Instrumentation & Control

IMRAN KHAN

Registration No: - 10D2-113031

Program: - B-Tech (Pass) Electronics

Page 2: Instrumentation  Control Process

What is instrument ?

Instrument is a devices which is used to measure,

monitor, display etc. of a process variable.

• What are the process Variable ?

The process Variable are :

1. Flow

2. Pressure

3. Temperature

4. Level

Page 3: Instrumentation  Control Process

A process of ( liquid, gas, or electricity) move steadily and

continuously in a current or stream.

What is Flow ?

go from one place to another in a steady stream, typically in

large numbers. .

Flow can be measured in a variety of ways. Positive-

displacement flow meters accumulate a fixed volume of fluid

and then count the number of times the volume is filled to

measure flow.

Page 4: Instrumentation  Control Process

What is pressure ?

Pressure is force per unit area applied in a direction perpendicular to the surface of an object .

Pressure is the ratio of force applied per area covered …

P = F/A he unit of pressure is the Pascal

Pa = N = kg m/s2 =kg The Pascal is also a unit of stress and the topics of pressure and

stress are connected.

Bed of nails (not really pressure but shear strain?)

Finger bones are flat on the gripping side to increase surface area in

contact and thus reduce compress ional stresses .

Page 5: Instrumentation  Control Process

What is Temperature ?

In a qualitative manner, we can describe the temperature of an object as that which determines the sensation of warmth or coldness felt from contact with it.

Temperature is a degree of hotness or coldness the can be measured using a thermometer. It's also a measure of how fast the atoms and molecules of a substance are moving. Temperature is measured in degrees on the Fahrenheit, Celsius, and Kelvin scales.

A temperature is a numerical measure of hot or cold. Its measurement is by detection of heat radiation or particle velocity or kinetic energy, or by the bulk behavior of a thermometric material. It may be calibrated in any of various temperature , Celsius, Fahrenheit, Kelvin, etc. The fundamental physical definition of temperature is provided by thermodynamic .

Page 6: Instrumentation  Control Process

What is Level ?

A device for establishing a horizontal line or plane by means of a

bubble in a liquid that shows adjustment to the horizontal by

movement to the center of a slightly bowed glass tube

A measurement of the difference of altitude of two points by

means of a level .

Horizontal condition; especially : equilibrium of a fluid

marked by a horizontal surface of even altitude <water seeks its

own level>

The magnitude of a quantity considered in relation to an

arbitrary reference value; broadly : magnitude, intensity <a

high level of hostility>

Page 7: Instrumentation  Control Process

What is meaning of Loop in instrumentation ?

In computer programming, a loop is a sequence of instructions that is continually repeated until a certain condition is reached. Typically, a certain process is done, such as getting an item of data and changing it, and then some condition is checked such as whether a counter has reached a prescribed number. If it hasn't, the next instruction in the sequence is an instruction to return to the first instruction in the sequence and repeat the sequence. If the condition has been reached, the next instruction "falls through" to the next sequential instruction or branches outside the loop. A loop is a fundamental programming idea that is commonly used in writing programs. An infinite loop is one that lacks a functioning exit routine . The result is that the loop repeats continually until the operating system senses it and terminates the program with an error or until some other event occurs (such as having the program automatically terminate after a certain duration of time).

Page 8: Instrumentation  Control Process

Define the types of loop control ?

Open loop control system .

Close loop control system .

Cascade loop control system .

Page 9: Instrumentation  Control Process

What is open loop system ?

An open-loop controller, also called a non-feedback controller, is a type

of controller that computes its input into a system using only the current

state and its model of the system.

A characteristic of the open-loop controller is that it does not use feedback

to determine if its output has achieved the desired goal of the input. This

means that the system does not observe the output of the processes that it is

controlling. Consequently, a true open-loop system can not engage in

machine learning and also cannot correct any errors that it could make. It

also may not compensate for disturbances in the system.

An open-loop controller is often used in simple processes because of its

simplicity and low cost, especially in systems where feedback is not critical.

A typical example would be a conventional washing machine .

Page 10: Instrumentation  Control Process

Open loop control system Diagram

Open loop

Page 11: Instrumentation  Control Process

What is close loop system ?

Closed loop control systems are those that provide feedback of the actual state of the

system and compare it to the desired state of the system in order to adjust the system.

The closed loop control system is a system where the actual behavior of the system is

sensed and then fed back to the controller and mixed with the reference or desired

state of the system to adjust the system to its desired state. The objective of the

control system is to calculate solutions for the proper corrective action to the system

so that it can hold the set point (reference) and not oscillate around it.

When a scale out triggering event occurs, the input parameter that triggers the event

is monitored around its set point. The system increases and decreases capacity on

demand to stay as close as possible to the set point for the triggering parameter.

With closed loop systems, you can evaluate the system near the set point using a PID

control algorithm or similar control scheme. A simpler approach, such as hysteretic,

can be very effective and can be implemented with less complexity and tuning.

Page 12: Instrumentation  Control Process

Close loop system diagram .

Close loop Block diagram

Page 13: Instrumentation  Control Process

What is Cascade loop control system ?

A cascade control system is a multiple-loop system where the primary variable is

controlled by adjusting the set point of a related secondary variable controller. The

secondary variable then affects the primary variable through the process.

The primary objective in cascade control is to divide an otherwise difficult to control

process into two portions, whereby a secondary control loop is formed around a

major disturbances thus leaving only minor disturbances to be controlled by the

primary controller.

The use of cascade control is described in many texts on process control

applications.

Cascade control is most advantageous on applications where the secondary closed

loop can include the major disturbance and second order lag and the major lag is

included in only the primary loop. The secondary loop should be established in an

area where the major disturbance occurs.

Page 14: Instrumentation  Control Process

Cascade loop control system Diagram.

Cascade loop

Page 15: Instrumentation  Control Process

Pressure measurements .

Pressure is the force exerted per unit area

Pressure is the action of one force against another force. Pressure is force applied to, or

distributed over, a surface. The pressure P of a force F distributed over an area A is

defined as P = F/A

TOTAL VACUUM - 0 PSIA

PRESSURE

ABSOLUTE

GAUGE

COMPOUND

BAROMETRIC RANGE

ATMOSPHERIC PRESSURE

NOM. 14.7 PSIA

Page 16: Instrumentation  Control Process

Pressure Measurement Terms.

Absolute Pressure

Measured above total vacuum or zero absolute. Zero absolute represents total lack of pressure.

Atmospheric Pressure

The pressure exerted by the earth’s atmosphere. Atmospheric pressure at sea level is 14.696 PSI. The value of atmospheric pressure decreases with increasing altitude.

Barometric Pressure

Same as atmospheric pressure.

Gauge Pressure

The pressure above atmospheric pressure. Represents positive difference between measured pressure and existing atmospheric pressure. Can be converted to absolute by adding actual atmospheric pressure value.

Differential Pressure

The difference in magnitude between some pressure value and some reference pressure. In a sense, absolute pressure could be considered as a differential pressure with total vacuum or zero absolute as the reference. Likewise, gauge pressure (defined above) could be considered as Differential Pressure with atmospheric pressure as the reference.

Page 17: Instrumentation  Control Process

Pressure Units.

psi 100

bar 6.895

mbar 6895

mm of Hg 5171

mm of WC 70358

in of WC 2770

Kg/cm2 7.032

Pascal 689476

kPa 689.5

atm 6.805

Page 18: Instrumentation  Control Process

Types of Pressure Instruments

Pressure Gauges (Vacuum, Compound, Absolute, Gauge)

Differential Pressure Gauge

Pressure Switch (Vacuum, Absolute, Gauge)

Differential Pressure Switch

Pressure Transmitter (Vacuum, Absolute, Gauge)

Differential Pressure Transmitter

PRESSURE GAUGE

PRESSURE SWITCH DIFFERENTIALPRESSURE

TRANSMITTER

Page 19: Instrumentation  Control Process

PRESSURE GAUGES

A Pressure Gauge is used for measuring the pressure of a gas or liquid.

A Vacuum Gauge is used to measure the pressure in a vacuum.

A Compound Gauge is used for measuring both Vacuum and Pressure.

Pressure Gauges are used for Indication only.

Measuring Principle

Bourdon tube measuring element is made of a thin-walled C-shape tube or

spirally wound helical or coiled tube. When pressure is applied to the

measuring system through the pressure port (socket), the pressure causes the

Bourdon tube to straighten itself, thus causing the tip to move. The motion of

the tip is transmitted via the link to the movement which converts the linear

motion of the bourdon tube to a rotational motion that in turn causes the

pointer to indicate the measured pressure.

Page 20: Instrumentation  Control Process

Gauge Construction types .

“C” Type Bourdon

Helical Bourdon

Coiled Bourdon

Page 21: Instrumentation  Control Process

Pressure Switch

The device contains a micro switch, connected to a mechanical lever and set pressure spring. The contacts get actuated when process pressure reaches the set pressure of the spring.

It can be used for alarming or interlocking purposes, on actuation.

It can be used for high / high-high or low / low-low actuation of pressure in the process . The set range can be adjusted within the switch range.

The sensing element may be a Diaphragm or a piston

Page 22: Instrumentation  Control Process

Working principle

Pressure/Vacuum Switch - A device that senses a change in pressure/vacuum and opens or closes an electrical circuit when the set point is reached.

Pressure switches serve to energize or de-energize electrical circuits as a function of whether the process pressure is normal or abnormal.

The electric contacts can be configured as single pole double throw (SPDT), in which case the switch is provided with one normally closed (NC) and one normally open (NO) contact.

Alternately, the switch can be configured as double pole double throw (DPDT), in which case two SPDT switches are furnished, each of which can operate a separate electric circuit.

Page 23: Instrumentation  Control Process

Pressure Transmitter

Page 24: Instrumentation  Control Process

Pressure Transmitter Advantages

A Pressure Transmitter is used where indication and/or record of

pressure is required at a location not adjacent to the primary

element.

A Pressure Transmitter is used for both indication and control of

a process.

A Pressure Transmitter is used where overall high performance

is mandatory.

Both Electronic and Pneumatic Transmitters are used.

These can be either Gauge, Absolute or Differential Pressure

Transmitters.

Page 25: Instrumentation  Control Process

Transmitter Measuring Principle

The diagram shows an electronic differential pressure

sensor. This particular type utilizes a two-wire

capacitance technique.

Another common measuring technique is a strain gauge.

Process pressure is transmitted through isolating

diaphragms and silicone oil fill fluid to a sensing

diaphragm.

The sensing diaphragm is a stretched spring element that

deflects in response to the differential pressure across it.

The displacement of the sensing diaphragm is

proportional to the differential pressure.

The position of the sensing diaphragm is detected by

capacitor plates on both sides of the sensing diaphragm.

The differential capacitance between the sensing

diaphragm and the capacitor plates is converted

electronically to a 4–20 mA or 1-5 VDC signal.

For a gauge pressure transmitter, the low pressure side is

referenced to atmospheric pressure.

Page 26: Instrumentation  Control Process

Flow Measurements.

The Orifice Plate

The orifice plate is the simplest and cheapest. It is simply

a plate with a hole of specified size and position cut in it,

which can then clamped between flanges in a pipeline

The increase that occurs in the velocity of a fluid as it

passes through the hole in the plate results in a pressure

drop being developed across the plate.

After passing through this restriction, the fluid flow jet

continues to contract until a minimum diameter known as

the vena contracta is reached.

Page 27: Instrumentation  Control Process

Orifice Plate

Page 28: Instrumentation  Control Process

Working principle & Advantages

The orifice plate is the simplest and cheapest.

The increase that occurs in the velocity of a fluid as it passes through the hole in

the plate results in a pressure drop being developed across the plate. After passing

through this restriction, the fluid flow jet continues to contract until a minimum

diameter known as the vena contracta is reached.

The equation to calculate the flow must be modified

Page 29: Instrumentation  Control Process

The Venturi Tube

The classical or Herschel Venturi tube is the oldest type of differential pressure

flow meter (1887).

The restriction is introduced into the flow in a more gradual way

The resulting flow through a Venturi tube is closer to that predicted in theory so the

discharge coefficient C is much nearer unity (0.95).

The pressure loss caused by the Venturi tube is lower, but the differential pressure

is also lower than for an orifice plate of the same diameter ratio.

Page 30: Instrumentation  Control Process

Advantages of Venturi Tube

The smooth design of the Venturi tube means that it is less sensitive to erosion than the orifice plate, and thus more suitable for use with dirty gases or liquids.

The Venturi tube is also less sensitive to upstream disturbances, and therefore needs shorter lengths of straight pipe work upstream of the meter than the equivalent orifice plate or nozzle.

Like the orifice plate and nozzle, the design, installation, and use of the Venturi tube is covered by a number of international standards.

The disadvantages of the Venturi tube flow meter are its size and cost.

Page 31: Instrumentation  Control Process

The Nozzle

The nozzle combines some of the best features of the orifice plate and Venturi

tube.

It is compact and yet, because of its curved inlet, has a discharge coefficient close

to unity.

There are a number of designs of nozzle, but one of the most commonly used in

Europe is the ISA-1932 nozzle, while in the U.S., the ASME long radius nozzle is

more popular. Both of these nozzles are covered by international standards

Page 32: Instrumentation  Control Process

Rota meter

Rota meter consists of a conical transparent vertical glass tube containing a “bob”.

The flow rate is proportional to the height of the bob.

The Rota meter is characterized by:

Simple and robust construction

High reliability

Low pressure drop

Page 33: Instrumentation  Control Process

Axial Turbine Flow meters

The modern axial turbine flow meter is a reliable device capable of providing the highest accuracies attainable by any currently available flow sensor for both liquid and gas volumetric flow measurement. It is the product of decades of intensive innovation and refinements to the original axial vaned flow meter principle first credited to Wolman in 1790, and at that time applied to measuring water flow.

The initial impetus for the modern development activity was largely the increasing needs of the U.S. natural gas industry in the late 1940s and 1950s for a means to accurately measure the flow in large-diameter, high-pressure, interstate natural gas lines.

Today, due to the tremendous success of this principle, axial turbine flow meters of different and often proprietary designs are used for a variety of applications where accuracy, reliability, and range ability are required in numerous major industries besides water and natural gas, including oil, petrochemical, chemical process, cryogenics, milk and beverage, aerospace, biomedical, and others.

Page 34: Instrumentation  Control Process

Turbine Flow meter

Page 35: Instrumentation  Control Process

Turbine Flow meter & working principle

The meter is a single turbine rotor, concentrically mounted on a shaft within a cylindrical housing through which the flow passes.

The shaft or shaft bearings are located by end supports inside suspended upstream and downstream aerodynamic structures called diffusers, stators, or simply cones.

The flow passes through an annular region occupied by the rotor blades. The blades, which are usually flat but can be slightly twisted, are inclined at an angle to the incident flow velocity and hence experience a torque that drives the rotor.

The rate of rotation, which can be up to several ×104 rpm

A magnetic pick up coil detect the rotation

Page 36: Instrumentation  Control Process

Level Measurement Types

Level Gauges

Guided Wave Radar

Radar

Differential Pressure

Float / Displacer

Ultrasonic

Capacitance

Nuclear

Page 37: Instrumentation  Control Process

Level Gauges

Tubular

Glass Tube with Option of Graduations

Not Popular for Process Applications

Typically Used for Calibrating Metering Pumps (Calibration Tubes)

Page 38: Instrumentation  Control Process

Flat Glass Gauges

Glass Sections on Opposite Sides of the Chamber

View the Liquid Level through the Gauge

Used on Interface Applications and Dirty or Viscous Liquids

Illuminators Can be Used to Diffuse Light Evenly on the Back of the Gauge

Page 39: Instrumentation  Control Process

Reflex Flat Glass Gauge

Single Glass Section with Prisms Cut in the Glass on the Process Side

Light Striking the Vapor Phase is Refracted to the Viewer which Appears

Silvery White

Light Striking the Liquid Phase is Refracted into the Liquid which Appears

Black

Used on Clean, Clear, No corrosive Liquids

Page 40: Instrumentation  Control Process

Magnetic Level Gauge

Consists of a Non-Magnetic Chamber, Internal Float with Magnet and Bi-

Colored Indicator Wafers

Page 41: Instrumentation  Control Process

Float / Displacer

The Visible Length Should Cover the Full Operating Range of Interest Including any Other Level Instrumentation on the Vessel

If More than One Gauge is Required, the Gauges Must Overlap Each Other

Level Chamber Needs to be Installed Vertically Level to Reduce any Possible Friction with the Float

Require Jig Set Connections

May Require a Magnetic Trap

Page 42: Instrumentation  Control Process

Level Float / Displacer

Advantages

Long Visible Lengths

Corrosive or Toxic Liquid Applications

Adaptable to Variations in Fluid Densities

High Pressure or Temperature Applications

Limitations

Affected by changes in fluid density

Coating media may seize moving parts

Over Pressuring can Implode Float

Long ranges may require additional support

Page 43: Instrumentation  Control Process

Bubbler

When Air Pressure Enters a Dip Pipe with a Pressure Greater Than the Hydrostatic Head of the Process Fluid, the Air will Bubble out the Bottom of the Dip Pipe

As the Liquid Level Changes, the Air Pressure in the Dip Pipe also Changes

Consists of Pressure Regulator, Rota meter and Pressure Gauge Along with a Stilling Well

VENT

D/P TRANSMITTER

INSTRUMENT

AIR

Page 44: Instrumentation  Control Process

Types of Temperature Instrument

Thermocouple T/C

Resistance Temperature Detector (RTD)

Thermo well

Bi-metallic Thermometers

Filled Thermal Systems

Page 45: Instrumentation  Control Process

Various Units of Temperature Measurement

°C – degrees Celsius (or Centigrade)

°F – degrees Fahrenheit

K – Kelvin

R – Rankin

Relationship between different units

°C = (°F - 32)/1.8

°F = 1.8 x °C + 32

K = °C + 273.15

R = °F + 459.67

Conversion tables or software can be utilized to facilitate

with converting between these units.

Page 46: Instrumentation  Control Process

Thermocouples (TC’s)

Basic Theory

In 1821 a German physicist named See back discovered the thermoelectric effect which forms the basis of modern thermocouple technology. He observed that an electric current flows in a closed circuit of two dissimilar metals if their two junctions are at different temperatures.

The thermoelectric voltage produced depends on the metals used and on the temperature relationship between the junctions.

If the same temperature exists at the two junctions, the voltage produced at each junction cancel each other out and no current flows in the circuit.

With different temperatures at each junction, different voltages are produced and current flows in the circuit.

A thermocouple can therefore only measure temperature differences between the two junctions, a fact which dictates how a practical thermocouple can be utilized.

Iron (Fe)

Constantan (CuNi)

0ºC100ºC

Thermocouple Circuit

Page 47: Instrumentation  Control Process

Thermocouple measuring circuit

20ºC

Copper (Cu)

Copper (Cu)

0

mV

10

Hot Junction:

In Process

100ºC

Iron (Fe)

Constantan (CuNi)

Equivalent to

80ºC reading

Cold Junction:

Needs to be held constant to give a

fixed reference. ( early methods held

cold junction at 0ºC using ice or

refrigeration unit).

Page 48: Instrumentation  Control Process

Standard Thermocouple Alloy Conductor Combinations

CODE CONDUCTOR COMBINATION TYPICAL OPERATING RANGE ºF

B Platinum-30% Rhodium / Platinum-6% Rhodium +2500 to +3100

C Tungsten-5% Rhenium / Tungsten-26% Rhenium +3000 to +4200

D Tungsten-3% Rhenium / Tungsten-25% Rhenium +2800 to +3800

E Nickel Chromium / Constantan 0 to +1650

J Iron / Constantan +0 to +1400

K Nickel Chromium / Nickel Aluminium 0 to +2300

N Nickel-Chromium-Silicon / Nickel-Silicon-Magnesium 1200 to +2300

R Platinum-13% Rhodium / Platinum 1600 to +2600

S Platinum-10% Rhodium / Platinum 1800 to +2600

T Copper / Constantan -300 to +650

Page 49: Instrumentation  Control Process

Thermocouple Construction

• Normally element is in a thermowell

• Commonly element is 1/4” outside Diameter

• Sheath material, normally Stainless steel but can be

special material such as Inconel, Incoloy, Hastelloy

etc.

• Duplex thermocouples have 2 elements inside one

sheath.

Page 50: Instrumentation  Control Process

RTDs

RTDs (Resistance Temperature Detectors) operate under the principle that the

electrical resistance of certain metals increases and decreases in a repeatable

and predictable manner with a temperature change.

Page 51: Instrumentation  Control Process

RTD Elements

Wire Wound ElementPrecise lengths of wire are wrapped around a ceramic mandrel, then inserted inside a ceramic shell which acts to support and protect the wire windings.

Inner Coil ElementWires are coiled then slid into the holes of a ceramic insulator. Some manufacturers backfill the bores with ceramic powder after the coils are inserted. This keeps the coils from shorting against each other.

Thin Film ElementMetallic ink is deposited onto a ceramic substrate. Lasers then etch the ink to provide a resistance path. The entire assembly is encapsulated in ceramic to support and protect.

Page 52: Instrumentation  Control Process

RTD Lead wire Configuration

2-wire: Should only be used with

very short runs of leadwire. No

compensation for leadwire

resistance.

3-wire: Most commonly used for

industrial applications. Leadwire

compensation.

4-wire: Laboratory use historically,

moving more into industrial

applications. Full compensation

for leadwire resistance.

Page 53: Instrumentation  Control Process

Wheatstone Bridge

The most common method for measuring the resistance of an RTD is to use a

Wheatstone bridge circuit. In a Wheatstone bridge, electrical excitation current

is passed through the bridge, and the bridge output current is an indication of the

RTD resistance.

R1 R

2

R3

AMMETER

RT

D

Page 54: Instrumentation  Control Process

Temperature Element Assembly

Head Nipple-Union-Nipple Thermowell

Page 55: Instrumentation  Control Process

Thermo wells

Straight Shank

FlangedVan Stone

Step Shank

Tapered Shank

Threaded

Weld-in

Plug

Plug

with

Chain

Accessories

Page 56: Instrumentation  Control Process

Thermo wells

Page 57: Instrumentation  Control Process

Thermo well Insertion Modification

TYPICAL THERMOWELL

CONSTRUCTION

SHORTENED

THERMOWELL

CONSTRUCTION

STEPPED THERMOWELL

CONSTRUCTION

Page 58: Instrumentation  Control Process

Temperature Transmitters

Signal Conditioner

Low level inputs

mV from thermocouples

from RTD’s

High level outputs

4-20mA current

Digital (i.e. Fieldbus)

Page 59: Instrumentation  Control Process

Thermistors

Thermistors are temperature sensing devices that are similar to RTD’s in that their resistance changes as temperature changes.

The major difference is that for most thermistors the resistance decreases as temperature increases.

Thermistors are an inexpensive alternative to RTD’s when temperature ranges are below 150°C. Thermistors can be used from temperatures of –80°C to 300°C.

Most thermistors have base resistances, which are much higher than RTD’s.

One of the greatest advantages of using a thermistor sensor is the large change in resistance to a relatively small change in temperature. This makes them very sensitive to small changes in temperature.

Page 60: Instrumentation  Control Process

Bimetallic Thermometers

A Bimetallic Thermometer consists

of an indicating or recording device,

a sensing element and a means for

connecting the two. Basic example:

Two metal strips expand at different rates as

the temperature changes.A pointer is attached to the rotating

coil which indicates the

temperature on the dial.

Coil rotation is caused by the

difference in thermal expansions

of the two metals.

Bimetal Coil

Page 61: Instrumentation  Control Process

Gas chromatography & analyzer

Gas chromatography - specifically gas-liquid chromatography - involves a

sample being vaporized and injected onto the head of the chromatographic

column. The sample is transported through the column by the flow of inert,

gaseous mobile phase. The column itself contains a liquid stationary phase

which is adsorbed onto the surface of an inert solid.

Carrier gas

The carrier gas must be chemically inert. Commonly used gases include

nitrogen, helium, argon, and carbon dioxide. The choice of carrier gas is

often dependant upon the type of detector which is used. The carrier gas

system also contains a molecular sieve to remove water and other impurities.

Page 62: Instrumentation  Control Process

schematic diagram of a gas chromatograph

Page 63: Instrumentation  Control Process

Sample injection port

For optimum column efficiency, the sample should not be too large, and should be introduced onto the column as a "plug" of vapor - slow injection of large samples causes band broadening and loss of resolution. The most common injection method is where a micro syringe is used to inject sample through a rubber septum into a flash vaporizer port at the head of the column. The temperature of the sample port is usually about 50°C higher than the boiling point of the least volatile component of the sample. For packed columns, sample size ranges from tenths of a micro liter up to 20 micro liters. Capillary columns, on the other hand, need much less sample, typically around 10-3 mL. For capillary GC, split/split less injection is used. Have a look at this diagram of a split/split less injector;

Page 64: Instrumentation  Control Process

The split /injector

Page 65: Instrumentation  Control Process

Detectors

Page 66: Instrumentation  Control Process

Columns

There are two general types of column, packed and capillary (also known as open

tubular). Packed columns contain a finely divided, inert, solid support material

(commonly based on diatomaceous earth) coated with liquid stationary phase. Most

packed columns are 1.5 - 10m in length and have an internal diameter of 2 - 4mm.

Page 67: Instrumentation  Control Process

Gas Turbine for Power Generation

The use of gas turbines for generating electricity dates back to 1939 Today, gas turbines are one of the most widely-used power generating technologies. Gas turbines are a type of internal combustion (IC) engine in which burning of an air-fuel mixture produces hot gases that spin a turbine to produce power. It is the production of hot gas during fuel combustion, not the fuel itself that the gives gas turbines the name. Gas turbines can utilize a variety of fuels, including natural gas, fuel oils, and synthetic fuels. Combustion occurs continuously in gas turbines, as opposed to reciprocating IC engines, in which combustion occurs intermittently.

How Do Gas Turbines Work?Gas turbines are comprised of three primary sections mounted on the same shaft: the compressor, the combustion chamber (or combustor) and the turbine. The compressor can be either axial flow or centrifugal flow. Axial flow compressors are more common in power generation because they have higher flow rates and efficiencies. Axial flow compressors are comprised of multiple stages of rotating and stationary blades (or stators) through which air is drawn in parallel to the axis of rotation and incrementally compressed as it passes through each stage. The acceleration of the air through the rotating blades and diffusion by the stators increases the pressure and reduces the volume of the air. Although no heat is added, the compression of the air also causes the temperature to increase.

Page 68: Instrumentation  Control Process

Turbines Work

Page 69: Instrumentation  Control Process

Principle of turbine

The compressed air is mixed with fuel injected through nozzles. The fuel and

compressed air can be pre-mixed or the compressed air can be introduced directly into

the combustor. The fuel-air mixture ignites under constant pressure conditions and the

hot combustion products (gases) are directed through the turbine where it expands

rapidly and imparts rotation to the shaft. The turbine is also comprised of stages, each

with a row of stationary blades (or nozzles) to direct the expanding gases followed by

a row of moving blades. The rotation of the shaft drives the compressor to draw in

and compress more air to sustain continuous combustion. The remaining shaft power

is used to drive a generator which produces electricity. Approximately 55 to 65

percent of the power produced by the turbine is used to drive the compressor. To

optimize the transfer of kinetic energy from the combustion gases to shaft rotation,

gas turbines can have

Page 70: Instrumentation  Control Process

Turbine field installation

Page 71: Instrumentation  Control Process

Final instrument of process control valve

Topics:-

Introduction

Control Valve Characteristics and Types

Control Valve Parts

Control Valve Accessories

Control Valve Operation

Valve Hand Jack and Minimum Stop

Page 72: Instrumentation  Control Process

Introduction of control valve

Introduction:-

The control valve is composed of a valve with an externally powered actuator. The control valve is designed specifically for reliable continuous throttling with minimum backlash and packing friction. The control valve is involved with the disposition of energy in a process. It dispenses energy from the source, dissipated energy that exists within the system, or distributes energy in the system in one way or another.

The chemical and petroleum industries have many applications requiring control of gases, liquids, or vapors processes. Many process operation require regulation of such quantities as density and composition, but by far the most important control parameter is flow rate. A regulation of flow rate emerges as the regulatory parameters for reaction rate, temperature, composition, or a host of other fluid properties. For this purposes the control valve is using as the process control element.

Page 73: Instrumentation  Control Process

Control Valve Characteristics and Types

The different types of control valves are classified by a relationship between

the valve stem position and the flow rate through the valve. This control valve

characteristic is assigned with the assumptions that the stem position indicates

the extent of the valve opening and that the pressure difference is determined

by the valve alone. There are three basic types of control valves whose

relationship between stem position (as percentage of full range) and the flow

rate (as a percentage of maximum)

• Quick Opening:-

This types of valve is used predominantly for full ON/full OFF control

applications. The valve characteristic shows that a relatively small motion of

valve stem results in maximum possible flow rate

Page 74: Instrumentation  Control Process

Through the valve. Such a valve, for Example , may allow 90% of the flow rate with only a 30% travel of the stem.

2. Linear:-

This type of valve, as shown in picture, has a flow rate that varies linearly with the stem position. It depends the ideal situation where the valve alone determines the pressure drop.

3. Equal Percentage:-

Equal percentage is the characteristic most commonly used in process control. The change in flow per unit of valve stroke is directly proportional to the flow occurring just before the change is made. While the flow characteristic of the valve itself may be equal percentage, most control loops will produce an installed characteristic approaching linear when the overall system pressure drop is large relative to that across the valve.

Page 75: Instrumentation  Control Process

The types of the valves as follows,

Globe valve

Butterfly valves

Gate valves

Diaphragm valves

Ball valves

Knife edge valves

Page 76: Instrumentation  Control Process

Control Valve Parts

The Valves has Two Main Parts

Body Assembly

Actuator Assembly

Page 77: Instrumentation  Control Process

Body Assembly Parts

Body:

The pressure retaining housing through which the service fluid flows. It has inlet and outlet connections, and houses the trim components

Seat Ring:

Trim component the plug makes contact with to close the valve.

Seat Retainer:

Trim component which clamps the seat ring in place. The seat retainer does not guide the plug, and should not be confused with a cage

All Gaskets:

are used in control valves to prevent leakage. around the seat ring, bonnet or pressure-balanced sleeve.

Page 78: Instrumentation  Control Process

Plug:

Part that moves in and out of the seat ring to open and close the valve. It can also be used to characterize the flow.

Bonnet:

The valve component which houses the guides and packing. It also seals one opening to the body.

Bonnet Flange:

Flange that attaches the bonnet to the body.

Guides — Bushings contained in the packing box which align the plug with the seat ring.

Guides — Bushings contained in the packing box which align the plug with the seat ring.

Packing — Material used to seal the valve from leaking around the plug stem.

Packing Box — Internal bore of bonnet which contains guiding and packing.

Page 79: Instrumentation  Control Process

Actuator Assembly

Page 80: Instrumentation  Control Process

Actuator Assembly Parts

Actuator — Device which develops sufficient thrust to open or close the valve. Common designs include piston, diaphragm, hydraulic, manual hand wheel and electro-hydraulic actuators.

Lifting Ring: Used for Lifting The Valve

Adjusting Screw: Part used to compress the actuator spring.

Cylinder: Actuator part used for containing air pressure and enclosing the piston.

Spring Button: The part that prevents movement of the actuator spring and permits the adjusting screw to compress the spring.

Spring: In piston actuators, the part which provides force for fail-safe operation; in diaphragm actuators, the part that provides force to counteract air pressure from the opposing chamber.

Piston: Part used to separate two air chambers of piston actuator.

Actuator Stem: Part used to connect the valve plug with the piston actuator.

Yoke: A component which secures the actuator to the valve body.

Page 81: Instrumentation  Control Process

Butterfly Valve Body Assembly

Page 82: Instrumentation  Control Process

Spring Cylinder Rotary Actuator

Page 83: Instrumentation  Control Process

Valve Accessories

Positioner

I/P Transducer

Volume Booster

Quick Exhaust

Lockup Realy

Solenoid

Limit Switch

Page 84: Instrumentation  Control Process

Positioner

A valve Positioner is like a proportional controller. The set point is the control signal from the primary controller and the controlled variable is the valve position. The Positioner compensates for disturbances and nonlinearities.

The use of positioner are as follows,

When the signal pressure is not enough to operate the control valve.

To make split range between the valves.

It can be used to reverse the action of the actuator from air to open to air to close and vice versa.

To minimize the effect of hysterisis effect.

To minimize the response time for the valve.

If the actuator is spring less positioner will be used.

If the valve has high friction.

Page 85: Instrumentation  Control Process

Operation:-

The operation of the most common positioner as follows. In construction, pneumatic valve

positioners have diaphragms or bellows to sense the incoming signal from the controller and

feed back devices from the valve stem. The unit may be position balanced or force balanced.

Any error in the two signals causes a proportional change in the output of a pilot valve.

In our plant we are using Valtek beta positioner and the main parts are shown in the picture.

Page 86: Instrumentation  Control Process

Instrument Signal Capsule: It will receive The Signal from I/P Transducer & move The Pilot Stem.

Spool Valve:

Feedback Spring

Cam

Range Arm

Range Adjustment Locking Screw

Range Adjustment Gear

Zero Adjustment Locking Knob

Zero Adjustment

Page 87: Instrumentation  Control Process

I/P Transducer

Transducers convert a current signal to a pneumatic signal. The most common transducer converts a 4-20 mA electric signal to a 3-15 psig pneumatic signal.

An increase in the dc signal to the coil increases the magnetic field around the coils. This field increases the magnetic strength in the armature and the magnetic attraction across the air gap between the armature and the pole pieces. The magnetic attraction will therefore downward at the nozzle end and upward at the feed back bellows end, resulting in a torque that rotates the armature about the torsion rod to cover the armature nozzle. The resulting restriction produces an increased pressure in the nozzle, in the upper chamber of the relay, and in the feed back bellows. The relay responds to the increase in nozzle pressure to increase the output pressure to the actuator and control valve.

Volume Booster:

Volume Boosters are used on throttling control valves to provide fast stroking action with large input signal changes. At the same time, the flow boosters allownormal positioner air flow (and normal actuation) with small changes in the positioner input signal. Depending on actuator size, packing set and the numberused, boosters can decrease valve stroking times up to 90 percent.

Page 88: Instrumentation  Control Process

Valve Operation:-

Air to Open

Air to Close

Air fail to Lock in the same position

Fail Safe System for Valves:- Where service conditions exceed the capabilities of the standard fail-safe

spring to drive the valve to its failure position, and where specially

designed, extra-strong

failure springs may be both mechanically and economically unfeasible, air

spring fail-safe systems on Valtek control valves provide the thrust

necessary to drive the

Page 89: Instrumentation  Control Process

plug to its failure position. An air spring provides a pressurized volume of air to drive

the actuator piston in the failure direction. The volume of air is sometimes provided

within the actuator itself, or where the cylinder volume is insufficient, a separate

external volume tank is provided.

Air spring systems are used primarily to close valves upon air failure. And sometimes

they must open valves upon air failure. A fail-closed valve is customarily operated

with the flow direction over the plug. Thus, with the plug on the seat, the upstream

pressure acts to hold the valve closed.

Fail-open valves customarily operate with the flow direction under the plug. Thus,

when a general system failure occurs, the upstream pressure will keep the plug off the

seat and the valve open.

Air springs on valves are practical because the locked-up air is used only at the instant

of air failure to drive the valve to the fail position. Line pressure will insure that the

valve stays either closed or open.

Page 90: Instrumentation  Control Process

• Occasionally, service conditions require that the valve remain in the last operating position upon loss of air supply. For such applications, valves can be equipped with a fail-in-place lock-up system. If air failure occurs, the system activates two pilot-operated lock-up valves that trip and lock the existing cylinder pressures on both sides of the piston, thus maintaining the last throttling position.

Signal-to-open, Fail-closed Signal-to-close, Fail-open

Page 91: Instrumentation  Control Process

-------------The End ------------