Medium-voltage switchgear

No. AGS 531 446-01

Edition 04/2014

www.schneider-electric.com

GHAGas-insulated switchgear ≤ 40.5 kV (≤ 40 kA)for single and double busbar panels

Assembly Instructions

Page 2: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

Manufacturer:

Schneider Electric Sachsenwerk GmbH Rathenaustrasse 2 D-93055 Regensburg Germany ( +49 (0) 9 41 46 20-0 7 +49 (0) 9 41 46 20-418

Service:

Schneider Electric GmbH MA GIS Rathenaustrasse 2 D-93055 Regensburg Germany ( +49 (0) 9 41 46 20-777 7 +49 (0) 9 41 46 20-776

Page 3: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

3AGS 531 446-01 | Edition 04/2014

Contents

Remarks on this manual .............................................................................5Purpose and target group ........................................................................................... 5Reference documents ................................................................................................ 5Terms and symbols used ............................................................................................ 6Abbreviations used ..................................................................................................... 6Any questions or suggestions?................................................................................... 6

1 Safety provisions ..............................................................................7

2 Design, description, variants ...........................................................82.1 Switchgear panels with single busbar ............................................................. 82.2 Panels with double busbar .............................................................................112.3 Dimensions and weights ............................................................................... 132.4 Applicable standards ..................................................................................... 172.5 Environmental and operating conditions ....................................................... 172.6 Intended use ................................................................................................. 182.7 Disposal after the end of service life ............................................................. 18

3 Packaging, transport, storage........................................................193.1 Shipping units ................................................................................................ 193.2 Transport ....................................................................................................... 193.3 Storage .......................................................................................................... 20

4 Assembly .........................................................................................214.1 Safety provisions ........................................................................................... 214.2 Important instructions for assembly .............................................................. 214.3 Requirements regarding the switchgear room .............................................. 224.4 Transporting the panels on the construction site........................................... 254.4.1 Transport of panel by means of a crane ................................................... 254.4.2 Transport using the transport frame ......................................................... 264.4.3 Transporting the panels onto the base frame ........................................... 274.5 Attachment of pressure relief duct ................................................................ 284.6 Remove cable compartment cover and shutters ........................................... 294.6.1 Cable compartment interlock (optional) .................................................... 294.6.2 Remove cable compartment cover and shutters ...................................... 304.7 Installation of panels ..................................................................................... 324.7.1 Installationofthefirstswitchgearpanel .................................................... 324.7.2 Removal of transport securing device ...................................................... 324.7.3 Pre-coat the high-quality electrical joints of the busbar link ...................... 334.7.4 Preassembling the clamping contacts ...................................................... 344.7.5 Screw-fastening the panels to one another .............................................. 354.8 Compensating shutters for the panel front .................................................... 364.9 Busbar link: B link .......................................................................................... 394.9.1 Press silicone sleeve back ....................................................................... 404.9.2 Connecting the busbar (fasten preassembled clamping contacts) ........... 414.9.3 Contact resistance measurement of busbar screw fastening ................... 424.9.4 Fasten silicone sleeve to adjacent panel .................................................. 434.9.5 Cover of busbar link in case of panels without pressure relief duct .......... 444.9.6 Current transformer on the busbar for fan control .................................... 474.10 Reinforcement ............................................................................................... 504.11 Screw-fastening the panel to the base frame ................................................ 514.12 Mounting the earth bus ................................................................................. 52

5 Busbar attachments ........................................................................535.1 Safety provisions ........................................................................................... 535.2 Assembly of surge arresters ......................................................................... 535.3 Assembly of voltage transformers ................................................................. 54

6 Low-voltage cabinet ........................................................................566.1 Assembly ....................................................................................................... 566.2 Connecting the control lines .......................................................................... 57

Page 4: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

4 AGS 531 446-01 | Edition 04/20144

Contents

7 Switchgear termination...................................................................597.1 Attachment of the protective tank to the left-hand / right-hand end of the

busbar ........................................................................................................... 597.2 Switchgear without pressure relief duct ........................................................ 607.2.1 Overview ................................................................................................... 607.2.2 Attachment of the right-hand or left-hand side wall .................................. 617.2.3 Extension of side wall in double busbar switchgear ................................. 637.3 Attachment of fan .......................................................................................... 65

8 Switchgear with pressure relief device .........................................678.1 Overview ....................................................................................................... 678.2 Cover plate ................................................................................................... 698.3 Attachment of pressure relief duct ................................................................ 708.4 Attachment of side walls for pressure relief from the switchgear room ......... 718.5 Attachment of side walls for pressure relief into the switchgear room .......... 72

9 High-voltage connection ................................................................739.1 Cable compartment with base plates (optional) ............................................ 739.2 Outer cone-type bushing ............................................................................... 749.3 Inner cone-type socket .................................................................................. 77

10 Commissioning ...............................................................................8010.1 Final steps ..................................................................................................... 8010.1.1 Attachment of the tool board .................................................................... 8010.1.2 Cleaning and checking assembly ............................................................. 8010.1.3 Remount covers (see Chapter 4.6, page 29) ........................................... 8110.1.4 Damaged paint ......................................................................................... 8110.1.5 Inspection ................................................................................................. 8110.2 Commissioning .............................................................................................. 81

11 Optional high-voltage test on commissioning .............................8211.1 Power frequency withstand test of the busbar .............................................. 8211.2 Cable testing ................................................................................................. 8411.3 Cable jacket test ............................................................................................ 88

12 Replacement of components and panels .....................................89

13 Annex ...............................................................................................9013.1 Auxiliary products .......................................................................................... 9013.2 Required tools (not included in the scope of supplies) ............................... 9013.3 Coating the contact surfaces ...................................................................... 9213.4 Screw locking compound .............................................................................. 9213.5 Specificationsforscrewconnections ............................................................ 93

Page 5: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

5AGS 531 446-01 | Edition 04/2014

For information which is not included in this manual and the assembly drawings sup-plied with the equipment, please contact the manufacturer.As our products are subject to continuous further development, we reserve the right to make changes regarding the standards, illustrations and technical data.Alldimensionsspecifiedinthismanualareinmillimeters.

Purpose and target group

This Technical Manual describes assembly and commissioning of gas-insulated medium-voltage switchgear units of the GHA series.It is an integral part of the product and must be stored so that it is readily accessible at all times for and can be used by persons who are to work on the switchgear. If the switchgear is sold to new owners, they must receive this document along with the switchgear.This Technical Manual is exclusively intended for specialist electricians who havebeencertifiedfortheGHAseries(trainingcertificate).This Technical Manual cannot describe every imaginable individual case or every customer-specificversionoftheproduct.Thus,onlythebasicassemblyprocedureisdescribed. The detailed assembly work for the switchgear model in question is illus-trated for each operation required in the assembly drawings provided to this effect.

Reference documents

Purchaseagreementwiththestipulationsregardingtheswitchgear-specificequipment and the legal details

Theappropriateswitchgear-specificcircuitdiagrams/documentation GHA Operating Manual The Operating Manuals of the devices installed in the switchgear:

– Voltage detection systems, e. g. IVIS (no. AGS 531 751-01) – Insulating gas monitoring system IDIS (no. AGS 531 691-01) – System for the detection of internal arcs ILIS (optional) (no. AGS 531 761-01) – Devices in the low-voltage cabinet.

The Assembly Instructions of the manufacturer – of the cable connection systems to be connected to the switchgear – of the voltage transformers.

The assembly drawings supplied with the equipment

The following additional documents must be complied with:

Remarks on this manual

Page 6: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

6 AGS 531 446-01 | Edition 04/20146

Remarks on this manual

Terms and symbols used

This Technical Manual uses certain terms and symbols. They warn about dangers or provide important information which must be complied with in order to avoid danger to persons and damage to equipment:

"Danger!"This danger symbol warns about dangerous electrical voltage. Contact with voltage may result in fatal injury!

"Warning!"This danger symbol warns about the risk of injury. Please comply with all the provisions identified by this symbol in order to avoid death or serious injury.

"Warning!"This danger symbol warns about the risk of falling.

"Notice:"This instruction symbol is used for information which is important to avoid material damage.

Abbreviations used

Forreasonsofsimplification,thefollowingabbreviationsareusedinthismanual:ESS = Single busbarDSS = Double busbarSS1 = Busbar 1SS2 = Busbar 2SS-StW = Busbar current transformerTrSS = Disconnector in the busbar run

Ur = Rated voltage Ir = Rated normal current (feeder panel)

Any questions or suggestions?

Do you have any questions or suggestions regarding this manual, or do you require further information?We always strive to provide you with the best-possible information for optimum, safe use of our products. Thus, do not hesitate to contact us if you have any recommen-dations, amendments or proposals for improvement.

Page 7: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

7AGS 531 446-01 | Edition 04/2014

1 Safety provisions

The work described in this manual may only be performed by specialist electricians with proven experience in conjunction with the GHA series and the applicable safety provisions.Please read the whole manual carefully before working on the switchgear.

Metal-enclosed AC switchgear for rated voltages > 1 kV up to including 52 kV: IEC 62271-200

Useandhandlingofsulphurhexafluoride(SF6) in high-voltage switchgear: IEC 62271-303

The locally applicable accident prevention, operating and work instructions must be complied with.

Installation: IEC 61936-1/EN 61936-11

Operation of electrical equipment: EN 50110-11

1 The national standards applicable in the country where the equipment is to be installed must be complied with.

Before performing work on the panels, it is essential that you comply with the follow-ing instructions:

Danger!Risk of fatalities due to high voltage. Isolation from high voltage and earthing must always be ensured before performing assembly or maintenance work.

Danger!Risk of fatalities due to supply voltage. Isolation from supply voltage must always be ensured before performing assembly or maintenance work.

Warning!Risk of injury due to movable parts in mechanical drives. For maintenance work,

isolate the system from the supply voltage release the circuit-breaker’s energy storing device by OFF-

ON-OFF operation and make-proof earthing switches by the appropriate ON-operation.

Warning!After removing covers from a switchgear unit, operator safety may be reduced regarding internal arcs unless the switchgear is isolated from the power supply. Optimum operator safety is only ensured if the switchgear is completely disconnected from the power supply and grounded during assembly.

For the case of an internal fault, the GHA switchgear features pressure relief ports which prevent the panels and the switchgear from bursting.This Technical Manual does not include information regarding the safety of buildings in case of internal faults (pressure load of the switchgear room and necessary pres-sure relief ports). Pressure calculations for switchgear rooms incl. recommendations regarding pressure relief ports can be provided on request against a fee. For further details, please contact the manufacturer.Incaseoffireorofinternalfaults,toxicandcausticdecompositionproductsmaybeproduced. Comply with the locally applicable accident and safety provisions.Incaseofpersonalinjury,takefirst-aidmeasuresorcausethemtobetaken.

Applicable standards and regulations:

Behaviour in case of incidents or accidents

Page 8: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

8 AGS 531 446-01 | Edition 04/2014

2 Design, description, variants

2.1 Switchgear panels with single busbar

1

2

3

4

56a

7

8

9

10

1213

14

15

16

17

1 Busbar tank with three-position switch

2 Jack rings3 Busbar link4 Circuit-breaker tank with vacuum

interrupter chambers5 Toroidal-core current transformer6a Outer cone-type bushing6b Inner cone-type socket7 Voltage transformer (optional)8 Cable support9 Cable compartment cover10 Disconnecting device for voltage

transformer (optional)11 Test sockets for cable test12 Capacitive voltage testing system13 IDIS indicator for insulating gas

monitoring14 Hinged front frame15 Manual operator interface16 Low-voltage cabinet17 IDIS gas density switch

Fig. 1Circuit-breaker panel with outer cone-type bushing

1

2

3

4

5

7

11

16

17

18

10

6b

8 9

11

6b

8

7

5

10

Fig. 2Circuit-breaker panel with inner cone-type socket

Page 9: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

9AGS 531 446-01 | Edition 04/2014 9

2 Design, description, variants

123

4

5

6

9

12

10

11

87

13

14

1 Right-hand busbar tank with three-position switch

2 Left-hand busbar tank with three-position switch

3 Jack rings4 Busbar link5 Circuit-breaker tank with vacuum

interrupter chambers6 Toroidal-core current transformer

(optional)7 Voltage transformer (optional)8 Cable compartment cover9 Test sockets (optional)10 IDIS indicator for insulating gas

monitoring11 Hinged front frame12 Manual operator interface13 Low-voltage cabinet14 IDIS gas density switch

Fig. 3Bus section coupler, shown for rated current Ir≤2000A

6

8

Fig. 4Bus section coupler, shown for rated current Ir≤2500A

L R

L R

Page 10: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

10 AGS 531 446-01 | Edition 04/201410

2 Design, description, variants

Busbar attachments

Fig. 5Busbar voltage transformers (2 variants available)

Fig. 6Busbar surge arresters (2 variants available)

Fig. 7Busbar earthing switch

Page 11: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

11AGS 531 446-01 | Edition 04/2014 11

2 Design, description, variants

2.2 Panels with double busbar

1

2

7

3

4a

5

6

171819 16

8

9

10

12

13

14

15

11

1 Gas density switch of the IDIS sys-tem for busbar 1 (rear busbar)

2 Busbar link SS13 Circuit-breaker tank with vacuum

interrupter chambers4a Outer cone-type bushing4b Inner cone-type socket5 Toroidal-core current transformer6 Voltage transformer (optional)7 Cable support8 Cable compartment cover9 Disconnecting device for voltage

transformer (optional)10 Capacitive voltage testing system11 IDIS indicator for insulating gas

monitoring 12 Hinged front frame13 Manual operator interface14 Low-voltage cabinet15 Gas density switch of the IDIS sys-

tem for busbar 2 (upper busbar)16 Busbar link SS217 Tank, busbar 2 (upper busbar) with

three-position switch18 Jack rings19 Tank, busbar 1 (rear busbar) with

disconnector20 Test sockets for cable test

Fig. 8Circuit-breaker panel with outer cone-type bushing

1

2

3

4

5

7

20

16

17

18

10

6b

8 9

5

11

10

7

8

6b

Fig. 9Circuit-breaker panel with inner cone-type socket

12

12

Page 12: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

12 AGS 531 446-01 | Edition 04/201412

2 Design, description, variants

Fig. 10Bus section coupler, busbar 2 (busbar 1 analogous)

Fig. 11Bus coupler

Fig. 12Metering panel with busbar voltage transformer or with bus-bar surge arrester (not shown)

Fig. 13Bus section coupler, busbar 2 (busbar 1 analogous)

12 1

2

12 1

2

Page 13: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

13AGS 531 446-01 | Edition 04/2014 13

2 Design, description, variants

2.3 Dimensions and weightsSwitchgear panels with single busbar (see Fig. 14, page 16)

Panel type Rated current Ir1 [A]

Panel width A [mm]

Depth2 [mm]

Depth3 [mm]

Approx. weight [kg]4

Feeder panel

≤ 1250 6001330

2400/2780(Height of low-voltage

cabinet: 800/1200)

7001600

600/8005800

2000 1380/13305 900

2500 900 1330 1100

L R

Bus section coupler

≤ 1250800

1330 9001600/2000 1380 1100

2500 1000 1330 1300

Bus sectionalizer with disconnector ≤ 2500 600 1330 300

Busbar measure-ment with current transformer

≤ 2500 600 1330

2600/2780 (Height of low-voltage

cabinet: 800/1200)

300

Attached busbar earthing switch +70

Disconnecting device attached to the busbar (for voltage transformer or surge arrester) (panel height depending on the attachment design, see Chapter 2.1, page 10)

24006/25007 +70

Voltage transformer for outgoing feeder cable / busbar +120 (3 x 40)

1 In the case of feeder panels, the rated current Ir refers to the feeder (max. busbar nominal current: 2500 A)2 The values listed in the Tables are referred to a panel depth without pressure relief duct on the rear.

Depth of panels with rear pressure relief duct: 1595 mm3 –Dampingresistor(foroptionalvoltagetransformer)onthelow-voltagecabinet:specifiedheight+150 – Height of pressure relief duct: 2400 – Height of pressure relief duct with fan: 26004 including the low-voltage cabinet, without voltage transformer and for feeder panels with outer cone-type bushing

feeder panels with inner cone-type socket: max. + 200 kg Panels with rear pressure relief duct: max. + 100 kg

5 The dimensions depend on the cable connection system; inner cone-type socket / outer cone-type bushing system6 Voltage transformer on the busbar can be removed by pulling it laterally (see Fig. 5, page 10)7 Voltage transformer on the busbar can be removed by pulling it upwards (see Fig. 5, page 10

Page 14: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

14 AGS 531 446-01 | Edition 04/201414

2 Design, description, variants

Switchgear panels with double busbar (see Fig. 15, page 16)

Panel type Rated current Ir1 [A]

Panel width A

[mm]

Depth2 [mm]

Depth3

[mm]

Approx. weight [kg]4

12

Feeder panel

≤ 1250 6001700

2400/2780(Height of low-voltage

cabinet: 800/1200)

9001600

600/8005900

2000

1860

1200

2500 900 1400

12

Bus section coupler≤ 1250/1600

8001700 1100

2000 1980 14002500 1000 2030 1300

12

Bus section coupler

≤ 1250/1600800 1700

11002000 1400

2500 1000 1850 1300

12

Bus coupler

≤ 1250/1600600

1700 9002000

1860

1100

2500 900 1600

12

Bus sectionalizer with disconnector

≤ 1600 ≤ 2500

600 600

1700 1970

400 450

12 Busbar measurement

with current trans-former ≤ 2500 600 1700 2600/2780 600

1 In the case of feeder panels, the rated current Ir refers to the feeder (max. busbar nominal current: 2500 A).2 The values listed in the Tables are referred to a panel depth without pressure relief duct on the rear. Technicaldetailsandthedesignfortherearpressurereliefductmustbeclarifiedwiththemanufacturerasrequired.3 –Dampingresistor(foroptionalvoltagetransformer)onthelow-voltagecabinet:specifiedheight+150 – Height of pressure relief duct: 2400 – Height of pressure relief duct with fan: 26004 Thespecifiedweightsapplyincludingthelow-voltagecabinetandwithoutthevoltagetransformer;theyrefertofeederpanels

with outer cone-type bushing. - Feeder panels with inner cone-type socket: max. + 200 kg

– Panels with rear pressure relief duct: max. + 150 kg5 The dimensions depend on the cable connection system; inner cone-type socket / outer cone-type bushing

Page 15: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

15AGS 531 446-01 | Edition 04/2014 15

2 Design, description, variants

Panel type Rated current Ir1 [A]

Panel width A

[mm]

Depth2 [mm]

Depth3

[mm]

Approx. weight [kg]4

12 Metering panel for volt-

age transformer ≤ 2500 600 1700 24006/25007 400

12 attached busbar earth-

ing switch ≤ 2500 600 1700 2400/2780 400

attached voltage transformer for outgoing feeder cable / busbar + 120 (3 x 40)

1 In the case of feeder panels, the rated current Ir refers to the feeder (max. busbar nominal current: 2500 A).2 The values listed in the Tables are referred to a panel depth without pressure relief duct on the rear. Technicaldetailsandthedesignfortherearpressurereliefductmustbeclarifiedwiththemanufacturerasrequired.3 –Dampingresistor(foroptionalvoltagetransformer)onthelow-voltagecabinet:specifiedheight+150 – Height of pressure relief duct: 2400 – Height of pressure relief duct with fan: 26004 Thespecifiedweightsapplyincludingthelow-voltagecabinetandwithoutthevoltagetransformer;theyrefertofeederpan-

els with outer cone-type bushing. - Feeder panels with inner cone-type socket: max. + 200 kg

– Panels with rear pressure relief duct: max. + 150 kg5 The dimensions depend on the cable connection system; inner cone-type socket / outer cone-type bushing6 Voltage transformer can be removed by pulling it laterally (see Fig. 12, page 12)7 Voltage transformer can be removed by pulling it upwards

Page 16: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

16 AGS 531 446-01 | Edition 04/201416

2 Design, description, variants

1340/13803

15954

2380

/278

01

2400

A

2100

- 23

00

+150 +20056

1 with low-voltage cabinet 800/1200 mm

2 Height depends on the busbar cooler attachments

3 Panel depth depending on rated current Ir of the panel (without/with cooler, see Table)

4 Depth of panel with pressure relief duct

5 Damping resistor6 Fan attachment

Fig. 14Dimensions of a series GHA single busbar panel

2100

- 23

00

2380

/278

01

1700/1960

19906/22107

A

2400

+150 +2005 4

1 with low-voltage cabinet 800/1200 mm

2 Height depends on the busbar cooler attachments

3 Panel depth depending on rated current Ir of the panel (see Table)

4 Damping resistor5 Fan attachment6 Depth of panel with pressure relief

duct 7 Depth of panel with pressure relief

duct and bus section coupler of the rear busbars (Ir = 2500 A)

Fig. 15Dimensions of a series GHA double busbar panel

Page 17: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

17AGS 531 446-01 | Edition 04/2014 17

2 Design, description, variants

2.4 Applicable standards

metal-enclosed SF6-insulated type-tested and prefabricated testedforinternalfaults(qualificationIAC) dimensioned for indoor installation

Designation Standards

Switchgear IEC 62271-1 IEC 62271-200

Circuit-breaker IEC 62271-100Earthing switch IEC 62271-102Disconnector IEC 62271-102Current transformer IEC 61869-2Voltage transformer IEC 61869-3Voltage detection systems IEC 61243-5Protection against accidental contact, foreign bodies and water IEC 60529Installation IEC 61936-1Operation of electrical equipment EN 50110-11

InsulatinggassulphurhexafluorideSF6 IEC 60376 Useandhandlingofsulphurhexafluoride(SF6) IEC 62271-303

1 The national standards applicable in the country where the equipment is to be installed must be complied with.

Degrees of protection against accidental contact and foreign objects accord-ing to IEC 60529Main electric circuits IP65

Drive mechanisms IP2X1

Low-voltage cabinet IP3X1

Cable compartment IP3X1

1 optional IP5X

2.5 Environmental and operating conditions

GHA is an indoor switchgear and may only be operated under normal conditions in acc. with IEC 62271-1. Operation under conditions deviating from these is only admissible subject to consultation with and written approval from the manufacturer.

Ambient conditions (in accordance with IEC 62271-1)

Temperature class "Minus 5 indoors”

Min./max. ambient temperature °C –51/+401

Average value over 24 hours °C ≤ 351

mean rel. air humidity: 24 hour/1 month % ≤ 95/≤ 90Installation altitude above sea-level m ≤ 10001

1 other values available on request

Type GHA switchgear units are:

GHA switchgear units meet the following standards and regulations:

Degree of protection against accidental contact and foreign objects:

Page 18: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

18 AGS 531 446-01 | Edition 04/201418

2 Design, description, variants

2.6 Intended use

Gas-insulated GHA medium-voltage switchgear units are exclusively intended for switching and distributing electrical energies. They may only be used in the scope of thespecifiedstandardsandtheswitchgear-specifictechnicaldata.Anyotherutiliza-tion constitutes improper use and may result in dangers and damage.

The manufacturer shall not be held responsible for damage which occurs if instructions in this Technical Manual are not complied with; the switchgear is not operated according to its intended use (see above); the switchgear is assembled, connected or operated improperly; accessories or spare parts are used which have not been approved by the

manufacturer; the switchgear is converted without the manufacturer’s approval, or if inadmis-

sible parts are added.No liability is accepted for parts provided by customers, e.g. current transformers.

2.7 Disposal after the end of service life

TheoperatingequipmentcontainsthefluorinatedgreenhousegasSF6 covered by the Kyoto Protocol with a global warming potential (GWP) of 22 200.SF6 must be recovered and must not be released into the atmosphere. When trans-porting and handling SF6,thespecificationsinIEC62271High-VoltageSwitchgearandControlgear–Part303UseandHandlingofSulphurHexafluoride(SF6), must be complied with.A material and recycling data sheet can be provided on request for the disposal of series GHA switchgear units at the end of their service life.Disposal is performed as a service by the manufacturer’s Service Center and is subject to a fee.

Liability Disclaimers

Page 19: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

19AGS 531 446-01 | Edition 04/2014

3 Packaging, transport, storage

3.1 Shipping units

Delivery is effected in terms of prefabricated single switchgear panels. One transport unit consists of max. 2 individual switchgear panels which are fastened to the pallet. The busbar compartment with three-position switch, the circuit-breaker compart-ment, the drive mechanisms and the supporting structures are mounted ready for connection and routine-tested. The individual busbar links are mounted on site. The low-voltage cabinets are assembled in the factory or supplied as accessories, depending on the customer’s wishes.

If packed exclusively for truck transport, the panels are delivered on a pallet withPEprotectivefilm.

For sea transport, the units are packed in sealed aluminium foil with desiccant and in a closed wooden case with tightly closed wooden base (also for con-tainer transport).

In case of air transport, the panels are packaged in wooden crates with a protectivePEfilmhood(dustprotection)orinwoodencrates,alsowithclosedwooden bases, however without protective hoods (dust protection).

Notice:The weight of the entire transport unit is indicated on the packaging.

3.2 Transport

Warning!Danger due to tipping load.

Transport units must be protected sufficiently against slipping and tipping during transport.

Warning!Sufficient stability and evenness of the supporting area (floor) must be ensured.

Handle shipping units carefully when unloading and unpacking them Shipping units must be checked upon receipt. Any damage which may have

occurred in transit must be recorded and reported to the manufacturer immedi-ately.

The consignment must be checked for completeness based on the shipping documents.

Thesuppliermustbenotifiedinwritingwithoutdelayaboutanypossibledevia-tions.

Packaging

Abb. 16Do not tip the transport units

Transport using a forklift truck

Page 20: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

20 AGS 531 446-01 | Edition 04/201420

3 Packaging, transport, storage

The panel may only be transported on a pallet. The entire length of the forks must be placed under the transport unit (Fig. 17).

Fig. 17Transport with forklift truck

3.3 Storage

Warning!Sufficient stability and evenness of the supporting area (floor) must be ensured.

If the panels are not installed immediately after delivery, they can be stored under the following conditions:

Panels must be stored in vertical position, and must not be stacked. Storage only admissible indoors Panels and accessories must be packed in a wooden crate with a dessicant

and sealed in aluminium foil (storage period max. 2 years after date of packaging).

– 5 ºC

+ 40 ºC

Fig. 18Diagram showing the storage conditions

Page 21: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

21AGS 531 446-01 | Edition 04/2014

4 Assembly

4.1 Safety provisions

The switchgear panels may only be installed and assembled by the manufacturer’s stafforbypersonswhohavebeencertifiedforthiswork.The GHA series switchgear panels are delivered with the circuit-breaker set to “OFF”, the energy storing device released and the disconnector and earthing switch set to “OFF”.

Warning!Risk of injury due to movable parts in the mechanical drive. The energy storing device of the circuit-breakers and the earthing switches must not be charged during assembly.

Warning!Risk of accidents! Watch out for floor openings in the switchgear room.

Danger!Danger due to insufficient dielectric strength of high-voltage con-nections in case of assembly under aggravated ambient condi-tions. During assembly of the busbar link and the high-voltage connections, it is essential to avoid condensation, dirt and dust deposits. At the time of installation, the ambient temperature must amount to ≥ 10 °C.

Warning!The top sides of the panels are not meant to be walked on. Per-sons may fall through them, get injured or may damage the panel. When work has to be performed on the panel top - e.g. assembly of deflectors, fans or pressure relief ducts - temporarily position a solid mounting rack to step on.

Warning!Risk of injury due to non-respect of the safety provisions in Chap-ter 1, on page 7.

4.2 Important instructions for assembly

Notice: Switchgear with pressure relief duct (see Chapter 8, as of page

67): The pressure relief duct must be mounted before the panel is positioned on the base frame.

Condensation, dirt and dust should be avoided during assembly on all accounts, in order to prevent damage to the panels.

For assembly, observe the assembly drawings supplied with the equipment. Read them before you commence assembly work. The drawing numbers are specified in this manual under the de-scription of the assembly work in question.

For all screw connections, refer to the tightening torques specified in the Annex.

The transport securing device on the busbars must not be re-moved before assembly of the busbar link acc. to Chapter 4.7 on page 32.

Page 22: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

22 AGS 531 446-01 | Edition 04/201422

4 Assembly

4.3 Requirements regarding the switchgear room

Notice:Before installing the switchgear panels, make sure that the switchgear room is checked according to the customer-specific switchgear docu-mentation.

Observe the minimum distance between the switchgear and the wall of the building.

The load-bearing capacity of the fastening areas must correspond to the weight of the switchgear (perform a stress analysis of the building).

Check base frame for dimensions and tolerances in position. Checkpositionofflooropeningsforhigh-voltageandlow-voltagecables.

Before the switchgear is positioned at its site of installation, check that the base frame dimensions are precisely correct.

– Flatness: ±1 mm/meter – Straightness: ±1 mm/meter – Parallelism: ±1 mm/meter – Height difference over the entire length of the switchgear: ±2 mm

Design data of GHA switchgear: Examples for various switchgear panel variants

500

1194

41

180 600/800 600/800

5050

7

2

50

6

8

14

2 3

50

900800

900800

100

460/660 660

175

35

5

Fig. 19Location of base frame and ceiling ducts (example: double busbar switchgear)1 Rear gap cover2 Steel base frame3 Ceiling duct for high-voltage connections4 Wall of building5 Possible cross-bracings 6 Cooler attachments7 Side wall8 Side wall extension for double busbar switchgear

Page 23: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

23AGS 531 446-01 | Edition 04/2014 23

4 Assembly

≥100

≥1700

1000

1340

2400/2780

Fig. 20Example of panels with single busbar in the switchgear room

≥500 ≥2100

1000

2380/2780

1700

Fig. 21Example of panels with double busbar in the switchgear room

Page 24: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

24 AGS 531 446-01 | Edition 04/201424

4 Assembly

≥5001 ≥17001595

1000

2400

Fig. 22Example of panels with single busbar and pressure relief duct in the switchgear room 1Switchgearaccessiblefromtherear:≥800

≥5001 ≥21001990

1000

2400

Fig. 23Example of panels with double busbar and pressure relief duct in the switchgear room 1Switchgearaccessiblefromtherear:≥800

Page 25: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

25AGS 531 446-01 | Edition 04/2014 25

4 Assembly

4.4 Transporting the panels on the construction site

Warning!Make sure the rope or chain is strong enough to bear the weight of the panel and the trucks. Comply with the relevant provisions for hoisting equipment.

Warning!On lowering the panels, make sure that the supporting platform is sufficiently stable and even.

Warning!Risk of tipping over. During transport, pay attention to the weight distribution. The center of gravity is at gas tank level in the upper part of the switchgear panel. Never move panels without using transport aids.

Warning!Risk of accidents. Pay attention to floor openings!

4.4.1 Transport of panel by means of a crane1. Removetransportpackaging(protectivefilms).2. Attach rope/chains to the jack rings located on the busbar tank (Fig. 24).

Notice:The ropes must have the following minimum lengths: L ≥ 900 mm

3. Release transport fastening device of the panel from the transport pallet (Fig. 24, item 1).

4. Lift the panel carefully with the crane.5. If necessary, mount transport rollers (Fig. 26). Description of assembly, see

following page.6. Lowerthepanelslowlytotheflooratitsplaceofdestination.

1

L ≥ 900

Fig. 24When lifting, make sure that at least the minimum rope length L is used.1 Transport fastening

1

Fig. 25Panels with cooler and busbar attach-ments1 Use an additional frame for crane

transport.

Fig. 26Mounting the transport rollers (see Chap. 4.4.2, page 26)

Page 26: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

26 AGS 531 446-01 | Edition 04/201426

4 Assembly

4.4.2 Transport using the transport frameFortransportonthefloor,aframemustbemountedtotheleftandrightoftheswitchgear panel (not included in scope of supplies).

1. Insert locating pins of transport frame into the lateral bore-holes in the support-ing structure of the switchgear panel, and secure them by means of the two knurled screws (Fig. 27, item 2).

2. Actuate front toggle lever (3) to its stop in the direction of the arrow. Press the button on the rear lifting device (4) and actuate lever to its stop in the direction of the arrow till it reaches its stop.

3. The panel is lifted.

1 2

3 4

5

Fig. 27Mounting the transport rollers1 Transport frame2 Knurled screws3 Front toggle lever4 Rear lifting device with push-button5 Switchgear panel

Thesepanelsaredeliveredfromthefactorywithadditionalsupportingprofilesmounted.Thesupportingprofilesmustnotberemovedduringassembly.Fortransportonthefloor,thetransportrollersmustbesecuredtothesupportingprofilestotheleftandrightofthesupportsprovidedtothiseffect(Fig. 28).Removeasupportingprofilebeforescrew-fasteningthepaneltoanadjacentpanel.Asupportingprofile-left-handorright-hand-mustalwaysbeleftmountedtothepanel as long as the panel is not screw-fastened to the adjacent panel. Remove sup-portingprofileafterhavingscrew-fastenedthepanels.

Fig. 28Panelwithpre-assembledsupportingprofilesandattachedtransportrollers

Assembly

Panels with center of gravity located in the rear part (e. g. single busbar panel with bus section coupler on the rear busbar)

Page 27: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

27AGS 531 446-01 | Edition 04/2014 27

4 Assembly

4.4.3 Transporting the panels onto the base frame1. PlacetwoUprofiles(notincludedinscopeofsupplies)onthebaseframeas

traversing aid and block them by (lower) stops against slipping in the base frame (Fig. 29, item 1).

2. AdjustthedistancebetweenthetwoUprofilesinaccordancewiththepanelwidth. When positioning the panels, make sure that the transport rollers are locatedintheUprofiles.

3. Move panel onto the base frame, align front edge (see space assignment plan) and lower the panel.

4. RemovetransportrollersandUprofiles.

1

2 3

Fig. 29Moving the panel on the base frame1 Uprofileswithstopedgesastraversingaid2 Transport frame3 Switchgear panel

Page 28: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

28 AGS 531 446-01 | Edition 04/201428

4 Assembly

4.5 Attachment of pressure relief duct

Switchgear units are provided with pressure relief duct, if the following is required: Accessibilityinacc.withIEC62271-200:QualificationIACAFLR(accessibility

from all sides) and/or QualificationIACAFL(R)internalarc40kA/1s

Notice:The pre-assembled pressure relief duct supplied with the equipment must be mounted before the panel is positioned on the base frame. After installation of the panels, mounting may no longer be possible in part.

L

2

L

3

Fig. 30Switchgear panel with single busbar and pressure relief duct

Fig. 31Switchgear panel with double busbar and pressure relief duct

The attachment of the pressure relief duct is described in the assembly drawing in question:

Panel width [mm]

Busbar system

Pressure relief from the switchgear room with customized duct

Pressure relief into the switchgear room

for fan attach-ment

TrSS SS-Stw 600 800 900 1000

Sin-gle

bus-bar

Dou-ble

bus-bar

Internal arc qualification IAC AFLR, ≤25 kA/1 s

Internal arc qualification IAC AFLR, ≤40 kA/1 s

AGS002105-02 AGS003379-012

AGS002105-04 AGS002105-04 AGS002105-06 AGS002105-06 AGS002105-151

AGS002105-07 AGS002105-07 AGS002105-161

AGS003216-01 AGS003216-01 AGS002105-08 AGS003379-08

AGS002105-10 AGS002105-10 AGS002105-12 AGS002105-12

AGS002105-14 AGS002105-14 AGS003216-02 AGS003216-02

AGS002105-08 AGS002105-08 AGS002105-183

1 Optional fan attachment2 only to be used for panels without busbar top structure, in this case AGS002105-02 3 only in case of Ir = 2500 A

Page 29: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

29AGS 531 446-01 | Edition 04/2014 29

4 Assembly

4.6 Remove cable compartment cover and shutters4.6.1 Cable compartment interlock (optional)An additional interlock prevents the cable compartment cover from being removed if the earthing switch is not switched ON.1. Charge spring mechanism of the circuit-breaker (Fig. 32, item 3). Earth the

outgoing feeder cable (see Operating Manual).2. Push interlocking slide of cable compartment cover (2) upwards.At the same time, the cable compartment cover is unlocked and actuation of the earthing switch (1) interrupted mechanically and electrically.

Notice:After removing the cable compartment cover, it is impossible to push the slide (Fig. 32, item 2) down. The earthing switch remains locked.

1

2

3

00346

Fig. 32Unlock/lock cable compartment cover1 Insertion opening for manual actuation of the earthing switch2 Slide for locking/unlocking the cable compartment cover3 Charge the spring mechanism of the circuit-breaker drive manually (as long no

supply voltage is applied).

Interlocking matrix Earthing switch Cable compartment cover

Cable compart-ment cover

screw-fastened unlocked –

removed locked –

Earthing switchON – unlockedOFF – locked

After assembly of the cable compartment cover, press interlocking slide (Fig. 32, item 2) down. The earthing switch (1) can be switched off mechanically and electrically.

Unlocking the cable compartment cover

Locking the cable compartment cover

Page 30: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

30 AGS 531 446-01 | Edition 04/201430

4 Assembly

4.6.2 Remove cable compartment cover and shutters

Notice:Store screws, bolts and shutters carefully for subsequent reuse.

1. Open front frame: – Operating shutter without inspection glass:

Release the two securing bolts (Fig. 33, item 1). – Operating shutter with inspection glass:

Open interlocking mechanism using the double-bit key (Fig. 34, item 2).Then, open the front frame by swinging it to the left.

2. Unscrew the two securing bolts from the cable compartment cover (3).3. First pull the cable compartment cover up, then forwards to remove it.

1

1

3

4

Fig. 33Operating shutter without inspection glass1 Securing bolts of the front panel3 Securing bolts of cable compart-

ment cover4 Hinged front frame

3

4

2

Fig. 34Operating shutter with inspection glass2 Lock and double-bit key3 Securing bolts of cable compart-

ment cover4 Hinged front frame

Removing cable compartment cover

Page 31: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

31AGS 531 446-01 | Edition 04/2014 31

4 Assembly

Notice:Identify panel in accordance with the nameplate on the operating shut-ter to avoid confusion.

1. Release screw connection of the operating shutter (Fig. 35, item 5) from the 4 fastening points and remove shutter

2. Release the fastening of the two lateral covers (4) of the right-hand cable tray and remove covers.

1 2

34

5

Fig. 35Removal of shutters1 Hinged front frame2 Operating shutter3 Cable compartment cover4 Cable tray cover5 Screw connection of operating shutter (4 x)

Unscrewing the shutters

Page 32: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

32 AGS 531 446-01 | Edition 04/201432

4 Assembly

4.7 Installation of panels

4.7.1 Installation of the first switchgear panel

Notice:The position of the first panel is decisive for placement of the subse-quent panels, thus it is essential that measuring is effected with the utmost precision!

1. Placethepanelonthebaseframeaccordingtotheswitchgear-specificspaceassignment plan (see Chapter 4.4.3, page 27).

2. Align panel. Check the panel front for correct horizontal and vertical position. If applicable, lift the panel and place shims in the direct vicinity of the fastening areas, until the horizontal position has been reached.

3. Positionthefollowingpanelonthebaseframenexttothefirstpanelaccordingtotheswitchgear-specificspaceassignmentplan.

4. Remove shutters from the panels as described in Chapter 4.6 as of page 29.

4.7.2 Removal of transport securing deviceRemove transport securing device above the high-quality electrical joints of the busbar link.

– Remove plastic cover from the busbar bushing (Fig. 36). – The plastic hood above the silicone sleeve is attached laterally and on top of

the retaining clip (Fig. 37). Remove plastic hood carefully applying little force only.

Fig. 36Plastic cover on the busbar bushing

Fig. 37Plastic hood above the silicone sleeve

Page 33: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

33AGS 531 446-01 | Edition 04/2014 33

4 Assembly

4.7.3 Pre-coat the high-quality electrical joints of the busbar link

Notice: Make sure the high-quality electrical joints are absolutely clean. Special grease (art. no. AGS 003371-01) and the sponge element

(art. no. S 065969) are either included in the scope of supplies or must be purchased separately, depending on the agreement concluded. In case of doubt, please contact the manufacturer as required.

1. Clean the high-quality electrical joints of the busbar link (Fig. 40) using white spirit(art.no.S009002)andalint-freecloth(alsomicro-fibrecloths).

2. For each side of a high-quality electrical joint, press a length of approx. 10 mm substance out of the tube and apply it using the sponge element (Fig. 40). In the beginning, apply slightly more (approx. 15 mm), as the sponge also absorbs grease. Onetube(90g)issufficientforapprox.36completehigh-qualityelectricaljoints(72 high-quality joint surfaces).

Abb. 38Special grease (art. no. AGS 003371-01)

Abb. 39Sponge element (art. no. S 065969)

10-15

1

Fig. 40High-quality electrical joint at the bus-bar bushing1 Make sure that the inner diameter

is greased thoroughly!

10-15

1

Fig. 41High-quality electrical joint on the sili-cone sleeve1 Make sure the electrode ring is

clean!

3. Usethespongeelementtospreadauniformthinfilmofthethespecialgreaseover the entire surface. Blank spots not covered by grease should be avoided on all accounts. Once treated, do not touch the surfaces of the high-quality electrical joints any longer.

Notice: Busbar bushing (Fig. 40): Check especially the inner diameter

of the high-quality electrical joint for non-greased areas and, if necessary, re-coat.

Check the electrode ring in the silicone sleeve (Fig. 41, item 1) for cleanness and the absence of grease and, if necessary, clean.

Apply special grease and spread it uniformly by means of the sponge element.

Page 34: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

34 AGS 531 446-01 | Edition 04/201434

4 Assembly

4.7.4 Preassembling the clamping contacts1. The following factory setting of the clamping contacts (Fig. 42) must be checked

prior to assembly: Turn the two screws until the two clamping contacts are in loose contact, then turn the screws back by a half turn of the thread.

2. Clean and grease busbar contact surfaces and contact points on the clamping contact (see Chapter 13.3, page 92).

3. Carefully slip the clamping contacts into the busbar tubes of the left-hand panel.

3 2

1

Fig. 421 Check the clamping contact screws.2 Clean and grease the contact surfaces3 Insert the contact tips

Page 35: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

35AGS 531 446-01 | Edition 04/2014 35

4 Assembly

4.7.5 Screw-fastening the panels to one another1. Push panels carefully together. Clearance between busbar tanks: 153 ± 2 mm

(Fig. 43, item 1).2. Connect panels to one another

(assembly drawing AGS 000913-01): – front panel screw connection:

9 x self-locking screw M8 to its stop (Fig. 43, item 3). Panels with a width of 900 or 1000 mm are screw-fastened using compen-sating shutters (see Chapter 4.8, page 36).

– rear panel screw connection: Screw-fasten connecting link to the jack ring plate 2 x self-locking screw connection M8 (Fig. 43, item 2).

Panel types Pressure relief duct Mat. no.without with

All panel variants, except busbar current transformers

AGS000913-03 AGS000913-01

Busbar current transformer AGS000913-02

AGS000913-05

3

2

1

9x

153±2

2

Fig. 43Screw-fastening the panels to one another1 Check setting 153 ± 2; measuring location: Edge shown on the busbar tank2 Rear panel screw connection: fasten connecting link3 Screw-fasten panels on the front.

Page 36: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

36 AGS 531 446-01 | Edition 04/201436

4 Assembly

4.8 Compensating shutters for the panel front

Compensating shutters are only required for panels with a width of 900/1000 mm (seealsoswitchgear-specificdocumentation),panelswithawidthof600/800mmdonot require compensating shutters in-between each other. The shutters are always supplied in preassembled condition as accessories. The compensating shutter vari-ants are subdivided in accordance with the following dependencies:

– Height of low-voltage cabinet 800 mm or 1200 mm – Nominal width of compensating shutter 50 mm or 100 mm, depending on panel

arrangement (see Table)

Panel with panel width [mm]

Panel width, adjacent panel (left-hand or right-hand)

[mm]

Rated width, compensating shutter (left-hand or right-

hand) [mm]

900/1000600/800 50

900/1000 100

A

1

2

3

4

5

50 100

4 4 1/23/5

900/1000

A

Fig. 44Compensating shutters in the panel front1 Upper compensating shutter, width

100 mm 2 Lower compensating shutter, width

100 mm

3 Lower compensating shutter, width 50 mm

4 Screw connection M8 (12 x per shutter)

5 Upper compensating shutter, width 50 mm

Required nominal width of the compensating shutter depending on the panel arrangement:

Page 37: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

37AGS 531 446-01 | Edition 04/2014 37

4 Assembly

In-line panel, left-hand

Panel width

LV cabinet height End panel, left-hand

600/800 mm

In-line panel, right-hand

Panel width800 1200

not required 600/800 AGS003372-01

900/1000 AGS003372-02

In-line panel, left-hand

Panel width

LV cabinet height End panel, left-hand

900/1000 mm

In-line panel, right-hand

Panel width800 1200

AGS003372-01600/800/900/1000

AGS003372-02In-line panel, left-

hand Panel width

LV cabinet height Center panel 600/800 mm

In-line panel, right-hand

Panel width800 1200

600/800 not required 600/800 AGS003372-01

900/1000 AGS003372-02

900/1000

AGS003374-01600/800

AGS003374-02

AGS003372-01 +AGS003374-01

900/1000 AGS003372-02

+AGS003374-02In-line panel, left-

hand Panel width

LV cabinet height Center panel 900/1000 mm

In-line panel, right-hand

Panel width800 1200

600/800/900/1000 AGS003372-01

+AGS003374-01600/800/900/1000

AGS003372-02 +AGS003374-02

In-line panel, left-hand

Panel width

LV cabinet height End panel, right-hand

600/800 mm

In-line panel, right-hand

Panel width800 1200

600/800 not required

900/1000 AGS003374-01

AGS003374-02In-line panel, left-

hand Panel width

LV cabinet height End panel, right-hand 900/1000

mm

In-line panel, right-hand

Panel width800 1200

600/800/900/1000 AGS003374-01

AGS003374-02In-line panel, left-

hand Panel width

LV cabinet height End panel, left-hand

900 mm

In-line panel, right-hand

Panel width800 1200

AGS002596-01600/800

AGS002596-02 AGS002597-01

900/1000 AGS002597-02

Front compensating shutter, attachment to panel

Page 38: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

38 AGS 531 446-01 | Edition 04/201438

4 Assembly

In-line panel, left-hand

Panel width

LV cabinet height Center panel 900/1000 mm

In-line panel, right-hand

Panel width800 1200

600/800

AGS002598-01600/800

AGS002598-02 AGS002599-01

900/1000 AGS002599-02

900/1000

AGS002596-01600/800

AGS002596-02 AGS002597-01

900/1000 AGS002597-02

In-line panel, left-hand

Panel width

LV cabinet height End panel, right-hand 900 mm

In-line panel, right-hand

Panel width800 1200

600/800 AGS002600-01

AGS002600-02900/1000 not required

Front compensating shutter, attachment to panel

Page 39: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

39AGS 531 446-01 | Edition 04/2014 39

4 Assembly

4.9 Busbar link: B link

L1

L2

L3

L1L2

L3

SS1

SS2

Fig. 45Overview of designations for busbars and phase angle– Upper busbar = SS2 – Rear busbar = SS1

1 2 3 4 5 67Fig. 46

Overview of busbar link1 Busbar support with high-quality

electrical joint2 Busbar3 Spacer pin

4 Retaining clip5 Busbar clamping contacts6 Silicone sleeve with securing

half-shells

Detail drawing of a B-link

Page 40: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

40 AGS 531 446-01 | Edition 04/201440

4 Assembly

4.9.1 Press silicone sleeve back

Fig. 47Tool for compressing the silicone sleeve - fork

Fig. 48Tool for compressing the silicone sleeve (alternative) - claw fastener

To get access to the pre-assembled clamping contacts and to complete the busbar link, it is necessary to press the silicone sleeve back.To this effect, only the auxiliary equipment approved by the manufacturer may be used, e.g. the fork Fig. 47 and the claw fastener Fig. 48.Position the tool according to the illustration and press the silicone sleeve back.Relieve the silicone sleeve. To do so, slowly release the silicone sleeve using the tool being used, and remove the tool.

Notice:Switchgear units with fan are equipped with a current transformer on the busbar link for fan control. Before mounting the busbar link, refer to Chapter 4.9.6, page 47.

Tool for pressing the silicone sleeve back (see also Annex, Chapter 13.2, page 85)

Page 41: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

41AGS 531 446-01 | Edition 04/2014 41

4 Assembly

4.9.2 Connecting the busbar (fasten preassembled clamping contacts)

Notice:The two lugs of the upper clamping contact must be located between the busbar tubes.

Assembly drawing for single and double busbar: AGS 002 268-011. Position the preassembled clamping contacts (see Chapter 4.7.4, page 34) acc.

to Fig. 49, item 2. The two lugs of the upper clamping contact must be located between the busbar tubes (see Fig. 49, item 4).

2. Tighten the clamped connection with a torque of 8 ± 1 Nm.3. Aftertighteningtheclampedconnectionapplyingthespecifiedtorque,remove

theredfilmfromthesandwichlabel(5).Agreenstripeappearswhichindicatesthat the busbar link has been established correctly.

1

8 ± 1 Nm

0-3 mm

2

3

4

5 4

Fig. 49Busbar link1 Tool2 Clamping contacts3 Busbar4 Locating lugs5 Sandwich label

Page 42: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

42 AGS 531 446-01 | Edition 04/201442

4 Assembly

4.9.3 Contact resistance measurement of busbar screw fastening

Notice:Comply with the manufacturer’s specifications regarding the contact resistance measuring unit.

1. Set the feeder panel for resistance measurement in testing position (A) (Fig. 50): Switch disconnector and circuit-breaker ON, refer also to operating manual.

2. Connect the clip-on ammeter probes of the contact resistance measuring unit to the high-voltage cable connection in the right-hand panel (B). Illustrated: Outer cone-type bushing. Use suitable current probes for the inner cone-type bushing.

3. On the lined-up panel, connect clip-on ammeter probes of the contact resis-tance measuring unit to the busbar tube by means of inner cone-type current probes (C).

4. Apply test current 100 A DC (D).5. Measure contact resistance R between the busbar tube and the lug of the

clampingcontact(E).SetvalueR:≤5μΩ. Ifthemeasuredvalueexceedsthespecifiedvalue:

– Undo busbar screw fastening. – Clean contact surfaces carefully and repeat the mounting and measuring

procedure.In this way, check the contact resistance of all phases between all panels.

100 A DC

00243

C

D

E A

B

R ≤ 5 µΩ

Fig. 50Contact resistance measurement

Page 43: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

43AGS 531 446-01 | Edition 04/2014 43

4 Assembly

4.9.4 Fasten silicone sleeve to adjacent panel

Notice:Check pre-coated high-quality electrical joints again for absolute clean-ness. The surfaces of the high-quality electrical joint must be coated com-pletely and uniformly with a thin layer of special grease. Check high-quality electrical joints for non-greased areas and, if neces-sary, coat again, see Chapter 4.7.3, page 33.

6. Relieve the silicone sleeve. To do so, slowly release the silicone sleeve using the tool being used, and remove the tool.

7. Clean spacer pins (accessories, Fig. 46, item 3, page 39) and welding studs and coat them with a screw locking compound (see Chapter 13.3, page 92). Screw-fasten spacer pin onto the welding studs.

8. Slip retaining clip onto the two pins. The sides of the retaining clip must butt against the retaining lugs of the securing half-shells. Subsequently, position the cage with the cup springs and fasten retaining clip by means of a M8 self-locking nut. The surfaces of the high-quality electrical joint must be compressed by the retaining clip.

1

(10 ± 1,5 Nm)

23

4(12 ± 1,5 Nm)

Fig. 51Fastening the silicone sleeve to the adjacent panel1 Spacer pin2 Retaining clip3 Cup spring package4 Nut

Checking high-quality electrical joints

Mounting the retaining clips

Page 44: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

44 AGS 531 446-01 | Edition 04/201444

4 Assembly

4.9.5 Cover of busbar link in case of panels without pressure relief duct

Panel width, adja-cent panel, left-hand

[mm]

Panel width [mm]

Assembly drawing

Single busbar Double busbar

600/800 600 AGS003202-01 AGS003202-02600/800 800 AGS003202-01 AGS003203-02

900/1000 600/800 AGS003204-01 AGS003204-02600/800 900 AGS003205-01 AGS003205-02

900/1000 900 AGS003206-01 AGS003206-02600/800 1000 AGS002609-02 AGS003205-02

900/1000 1000 AGS002610-02 AGS003206-02SS-StW 600/800 AGS003215-03 AGS003215-07SS-StW 900 AGS003215-04 AGS003215-08600/800 SS-StW AGS003215-01 AGS003215-05

900 SS-StW AGS003215-02 AGS003215-06

1

2

Fig. 52Cover of busbar link1 Cover of upper busbar link2 Cover of rear busbar link

Page 45: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

45AGS 531 446-01 | Edition 04/2014 45

4 Assembly

Cover of busbar link in case of panels with pressure relief duct

Fig. 53Cover of busbar link in case of panels with pressure relief duct

Panel width [mm]

adjacent panel, right-hand Panel width

[mm]

Busbar sys-tem

Mat. no.

SS-Stw 600 800 900 1000 SS-Stw 600 800 900 1000Single bus-bar

Dou-ble

bus-bar

AGS002115-05 AGS002115-03 AGS003217-01

AGS002115-04 AGS002115-06 AGS003217-02

AGS002115-06 AGS002115-02 AGS002115-07 AGS003217-05

AGS002115-08 AGS002115-09 AGS003217-06

AGS003217-03 AGS003217-04 AGS003217-07 AGS003217-08 AGS003217-09 AGS003217-10

AGS002115-10 AGS002115-11H O AGS002115-14

O = Bus section coupler with upper busbar separation (SS2) H = Bus section coupler with rear busbar separation (SS1)

Page 46: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

46 AGS 531 446-01 | Edition 04/201446

4 Assembly

Panel width [mm]

adjacent panel, right-hand

Panel width [mm]

Busbar system

LV cabinet Height [mm]

Cover Pressure

relief device

Cover SS (to the right-hand

adjacent panel)

Cover LV cabinet

SS-S

tw

600

800

900

1000

SS-S

tw

600

800

900

1000

Sing

le b

usba

r

Dou

ble

busb

ar

800

1200

AGS002113-01 AGS003386-03 - AGS002113-03 AGS003386-01 AGS003416-02 AGS002113-03 AGS003386-01 AGS003416-04 - - -

AGS002113-03 AGS003386-02 AGS003416-02 AGS002113-03 AGS003386-02 AGS003416-04 AGS002113-04 AGS003386-05 AGS003416-03 AGS002113-04 AGS003386-05 AGS003416-05 - - AGS003416-02 - - AGS003416-04

AGS002113-04 AGS003386-05 AGS003416-03 AGS002113-04 AGS003386-05 AGS003416-05

AGS002113-02 AGS003386-03 - AGS002113-05 AGS003386-01 AGS003416-02 AGS002113-05 AGS003386-01 AGS003416-04

AGS002113-05 AGS003386-02 AGS003416-02 AGS002113-05 AGS003386-02 AGS003416-04 AGS002113-06 AGS003386-05 AGS003416-03 AGS002113-06 AGS003386-05 AGS003416-05

- - - - - AGS003416-02 - - AGS003416-04

- - AGS003416-02 - - AGS003416-04

- - AGS003416-02 - - AGS003416-04 - - AGS003416-03 - - AGS003416-05

Page 47: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

47AGS 531 446-01 | Edition 04/2014 47

4 Assembly

4.9.6 Current transformer on the busbar for fan control

To control fans for disconnectors on the busbar, a toroidal-core current transformer is factory-mounted for each busbar; this transformer is positioned as follows:Single busbar: an der hinteren Phase (on the rear phase (normally designated as L3)Double busbar: Upper busbar (SS2): on the rear phase (L3) Rear busbar (SS1): on the upper phase (L1)

1

2

3

4

3 4

Fig. 54The illustration shows a panel in double-busbar design.The busbar curent transformer is mounted to the single busbar panel in analogy to the upper busbar.1 Busbar current transformer SS22 Busbar current transformer SS13 Silicone sleeve4 Retaining plate for current transformer

Description and variants overview

Page 48: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

48 AGS 531 446-01 | Edition 04/201448

4 Assembly

1

2

3

4

5 6

7

Fig. 551 Retaining clip2 Securing half-shells, rear3 Current transformer4 Securing half-shells, front

5 Silicone sleeve 6 Retaining plate for current trans-

former7 Wiring of current transformer

Toensurethatthesiliconesleevecanbepressedbacksufficientlyduringbusbaras-sembly, the current transformer must be disconnected and displaced previously. The current transformer as such must not be disassembled.

1. Unscrew the retaining clip of the B link (Fig. 55, item 1).2. Remove the securing half-shells (item 2).3. Detach the current transformer from the retaining plate (item 6).4. Push the current transformer into the position of the removed securing half-

shells.5. Assemble the busbar link acc. to Chapter 4.9 as of page 39.6. After having completed the busbar link, push the current transformer back to its

initial position and re-fasten it to the retaining plate.

Mounting current transformers to the busbar for fan control

Assembly workflow for busbar link (B link)

Page 49: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

49AGS 531 446-01 | Edition 04/2014 49

4 Assembly

7. Remount the two securing half-shells (Fig. 56, item 2) to the silicone sleeve (3).

Notice:Make sure that the securing half-shells are positioned correctly! The bead of the silicone sleeve (Fig. 56, item 5) must be in the groove of the securing half-shell (8).

Comply with the tightening torque 12 ± 1.5 Nm for screw-fastening the securing half-shells.8. Push retaining clip (Fig. 56, item 1) onto the two bolts (6). The sides of the

retaining clip must butt against the retaining lugs of the securing half-shells.Subsequently, position the cup spring package (7) and secure it to the retaining clip using a self-locking nut M8 (6). The surfaces of the high-quality electrical joint must be compressed by the retaining clip.

1234

5

6

7

8

9

5

(12 + 1.5 Nm)

Fig. 56Re-fastening the silicone sleeve to the panel side from which it was previously detached 1 Retaining clip2 Securing half-shells, rear3 Silicone sleeve4 Securing half-shells, front5 Bead

6 Threaded pin M8 with self-locking nut M8

7 Spring cup package8 Groove of securing half-shell9 Hex. socket-head screw M8

Page 50: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

50 AGS 531 446-01 | Edition 04/201450

4 Assembly

4.10 Reinforcement

Required in case of internalarcstrengthacc.toIEC62271-200,qualificationIACAFL(R),internal

arc 40 kA/1 s Seismic design / vibration-resistance

Fan attachment

Panel width adjacent panel,

left-hand

Panel width

Assembly drawing

with-out

with Single busbar Double busbar

600/800 600 AGS003389-01 AGS003389-02 600/800 800 AGS003389-01 AGS003389-02 900/1000 600/800 AGS003389-03 AGS003389-04 600/800 900/1000 AGS003389-05 AGS003389-06 900 900 AGS003389-07 AGS003389-08 900 1000 AGS003389-09 AGS003389-10 1000 900 AGS003389-09 AGS003389-10 SS-StW 600/800 AGS003389-11 AGS003389-12 SS-StW 900 AGS003389-13 AGS003389-14 600/800 SS-StW AGS003389-15 AGS003389-16 900 SS-StW AGS003389-17 AGS003389-18

Fig. 57Reinforcements

Page 51: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

51AGS 531 446-01 | Edition 04/2014 51

4 Assembly

4.11 Screw-fastening the panel to the base frame

Notice:The switchgear panels may not be screw-fastened to the base frame before they have all been installed and adjusted.

Cut thread M8 in the base frame at the securing points provided to this effect (Fig. 58). To this effect, drill initial holes of Ø 6.8. Screw-fasten the panels 2 x each on the front and rear.

1 14

2 3

Fig. 58Fastening points in the base frame

If the rear fastening points are not accessible, e. g. due to voltage trans-formers, fastening links (Fig. 59) can be mounted.Screw-fasten both fastening links to the panel's supporting structure. Cut a thread M8 in the base frame on thespecifiedfasteningpoints.Tothiseffect, drill initial holes of Ø 6.8.

Panel width [mm]

Seismic design / vibration-resistance

Mat. no.

600 800 900 1000 without with AGS002206-01 AGS002206-02

AGS002206-03 AGS002206-04

The base frame must be designed in view of the seismic design. The panels are fastened to the base frame by means of screws M12.

Additional securing points (optional)

1

2

3

Fig. 59Rear fastening links1 Rear base frame2 Fastening link3 Screw connection

Page 52: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

52 AGS 531 446-01 | Edition 04/201452

4 Assembly

4.12 Mounting the earth bus

Notice:Observe the specific standards referring to earthing systems which ap-ply in the country in question.

1. Clean all contact areas of the connecting bar and the appropriate earth bar in the switchgear panels and coat them with lubricant (KL) (see Chapter 13.3, page 92).

2. Slip the connecting bar into the adjacent panel's supporting structure through the cutout in the panel.

3. Screw-fasten the connecting bar with the support brackets on both sides, to the earth bar in question and screw-fasten the support brackets to the panel.

4. Mount the connecting piece for switchgear earthing (Fig. 60, item 6). Connect the earth bus to the earthing system of the switchgear building. Connecting lines and screw accessories are not included in the scope of supplies. Connecting piece for switchgear earthing: AGS 000294-03 Panels with base plates: Observe Chapter 9.1, page 73.

The earth bus should be connected to the earth conductor of the building's earth connectionatleastatthefirstandateachtenthpaneloftheswitchgear.

Panel width [mm]

Panel width Adjacent panel

[mm]Assembly drawing

600 (also for end panel right-hand)600/800

AGS 000294-01

800 (also for end panel right-hand) AGS 000294-02600 900 AGS 000294-04

900 (also for end panel right-hand) 600/800 AGS 002510-01900 900 AGS 002510-02

1000600/800 AGS 002510-03

900 AGS 002510-04

1

2

34

5

6 ( 13 mm)

Fig. 60Mounting the earth bar and connecting bar1 Earth bar2 Support brackets3 Connecting bar4 Screw-fastening the support brackets to the earth bar and the connecting bar5 Screw-fastening the support brackets to the panel6 External point of connection for the earth bus of the panel

The earth bars are screw-fastened from panel to panel by means of connecting bars (Fig. 57, item 3).

Page 53: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

53AGS 531 446-01 | Edition 04/2014

5 Busbar attachments

5.1 Safety provisions

Warning!When performing assembly work on busbar attachments, the ap-propriate disconnecting device must be in earthed position (see Operating Manual).

Warning!Please comply with the safety provisions in Chapter 1, page 7.

5.2 Assembly of surge arresters

Notice: Remove grease and silicone from the contact surfaces and insu-

lating areas on the inner cone-type sockets in the tank and on the surge arresters before assembly.

Comply with the assembly instructions of the surge arrester.

1. Clean and grease contact surfaces on the surge arrester and inside the inner cone-type socket (see Chapter 13.3, page 92).

2. Clean the insulating areas of the surge arrester and in the inner cone-type socketcarefullyandapplyauniformfilmofspecialpaste(seeinstructionsforassembly of the surge arrester).

3. Slip surge arrester in correct axial position into the inner cone-type socket and screw-fasten it.

4. Screw-fasten the earthing cable of the surge arrester on the busbar tank.

Fig. 61Surge arrester

Page 54: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

54 AGS 531 446-01 | Edition 04/201454

5 Busbar attachments

5.3 Assembly of voltage transformers

Rated voltage Ur [kV] Assembly drawing≤ 24 AGS 001861-02

> 24 AGS 001861-01

Notice: Remove grease and silicone from the contact surfaces and insu-

lating areas on the inner cone-type sockets in the tank and on the voltage transformers before assembly.

Observe the instructions for assembly of the voltage transformers. The weight of the transformers must be taken into consideration!

Support the transformer or secure it by attaching a crane hook to the transformer jack rings.

1. Clean and grease contact surfaces on the transformer connector and inside the inner cone-type socket (see Chapter 13.3, page 92).

2. Clean the insulating areas of the transformer connector and inside the inner cone-typesocketcarefullyandapplyauniformfilmofspecialpaste(seeas-sembly instructions for voltage transformer).

3. Push voltage transformer into inner cone-type socket in correct axial direction and screw-fasten it (Fig. 62, item 2); 4 x M8 self-locking nut. Fasten transformer additionally to angle bracket (4). 2 x M8 self-locking screw

4. Connect the transformer secondary lines (plug-in contacts) (6). Comply with themarking!Fastentheprotectivehose(tightennutbyhandandfixcablesbymeans of cable clamps, 7 and 8).

5. Mount cover plate (5) above the transformer cables. 2 x M5 Torx screw

12 4

5

3

3

7

68

Fig. 62Assembly / disassembly of busbar voltage transformer1 Attachment with disconnecting device on busbar2 Connectingsocketandflangefastening3 Voltage transformer4 Angle bracket5 Cover plate for transformer wiring6 Terminal connection of transformer cables7 Fastening by means of cable clamp8 Fastening the protective hose

Page 55: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

55AGS 531 446-01 | Edition 04/2014 55

5 Busbar attachments

The voltage transformers are inserted from above into the inner cone-type socket in the busbar tank (optional, Fig. 63).Assembly is effected as described above.

Fig. 63Voltage transformer attachment from above

Rated voltage Ur [kV] Assembly drawing≤ 24 AGS 002260-02

> 24 AGS 002260-01

Page 56: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

56 AGS 531 446-01 | Edition 04/2014

6 Low-voltage cabinet

6.1 Assembly

The low-voltage cabinets are either supplied as accessories or already mounted to the panel, depending on the transport requirements.1. Remove transport protection covers from the interface between drive compart-

ment and low-voltage cabinet. All the wiring with terminals for the low-voltage cabinet must be located in the drive area below the upper sheet metal edge.

2. Assign the low-voltage cabinet to the appropriate panel. Remove the packag-ing of the low-voltage cabinet and place the cabinet on the lifting table (Fig. 64). Raise lifting table until the low-voltage cabinet is above the drive area.

3. Carefully push the low-voltage cabinet onto the panel above the drive area, align it and screw-fasten it to the panel. To this effect, open the switch cabinet door using the double bit key. Lower screw fastening (1): 4x M8 self-locking screw; rear screw fastening (2): 4x M8 self-locking screw.

4. Screw-fasten the low-voltage cabinets laterally to one another (3). Screw-fasten by means of a M8 self-locking screw connection, depending on the height of the low-voltage cabinet 800/1200: 2x/3x. Assembly drawing: AGS 003252-02

1

33

2

4

5

1

2

2x/3x

6Top view

3

4x 4x

Fig. 64Mounting the low-voltage cabinet1 Lower screw fastening (4x)2 Rear screw fastening (4x)3 Lateral screw fastening (2x/3x)

4 Lifting table5 Low-voltage cabinet6 Spacer

Page 57: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

57AGS 531 446-01 | Edition 04/2014 57

6 Low-voltage cabinet

6.2 Connecting the control lines

1. Slip the terminals of the drive box wiring onto the terminal strips in the low-volt-age cabinet according to the marking on the connector (Fig. 65).

2. Close opening in the base of the low-voltage cabinet to the drive area by means of a cover plate (2). 5 x M6 self-locking screw connection.

1

2

3

Fig. 651 Drive wiring to terminal strip in low-voltage cabinet2 Cover plate3 Fastening the cover plate

1. Route the secondary lines for the intra-panel wiring through the lateral rubber sleeves of the low-voltage cabinet (Fig. 66).

2. The ring circuits are designed with connectors and are connected to the ap-propriate terminal strips in the low-voltage cabinet according to the connector designations (or the circuit diagram) (2).

1

2

Fig. 661 Ring circuits between panels2 Connection of the ring circuits to terminal strips

Connecting internal control lines of panel:

Connecting the ring circuits:

Page 58: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

58 AGS 531 446-01 | Edition 04/201458

6 Low-voltage cabinet

Customized low-voltage lines for control and measuring purposes can be routed on the right-hand inside of each panel (Fig. 67).1. Route external cables from the cable basement into the cable compartment of

the panel (1) and place them in the right-hand cable tray of the panel to the low-voltage cabinet (3). Fasten cables to the panel by means of cable clamps (2).

2. Connect external cables to the terminal strip in the low-voltage cabinet ac-cording to the circuit diagram. Additionally, ground shielded lines on the cable supports.

3. Re-fasten metallic cable tray covers in the supporting structure (4). 4 x M8 self-locking screw

1

1

2

3

4

Fig. 67Placing external control cables1 External control lines2 Cable clamp3 Low-voltage cabinet4 Metallic cable tray covers

Placing external control lines in the switchgear panel:

Page 59: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

59AGS 531 446-01 | Edition 04/2014

7 Switchgear termination

7.1 Attachment of the protective tank to the left-hand / right-hand end of the busbar

On the busbar end, a protective tank must be mounted on the left and right sides of the voltage-proof busbar caps.

Panel width [mm] End panel

Single busbar Double busbar

600/800

left-hand side 1 x AGS001760-01 AGS001760-05

+AGS001760-03right-hand side

1 x AGS001760-02 AGS001760-02 +AGS001760-04

900/1000

left-hand side AGS002570-05 AGS002570-01

+AGS002570-03right-hand side

AGS002570-02 AGS002570-02 +AGS002570-04

Panel width [mm] End panel

Single busbar Double busbar

600/800

left-hand side AGS001760-30 AGS001760-35

+ AGS001760-20right-hand side

AGS001760-31 AGS001760-31 + AGS001760-21

900/1000

left-hand side AGS001760-32 AGS001760-32

+ AGS001760-22right-hand side

AGS001760-33 AGS001760-33 + AGS001760-23

1

2

Fig. 68Protective tanks at the busbar end (example) for1 upper busbar2 rear busbar (in case of

double busbar switchgear)

Models without pressure relief duct

Models with pressure relief duct

Page 60: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

60 AGS 531 446-01 | Edition 04/201460

7 Switchgear termination

7.2 Switchgear without pressure relief duct

(Accessibility in acc. with IEC 62271-200: IAC AFL)

7.2.1 OverviewVariants:

– The switchgear is accessible from the front and from the right-hand side (the switchgear is located in the left-hand corner of the room, Fig. 69).

– The switchgear is accessible from the front and from both sides (Fig. 70). – The switchgear is accessible from the front and from the left-hand side (the

switchgear is located in the right-hand corner of the room, without illustration).

Notice:Comply with the appropriate documentation for the switchgear. It de-fines the applicable variant in accordance with the customer's require-ments.

All individual parts are included in the accessories. Design is identical for the right-hand and left-hand sides.

≥1700

1

2≥800

3

100+30 -0

100+30 -0

3

Fig. 69Design example: Switchgear located in the left-hand corner of the room1 Rear gap cover (see page 64)2 Operating area3 Side wall (see Chapter 7.2.2, page 61)

Page 61: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

61AGS 531 446-01 | Edition 04/2014 61

7 Switchgear termination

1

3

1

2

≥800

≥800

≥1700 ≥1700

100+30 -0

100+30 -0

Fig. 70Design example: The switchgear is accessible from the front and from both sides1 Gap cover (see page 64)2 Operating area3 Side wall (see Chapter 7.2.2)

7.2.2 Attachment of the right-hand or left-hand side wall

Height of low-voltage cabinet [mm]

Assembly drawing of side wallleft-hand side right-hand side

800 AGS 000630-01 AGS 000630-031200 AGS 000630-02 AGS 000630-04

Page 62: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

62 AGS 531 446-01 | Edition 04/201462

7 Switchgear termination

If applicable, remove the covers of the lateral cable ducts in the cable compartment (Fig. 71, item 3).1. Screw-fastenfire-protectionboard(2)andbaseplate(1)tooneanother(11);

2 x M8 self-locking screws.2. Screw-fasten (10) base plate (1) to the last panel (8);

2 x M8 self-locking screws.3. Fasten base plate to the spacer bar (9). 2 x M8 self-locking screws. Cut thread

M8 in the base frame.4. Screw-fasten top and bottom side wall sections (4) to one another (6);

6 x M8 self-locking screw connections.5. Mount complete side wall. To this effect, screw-fasten:

– side wall to base plate (1); 5 x M8 self-locking screw. – side wall to panel (8); 9 x M8 self-locking screws. – side wall to low-voltage cabinet (7) (see also Chapter 6.1); 3 x M8 self-

locking screws. – rear side wall fastening (5) with the retaining plate on the panel;

3 x M8 screw fastening (only required for ESS, not for DSS).

9

2

5

6

8

7

3

5

4

2

11

1

11

110

6

Fig. 71Attaching the right-hand side wall1 Base plates 2 Fire-protection plates3 Cable tray cover4 Top and bottom side wall sections5 Rear screw fastening of the side wall to the panel6 Screw fastening of the two side wall sections7 Screw fastening the side wall to the low-voltage cabinet8 Screw fastening the side wall to the panel supporting

structure

9 Screw fastening the base plate to the base frame10 Screw fastening the base plate to the panel11 Screwfasteningthefire-protectionboardtothebaseplate

Page 63: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

63AGS 531 446-01 | Edition 04/2014 63

7 Switchgear termination

7.2.3 Extension of side wall in double busbar switchgear

Height of low-voltage cabinet [mm]

Assembly drawing of side wallleft-hand side right-hand side

800 AGS 000633-01 AGS 000633-031200 AGS 000633-02 AGS 000633-04

In double busbar switchgear, the side wall (Chapter 7.2.2, page 61) is extended to the rear (Fig. 72). 1. Mount side wall acc. to Chapter 7.2.2, page 61.2. Screw-fasten upper and lower cover bracket (Fig. 72, item 5) and upper and

lower termination plates (1 and 2) to the side wall (4).3. Mount the rear fastening link (3).

1

2

3

5

4

Fig. 72Side wall extension for double busbar switchgear1 Upper termination plate2 Lower termination plate 3 Fastening link with screw fastening4 Screw-fasten the termination plates and cover bracket to the side wall5 Upper and lower cover bracket

Page 64: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

64 AGS 531 446-01 | Edition 04/201464

7 Switchgear termination

Rear gap cover

Wall clear-ance [mm]

Height of LV cabinet

[mm]

Busbar system Mat. no. in case of side wall side

800 1200 ESS Attachment on the front to

end wall or at the ear to end wall

DSS Attachment only at the rear

to end wall

left-hand side right-hand side

100 AGS001967-01 AGS001967-02

500 AGS001967-07 AGS001967-08100 AGS001963-01 AGS001963-02500 AGS001963-07 AGS001963-08

The rear gap cover is installed between the mounted side wall and the rear wall of the building (Fig. 73).Thenominalwidthofthegapcoveris100mmforsinglebusbarand500(≥300)mmfor double busbar. Assembly is performed identically.1. Screw-fasten upper and lower gap covers (1) to the side wall.

11 x M8 hex. bolt2. Apply gap cover (2) on wall side as shown in the drawing and mark securing

bore-holes on the wall of the building and on the mounted gap cover.3. Remove gap cover on wall side. Provide securing bore-holes for the mounted

gapcover(Ø4.5)andforthebuildingwall(Ø10).Subsequently,fitdowelpinsin the wall of the building.

4. Screw-fasten gap cover on building wall. 9 x M8 hex. bolt

5. Screw-fasten both gap covers to one another. 9 x M5 hex. bolt.

Fig. 73Rear gap cover (shown for left-hand switchgear end, 100 mm wall clearance)1 Front gap cover2 Gap cover on the wall side3 M5 hex. bolt4 M8 hex. bolt5 Fastening to building wall: Dowel and M8 hex. bolt

3

5

2

1

4

100+30

≥ 50

105

1

2

34

5A

Page 65: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

65AGS 531 446-01 | Edition 04/2014 65

7 Switchgear termination

7.3 Attachment of fan

1

23

4

Fig. 74Fan attachment1 Cover plate2 Fan

3 Angular bracket on the low-voltage cabinet4 Low-voltage cabinet

Panel width [mm] Height, low-voltage cabinet [ mm ]

Mat. no.

800/900 1000 800 1200 AGS003149-02 AGS003154-02

AGS003149-03 AGS003154-03

Height, low-voltage cabinet [ mm ] Mat. no. 800 1200 AGS003181-01

AGS003181-02

Panel width [mm] Panel width, adjacent panel, right-hand [mm]

Mat. no. 900 1000 600 / 800 / 900 / 1000 AGS003183-13

600 / 800 / 900 / 1000 AGS003183-12

Angular bracket (Fig. 74, item 3)

Attachment of angular bracket on the low-voltage cabinet (Fig. 74, item 3)

Cover plate (Fig. 74, item 1)

Page 66: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

66 AGS 531 446-01 | Edition 04/201466

7 Switchgear termination

Panel variant 50 Hz 60Hz Busbar system

Mat. no.

Sin-gle

bus-bar

Dou-ble

bus-bar

Bus section coupler 2500 A1 AGS002723-04Feeder panel 2500 A1 AGS002723-03

Bus section coupler 2500 A1 AGS002723-08 + AGS002723-06

Feeder panel 2500 A1 AGS002723-07 + AGS002723-09

Current transformer in the busbar run 2500A AGS003216-04

Disconnector in the busbar run 2500 A AGS003515-01

Disconnector in the busbar run 2500 A

AGS003515-01 + AGS003532-01 + AGS000982-04

Disconnector in the busbar run 2500A1

AGS003515-01 + AGS003532-02 + AGS000982-04

Feeder panel 2500 A AGS002723-07 + AGS003678-01

Bus section coupler 2500 A AGS002723-08 + AGS003678-02

1 only possible in conjunction with pressure relief duct

Fan (Fig. 74, item 2, 65)

Page 67: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

67AGS 531 446-01 | Edition 04/2014

8 Switchgear with pressure relief device

8.1 Overview

Switchgear units with pressure relief duct are accessible on all sides and can thus be located centrally in the room.

Notice: The pressure relief duct must be mounted before the panel is

positioned on the base frame (see Chapter 4.5, page 28). After installation of the panels, mounting is no longer possible.

The customized pressure relief duct and the pressure relief flap are not included in the scope of supplies.

The attachments for the pressure relief duct are included in the accessories.The pressure relief ducts and the side walls are attached on the construction site.

L

2

L

3

Fig. 75Switchgear panel with single busbar and pressure relief duct

Fig. 76Switchgear panel with double busbar and pressure relief duct

Available for: Accessibilityinacc.withIEC62271-200:QualificationIACAFLR(accessibility

from all sides) and/or QualificationIACAFL(R)internalarc40kA/1s

The connection for a customized pressure relief duct is integrated on the left and/or rightinthesidewall(seeswitchgear-specificdocumentation).

Available for: Switchgear with pressure relief duct and opening into the switchgear room Internalarcstrengthacc.toIEC62271-200,qualificationIACAFL(R),internal

arc≤25kA/1s(40kA/1s)

Switchgear with pressure relief duct: Model with pressure relief from the switchgear room

Model with pressure relief into the switchgear room

Page 68: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

68 AGS 531 446-01 | Edition 04/201468

8 Switchgear with pressure relief device

1

2

34

2

≥ 5

00

520

180 180

1595

5

6 7

2009

520180

1

180 4

7

2 2

8

6

Fig. 77Illustrated: Switchgear with single busbar, accessible on all sides1 Switchgear2 Side walls (see Chapter 8.4, page 66)3 Integrated pressure relief duct of the switchgear (see Chapter 4.5, page 28)4 Connectionforswitchgearpressureductwithconnectingflange5 Wall of building 6 Customized pressure relief duct7 Pressurereliefflapinthewallofthebuilding8 Assembly aisle for switchgear not accessible from the rear

switchgearaccessiblefromtherear:≥800

Page 69: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

69AGS 531 446-01 | Edition 04/2014 69

8 Switchgear with pressure relief device

8.2 Cover plate

Required in case attached pressure relief duct

Panel width [mm] Panel width, adja-cent panel, right-

hand [mm]

Pressure relief from the switchgear room 40kA

800/1200 LV cabinet

Pressure relief into the switch-gear room 40kA 1200 mm LV

cabinetSS-StW 600 800 900 1000

600 / 800 AGS002115-16

900 / 1000 AGS002115-15 600 / 800 AGS002115-17 900 / 1000 AGS002115-16

600 / 800 / 900 / 1000 AGS003216-03 AGS003216-03

Fig. 78Cover plate

Page 70: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

70 AGS 531 446-01 | Edition 04/201470

8 Switchgear with pressure relief device

8.3 Attachment of pressure relief duct

12

Fig. 791 Reinforcement 2 Pressure relief duct

Panel width [mm] Busbar system

Assembly drawing

600 800 900 1000 ESS DSS AGS002110-05

AGS002110-06 AGS002110-05

Single parts for pressure relief duct

Panel width [mm]

adjacent panel, right-hand

Panel width [mm]

Busbar system

Pressure relief Reinforcement Special attach-ments

600 800 900 1000 600 800 900 1000 ESS DSS AGS002103-04 AGS002104-01 AGS002103-031

AGS002103-04 AGS002104-02 AGS002103-031

AGS002103-05 AGS002104-01 - AGS002103-05 AGS002104-02 -

AGS002103-05 AGS002104-02 AGS002103-122

AGS002103-05 AGS002104-03 AGS002103-122

AGS002103-06 AGS002104-02 AGS002103-083

AGS002103-06 AGS002104-03 AGS002103-083

without AGS002103-04 - AGS002103-031

without AGS002103-05 - - without AGS002103-05 - AGS002103-122

without AGS002103-06 - AGS002103-083

AGS002103-04 AGS002104-02 - AGS002103-04 AGS003481-02 -

AGS002103-05 AGS002104-02 - AGS002103-05 AGS003481-02 -

AGS002103-05 AGS002104-03 AGS002103-122

AGS002103-05 AGS003481-04 AGS002103-122

AGS002103-06 AGS003481-01 AGS002103-083

AGS002103-06 AGS003481-03 AGS002103-083

AGS002103-06 AGS002104-03 AGS002103-083

1 Item number required in case of pressure discharge 40 kA into the room, item number AGS002103-04 deleted2 Item number required in case of fan attachment 2500 A FB900 and pressure relief duct; item number AGS002103-05 deleted3 Item number required in case of fan attachment 2500 A FB1000 and pressure relief duct; item number AGS002103-06 deleted

Page 71: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

71AGS 531 446-01 | Edition 04/2014 71

8 Switchgear with pressure relief device

8.4 Attachment of side walls for pressure relief from the switchgear room

1

520

Fig. 80Sidewallwithconnectionflangeforcustomizedpressurereliefduct(item1)

Height LV cabinet [mm]

Busbar system Connection flange for customized pressure

relief duct*

Mat. no. in case of side wall on the Panel width (600, 800, 900)

800 1200 ESS DSS left-hand side

right-hand side left-hand side right-hand side

AGS002130-01 AGS002175-01

AGS002123-01 AGS002124-01

AGS002123-02 AGS002124-02

AGS002130-02 AGS002175-09

AGS002130-05 AGS002175-05

AGS002130-06 AGS002124-05

AGS002130-05 AGS002124-06

AGS002130-06 AGS002175-06

AGS002130-03 AGS002175-01

AGS002123-03 AGS002124-01

AGS002123-04 AGS002124-02

AGS002130-04 AGS002175-09

AGS002130-07 AGS002175-05

AGS002130-08 AGS002124-05

AGS002130-07 AGS002124-06

AGS002130-08 AGS002175-06

* required for routing the pressure relief duct outwards at the side of the end panel to the left or right

Page 72: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

72 AGS 531 446-01 | Edition 04/201472

8 Switchgear with pressure relief device

8.5 Attachment of side walls for pressure relief into the switchgear room

Fig. 81Sidewallwithoutconnectionflangeandmodelwithpressurereliefintotheswitch-gear room

Height LV cabinet [mm]

Busbar system

Internal arc strength, qualification IAC AFLR, internal arc (1s)

Mat. no. in case of side wall on the

Panel width (600, 800, 900)800 1200 ESS DSS ≤ 25 kA ≤ 40 kA left-hand side right-hand side

AGS002123-02 AGS002124-02

AGS002123-01 AGS002124-01

AGS002130-05 AGS002124-06

AGS002130-06 AGS002124-05

AGS002123-04 AGS002124-02

AGS002123-03 AGS002124-01

AGS002130-07 AGS002124-06

AGS002130-08 AGS002124-05

Page 73: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

73AGS 531 446-01 | Edition 04/2014

9 High-voltage connection

Depending on customer requirements, the panels can be equipped at choice with outer cone-type bushings or inner cone-type sockets.Optionally, the panels can also be supplied with high-voltage terminals for conductor bars(seeswitchgear-specificdocumentation).

Danger!Risk of fatalities due to high voltage!The transport protection caps provided by the factory on the high-voltage terminals are not voltage-proof.

Before commissioning, replace the transport protection caps by voltage-proof covers.

9.1 Cable compartment with base plates (optional)

The cable compartment of a panel can be designed optionally with mounted base plates. Thus, the cable compartment and the cable basement are separated from each other.

1. For assembly of the high-voltage cables, remove the front base plates and the plastic sleeves (Fig. 82).

2. Cuttheplasticsleevestofitthecablediameterandslipthemoverthecablebefore mounting the cable connectors.

3. After mounting the cables, position plastic sleeves, then reinsert and screw-fasten the removed base plate.

1

2

3

4

Fig. 82Panel with base plates1 Base plate2 Plastic sleeves3 High-voltage cable (cable support not shown)4 Perforated sheet metal cutout for connection of a connecting cable to the

switchgear earth bus (see also Chapter 4.12, page 52). Break sheet-metal cutouts out as required.

Preassemble base plate in the panel

Page 74: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

74 AGS 531 446-01 | Edition 04/201474

9 High-voltage connection

9.2 Outer cone-type bushing

Standard design of the outer cone-type bushings: in acc. with EN 50181, terminal type C (screw-type contact with internal thread

M16 and reinforced conductor pin for 1250 A rated current) for cable Tee screw-type plugs

L1L2

L3L1

L2

Fig. 831 x outer cone-type bushing per phase with one double cable connection each

L1L2

L3

L2

L1

L1

L1

L1

Fig. 842 x outer cone-type bushing per phase with one triple cable connection each

Page 75: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

75AGS 531 446-01 | Edition 04/2014 75

9 High-voltage connection

635,5

746,4

600

191 191

96

800

229 229

564

590 740

1 2 3

1 2 3

Fig. 85Dimension drawings for outer cone-type bushing with one terminal per phase (top) and with two terminals per phase (bottom)

Warning!The cable support must be adjusted and the cable/cable connec-tor must be fastened so that no additional forces act on the outer cone-type bushing! The bushings may be damaged due to inad-missible stress, so that insulating gas can escape.

Practically all the commercially available cable connection systems (fully insulated, metal-enclosed or partially insulated) can be mounted to the switchgear.Tools and accessories (cable clips, screws, spring washers etc.) for the assembly of the cable connection systems (cable connectors) are not included in the scope of supplies.The switchgear is accessible from the front to enable assembly of the cable connec-tion systems. To this effect, remove front cable compartment covers (see Chapter 4.6.2, page 30).

Dimension drawings

Page 76: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

76 AGS 531 446-01 | Edition 04/201476

9 High-voltage connection

Danger!Close vacant outer cone-type bushings with surge-proof caps (not included in the scope of supplies).

1. Put the adjustable cable supports (Fig. 86, item 4) in the required position and fasten them (horizontally and vertically adjustable).

2. Mount cable connectors according to the manufacturer's Assembly Instructions. 3. Remove the protective transport caps from the appliance couplers. Use a

cleaning agent to remove grease and silicone from the appliance couplers (see Chapter 13.1, page 90).

4. Coat contact areas of Cu insert on the appliance coupler and screw-type con-tactwithathingreasefilm(seeChapter13.3, page 92).

5. Treatinsulatingsurfacesasspecifiedbythemanufacturerofthecableconnec-tor. Slip cable connector on the appliance coupler. The cable connection to the outer cone-type bushing (thread M16) must be tightenedwithamax.torqueof50Nm.Observethemanufacturer'sspecifica-tions.

6. If necessary, re-adjust cable support, align cables and fasten them to the cable support using cable clips.

7. Connect earthing cables (2) of cable and cable connector to the cable support (3). Coat contact surfaces (see Chapter 13.3, page 92).

If surge arresters are provided, the switchgear can be equipped additionally with retaining plates to which the fasteners for surge arresters can be mounted.

The contact areas of the earth connections must be coated as described in the Annex.

For assembly, refer to the instructions of the manufacturer of the surge arrest-ers.

1

4

5

2

3

Fig. 86High-voltage cable connector, outer cone-type, screw-type contact1 Screw-type contact2 Cable connector3 Earth conductors4 Cable supports, adjustable5 Cable clip

Cable assembly

Page 77: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

77AGS 531 446-01 | Edition 04/2014 77

9 High-voltage connection

9.3 Inner cone-type socket

Inner cone-type sockets acc. to EN 50181 can be standard equipment of the panels.Cable connectors, tools, accessories (cable clips, screws, spring washers etc.) are not included in the scope of supplies.

Notice: When shrink-fitting cable end boxes, make sure that the cable

connection area of the panel is not heated beyond the admissible service temperature. We cannot accept any liability for consequential damage (e.g. damaged cables of the capacitive indicator) which might result from shrink-fitting components in the cable compartment using an open flame.

An accessible cable tray must be provided below the panel for as-sembly of the cable supports and the high-voltage cables.

L1L2

L3

L1

43227

5

Fig. 87Inner cone-type sockets with cable supports above spacer bar level

289

266

113

Fig. 88Inner cone-type cable socket with cable supports below spacer bar level (attachment on site)

Page 78: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

78 AGS 531 446-01 | Edition 04/201478

9 High-voltage connection

(only required for models acc. to Fig. 87)Assembly drawing AGS 003010-04The individual parts are included in the accessories.1. Screw-fasten sides to the supporting structure of the panel.2. Mount the cable support.

Fig. 89Attachment of cable support in case of inner cone-type socket design acc. to Fig. 90

Installation of the base plates (optional and only for versions acc. to Fig. 90).Assembly drawing AGS 003014-01.The individual parts are included in the accessories.1. Cuttheplasticsleevestofitthecablediameterandslipthemoverthecable

before mounting the cable connectors.2. After mounting the cables, position plastic sleeves, then insert and screw-fasten

the base plate.

1

2 3 4 (2)

Fig. 90Installation of the base plates1 Floor pan2 Cable support3 Divided base plates4 Plastic sleeves

Installation of the cable support

Base plates in the accessories

Page 79: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

79AGS 531 446-01 | Edition 04/2014 79

9 High-voltage connection

Warning!The cable support must be adjusted and the cable/cable connec-tor must be fastened so that no additional forces act on the inner cone-type socket! The bushings may be damaged due to inadmis-sible stress, so that insulating gas can escape.

1. Mount cable connector (Fig. 91, item 2) according to the instruc-tions of the cable connector manufacturer.

2. Remove transport protective caps from the appliance couplers (socket-contacts). Remove grease and silicone from appliance cou-plers using a cleaning agent (see Chapter 13.1, page Fig. 90).

3. Slightly grease contact surfaces on the appliance coupler and on the cable connector (see Chapter 13.3, page 92).

4. Treat insulating surfaces as speci-fiedbythemanufacturerofthecable connector. Insert cable con-nector in inner cone-type socket (press down) and screw-fasten safely. Tighten screw fastenings M8 with a torque of 15 ± 3 Nm.

5. If necessary, re-adjust cable sup-port (5), align cables and fasten them to the cable support using cable clips (4).

6. Connect earthing cables (3) of cable and cable connector to the cable support (5). Coat contact sur-faces (see Chapter 13.3, page 92).

Danger!Close unused inner cone-type sockets with surge-proof dummy plugs

If the metallic connector housing features a conductive contact surface touching the metal enclosure of the switchgear (appliestoPfisterermodel,systemCONNEX): Do not connect the cable's earth conductor to the connector housing (contact-making). Make sure that the earth conductor is connected directly to the cable support.

Cable assembly

1

2

3

4 5

Fig. 911 Socket contacts2 Cable connector3 Earth conductors4 Cable clip5 Cable support

Fig. 92Connection of cable earth conductor if cable-type transformers are used

Connector shell with conductive contact surface with reference to switchgear's metal enclosure:

Page 80: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

80 AGS 531 446-01 | Edition 04/2014

10 Commissioning

10.1 Final steps

10.1.1 Attachment of the tool board1. Fasten tool panel at choice to the left or right side of the side wall (depending

on switchgear installtion) (Fig. 93); 2 x M5 Torx screw.2. Place operating elements and instruction manuals on the tool board acc. to Fig.

92.

1

5

4

3

2

9

8

7

6

Fig. 93Tool board attachment1 Tool board2 Fastening by means of a M5 Torx

screw3 Double-bit key for low-voltage

cabinet4 Crank for actuation of earthing

switch / disconnector5 Handle for transformer disconnect-

ing device (inner cone-type cable

socket)6 Spring charging crank for energy-

storing device7 Assembly and Operating Instruc-

tions8 Handle for transformer disconnect-

ing device (outer cone-type cable bushing)

9 Service address

10.1.2 Cleaning and checking assembly

Danger!The high-voltage supply must not be connected. All active parts must be earthed.

Clean the switchgear, removing contamination resulting from assembly work. Remove all the attached information tags, cards, brochures and instructions no

longer needed. Check the tightening torques of all screw fastenings and connections estab-

lished on the site of installation: – Cablefittingsonappliancecouplers – Surge-proof covers on the appliance couplers – Earth conductor – Panel screw fastenings – Special attachments

Notice:Make sure the fastening of the silicone sleeves and busbar connection are no longer detached.

Page 81: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

81AGS 531 446-01 | Edition 04/2014 81

10 Commissioning

10.1.3 Remount covers (see Chapter 4.6, page 29)

Lateral low-voltage cable tray cover Cable compartment cover Operating shutter Close front frame again.

10.1.4 Damaged paintThe components are powder-coated. Minor damage to the paint can be repaired using commercially available paint (standard colour RAL 7044 or corresponding colour).

10.1.5 Inspection Check the switchgear for damage which might be due to transport or assembly

work. Compare data on nameplate to the required ratings. Check rated supply voltage of control and operating devices. Check wiring laid on site. Check insulation gas monitoring:

– IDIS system: see operating manual IDIS (AGS 531 691-01)

10.2 Commissioning

Danger!The high-voltage supply must not be connected. All active parts must be earthed.

Notice: Refer to the operating manual of the GHA series. While the power supply is not available, blocking coils (locking the

interrogation slides and circuit-breaker push-buttons, depending on design) are in “locked” position. An undervoltage release (op-tional) has dropped out. In this case, first perform items 3 to 5.

The energy-storing device of the circuit-breaker drive is charged autonomously as soon as the supply voltage is applied.

1. Perform manual switching trials on the individual switching devices.2. Check switch position indicators.3. Apply supply voltage.4. Check electrical functions of control and operating devices:

– Motor drives for disconnector and earthing switch (optional) – Closing and opening releases for circuit-breaker

5. Check switch position indicators and interlocks.6. Before connecting, check the connected feeder cables for phase coincidence

(see Operating Manual).

Page 82: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

82 AGS 531 446-01 | Edition 04/2014

11 Optional high-voltage test on commissioning

11.1 Power frequency withstand test of the busbar

A power frequency test of the busbar can be performed optionally. The test voltage is supplied via the high-voltage terminal of a panel. To this effect, a test unit and test cables are required, which are not included in the scope of supplies.

Warning!Comply with the safety provisions in Chapter 1, page 7.

Danger!No high-voltage cables must be connected in the incoming feeder panel for the voltage test and on the busbar. All high-voltage terminals must be closed surge-proof during the test phase. Earth the residual phases using commercially available earthing devices.

Notice:All the switching operations mentioned in this context must be per-formed in accordance with the applicable Operating Manual GHA.

1. All panels must be isolated from the power supply, and earthed.2. Incoming feeder panel for voltage test:

– Remove the cable compartment cover. – Test phase: Mount test cable to the high-voltage terminal (see Fig. 94).

Open high-voltage terminals must be closed surge-proof during the test phase. Earth the residual phases using commercially available earthing devices.

– Earth the voltage transformers and capacitive measuring points. Discon-nect surge arresters.

4

3

56

7

21

Fig. 941 Outgoing feeder panels2 Incoming feeder panel for voltage test3 Voltage transformer4 Busbar5 Test unit (e g. high-voltage source, test transformer)6 Test cable7 Busbar voltage transformer

General

Preparations

Page 83: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

83AGS 531 446-01 | Edition 04/2014 83

11 Optional high-voltage test on commissioning

3. Busbar: – Earth voltage transformer / surge arrester. – Earth capacitive measuring connectors. – Close open high-voltage terminals in a surge-proof fashion.

4. Power frequency withstand test of the busbar: – Connect test unit to the test cable. – Switch earthing switch in the incoming feeder panel OFF. – Switch disconnector and circuit-breaker in the incoming feeder panel ON. – Perform power frequency withtstand tests successively for all phases (L1,

L2,L3)accordingtothespecificationsofthetestunitmanufacturer.

Notice:Observe admissible test values for the switchgear and the admissible test values for power-frequency tests after installation of the switchgear in accordance with IEC 62271-200.

5. Once the power frequency withstand test has been completed, earth all the tested high voltage lines again. Comply with the applicable safety provisions!

6. Once the power-frequency test has been completed: – remove the test unit and the test cable, – reconnect earthed or removed voltage transformers, capacitive measuring

connectors or surge arresters. – Mount high-voltage cable or surge-proof covers on the incoming feeder

panel and reinsert cable compartment cover.

Power frequency withstand test:

Once the power-frequency test has been completed:

Page 84: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

84 AGS 531 446-01 | Edition 04/201484

11 Optional high-voltage test on commissioning

11.2 Cable testing

Cable tests with the cables connected can be performed for outer cone-type as well as for inner cone-type cable connections for each phase.

The test sockets for inner cones are accessible from the panel front after re-moval of the cable compartment cover (Fig. 95, page 85).

The busbar can be operated with rated voltage during cable tests in the outgo-ing feeder (see nameplate).

For cable testing, a test unit and a test adapter are required, which are not included in the scope of supplies.

Danger!Risk of fatalities due to high voltage. Before the cable test, the outgoing feeder cable must be isolated from the power supply and earthed. The outgoing feeder cable of the remote station must also be isolated from the power supply.

Danger!Risk of fatalities due to supply voltage. Isolation from supply volt-age must be ensured.

Warning!Risk of injury due to movable parts in mechanical drives.

Release the circuit-breaker’s energy storing device by OFF-ON-OFF operation and make-proof earthing switches by the appropriate ON-operation.

Warning!After removing covers from a switchgear unit, operator safety may be reduced regarding internal arcs unless the switchgear is isolated from the power supply. Optimum operator safety is only ensured if the switchgear is completely disconnected from the power supply and grounded during assembly.

Notice: All the switching operations mentioned in this context must be per-

formed in accordance with the applicable Operating Manual GHA. The assembly, operating and testing instructions for cable fittings

and connectors and the test unit must be taken into consideration. Comply with the admissible limits (see Table). Other limits are

only admissible after having obtained the written approval of the manufacturer.

Admissible limits for the switchgear panels in case of cable tests

Ur

[kV]DC test voltage for initial / repeat test

[kV] max. 15 min.

0.1 Hz AC test voltage

[kV] max. 60 min.

12 34 19

24 67 4536 76 57

40,5 – 62

General

Page 85: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

85AGS 531 446-01 | Edition 04/2014 85

11 Optional high-voltage test on commissioning

1. Isolate outgoing feeder cable of the appropriate switchgear panel from the power supply.

2. Isolate outgoing feeder cable in remote station.3. Earth outgoing feeder cable.4. Remove cable compartment cover (see Chapter 4.6, page 29).5. Earth connected voltage transformers in the outgoing feeder cable.6. Short-circuit and earth capacitive measuring points in outgoing feeder cable.7. Remove surge-proof covers from measuring points:

– Inner cone: Remove dummy plug

– Outer cone: RemoveterminatingelementsinTeeplugsasspecifiedbythemanufac-turer

8. Connect test adapter to test connector and test unit (Fig. 95 and Fig. 96, page 86).Complywiththemanufacturer'sspecifications.

Notice: Make sure that the distance between the metallic components of

the test adapter and the earthed subconstruction of the switchgear is sufficiently dimensioned.

Earth the residual phases using commercially available earthing devices.

1

2

Fig. 95Test cable for inner cone-type socket (size 2)1 Test socket2 Test cable

Preparations

Performing the cable test

Page 86: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

86 AGS 531 446-01 | Edition 04/201486

11 Optional high-voltage test on commissioning

12

Fig. 96Cable test, outer cone1 Cover and adapter2 Test adapter

9. In case of optional interlocking of the cable compartment cover, the circuit-breaker cannot be switched off until after simulation of a cable compartment cover (Fig. 97).

Warning!Interrupting the inter-locking protection: With the cable compart-ment cover removed, the earthing switch interlock may only be eliminated during cable test!

– Swing interlock (1) of the cable compartment cover downwards and keep it in this position.

– Push interlocking slide (2) down; the actuating port for the earthing switch is set free.

1

2

Fig. 97Unlocking the earthing switch1 Cable compartment cover interlock2 Interlocking slide

Page 87: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

87AGS 531 446-01 | Edition 04/2014 87

11 Optional high-voltage test on commissioning

10. Set switchgear panel to test position. If an intertripping circuit is provided, the circuit-breaker is switched off by actuation of the earthing switch towards “OFF” (Fig. 98).

– Free actuating port of the earthing switch (B) by push-ing the interrogation slide (A) upwards, and insert the crank (C).

– Turn crank counterclockwise by approx. one rotation, until the circuit-breaker has switched OFF (D). The crank cannot be removed.

11. Performcabletestaccordingtothespecificationsofthemanufacturerofthecable or the cable connector, taking the admissible limits into consideration (see Table on page 86). Perform cable test for all phases.

12. Earth outgoing feeder cable again: – Switch earthing switch completely OFF – Charge spring mechanism – Switch earthing switch ON again

13. Remove test set. – Inner cone-type socket:

Close test socket “surge-proof” using the dummy plug. – Outer cone-type bushing:

Providecablefittingswithterminatingelementaccordingtothemanufac-turer's instructions.

14. Re-connect voltage transformer.15. De-earth capacitive measuring points in outgoing feeder cable and reset short-

circuit.16. Mount cable compartment cover again.

Test position: – Earthing switch ON – Circuit-breaker OFF

00243

A

B

C

D

Fig. 98Set switchgear panel to test position

After the cable test

Page 88: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

88 AGS 531 446-01 | Edition 04/201488

11 Optional high-voltage test on commissioning

11.3 Cable jacket test

If there are no documents to inform whether a cable jacket test may be performed on the cable connection system, the manufacturer of the cable connection system must be consulted before performing such a test.

Warning!Do not connect the cable's earth conductor to the connector housing (contact-making). Make sure to check the earthing cable directly.

1. To perform the cable jacket test, disconnect the earth connections (Cu shield) from the cable support.

2. To determine any damage on the outer plastic jackets or sheathes between the cable's Cu shield and the earth, apply test DC voltage in accordance with the applicable standard or the instructions of the cable manufacturer.

3. Once the test has been completed, re-mount the earth connection (Cu shield) on the cable support.

Fig. 99Cable jacket testing principlefor outer cone

Page 89: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

89AGS 531 446-01 | Edition 04/2014

12 Replacement of components and panels

Drive mechanisms, current transformers, voltage transformers, testing and monitor-ing systems and complete switchgear panels can be replaced as required.Should you have any queries regarding replacement of components or panels, please contact the manufacturer’s Service Center.For correct processing of your enquiry, the following data of the nameplate of the panel in question are required (see Operating Instructions AGS 531 441-01, Chap-ter 2.6):

Type designation Serial number Year of construction

Page 90: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

90 AGS 531 446-01 | Edition 04/2014

13 Annex

13.1 Auxiliary products

The auxiliary products are available from the manufacturer. The use of other auxil-iary products is not admissible.

Warning!Risk of injury if these products are handled improperly. Observe the safety data sheets of the manufacturers of the auxiliary prod-ucts.

Auxiliary products Ref. no.Cleaning agent S 008 152Synthetic lubricant (KL), 0.5 kg can ST 312-111-835Liquid lubricant FL, 0.5 kg can S 008153Touch-up pen RAL 7044, silk-grey, 50 ml S 009 561Touch-up pen, special paint (specify colour shade) S 009 562Screw locking compound Loctite 648® ST318-225-001

Auxiliary products for assembly of the busbar link (B-Link)

Ref. no.

Cleaning agent Ethanol, type 641 (methylated spirit) S 009 002 ÄSpecial grease Klüberalfa® HBK 83-102 AGS 003371-01Sponge element S065969lint-freecloth(alsomicro-fibercloths) –lint-free rubber gloves –

13.2 Required tools (not included in the scope of supplies)

Cutter Nail puller

approved torque wrenches with different bits for hexagon socket screws and socket-head screws and nuts; bits for screw and nut grades M 5, M 6, M 8, M 10, M 12Screwdriver and Philips screwdriver

Nipping pliers

4cranestraps/chainseachofL≥2000mm,liftingca-pacity≥1500kglint-free, clean cloths

Page 91: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

91AGS 531 446-01 | Edition 04/2014 91

13 Annex

Fig. 100Transport frame

Fig. 101Fork to compress the silicone sleeve

Fig. 102Claw fastener

Fig. 103Lifting table for low-voltage cabinet

Fig. 104Uprofileswithstopastraversingaid

Fig. 105Special hoisting equipment SLAM

Page 92: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

92 AGS 531 446-01 | Edition 04/201492

13 Annex

13.3 Coating the contact surfaces

Notice:Contact areas, once coated with synthetic lubricant, should not be touched, if possible.

1. Contact surfaces must be subjected to preliminary treatment before screw-fastening (see Table below).

2. Immediately after the pre-treatment, coat both contact surfaces sparingly with a thinanduniformfilmofsyntheticlubricantsothatthespacebetweenthecon-tactsurfacesiscompletelyfilledoncethescrewshavebeenfastened.

Material of contact surfaces Pre-treatmentSilver-plated Clean1

Copper or copper alloy Clean1, expose metallic surface2

Aluminium Clean1, expose metallic surface2

Steel Clean1, expose metallic surface2

Galvanized steel Remove passivation, not, however, the zinc layer3

Sheet metal, hot dip galvanized Clean1; passivation need not be removed1 Clean by means of a lint-free cloth; use cleaning agent in case of serious con-

tamination 2 Expose metallic surface

- by treating the entire surface with emery cloth or a rotating grinding tool (grain size 100 or 80) or

- using a wire brush which is clearly marked for use exclusively for aluminium or exclusively for copper

3 using a brass brush, steel brush

13.4 Screw locking compound

Notice: Observe the specifications of the manufacturer of the screw lock-

ing compound. In case the thread reach exceeds 1.2 x the screw diameter and in

case of blind hole threads, only wet the nut's thread.

1. Preparing the thread surfaces: clean and degrease thread surfaces using cleaning agent and a lint-free cloth.

2. Application of adhesive: Coat the entire circumference of 2 or 3 threads in the area to be glued with liquid screw locking compound.

Max. time for positioning: 60 sec.

Page 93: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

GHA

93AGS 531 446-01 | Edition 04/2014 93

13 Annex

13.5 Specifications for screw connections

Notice: The threads of screws and bolts must generally not be pre-treat-

ed! Max. tolerance for the effective tightening torques: ±15% The nut must correspond in strength to the grade of the screw/bolt

used or be of better quality.

Grade or material

Screw/bolt Plastic ≥8.8≤10.9Self-locking screw

≥8.8Thread Ø Tightening torques [Nm]

M 4 0.25 2.6

M 5 0.5 5.0 7.0

M 6 0.8 8.8 12.3

M 8 1.8 21.0 30.0

M 10 3.5 42.0 59.0

M 12 6.0 70.0 97

M 16 12 170

M 20 330

Screw connection for current transmission

Screw connection for terminal strips

Screwsandbolts:Grade≥8.8

Conductor material: copperThread Ø Tightening

torques [Nm]M 6 6.5M 8 17M 10 35M 12 68M 16 135

Thread Ø Tightening torques [Nm]

M 2.5 (M 2.6) 0.5M 3 0.7

M 3.5 1.0M 4 1.5M 5 2.5

General screw connections

Page 94: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

Notes:

Page 95: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition
Page 96: Medium-voltage switchgear GHA - Schneider Electric Belgiëms.schneider-electric.be/Main/GHA/instructions/GHA_MA_AGS531446-01_EN.pdfMedium-voltage switchgear No. AGS 531 446-01 Edition

Schneider Electric35, rue Joseph MonierCS 3032392506 Rueil-Malmaison Cedex, France

RCS Nanterre 954 503 439Capital social 896 313 776 €www.schneider-electric.com AGS 531 446-01 | 04/2014

As our products are subject to continuous development, we reserve theright to make changes regarding the standards, illustrations and technicaldata described in this Technical Manual. For any requests, please contact the address given below.

Schneider Electric Sachsenwerk GmbHRathenaustrasse 2D-93055 Regensburg, Germany( +49 (0) 9 41 46 20-0 7 +49 (0) 9 41 46 20-418

© S

chne

ider

Ele

ctric

201

4 –

All

right

s re

serv

ed to

this

tech

nica

l man

ual.

Rep

rodu

ctio

n an

d m

akin

g av

aila

ble

of th

is te

chni

cal m

anua

l, or

ext

ract

s, to

third

par

ties

are

proh

ibite

d.

Onl

y in

tegr

al re

prod

uctio

n of

this

tech

nica

l man

ual i

s pe

rmitt

ed w

ith th

e w

ritte

n pe

rmis

sion

from

Sch

neid

er E

lect

ric. E

lect

roni

c co

pies

in e

.g. P

DF-

form

at o

r sca

nned

ver

sion

ha

ve th

e st

atus

“for

info

rmat

ion

only

” . T

he o

nly

valid

ver

sion

of t

his

tech

nica

l man

ual i

s al

way

s en

clos

ed d

irect

ly to

the

prod

uct i

n qu

estio

n by

the

fact

ory.


Top Related