Page 1: Nh3 Refrig Ragagep

For Official Use Only

Ammonia RefrigerationAmmonia Refrigeration

RAGAGEPsRAGAGEPs

For Official Use Only

Page 2: Nh3 Refrig Ragagep

Objectives

Gain a basic understanding of: Gain a basic understanding of: – RAGAGEPs unique to Ammonia

RefrigerationRefrigeration– Equipment-specific RAGAGEP

requirementsrequirements

Again, this is an overview discussion. There is usually an exception to most rules

Slide 2

Page 3: Nh3 Refrig Ragagep

RAGAGEP Organizations

ASME ASME

ANSI /ASHRAE

IIAR

NB NB

NIOSH

RMA

Slide 3

Page 4: Nh3 Refrig Ragagep

ASME / NB

BPVCDesign, fabrication, inspection, testing and certification of vessels operating above 15 psig (internal and/or external)psig (internal and/or external)

B31.5Refrigeration Piping and Heat Transfer Components

NBIC NB-23In-service inspections, repairs, alteration, re-

Slide 4

rates

Page 5: Nh3 Refrig Ragagep

ANSI / ASHRAE

ANSI/ASHRAE 15 ANSI/ASHRAE 15Safety Standard for Refrigeration SystemsRefrigeration Systems

Slide 5

Page 6: Nh3 Refrig Ragagep

IIAR

Process Safety Management Guidelines for Ammonia Refrigeration (update coming soon)

Ammonia Refrigeration Piping Handbook

Ammonia Data Book Ammonia Data Book(chemical and technology PSI resource)

Oil D i i G id li Oil Draining Guidelines

Slide 6

Page 7: Nh3 Refrig Ragagep

IIAR

ANSI/IIAR Standard 2Equipment, Design, and Installation of Closed-Circuit Ammonia Mechanical Refrigeration SystemsRefrigeration Systems

Bulletin No. 107Suggested Safety and Operating Procedures When Making Ammonia Refrigeration Plant Tie InsRefrigeration Plant Tie-Ins

Bulletin No. 108

Slide 7

Guidelines for Water Contamination in Ammonia Refrigeration Systems

Page 8: Nh3 Refrig Ragagep

IIAR

Bulletin No. 109Guidelines for IIAR Minimum Safety Criteria for a Safe Ammonia Refrigeration System

Bulletin No. 110Guidelines for Start-Up, Inspection, and Maintenance of Ammonia Mechanical Refrigeration Systems

Bulletin No. 111Guidelines for Ammonia Machinery Room

Slide 8

Ventilation

Page 9: Nh3 Refrig Ragagep

IIAR

Bulletin No. 112Guidelines for Ammonia Machinery Room Design

Bulletin No. 114Guidelines for Identification of Ammonia Refrigeration Piping and System Components

Bulletin No. 116Bulletin No. 116Guidelines for Avoiding Component Failure in Industrial Refrigeration Systems Caused by

Slide 9

Abnormal Pressure or Shock

Page 10: Nh3 Refrig Ragagep

NIOSH

Publication No. 79-120Working Safely with Anhydrous Ammonia

Publication No. 79-119A Guide for Developing a Training Program for Anhydrous Ammonia Workers

Slide 10

Page 11: Nh3 Refrig Ragagep

RMA

Publication IP-14Publication IP 14Specifications for Anhydrous Ammonia Hose

Publication IP-11-2 Hose Technical Bulletin - Manual for UseHose Technical Bulletin Manual for Use, Maintenance, Testing, and Inspection of Anhydrous Ammonia Hose

Slide 11

Page 12: Nh3 Refrig Ragagep

Slide 12

Page 13: Nh3 Refrig Ragagep

ANSI/ASHRAE 15

Safety Code for Mechanical RefrigerationSafety Code for Mechanical Refrigeration

Establishes safeguards for personnel and propertyproperty

Applies to:– Design, construction, test, installation,

operation, and inspection– Modifications (non-RIK)– Substitutions of refrigerants

Slide 13

Subst tut o s o e ge a ts

Page 14: Nh3 Refrig Ragagep

ANSI / IIAR Standard 2

Standard for Equipment, Design & Installation of Ammonia Mechanical Refrigerating Systems

Applies to closed-circuit mechanical refrigeration systems

Provides minimum requirements for:Equipment– Equipment

– Machinery room design

Slide 14

– Installation of systems

Page 15: Nh3 Refrig Ragagep

IIAR Bulletin No. 109

Minimum Safety Criteria for a SafeMinimum Safety Criteria for a Safe Ammonia Refrigeration System

Identifies mandatory safety requirements Identifies mandatory safety requirements

Provides safety inspection checkliststo be performed annually

References other codes and standards as e e e ces ot e codes a d sta da ds asbasis for checklists

Slide 15

Page 16: Nh3 Refrig Ragagep

IIAR Bulletin No. 110

Start-Up, Inspection, and Maintenance ofStart Up, Inspection, and Maintenance of Ammonia Mechanical Refrigerating Systems

Startup StartupPSSR, Evacuation, Dehydration, Leak Checking, Charging Testing Protective DevicesCharging, Testing Protective Devices

I&MSystem Log/inspection Compressors PVs andSystem Log/inspection, Compressors, PVs, and HEs, Pumps, Valves, Piping, Oil, Motors

Provides example ITPM planSlide 16

– Provides example ITPM plan

Page 17: Nh3 Refrig Ragagep

IIAR Bulletin No. 110

System log/inspection – at least dailySystem log/inspection at least daily (example in Appendix I)

Slide 17

Page 18: Nh3 Refrig Ragagep

IIAR Bulletin No. 110

Appendix GAppendix G

Typical Inspection and Maintenance Plan

Slide 18

Page 19: Nh3 Refrig Ragagep

IIAR Bulletin No. 111

Ammonia Machinery Room VentilationAmmonia Machinery Room Ventilation

Ventilation DesignEAC Emergency Vent Rate FanEAC, Emergency Vent Rate, Fan Selection & Layout, Detectors, Controls

Operation & MaintenanceFans/Intakes, Room Pressure, Detectors, ControlsControls

Slide 19

Page 20: Nh3 Refrig Ragagep

IIAR Bulletin No. 111

Slide 20

Page 21: Nh3 Refrig Ragagep

IIAR Bulletin No. 114

Identification of Ammonia RefrigerationIdentification of Ammonia Refrigeration Piping and System Components

Comprehensive labeling scheme Comprehensive labeling scheme– Label size– Colors– Locations– Label material requirements

Slide 21

Page 22: Nh3 Refrig Ragagep

Equipment-specific Requirements

Slide 22

Page 23: Nh3 Refrig Ragagep

Alarms & Detectors

Each machinery room is equipped withEach machinery room is equipped with ammonia detection that alarms and starts ventilation at a concentration of no higher than 1,000 ppm (ASHRAE-15, 8.11.2.1)

Detector alarms annunciate with visualDetector alarms annunciate with visual and audible means both inside and outside each entrance to machinery room (ASHRA-15, 8.11.2.1)

Alarm is triggered when the continuous

Slide 23

Alarm is triggered when the continuous ventilation system fails (IIAR-111, 3.5.3)

Page 24: Nh3 Refrig Ragagep

Alarms & Detectors

A high-range detector will automaticallyA high range detector will automatically shut down all unclassified equipment in the machinery room at no more than 15,000 ppm (IIAR-111, 3.5.2)

Must be manual reset type with the resetMust be manual reset type with the reset located inside the refrigerating machinery room (ASHRAE-15, 8.11.2.1)

The meaning of each alarm shall be clearly marked by signage near the

Slide 24

clearly marked by signage near the annunciators (ASHRAE-15, 8.11.2.1)

Page 25: Nh3 Refrig Ragagep

Compressors

Fitted with high pressure cutoutsFitted with high pressure cutoutsthat unload the machine at 90% of the pressure relief valve set pressure (ASHRAE-15, 9.9)

Moving parts are guardedMoving parts are guarded(ASHRAE-15, 8.2)

Located such that there is Located such that there is unobstructed access for both normal and emergency tasks

Slide 25

normal and emergency tasks (ASHRAE-15, 8.3)

Page 26: Nh3 Refrig Ragagep

Compressors

Must have both suction and dischargeMust have both suction and discharge shut-off valves (ASHRAE-15, 9.12.4)

Fitted with nameplates that include: Fitted with nameplates that include: manufacturer, identification number, design pressures and refrigerant useddesign pressures, and refrigerant used (IIAR-2, 6.1.4)

Each must be identified with signage with Each must be identified with signage with lettering greater than 0.5" in height (ASHRAE-15 11 2 2)

Slide 26

(ASHRAE 15, 11.2.2)

Page 27: Nh3 Refrig Ragagep

Compressors

Each compressor has a high dischargeEach compressor has a high discharge temperature and pressure cutout(IIAR-2, 6.1.2.2)

Each compressor has a low suction pressure cutout (IIAR-2 6 1 2 2)pressure cutout (IIAR 2, 6.1.2.2)

Each compressor package with an oil pump has an oil flow failure indicatorpump has an oil flow failure indicator(more than just checking oil pressure and DP) (IIAR-2 6 1 2 2)

Slide 27

DP) (IIAR 2, 6.1.2.2)

Page 28: Nh3 Refrig Ragagep

Design Pressures

High-side components on systemsHigh side components on systems– 250 psig - evaporative condensing

300 psig air cooled condensing– 300 psig – air-cooled condensing(IIAR-2, 6.1 and 9.1)

Low-side components are rated for MAWPs of 150 psig or greater (IIAR-2, 9 1)9.1)

Slide 28

Page 29: Nh3 Refrig Ragagep

Machinery / Engine Room

Head room of at least 7.25 ft below equipment it t d (ASHRAE 15situated over passageways (ASHRAE-15,

8.11.1)

Self-closing, tight-fitting doors that open outward (ASHRAE-15, 8.11.2)

No other wall penetrations that would allow ammonia tothat would allow ammonia to other parts of building (ASHRAE-15, 8.11.2)

Slide 29

( , )

Page 30: Nh3 Refrig Ragagep

Machinery Room

Emergency ventilation amount is greaterEmergency ventilation amount is greater than 100 times the square-root of the charge of refrigerant in pounds(ASHRAE-15, 8.11.5)

Continuous ventilation amount is at leastContinuous ventilation amount is at least 0.5 cfm/ft2 or 20 cfm/person(ASHRAE-15, 8.11.5 and IIAR-111, 3.2.3)

Slide 30

Page 31: Nh3 Refrig Ragagep

Machinery Room

Does not permanently contain equipmentDoes not permanently contain equipment with continuous operating surface temperatures in excess of 800°F[ASHRAE-15, 8.12(a)]

Walls are noncombustible and at leastWalls are noncombustible and at least one-hour fire resistive construction [ASHRAE-15, 8.12(c)]

At least one door opens directly outside but not under a fire escape/open stairway

Slide 31

but not under a fire escape/open stairway [ASHRAE-15, 8.12(d),(e)]

Page 32: Nh3 Refrig Ragagep

Machinery Room

Emergency shutdown control of is locatedEmergency shutdown control of is located immediately outside of the machinery room door [ASHRAE-15, 8.12(i)]

Emergency ventilation fans are on a separate electrical circuit and have aseparate electrical circuit and have a control switch immediately outside of the machinery room door [ASHRAE-15, 8.12(i)]

Slide 32

Page 33: Nh3 Refrig Ragagep

Machinery Room

Signage indicatingSignage indicating– Name and address of installer

Refrigerant number and amount– Refrigerant number and amount– Lubrication identity and amount– Field test pressure (ASHRAE-15, 11.2.1)

Access is limited to authorized personnel only, ccess s ted to aut o ed pe so e o y,signage indicating MACHINERY ROOM-AUTHORIZED PERSONNEL ONLY at each

Slide 33

door (ASHRAE-15, 8.11.8 and 11.2.4)

Page 34: Nh3 Refrig Ragagep

Machinery Room Personnel Safety

ANSI Z358 1 e e ash/safet ANSI Z358.1 eyewash/safety shower located in close proximity outside of the machinery roomoutside of the machinery room (IIAR-2, 13.3.1.4)

ANSI Z358 1 h/ h ANSI Z358.1 eyewash/shower station should be located inside the machinery room within 50 ft of anymachinery room within 50 ft of any point in the room (IIAR-2, 13.3.1.4)

Slide 34

Page 35: Nh3 Refrig Ragagep

Piping

All refrigerant piping less than 6" NPS is at least schedule 40 (B31.5)

All refrigerant piping less than 2" NPS is atAll refrigerant piping less than 2 NPS is at least schedule 80 (B31.5)

Refrigerant piping must be fabricated by Refrigerant piping must be fabricated by certified welders-WPS/PQR/WQR (B31.5)

All piping mains, headers, and branches are identified including the refrigerant's physical state relative pressure level and

Slide 35

physical state, relative pressure level, and the direction of flow (IIAR-2, 10.5, IIAR-114)

Page 36: Nh3 Refrig Ragagep

Piping

Slide 36

Page 37: Nh3 Refrig Ragagep

Piping

Main shut-off valve(s) (i.e., king valves) should be readilyvalves) should be readily accessible and identified with a prominent signprominent sign(IIAR-109, 4.10.3)

Slide 37

Page 38: Nh3 Refrig Ragagep

Pumps

Pumps are protected from hydrostaticPumps are protected from hydrostatic overpressure with an relief device(IIAR-2, 6.2.1.2)

All exposed rotating parts of the pump are guarded (IIAR-2 6 2 1 4)guarded (IIAR 2, 6.2.1.4)

Liquid refrigerant pumps are equipped with low liquid level pump cut outlow liquid level pump cut-out

Slide 38

Page 39: Nh3 Refrig Ragagep

Relief Devices

Pressure relief devices protecting ASME ratedPressure relief devices protecting ASME rated components are stamped with a UV or VR symbol (ASHRAE -15, 9.4.2)

If a stop valve exists on the discharge of a pressure relief device it is full-port and lockedpressure relief device, it is full port and locked open (ASHRAE-15, 9.4.7)

Pressure relief device set pressure is equal to or Pressure relief device set pressure is equal to or less than the maximum allowable working pressure of the protected component(s)

Slide 39

pressure of the protected component(s) (ASHRAE-15 and ASME Sect. VIII)

Page 40: Nh3 Refrig Ragagep

Relief Devices

The capacities of the relief devicesThe capacities of the relief devices protecting liquid containing vessels are equal to or exceed ASHRAE 15 requirements

The inlet and outlet piping of the relief deviceThe inlet and outlet piping of the relief device and the protected component is at least the same size as the relief device inlet and outlet connections (ASHRAE-15, 9.7.6 and 9.7.8.4)

Slide 40

Page 41: Nh3 Refrig Ragagep

Relief Devices

Discharge from relief device(s) are greaterDischarge from relief device(s) are greater than 15 ft above the adjoining ground level (verify vent does not put people in "harms way") (ASHRAE-15, 9.7.8)

Discharge from relief device(s) are greaterDischarge from relief device(s) are greater than 20 ft from windows, ventilation intakes or building exits (ASHRAE-15, 9.7.8)

Replaced or cleaned/inspected tested every 5 years (IIAR-109 4 9 7)

Slide 41

5 years (IIAR 109, 4.9.7)

Page 42: Nh3 Refrig Ragagep

Pressure Vessels

Press re essels incl ding shell and t be Pressure vessels, including shell and tube exchangers must have a nameplate(IIAR-2 7 and 9)(IIAR 2, 7 and 9)

Liquid level indicators should be protected f h i l d (IIAR 109 4 6)from physical damage (IIAR-109, 4.6)

Inspected– During daily rounds– Annually

Slide 42

Annually– Every 5 years

Page 43: Nh3 Refrig Ragagep

Review

We covered– Ammonia

Refrigeration RAGAGEPs

– Some equipment-specific

i trequirements

Slide 43