reinforcing meshembedded in base coat
Soffit vent by others
Dryvit adhesive
Lamella
Dryvit reinforcing meshembedded in base coat
Dryvit finish
Substrate
Insulated
R-002-07-08