Transcript
Page 1: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/1

6Hybrid Motor Starters Industrial Control Product Catalog 2021 Section

contentsSIRIUS 3RM1 motor starters

General data 6/2 – 6/7Selection and ordering 6/8 – 6/9Accessories 6/10 – 6/11

ET 200SP motor starters

General data 6/12 – 6/18Selection and ordering 6/19Base units and control module 6/20Accessories 6/21

ET 200pro motor starters

General data 6/22 – 6/27Standard motor starters 6/28High Feature motor starters 6/29ET 200pro isolator modules 6/30ET 200pro safety motor starters 6/31Solutions local/PROFIsafe - Safety modules local 6/32 – 6/33 - Safety modules PROFIsafe 6/34Accessories for ET 200pro motor starters 6/35 – 6/39SoftwareMotor Starter ES 6/40

SIRIUS M200D motor starters

General data 6/41 – 6/43M200D motor starters for AS-InterfaceGeneral data 6/44 – 6/46M200D Basic motor starters 6/47M200D Standard motor starters 6/48M200D motor starters for PROFIBUS/PROFINETGeneral data 6/49 – 6/54Communication modules, motor starter modules 6/55SoftwareMotor Starter ES 6/56AccessoriesFor all M200D motor starters 6/57 – 6/61For M200D motor starters for AS-Interface 6/62 – 6/63For M200D motor starters for PROFIBUS 6/64For M200D motor starters for PROFINET 6/65

Hybrid fieldbus connections

General data 6/66Selection and ordering 6/67

New naming conventionic21-sect-06-hybrid-starters

Remove IP20 infoRevised on 01/06/20

SIRIUS M200D

ET 200pro

SIRIUS 3RM1

ET 200SP

Page 2: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/2

Hybrid Motor Starters

SIRIUS 3RM1 motor startersIntroduction

8/85Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

■ Overview

3RM13 motor starter with reversing functionality, electronic overload protection and safety-related shutdown

SIRIUS 3RM1 motor starters are compact devices, 22.5 mm wide, combining a large number of functions in a single enclosure. They consist of combinations of relay contacts, power semiconductors (hybrid technology), and an electronic overload relay for operational switching of three-phase motors up to 3 HP (at 480V).

The 3RM1 motor starters with overload protection with wide setting range are available as direct-on-line starters and reversing starters and as versions with safety-related shutdown up to SIL 3/PL e.

Seamlessly integrated safety right through to the main circuit

Problem-free integration of functional safety into the main circuit through the simple combination of 3RM1 and 3SK devices

Functional safety in the main circuit needs to be both simple and flexible.

The unique compatibility of hybrid 3RM1 fail-safe motor starters and 3SK safety relays means that integrated functional safety right through to the main circuit is no longer a problem.

Their compact design allows the motor starters to be installed to the right of the safety relay in a simple manner, just like an output expansion. The wiring of the safety-related signals to the relay can be performed simply, quickly and in an error-free manner using the device connector.

The ergonomically designed enclosure with removable termi-nals and terminal labeling in the hinged cover allows for the cables to be conveniently diagonally mounted from the front. Either screw or spring-loaded terminals with push-in technology are available.

Highlights• Fail-safe disconnection of motors up to 3 kW• Problem-free combination of fail-safe motor starters and safety

relays• End-to-end system, simple setup using device connectors• Ergonomic enclosure

Note:

For SIRIUS 3SK safety relays, see page 11/12.

IC01

_005

333SK + 3RM1

IC10_08_06.fm Page 85 Sunday, July 19, 2020 8:43 PM

For SIRIUS 3SK safety relays, see page 13/133.

Revised on 07/20/20Whole section is new pages from German catalog

Page 3: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/3

Hybrid Motor Starters

SIRIUS 3RM1 motor startersGeneral data

8/86 Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

Article No. scheme

1) Standard three-phase motor; the actual startup characteristics of the motor as well as its rated data are important factors here.

Note:

The article number scheme shows an overview of product versions for better understanding of the logic behind the article numbers.

For your orders, please use the article numbers quoted in the selection and ordering data.

■ Benefits

Product advantages• Less space required in the control cabinet (20 to 80%) thanks

to high functional density, which also means reduced wiring and testing

• Greater endurance and reduced heat losses thanks to hybrid technology

• Lower costs for stock keeping and configuration as a result of the wide setting range of the electronic overload release (up to 1:5)

• Fast wiring without tools for rigid conductors or conductors equipped with end sleeves thanks to spring-loaded terminals (push-in)

• Safety-related shutdown in accordance with SIL 3/PL e by shutting down the control supply voltage without additional devices in the main circuit

• The motor starters can be ideally combined with 3SK safety relays for safety-related shutdown (see page 11/12)

• Motor status feedback to the higher-level control system in the case of 3RM10 and 3RM12 motor starters in the 24 V DC version

• Virtually error-free wiring on the mains connection side and reduction in short-circuit protective devices by means of 3RM19 infeed system

• ATEX certification of the overload protection of the 3RM1 Failsafe motor starters: "Increased safety" type of protection EEx e according to ATEX directive 2014/34/EU

• The 3RM1 motor starters can be used with highly energy-efficient IE3/IE4 motors. In this regard, please observe the information on dimensioning and configuring, see Application Manual.For more information about IE3/IE4, see page 1/7.

Standards and approvals• IEC/EN 60947-4-2• UL 60947-4-2• CSA• ATEX• IEC 61508-1: SIL 3• ISO 13849: PL e• CCC approval for China

Product versions Article number

Product function Direct-on-line starters 3RM10 0 @ – @ AA @ 4Failsafe direct-on-line starters 3RM11 0 @ – @ AA @ 4 with ATEX certification and safety-related shutdownReversing starters 3RM12 0 @ – @ AA @ 4Failsafe reversing starters 3RM13 0 @ – @ AA @ 4 with ATEX certification and safety-related shutdown

Wide setting range for electronic overload release

0.1 ... 0.5 A 10.4 ... 2.0 A 2 For motor standard output up to 3/4 HP1) 1.6 ... 7.0 A (UL=6.1A) 7 For motor standard output up to 3 HP1)

Connection method Screw terminals 1Spring-loaded terminals (push-in)

2

Mixed connection method 3 Spring-loaded terminals (push-in)

Rated control supply voltage Us

24 V DC 0110 ... 230 V AC; 110 V DC 1

Example 3RM13 0 1 – 2 AA 0 4

IC10_08_06.fm Page 86 Sunday, July 19, 2020 8:43 PM

• The motor starters can be ideally combined with 3SK safetyrelays for safety-related shutdown (see page 13/133).

• The 3RM1 motor starters can be used with highly energy-efficient IE3/IE4 motors. In this regard, please observe the information on dimensioning and configuring, seeApplication Manual.For more information about IE3/IE4, see page 1/7.

Revised on 07/20/20Whole section is new pages from German catalog

Page 4: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/4

8/87Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

■ Technical specifications

More information

Industry Mall, see www.siemens.com/product?3RM1

Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/66295730

FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16311/faq

Article number 3RM10,3RM12

3RM11,3RM13

General technical specifications:Dimensions (W x H x D) mm 22.5 x 100 x 141.6

Ambient temperature• During operation °C -25 … +60• During storage °C -40 … +70• During transport °C -40 … +70

Installation altitude at height above sea level, maximum m 4 000 2 000

Shock resistance 6 g / 11 ms

Vibration resistance 1 ... 6 Hz, 15 mm; 20 m/s², 500 Hz

Degree of protection IP20

Mounting position Vertical, horizontal, standing (consider derating)

Article number 3RM1.01 3RM1.02 3RM1.07

Main circuit:Operational voltage, rated value, maximum V 500

Operating frequency Hz 50/60

Operational current at AC-53a at 400 V at an ambient temperature of 40 °C A 0.5 2 7

Minimum load [% of IM] % 20

Adjustable current response value of the inverse-time delayed overload release A 0.1 ... 0.5 0.4 ... 2 1.6 ... 7

Article number 3RM1.0.-.AA04 3RM1.0.-.AA14

Control circuit:Type of voltage of the control supply voltage DC AC/DC

Control supply voltage• At DC V 24 110• At AC at 50 Hz V -- 110 … 230

Frequency of the control supply voltage Hz -- 50/60

IC01

_004

69

IC10_08_06.fm Page 87 Sunday, July 19, 2020 8:43 PM

Hybrid Motor Starters

SIRIUS 3RM1 motor startersGeneral data

Industry Mall, see www.siemens.com/product?3RM1Equipment Manual, seehttps://support.industry.siemens.com/cs/ww/en/view/66295730

FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16311/faq

Page 5: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/5

8/88 Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

■ Accessories

Three-phase infeed system (3RM19 three-phase busbar system)

The system permits an easy, time-saving and safe means of feeding two or more 3RM1 motor starters. It can be used only with motor starters with screw terminals and in combination with 8US1716-0RK00 adapters for mounting rails in the main circuit.

The maximum summation current must not exceed 25 A. The primary infeed is connected via a three-phase infeed terminal.

The busbars are available in three lengths, for two, three or five motor starters. More than five devices can be connected by clamping the connection tags of a second busbar rotated by 180°.

The three-phase busbars are finger-safe but empty connection tags must be fitted with covers.

3RM19 infeed system with three-phase infeed terminal: In the above example, two three-phase busbars (5-pole busbars) rotated through 180° allow up to nine 3RM1 motor starters to be connected. Contact with the unused connection tags in unoccupied positions is prevented safely by the covers.

Type 3RM1.0.-1AA.4 3RM1.0.-3AA.4 3RM1.0.-2AA.4

Connections/terminals:Type of electrical connection for main circuit(1 or 2 conductors can be connected)

Screw terminals Spring-loaded terminals (push-in)

Connectable conductor cross-section for main contacts• Solid mm² 1 x (0.5 ... 4), 2 x (0.5 ... 2.5) 1 x (0.5 ... 4)• Finely stranded

- With end sleeve mm² 1 x (0.5 ... 4), 2 x (0.5 ... 1.5) 1 x (0.5 ... 2.5)- Without end sleeve mm² -- 1 x (0.5 ... 4)

Type of electrical connection for auxiliary and control circuit(1 or 2 conductors can be connected)

Screw terminals

Spring-loaded terminals (push-in)

Type of connectable conductor cross-sections for auxiliary contacts• Solid mm² 1 x (0.5 ... 2.5),

2 x (1.0 ... 1.5)1 x (0.5 ... 1.5), 2 x (0.5 ... 1.5)

• Finely stranded- With end sleeve mm² 1 x (0.5 ... 2.5),

2 x (0.5 ... 1)1 x (0.5 ... 1.0), 2 x (0.5 ... 1.0)

- Without end sleeve mm² -- 1 x (0.5 ... 1.5), 2 x (0.5 ... 1.5)

Type of connectable conductor cross-sections for AWG cables• For main contacts 1 x (20 ... 12), 2 x (20 ... 14) 1 x (20 ... 12)• For auxiliary contacts 1 x (20 ... 14),

2 x (18 ... 16)1x (20 ... 16), 2 x (20 ... 16)

More information

Equipment Manual, seehttps://support.industry.siemens.com/cs/ww/en/view/66295730

1

4

2

3

1

2

3

4

Four 3RM1 motor starters on standard mounting rail with one free slot

3RM1920-1AA three-phase infeed terminal

Two 3RM1910-1DA three-phase busbars rotated through 180° for the connection of up to nine motor starters

Covers for three 3RM1910-6AA connection tags respectively for unused slots

IC01

_001

69c

IC10_08_06.fm Page 88 Sunday, July 19, 2020 8:43 PM

Hybrid Motor Starters

SIRIUS 3RM1 motor startersGeneral data

Equipment Manual, seehttps://support.industry.siemens.com/cs/ww/en/view/66295730

Page 6: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/6

8/89Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

Fuse module for the use of 3RM1 motor starters on 8US busbar systems and mounting rails

The fuse module permits the very compact construction of a load feeder with a maximum width of 22.5 mm. The 3RM1 motor starter in combination with the integrated fuses for short-circuit protection can therefore be used on 8US busbar systems.Thanks to the range of different adapters, the fuse module can be used in all 60 mm busbar systems and also in compact busbar systems and on mounting rails. The interface to the adapter also permits a simple and secure replacement of the load feeder.

The fuse module can be combined with all 3RM1 motor starters. The easily replaceable fuses protect the connected motor and the cables.

By means of the fuse module, 3RM1 motor starters can be used in busbar systems and 8US compact busbar systems, as well as on mounting rails

2 34 5

51

67

Busbar system

Cover profiles for busbars

Compact busbar adapter

Busbar adapter

3RM1 motor starter

3RM19 fuse module

3RM19 fuse module with open flap(Flap cannot be opened when fuse module is inserted. The fuse module must be removed to change the fuses.)

2

1

3

4

6

5

7

IC01

_006

11a

IC10_08_06.fm Page 89 Sunday, July 19, 2020 8:43 PM

Hybrid Motor Starters

SIRIUS 3RM1 motor startersGeneral data

Page 7: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/7

8/90 Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

Device connectors for the control circuitThe device connectors for 3RM1 motor starters (24 V DC control supply voltage only) reduce the outlay for cabling by looping through the control supply voltage. The device connectors can be snapped onto a standard mounting rail or fixed to a level mounting panel using screws.

Device connector with 3RM1 motor starter

Using the device connectors exclusively for feeding in thecontrol supply voltage

By using device connectors, a maximum of five motor starters can be supplied with 24 V DC control supply voltage. This requires the control supply voltage to be applied to the A1 and A2 terminals of only one motor starter.

Device daisy chain connectors can be used for gaps between two motor starters. Device termination connectors terminate a group.

Using the device connectors for safe group shutdown

In combination with the 3RM11 and 3RM13 fail-safe motor starters, the device connector can also be used for safety-related shutdown. For this application, groups of no more than five fail-safe motor starters can be connected using a device connector, and the group must be terminated with a termination connector. Removing the control voltage supply from the first motor starter will safely shut down the whole group.

Safe group shutdown can be implemented particularly easily in conjunction with 3SK safety relays. In this case, up to five motor starters can be directly connected to 3SK safety relays via the device connector and then safely shut down (see page 13/133).

Ideal connection: Combination of four SIRIUS 3RM1 Failsafe motor starters with SIRIUS 3SK safety relays

Electromechanical switching devices in series with hybrid motor startersSwitching an inductive load - in particular of motors < 1 kW with high inductance - with an electromechanical switching device (e.g. contactor) can cause high and steep voltage edges.

The resulting faults/damage can be prevented by first disconnecting with the hybrid motor starter or by using EMC suppression modules:• For 3RT2916-1P.. EMC suppression modules for direct

mounting on the contactor, see page 2/78• For motor suppression modules that are fitted in the main

circuit, see page 8/94

Note:

For more information, see https://support.industry.siemens.com/cs/ww/en/view/109758696.

IC01

_0

0218

b

Motor

3RM1 motor starter3SK safety relay

IC01

_0

0178

a

IC10_08_06.fm Page 90 Sunday, July 19, 2020 8:43 PM

Hybrid Motor Starters

SIRIUS 3RM1 motor startersGeneral data

For more information, see https://support.industry.siemens.com/cs/ww/en/view/109758696.

• For motor suppression modules that are fitted in the maincircuit, (see page 6/11).

Page 8: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/8

Hybrid Motor Starters

SIRIUS 3RM1 motor startersSelection and ordering data IE3/IE4 ready

8/91Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

Selection and ordering data

1) The actual startup characteristics of the motor as well as its rated data are important factors here.

More information

Industry Mall, see www.siemens.com/product?3RM1

Operational powerfor three-phase motorat 460 V1)

Adjustable current response value of theinverse-time delayedoverload release

Control supply voltage SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

At DC At AC at 50 Hz

HP A V V d

Direct-on-line starters

3RM1001-1AA04

-- 0.1 … 0.5 24 -- 2 3RM1001-@AA04 1 1 unit

3/4 0.4 … 2 24 -- 2 3RM1002-@AA04 1 1 unit

3 1.6 … 6.1 24 -- 2 3RM1007-@AA04 1 1 unit

-- 0.1 … 0.5 110 110 ... 230 2 3RM1001-@AA14 1 1 unit

3/4 0.4 … 2 110 110 ... 230 2 3RM1002-@AA14 1 1 unit

3 1.6 … 6.1 110 110 ... 230 2 3RM1007-@AA14 1 1 unit

Reversing starters

3RM1201-1AA04

-- 0.1 … 0.5 24 -- 2 3RM1201-@AA04 1 1 unit

3/4 0.4 … 2 24 -- 2 3RM1202-@AA04 1 1 unit

3 1.6 … 6.1 24 -- 2 3RM1207-@AA04 1 1 unit

-- 0.1 … 0.5 110 110 ... 230 2 3RM1201-@AA14 1 1 unit

3/4 0.4 … 2 110 110 ... 230 2 3RM1202-@AA14 1 1 unit

3 1.6 … 6.1 110 110 ... 230 2 3RM1207-@AA14 1 1 unit

Failsafe direct-on-line starters

3RM1101-1AA04

-- 0.1 … 0.5 24 -- 2 3RM1101-@AA04 1 1 unit

3/4 0.4 … 2 24 -- 2 3RM1102-@AA04 1 1 unit

3 1.6 … 6.1 24 -- 2 3RM1107-@AA04 1 1 unit

-- 0.1 … 0.5 110 110 ... 230 2 3RM1101-@AA14 1 1 unit

3/4 0.4 … 2 110 110 ... 230 2 3RM1102-@AA14 1 1 unit

3 1.6 … 6.1 110 110 ... 230 2 3RM1107-@AA14 1 1 unit

Failsafe reversing starters

3RM1301-1AA04

-- 0.1 … 0.5 24 -- 2 3RM1301-@AA04 1 1 unit

3/4 0.4 … 2 24 -- 2 3RM1302-@AA04 1 1 unit

3 1.6 … 6.1 24 -- 2 3RM1307-@AA04 1 1 unit

-- 0.1 … 0.5 110 110 ... 230 2 3RM1301-@AA14 1 1 unit

3/4 0.4 … 2 110 110 ... 230 2 3RM1302-@AA14 1 1 unit

3 1.6 … 6.1 110 110 ... 230 2 3RM1307-@AA14 1 1 unit

Type of electrical connection• Screw terminals for main circuit, screw terminals for control circuit

• Spring-loaded terminals (push-in) for main circuit, spring-loaded terminals (push-in) for control circuit

• Screw terminals for main circuit, spring-loaded terminals (push-in) for control circuit

12

3

IC10_08_06.fm Page 91 We dnesday, July 15, 2020 3:42 PM

Industry Mall, see www.siemens.com/product?3RM1

Page 9: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/9

8/92 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

1) For details of alternative fuses, see Equipment Manual.

DSnoitangised tcudorP Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Three-phase infeed system for 3RM1 with screw terminals

3RM1920-1AA

Three-phase infeed terminals• For three-phase busbars

} 3RM1920-1AA 1 1 unit

Three-phase busbars

3RM1910-1AA

• For 2 motor starters } 3RM1910-1AA 1 1 unit

3RM1910-1BA

• For 3 motor starters } 3RM1910-1BA 1 1 unit

3RM1910-1DA

• For 5 motor starters } 3RM1910-1DA 1 1 unit

3RM1910-6AA

CoversFor 3 connection tags of the three-phase busbars

} 3RM1910-6AA 1 10 units

Fuse modules for 3RM1 for use on busbars or mounting rails

3RM1932-1AB

Fuse module with 3NW6007-1 fuse 2 3RM1932-1AB 1 1 unit

Fuse module without fuse1) 10 3RM1930-1AA 1 1 unit

Adapters

8US1216-0AS00

Adapters for 60 mm busbar systems22.5 mm x 200 mm x 41.5 mm

Note: The adapter can be used on busbars with a width of 12 mm and a thickness of 5 mm or 10 mm.

5 8US1216-0AS00 1 1 unit

8US1616-0AK02

Adapters for 60 mm compact busbar systems22.5 mm x 160 mm x 41.5 mm

Note: The adapter can be used on busbars with a width of 12 mm, 15 mm, 20 mm, 25 mm or 30 mm and a thickness of 5 mm or 10 mm.

5 8US1616-0AK02 1 1 unit

IC10_08_06.fm Page 92 Sunday, July 19, 2020 8:43 PM

Hybrid Motor Starters

SIRIUS 3RM1 motor startersAccessories

For details of alternative fuses, see Equipment Manual.

Page 10: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/10

Hybrid Motor Starters

SIRIUS 3RM1 motor startersAccessories

8/93Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

1) The cover profiles for busbars can be used for maintaining minimum spacing between the load feeders.

2) For further accessories for the configuration of a busbar system, see Catalog LV 10.

DSnoitangised tcudorP Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Adapters

8US1716-0RK00

Adapter for 35 mm DIN mounting rails22.5 mm x 185 mm x 23.5 mm

5 8US1716-0RK00 1 1 unit

Cover profiles1)2)

Cover profiles for busbars

8US1922-2CA00

12 mm x 5 mm x 1 000 mm

40 mm or 60 mm center-to-center busbar clearancedepending on busbar system

2 8US1922-2CA00 1 10 units

8US1922-2AA00

15 mm x 5 mm x 1 000 mm20 mm x 5 mm x 1 000 mm25 mm x 5 mm x 1 000 mm30 mm x 5 mm x 1 000 mm

40 mm or 60 mm center-to-center busbar clearancedepending on busbar system

2 8US1922-2AA00 1 10 units

8US1922-2BA00

12 mm x 10 mm x 1 000 mm15 mm x 10 mm x 1 000 mm20 mm x 10 mm x 1 000 mm25 mm x 10 mm x 1 000 mm30 mm x 10 mm x 1 000 mm

60 mm center-to-center busbar clearance

2 8US1922-2BA00 1 10 units

Device connectors

3ZY1212-2EA00

Device connectorsFor 3RM1 motor starters, 24 V DC, 22.5 mm

2 3ZY1212-2EA00 1 1 unit

3ZY1212-2AB00

Device daisy chain connectorsFor 3RM1 motor starters 24 V DC, 22.5 mm For gaps without motor starters in assemblies

2 3ZY1212-2AB00 1 1 unit

3ZY1212-2FA00

Device termination connectorsFor 3RM1 motor starters, 24 V DC, 22.5 mm

2 3ZY1212-2FA00 1 1 unit

IC10_08_06.fm Page 93 Sunday, July 19, 2020 8:43 PM

For further accessories for the configuration of a busbar system, see Catalog LV 10.

Page 11: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/11

8/94 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Load Feeders and Motor Starters for Use in the Control Cabinet

SIRIUS 3RM1 motor starters

8

DSnoitangised tcudorP Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Removable terminals

3ZY1122-1BA00

Terminal for main circuit, 2-poleScrew terminals

• Screw terminals, 1 x 4 mm²

2 3ZY1122-1BA00 1 6 units

Spring-loaded terminals (push-in)

• Spring-loaded terminals (push-in), 1 x 4 mm²

2 3ZY1122-2BA00 1 6 units

3ZY1131-1BA00

Terminal for control circuit, 3-poleScrew terminals

• Screw terminals, 1 x 2.5 mm²

2 3ZY1131-1BA00 1 6 units

Spring-loaded terminals(push-in)

• Spring-loaded terminals (push-in), 1 x 2.5 mm²

2 3ZY1131-2BA00 1 6 units

Further accessories

3ZY1311-0AA00

Push-in lugs for wall mounting2 lugs per device are required

2 3ZY1311-0AA00 1 10 units

3ZY1321-2AA00

Sealable covers, 22.5 mmFor simple protection against unauthorized access

2 3ZY1321-2AA00 1 5 units

3ZY1440-1AA00

Coding pins for removable terminalsFor mechanical coding of the terminals

2 3ZY1440-1AA00 1 12 units

3ZY1450-1AB00

Hinged coverReplacement cover, without terminal labeling, 22.5 mm wide

• Titanium gray 2 3ZY1450-1AB00 1 5 units

• Yellow 2 3ZY1450-1BB00 1 5 units

3RK1911-6EA00

Motor suppression module51erauqS• 3RK1911-6EA00 1 1 unit

51dnuoR• 3RK1911-6EB00 1 1 unit

3RA2908-1A

ScrewdriversFor all SIRIUS devices with spring-loaded terminals

Spring-loaded terminals

Length approx. 200 mm, 3.0 mm x 0.5 mm, titanium gray/black, partially insulated

2 3RA2908-1A 1 1 unit

IC10_08_06.fm Page 94 Sunday, July 19, 2020 8:43 PM

Hybrid Motor Starters

SIRIUS 3RM1 motor startersAccessories

Page 12: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/12

8/95Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

Overview

Motor starter, BaseUnit, fan and 3DI/LC control module 3RK1308 motor starter in the ET 200SP I/O system

ET 200SP motor startersET 200SP is a scalable and extremely flexible modular I/O system.

As I/O modules, the ET 200SP motor starters are an integral part of this I/O system. They are switching and protection devices for single- and three-phase loads and are available as direct-on-line or reversing starters.

Basic functionality

All versions of the ET 200SP motor starter feature the following functionality:• Fully pre-wired motor starters for switching and protecting any

AC loads up to 5.5 kW from 48 V AC to 500 V AC• Disconnection possible via fail-safe motor starters up to SIL 3

and PL e Cat. 4• With self-assembling 32 A power bus, i.e. the load voltage is

only fed in once for a group of motor starters• All control supply voltages connected only once, i.e. when

modules are added they are automatically connected to the next module

• Hot swapping is permissible• Digital inputs can optionally be used via a 3DI/LC module• Control of the motor starter from the control system and

extensive diagnostics status via the cyclic process image• Diagnostics capability for active monitoring of the switching

and protection functions

• The signal states in the process image of the motor starter provide information about protective devices (short circuit or overload), the switching states of the motor starter, and system faults.

Starter Kit

The 3RK1908-1SK00 Starter Kit is a favorably priced complete package for switching and monitoring motors in the ET 200SP system, see page 8/104.

It contains:• a 3RK1308-0BC00-0CP0 reversing starter (0.9 to 3 A)• a 3RK1908-0AP00-0AP0 BaseUnit with 500 V and

24 V AC/DC infeed• an EMC distance module

(consisting of 6ES7193-6BP00-0BA0 BaseUnit plus 6ES7133-6CV15-1AM0 BU cover 15 mm)

Use of fan

For motor starters with a 12 A rated current, the 3RW4928-8VB00 fan is included in the scope of supply.

This fan can also be ordered as an option for motor starters with lower rated currents, if the boundary conditions demand this. For information on the ambient conditions for the use of motor starters, see chapter "Product overview" in the Equipment Manual.

2

4

3

1

2

1

3

4

5

5

BaseUnit for ET 200SP motor starter

3DI/LC module

Fan

ET 200SP fail-safe motor starter

Infeed bus cover

IC01

_0

06

62a

8

1 3 4 65 6 72

9

Dummy module consisting of BaseUnit + BU cover, 30 mmDummy module consisting of

BaseUnit + BU cover, 15 mm3DI/LC module

ET 200SP motor starter F-DI and ET 200SP motor starter

ET 200SP digital output

ET 200SP analog input

ET 200SP interface module

ET 200SP digital input

6 Infeed bus cover9

4

5

8

2

1

3

7

IC01

_0

061

3a

More information

Homepage, see www.siemens.com/ET200SP-motorstarter

Industry Mall, see www.siemens.com/product?3RK1308

TIA Selection Tool, see www.siemens.com/TST

Further components in the ET 200SP I/O system:

• Catalog ST 70

• Industry Mall, see www.siemens.de/product?ET200SP

IC10_08_07.fm Page 95 Sunday, July 19, 2020 8:54 PM

Hybrid Motor Starters

ET 200SP motor starterIntroduction

Homepage, see www.siemens.com/ET200SP-motorstarterIndustry Mall, see www.siemens.com/product?3RK1308TIA Selection Tool, see www.siemens.com/TST

Further components in the ET 200SP I/O system:• Catalog ST 70• Industry Mall, see www.siemens.de/product?ET200SP

The 3RK1908-1SK00 Starter Kit is a favorably priced completepackage for switching and monitoring motors in the ET 200SPsystem, see page 6/21.

This fan can also be ordered as an option for motor starters withlower rated currents, if the boundary conditions demand this.For information on the ambient conditions for the use of motorstarters, see chapter “Product overview” in the EquipmentManual.

Remove IP20 infoRevised on 01/06/20

Page 13: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/13

Hybrid Motor Starters

ET 200SP motor starterIntroduction

8/96 Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

Designing interference-free motor starters

For interference-free operation of the ET 200SP station in accordance with IEC 60947-4-2 standard, use a dummy module before the first motor starter. The dummy module consists of the 6ES7193-6BP00-0BA0 or 6ES7193-6BP00-0DA0 BaseUnit and the 6ES7133-6CV15-1AM0 BU cover 15 mm.

The 15 mm BU cover protects the plug contacts of the BaseUnit against dirt.

Electromechanical switching devices in series with hybrid motor starters

Switching an inductive load - in particular of motors <1 kW with high inductance - with an electromechanical switching device (e.g. contactor) can cause high and steep voltage edges.

The resulting faults/damage can be prevented by first disconnecting with the hybrid motor starter or by using EMC suppression modules:• For 3RT2916-1P.. EMC suppression modules for direct

mounting on the contactor, see page 3/118• For motor suppression modules that are fitted in the main

circuit, see page 8/104

Note:

For more information, see https://support.industry.siemens.com/cs/ww/en/view/109758696.

3DI/LC control module

This is a digital input module with three inputs for local motor starter functions such as "manual local control", "implementation of fast inputs" or "end position disconnection". For a list of all the functions permitted by the 3DI/LC module, see chapter "Overview of functions" in the Equipment Manual.

The module is plugged into the front of the motor starter from which it is supplied with a 24 V DC operating voltage.

BaseUnits for motor starters

View of the BaseUnit infeeds for the motor starters

BaseUnits are components for accommodating the ET 200SP I/O modules.

The self-assembling voltage buses integrated into the BaseUnits reduce wiring outlay to the single infeed (both of auxiliary and load voltage).

All modules following on the right are automatically supplied upon plugging the BaseUnits together, if BaseUnits are inserted with routing.

The rugged design and keyed connection technology enables use in harsh industrial conditions.

The BaseUnits are available with various infeeds for the motor starters.

2 3 4 7

5

6

7

9

9

810

10

81

4

2

1

3

500 V AC with F-DI infeed

500 V AC with F-DI loop-through

without infeed with F-DI infeed

without infeed with F-DI loop-through

3RK1908-0AP00-0EP0(not shown here)

3RK1908-0AP00-0FP0(not shown here)

24 V and 500 V DC

500 V AC24 V DCwithout infeed

IC01

_005

35a

IC10_08_07.fm Page 96 Sunday, July 19, 2020 8:54 PM

This is a digital input module with three inputs for local motorstarter functions such as “manual local control”, “implementationof fast inputs” or “end position disconnection”. For a list of all thefunctions permitted by the 3DI/LC module, see chapter “Overview of functions” in the Equipment Manual.

For more information, see https://support.industry.siemens.com/cs/ww/en/view/109758696..

• For 3RT2916-1P.. EMC suppression modules for directmounting on the contactor, see page 13/133.

• For motor suppression modules that are fitted in the maincircuit, see page 16/21.

Page 14: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/14

Hybrid Motor Starters

ET 200SP motor starterGeneral data

8/97Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

Article No. scheme

1) For standard motors: Single- or three-phase asynchronous motors, single-phase AC motors, single-phase asynchronous motors, at 400 V AC and 500 V AC; the actual startup characteristics of the motor as well as its rated data are important factors here.

Note:

The article number schemes show an overview of product ver-sions for better understanding of the logic behind the article numbers.

For your orders, please use the article numbers quoted in the selection and ordering data.

■ Benefits

Product advantages

The ET 200SP motor starters offer a number of advantages:• Fully integrated into the ET 200SP I/O system (including

TIA Selection Tool and TIA Portal)• High degree of flexibility when it comes to safety applications

via SIMATIC F-CPU or SIRIUS 3SK safety relays up to SIL 3 and PL e Cat. 4.

• Simple, integrated current value transmission• Extensive parameterization by means of TIA Portal• Increase of plant availability through fast replacement of units

(easy mounting and plug-in technology)• Greater endurance and reduced heat losses thanks to hybrid

technology• Less space required in the control cabinet (20 to 80%) as a

result of greater functional density (direct-on-line and reversing starters in same width)

• Extensive diagnostics and information for preventive maintenance

• Parameterizable inputs via 3DI/LC control module• Less wiring and testing required as a result of integrating

several functions into a single device• Lower overheads for stock keeping and configuration as a

result of the wide setting range of the electronic overload release (up to 1:3)

• Technology has lower inherent power losses than speed-controlled drive systems, so that less cooling (and smaller footprint) are possible

• The ET 200SP motor starters can be used with highly energy-efficient IE3/IE4 motors, see Application Manual. Take the current characteristics of the connected motor and motor starter into account when dimensioning. In addition to the rated current, the maximum permissible current range of the motor starter and the ratio of the rated current to the starting current of the motor are relevant.For more information on IE3/IE4, see page 1/7.

Standards and approvals• IEC/EN 60947-4-2• UL 60947-4-2 • CSA• ATEX• IEC 61508-1: SIL 3• ISO 13849: PL e• CCC approval for China

Product versions Article number

Motor starters 3RK1308 – 0 @ @ 0 0 – 0 C P 0

Product function Direct-on-line starters A For motor standard output 0.09 ... 5.5 kW1)

Reversing starters B For motor standard output 0.09 ... 5.5 kW1) Fail-safe direct-on-line starters C For motor standard output 0.09 ... 5.5 kW1) Fail-safe reversing starters D For motor standard output 0.09 ... 5.5 kW1)

Current range 0.1 ... 0.4 A A Maximum current-carrying capacity when starting 4 A0.3 ... 1 A B Maximum current-carrying capacity when starting 10 A0.9 ... 3 A C Maximum current-carrying capacity when starting 30 A2.8 ... 9 A D Maximum current-carrying capacity when starting 90 A4 ... 12 A E Including fan (3RW4928-8VB00),

maximum current-carrying capacity when starting 100 A

Example 3RK1308 – 0 A D 0 0 – 0 C P 0

Product versions Article number

BaseUnit 3RK1908 – 0 A P 0 0 – 0 @ P 0

BU infeed 24 V and 500 V AC A24 V DC B500 V AC Cwithout infeed D500 V AC G with F-DI infeed500 V AC H with F-DI loop-throughwithout infeed J with F-DI loop-throughwithout infeed K with F-DI infeed

Example 3RK1908 – 0 A P 0 0 – 0 A P 0

IC10_08_07.fm Page 97 Sunday, July 19, 2020 8:54 PM

• The ET 200SP motor starters can be used with highly energy efficient IE3/IE4 motors, see Application Manual.Take the current characteristics of the connected motor andmotor starter into account when dimensioning. In addition tothe rated current, the maximum permissible current range ofthe motor starter and the ratio of the rated current to thestarting current of the motor are relevant.For more information on IE3/IE4, see page 1/7.

Page 15: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/15

Hybrid Motor Starters

ET 200SP motor starterGeneral data

8/98 Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

ApplicationThe ET 200SP motor starters are suitable for the following applications:• Switching and monitoring of

- three-phase motors with overload and short-circuit protection (e.g. 400 V asynchronous motors for secondary drives in conveyor systems)

- single-phase motors with overload and short-circuit protection (e.g. 230 V motors for pump applications)

- Resistive loads by means of current value and diagnostics via the maintenance function (e.g. for heaters)

• Plant monitoring and energy management in conveyor systems:By means of the phase asymmetry and zero current detection during current measurement, for example, drive belt monitoring and blocking monitoring are possible.

• Track switching and lifting table control in conveyor systems:Track switches can be implemented using the quick stop function and lifting table controls by means of the "immediate end position disconnection" function without any laborious programming.

• Safe isolation of the drive from main power supply:The isolating functions according to IEC 60947-1 offer protection against inadvertent activation during plant maintenance.

Motor starters in the process industry

For the ET 200SP motor starters, special BaseUnits are available that enable the device to be used in the ET 200SP HA I/O system, too. This is typically used in process engineering applications.

Technical specifications

ET 200SP motor starters

More information

Industry Mall, see www.siemens.com/product?3RK1308

Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/109479973

FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/21800/faq

Article number 3RK1308-0AA00-0CP03RK1308-0BA00-0CP0

3RK1308-0AB00-0CP03RK1308-0BB00-0CP0

3RK1308-0AC00-0CP03RK1308-0BC00-0CP0

3RK1308-0AD00-0CP03RK1308-0BD00-0CP0

3RK1308-0AE00-0CP03RK1308-0BE00-0CP0

Product category Motor startersGeneral technical specifications:Width x height x depth mm 30 × 142 × 150

Design of the switching contact Hybrid

Design of the motor protection Electronic

Installation altitude at height above sea level, maximum

m 4 000

Mounting position Vertical, horizontal, flat (observe derating)

Type of mounting Can be plugged into BaseUnit

Ambient temperatureC°noitarepo gniruD• -25 ... +60C°tropsnart gniruD• -40 ... +70C°egarots gniruD• -40 ... +70

Relative humidity during operation % 10 ... 95

Vibration resistance 15 mm up to 6 Hz; 2 g up to 500 Hz

Shock resistance 6 g / 11 ms

Type of coordination 1

Electrical data:Supply voltage at DC rated value V 24

Operational power for AC-53a at 400 V rated value

kW 0.12 0.25 1.1 4 5.5

Operating frequency, rated value Hz 50 ... 60

Ultimate short-circuit current breaking capacity (Icu)Akeulav detar V004 ta• 55Akeulav detar V005 ta• 55

Adjustable current response value of the inverse-time delayed overload release

A 0.1 ... 0.4 0.3 ... 1 0.9 ... 3 2.8 ... 9 4 ... 12

Max. current carrying capacity at startup A 4 10 30 90 100

Max. permissible voltage for protective separation between main and auxiliary circuit

V 500

Insulation voltage, rated value V 500

Trip class CLASS 5 and 10 adjustable

W

H

D

IC10_08_07.fm Page 98 Sunday, July 19, 2020 8:54 PM

Industry Mall, see www.siemens.com/product?3RK1308Equipment Manual, seehttps://support.industry.siemens.com/cs/ww/en/view/109479973

FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/21800/faq

Remove IP20 infoRevised on 01/06/20

Page 16: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/16

Hybrid Motor Starters

ET 200SP motor starterGeneral data

8/99Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

ET 200SP fail-safe motor starters

Article number 3RK1308-0CA00-0CP03RK1308-0DA00-0CP0

3RK1308-0CB00-0CP03RK1308-0DB00-0CP0

3RK1308-0CC00-0CP03RK1308-0DC00-0CP0

3RK1308-0CD00-0CP03RK1308-0DD00-0CP0

3RK1308-0CE00-0CP03RK1308-0DE00-0CP0

Product category Motor startersGeneral technical specifications:Width x height x depth mm 30 × 142 × 150

Design of the switch contact Hybrid

Design of the motor protection Electronic

Installation altitude at height above sea level, maximum

m 2 000

Mounting position Vertical, horizontal, flat (observe derating)

Type of mounting Can be plugged into BaseUnit

Ambient temperatureC°noitarepo gniruD• -25 ... +60C°tropsnart gniruD• -40 ... +70C°egarots gniruD• -40 ... +70

Relative humidity during operation % 10 ... 95

Vibration resistance 15 mm up to 6 Hz; 2 g up to 500 Hz

Shock resistance 6 g / 11 ms

Type of coordination 1

Electrical data:Supply voltage at DC rated value V 24

Operational power for AC-53a at 400 V, rated value

kW 0.12 0.25 1.1 4 5.5

Operating frequency, rated value Hz 50 ... 60

Ultimate short-circuit current breaking capacity (Icu)Akeulav detar V004 ta• 55Akeulav detar V005 ta• 55

Adjustable current response value of the inverse-time delayed overload release

A 0.1 ... 0.4 0.3 ... 1 0.9 ... 3 2.8 ... 9 4 ... 12

Max. current carrying capacity at startup A 4 10 30 90 100

Max. permissible voltage for protective separation between main and auxiliary circuit

V 500

Insulation voltage, rated value V 500

Trip class CLASS 5 and 10 adjustable

W

H

D

IC10_08_07.fm Page 99 Sunday, July 19, 2020 8:54 PM

Remove IP20 infoRevised on 01/06/20

Page 17: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/17

Hybrid Motor Starters

ET 200SP motor starterGeneral data

8/100 Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

BaseUnits for motor starters

Article number 3RK1908-0AP00-0AP0

3RK1908-0AP00-0BP0

3RK1908-0AP00-0CP0

3RK1908-0AP00-0DP0

3RK1908-0AP00-0GP0

3RK1908-0AP00-0HP0

3RK1908-0AP00-0JP0

3RK1908-0AP00-0KP0

Product designation BaseUnitGeneral technical specifications:Width x height x depth mm 30 × 215 × 75

Ambient temperature• During operation °C -25 ... +60• During transport °C -40 ... +70• During storage °C -40 ... +70

Touch protection against electric shock

Finger-safe

Connections/terminals:Type of connectable conductor cross-sections• At the inputs for supply voltage

- Solid 1 x 0.5 ... 2.5 mm2 --- Finely stranded

with end sleeve1 x 0.5 ... 2.5 mm2 --

- Finely stranded without end sleeve

1 x 0.5 ... 2.5 mm2 --

- Solid for AWG cables 1 x 20 ... 12 --

• For infeed- Solid 1 x 1 ... 6 mm2 -- 1 x 1 ... 6 mm2 -- 1 x 1 ... 6 mm2 --- Finely stranded

with end sleeve1 x 1 ... 6 mm2 -- 1 x 1 ... 6 mm2 -- 1 x 1 ... 6 mm2 --

- Finely stranded without end sleeve

1 x 1 ... 6 mm2 -- 1 x 1 ... 6 mm2 -- 1 x 1 ... 6 mm2 --

- Solid for AWG cables 1 x 18 ... 10 -- 1 x 18 ... 10 -- 1 x 18 ... 10 --

• For load-side outgoing feeder- Solid 1 x 0.5 ... 2.5 mm2

- Finely stranded with end sleeve

1 x 0.5 ... 2.5 mm2

- Finely stranded without end sleeve

1 x 0.5 ... 2.5 mm2

- Solid for AWG cables 1 x 20 ... 12

Type of electrical connection for auxiliary and control circuits

Spring-loaded terminals (push-in)

Miscellaneous:Type of screwdriver tip Slotted

Size of screwdriver tip Standard screwdriver 0.6 mm x 3.5 mm

W

H

D

IC10_08_07.fm Page 100 Sunday, July 19, 2020 8:54 PM

Remove IP20 infoRevised on 01/06/20

Page 18: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/18

8/101Siemens IC 10 · 2020

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

3DI/LC control module

Article number 3RK1908-1AA00-0BP0

Product designation 3DI/LC control module

General technical specifications:Width x height x depth mm 30 × 54.5 × 42.3

Type of product Accessories

Number of digital inputs 4

Installation altitude at height above sea level, maximum

m 2 000

Mounting position Vertical, horizontal, flat

Type of mounting Can be plugged onto motor starter

Ambient temperature• During operation °C -25 ... +60• During transport °C -40 ... +70• During storage °C -40 ... +70

Connections/terminals:Connectable conductor cross-section for auxiliary contacts• Solid or stranded mm² 0.2 ... 1.5• Finely stranded with end sleeve mm² 0.25 ... 1.5• Finely stranded without end sleeve mm² 0.2 ... 1.5

AWG number as coded connectable conductor cross-section

24 ... 16

Type of electrical connection for auxiliary and control circuits

Spring-loaded terminals (push-in)

Electrical data:Type of voltage of the control supply voltage DC

Control supply voltage at DC rated value V 20.4 ... 28.8

Miscellaneous:Type of screwdriver tip Slotted

Size of screwdriver tip Standard screwdriver 0.6 mm x 3.5 mm

W

H

D

IC10_08_07.fm Page 101 Sunday, July 19, 2020 8:54 PM

Hybrid Motor Starters

ET 200SP motor starterGeneral data

Page 19: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/19

8/102 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

■ Selection and ordering data

Adjustable current response value of the inverse-time delayed overload release

Max. current carrying capacity at startup

at 480V

SD Article No. Priceper PU

PU (UNIT,SET, M)

PS*

A A dMotor starters

Direct-on-line starters

3RK1308-0AB00-0CP0

0.1 ... 0.4 3.2 2 3RK1308-0AA00-0CP0 1 1 unit0.3 ... 1 8 2 3RK1308-0AB00-0CP0 1 1 unit0.9 ... 3 24 2 3RK1308-0AC00-0CP0 1 1 unit2.8 ... 9 72 2 3RK1308-0AD00-0CP0 1 1 unit4 ... 12 72 2 3RK1308-0AE00-0CP0 1 1 unit

Reversing starters

3RK1308-0BB00-0CP0

0.1 ... 0.4 3.2 2 3RK1308-0BA00-0CP0 1 1 unit0.3 ... 1 8 2 3RK1308-0BB00-0CP0 1 1 unit0.9 ... 3 24 2 3RK1308-0BC00-0CP0 1 1 unit2.8 ... 9 72 2 3RK1308-0BD00-0CP0 1 1 unit4 ... 12 72 2 3RK1308-0BE00-0CP0 1 1 unit

Fail-safe direct-on-line starters

3RK1308-0CE00-0CP0

0.1 ... 0.4 3.2 2 3RK1308-0CA00-0CP0 1 1 unit0.3 ... 1 8 2 3RK1308-0CB00-0CP0 1 1 unit0.9 ... 3 24 2 3RK1308-0CC00-0CP0 1 1 unit2.8 ... 9 72 2 3RK1308-0CD00-0CP0 1 1 unit4 ... 12 72 2 3RK1308-0CE00-0CP0 1 1 unit

Fail-safe reversing starters

3RK1308-0DE00-0CP0

0.1 ... 0.4 3.2 2 3RK1308-0DA00-0CP0 1 1 unit0.3 ... 1 8 2 3RK1308-0DB00-0CP0 1 1 unit0.9 ... 3 24 2 3RK1308-0DC00-0CP0 1 1 unit2.8 ... 9 72 2 3RK1308-0DD00-0CP0 1 1 unit4 ... 12 72 2 3RK1308-0DE00-0CP0 1 1 unit

NEW NEU

NEW NEU

NEW NEU

NEW NEU

IC10_08_07.fm Page 102 Sunday, July 19, 2020 8:54 PM

Hybrid Motor Starters

ET 200SP motor starterSelection and ordering data IE3/IE4 ready

Page 20: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/20

8/103Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

1) The voltage is looped-through from BaseUnits with infeed to subsequent BaseUnits without infeed.

Type of product Operational voltage of the AC infeed

Supply voltage of the DC infeed

SD Push-in terminals PU (UNIT,SET, M)

PS*

Article No. Priceper PU

V V d

BaseUnits1)

3RK1908-0AP00-0AP0

For motor starters• with AC/DC infeed 500 24 2 3RK1908-0AP00-0AP0 1 1 unit

• with DC infeed -- 24 2 3RK1908-0AP00-0BP0 1 1 unit

• with AC infeed 500 -- 2 3RK1908-0AP00-0CP0 1 1 unit

• without infeed -- -- 2 3RK1908-0AP00-0DP0 1 1 unit

For fail-safe motor starters• with AC infeed,

with F-DI infeed for fail-safe motor starters

500 -- 2 3RK1908-0AP00-0GP0 1 1 unit

• with AC infeed, with F-DI loop-through for fail-safe motor starters

500 -- 2 3RK1908-0AP00-0HP0 1 1 unit

• without AC/DC infeed, with F-DI loop-through for fail-safe motor starters

-- -- 2 3RK1908-0AP00-0JP0 1 1 unit

• without AC/DC infeed, with F-DI infeed for fail-safe motor starters

-- -- 2 3RK1908-0AP00-0KP0 1 1 unit

NEW NEU

Type of product Supply voltage at DC rated value

Loop through the potential group from the left

SD Push-in terminals PU (UNIT,SET, M)

PS*

Article No. Priceper PU

V d

BaseUnits

6ES7193-6BP00-0BA0

For dummy modules• dark, looping through the

potential group24 Yes 1 6ES7193-6BP00-0BA0 1 1 unit

• light, opening a new potential group

24 No 1 6ES7193-6BP00-0DA0 1 1 unit

Control supply voltage at DCrated value

Product function SD Push-in terminals PU (UNIT,SET, M)

PS*

Local control Digital inputs parameterizable

Article No. Priceper PU

V d

3DI/LC control module

3RK1908-1AA00-0BP0

20.4 ... 28.8 Yes Yes 2 3RK1908-1AA00-0BP0 1 1 unit

IC10_08_07.fm Page 103 Sunday, July 19, 2020 8:54 PM

Hybrid Motor Starters

ET 200SP motor starterBase units and control module

Page 21: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/21

8/104 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Load Feeders and Motor Starters for Use in the Control Cabinet

ET 200SP motor starters

8

Product designation Type of product SD Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

Accessories

6ES7133-6CV15-1AM0

BU cover 15 mm for BaseUnits Type A0 or A1

1 6ES7133-6CV15-1AM0 1 5 units

3RK1908-1CA00-0BP0

BU cover 30 mm For protection of empty slots, 30 mm

2 3RK1908-1CA00-0BP0 1 1 unit

3RK1908-1DA00-2BP0

Infeed bus cover(1 bag containing 10 covers)

For ET 200SP 2 3RK1908-1DA00-2BP0 1 1 unit

3RK1908-1EA00-1BP0

Mechanical bracket(1 bag containing 5 mechanical brackets)

Mechanical,for ET 200SP

2 3RK1908-1EA00-1BP0 1 1 unit

3RW4928-8VB00

Fan Can be used for 3RK1308 } 3RW4928-8VB00 1 1 unit

Motor suppression module

3RK1911-6EA00

51erauqS• 3RK1911-6EA00 1 1 unit

3RK1911-6EB00

51dnuoR• 3RK1911-6EB00 1 1 unit

3RK1908-1SK00

Starter Kit consists of 3RK1308-0BC00-0CP0 reversing starter (0.9 ... 3 A), 3RK1908-0AP00-0AP0 BaseUnit with 500 V and 24 V AC/DC infeed, and EMC distance module (consisting of 6ES7193-6BP00-0BA0 BaseUnit plus 6ES7133-6CV15-1AM0 BU cover 15 mm)

5 3RK1908-1SK00 1 1 unitNEW NEU

IC10_08_07.fm Page 104 Sunday, July 19, 2020 8:54 PM

Hybrid Motor Starters

ET 200SP motor starterAccessories

Page 22: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/22

9/2 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of Protection

Introduction

9

Overview

Flexible and cost-efficient distributed starter solutionsBe it their high degree of protection, compact design or inte-grated multifunctionality – our motor starters and soft starters for use in the field are ideal for realizing distributed drive solutions. The modular concepts, distributed power supply and integrated safety technology of our portfolio for a high degree of protection consistently supports current trends in drive technology.

5131KR34031KR3Type Page

ET 200pro motor startersMotor starters in the SIMATIC ET 200pro I/O system up to 5.5 kWStandard motor starters 3RK1304High Feature motor starters 3RK1304

noitcennocsid efas rof noitcnuf rotcennocsid hctiws htiW•seludom rotalosi orp002TE 3RK1304Safety modules local • Isolator module, 400 V disconnecting module 3RK1304

efasIFORP hctiwS-F•efasIFORP seludom ytefaS 6ES7148Accessories for ET 200pro motor starters • Incoming power supply, power loop-through connection on the field device,

motor cable, power bus with power terminal connectors3RK19

ET 200pro – interface modules • For communication with PROFIBUS, PROFINET and IWLAN 6ES71ET 200pro – CPUs • Standard CPUs, fail-safe CPUs 6ES71ET 200pro – I/O modules • Digital/analog expansion modules, fail-safe expansion modules,

power modules, ET 200pro pneumatic interfaces6ES71

ET 200pro PS • Stabilized power supplies 6ES7148ET 200pro FC-2 frequency converters 6SL35ET 200pro add-on products • Modules for EtherNet/IP ZNX:EIPSIRIUS M200D motor startersDistributed motor starters up to 5.5 kWM200D AS-i Basic motor starters 3RK1315M200D AS-i Standard motor starters 3RK1325M200D communication modules for PROFIBUS 3RK1305M200D communication modules for PROFINET 3RK1335M200D motor starter modules 3RK1395Accessories • Incoming power supply, motor cable, power bus with power terminal connectors 3RK1911

• Motor control with I/O communication 3RK1902• Motor control with AS-i communication 3RK1902• Motor control with PROFIBUS 3RK1902• Motor control with PROFINET 3RK1902

Hybrid fieldbus connections• Passive and active 3RK1911

IC10_09_02.fm Page 2 Sunday, July 19, 2020 9:08 PM

Hybrid Motor Starters

For Use in the Field, High Degree of ProtectionIntroduction

6/28

6/29

6/30

6/31

6/34

6/35

6/47

6/48

6/55

6/55

6/55

6/59

6/61

6/62

6/64

6/65

6/67

ST 70

ST 70

ST 70

ST 70

ST 70

D 31.2

Page 23: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/23

9/3Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

General data

9

■ Overview

ET 200pro motor starters in I/O system ET 200pro

SIMATIC ET 200pro is the modular I/O system with high degree of protection IP65/66/67 for local, cabinet-free use. The ET 200pro motor starters with the high degree of protection IP65 are an integral part of ET 200pro.

ET 200pro motor starter: Isolator module, Standard starter and High Feature starter mounted on a wide module rack

ET 200pro motor starters (see pages 9/8 and 9/9)• Only two variants up to 5.5 kW• All settings can be parameterized by bus• Comprehensive diagnostic signals• Support for PROFIenergy• Overload can be acknowledged by remote RESET• Current asymmetry monitoring• Stall protection• EMERGENCY START function on overload• Current value transmission by bus• Current limit monitoring• Full support of acyclic services• Direct-on-line or reversing starters• Power bus connection can be plugged in using Han Q4/2

connectors• Motor feeder with Han Q8/0 plug• Conductor cross-section up to 6 x 4 mm²• 25 A per segment (power looped through using jumper plug)• In the Standard and High Feature versions

(with 4 DI on-board)• Electromechanical switching and electronic switching• Electronic starter for direct activation or with integrated soft

starter function• Supplied with 400 V AC brake contact as an option• Temperature sensor can be connected

(Thermoclick or PTC type A)• Provision of the motor current in PROFIenergy format to

higher-level systems, motor current shutdown in dead times using PROFIenergy

ET 200pro isolator modules (see page 9/10)

The isolator module with switch disconnector function is used for safe disconnection of the 400 V operational voltage during repair work in the plant and provides an integrated group fusing function (i.e. additional group short-circuit protection for all subsequently supplied motor starters).

Depending on the power distribution concept, all stations can be equipped with an isolator module as an option.

Safety applications

Safety Solution local (see page 9/11)

With the Safety local modules• Safety local isolator module and • 400 V disconnecting module with an appropriate connection, safety level PL e (according to ISO 13849-1) can be reached.

Safety Solution PROFIsafe (see page 9/14)

With the Safety PROFIsafe modules • F-Switch and • 400 V disconnecting module with an appropriate connection, safety levels SIL 3 (according to IEC 62061) and PL e (according to ISO 13849-1) can also be reached.

Functionality

With the ET 200pro motor starters, any three-phase loads can be protected and switched.

The ET 200pro motor starters are available with mechanical and also electronic contacts.

The ET 200pro electromechanical starters are offered as direct-on-line starters (DSe) and reversing starters (RSe) as Standard and High Feature versions. There are device versions with or without control for externally fed brakes with 400 V AC.

Compared with the Standard motor starters, the High Feature, mechanical motor starter also has:• Four digital inputs• Advanced parameterization options

The ET 200pro electronic starters are offered as direct-on-line starters (sDSSte/sDSte) and reversing starters (sRSSte/sRSte) in the High Feature version.

Compared with the High Feature mechanical motor starters, the High Feature electronic motor starter also has:• Soft starting and smooth ramp-down function• Deactivated soft start function as an electronic starter for

applications with a high switching frequency• Advanced parameterization options

More information

Homepage, see www.siemens.com/ET200pro

Industry Mall, see www.siemens.com/product?ET200pro

Further components in the ET 200pro distributed I/O system:

• Interface modules, central units, I/O modules, ET 200pro PS, see Catalog ST 70

• ET 200pro FC-2 frequency converters, see Catalog D 31.2

IC10_09_03.fm Page 3 Sunday, July 19, 2020 9:29 PM

Homepage, see www.siemens.com/ET200proIndustry Mall, see www.siemens.com/product?ET200proFurther components in the ET 200pro distributed I/O system:• Interface modules, central units, I/O modules, ET 200pro PS,

see Catalog ST 70• ET 200pro FC-2 frequency converters, see Catalog D 31.2

(see pages 6/28 and 6/29) (see page 6/34)

(see page 6/31)

(see page 6/30)

Hybrid Motor Starters

ET 200pro motor starterGeneral data

Page 24: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/24

Hybrid Motor Starters

ET 200pro motor starterGeneral data

9/4 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

General data

9

As a result of the protection concept with solid-state overload evaluation and the use of SIRIUS switching devices, size S00, additional advantages are realized on the Standard and High Feature motor starters – advantages that soon make themselves positively felt particularly in manufacturing processes with high plant stoppage costs: • Configuration is made easier and flexibility is increased by the

fine modular structure with ET 200pro. When using ET 200pro motor starters, the parts list per load feeder is reduced to two main items: the bus module and the motor starter. This makes the ET 200pro ideal for modular machine concepts or solu-tions for conveying systems and in machine-tool building.

• Expansions are easily possible through the subsequent adding of modules. The innovative plug-in technology also does away with the wiring needed up to now. Through the hot swapping function (disconnection and connection during operation) a motor starter can be replaced within seconds if necessary, without having to shut down the ET 200pro station and with it the process in the plant. The motor starters are therefore recommendable in particular for applications with special demands on availability. Storage costs are also opti-mized by the low level of variance (two units up to 7.5 HP).

• With four locally acting inputs available on the High Feature motor starter it is possible to realize autonomous special functions that work independently of the bus and the higher level control system, e.g. as a quick stop on gate valve controls or limit position disconnectors. In parallel with this, the states of these inputs are signaled to the control system.

Article No. scheme

Note:

The Article No. scheme shows an overview of product versions for better understanding of the logic behind the article numbers.

For your orders, please use the article numbers quoted in the selection and ordering data.

Product versions Article number

Motor starters 3RK1304 – 5 @ S @ 0 – @ A A @

Setting range 0.15 ... 2.0 A K1.5 ... 12 A L

Product function Direct-on-line starters DSe 4 4 StandardReversing starters RSe 4 5 StandardDirect-on-line starters DSe 4 2 High FeatureReversing starters RSe 4 3 High FeatureDirect-on-line starters sDSSte/sDSte

7 2 High Feature

Reversing starters sDSSte/sDSte 7 3 High Feature

Inputs/outputs Without brake output 0With brake output 3 400 V AC, with High Feature + 4 inputs

Example 3RK1304 – 5 K S 4 0 – 4 A A 0

Product versions Article number

Modules 3RK1304 – 0 H S 0 0 – @ A A 0

Product function Isolator modules 6Isolator modules 7 Safety modules local 400 V disconnecting modules 8 Safety modules local/PROFIsafe

Example 3RK1304 – 0 H S 0 0 – 6 A A 0

IC10_09_03.fm Page 4 Sunday, July 19, 2020 9:29 PM

Page 25: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/25

Hybrid Motor Starters

ET 200pro motor starterGeneral data

9/5Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

General data

9

✓ Function available

-- Function not available1) DS .... Direct-on-line starters

RS .... Reversing startersDSS .. Direct-on-line soft startersRSS .. Reversing soft starterse ....... Electronic motor protectionte ...... Full motor protection (thermal + electronic)s ....... Electronic switching with semiconductor.

Type Standard motor starters High Feature motor starters

Technology designation1) DSe, RSe DSe, RSe sDSSte, sDSte, sRSSte, sRSte

Device functions (firmware features) Parameterizable rated operational current ✓

Integrated short-circuit protection ✓

Parameterizable current limit values -- ✓ 2 limit values

Parameterizable response in case of current limit violation -- ✓

Zero current monitoring ✓

Parameterizable response in case of zero current violation ✓

Parameterizable current asymmetry limit % -- Fixed limit value (30 x Ie) ✓ 30 ... 60 x IeParameterizable response in case of asymmetry limit violation ✓

Motor blocking monitoring -- ✓

Parameterizable blocking current limit % -- ✓ 150 ... 1 000 x IeParameterizable blocking time limit s -- ✓ 1 ... 5

Current value transmission ✓

Group warning diagnostics -- ✓ Parameterizable

Group diagnostics ✓ Parameterizable

EMERGENCY START ✓

Digital inputs -- ✓ 4 inputs• Parameterizable input signal -- ✓ Latching/non-latching• Parameterizable input level -- ✓ NC/NO contacts• Parameterizable input signal delay ms -- ✓ 10 ... 80• Parameterizable input signal extension ms -- ✓ 0 ... 200• Parameterizable input control actions -- ✓ 12 different actions

Brake output (400 V AC) ✓ Order option

Parameterizable brake enabling delay s ✓ -2.5 ... +2.5

Parameterizable holding time of the brake during stopping s ✓ 0 ... 25

Parameterizable startup type -- ✓

Parameterizable ramp-down time -- ✓

Parameterizable starting voltage -- ✓

Parameterizable stopping voltage -- ✓

Local device interface ✓

Firmware update ✓ By specialists

Thermal motor model ✓

Parameterizable trip class -- CLASS 10 fixed ✓ CLASS 5, 10, 15, 20

Parameterizable response in case of overload of thermal motor model

-- ✓ 3 possible states

Advance warning limit for motor heating % -- ✓ Parameterizable 0 ... 95

Advance warning limit time-related trip reserve s -- ✓ Parameterizable 0 ... 500

Parameterizable recovery time min -- ✓ 1 ... 30

Parameterizable protection against voltage failure -- Permanently integrated ✓

Reversing start function ✓ Order option

Parameterizable interlock time for reversing starters -- 150 ms fixed ✓ 0 ... 60 s

Integrated logbook functions ✓ 3 device logbooks

Integrated statistics data memory ✓

Parameterizable response in case of CPU/master stop ✓

PROFIenergy profile support• Disconnection of the motor current during idle times ✓• Measured motor current values ✓

Device indications• Group fault SF LED (red)• Switching state STATE LED (red, yellow, green)• Device status DEVICE LED (red, yellow, green)• Digital inputs -- IN 1 ... IN 4, LED

IC10_09_03.fm Page 5 Sunday, July 19, 2020 9:29 PM

Page 26: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/26

Hybrid Motor Starters

ET 200pro motor starterGeneral data

9/6 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

General data

9

■ Benefits

ET 200pro motor starters provide the following advantages:• High flexibility thanks to a modular and compact design • Little variance among all motor starter versions

(two units up to 5.5 kW) • Extensive parameterization using STEP 7 HW Config • Increase of plant availability through fast replacement of units

(easy mounting and plug-in technology)

• Extensive diagnostics and information for preventive maintenance

• Parameterizable inputs for on-site control functions (High Feature)

• Cabinet-free design thanks to high degree of protection IP65

■ Application

The SIMATIC ET 200pro motor starters are ideal for the use of several spatially concentrated distributed drive solutions in which several motors, or digital or analog sensors and actuators are addressed from a distributed station. They are perfectly suited for protecting and switching any AC loads.

Application areas

The SIMATIC ET 200pro motor starters are suitable for numerous sectors of industry, e.g. machinery and plant engineering or conveying applications.

Use of ET 200pro motor starters in conjunction with IE3/IE4 motors

Note:

For the use of ET 200pro motor starters in conjunction with highly energy-efficient IE3/IE4 motors, please observe the information on dimensioning and configuring; see Application Manual.

IC10_09_03.fm Page 6 Sunday, July 19, 2020 9:29 PM

For the use of ET 200pro motor starters in conjunction with highlyenergy-efficient IE3/IE4 motors, please observe the informationon dimensioning and configuring; see Application Manual.

Page 27: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/27

9/7Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

General data

9

Technical specifications

1) DS .... Direct-on-line startersRS .... Reversing startersDSS .. Direct-on-line soft startersRSS .. Reversing soft starterse ....... Electronic motor protectionte ...... Full motor protection (thermal + electronic)s ....... Electronic switching with semiconductor.

2) If the soft starter control function is deactivated, the permissible rated operational current is reduced to 9 A up to CLASS 10.

3) With parameterization as electronic starter max. 4 kW.4) 8-hour operation.

More information

Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/22332388

Notes on security:System networking requires suitable protective measures (including network segmentation for IT security) in order to ensure safe plant operation. For more information on the subject of Industrial Security, see www.siemens.com/industrialsecurity.

Type Standard motor starters High Feature motor startersMechanical switching without inputs

Mechanical switching with inputs

Electronic switching with inputs and soft starter function

Technology designation1) DSe, RSe DSe, RSe sDSSte, sDSte, sRSSte, sRSte

Mechanics and environmentMotor starters or modules that can be connected to ET 200pro With width of 110 mm

max. 8

Mounting dimensions (W x H x D)• Direct-on-line starters and reversing starters mm 110 x 230 x 150 110 x 230 x 160

Permissible ambient temperatureC°noitarepo gniruD• -25 ... +55, from +40 with deratingC°egarots gniruD• -40 ... +70

Permissible mounting position Vertical, horizontal

Vibration resistance acc. to IEC 60068, Part 2-6 g 2

Shock resistance acc. to IEC 60068, Part 2-27 g/ms Half-sine 15/11

Degree of protection IP65

Pollution degree 3, IEC 60664 (IEC 61131)

Electrical specificationsPower consumption at 24 V DC

Am)1U( M/+L tiucric yrailixua morF• Approx. 40Am)2U( 2A/1A tiucric yrailixua morF• Approx. 200

Rated operational current Ie for power bus A 25

Rated operational voltage Ue V AC 400 (50/60 Hz)• Approval according to EN 60947-1, Appendix N V AC Up to 400 (50/60 Hz) Up to 400 (50/60 Hz)

CAVLU dna ASC ot gnidrocca lavorppA• Up to 600 (50/60 Hz) Up to 480 (50/60 Hz)

Approval V101traP ,6010EDVNID• Up to 400 Up to 480Vlavorppa LU dna ASC• Up to 600 Up to 480

Conductor cross-sectionsmmylppus rewop gnimocnI• 2 Max. 6 x 4

Touch protection Finger-safe

Rated impulse withstand voltage Uimp kV 6

Rated insulation voltage Ui V 400

Rated operational current Ie for starters• AC-1 / 2 / 3 at 40 °C AV004 tA- 0.15 ... 2.0/1.5 ... 12.0 0.15 ... 2.0/1.5 ... 12.02)

AV005 tA- 0.15 ... 2.0/1.5 ... 9.0• AC-4 at 40 °C AV004 tA- 0.15 ... 2.0/1.5 ... 4.0

Rated short-circuit breaking capacity kA 100 at 400 V

Type of coordination acc. to IEC 60947-4-1 1

Power of three-phase motors at 400 V kW Max. 5.5 Max. 5.5/43)

Utilization categories AC-1, AC-2, AC-3, AC-4 AC-53a4) (max. 9 A with deactivated soft start function up to CLASS 10)

Protective separation between main and auxiliary circuits V 400, acc. to EN 60947-1, Appendix N

Endurance of contactorselcyc gnitarepO lacinahceM• 30 million --selcyc gnitarepO lacirtcelE• Up to 10 million; depending on the current loading

(see manual)--

Permissible switching frequency Depending on the current loading, motor starting time, and relative ON period (see manual)

Operating times for 0.85 ... 1.1 x Uesmyaled gnisolC• 11 ... 50 --smyaled gninepO• 5 ... 45 --

IC10_09_03.fm Page 7 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterGeneral data

Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/22332388

Notes on security:System networking requires suitable protective measures (including networksegmentation for IT security) in order to ensure safe plant operation.For more information on the subject of Industrial Security, seewww.siemens.com/industrialsecurity.

Page 28: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/28

9/8 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

Standard motor starters

9

■ Overview

The functionality, device functions, and technical specifications of the Standard motor starter are described in "ET 200pro Motor Starters, General data" (see page 9/3 onwards).

■ Selection and ordering data

✓ = Additional price1) Only functions when used together with the backplane bus module and the

wide module rack. The backplane bus module and the wide module rack must be ordered separately (see "Accessories for ET 200pro motor starters", page 9/19).

Version SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Standard motor starters, mechanical Motor protection: thermal model

DSe Standard

DSe direct-on-line starters1)

• Without brake output 2 3RK1304-5@S40-4AA0 1 1 unit• With brake output 400 V AC 2 3RK1304-5@S40-4AA3 1 1 unit

RSe reversing starters1)

• Without brake output 2 3RK1304-5@S40-5AA0 1 1 unit• With brake output 400 V AC 2 3RK1304-5@S40-5AA3 1 1 unit

Setting range Rated operational current

Additionalprice

• 0.15 ... 2.0 A None• 1.5 ... 12.0 A ✓

KL

IC10_09_03.fm Page 8 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterStandard motor starter IE3/IE4 ready

The functionality, device functions, and technical specifications of the Standard motor starter are described in “ET 200pro MotorStarters, General data” see page 6/23 onwards.

Only functions when used together with the backplane bus module and thewide module rack. The backplane bus module and the wide module rackmust be ordered separately (see “Accessories for ET 200pro motorstarters”, page 6/39).

Page 29: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/29

9/9Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

High Feature motor starters

9

■ Overview

The functionality, device functions, and technical specifications of the High Feature motor starter are described in "ET 200pro Motor Starters, General data" (see page 9/3 onwards).

The High Feature motor starter differs from the Standard motor starter in having more parameters and four integrated, freely-parameterizable digital inputs.

■ Selection and ordering data

✓ = Additional price1) Only functions when used together with the backplane bus module and the

wide module rack. The backplane bus module and the wide module rack must be ordered separately (see "Accessories for ET 200pro motor starters", page 9/19).

2) The electronic motor starters can be used not only as electronic motor starters with a high level of switching frequency but also as fully fledged soft starters for soft starting and stopping. The changeover from motor starter to soft starter takes place through reparameterization in HW Config. Depending on the setting, this results in the following current ranges: - Parameterization as electronic motor starter: 0.15 to 2 A and 1.5 to 9 A (4 kW)

- Parameterization as soft starter: 0.15 to 2 A and 1.5 to 12 A (5.5 kW).

Version SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

High Feature motor starters, mechanical Motor protection: thermal model

RSe High Feature

DSe direct-on-line starters1)

• Without brake output and with 4 inputs 2 3RK1304-5@S40-2AA0 1 1 unit• With brake output 400 V AC and 4 inputs 5 3RK1304-5@S40-2AA3 1 1 unit

RSe reversing starters1)

• Without brake output and with 4 inputs 2 3RK1304-5@S40-3AA0 1 1 unit• With brake output 400 V AC and 4 inputs 2 3RK1304-5@S40-3AA3 1 1 unit

Setting range Rated operational current

Additionalprice

• 0.15 ... 2.0 A None• 1.5 ... 12.0 A ✓

High Feature motor starters2), electronicFull motor protection, comprising thermal motor protection and thermistor motor protection

sRSSte High Feature

sDSSte/sDSte direct-on-line starters1)2)

• Without brake output and with 4 inputs 2 3RK1304-5@S70-2AA0 1 1 unit• With brake output 400 V AC and 4 inputs 5 3RK1304-5@S70-2AA3 1 1 unit

Reversing starters sRSSte/sRSte1)2)

• Without brake output and with 4 inputs 2 3RK1304-5@S70-3AA0 1 1 unit• With brake output 400 V AC and 4 inputs 2 3RK1304-5@S70-3AA3 1 1 unit

Setting range Rated operational current

Additionalprice

• 0.15 ... 2.0 A None• 1.5 ... 12.0 A ✓

KL

KL

IC10_09_03.fm Page 9 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterHigh Feature motor starter IE3/IE4 ready

Only functions when used together with the backplane bus module and thewide module rack. The backplane bus module and the wide module rackmust be ordered separately (see “Accessories for ET 200pro motorstarters”, page 6/39).

The functionality, device functions, and technical specificationsof the High Feature motor starter are described in “ET 200proMotor Starters, General data” see page 6/23 onwards.

Page 30: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/30

9/10 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

ET 200pro isolator modules

9

■ Overview

The isolator module with integrated group fusing function (i.e. additional group short-circuit protection for all subsequently supplied motor starters) and switch disconnector function is used for safe disconnection of the 400 V operational voltage in the plant.

Depending on the power distribution concept, all stations can be equipped with an isolator module as an option.

The following properties apply to the isolator module:• Increase of plant availability through fast replacement of units

(easy mounting and plug-in technology) • Cabinet-free design thanks to high degree of protection IP65

The isolator module is available in addition in a safety version (see "Safety local isolator module" on page 9/11).

■ Technical specifications

■ Selection and ordering data

1) Only functions when used together with the related 110 mm backplane bus module and the wide module rack. The backplane bus module and the wide module rack must be ordered separately (see page 9/19).

Type Isolator modules

General dataMounting dimensions (W x H x D)• Direct-on-line starters and reversing

startersmm 110 x 230 x 170

Permissible ambient temperature• During operation °C -25 ... +55• During storage °C -40 ... +70

Permissible mounting position Any

Vibration resistance acc. to IEC 60068 Part 2-6

g 2

Shock resistance acc. to IEC 60068 Part 2-27

g/ms Half-sine 15/11

Power consumption• From auxiliary circuit L+/M (U1) mA Approx. 20• From auxiliary circuit A1/A2 (U2) --

Rated operational current Ie for power bus

A 25

Rated operational voltage Ue V 400

Approvals according to • DIN VDE 0106, Part 101 V Up to 500• CSA and UL V Up to 600

Conductor cross-sections• Incoming power supply mm2 Max. 6 x 4

Degree of protection IP65

Touch protection Finger-safe

Pollution degree 3, IEC 60664 (IEC 61131)

Rated impulse withstand voltage Uimp

kV 6

Rated insulation voltage Ui V 400

Rated operational current Ie for starters

• AC-1/2/3 at 40 °C- At 400 V A 25- At 500 V A 25

Rated short-circuit breaking capacity

kA 50 at 400 V

Type of coordination acc. to IEC 60947-4-1

2

Protective separation between main and auxiliary circuits

V 400, according to DIN VDE 0106, Part 101

Device functions• Group diagnostics Yes, parameterizable

Device indications• Group fault SF LED (red)

Type Isolator modules

Version SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

ET 200pro isolator modules, mechanical

3RK1304-0HS00-6AA0

Isolator modules1)

Rated operational current 25 A 2 3RK1304-0HS00-6AA0 1 1 unit

IC10_09_03.fm Page 10 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterIsolator modules IE3/IE4 ready

The isolator module is available in addition in a safety version(see “Safety local isolator module” on page 6/31).

Only functions when used together with the related 110 mm backplane busmodule and the wide module rack. The backplane bus module and thewide module rack must be ordered separately (see page 6/39).

Page 31: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/31

9/11Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

ET 200pro Safety Motor Starters Solutions Local/PROFIsafe

Safety modules local

9

■ Overview

Safety Solution local

With the Safety local modules• Safety local isolator module and• 400 V disconnecting module with an appropriate connection, safety level PL e (according to ISO 13849-1) can be reached.

ET 200pro motor starter (Safety Solution local): Safety local isolator module, disconnecting module, Standard starter and High Feature starter mounted on a wide module rack

Safety local isolator module

The Safety local isolator module is a repair switch with integrated safety evaluation functions that can be parameterized using DIP switches.

It is used for • Connection of a one- or two-channel EMERGENCY STOP

circuit up to PL e (protective door or EMERGENCY STOP pushbuttons) and parameterizable start behavior

• For controlling the 400 V disconnecting module by means of a safety rail signal

400 V disconnecting module

The 400 V disconnecting module enables the safe disconnec-tion of an operational voltage of 400 V up to PL e. For operation in a Safety Solution local application, it functions only in combination with the Safety local isolator module.

For operation in a Safety PROFIsafe application it functions only in combination with the F-Switch.

Functionality

Safety local isolator module

The Safety local isolator module features the same functions as a standard isolator module with an additional local safety function.

The Safety local isolator module contains a 3TK2841 module and is equipped with M12 terminals for the connection of external safety components.

Terminals 1 and 2 can be used to connect either one- or two-channel EMERGENCY STOP circuits or protective door circuits (IN 1, IN 2).

For monitored starts, an external START switch can be connected to terminal 3.

The required safety functions can be set using two slide switches located under the left M12 opening.

In the event of an EMERGENCY STOP, the Safety local isolator module trips the downstream 400 V disconnecting module. This safely separates the 400 V circuit up to PL e.

In combination with the 400 V disconnecting module, the Safety local isolator module can be used for safety applications up to PL e.

400 V disconnecting module

The 400 V disconnecting module can be used together with the Safety local isolator module for local safety applications and together with the F-Switch for PROFIsafe safety applications.

It contains two contactors connected in series for safety-related disconnection of the main circuit.

The auxiliary circuit supply of the device is over a safety power rail in the backplane bus module.

The 400 V disconnecting module can be used in conjunction with the Safety local isolator module or with the F-Switch for safety applications up to PL e.

IC10_09_03.fm Page 11 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterSafety modules

Page 32: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/32

9/12 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor StartersET 200pro Safety Motor Starters Solutions Local/PROFIsafe

Safety modules local

9

■ Technical specifications

Type Safety local isolator module 400 V disconnecting module

General dataMounting dimensions (W x H x D)• Direct-on-line starters and reversing starters mm 110 x 230 x 170 110 x 230 x 150

Permissible ambient temperature• During operation °C -25 ... +55• During storage °C -40 ... +70

Permissible mounting position Any

Vibration resistance acc. to IEC 60068, Part 2-6 2 g

Shock resistance acc. to IEC 60068, Part 2-27 Half-sine 15 g/11 ms

Power consumption• From auxiliary circuit L+/M (U1) mA Approx. 20• From auxiliary circuit A1/A2 (U2) --

Rated operational current Ie for power bus A 25

Rated operational voltage Ue V 400 (50/60 Hz)

Approval DIN VDE 0106, Part 101 V Up to 500

CSA and UL approval V Up to 600

Conductor cross-sectionsIncoming power supply mm2 Max. 6 x 4

Degree of protection IP65

Touch protection Finger-safe

Pollution degree 3, IEC 60664 (IEC 61131)

Rated impulse withstand voltage Uimp kV 6

Rated insulation voltage Ui V 400

Rated operational current Ie for starters

• AC-1/2/3 at 40 °C- At 400 V A 16 25- At 500 V A 16 25

Rated short-circuit breaking capacity kA 50 at 400 V

Type of coordination acc. to IEC 60947-4-1 2

Protective separation between main and auxiliary circuits V 400, according to DIN VDE 0106, Part 101

Operating times for 0.85 ... 1.1 x Ue• Closing delay ms -- 25 ... 100• Opening delay ms -- 7 ... 10

Device functions• Group diagnostics Yes, parameterizable

Device indications• Group fault SF LED (red)

IC10_09_03.fm Page 12 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterSafety modules

Page 33: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/33

9/13Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

ET 200pro Safety Motor Starters Solutions Local/PROFIsafe

Safety modules local

9

■ Selection and ordering data

1) The Safety local isolator module only functions when used together with the 400 V disconnecting module.

2) Only in combination with the special backplane bus module for the Safety local isolator module (see "Accessories for ET 200pro motor starters", page 9/19).

3) The 400 V disconnecting module functions only when used together with the Safety local isolator module or with the F-Switch.

4) The 400 V disconnecting module functions only when used together with the backplane bus module and the wide module rack. The backplane bus module and the wide module rack must be ordered separately (see "Accessories for ET 200pro motor starters", page 9/19).

Version SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Safety modules local

3RK1304-0HS00-7AA0

Safety local isolator module1)2)

Rated operational current 16 A 5 3RK1304-0HS00-7AA0 1 1 unit

3RK1304-0HS00-8AA0

400 V disconnecting modules3)4)

Rated operational current 25 A 2 3RK1304-0HS00-8AA0 1 1 unit

IC10_09_03.fm Page 13 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterSafety modules IE3/IE4 ready

Only in combination with the special backplane bus module for theSafety local isolator module (see “Accessories for ET 200pro motorstarters”, page 6/39).

The 400 V disconnecting module functions only when used together withthe backplane bus module and the wide module rack. The backplane busmodule and the wide module rack must be ordered separately (see “Accessories for ET 200pro motor starters”, page 6/39).

Page 34: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/34

9/14 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor StartersET 200pro Safety Motor Starters Solutions Local/PROFIsafe

Safety modules PROFIsafe

9

■ Overview

Safety Solution PROFIsafe

With the Safety PROFIsafe modules • F-Switch and • 400 V disconnecting module with an appropriate connection, safety levels SIL 3 (according to IEC 62061) and PL e (according to ISO 13849-1) can be reached.

F-Switch PROFIsafe

Fail-safe digital inputs/outputs in degrees of protection IP65 to IP67 for near-machine, cabinet-free use.

Fail-safe digital inputs• For the fail-safe reading in of sensor information

(one-/two-channel)• Including integrated discrepancy evaluation for 2v2 signals• Internal sensor supplies (incl. testing) available

Fail-safe digital outputs • Three fail-safe PP-switching outputs for safe switching of the

backplane busbars

The F-Switch is certified up to SIL 3/PL e and has detailed diagnostics.

It supports PROFIsafe in PROFIBUS configurations as well as in PROFINET configurations.

Functionality

The PROFIsafe F-Switch is a fail-safe solid-state module for PROFIsafe safety applications. It has two fail-safe inputs and outputs for safe switching of the 24 V supply over backplane busbars. In combination with the 400 V disconnecting module, fail-safe disconnection of ET 200pro motor starters is possible in PROFIsafe applications up to SIL 3/PL e.

400 V disconnecting module

See "Safety modules local", Overview, page 9/11 and Technical specifications, page 9/12.

■ Selection and ordering data

1) The 400 V disconnecting module functions only when used together with the Safety local isolator module or with the F-Switch.

2) The 400 V disconnecting module functions only when used together with the backplane bus module and the wide module rack. The backplane bus module and the wide module rack must be ordered separately (see "Accessories for ET 200pro motor starters", page 9/19).

Version SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Safety modules PROFIsafe

3RK1304-0HS00-8AA0

400 V disconnecting modules1)2)

Rated operational current 25 A 2 3RK1304-0HS00-8AA0 1 1 unit

6ES7148-1FS00-0AB0

F-Switch PROFIsafe

24 V DC, including bus module

Note:

Connection module must be ordered separately

1 6ES7148-4FS00-0AB0 1 1 unit

Connection modules for F-Switch

24 V DC 1 6ES7194-4DA00-0AA0 1 1 unit

IC10_09_03.fm Page 14 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterSafety modules PROFIsafe IE3/IE4 ready

See “Safety modules local”, Overview, page 6/31 and Technicalspecifications, page 6/32.

The 400 V disconnecting module functions only when used together withthe backplane bus module and the wide module rack. The backplane busmodule and the wide module rack must be ordered separately (see “Accessories for ET 200pro motor starters”, page 6/39).

Page 35: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/35

9/15Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

Accessories for ET 200pro motor starters

9

■ Overview

Basic design of an ET 200pro version with (from the left) connection module for IM, interface module for communication (IM), RSM isolator module, two ET 200pro motor starters (MS), and connections for energy

Infeed on the ET 200pro motor starter

Infeed on the RSM isolator module

Legend: Power feeder plug (see page 9/17) Power connection plug (see page 9/17) Power jumper plug (see page 9/17) Motor connection plug (see page 9/17) Motor plug (see page 9/17) Motor plug with EMC suppressor circuit (see page 9/17) Power loop-through plug (see page 9/17) Power connection cable (see page 9/17) Power connection cable for isolator module (see page 9/17) Motor cable (see page 9/18)

M M

6

2

1

5 /

743N

SA

0_00

465a

MSMS

RSM

MS MS

NS

A0_

0046

6a

108

Infeed onET 200pro motor starter

NS

A0_

0046

7a

MSMS

RSM

9

9

Infeed onisolator module

Power connection cable for isolator module

IC10_09_03.fm Page 15 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterAccessories

Legend: Power feeder plug (see page 6/37)b Power connection plug (see page 6/37)c Power jumper plug (see page 6/37)d Motor connection plug (see page 6/37)e Motor plug (see page 6/37)f Motor plug with EMC suppressor circuit (see page 6/37)g Power loop-through plug (see page 6/37)h Power connection cable (see page 6/37)i Power connection cable for isolator module (see page 6/37)j Motor cable (see page 6/38)

Page 36: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/36

Hybrid Motor Starters

ET 200pro motor starterAccessories

9/16 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

Accessories for ET 200pro motor starters

9

Power busThe power supply to the field devices (ET 200pro motor starters, M200D motor starters) is provided via the power bus, in which the power T terminal connectors or power double-T terminal connectors are connected by power bus cables.

FeedersFrom the terminal connectors, spur lines with Han Q4/2 plugs lead to the field devices, from which the motors are supplied with power via motor connection cables.

Interruption-free thanks to power terminal connectorsIn finger-safe connection technology the power T terminal connectors and power double-T terminal connectors connect the components of a feeder to the power bus. They ensure interruption-free operation, i.e. the power bus is not interrupted when the components are unplugged.

Power supply to the motors via the power bus with power T and double-T terminal connectors linked by power bus cables, spur lines to the field devices (motor starters), and power loop-through connections to the motors via motor connection cables

Motor control via PROFIBUSThe interface modules (IM) for PROFIBUS can be combined with three different connection modules for connecting PROFIBUS DP and the power supply:• Direct connection with cable gland• ECOFAST connection with hybrid fieldbus cables (with two

copper cores for data transmission with PROFIBUS DP, and four copper cores for the power supply), and ECOFAST plugs (HanBrid)1)

• M12, 7/8" connection - with M12 connecting cable and M12 plugs for data

transmission with PROFIBUS DP- with 7/8" connecting cable and 7/8" plugs for the power

supply2)

For connection modules with the relevant accessories, see "Accessories for ET 200pro interface modules" in Catalog ST 70 or the Industry Mall.

1) Hybrid fieldbus connections with HanBrid sockets designed as cabinet bushings transmit data and energy from the control cabinet (IP20) to the field (IP65). They are the interface for jointly routing PROFIBUS DP and the auxiliary voltages into the hybrid fieldbus cable (see page 9/46).

2) On the control cabinet bushings with two M12 sockets for the PROFIBUS M12 connecting cables (see page 9/46), the 24 V supply of the motor starters is implemented via separate 7/8" connecting cables.

Motor control via PROFINETFor connection modules with the relevant accessories, see "Accessories for ET 200pro interface modules" in Catalog ST 70 or the Industry Mall.

1211

13 13

11

12

13

Power bus line (sold by the meter)

Power T terminal connector

Power double-T terminal connector

Motors

IC01

_002

30a

ET 200pro

M200DM200D

IC10_09_03.fm Page 16 Sunday, July 19, 2020 9:29 PM

For connection modules with the relevant accessories, see “Accessories for ET 200pro interface modules” in Catalog ST 70 or the Industry Mall.

For connection modules with the relevant accessories, see “Accessories for ET 200pro interface modules” in Catalog ST 70 or the Industry Mall.

Hybrid fieldbus connections with HanBrid sockets designed as cabinetbushings transmit data and energy from the control cabinet (IP20) to thefield (IP65). They are the interface for jointly routing PROFIBUS DP and theauxiliary voltages into the hybrid fieldbus cable (see page 6/66).

On the control cabinet bushings with two M12 sockets for the PROFIBUSM12 connecting cables (see page 6/66), the 24 V supply of the motorstarters is implemented via separate 7/8" connecting cables.

Page 37: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/37

9/17Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

Accessories for ET 200pro motor starters

9

Selection and ordering data

DSnoisreV Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Incoming power supplyPower feeder plugs

Connector set for incoming power supply, e.g. for connecting to T terminal connectors, comprising a coupling enclosure, straight outgoing feeder (with bracket), pin insert for HAN Q4/2, incl. gland

• 5 male contacts, 2.5 mm2 5 3RK1911-2BS60 1 1 unit• 5 male contacts, 4 mm2 5 3RK1911-2BS20 1 1 unit• 5 male contacts, 6 mm2 5 3RK1911-2BS40 1 1 unit

Power connection plugsConnector set for incoming power supply for connection to ET 200pro motor starters/ET 200pro isolator modules, comprising a cable-end connector hood, angular outgoing feeder, female insert for HAN Q4/2, incl. gland

• 5 female contacts, 2.5 mm2 5 3RK1911-2BE50 1 1 unit• 5 female contacts, 4 mm2 5 3RK1911-2BE10 1 1 unit• 5 female contacts, 6 mm2 5 3RK1911-2BE30 1 1 unit

Power connection cables, assembled at one endPower connection cable for ET 200pro motor starters, open at one end, for HAN Q4/2, angular, 4 x 4 mm2

5m5.1 htgneL• 3RK1911-0DB13 1 1 unit5m0.5 htgneL• 3RK1911-0DB33 1 1 unit

Power connection cables for isolator module, assembled at one endPower connection cable for ET 200pro isolator modules, open at one end, for HAN Q4/2, angular, insert turned at isolator module end, 4 x 4 mm2

03m5.1 htgneL• 3RK1911-0DF13 1 1 unit03m0.5 htgneL• 3RK1911-0DF33 1 1 unit

Power loop-through on the field devicePower jumper plugs 2 3RK1922-2BQ00 1 1 unit

Power loop-through plugsConnector set for power loop-through for connection to ET 200pro motor starters/ET 200pro isolator modules, comprising a cable-end connector hood, angular outgoing feeder, pin insert for HAN Q4/2, incl. gland

• 4 male contacts, 2.5 mm2 5 3RK1911-2BF50 1 1 unit• 4 male contacts, 4 mm2 5 3RK1911-2BF10 1 1 unit

Motor cables Motor connection plugs

Connector set for motor cable for connection to ET 200pro motor starters, comprising a cable-end connector hood, angular outgoing feeder, pin insert for HAN Q8/0, incl. gland

• 8 male contacts, 1.5 mm2 5 3RK1902-0CE00 1 1 unit• 6 male contacts, 2.5 mm2 5 3RK1902-0CC00 1 1 unit

Motor plugsConnector set for motor cable for connection to motors, comprising a cable-end connector hood, straight outgoing feeder, female insert for HAN 10e, incl. star jumper, incl. gland

• 7 female contacts, 1.5 mm2 30 3RK1911-2BM21 1 1 set• 7 female contacts, 2.5 mm2 30 3RK1911-2BM22 1 1 set

Motor plugs with EMC suppressor circuitConnector set for motor cable for connection to motors, comprising a cable-end connector hood, straight outgoing feeder, female insert for HAN 10e with EMC suppressor circuit, incl. star jumper, incl. gland

• 7 female contacts, 1.5 mm2 30 3RK1911-2BL21 1 1 set• 7 female contacts, 2.5 mm2 30 3RK1911-2BL22 1 1 set

IC10_09_03.fm Page 17 Sunday, July 19, 2020 9:29 PM

��

Hybrid Motor Starters

ET 200pro motor starterAccessories

Page 38: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/38

9/18 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

Accessories for ET 200pro motor starters

9

Motor cables (continued)Motor cables, assembled at one end

Open at one end, HAN Q8, angular, length 5 m

• For motor without brake, for ET 200pro, 4 x 1.5 mm2 15 3RK1911-0EB31 1 1 unit

• For motor with brake for ET 200pro, 6 x 1.5 mm2 30 3RK1911-0ED31 1 1 unit

• For motor without brake, with thermistor, for ET 200pro, 6 x 1.5 mm2

30 3RK1911-0EF31 1 1 unit

• For motor with brake and thermistor for ET 200pro, 8 x 1.5 mm2

30 3RK1911-0EG31 1 1 unit

Power bus Power T terminal connectors

For 400 V AC, for connection of feeders (e.g. motor starters) by means of standard round cable at any point of the power bus, by insulation displacement connection,used with preassembled bus segments

• 2.5 mm2/4 mm2 5 3RK1911-2BF01 1 1 unit• 4 mm2/6 mm2 5 3RK1911-2BF02 1 1 unit

Power double-T terminal connectors For 400 V AC, for connection of feeders (e.g. motor starters) by means of standard round cable at any point of the power bus, by insulation displacement connection,used with preassembled bus segments,connection of two motor starters possible

• 4 mm2/6 mm2 5 3RK1911-2BG02 1 1 unit

Sealing set (comprising 2 seals) For power T/power double-T terminal connectors

5mm 31...01 Ø htiw selbac rewop roF• 3RK1911-5BA00 1 1 unit5mm 61...31 Ø htiw selbac rewop roF• 3RK1911-5BA10 1 1 unit5mm 91...61 Ø htiw selbac rewop roF• 3RK1911-5BA20 1 1 unitXmm 22...91 Ø htiw selbac rewop roF• 3RK1911-5BA30 1 1 unit5sgulp gniknalB• 3RK1911-5BA50 1 1 unit

Further accessories for power connections

3RK1902-0CW00

Crimping tool for pins/sockets, 4 mm2 and 6 mm2

15 3RK1902-0CW00 1 1 unit

Dismantling tools• For male and female contacts for 9-pole

HAN Q4/2 inserts15 3RK1902-0AB00 1 1 unit

• For male and female contacts for 9-pole HAN Q8 inserts

5 3RK1902-0AJ00 1 1 unit

3RK1902-0CK00

Sealing capsFor 9-pole power sockets

5kcap rep tinu 1• 3RK1902-0CK00 1 1 unit5kcap rep stinu 01• 3RK1902-0CJ00 1 10 units

DSnoisreV Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

IC10_09_03.fm Page 18 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterAccessories

Page 39: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/39

9/19Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor Starters

Accessories for ET 200pro motor starters

9

1) The wide module rack can accommodate all ET 200pro motor starters and any optional modules (isolator module, Safety local isolator module and 400 V disconnecting module).

2) The backplane bus module is a prerequisite for operation of the ET 200pro motor starter and the optional module.

For more connection technology products, see https://support.industry.siemens.com/cs/ww/en/view/65355810.

Version SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Further accessories Module racks, wide1)

• Length 500 mm 1 6ES7194-4GB00-0AA0 1 1 unit• Length 1 000 mm 1 6ES7194-4GB60-0AA0 1 1 unit• Length 2 000 mm 1 6ES7194-4GB20-0AA0 1 1 unit

Module racks, wide, compact1)

• Length 500 mm 1 6ES7194-4GD00-0AA0 1 1 unit• Length 1 000 mm 1 6ES7194-4GD10-0AA0 1 1 unit• Length 2 000 mm 1 6ES7194-4GD20-0AA0 1 1 unit

Backplane bus modules 110 mm2) 2 3RK1922-2BA00 1 1 unit

Backplane bus module for Safety local isolator modules

2 3RK1922-2BA01 1 1 unit

3RK1922-3BA00

Handheld devicesFor ET 200pro motor starters (or for ET 200S High Feature and M200D motor starters) for local operation.

Notes:

• The motor-starter-specific serial interface cables must be ordered separately.

• The RS 232 interface cable 3RK1922-2BP00 is used for the MS ET 200pro.

5 3RK1922-3BA00 1 1 unit

RS 232 interface cableSerial data connection between ET 200pro (or M200D) motor starters and the RS 232 interface of a PC/PG/laptop (with the Motor Starter ES software) or the handheld device 3RK1922-3BA00.

5 3RK1922-2BP00 1 1 unit

USB interface cable, 2.5 mSerial data connection between ET 200pro (or M200D) motor starters and the USB interface of a PC/PG/laptop (with the Motor Starter ES software).

3 6SL3555-0PA00-2AA0 1 1 unit

3RK1901-1KA00

M12 sealing capsFor sealing unused M12 input or output sockets (one set contains ten sealing caps)

} 3RK1901-1KA00 100 10 units

3RK1911-6EA00

Motor suppression moduleRC element for installation in motor terminal box

• Angular design 15 3RK1911-6EA00 1 1 unit

3RK1911-6EB00

• Round design 15 3RK1911-6EB00 1 1 unit

IC10_09_03.fm Page 19 Sunday, July 19, 2020 9:29 PM

Hybrid Motor Starters

ET 200pro motor starterAccessories

For more connection technology products, see https://support.industry.siemens.com/cs/ww/en/view/65355810..

Page 40: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/40

9/20 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionET 200pro Motor StartersSoftware

Motor Starter ES

9

■ Overview

Motor Starter ES for parameterization, monitoring, diagnostics and testing of motor starters

Motor Starter ES is used for the startup, parameterization, diagnostics, documentation and preventive maintenance of SIMATIC ET 200S, ET 200pro, ECOFAST and M200D motor starters.The software program is available in three versions which differ in their user-friendliness, scope of functions and price.

More information

Industry Mall, see www.siemens.com/product?3ZS1

Technical specifications and system requirements, seehttps://support.industry.siemens.com/cs/ww/en/ps/16713/td

IC10_09_04.fm Page 20 Sunday, July 19, 2020 9:59 PM

Hybrid Motor Starters

Motor starter ESSoftware

Industry Mall, see www.siemens.com/product?3ZS1Technical specifications and system requirements, seehttps://support.industry.siemens.com/cs/ww/en/ps/16713/td

Page 41: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/41

9/21Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

General data

9

Overview

SIRIUS M200D AS-i Basic motor starter with manual local operation

The intelligent and highly flexible SIRIUS M200D motor starters for distributed installation start, monitor and protect motors and loads up to 7.5 HP.

The M200D motor starters are available in four versions:

Function available

-- Function not available

Basic functionalityThe versions of the M200D motor starter are equipped with the following properties and functions:• Available as direct-on-line and reversing starters in a rugged

design• Electromechanical or electronic switching version• Low variance – only two device versions up to 7.5 HP thanks

to wide range setting• All versions have the same enclosure size.• Degree of protection IP65• Quick and fail-safe wiring of system and motor cables using

ISO 23570 plug-in connector technology (Q4/2 and Q8/0)• Robust and widely used M12 connection method for digital

inputs and outputs• Integrated feeder connector monitoring• Full motor protection through overload protection and a

temperature sensor (PTC, TC)• Short-circuit and overload protection integrated • Integrated repair switch lockable with three locks

(multi-level service)• Uniform wiring to the SINAMICS G110D, SINAMICS G110M

and SINAMICS G120D frequency inverters and to the ET 200pro distributed I/O system

• Extensive diagnostics concept using LEDs • Optional integrated manual local control with key-operated

switch (ordering option)• Optionally available brake actuation with voltages from

180 V DC (no rectifier needed in motor) or 230/400 V AC (ordering options)

Article No. scheme

Note:

The Article No. scheme shows an overview of product versions for better understanding of the logic behind the article numbers.

For your orders, please use the article numbers quoted in the selection and ordering data.

M200DAS-i Basic

M200DAS-i Standard

M200DPROFIBUS

M200DPROFINET

Motor control withAS-i communication PROFIBUS PROFINET

Mechanical or electronic switching

Electronic switching with soft starter functionality--

More information

Homepage, see www.siemens.com/motorstarter

Industry Mall, see www.siemens.com/product?M200D

TIA Selection Tool Cloud (TST Cloud), see https://www.siemens.com/tstcloud/?node=MS_M200D

Product versions Article number

Motor starters 3RK13 @ 5 – 6 @ S @ 1 – @ A @ @

cisaB i-SAepyT 1 AAS-i Standard 2 APROFIBUS/PROFINET 9 D

Setting range for rated operational current IA

0.15 ... 2 A K1.5 ... 9 A N1.5 ... 12 A L

Starter version Electromechanical starters 4 with integrated contactorElectronic starters 7 with thyristors

Product function Direct-on-line starters 0Reversing starters 1Direct-on-line starters 2 with manual local operationReversing starters 3 with manual local operation

Brake actuation None 0230/400 V AC 3180 V DC 5

Example 3RK13 1 5 – 6 K S 4 1 – 3 A A 0

IC10_09_05.fm Page 21 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D motor startersGeneral data

Homepage, see www.siemens.com/motorstarterIndustry Mall, see www.siemens.com/product?M200DTIA Selection Tool Cloud (TST Cloud), seehttps://www.siemens.com/tstcloud/?node=MS_M200D

Page 42: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/42

Hybrid Motor Starters

SIRIUS M200D motor startersGeneral data

9/22 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

General data

9

■ Benefits

M200D motor starters provide the following advantages for customers:• High plant availability through plug-in capability of the main

circuit, communication and I/Os – relevant for installing and replacing devices

• Cabinet-free construction and near-motor installation thanks to the high degree of protection IP65

• The motor starters record the actual current flow for the parameterizable electronic motor overload protection. Reliable messages concerning the overshooting or undershooting of setpoint values ensure comprehensive motor protection. All motor protection functions can be defined by simple parameterization

• Low stock levels and low order costs thanks to a wide setting range for the electronic motor protection of 1:10 (only two device versions up to 7.5 HP)

• The integrated wide range for the current enables a single device to cover numerous standard motors of different sizes.

• Comprehensive offering of accessories, including ready-assembled cables

• The M200D motor starters can be installed with a few manual steps. The integrated plug-in technology enables far lower wiring outlay: Preassembled cables can be plugged directly onto the motor starter module.

• Easy and user-friendly installation because all versions have the same enclosure dimensions.

• Fast and user-friendly commissioning using optional manual local operation

• Increase of process speed through integrated functions such as "Quick Stop" and "Disable Quick Stop", e.g. at points and crossings

• Optional manual local control with momentary-contact and latching operation for easier startup and easier servicing

■ Application

The high degree of protection IP65 makes the M200D motor starters suitable in particular for use on extensive conveying systems such as are found in mail sorting centers, airports, automotive factories and the packing industry.

For simple drive tasks, particularly in conveyor applications, the new SINAMICS G110D frequency inverter series with a perform-ance range from 0.75 kW to 7.5 kW and degree of protection IP65 is the ideal partner for the M200D motor starters.

SINAMICS G110D converters allow for stepless speed control of three-phase asynchronous motors and comply with the require-ments for materials handling applications with frequency control.

For simple drive tasks in conveyor applications in which a frequency inverter integrated into the motor is required, the SINAMICS G110M frequency inverter with a performance range from 0.37 kW to 4 kW and degree of protection IP65/66 is the ideal partner. The SINAMICS G110M is available individually as a frequency converter for self-assembly and pre-mounted on SIMOGEAR geared motors, and with its conveyor-specific functions it satisfies the requirements of conveyor technology applications.

Use of SIRIUS M200D motor starters in conjunction with IE3/IE4 motors

Note:

For the use of SIRIUS M200D motor starters in conjunction with highly energy-efficient IE3/IE4 motors, please observe the information on dimensioning and configuring, see Application Manual.

IC10_09_05.fm Page 22 Sunday, July 19, 2020 10:22 PM

For the use of SIRIUS M200D motor starters in conjunction withhighly energy-efficient IE3/IE4 motors, please observe theinformation on dimensioning and configuring, see ApplicationManual..

Page 43: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/43

9/23Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

M200D Motor Starters for AS-Interface

General data

9

OverviewFor motor control using AS-Interface there are the following M200D motor starter versions: SIRIUS M200D AS-i Basic and SIRIUS M200D AS-i Standard (basic functionality, see page 9/21 "SIRIUS M200D Motor Starters" "General data" "Overview").

SIRIUS M200D AS-i BasicFunctionality• Easy and fast on-site startup through parameterization of local

setting knobs (DIP switches) and rotary coding switches for adjusting the rated operational current. The rotary coding switch has an OFF position for deactivating the overload protection with the help of the thermal motor model when using a temperature sensor.

Communications• AS-i communication with A/B addressing according to

Spec V2.1• The AS-i bus is connected cost-effectively using an

M12 connection on the device. Of the four digital inputs, two are contained in the process image and can therefore be used in the PLC program. The other two inputs are locally effective and permanently assigned with functions.

• The LEDs can provide comprehensive diagnostics of the device on the spot. In addition to diagnostics using the PAE process image, the device can create up to 15 different diagnostic signals per slave. The message with the highest priority can be read out through the AS-i communication. This is yet another new development which distinguishes the M200D AS-i Basic motor starter from the rest of the market and adds innovative technology, maximum availability and transparency to the system.

SIRIUS M200D AS-i StandardThe intelligent and highly flexible M200D AS-i Standard motor starter in A/B technology starts and protects motors and loads up to 5.5 kW. They are available in direct-on-line or reversing starter versions, in a mechanical version and also an electronic version (the latter with soft start function).

The M200D AS-i Standard motor starter is the most functional member of the SIRIUS motor starter family in the high degree of protection IP65 for AS-i communication. Consistency with other products of the SIRIUS M200D motor starter range and with the frequency converter and ET 200pro I/O system is assured.

Functionality• AS-i communication with A/B addressing according to

Spec 3.0• Electronic version also with soft start function • AS-i slave profile 7AE/7A5 with process image 6E/4A • Full TIA integration: All digital inputs and outputs exist in the

cyclic process image and are visible through AS-i, providing maximum flexibility and best adaptability to the application.

• Additionally expanded diagnostics using data record through AS-i bus

• Complete plant monitoring using statistics data record and current value monitoring by means of data records

• Parameterization through AS-i bus with the help of data records or an expanded process image from the user program

• Control of the motor starter using a command data record from the user program

• Flexible assignment of the digital inputs and outputs with all available assignable input actions

• Parameterization using Motor Starter ES at the local interface (ordering option for startup software)

• Diagnostics with the help of Motor Starter ES (ordering option for startup software)

Mounting and installationThe M200D motor starters can be installed with a few manual steps. The integrated plug-in technology enables far lower wir-ing outlay. Connecting cables can be plugged directly onto the motor starter module. Swapping of the connecting wires and malfunctions within the plant are prevented by preassembled cables. The AS-i bus is connected cost-effectively using an M12 connection on the device. All versions have identical enclosure dimensions for easier system design and conversion.

Parameterization and configuration

The particularly robust M200D AS-i Standard motor starter is characterized by numerous functions which can be flexibly parameterized. It enables highly flexible parameterization through the AS-i bus using data records from the user program as well as user-friendly local parameterization using the Motor Starter ES startup software through the local point-to-point interface.

Functions can be flexibly assigned to the digital inputs and outputs, adapting them to all possible conveyor applications. All motor protection functions, limit values and reactions can be defined by parameterization. The AS-i Standard is unique. In its 6E/4A process image the motor starter sends all four digital inputs and the digital output via the process image to the PLC in cyclic mode. System configuration and system documentation are facilitated not least by a number of CAX data.

Operation

The new generation of motor starters is characterized by its advanced functionality, maximum flexibility and extremely high degree of automation.

All digital inputs and outputs exist in the cyclic process image. All limit values for monitoring functions and their reactions are parameterizable and therefore adaptable to the application. The motor starters record the actual current flow. Evaluating the current of the parameterizable solid-state overload protection increases the availability of the drives, as do reliable messages concerning the overshooting or undershooting of setpoint values.

Diagnostics and maintenance

The M200D sets new standards for diagnostics. In addition to diagnostics using the PAE process image and diagnostics by "parameter echo" (up to 15 different diagnostic signals per slave can be read out via AS-i communication), the possibility of reading out diagnostic data records is unique on the market.

The AS-i Standard is recommended in particular for expansive and highly automated system components because the possi-bility of monitoring devices and systems with data records (statistical data, measured values and device diagnostics) provides an in-depth view of the plant from the control room, guaranteeing the monitoring process and increasing plant availability.

Preventive maintenance can be carried out with the integrated maintenance timer and plant downtimes prevented as a result in advance.

Local control of a drive is possible using the ordering option with integrated manual operation. This is yet another new develop-ment which distinguishes the M200D AS-i Standard motor starter from the rest of the market and adds innovative technology, maximum availability and transparency to the plant.

IC10_09_05.fm Page 23 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D motor startersGeneral data

For motor control using AS-Interface there are the followingM200D motor starter versions: SIRIUS M200D AS-i Basic andSIRIUS M200D AS-i Standard (basic functionality, see page 16/41“SIRIUS M200D Motor Starters” “General data” “Overview”).

Page 44: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/44

9/24 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersM200D Motor Starters for AS-Interface

General data

9

Function available

-- Function not available1) The data records are a reduced selection compared with

PROFIBUS/PROFINET.

SIRIUS M200D SIRIUS M200DAS-i Basic AS-i Standard

Device functions (firmware features)Slave on the busFieldbus AS-i

Slave type A/B acc. to Spec 2.1 A/B acc. to Spec 3.0

Profile 7.A.E 7.A.E & 7.A.5

Number of assigned AS-i addresses on the bus 1 2

Number of stations per AS-i master Max. 62 devices Max. 31 devices

AS-i master profile M3 and higher M4 and higher

Parameter assignmentDIP switches --

Potentiometer for rated operational current --

Motor Starter ES --

--i-SA hguorht sdrocer ataD

DiagnosticsDiagnostics through parameter channel

Acyclic through data records --

Expanded process image PAE 4 bytes --

Process imageProcess image 4E/3A 6E/4A

Data channelsLocal optical interface (manual local)

AS-i bus

Motor Starter ES through local interface --

Motor Starter ES through bus --

Data records1) (acyclic)Parameter assignment --

--scitsongaiD

Measured values --

--scitsitatS

Commands --

InputsNumber 4

• Of these in the process image 2 through AS-i 4 through AS-i

Input action For permanently assigned functions, Parameterizable: flexible

Quick stop Permanent function: latching, edge-triggered Parameterizable function: latching (edge-triggered), non-latching (level-triggered)

OutputsNumber 1

Output action Permanent function: assigned with group fault Parameterizable: For function,

Brake output180 V DC / 230/400 V AC / none

Motor protectionOverload protection Electronic, wide range 1:10

Short-circuit protection

Full motor protection

Temperature sensor Parameterizable using DIP switches: PTC or Thermoclick or deactivated

Parameterizable via Motor Starter ES, data record: PTC or Thermoclick or deactivated

IC10_09_05.fm Page 24 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D motor starters for AS-InterfaceGeneral data

see manual

see manual

Page 45: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/45

Hybrid Motor Starters

SIRIUS M200D motor starters for AS-InterfaceGeneral data

9/25Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

M200D Motor Starters for AS-Interface

General data

9

✓ Function available

-- Function not available

■ Application

The M200D AS-i standard is particularly suitable for highly auto-mated applications in conveyor systems requiring devices and systems to be monitored to prevent or limit plant downtime. The option of planning the functions of the motor starter or its interfaces also creates the prerequisite for fine-adjustment to the function of the motor starter in the application and hence provides for extreme flexibility.

Use of M200D motor starters in conjunction with IE3/IE4 motors

Note:

For the use of SIRIUS M200D motor starters in conjunction with highly energy-efficient IE3/IE4 motors, please observe the information on dimensioning and configuring, see Application Manual.

■ Technical specifications

SIRIUS M200D SIRIUS M200D

AS-i Basic AS-i Standard

Device functions (firmware features) (continued)Device function

Repair switch ✓

Current limit monitoring bottom -- ✓ Parameterizable

Current limit monitoring top -- ✓ Parameterizable

Zero current detection ✓ Permanent function: disconnection, less than 18.75% of the rated operational current Ie

✓ Parameterizable

Blocking current ✓ Permanent function: starting up of the motor: Tripping limit up to 800% of the rated operational current Ie for 10 s

Active operation: Threshold for tripping "blocking current" up to 400% of the rated operational current Ie

✓ Parameterizable

Asymmetry ✓ Permanent function: up to 30% of the rated operational current Ie (only mechanical MS)

✓ Parameterizable

Load type ✓ Permanent function: Three-phase ✓ Parameterizable: single-phase and three-phase

Shutdown class ✓ Parameterizable using DIP switches: CLASS 10/deactivated

Parameterizable via Motor Starter ES, data record: CLASS 5, 10, 15, 20

Protection against voltage failure ✓ ✓ Parameterizable: activated/deactivated

Soft starter control function

Soft start function -- ✓ Only solid-state version

Bypass function -- ✓ Only solid-state version

More information

Manuals for SIRIUS M200D:

• AS-i Basic, see https://support.industry.siemens.com/cs/ww/en/view/35016496

• AS-i Standard, see https://support.industry.siemens.com/cs/ww/en/view/38722160

FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16324/faq

Notes on security:

In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens products and solutions represent only one component of such a concept.

For more information on the subject of Industrial Security, see www.siemens.com/industrialsecurity.

IC10_09_05.fm Page 25 Sunday, July 19, 2020 10:22 PM

For the use of SIRIUS M200D motor starters in conjunction withhighly energy-efficient IE3/IE4 motors, please observe theinformation on dimensioning and configuring,; see Application Manual.

Manuals for SIRIUS M200D:• AS-i Basic, see

https://support.industry.siemens.com/cs/ww/en/view/35016496• AS-i Standard, see

https://support.industry.siemens.com/cs/ww/en/view/38722160FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16324/faq

Notes on security:In order to protect plants, systems, machines and networks against cyberthreats, it is necessary to implement – and continuously maintain – a holistic,state-of-the-art industrial security concept. Siemens products and solutionsrepresent only one component of such a concept.For more information on the subject of Industrial Security, seewww.siemens.com/industrialsecurity.

Page 46: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/46

9/26 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersM200D Motor Starters for AS-Interface

General data

9

1) DS .... Direct-on-line startersRS .... Reversing startersDSS .. Direct-on-line soft startersRSS .. Reversing soft starterste ...... Full motor protection (thermal + electronic)s ....... Electronic switching with semiconductor.

2) Only systems with grounded neutral point permitted.

Type M200D motor startersAS-i Basicelectromechanical switching

AS-i Basicelectronic switching

AS-i Standardelectromechanical switching

AS-i Standardelectronic switching

Technology designation1) DSte/RSte sDSte/sRSte DSte/RSte sDSSte/sRSSteMechanics and environmentMounting dimensions (W x H x D) mm 294 x 215 x 159

Permissible ambient temperatureC°noitarepo gniruD• -25 ... +55C°egarots gniruD• -40 ... +70

Weight g 2 880/3 130 3 220/3 420 2 880/3 130 3 220/3 420

Permissible mounting position Vertical, horizontal, lying

Vibration resistance acc. to IEC 60068 Part 2-6 g 2

Shock resistance • Acc. to IEC 60068 Part 2-27 g/ms 12/11 half-sine• Without influencing the contact position g/ms 9.8/5 or 5.9/10

Degree of protection acc. to IEC 529 IP65

Installation altitude• Up to 1 000 m No derating• Up to 2 000 m 1% per 100 m

Cooling Convection

Protection class IEC 536 (VDE 0106-1) 1

Electrical specificationsControl circuitOperating voltage UAs-i V DC 26.5 ... 31.6

Supply voltage Uaux V DC 20.4 ... 28.8

Power consumption from AS-i (incl. 200 mA sensor supply) mA < 300

Current consumption from Uaux (without digital output)Am.xaM• 155 15 (direct-on-line)/

175 (reversing)155 15 (direct-on-line)/

175 (reversing)Am.pyT• 75 10 (direct-on-line)/

75 (reversing)75 10 (direct-on-line)/

75 (reversing)

Main circuitMaximum power of three-phase motors at 400 V AC kW 5.5 4 5.5 5.5

Rated operational voltage UeCAV1-74906NE ot .cca lavorppA• 400 (50/60 Hz)CAVASC dna LU ot .cca lavorppA• 600 (50/60 Hz) 480 (50/60 Hz) 600 (50/60 Hz) 480 (50/60 Hz)

Aegnar tnerruc lanoitarepo detaR• 0.15 ... 2/1.5 ... 12 -- 0.15 ... 2/1.5 ... 12 --• Rated operational current range for soft starting A -- 0.15 ... 2/1.5 ... 12• Rated operational current range for direct-on-line starting A -- 0.15 ... 2/1.5 ... 9 -- 0.15 ... 2/1.5 ... 9

Rated operational current for starters Ie at 400 V ACA3/2/1-CA ta V004• 12 -- 12 --A3/2/1-CA ta V005• 9 -- 9 --A4-CA ta V004• 4 -- 4 --Aa35-CA ta V004• -- 9 -- 12 for soft starting

9 for direct-on-line starting

Mechanical endurance of contactor Operating cycles 30 million -- 30 million --

Trip class CLASS 10 CLASS 5, 10, 15, 20

Type of coordination acc. to IEC 60947-4-1 1 (2 for device version 2A)

1 1 (2 for device version 2A)

1

Permissible switching frequencyRated ultimate short-circuit breaking capacity Iq

AkCAV004 tA• 50AkCAV005 tA• 502) 202) 50 202)

Short-circuit protection • At Iemax = 2 A Integrated, 2 x13 Ie = 26 A• At Iemax = 9/12 A Integrated, 2 x13 Ie = 208 A

Brake actuation (option)Operational voltage V 230/400 AC or 180 DC

Uninterrupted current A < 0.5 at 230/400 V AC< 0.8 at 180 V DC

Short-circuit protection Yes, 1 A melting fuse

IC10_09_05.fm Page 26 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D motor starters for AS-InterfaceGeneral data

see manual see manual

Page 47: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/47

9/27Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

M200D Motor Starters for AS-Interface

M200D Basic motor starters

9

■ Selection and ordering data

✓ = Additional price

Version SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Electromechanical starters (with integrated contactor)15 3RK1315-6@S41-@AA@ 1 1 unit

Rated operational current setting range/A Additional price

• 0.15 ... 2 None

• 1.5 ... 12 ✓

Direct-on-line starters/reversing starters

• Direct-on-line starters None

• Reversing starters ✓

• Direct-on-line starters with manual local operation ✓

• Reversing starters with manual local operation ✓

Brake actuation

• Without brake actuation None

• Brake actuation (230/400 V AC) ✓

• Brake actuation (180 V DC) ✓

Electronic starters (with thyristors)15 3RK1315-6@S71-@AA@ 1 1 unit

Rated operational current setting range/A Additional price

• 0.15 ... 2 None

• 1.5 ... 9 ✓

Direct-on-line starters/reversing starters

• Direct-on-line starters None

• Reversing starters ✓

• Direct-on-line starters with manual local operation ✓

• Reversing starters with manual local operation ✓

Brake actuation

• Without brake actuation None

• Brake actuation (230/400 V AC) ✓

• Brake actuation (180 V DC) ✓

M200D AS-i Basic without manual local operation M200D AS-i Basic with manual local operation

K

L

0

1

2

3

0

3

5

K

N

0

1

2

3

0

3

5

IC10_09_05.fm Page 27 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D motor starters for AS-InterfaceBasic motor starter IE3/IE4 ready

Page 48: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/48

9/28 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersM200D Motor Starters for AS-Interface

M200D Standard motor starters

9

■ Selection and ordering data

✓ = Additional price

M200D AS-i Standard without manual local operation M200D AS-i Standard with manual local operation

Version SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

Electromechanical starters (with integrated contactor)15 3RK1325-6@S41-@AA@ 1 1 unit

Rated operational current setting range/A Additional price

• 0.15 ... 2 None

• 1.5 ... 12 ✓

Direct-on-line starters/reversing starters

• Direct-on-line starters None

• Reversing starters ✓

• Direct-on-line starters with manual local operation ✓

• Reversing starters with manual local operation ✓

Brake actuation

• Without brake actuation None

• Brake actuation (230/400 V AC) ✓

• Brake actuation (180 V DC) ✓

Electronic starters (with thyristors)15 3RK1325-6@S71-@AA@ 1 1 unit

Rated operational current setting range/A Additional price

• 0.15 ... 2 None

• 1.5 ... 12 ✓

Direct-on-line starters/reversing starters

• Direct-on-line starters None

• Reversing starters ✓

• Direct-on-line starters with manual local operation ✓

• Reversing starters with manual local operation ✓

Brake actuation

• Without brake actuation None

• Brake actuation (230/400 V AC) ✓

• Brake actuation (180 V DC) ✓

K

L

0

1

2

3

0

3

5

K

L

0

1

2

3

0

3

5

IC10_09_05.fm Page 28 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D motor starters for AS-InterfaceStandard motor starter IE3/IE4 ready

Page 49: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/49

9/29Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

M200D Motor Starters for PROFIBUS/PROFINET

General data

9

OverviewThe intelligent, highly flexible M200D PROFIBUS/PROFINET motor starters are the most functional motor starters of the SIRIUS motor starter family in the high degree of protection IP65 for PROFIBUS/PROFINET communication.

They start and protect motors and loads up to 7.5 HP. Direct-on-line and reversing starter versions are available, in a mechanical version and also an electronic version (the latter with soft start function).

The particularly robust M200D PROFIBUS/PROFINET motor starters are characterized by numerous functions which can be flexibly parameterized. Their modular design comprises a motor starter module and a communication module.

The M200D PROFINET motor starters enable TIA-integrated parameterization through PROFINET from STEP 7 – in familiar, user-friendly manner with the look and feel of PROFIBUS.

Functionality• For basic functionality, see page 9/21 "SIRIUS M200D Motor

Starters" "General data" "Overview"• Electronic version also with soft start function • Robust and widely used M12 connection method for the

digital inputs and outputs and the PROFIBUS/PROFINET bus connection

• All four digital inputs and two digital outputs exist in the cyclic process image. This provides complete transparency of the process on the control level

• Full TIA integration: All digital inputs and outputs exist in the cyclic process image and are visible through the bus, providing maximum flexibility and excellent adaptability to the application

• Flexible assignment of the digital inputs and outputs with all available assignable input actions

• Extensive diagnostics concept using LEDs and through the bus with the TIA-compatible mechanisms

• Expanded diagnostics using data records• Complete plant monitoring using statistics data record and

current value monitoring by means of data records• Parameterization through PROFIBUS/PROFINET bus with the

help of data records from the user program• Control of the motor starter using a command data record from

the user program• Removable modular control unit – quicker device replacement

and therefore lower costs when device outages occur – since existing wiring is on the control unit and only one device needs to be replaced

• Parameterization in STEP 7 HW Config using Motor Starter ES (ordering option for startup software)

• Startup and diagnostics with the help of Motor Starter ES (ordering option for startup software)

• Trace function through Motor Starter ES for optimized startup and tracking of process and device values

Only with PROFINET:• Just one bus system from the MES level to the devices – no

routers • More stations on the bus and possible configuration of flexible

bus structures• Automatic re-parameterization in case of device replacement

thanks to proximity detection• Wireless integration of plant segments in difficult

environments using WLAN • Easier expansion of the system thanks to a higher number of

stations on the bus and elimination of terminating resistors

M200D motor starter module for PROFIBUS/PROFINET (without communication module)

M200D communication module for PROFIBUS

M200D communication module for PROFINET

IC10_09_05.fm Page 29 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D motor starters for PROFIBUS/PROFINETGeneral data

For basic functionality, see page 16/41 “SIRIUS M200D Motor Starters” “General data” “Overview”

Page 50: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/50

Hybrid Motor Starters

SIRIUS M200D motor starters for PROFIBUS/PROFINETGeneral data

9/30 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersM200D Motor Starters for PROFIBUS/PROFINET

General data

9

Mounting and installation

The M200D PROFIBUS/PROFINET motor starter is comprised of the communication module and the motor starter module. Only the motor starter module has to be replaced therefore when replacing devices. This saves time and money. The communica-tion module remains as an active station on the bus and all other system components continue running. This prevents downtimes.

The integrated plug-in technology enables far lower wiring outlay: Connecting cables can be plugged directly onto the motor starter module. The PROFINET bus is connected cost-effectively using an M12 connection on the device. All versions have identical enclosure dimensions for easier system design and conversion.

Parameterization and configuration

All motor protection functions, limit values and reactions can be defined by parameterization.

The user has several user-friendly options for the parameteriza-tion. In addition to parameterization directly from STEP 7, which also permits automatic re-parameterization in case of device re-placement, it is possible to use the user-friendly Motor Starter ES startup software. By connecting a programming device directly to PROFIBUS/PROFINET and the Motor Starter ES startup software, the devices can also be conveniently programmed from a central point through the bus. Also, parameters can be changed during operation from the user program using the data record mechanism so that the function of the motor starter is adapted to the process when required. With the help of a PC and the Motor Starter ES software it is also possible to perform the parameterization through the local point-to-point interface on-site.

Functions can be flexibly assigned to the digital inputs and outputs, adapting them to all possible conveyor applications. All digital inputs and outputs exist in the cyclic process image. All limit values for monitoring functions and their reactions are parameterizable and therefore adaptable to the application. Consistency with other products of the SIRIUS M200D motor starter range and with the frequency converter and ET 200pro I/O system is assured.

Only with M200D PROFINET motor starters

Thanks to the integrated proximity detection, the device name does not need to be issued manually when a device is replaced. The name is issued automatically by the neighboring devices which note the "names" of the devices in their proximity. No additional startup measures are required therefore when replacing a device.

The new motor starter generation is characterized by high functionality, maximum flexibility and the highest level of automa-tion. PROFINET is especially recommended for large-scale and highly automated system components, since the possibility of monitoring the devices or plants with data records (statistical data, measured values and device diagnostics) ensures a broader insight into the plant by the control room, and hence increases the availability of the plant sustainably.

Operation

The motor starters record the actual current flow. Evaluating the current of the parameterizable solid-state overload protection increases the availability of the drives, as do reliable signals concerning the overshooting or undershooting of setpoint values.

Diagnostics and maintenance

Diagnostics is provided through numerous mechanisms – and can be used as the customer prefers.

The motor starter is TIA-diagnostics compatible, which means that when a fault is identified, a diagnostics alarm is distributed, which invokes the diagnostics OB in the case of a SIMATIC control. The fault can be evaluated as usual in the user program.

The M200D motor starter offers a large variety of diagnostics data through data records. Its functionality is without equal on the market. There are extensive options for reading out data from the motor starter for monitoring devices, systems or processes.

The motor starter is equipped internally with three logbooks for device faults, motor starter trips and events that are issued with a time stamp. These logbooks can be read out of the motor starter at any time in the form of data records and provide the plant operator with plenty of information about the state of his plant and process which he can use to carry out improvements.

With the slave pointer and statistical data functions it is possible to read out, for example, the maximum internal current values or the number of motor starter connection operations for plant monitoring purposes. This allows deviations in the process to be monitored, but also optimum initial commissioning to take place. The user can draw conclusions about the actual load conditions of the devices in his process and on this basis can optimize his plant maintenance intervals.

The device diagnostics data record contains details of all the states of the motor starter, the device configuration and the communication status as a basis for central device and plant monitoring.

With installation and maintenance functions (I&M), information on modules employed and data specified by the user during configuration, such as location designations, are stored in the motor starter. I&M functions are used for troubleshooting faults and localizing changes in hardware in a plant or checking the system configuration. Reordering a device is particularly easy as the result.

The integrated maintenance timer can be used to implement preventative maintenance and avoid plant downtimes through look-ahead servicing.

Another new addition is the TRACE integrated into the Motor Starter ES software. It can be used to record measured values as a function of time following a trigger event. This enables pro-cess flows to be recorded and their timing optimized.

Local control of a drive is possible using the ordering option with integrated manual operation. This is yet another new develop-ment which distinguishes the M200D PROFIBUS/PROFINET motor starter from the rest of the market and adds innovative technology, maximum availability and transparency to the system.

M200D PROFINET motor starters with PROFIenergy

Increasing energy prices, far-reaching ecological problems worldwide and the threat of climate change make it necessary for you to be more conscious about your use of energy.

Active and effective energy management is possible with PROFIenergy.

PROFIenergy is a manufacturer-independent profile on PROFINET, which can be used by all manufacturers, has been standardized by PNO1) and supports switching off electrical devices during dead times and measuring the energy flow.1) In the PNO (PROFIBUS Nutzerorganisation e. V. – PROFIBUS User

Organization), manufacturers and users have come together to agree on the PROFIBUS and PROFINET standardized communication technologies.

IC10_09_05.fm Page 30 Sunday, July 19, 2020 10:22 PM

Page 51: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/51

Hybrid Motor Starters

SIRIUS M200D motor starters for PROFIBUS/PROFINETGeneral data

9/31Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

M200D Motor Starters for PROFIBUS/PROFINET

General data

9

Switching off during dead times

PROFIenergy supports the targeted switching-off of loads during dead time.

These can be planned short breaks of a few minutes (such as lunch breaks), longer dead times (such as nights) or unplanned dead times. Energy is always saved when no power is required.

Measuring and visualizing the energy flow as a basis ofenergy management

The objective of energy management is to optimize the use of energy in a company – from the purchasing of energy through to the consumption of energy – economically and ecologically.

Analyses of energy consumption over time can be used to control energy flows, avoid energy peaks, improve ratings and thus save costs.

PROFIenergy enables consumption data to be read off from the devices in a unified form. This is recorded during operation and can be displayed on a control panel, for example, or sent to overlying energy management software packages. This ensures that the measured variables are in a uniform manufacturer-inde-pendent form and structure that is available to the user for further processing. These PROFIenergy functions thus provide the basis for active load and energy management during operation.

PROFIenergy in the M200D PROFINET motor starter

The M200D PROFINET motor starter supports the "switching during dead times" and "current measurement values" functions of the motor current using PROFIenergy. These are called commands, because they trigger a reaction in the M200D motor starter.

Function available

-- Function not available

SIRIUS M200D SIRIUS M200DPROFIBUS PROFINET

Device functions (firmware features)Slave on the busFieldbus PROFIBUS to M12 PROFINET to M12

Adjustable number of stations 1 ... 125 1 ... 128 with CPU 315, CPU 3171 ... 1 256 with CPU 319

Parameter assignment DIP switches For address setting and terminating resistor --

Motor Starter ES Through bus, optical interface

PROFIBUS/PROFINET data records

From STEP 7/HW Config

DiagnosticsAcyclic through data records

Diagnostic interrupt support

Process imageProcess image 2 bytes PAE/2 bytes PAA

Data channelsLocal optical interface (manual local)

Motor Starter ES through local interface

Using Motor Starter ES through bus

Data records (acyclic)Parameter assignment Using DS 131 (DS = data record)

Diagnostics Device-specific DS 92

Measured values Measured values DS 94

Statistics Statistical data DS 95

Commands Using DS 93

Slave pointer Slave pointer DS 96

Logbook Using Motor Starter ES and data records: device faults DS 72, tripping operation DS 73, events DS 75

Device identification Using DS 100

I&M data Using DS 231 ... 234 Using data records 0xAFF0 ... 0xAFF3

InputsNumber 4

• Of these in the process image 4

Input action Parameterizable: For flexibly assignable action,

Quick stop Parameterizable: latching, non-latching

IC10_09_05.fm Page 31 Sunday, July 19, 2020 10:22 PM

see manual

Page 52: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/52

Hybrid Motor Starters

SIRIUS M200D motor starters for PROFIBUS/PROFINETGeneral data

9/32 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersM200D Motor Starters for PROFIBUS/PROFINET

General data

9

Function available

-- Function not available

Benefits

M200D PROFINET motor starters with PROFIenergyBoth standards and laws are making environmental protection and energy management increasingly important, as is the desire to cut energy costs in production facilities and thus ensure a sustainable competitive advantage.

It is thus an objective within the industry to save energy and actively reduce CO2 emissions. By the careful use of valuable resources, the manufacturer-independent PROFIenergy profile on PROFINET can make an active contribution to environmental protection.

ApplicationM200D PROFIBUS/PROFINET motor starters are particularly suitable for fully TIA-integrated, highly automated conveyor applications that meet all needs with regard to the monitoring of devices and systems and preventive maintenance.

Adaptability of the motor starter functions and maximum flexibility of the device enable a broad range of application without any limits. The PROFINET-specific expansions are the best assurance of a future-proof investment.

SIRIUS M200D SIRIUS M200DPROFIBUS PROFINET

Device functions (firmware features) (continued)OutputsNumber 2

• Of these in the process image 2

Output action Parameterizable: For flexibly assignable action,

Brake output180 V DC / 230/400 V AC / none

Motor protectionOverload protection Electronic, wide range 1:10

Short-circuit protection

Full motor protection

Temperature sensor Parameterizable via Motor Starter ES, data record: PTC or Thermoclick or deactivated

Device functionRepair switch

Current limit monitoring bottom Parameterizable

Current limit monitoring top Parameterizable

Zero current detection Parameterizable: tripping, warning

Blocking current Parameterizable

Asymmetry Parameterizable

Load type Parameterizable: single-phase and three-phase

Shutdown class Parameterizable via Motor Starter ES, data record: CLASS 5, 10, 15, 20

Protection against voltage failure Parameterizable: activated/deactivated

Support for PROFIenergy profile Switching during dead times -- 3

Measured motor current values -- 3

Soft starter control functionSoft start function

Bypass function Only solid-state version

IC10_09_05.fm Page 32 Sunday, July 19, 2020 10:22 PM

see manual

Page 53: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/53

Hybrid Motor Starters

SIRIUS M200D motor starters for PROFIBUS/PROFINETGeneral data

9/33Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

M200D Motor Starters for PROFIBUS/PROFINET

General data

9

Technical specifications

1) DS .... Direct-on-line startersRS .... Reversing startersDSS .. Direct-on-line soft startersRSS .. Reversing soft starterste ...... Full motor protection (thermal + electronic)s ....... Electronic switching with semiconductor.

2) Only systems with grounded neutral point permitted.

More information

Equipment Manual for M200D PROFIBUS/PROFINET, see https://support.industry.siemens.com/cs/ww/en/view/38823402

FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16325/faq

Notes on security:

In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens products and solutions represent only one component of such a concept.

For more information on the subject of Industrial Security, see www.siemens.com/industrialsecurity.

Type M200D PROFIBUS/PROFINET motor starter modulesElectromechanical switching Electronic switching

Technology designation1) DSte/RSte sDSSte/sRSSteMechanics and environmentMounting dimensions (W x H x D)

mmeludom noitacinummoc tuohtiW• 294 x 215 x 159mmeludom noitacinummoc htiW• 295 x 215 x 163

Permissible ambient temperatureC°noitarepo gniruD• -25 ... +55C°egarots gniruD• -40 ... +70

Weight g 2 820/3 080 3 160/3 360

Permissible mounting position Vertical, horizontal, lying

Vibration resistance acc. to IEC 60068 Part 2-6 g 2

Shock resistance • Acc. to IEC 60068 Part 2-27 g/ms 12/11 half-sine• Without influencing the contact position g/ms 9.8/5 or 5.9/10

Degree of protection acc. to IEC 529 IP65

Installation altitude• Up to 1 000 m No derating• Up to 2 000 m 1% per 100 m

Cooling Convection

Protection class IEC 536 (VDE 0106-1) 1

Electrical specificationsMain circuitMaximum power of three-phase motors at 400 V AC kW 5.5

Rated operational voltage UeCAV1-74906NE ot .cca lavorppA• 400 (50/60 Hz)CAVASC dna LU ot .cca lavorppA• 600 (50/60 Hz) 480 (50/60 Hz)

Aegnar tnerruc lanoitarepo detaR• 0.15 ... 2/1.5 ... 12 --• Rated operational current range for soft starting A -- 0.15 ... 2/1.5 ... 12• Rated operational current range for direct-on-line starting A -- 0.15 ... 2/1.5 ... 9

Rated operational current for starters Ie at 400 V ACA3/2/1-CA ta V004• 12 --A3/2/1-CA ta V005• 9 --A4-CA ta V004• 4 --Aa35-CA ta V004• -- 12 for soft starting,

9 for direct-on-line starting

Mechanical endurance of contactor Operating cycles 30 million --

Trip class CLASS 5, 10, 15, 20

Permissible switching frequencyRated ultimate short-circuit breaking capacity Iq

AkCAV004 tA• 50AkCAV005 tA• 50 202)

Short-circuit protection • At Iemax = 2 A Integrated, 2 x13 Ie = 26 A• At Iemax = 9 /12 A Integrated, 2 x13 Ie = 208 A

IC10_09_05.fm Page 33 Sunday, July 19, 2020 10:22 PM

Equipment Manual for M200D PROFIBUS/PROFINET, seehttps://support.industry.siemens.com/cs/ww/en/view/38823402

FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16325/faq

Notes on security:In order to protect plants, systems, machines and networks against cyberthreats, it is necessary to implement – and continuously maintain – a holistic,state-of-the-art industrial security concept. Siemens products and solutionsrepresent only one component of such a concept.For more information on the subject of Industrial Security, seewww.siemens.com/industrialsecurity.

see manual

Page 54: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/54

9/34 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersM200D Motor Starters for PROFIBUS/PROFINET

General data

9

1) Integrated brake actuation supplies DC power supply for the brake.

Line voltage

380 V AC 400 V AC 440 V AC 480 V AC 500 V AC

Brake voltage with brake actuation 180 V DC1)

Operational voltage V 230/400 AC or 180 DC

Uninterrupted current A < 0.5 at 230/400 V AC, < 0.8 at 180 V DC

Short-circuit protection Yes, 1 A melting fuse

Rectified brake voltage V DC 171 180 198 216 225

Recommended brake coil voltage for Siemens motors V DC 170 ... 200 170 ... 200 184 ... 218 184 ... 218 --

Type M200D communication modules

For PROFIBUS For PROFINET

Mechanics and environmentMounting dimensions (W x H x D) mm 174 x 139 x 40

Permissible ambient temperature• During operation °C -25 ... +55• During storage °C -40 ... +70

Weight g 300

Permissible mounting position Vertical, horizontal, lying

Vibration resistance acc. to IEC 60068 Part 2-6 g 2

Shock resistance • Acc. to IEC 60068 Part 2-27 g/ms 12/11 half-sine• Without influencing the contact position g/ms 9.8/5 or 5.9/10

Degree of protection acc. to IEC 529 IP65

Installation altitude• Up to 1 000 m No derating• Up to 2 000 m 1% per 100 m

Cooling Convection

Protection class IEC 536 (VDE 0106-1) 1

Electrical specificationsControl circuitOperational voltage• UDC24V-NS V DC 20.4 ... 28.8• UDC24V-S V DC 20.4 ... 28.8

Power consumption from• UDC24V-NS mA < 300• UDC24V-S mA < 100

IC10_09_05.fm Page 34 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D motor starters for PROFIBUS/PROFINETGeneral data

Page 55: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/55

9/35Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

M200D Motor Starters for PROFIBUS/PROFINET

Communication modules, motor starter modules

9

■ Selection and ordering data

✓ = Additional price

M200D motor starter module M200D motor starter M200D motor starterPROFIBUS/PROFINET PROFIBUS PROFINET(without communication module)

Version SD Article No. Priceper PU

PU(UNIT,

SET, M)

PS*

d

M200D communication modules for PROFIBUSCommunication module for PROFIBUSM12 connection for communication, 7/8" for 24 V power supply

15 3RK1305-0AS01-0AA0 1 1 unit

M200D communication modules for PROFINETCommunication module for PROFINETM12 connection for communication, 7/8" for 24 V power supply

15 3RK1335-0AS01-0AA0 1 1 unit

M200D PROFIBUS/PROFINET motor starter modules

Electromechanical starters (with integrated contactor)15 3RK1395-6@S41-@AD@ 1 1 unit

Rated operational current setting range/A Additional price

• 0.15 ... 2 None

• 1.5 ... 12 ✓

Direct-on-line starters/reversing starters

• Direct-on-line starters None

• Reversing starters ✓

• Direct-on-line starters with manual local operation ✓

• Reversing starters with manual local operation ✓

Brake actuation

• Without brake actuation None

• Brake actuation (230/400 V AC) ✓

• Brake actuation (180 V DC) ✓

Electronic starters (with thyristors)15 3RK1395-6@S71-@AD@ 1 1 unit

Rated operational current setting range/A Additional price

• 0.15 ... 2 None

• 1.5 ... 12 ✓

Direct-on-line starters/reversing starters

• Direct-on-line starters None

• Reversing starters ✓

• Direct-on-line starters with manual local operation ✓

• Reversing starters with manual local operation ✓

Brake actuation

• Without brake actuation None

• Brake actuation (230/400 V AC) ✓

• Brake actuation (180 V DC) ✓

K

L

0

1

2

3

0

3

5

K

L

0

1

2

3

0

3

5

IC10_09_05.fm Page 35 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D motor starters for PROFIBUS/PROFINETCommunication modules, motor starter modules

Page 56: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/56

9/36 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersSoftware

Motor Starter ES

9

■ Overview

Motor Starter ES for parameterization, monitoring, diagnostics and testing of motor starters

Motor Starter ES is used for the startup, parameterization, diagnostics, documentation and preventive maintenance of SIMATIC ET 200S, ET 200pro, ECOFAST and M200D motor starters.The software program is available in three versions which differ in their user-friendliness, scope of functions and price.

More information

Industry Mall, see www.siemens.com/product?3ZS1

Technical specifications and system requirements, seehttps://support.industry.siemens.com/cs/ww/en/ps/16713/td

IC10_09_05.fm Page 36 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

Motor Starter ESSoftware

Industry Mall, see www.siemens.com/product?3ZS1Technical specifications and system requirements, seehttps://support.industry.siemens.com/cs/ww/en/ps/16713/td

Page 57: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/57

9/37Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

Accessories

For all M200D motor starters

9

■ Overview

Power and motor connection on the M200D motor starter(in this example: M200D for AS-i)

Communication connection using AS-Interface and digital inputs and outputs

Communication connection using PROFIBUS and digital inputs and outputs

Communication connection using PROFINET and digital inputs and outputs

M

1

1

23

4

56

2

3 6

4

5

Power feeder plug

Power connection plug

Power connection cable

Motor connection plug

Motor plug

Motor cable

NS

A0_

0048

4

NS

A0_

0048

5a

7

9 10

8

7

8

9

10

Connection for motor control with AS-i communication

AS-Interface M12 feeder

Connection for digital input (IO communication, 5-pole)

Connection for digital output (IO communication, 4- or 5-pole)

NS

A0_

0048

8a

11

12

9

10

13

14

13

11 12

14

9 10

Connection for digital input (IO communication, 5-pole)

Connection for digital output(IO communication, 4- or 5-pole)

PROFIBUS connection (input)

PROFIBUS connection (loop)

Connection for 24 V supply (infeed)

Connection for 24 V supply (loop)

NS

A0_

0048

7a

9

10

13

14

15

13

15 15

14

9 10

Connection for digital input (IO communication, 5-pole)

Connection for digital output (IO communication, 4- or 5-pole)

Connection for 24 V supply (infeed)

Connection for 24 V supply (loop)

Connection with PROFINET(input on the left, loop on the right)

IC10_09_05.fm Page 37 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D Motor StartersAccessories for all M200D motor starters

Page 58: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/58

Hybrid Motor Starters

SIRIUS M200D Motor StartersAccessories for all M200D motor starters

9/38 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersAccessories

For all M200D motor starters

9

Power supply to the motors via the power bus with power T and double-T terminal connectors linked by power bus cables, spur lines to the field devices (motor starters), and power loop-through connections to the motors via motor connection cables

Power bus

The power supply to the field devices (ET 200pro motor starters, M200D motor starters) is provided via the power bus, in which the power T terminal connectors or power double-T terminal connectors are connected by power bus cables.

Feeders

From the terminal connectors, spur lines with Han Q4/2 plugs lead to the field devices, from which the motors are supplied with power via motor connection cables.

Interruption-free thanks to power terminal connectors

In finger-safe connection technology the power T terminal connectors and power double-T terminal connectors connect the components of a feeder to the power bus. They ensure interruption-free operation, i.e. the power bus is not interrupted when the components are unplugged.

1716

18 18

Power bus cable (sold by the meter)

Power T terminal connector

Power double-T terminal connector

Motors

IC01

_002

31a

ET 200pro

M200DM200D

16

17

18

IC10_09_05.fm Page 38 Sunday, July 19, 2020 10:22 PM

Page 59: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/59

9/39Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

Accessories

For all M200D motor starters

9

Selection and ordering dataThe accessories listed below represent a basic selection sorted by: • Accessories for all M200D motor starters• Accessories for M200D motor starters for AS-Interface• Accessories for M200D motor starters for PROFIBUS• Accessories for M200D motor starters for PROFINET

DSnoisreV Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

Mountable accessoriesM200D protective brackets 5 3RK1911-3BA00 1 1 unit

Incoming power supplyPower feeder plugs

Connector set for incoming power supply, e.g. for connecting to T terminal connectors, comprising a coupling enclosure, straight outgoing feeder (with bracket), pin insert for HAN Q4/2, incl. gland• 5 male contacts, 2.5 mm2

• 5 male contacts, 4 mm2

• 5 male contacts, 6 mm2

5 3RK1911-2BS60 1 1 unit5 3RK1911-2BS20 1 1 unit5 3RK1911-2BS40 1 1 unit

Power connection plugsConnector set for incoming power supply for connection to M200D motor starters, comprising a cable-end connector hood, angular outgoing feeder, female insert for HAN Q4/2, incl. gland• 5 female contacts, 2.5 mm2,

2 female contacts, 0.5 mm25 3RK1911-2BE50 1 1 unit

• 5 female contacts, 4 mm2,2 female contacts, 0.5 mm2

5 3RK1911-2BE10 1 1 unit

• 5 female contacts, 6 mm2,2 female contacts, 0.5 mm2

5 3RK1911-2BE30 1 1 unit

+ Power connection cablesAssembled at one end with "N" and jumper pin 11 and 12 for plug monitoring, with HAN Q4/2, angular; open at one end; 5 x 4 mm2

01m5.1 htgneL • 3RK1911-0DC13 1 1 unit

01m 0.5 htgneL • 3RK1911-0DC33 1 1 unit

Motor cablesMotor connection plugs

Connector set for motor cable for connection to M200D motor starters, comprising a cable-end connector hood, angular outgoing feeder, pin insert for HAN Q8/0, incl. gland• 8 male contacts, 1.5 mm2 5 3RK1902-0CE00 1 1 unit• 6 male contacts, 2.5 mm2 5 3RK1902-0CC00 1 1 unit

Motor plugsConnector set for motor cable for connection to motors, comprising a cable-end connector hood, straight outgoing feeder, female insert for HAN 10e, incl. star jumper, incl. gland• 7 female contacts, 1.5 mm2 30 3RK1911-2BM21 1 1 set• 7 female contacts, 2.5 mm2 30 3RK1911-2BM22 1 1 set

+ Motor cables, assembled at one endFor connection to M200D motor starters, HAN Q8/0, angular, length 5 m• Motor cables for motor without brake, 4 x 1.5 mm2 15 3RK1911-0EB31 1 1 unit

• Motor cables for motor without brake with thermistor, 6 x 1.5 mm2

30 3RK1911-0EF31 1 1 unit

• Motor cables for motor with brake actuation, braking voltage 400 V AC or 180 V DC, 6 x 1.5 mm2

30 3RK1911-0ED31 1 1 unit

• Motor cables for motor with brake actuation, braking voltage 400 V AC or 180 V DC and thermistor, 8 x 1.5 mm2

30 3RK1911-0EG31 1 1 unit

• Motor cables for motor with brake actuation, braking voltage 230 V AC, 6 x 1.5 mm2

30 3RK1911-0EH31 1 1 unit

• Motor cables for motor with brake actuation, braking voltage 230 V AC and thermistor, 8 x 1.5 mm2

30 3RK1911-0EE31 1 1 unit

IC10_09_05.fm Page 39 Sunday, July 19, 2020 10:22 PM

� �

Hybrid Motor Starters

SIRIUS M200D Motor StartersAccessories for all M200D motor starters

Page 60: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/60

Hybrid Motor Starters

SIRIUS M200D Motor StartersAccessories for all M200D motor starters

9/40 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersAccessories

For all M200D motor starters

9

Power bus Power T terminal connectors

For 400 V AC, for connection of feeders (e.g. motor starters) by means of standard round cable at any point of the power bus, by insulation displacement connection,used with preassembled bus segments

5²mm4/²mm5.2• 3RK1911-2BF01 1 1 unit5²mm6/²mm4• 3RK1911-2BF02 1 1 unit

Power double-T terminal connectors For 400 V AC, for connection of feeders (e.g. motor starters) by means of standard round cable at any point of the power bus, by insulation displacement connection,used with preassembled bus segments, connection of two motor starters possible

5²mm6/²mm4• 3RK1911-2BG02 1 1 unit

Sealing set (comprising 2 seals) For power T/power double-T terminal connectors

• For power cables with5mm31...01 Ø- 3RK1911-5BA00 1 1 unit5mm61...31 Ø- 3RK1911-5BA10 1 1 unit5mm91...61 Ø- 3RK1911-5BA20 1 1 unitXmm22...91 Ø- 3RK1911-5BA30 1 1 unit

5sgulp gniknalB• 3RK1911-5BA50 1 1 unit

Further accessories for power connections

3RK1902-0CW00

Crimping tools for pins/sockets 4 mm2 and 6 mm2 15 3RK1902-0CW00 1 1 unit

Dismantling tools• For male and female contacts for 9-pole

HAN Q4/2 inserts15 3RK1902-0AB00 1 1 unit

• For male and female contacts for 9-pole HAN Q8 inserts

5 3RK1902-0AJ00 1 1 unit

3RK1902-0CK00

Sealing capsFor 9-pole power sockets

5kcap rep tinu 1• 3RK1902-0CK00 1 1 unit5kcap rep stinu 01• 3RK1902-0CJ00 1 10 units

DSnoisreV Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

IC10_09_05.fm Page 40 Sunday, July 19, 2020 10:22 PM

Page 61: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/61

9/41Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

Accessories

For all M200D motor starters

9For more connection technology products, see https://support.industry.siemens.com/cs/ww/en/view/65355810.

Motor control with I/O communication

3RK1902-4BA00-5AA0

M12 plugs, straightScrew fixing, 5-pole screw terminals, max. 0.75 mm2,A-coded, max. 4 A

5 3RK1902-4BA00-5AA0 1 1 unit

3RK1902-4DA00-5AA0

M12 plugs, angular Screw fixing, 5-pole screw terminals, max. 0.75 mm2,A-coded, max. 4 A

5 3RK1902-4DA00-5AA0 1 1 unit

3RK1902-4H...-5AA0

, Control cables, assembled at one endM12 plugs, angular, screw fixing, 5-pole, 5 x 0.34 mm2,A-coded, black PUR sheath, max. 4 A

5m5.1 htgnel elbaC• 3RK1902-4HB15-5AA0 1 1 unit5m5 htgnel elbaC• 3RK1902-4HB50-5AA0 1 1 unit5m01 htgnel elbaC• 3RK1902-4HC01-5AA0 1 1 unit

3RK1902-4PB15-3AA0

Control cables, assembled at both endsStraight M12 plug, straight M12 socket, screw fixing, 3-pole, 3 x 0.34 mm2, A-coded, black PUR sheath, max. 4 A

5m 5.1 htgnel elbaC• 3RK1902-4PB15-3AA0 1 1 unit

Further accessories

3RK1922-3BA00

Handheld devices For M200D motor starters (or for ET 200pro and ET 200S High Feature motor starters) for local operation. The motor starter-specific serial interface cables must be ordered separately.The RS 232 interface cable 3RK1922-2BP00 is used for the MS M200D.

5 3RK1922-3BA00 1 1 unit

RS 232 interface cableSerial data connection between M200D (or ET 200pro) motor starters and the RS 232 interface of a PC/PG/laptop (with the Motor Starter ES software) or the handheld device 3RK1922-3BA00

5 3RK1922-2BP00 1 1 unit

USB interface cable, 2.5 mSerial data connection between M200D (or ET 200pro) motor starters and the USB interface of a PC/PG/laptop (with the Motor Starter ES software).

3 6SL3555-0PA00-2AA0 1 1 unit

3RK1901-1KA00

M12 sealing capsFor sealing unused M12 input or output sockets and M12 sockets for PROFIBUS and PROFINET communication modules (one set contains ten sealing caps)

} 3RK1901-1KA00 100 10 units

3SU1950-0FB80-0AA0

RONIS SB30 keysReplacement key for M200D for "manual local control" ordering option

} 3SU1950-0FB80-0AA0 1 1 unit

DSnoisreV Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

IC10_09_05.fm Page 41 Sunday, July 19, 2020 10:22 PM

� �

Hybrid Motor Starters

SIRIUS M200D Motor StartersAccessories for all M200D motor starters

For more connection technology products, see https://support.industry.siemens.com/cs/ww/en/view/65355810..

Page 62: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/62

9/42 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersAccessories

For M200D motor starters for AS-Interface

9

Selection and ordering data

DSnoisreV Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

Motor control with AS-i communication

3RK1902-4GB50-4AA0

Control cables, assembled at one endM12 plug, angular, screw fixing, 4-pole, 4 x 0.34 mm2,A-coded, black PUR sheath, max. 4 A

5m 5 htgnel elbaC• 3RK1902-4GB50-4AA0 1 1 unit

3RK1902-4CA00-4AA0

M12 sockets, angledFor screw fixing, 4-pole screw terminals, max. 0.75 mm2,A-coded, max. 4 A

5 3RK1902-4CA00-4AA0 1 1 unit

3RK1901-2NR21

AS-Interface M12 feedersFor flat cable For Cable length Cable end in

feeder

AS-i/Uaux M12 socket -- not available 2 3RK1901-2NR20 1 1 unit

M12 cable box

1 m not available 2 3RK1901-2NR21 1 1 unit

2 m not available 2 3RK1901-2NR22 1 1 unit

3RK1901-1MN00

Cable terminating piecesFor sealing of open cable ends (shaped AS-Interface cable) in IP67

} 3RK1901-1MN00 1 10 units

3RX90..-0AA00

AS-Interface shaped cable, see also page 2/82

Material Color Quantity

Rubber Yellow (AS-Interface)

100 m roll 2 3RX9010-0AA00 1 1 unit

1 km drum 5 3RX9012-0AA00 1 1 unit

Black (24 V DC)

100 m roll 2 3RX9020-0AA00 1 1 unit

1 km drum 5 3RX9022-0AA00 1 1 unit

TPE Yellow (AS-Interface)

100 m roll 2 3RX9013-0AA00 1 1 unit

1 km drum 5 3RX9014-0AA00 1 1 unit

Black (24 V DC)

100 m roll 2 3RX9023-0AA00 1 1 unit

1 km drum 5 3RX9024-0AA00 1 1 unit

TPE special version according to UL Class 2

Yellow (AS-Interface)

100 m roll 5 3RX9017-0AA00 1 1 unit

Black (24 V DC)

100 m roll 5 3RX9027-0AA00 1 1 unit

PUR Yellow (AS-Interface)

100 m roll 2 3RX9015-0AA00 1 1 unit

1 km drum 5 3RX9016-0AA00 1 1 unit

Black (24 V DC)

100 m roll 2 3RX9025-0AA00 1 1 unit

1 km drum 5 3RX9026-0AA00 1 1 unit

IC10_09_05.fm Page 42 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D Motor StartersAccessories for M200D motor starters for AS-Interface

Page 63: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/63

9/43Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

Accessories

For M200D motor starters for AS-Interface

9

Version SD Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

Further accessories

3RK1904-2AB02

AS-Interface addressing unit V3.0• For AS-Interface modules and sensors and actuators

with integrated AS-Interface according to AS-i Specification V3.0

• For setting the AS-i address of standard slaves, and slaves with extended addressing mode (A/B slaves)

• With input/output test function and many other commissioning functions

• Battery operation with four type AA batteries (IEC LR6, NEDA 15)

• Scope of supply:- Addressing unit with four batteries- Addressing cable, with M12 plug to addressing plug

(hollow plug), length 1.5 m

2 3RK1904-2AB02 1 1 unit

3RK1902-4PB15-3AA0

M12 addressing cables to M12

• Standard M12 cable for addressing slaves with M12 connection, e.g. K60R modules

• When using the current version of the 3RK1904-2AB01 addressing unit

• 1.5 m

5 3RK1902-4PB15-3AA0 1 1 unit

"SIRIUS M200D Motor Starter" manualsEquipment Manual - SIRIUS M200D AS-Interface Basic Motor Starter, see https://support.industry.siemens.com/cs/ww/en/view/35016496

Equipment Manual - SIRIUS M200D AS-Interface Standard Motor Starter, see https://support.industry.siemens.com/cs/ww/en/view/38722160

IC10_09_05.fm Page 43 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D Motor StartersAccessories for M200D motor starters for AS-Interface

Equipment Manual -SIRIUS M200D AS-Interface Basic Motor Starter, see https://support.industry.siemens.com/cs/ww/en/view/35016496

Equipment Manual -SIRIUS M200D AS-Interface Basic Motor Starter, see https://support.industry.siemens.com/cs/ww/en/view/38722160

Page 64: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/64

9/44 Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.

Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor StartersAccessories

For M200D motor starters for PROFIBUS

9

Selection and ordering data

DSnoisreV Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

Motor control with PROFIBUS

3RK1902-1DA00

M12 plugs, angularFor screw fixing, 5-pole screw terminal, max. 0.75 mm2, B-coded, no terminating resistor

5stcatnoc elamef 5 • 3RK1902-1DA00 1 1 unit

3RK1902-1BA00

5stcatnoc elam 5 • 3RK1902-1BA00 1 1 unit

3RK1902-1G.

Control cables, assembled at one endM12, screw fixing, angular, B-coded, no terminating resistor

51m3 ,stcatnoc elamef 5 �

� �

• 3RK1902-1GB30 1 1 unit

51m5 ,stcatnoc elamef 5 • 3RK1902-1GB50 1 1 unit

51m01 ,stcatnoc elamef 5 • 3RK1902-1GC10 1 1 unit

3RK1902-1N.

Control cables, assembled at both endsM12, screw fixing, angular, pin/socket 5-pole, B-coded, no terminating resistor

51m0.3• 3RK1902-1NB30 1 1 unit51m0.5• 3RK1902-1NB50 1 1 unit51m 0.01• 3RK1902-1NC10 1 1 unit

Further accessoriesPROFIBUS trailing cables 1 6XV1830-3EH10 1 1 MMax. acceleration 4 m/s2, at least 3 000 000 bending cycles, bending radius at least 60 mm, 2-core, shielded, sold by the meter, minimum order quantity 20 m, maximum order quantity 1 000 m

PROFIBUS FC Food bus cables 1 6XV1830-0GH10 1 1 Mwith PE outer sheath for operation in the food and beverage industry, 2-core, shielded, sold by the meter, minimum order quantity 20 m, maximum order quantity 1 000 m

PROFIBUS FC Robust bus cables 1 6XV1830-0JH10 1 1 Mwith PUR outer sheath for operation in environments exposed to chemicals and mechanical loads, 2-core, shielded, sold by the meter, minimum order quantity 20 m, maximum order quantity 1 000 m

Power cables 1 6XV1830-8AH10 1 1 M5-core, 5 x 1.5 mm2, trailing, sold by the meter, minimum order quantity 20 m, maximum order quantity 1 000 m

Connection for 24 V power supply of the M200D PROFIBUS/PROFINETSee page 9/45

Equipment Manual "SIRIUS M200D PROFIBUS/PROFINET Motor Starters"See https://support.industry.siemens.com/cs/ww/en/view/38823402

IC10_09_05.fm Page 44 Sunday, July 19, 2020 10:22 PM

Hybrid Motor Starters

SIRIUS M200D Motor StartersAccessories for M200D motor starters for PROFIBUS

See https://support.industry.siemens.com/cs/ww/en/view/38823402

See page 6/65

Page 65: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/65

9/45Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of ProtectionSIRIUS M200D Motor Starters

Accessories

For M200D motor starters for PROFINET

9

Selection and ordering data

DSnoisreV Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

Motor control with PROFINET M12 plugs, angular

For screw fixing, 4-pole screw terminal, max. 0.75 mm2, angular, D-coded

5stcatnoc elam 4• 3RK1902-2DA00 1 1 unit

3RK1902-2H.

Control cables, assembled at one endM12 for screw fixing, angular, 4-pole, D-coded,

51m3 ,stcatnoc elam 4• 3RK1902-2HB30 1 1 unit51m5 ,stcatnoc elam 4• 3RK1902-2HB50 1 1 unit51m01 ,stcatnoc elam 4• 3RK1902-2HC10 1 1 unit

3RK1902-2N.

Control cables, assembled at both endsM12 for screw fixing, angular at both ends, 4-pole, D-coded, male contacts at both ends

51m3• 3RK1902-2NB30 1 1 unit51m5• 3RK1902-2NB50 1 1 unit51m01• 3RK1902-2NC10 1 1 unit

Further accessoriesPROFINET IE FC TP standard cable GP 2 x 2Sold by the meter

1 6XV1840-2AH10 1 1 M

PROFINET IE FC TP trailing cable 2 x 2Sold by the meter

1 6XV1840-3AH10 1 1 M

PROFINET IE FC TP trailing cable GP 2 x 2Sold by the meter

1 6XV1870-2D 1 1 M

PROFINET IE FC TP torsion cable 2 x 2Sold by the meter

1 6XV1870-2F 1 1 M

PROFINET IE FC TP marine cable, 4-coreSold by the meter

1 6XV1840-4AH10 1 1 M

Power cables 1 6XV1830-8AH10 1 1 M5-core, 5 x 1.5 mm2, trailing, sold by the meter, minimum order quantity 20 m, maximum order quantity 1 000 m

Connection for 24 V power supply of the M200D PROFIBUS/PROFINET

3RK1902-3DA00

PlugsOn M200D, 7/8" for screw fixing, angular, screw terminal, 1.5 mm2

5stcatnoc elamef 5 • 3RK1902-3DA00 1 1 unit

3RK1902-3BA00

5stcatnoc elam 5 • 3RK1902-3BA00 1 1 unit

3RK1902-3G.

Supply lines, assembled at one end7/8" for screw fixing, angular, 1.5 mm2

51m 3 ,stcatnoc elamef 5• 3RK1902-3GB30 1 1 unit51m 5 ,stcatnoc elamef 5• 3RK1902-3GB50 1 1 unit51m 01 ,stcatnoc elamef 5• 3RK1902-3GC10 1 1 unit

3RK1902-3N.

Supply lines, assembled at both ends7/8", for screw fixing, angular at both ends, 5-pole pin/socket, 1.5 mm2

51m 3• 3RK1902-3NB30 1 1 unit51m 5• 3RK1902-3NB50 1 1 unit51m01• 3RK1902-3NC10 1 1 unit

6ES7194-3JA00-0AA0

7/8" sealing caps1 pack = 10 units

1 6ES7194-3JA00-0AA0 1 10 units

Equipment Manual "SIRIUS M200D PROFIBUS/PROFINET Motor Starters"See https://support.industry.siemens.com/cs/ww/en/view/38823402

IC10_09_05.fm Page 45 Sunday, July 19, 2020 10:22 PM

� �

Hybrid Motor Starters

SIRIUS M200D Motor StartersAccessories for M200D motor starters for PROFINET

See https://support.industry.siemens.com/cs/ww/en/view/38823402

Page 66: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/66

9/46 Siemens IC 10 · 2020

Motor Starters for Use in the Field, High Degree of Protection

Hybrid fieldbus connections

9

Overview

Hybrid fieldbus connection with two HanBrid sockets

Control cabinet bushing with two M12 sockets

Hybrid fieldbus connections with HanBrid sockets designed as cabinet bushings transmit data and energy from the control cabinet (IP20) to the field (IP65). They are the interface for jointly routing PROFIBUS DP and the auxiliary voltages into the hybrid fieldbus cable.

On the cabinet bushings with two M12 sockets for the PROFIBUS M12 connecting cables, the 24 V supply of the motor starters is implemented via separate 7/8" connecting cables.

Passive and active hybrid fieldbus connectionsThe hybrid fieldbus connections are available in two versions which differ in their functionality:• Passive version • Active version with signal refresher function to considerably

increase the maximum PROFIBUS cable length

Connection methods

The field side is connected using HanBrid or M12 plug-in connections.

In the case of HanBrid, the following versions are available:• Socket/socket for feeding into the field• Pin/socket for looping through in the field

The M12 version is generally configured with socket/socket.

Following connections are available at the rear (cabinet side) in the case of the passive bushings:• Direct connection• FastConnect connection

The active bushing with refresher function has 9-pole Sub D sockets for the rear connection.

Auxiliary power infeed

HanBrid plug-in connection technology offers the option of feeding in or looping through two separate auxiliary voltages of 24 V DC (switched/unswitched) into the field in addition to the PROFIBUS signal. The terminal block with spring-loaded terminals on the rear (cabinet side) of the hybrid fieldbus connection provides a variety of interconnecting options for these auxiliary voltages.

Passive hybrid fieldbus connections• Bushing from the control cabinet (IP20) into the field (IP65)• HanBrid plug-in design socket/socket or pin/socket• Direct connection or FastConnect connection for PROFIBUS at

the rear• Terminal block with spring-loaded terminals (0.25 to 2.5 mm2)

for infeeding or forwarding the auxiliary voltages

Hybrid fieldbus connection as passive cabinet bushing

Active hybrid fieldbus connections with refresher function• Bushing from the control cabinet (IP20) into the field (IP65)• Three independent, electrically separated PROFIBUS

segments• Signal refresher function from and to all segments• Automatic continuous baud rate detection• Status/diagnostics displays with LEDs• Cascading depth of a maximum nine hybrid fieldbus

connections• HanBrid plug-in design socket/socket and pin/socket• M12 plug-in design socket/socket• 9-pole Sub D socket connection for PROFIBUS at the rear• Terminal block with spring-loaded terminals (0.25 to 2.5 mm2)

for infeeding or forwarding the auxiliary voltages

Hybrid fieldbus connection as active control cabinet bushing with refresher function

Pin or socket Socket

IP20

IP65

Pin or socket Socket

Refresher

IP20

IP65

IC10_09_06.fm Page 46 Sunday, July 19, 2020 10:28 PM

Hybrid Motor Starters

Hybrid fieldbus connectionsGeneral data

Page 67: Hybrid Motor Starters 6

6H

YBRID

MO

TOR

STARTERS

Smart Infrastructure, Industrial Control Catalog 2021 6/67

9/47Siemens IC 10 · 2020* You can order this quantity or a multiple thereof.Illustrations are approximate

Motor Starters for Use in the Field, High Degree of Protection

Hybrid fieldbus connections

9

Technical specifications

Selection and ordering data

PROFIBUS ECOFAST hybrid cables, see Catalog ST 70 or Industry Mall.

Type Passive hybrid fieldbus connections Active hybrid fieldbus connectionsMechanics and environmentDimensions (W x H x D) mm 93 x 103 x 65

Cutout (W x H) mm 80 x 90

Temperature range °C -25 ... +60

Degree of protection IP20 internal/IP65 on field side

Material/enclosure mm Plastic (black PC), flame retardant

Electrical specificationsRated operational voltage

CDV)SN( dehctiws ton CDV42• 24, ± 25%CDV)S( dehctiws CDV42• 24, ± 25%

Max. rated current A 10

Power supply -- From 24 V DC not switched (NS)

Max. power consumption mA -- 130

Mains buffering ms -- > 20

Baud rate detection -- Automatic

Maximum cascading depth -- 9 hybrid fieldbus connections

Baud rates kbps 9.6/19.2/45.45/93.75/187.5/500/1 500/3 000/6 000 /12 000

Electrical separation V DC 500

Hybrid fieldbus connection on the field side:With socket/socket (HanBrid)

With pin/socket (HanBrid)

Control cabinet bushing on the field sideWith socket/socket (M12)

Link type / function Connection IP65 Connection IP20 (PROFIBUS)

SD Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

Hybrid fieldbus connectionsPassive• Cu/Cu, for feeding into the field Socket/socket

(2 x HanBrid)Direct connection 5 3RK1911-1AA22 1 1 unit

• Cu/Cu, for looping through in the field

Pin/socket(2 x HanBrid)

Direct connection 5 3RK1911-1AA32 1 1 unit

• Cu/Cu, for feeding into the field Socket/socket(2 x HanBrid)

PROFIBUS FastConnect bus connector

5 3RK1911-1AF22 1 1 unit

• Cu/Cu, for looping through in the field

Pin/socket(2 x HanBrid)

PROFIBUS FastConnect bus connector

5 3RK1911-1AF32 1 1 unit

Active (refresher)• Cu/Cu, for feeding into the field Socket/socket

(2 x HanBrid)9-pole Sub D socket 5 3RK1911-1AJ22 1 1 unit

• Cu/Cu, for looping through in the field

Pin/socket(2 x HanBrid)

9-pole Sub D socket 5 3RK1911-1AJ32 1 1 unit

• Cu/Cu, for feeding into the field Socket/socket(2 x M12)

9-pole Sub D socket 5 3RK1911-1AK22 1 1 unit

DSnoisreV Article No. Priceper PU

PU (UNIT,SET, M)

PS*

d

Accessories

6ES7194-1JB10-0XA0

Sealing caps for HanBridProtective cover for bus and power supply connection (pack of 10)

1 6ES7194-1JB10-0XA0 1 10 units

IC10_09_06.fm Page 47 Sunday, July 19, 2020 10:28 PM

Hybrid Motor Starters

Hybrid fieldbus connectionsSelection and ordering

PROFIBUS ECOFAST hybrid cables, see Catalog ST 70 or Industry Mall.

Page 68: Hybrid Motor Starters 6

6H

YBRI

D M

OTO

R ST

ART

ERS

Smart Infrastructure, Industrial Control Catalog 20216/68

Hybrid Motor Starters

Notes


Top Related