First Canadian Place
Renewal FromThe Outside In
16th Annual Symposiumon Building ScienceJuly 30, 2012
Halsall (A Parsons Brinckerhoff Company)
![Page 2: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/2.jpg)
2
Services
Green Planning & Design
Property Condition Assessment
Restoration Engineering
Structural Engineering
Cladding Engineering
Outline• Background• Marble Management• Building Renewal Vision• Existing Construction Evaluation• Re-Cladding Design• Energy Retrofits
![Page 3: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/3.jpg)
3
Outline• Background• Marble Management• Building Renewal Vision• Existing Construction Evaluation• Re-Cladding Design• Energy Retrofits
72STOREYS
3MSQ-FT
8,500OCCUPANTS
First Canadian Place
![Page 4: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/4.jpg)
4
1975 Construction978 ft - Tallest in Canada
Photo by Brookfield PropertiesPhoto by Clifford Restoration
6,800cornerpanels
38,200face panels
9,000 IGUs4,500 windows
![Page 5: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/5.jpg)
5
Brookfield et.alHalsallMdeAs
B+HBLWTL/RWDI
Ellis DonSota/CliffordViracon/PPGTMP/Aquila
BSC
Team
Timelines
• Marble Management(2005-2010)
• Re-Cladding Design(2007-2009)
• Energy retrofits(2008-2012)
• Re-Cladding Construction(2010-2012)
![Page 6: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/6.jpg)
6
Outline• Background• Marble Management• Building Renewal Vision• Existing Construction Evaluation• Re-Cladding Design• Energy Retrofits
Staining from Silicone Sealant
![Page 7: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/7.jpg)
7
Cracks & Panel Thickness Variations
0%
5%
10%
15%
20%
25%
30%
35%
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Freq
uenc
y(%
)
Corner Panel Thickness (mm)Measured…
Thermal Hysteresis & Strength Loss
• Anisotropic behavior withthin marble &heat/moisture
• Volumetric expansion andbowing
• Reduced density andstrength loss
• Cracking
![Page 8: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/8.jpg)
8
Bowing Marble Panels
Sister Buildings byEdward Durell Stone Architect
images by MdeAs
Amoco (Aon Centre)Chicago ‘73
GM BuildingNew York ‘68
![Page 9: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/9.jpg)
9
Amoco Re-CladdingGranite Re-clad ‘89 -’92
$80M USD
Lincoln Bank, Rochester, NYConstructed 1970 – ‘80’s Aluminum Re-clad
![Page 10: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/10.jpg)
10
Finlandia Hall, HelsinkiConstructed ‘71 – Marble Reclad ‘97-’99
Management Strategy
• Comprehensive review,testing and monitoringprogram
• Targeted replacement tomaintain acceptable safetyand progressively renew
![Page 11: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/11.jpg)
11
0%
2%
4%
6%
8%
10%
12%
14%
16%
18%
0-50
50-1
0010
0-15
015
0-20
020
0-25
025
0-30
030
0-35
035
0-40
040
0-45
045
0-50
050
0-55
055
0-60
060
0-65
065
0-70
070
0-75
075
0-80
080
0-85
085
0-90
090
0-95
095
0-10
0010
00-1
050
1050
-110
011
00-1
150
1150
-120
012
00-1
250
1250
-130
013
00-1
350
1350
-140
014
00-1
450
1450
-150
015
00-1
550
1550
-160
016
00-1
650
1650
-170
017
00-1
750
1750
-180
018
00-1
850
1850
-190
019
00-1
950
1950
-200
020
00-2
050
2050
-210
021
00-2
150
2150
-220
022
00-2
250
2250
-230
023
00-2
350
2350
-240
024
00-2
450
2450
-250
025
00-2
550
2550
-260
026
00-2
650
2650
-270
027
00-2
750
2750
-280
028
00-2
850
2850
-290
029
00-2
950
2950
-300
0
Flexural Strength (psi)
Freq
uenc
y(%
)
112 Old Panels, f lexural st rength tested in 2006 (C880) and inspected in 2002
432 New Panels, f lexural st rength tested in 2002-2006 (C880)
Zoom in on Existing Panel St rength
Old vs New Marble Strength
Bow Measurements
![Page 12: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/12.jpg)
12
Bow vs. Strength Analysis
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
0 2 4 6 8 10 12 14 16 18 20 22
Flex
ural
Stre
ngth
,C88
0(p
si)
Bow (mm)
First Canadian Place - Marble CladdingBow vs C880 Flexural Strength of Panel Populations Tested in 2005/2006
Acoustic Testing
![Page 13: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/13.jpg)
13
Acoustic Testing vs Strength
0
50
100
150
200
250
300
350
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
Acou
stic
Test
Res
ults
(mic
rose
cs)
C880 Flexural Test Results (psi)
First Canadian Place - 100 King St., Toronto100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data
from 291 panels removed in 2005
If 100 ms Acoustic Threshold Applied(panels above the threshold will be
Avg. ProbableStrength, 875 psi
62% of panels would be
10% ofremainingpanelswould bebelow avg.
Pot
entia
lmin
imum
stre
ngth
obta
ined
Lower "best fit" line
1974 Wind Tunnel Testing
Max –50 / +30 psf
Cladding designed for +/- 60psf
![Page 14: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/14.jpg)
14
2002 Wind Tunnel TestingMax -92 psf and +53 psf
East North West South
Original FCP Compartment Layout (Red)
![Page 15: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/15.jpg)
15
Corner Closure Influence
Images Adopted from “Guide to Energy Efficiency in Masonry and Concrete Buildings” (1982) and Windand Air Pressures on the Building Envelope (1986)
PressureMeasurement
![Page 16: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/16.jpg)
16
Pressures at Middle of Wall
Pressures at Corners
![Page 17: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/17.jpg)
17
Prioritized Replacement by Safety Factor
Panels Replacedto 2008
(300 panels/yr -0.7%/yr)
![Page 18: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/18.jpg)
18
Current Cladding MaintenancePercent Replaced Panels Per Elevation
Percent Replacement
Silicone Strip Testing for Secondary Restraint
![Page 19: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/19.jpg)
19
Outline• Background• Marble Management• Building Renewal Vision• Existing Construction Evaluation• Re-Cladding Design• Energy Retrofits
Decision to Reclad – Business Drivers
• Minimize Risks/Improve Durability• Eliminate Ongoing Disruption and Cost• Marketability (LEED EB)• Renewed Image
![Page 20: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/20.jpg)
20
Outline• Background• Marble Management• Building Renewal Vision• Existing Construction Evaluation• Re-Cladding Design• Energy Retrofits
Interior/Exterior Evaluation (Scope)S E N W
![Page 21: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/21.jpg)
21
Interior/Exterior Evaluation
Typ. Section
![Page 22: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/22.jpg)
22
• spandrels• window components• sealants
Finishes
Control Layers
Others:• condensation• fire/smoke• uv/solar
![Page 23: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/23.jpg)
23
• anchorage/structure• wind• seismic• movement accom.
Supports
Key Considerations• Frame fading/staining• IGU aesthetics and
service life
• Air/water tightness• Solar/glare/comfort• Thermal/condensation• Fire
• Frame/anchorage/glasscapacity and condition
• Blast resistance• Cavity Air Pressures
![Page 24: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/24.jpg)
24
Air Seals Generally in Good Condition
Air Seals Generally in Good Condition
![Page 25: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/25.jpg)
25
Air Seals Generally in Good Condition
Minor Air Flow ControlLayer Discontinuities
![Page 26: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/26.jpg)
26
Corrosion Impacting Air Seal Durability
Corrosion Impacting Air Seal Durability
![Page 27: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/27.jpg)
27
Missing Fire Separation (window term. at fullheight marble)
Exterior Window Frame and MetalFlashing Finish Faded/Stained
![Page 28: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/28.jpg)
28
IGU’s ApproachingEnd of Service Life
IGU’s Approaching End of Service Life
Original Units are from 1974/1975
![Page 29: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/29.jpg)
29
Premature IGU Failures WhereOriginal Units Replaced
Window Sill Connection RequiredReinforcement
![Page 30: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/30.jpg)
30
Corrosion at Window Sill Connection
Window Assembly CapacitySatisfactory for New Wind Loads
• Mullion Assembly Structural Capacity• Full Scale Testing – ASTM E330
![Page 31: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/31.jpg)
31
Energy Consumption Not Sensitiveto Cladding Upgrades
• low glazing-to-wall ratio
• core dominated building
• enclosure’s role is largelycomfort-related in theperimeter zones
Outline• Background• Marble Management• Building Renewal Vision• Existing Construction Evaluation• Re-Cladding Design• Energy Retrofits
![Page 32: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/32.jpg)
32
Re-Cladding vs. Over-Cladding
• New Cladding Finish at Spandrels• Repair Existing Support/ Control at
– Spandrels– Windows
• Restore Finish at Window Frames• Replace IGU’s where Required
• New Continuous façade:– Finish– Control– Support
• Remove Existing IGU’s• Interior Trim Modifications
Over-cladding rejected:costscheduletenant disruptionchange to original design intent
Design Objectives
• Renew Image• Improve Durability• Restore Performance• Streamline Process/Schedule• Facilitate Future Maintenance• Economical
![Page 33: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/33.jpg)
33
Project Challenges
• Several Owners• Building Fully Occupied• Aggressive Schedule• Architectural Requirements• Site Constraints
Architect’s Vision
images by MdeAs
White/BrightImproved ScalePatterned Glass
![Page 34: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/34.jpg)
34
![Page 35: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/35.jpg)
35
![Page 36: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/36.jpg)
36
![Page 37: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/37.jpg)
37
Conceptual Work Flow
image by MdeAs
![Page 38: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/38.jpg)
38
Removals
image by B&H
RestoreConcealed Seals
![Page 39: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/39.jpg)
39
RestoreConcealed Seals
UpgradeSecondary
Drainage PlaneSeals
![Page 40: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/40.jpg)
40
SupplementalAnchors and
Corrosion Protection
Insulation and USP Support Trials
![Page 41: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/41.jpg)
41
Thermal Modeling
Performance Modeling Glare Analysis
Glare Threshold: 5,451 cd/m2
Max Glare: 58,374 cd/m2
% Over Threshold: 971%
Centre ofSun Reflection
ExchangeTowerShadow
ExchangeTowerReflection
FCP West Elevation
Simulated a Cladding with Reflective (Mirror-like) Glass SpandrelsView from Exchange Tower 38th Floor, September 21, 5:00pm
![Page 42: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/42.jpg)
42
Architects and Glass
Key Considerations – Finish/Support
• Glass Size• Glass Colour/Pattern• Glass Type
![Page 43: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/43.jpg)
43
Typ. Section
Closure Trims
![Page 44: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/44.jpg)
44
Glass• IGU vs Laminated Glass• Frit Study• Flatness• Retention
image by MdeAs
Glass Mockups
image by MdeAs
![Page 45: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/45.jpg)
45
Typ. Perimeter Framing
Unitized Spandrel Frame and Support
Lateral Connection:• prevents in/out movements
• accommodates:
• in - plane movement
• up - down movement
Fixed Gravity Connection:• provides gravity support
• prevents in/out movements
Sliding Gravity Connection:• provides gravity support
• prevents in/out movements
• accommodates:
• in - plane movement
![Page 46: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/46.jpg)
46
On-Site Mockups
![Page 47: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/47.jpg)
47
Typical Panel
• Transparency• Aesthetics• Constructability• Availability
• Load Types• Glass Types• Components• Redundancy• Post breakage
• Exposure• VLT/SHG/UV• Comfort• Condensation
Glass Design Considerations
![Page 48: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/48.jpg)
48
• Transparency• Aesthetics• Constructability• Availability
• Load Types• Glass Types• Components• Redundancy• Post breakage
• Exposure• VLT/SHG/UV• Comfort• Condensation
Glass Design Considerations
Performance / Maintenance / Repair / Replacement / Cost
Glass Design
Codes & Standards vs. Rational Engineering Analysis
Balance between Actions and ReactionsAction: Applied LoadsReactions: Glass Strength
Limit State Design– Strength and Stability– Serviceability
![Page 49: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/49.jpg)
49
Design Issues
• Laminated glass behavior– Monolithic– Laminated– Layered
Load Resistance– Heat treatment– Load duration– Design temperature
PVB Interlayer Shear Modulus
![Page 50: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/50.jpg)
50
Design Issues
• Laminated glass behavior– Monolithic– Laminated– Layered
• Load Resistance– Heat treatment– Load duration– Design temperature
CGSB/ASTM
CGSB12.20
ASTM E1300-09
![Page 51: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/51.jpg)
51
1974 Wind Loads
WLT: Max –50 / +30 psf
Design: +/- 60 psf
Wind Tunnel Re-Analysis
![Page 52: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/52.jpg)
52
2008 Wind Tunnel Study
Design Loads<= 60 psf 85% area60 to 94 psf 15% area>94 psf <0.5% area
Original Cladding designwind loads +/- 60 psf
Max loads- 117 / +56 psf
Wind vs. Temp
![Page 53: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/53.jpg)
53
Glass/USP QA/QC Considerations
• Performance Testing– Static and Cyclic Structural– Inter-storey Drift/Lateral Movement– Post-Breakage
• Fabrication Monitoring and testing– Heat Treatment– Lamination Process– Laminated Testing Services– Shop Reviews
Construction Logistics
image by Ellis Don
![Page 54: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/54.jpg)
54
Access
image by Ellis Don
![Page 55: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/55.jpg)
55
Access
image by B&H
Access
![Page 56: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/56.jpg)
56
Replacement
Completed Product
![Page 57: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/57.jpg)
57
Completed Product
photo by B&H image by MdeAs
![Page 58: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/58.jpg)
58
Outline• Background• Marble Management• Building Renewal Vision• Existing Construction Evaluation• Re-Cladding Design• Energy Retrofits
The ProcessThe Process
PLANNING INVESTIGATION > IMPLEMENTATION > TEACHING > MONITORING
![Page 59: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/59.jpg)
59
OccupantUse
BuildingOperations
BuildingSystems
NOT:“Is this the most efficient pump?”BUT: “Is this pump needed, and is it running when and how it should?”
Approach
Benchmarking
![Page 60: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/60.jpg)
60
Energy Modelling
Tower
Podium
Use Breakdown
MODELLED ENERGY DISTRIBUTION
![Page 61: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/61.jpg)
61
Tower Lighting Power ReductionGarage Lighting Power ReductionVFD’s on MAU’sReduce OA to ASHRAEDemand Control VentilationExhaust ReductionExhaust Heat RecoveryInduction Unit SwitchoverReplace ChillersConsolidate Chiller PlantReplace BoilersReplace Condenser PumpsReplace Chilled Water PumpsReplace Low Temp Heating PumpsVFD on Induction Supply/Return FansFull Floor Retrofits
Building Systems
Sub-meteringChiller Heat Recovery PlantInduction Unit SwitchoverInduction Unit FansBoiler PlantCompartment UnitsSanitary ExhaustsMechanical operating schedulesLighting schedules
Building Operations
![Page 62: First Canadian Place Renewal From The Outside In€¦ · First Canadian Place - 100 King St., Toronto 100 microsec Acoustic Threshold Applied to Acoustic and Flexural Test Data from](https://reader031.vdocuments.net/reader031/viewer/2022011909/5f6ad156bb22c32be93c045b/html5/thumbnails/62.jpg)
62
Daytime cleaningLighting schedulesOperating schedulesSupplemental coolingTenant awareness/engagement
Occupant Use
-
1,000,000
2,000,000
3,000,000
4,000,000
5,000,000
6,000,000
7,000,000
8,000,000
9,000,000
10,000,000
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Con
sum
ptio
n[k
Wh]
FCP Electricity Consumption
2009
2010
2011
22%REDUCTIONfrom 2009
CONSUMPTION
Energy Savings