![Page 1: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/1.jpg)
NATIONAL CONFERENCE ON ELECTRICAL SAFETY 2015
![Page 2: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/2.jpg)
AMALAN KESELAMATAN ELEKTRIK UNTUK PEPASANGAN BANGUNAN
KERAJAANKERAJAAN
OLEH : Ir. ZURAIDAH MUHAMAD
KETUA JURUTERA ELEKTRIK,UNIT PERUNDING INSPEKTORAT & KESELAMATAN ELEKTRIK,
CAWANGAN KEJURUTERAAN ELEKTRIK,IBU PEJABAT JKR MALAYSIA.
![Page 3: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/3.jpg)
KANDUNGAN
PENGENALAN
PIAWAI DAN PERATURAN KESELAMATAN ELEKTRIK
PUNCA KEGAGALAN KESELAMATAN ELEKTRIK
CONTOH KEMALANGAN ELEKTRIK
FAKTOR MEMPENGARUHI KEJUTAN ELEKTRIK
LANGKAH MEMASTIKAN KESELAMATAN ELEKTRIK
AMALAN TIDAK SELAMAT
![Page 4: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/4.jpg)
BAHAYANYA ELEKTRIK !
• Senyap, tidak boleh dilihat dan tiada bau….
TETAPI
Boleh membunuh (jantung terhenti)
Musnah harta benda
Kecacatan anggota badan
(melecur, terbakar)
Trauma
![Page 5: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/5.jpg)
RUJUKAN PIAWAIAN DAN PERATURAN RUJUKAN PIAWAIAN DAN PERATURAN KESELAMATAN KESELAMATAN
REKABENTUK MS, IEC, MS IEC, CIE
Spesifikasi JKR , arahan teknik JKR
KOMPETENSI Akta bekalan elektrik 1990
Peraturan-peraturan elektrik 1994
BAHAN/PEMBUATAN
MS, IEC, MS IEC
SENGGARAAN Manual Pengurusan Senggara
Manual Pengurusan Aset Menyeluruh Kerajaan
![Page 6: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/6.jpg)
PUNCA UTAMA KEGAGALAN PUNCA UTAMA KEGAGALAN KESELAMATAN ELEKTRIK….KESELAMATAN ELEKTRIK….
1) Sistem pembumian tidak sempurna/
lengkap
2) Kaedah pemasangan dan prosedur kerja2) Kaedah pemasangan dan prosedur kerja
yang salah
3) Pengendalian oleh orang bukan kompetan
4) Menggunakan peralatan tidak ikut piawaian
5) Peralatan yang tidak diselenggara
6) Kurang pengetahuan mengenai bahaya
elektrik
![Page 7: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/7.jpg)
KEMALANGAN ELEKTRIK
![Page 8: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/8.jpg)
KEMALANGAN DOMESTIK
![Page 9: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/9.jpg)
MENGAMBIL MUDAH TENTANG BAHAYA ELEKTRIK
Saraf pada pergelangan tangannya telah mati dan kemungkinan boleh mendatangkan mudarat pada anggota badan lain.
![Page 10: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/10.jpg)
KESAN MELECUR TERUK
![Page 11: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/11.jpg)
Kesan melecur/terbakar
![Page 12: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/12.jpg)
RENJATAN ELEKTRIK
FAKTOR YANG MEMPENGARUHI KEJUTAN
ELEKTRIK DARI SENTUHAN :-
a) Laluan arus ( rintangan , keadaan permukaan
kulit)kulit)
b) Tempoh arus
c) Magnitud arus
d) Nilai voltan
e) Cara tindakbalas mangsa
![Page 13: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/13.jpg)
KESAN MAGNITUD ARUS :KESAN MAGNITUD ARUS :--
ARUS
(1 saat)KESAN TERHADAP FIZIKAL BADAN
1 mA Kesan kejutan pada badan
5 mAJumlah maksimum manusia boleh bertahan. Tidak bahaya
10-20 mAOtot mula kejang. Otot tidak boleh dikawal (tahappermulaan boleh menyebabkan kematian)
50 mA Gangguan pada jantung, kesakitan, sukar bernafas
100 mA -300 mA
Jantung tidak berfungsi dengan betul, pengalirandarah terhenti atau sedikit sahaja yang mengalir
6 AKerosakan organ dalaman berlaku. Pernafasanlumpuh sementara. Tisu badan terbakar
**15/20 ANilai yang biasa digunakan untuk fius dan pemutuslitar
Data diperolehi dari : National Institute for Occupational Safety and Health, US
![Page 14: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/14.jpg)
![Page 15: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/15.jpg)
![Page 16: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/16.jpg)
![Page 17: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/17.jpg)
LANGKAH MEMASTIKAN LANGKAH MEMASTIKAN KESELAMATAN ELEKTRIK KESELAMATAN ELEKTRIK PADAPADA
PEPASANGANPEPASANGAN
REKABENTUK
PEMBINAAN
SENGGARA
![Page 18: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/18.jpg)
PERINGKAT REKABENTUKPERINGKAT REKABENTUK
JKR MENGAMALKAN AMALAN KEJURUTERAAN
TERBAIK (BEST ENGINEERING PRACTICE)
RUJUKAN REKABENTUK DAN KAWALAN BAHAN :
SPESIFIKASI JKR/PANDUAN TEKNIK JKR
IEC , MS, MS IEC IEC , MS, MS IEC
MS IEC 364
MS 941
KAWALAN PENGILANG :
UJIAN DIKILANG/SPESIFIKASI JKR
MS 948
![Page 19: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/19.jpg)
PERINGKAT PEMBINAANPERINGKAT PEMBINAAN
PENYELIAN TAPAK
FLYING SQUARD CKE, JKR
GARISPANDUAN PEMASANGAN, BEST PRACTISE, LESSON
LEARNT
STANDARD PENGUJIAN/TESTING AND COMMISSIONING
CIRI PENERIMAAN
KAWALAN BAHAN DAN PENGILANG
![Page 20: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/20.jpg)
Terminals for external conductors separated from vertical/distribution busbars.
Form 2b Separation
SWITCHBOARD
Distribution Busbars Compartment
IP2X or IPXXB
IP2X or IPXXB
1. Maintenance people should not be in a dangerous situation, e.g. parts not under maintenance should not create dangerous situation in parts under maintenance
2. Maintenance in one part should not create a dangerous situation in another part e.g. a screw or a tool falls in another part
3. Danger in one part should not expand to other parts e.g. an arc in one part should not influence other parts
![Page 21: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/21.jpg)
Distribution Busbars Compartment
Main Busbars Compartment
SWITCHBOARDForm 2b Separation
Compartment
![Page 22: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/22.jpg)
Form 3a or 3bSWITCHBOARD
![Page 23: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/23.jpg)
EARTHING BOND
CLAMPING METHOD : NO . To prevent discontinuity to earth.
EXORTHERMIC WELD : YES.
![Page 24: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/24.jpg)
FIRE BARRIERFIRE BARRIER
• Ruang lantai dibiarkan
terbuka: terdedah
bahaya jika ada
kebakaran
• Bukaan pada lantai
/dinding hendaklah di
tutup dengan fire
barrier.
![Page 25: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/25.jpg)
LIGHTNING PROTECTION SYSTEM( LPS)
JKR masih menetapkan kaedah konvensional ( faraday cage)
Lebih jaminan keselamatan : Rujuk :MS- IEC 62305-2
![Page 26: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/26.jpg)
BEBAN ATAS SILING
• Lampu digantung 4 penjuru terus ke bawah lantai (soffit
slab)
• Pendawaian dalam G.I / flexible G.I
• Koordinasi di tapak penting
![Page 27: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/27.jpg)
PEMASANGAN KIPAS SILING
• Safety wire tidak dipasangPemasangan Safety Wire
![Page 28: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/28.jpg)
PERINGKAT SENGGARAANPERINGKAT SENGGARAAN
Penyenggaraan pencegahan dan pembaikan.
Penyenggaraan komprehensif
Khidmat teknikal dan nasihat pelanggan
Garis panduan:
Manual Prosedur Senggara
Manual Pengurusan Aset Menyeluruh Kerajaan
![Page 29: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/29.jpg)
CIRI-CIRI KESELAMATANPENYENGGARAAN
VCB, EF/OC , lampu penunjuk hendaklah kemas, disenggara
dengan baik
Kekemasan penatang kabel untuk kemudahan senggara
All protection (ELR, O/C & E/F) relay will be calibrate once every two years.
![Page 30: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/30.jpg)
MSB/ SSBMSB/ SSBPEMERIKSAANPEMERIKSAAN ORANGORANG KOMPETANKOMPETAN , UNIT , UNIT
INSPEKTORATINSPEKTORAT DANDAN KESELAMATANKESELAMATANUse chromed type of screw with cylindrical knurled head c/w retaining clip for panel,coverand front door.
LED indicating light (RYB) install before and after main breaker.
Danger signage
![Page 31: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/31.jpg)
PENYENGGARAANPENYENGGARAAN PENCEGAHANPENCEGAHANMEMENUHIMEMENUHI KEHENDAKKEHENDAK
KESELAMATANKESELAMATAN Tatahan , ujian dan servis dilakukan oleh orang
kompetan
![Page 32: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/32.jpg)
PEMASANGAN BERCIRIKAN
KESELAMATAN
PEMASANGAN YANG MERBAHAYAPEMASANGAN YANG MERBAHAYA
![Page 33: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/33.jpg)
MSB : CIRIMSB : CIRI--CIRI KESELAMATANCIRI KESELAMATAN
Use SPD to protect from lightning effect
Use CT class 1 for measurement
Use CT for protection class 10P10 which is more accuracy compare to 5P10
effect
Use IDMT Overcurrent & Earth Fault relay for protection if use ACB.
Use ACB for big installation > 400A TPN
![Page 34: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/34.jpg)
PENDAWAIAN / KONDUIT / TRUNKING
FAKTOR RUANG MEMBERI KELEGAAN KEPADAPEPASANGAN
• KONDUIT• TRUNKING
40%
60%
45%
55%
![Page 35: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/35.jpg)
CIRI KESELAMATAN LAIN
• Copper bridge for continuity
Remote operate for VCB switching
![Page 36: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/36.jpg)
PEMASANGAN PEMASANGAN EARTHINGEARTHING BARBAR
Installation of earth bar size 6mm x 25mm around the Tx room at 300mm from floor level.
YES
![Page 37: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/37.jpg)
PENDAWAIAN TIDAK SELAMAT
• Penyambungan kabel tidak
dibenarkan
Tiada rubber bush menyebabkan kabel luka.
NO
NO
![Page 38: NATIONAL CONFERENCE ON ELECTRICAL SAFETY … · amalan keselamatan elektrik untuk pepasangan bangunan kerajaan oleh: ir. zuraidah muhamad ketuajuruteraelektrik, unit perunding inspektorat](https://reader031.vdocuments.net/reader031/viewer/2022012318/5b9eba2609d3f26e288be0f6/html5/thumbnails/38.jpg)
SEKIANTERIMA KASIH
CAWANGAN KEJURUTERAAN ELEKTRIK
IBU PEJABAT JKR MALAYSIA
KUALA LUMPUR
38