High Speed NCM (HS-NCM)
HS-NCM Overview
Supports 200 nodes No limitations when using a DVC to page over the
network Two node addresses per HS-NCM Compatible only with Onyx series panels (8th and
9th edition) 8th edition products can only be used in retrofit
applications
HS-NCM Overview
NFN on IP based VDSL Network (Very High Data Rate Subscriber Line)•Does not use ARCnet protocol
The HS-NCM is NOT compatible with the standard NCM Noti-Fire-Net Network.
Supports NUP (Notifier Universal Protocol)Can be configured as a network repeater by setting
address to 0Installs in same single module bay as NCM
HS-NCM Overview
Each HS-NCM has:• Two NUP Ports
ONYX FACP, NCA-2, DVC, Veri-Fire Tools and/or Gateway
• Two USB Connections One Host Standard A and One On-The-Go Mini AB Veri-Fire Tools
• External Power Connection (Remote Repeater)
• Ethernet Port for Future Diagnostics
HS-NCM Part Numbers
High Speed NCM (HS-NCM) • HS-NCM-MF Multimode Fiber• HS-NCM-MFSF Multimode/Singlemode Fiber• HS-NCM-SF Singlemode Fiber• HS-NCM-W Wire• HS-NCM-WMF Wire/Multimode Fiber• HS-NCM-WSF Wire/Singlemode Fiber• HS-GW-EM Embedded Gateways
BACNET-GW-3NWS-3NFN-GW-EM-3
VDSL Data Rate 12Mb (Variable 3Mb-24Mb Future)
Supports twisted pair wire• 18AWG- 14AWG•Maximum Distance 3,000 ft.
NFPA Style 4 (Class B) or Style 7 (Class A)
Data is regenerated at each node
HS-NCM-W
HS-NCM-W
Channel A Connection
Channel B Connection
Ground Fault Detection Switches S1 = CH A S2 = CH B
USB Connections
NUP Ports
External Power
Connection
HS-NCM-W Wire Requirements
MUST be Twisted Pair Prefer a Data Grade Cable (Belden) Non-Shielded Wire for High Speed Communications 200 Nodes at 3,000’
• Belden 5320UJ 18/2 FPL• Belden 5320UM 18/2 FPLR• Genesis 4050 18/2 FPL• Genesis 4631 18/2 FPLP• Genesis 4433 14/2 FPLR• Genesis 4633 14/2 FPLP
HS-NCM-W Wire Requirements
200 Nodes at 2,000’• Genesis 4431 18/2 FPLR
200 Nodes at 1,000’• Genesis 5500 18/2 FPLR• Genesis 5502 16/2 FPLR• Belden 5220UM 16/2 FPLR
200 Nodes at <1,000’• Genesis 5504 14/2 FPLP
This cable did not pass the test for 200 nodes at distances even less than 1,000’ and therefore should not be used as a network segment cable
HS-NCM-MF (Multi-Mode Fiber)
Data Rate of 100Mb Supports Fiber Optic Cable
• 62.5/125 10dB Limit• 50.0/125 6.5 dB Limit
NFPA Style 4 (Class B) or Style 7 (Class A)
Data is regenerated at each node
Fiber Connectors: LC Style
HS-NCM-SF (Single-Mode Fiber)
Data Rate of 100Mb Supports Fiber Optic Cable
• 9/125 30dB Limit NFPA Style 4 (Class B) or
Style 7 (Class A) Data is regenerated at each
node Fiber Connectors: LC Style
HS-NCM-SF (Single-Mode Fiber)
NO CONVERTERS REQUIRED !!!
Previous singlemode fiber segment required two NCM-F, two 14507714-001 singlemode converters and mounting kit.
HS-NCM Hybrids (Wire to Fiber)
HS-NCM-WSF HS-NCM-WMF
Multi-Mode fiber to Single-Mode fiber converter not shown
ONYXWorks™
Intel 2.0 GHz Pentium IV microprocessor
1 GB RAM80 GB hard drive1.44 MB floppy drive24/10/40X CD-RW drive19” Flatscreen LCD monitor
Microsoft Windows XP
HS-NCS
High Speed ONYXWorks•ONYXWORKS-HNMF (High Speed NFN Multi-mode Fiber)
•ONYXWORKS-HNSF•ONYXWORKS-HNW
High Speed card for ONYXWorks Add-On (Upgrade current ONYXWorks)•NFN-GW-PC-HNMF•NFN-GW-PC-HNSF•NFN-GW-PC-HNW
HS-NCS Cards for ONYXWorks
HS-NCS-MFHS-NCS-SF
HS-NCS-W
• NOT compatible with the NCS Workstation
For ONYXWorks only
HS-NCM Applications
NUP NUP
USB USB
NFN NFN
HS-NCM2 Node
Addresses
HS-NCMHS-NCM
Veri-Fire Tools
100
DVC,NCA-2,Gatewayor another FACP
HS-NCM Applications
NUP NUP
USB USB
NFN NFN
HS-NCM1 NodeAddress
HS-NCMHS-NCM
Veri-Fire Tools200
Veri-Fire Tools
(either/or connection)
HS-NCM USB Limitations
USB connection for the HS-NCM is NOT supported on the fire panels until the following releases:• NFS2-3030 Release 14.1• NFS2-640/NFS-320 Release 15.0
USB Connections not supported on NFS-640 or NFS-3030