Maintaining MV Switchgear Western Mining Electrical

Association Tucson, AZ

November 15, 2007

Page 2: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Maintenance of MV (Above 1000V and up to 38kV) Switchgear

Keywords:SafetyDeenergize Lockout/TagoutMaintenance IntervalArc-flashGroundingInterlocksToolsBackfeed

Page 3: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Why Maintain Switchgear?

It’s a Hobby!!!!!!!Switchgear is new and doesn’t need maintenance!!!Short-Circuit is unpredictable so why bother?

Page 4: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Why Maintain Switchgear? Getting Everyone’s Attention

Every Electrical Conductor or Circuit is Considered Energized (Unsafe) Until Proven Otherwise (Innocent)

Page 5: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Why Maintain Switchgear?

Reduce Hazards to Life and Property that can result from Failure or Malfunction of Poorly Maintained Electrical SystemsReduce the Outages and Down timeIncrease the efficiency of work force Significant Loss of Revenue until Service is RestoredWell Maintained Switchgear will last long time, More importantly, It is the safest thing to do

Page 6: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Factors affecting the Electrical Safety in Coal Mines

Inadequate or Improper Training Failure to Deenergize, Lockout and TagoutFailure to ensure proper groundingFailure to recognize downstream devices (Possible back feed from downstream device) Defeating and/or Ignoring Mechanical and Electrical Safety InterlocksPoor Grounding

Page 7: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Factors affecting the Electrical Safety in Coal Mines

Failure to Maintain Electrical Distribution Documents (What is that?)Aging Assets (Run to Failure Approach, No one wants to spend Time and Money until it breaks down)Intrusion by Animals into Electric Supply Substations

Page 8: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Potential Sources of Animal Outages

Animals Percentage

90%

86%

57%

46%

Cats 43%

Mice 30%

Rats 19%

Opossums 13%

Survey of 174 Public Utilities.

114 Responded

IEEE Std 1264-1993

IEEE Guide for Animal Deterrents for Electric Power Supply Substations

Page 9: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Potential Sources of Animal Outages

Animals Percentage

Squirrel 90%

Birds 86%

Raccoons 57%

Snakes 46%

Cats 43%

Mice 30%

Rats 19%

Opossums 13%

Survey of 174 Public Utilities.

114 Responded

IEEE Std 1264-1993

IEEE Guide for Animal Deterrents for Electric Power Supply Substations

Page 10: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Interrupting Devices and Key Components of MV Mining SwitchgearStationary Mounted or Drawout Vacuum Circuit Breakers Stationary Mounted Load-break and Non Load-break Disconnect SwitchesVacuum ContactorsNeutral Grounding ResistorsSurge ArrestersCurrent Transformers (CT’s)

Page 11: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Interrupting Devices and Key Components of MV Mining SwitchgearPotential Transformers (PT’s)Ground Monitors & Capacitor Trip DevicesStation Service Transformers (CPT’s)FusesProtective Relays, Meters, Control Switches and Indicating Lights

Page 12: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Mechanical Endurance Capabilities and Maintenance

Intervals

Vacuum Circuit Breakers and Air-break Switches

Page 13: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Schedule of Operating Endurance Capabilities for Circuit Breakers (ANSI Std C37.06-2000)

4.76kV, 15kV 600A-2000A (up to 31.5kA SC)No. of NO Load Mechanical Operations = 10,000No. of Load (Rated Current) Operations = 1,000Inrush Current Switching = 750No. of operations Between Servicing = 2,000

One Closing+One opening = 1 Operation

Page 14: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Schedule of Operating Endurance Capabilities for Circuit Breakers (ANSI Std C37.06-2000)

27kV, 600A- 2000A (up to 25kA SC)No. of NO Load Mechanical Operations = 2,500No. of Load (Rated Current) Operations = 200Inrush Current Switching = 100No. of operations Between Servicing = 500One Closing+One opening = 1 Operation

Page 15: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Periodic Inspection of Vacuum Circuit Breakers

Maintenance Intervals are usually based on both, an elapsed time and no. of operations, whichever Occurs firstIf Short-Circuit Operation Occurs (major event) before the completion of listed operations, maintenance is recommendedAn Annual inspection for serviceability is recommended by most manufacturers

Page 16: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

What is Recommended for Servicing Between Maintenance Interval (Breakers)

Cleaning ContactsAdjusting and Tightening ContactsLubricating and Dressing Contacts

Page 17: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Mechanical Endurance for MV Switches ANSI Std C37.22-1997

Page 18: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Load Current Switching Rating for MV Switches ANSI Std C37.22-1997

Page 19: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Recommended Minimum Electrical Clearances for Indoor Switches & Buss

supports (ANSI C37.32-1996)

Page 20: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Use Fluidized Epoxy Buss Insulation for Reducing Electrical Clearances

Epoxy Powder Aluminum

Foil Wrap

Page 21: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Silver Plating

Uniform coating

Fluidized Epoxy Buss

Page 22: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Maintenance/Inspection of Neutral Grounding Resistors

• Damage May Occur from:LighteningStormsEarthquakeWildlifeOverloadsExtended Service Life

Page 23: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Maintenance/Inspection of Neutral Grounding Resistors

• Periodic Inspection :• Deenergize the system being grounded and break

the connections between neutral and the grounding resistor

• An Isolation Switch may be used to break this connection

• Remove the front and rear covers for visual inspection of internal components

• Check for cracked insulators or bushings• Perform Dielectric Withstand Test (Hi-pot) to

ensure the insulation isolation

Page 24: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Maintenance/Inspection of Neutral Grounding Resistors

• Check the Resistive Element for continuity• Check all internal connections for tightness• Vacuum any dirt or debris from the inside of the

enclosure• Follow Manufacturer’s Maintenance Instructions

Page 25: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Surge Arresters - Short Cable Length

BIL Margin is Reduced Appox 1.6kV/Ft

Skirt-to-Skirt Clearance = 1”/30kV BIL

Page 26: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Maintain Good Ground (Inspect Grounding Connections for tightness and Absence of

Corrosion

Page 27: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Insulation Coordination When CT’s are Mounted on Buss

C-400 Class CT is bus mounted by using Polyester bottles with full coordination of Insulation and eliminating Corona

Page 28: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Disconnect Switches with Fluidized Epoxy Buss Insulation and Inter-phase Barriers

Page 29: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

When Specifying Switchgear, Consider Unusual Service

Conditions

Page 30: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Application Guide For Switchgear Unless Specified, Usual Service Conditions Apply

Ambient Air Temp does not exceed –30C or + 40CAltitude does not exceed 1000m above sea levelAir is not significantly polluted (Pollution level 1 for I/D, 2 for O/D per IEEE C37.100.1)Relative Humidity (Average value) does not exceed 95% over 24h period & 90% over 30 day periodVibration does not exceed low level per IEEE- 693Solar Radiation does not exceed 1044 W/m sq (O/D Swgr only)Ice coating for exposed movable parts does not exceed 1mm (O/D only)Wind speed does not exceed 40 m/s or 90 mph (O/D)

Page 31: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Application Guide For Switchgear

Unusual Service ConditionsAmbient Air Temp above 40 CCan’t exceed total temp (40C + 65C Rise = 105C)Continuous current rating must be de-rated per section 8.4 of C37.20.2Ambient Air Temp below –30 CUse Thermal insulation and Space heatingAltitudeHistorically, switchgear has been successfully applied at altitudes up to 1,000 m without the use of an altitude correction factor

Page 32: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Application Guide For Switchgear Unusual Service Conditions (Cont)

For Altitude higher than 1 000 m, multiply the rated insulation levels at sea level by a factor Ka in accordance with Figure 1 of C37.100.1Hot and Humid ClimatesMake Fungus-resistant by means of:- Heaters & Ventilation- Fungus resistant coating for secondary wiring- Fungus and rust resistant property for paint Solar Radiation (O/D Switchgear)When Solar radiation must be considered for specific geographic location, refer to IEEE Std C37.24 for details

Page 33: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Maintain and Update Electrical Distribution Documentation

• Instruction Manual• One-Line Diagram• Three-Line and schematic Diagrams• Wiring Diagrams• Material List• Utilize Mimic Buss for System Representation

Page 34: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

System Representation with Mimic Buss

Page 35: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss
Page 36: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss
Page 37: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Switchgear Looks Nice when it’s New

Page 38: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

What Happens if It is not Maintained

Page 39: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Reward for those who Maintain MV Switchgear

Page 40: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Reward for Maintaining Switchgear

Page 41: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

References

• NFPA 70B –2000 Recommended Practice for Electrical Equipment Maintenance

• NFPA 70E-2000, Electrical Safety Requirements for Employee Workplace

• IEEE Std 1264-1993, IEEE Guide for Animal Deterrents for Electric Power Supply Substations

• IEEE Std 1584-2002, IEEE Guide for performing Arc-Flash Hazard Calculations

• NFPA 70-2002, National Electric Code

Page 42: Maintaining MV Switchgear - WMEA Papers/Maintaining MV Swgr - AZZ_Central... · Maintaining MV Switchgear ... Switches ANSI Std C37.22-1997. ... Clearances for Indoor Switches & Buss

Questions?