NZS 3106:2009
New Zealand Standard
Design of concrete structures for the storage of liquids
Superseding NZS 3106:1986
NZS
3106:2009
NZS 3106:2009
New Zealand Standard
Design of concrete structures for the storage of liquids
Superseding NZS 3106:1986
ISBN 1-86975-125-6
NOTES
NZS 3106:2009
3
CONTENTS
Committee representation .......................................................................................... IFC
Acknowledgement ...................................................................................................... IFC
Copyright .................................................................................................................... IFC
Referenced documents .................................................................................................. 6
Latest revisions ............................................................................................................... 7
Review of Standards ...................................................................................................... 7
Foreword ........................................................................................................................ 8
Outcome statement ........................................................................................................ 8
Section
1 General ................................................................................................................9
1.1 Scope ......................................................................................................... 9
1.2 New Zealand building legislation ............................................................. 10
1.3 Interpretation ............................................................................................ 10
1.4 Appendices .............................................................................................. 10
1.5 Design and construction .......................................................................... 10
2 Definitions and abbreviations ............................................................................. 12
2.1 Definitions ................................................................................................ 12
2.2 Abbreviations ........................................................................................... 16
2.3 Notation ................................................................................................... 16
3 General design requirements ............................................................................ 20
3.1 Design methods ....................................................................................... 20
3.2 Support structures ................................................................................... 20
3.3 Tanks storing potable water ..................................................................... 20
3.4 Pipework .................................................................................................. 20
3.5 Freeboard ................................................................................................ 21
4 Loads and load combinations ............................................................................ 22
4.1 General .................................................................................................... 22
4.2 Loads and other actions .......................................................................... 22
4.3 Load control ............................................................................................. 27
4.4 Non-symmetric loads for circular tanks .................................................... 28
4.5 Load combinations for serviceability limit state ........................................ 28
4.6 Load combinations for ultimate limit state ................................................ 29
5 Design for serviceability ..................................................................................... 30
5.1 General considerations ............................................................................ 30
5.2 Reinforced concrete ................................................................................. 33
5.3 Prestressed concrete ............................................................................... 37
NZS 3106:2009
4
6 Design for strength and stability at the ultimate limit state ................................. 43
6.1 General .................................................................................................... 43
6.2 Stability design ......................................................................................... 43
6.3 Shear transfer .......................................................................................... 43
6.4 Minimum reinforcement ........................................................................... 45
7 Design for durability ........................................................................................... 46
Appendix
A Earthquake actions (Normative). ....................................................................... 48
B Design of reinforcement to control cracking (Normative). .................................. 62
C Testing (Informative) ..........................................................................................67
D Thermal stress coefficients (Normative) ............................................................ 69
Table
1 Roof temperature criteria ................................................................................... 25
2 Moisture variation – Shrinkage and swelling strains .......................................... 25
3 Liquid tightness class and leakage control provisions for Group A loads .......... 30
4 Reinforcement ratio for fully restrained concrete ............................................... 34
5 Limiting stresses in steel reinforcement where compression zone depth complies with 5.1.1 ............................................................................................35
6 Limiting stresses in steel reinforcement where compression zone depth is less than 5.1.1 ................................................................................................35
7 Limiting stresses in prestressed concrete .......................................................... 38
8 Exposure classifications .................................................................................... 46
A1 Displacement ductility factor, µ .......................................................................... 49
A2 Correction factor kf (µ, ξi) ................................................................................... 51
B1 Ratio of bond strength ....................................................................................... 63
B2 Strength and deformation characteristics for concrete ...................................... 64
D1 Thermal stress co-efficients – Pinned-base condition ....................................... 71
D2 Thermal stress co-efficients – Fixed-base condition .......................................... 74
D3 Thermal stress co-efficients – Sliding-base condition ........................................ 77
NZS 3106:2009
5
Figure
1 Temperature distributions in tank walls .............................................................. 23
2 Effective concrete area ......................................................................................33
3 Reduction of stiffness of doubly reinforced wall on cracking (including tension stiffening effect) .................................................................... 36
A1 Damping for horizontal impulsive mode ............................................................. 50
A2 Damping for vertical impulsive mode ................................................................. 50
A3 Dimensionless period for fundamental sloshing model ..................................... 52
A4 Equivalent weights of impulsive and convective contents (circular and rectangular tanks) ......................................................................... 53
A5 Equivalent weight distribution ............................................................................ 54
A6 Horizontal force distribution ............................................................................... 58
A7 Equivalent heights of impulsive and convective weights for overturning (circular and rectangular tanks) ...................................................... 60
A8 Approximate method for estimating buoyancy pressure on roof ....................... 61
B1 Effective tension area ........................................................................................64
B2 Crack width, w, at concrete surface relative to distance from bar ...................... 65
D1 Differential temperature change ........................................................................ 69
D2 Total temperature change .................................................................................. 70
NZS 3106:2009
6
REFERENCED DOCUMENTS
Reference is made in this document to the following:
NEW ZEALAND STANDARDS
NZS 1170.5:2004 Structural design actions – Earthquake actions – New Zealand
NZS 3101.1 & 2:2006 Concrete structuresNZS 3109:1997 Concrete constructionNZS 3112.2:1986 Methods of test for concrete – Tests relating to the determination
of strength of concrete
JOINT AUSTRALIAN/NEW ZEALAND STANDARDS
AS/NZS 1170 :- - - - Structural design actions Part 0:2002 General principles Part 1:2002 Permanent, imposed and other actionsAS/NZS 4671:2001 Steel reinforcing materials
AUSTRALIAN STANDARDS
AS 3735:2001 Concrete structures retaining liquidsAS 3735:2001 Supp 1 Concrete structures retaining liquids – Commentary
BRITISH STANDARDS
BS EN 1992-1-1:2004 UK National Annex to Eurocode 2: Design of concrete structures. General rules and rules for buildings
BS EN 1992-3:2006 UK National Annex to Eurocode 2. Design of concrete structures. Liquid retaining and containment structures.
BS 8007:1987 Code of practice for design of concrete structures for retaining aqueous liquids
OTHER PUBLICATIONS
American Concrete Institute (ACI), 344R-70, Analysis and design of reinforced concrete structures.
Comite Euro-International du Beton (CEB) and the Federation Internationale de la Precontrainte (FIP).CEB-FIP Model code, shrinkage and creep effects on prestressed concrete structures 1990.
Construction Industry Research and Information Association CIRIA C660, 2007. Early-age thermal crack control in concrete.
Gazetas, G M and Tassoulas, J L. Horizontal damping of arbitrarily shaped embedded foundations. Journal of Geotechnical Engineering, 113, No. 5, May 1987. United States.
New Zealand Society for Earthquake Engineering (NZSEE), Seismic design of storage tanks (in preparation, 2009). New Zealand.
Priestley, M J N. Ambient thermal stresses in circular prestressed concrete tanks. ACI Journal, October 1976.
Veletsos, A S, and Shivakumar, P. Computer analysis and design of earthquake resistant structures,Chapter 15 – Tanks containing liquids or solids. Computational Mechanics Publications, 1997. United Kingdom.
NZS 3106:2009
7
Veletsos, A S. and Tang, Y. Dynamics of vertically excited liquid storage tanks. Journal of Structural Engineering, 112, No. 6, June 1986. United States.
Vitharana, N D, and Priestley, M J N. Behaviour of reinforced concrete reservoir wall elements under applied and thermally-induced loadings. ACI Structural Journal, May-June 1998.
Vitharana, N D, and Priestley, M J N. Significance of temperature-induced loadings on concrete cylindrical reservoir walls. ACI Structural Journal, September-October 1999.
NEW ZEALAND LEGISLATION
Building Act 2004New Zealand Building Code (NZBC)Hazardous Substances (Dangerous Goods and Scheduled Toxic Substances) Transfer
Notice 2004
WEBSITES
http://www.legislation.govt.nz/http://www.dbh.govt.nz
LATEST REVISIONS
The users of this Standard should ensure that their copies of the above-mentioned New Zealand Standards are the latest revisions. Amendments to referenced New Zealand and Joint Australian/New Zealand Standards can be found on www.standards.co.nz.
REVIEW OF STANDARDS
Suggestions for improvement of this Standard will be welcomed. They should be sent to the Chief Executive, Standards New Zealand, Private Bag 2439, Wellington 6140.
NZS 3106:2009
8
FOREWORD
The aim of this Standard is to provide design information for users to meet the requirements of the New Zealand Building Code for concrete structures that will store liquid. NZS 3106 is intended to be used by engineers and organisations about to embark on a new storage tank project.
The committee has reviewed a number of Standards and other publications to identify ‘best practice’ and included provisions from these where appropriate.
This revision of NZS 3106:1986 aims to supplement NZS 3101:2006 and the AS/NZS 1170 suite of standards. Provisions that are adequately covered by the other Standards have not been included in this Standard.
Some of the the most significant changes are:
(a) In addition to the serviceability limit state loads, this Standard now requires users to also take into account the strength considerations required for ultimate limit state loads. This makes NZS 3106 consistent with the design procedures used for other structures.
(b) A new system to classify the liquid tightness of a structure has been adopted from BS EN 1992-3:2006. The designer can now decide what degree (if any) of leakage is acceptable from concrete cracks. The designer may then choose the appropriate crack control provisions to achieve liquid tightness.
(c) A new Appendix B provides procedures on how to calculate crack widths in reinforced concrete. These cracks may be caused by early-age thermal strains or from imposed loads and actions and given the critical importance of crack control in liquid retaining structures, the new procedures have been based on the worst case ‘fully restrained’ condition.
(d) The earthquake provisions have been reviewed in line with the New Zealand Society for Earthquake Engineering Study Group on the Seismic Design of Storage Tanks 2009 draft recommendations. Seismic force coefficients are based on NZS 1170.5, with allowance made for increased damping from soil-structure interaction which is particularly significant for liquid storage tanks.
OUTCOME STATEMENT
This Standard provides a basis for designing concrete structures for the storage of liquids so that they will require only limited periodic maintenance to remain serviceable for their design life, and will not allow an uncontrolled, rapid loss of the liquid contents in extreme events such as a major earthquake. This Standard supports public safety through designs that are safe and serviceable.
NZS 3106:2009
9
1 GENERAL
1.1 SCOpE
This Standard is intended to provide a means of compliance with the requirements of the New Zealand Building Code for concrete structures that will store liquid, and would be used regularly by engineers and organisations about to embark on a new storage tank project.
The Standard covers:(a) Design requirements and guidance;(b) Loading requirements;(c) Seismic considerations and allowances.
1.1.1 Inclusions
This Standard applies to containment structures for use with water of normal temperature (approximately 17 C) and pH (approximately 5.5 to 8.5) commonly found in drinking water supplies (fresh water) sewage, wastewater, and sea water.
The use of this Standard in the design of the following types of containment structures requires special consideration of the effects on the structure:
(a) Highly aggressive waters (for example, corrosive);(b) High temperature waters (> 35 ˚C);(c) Chemicals;(d) Oils (mineral and non-mineral) and fuels;(e) Slurries.
Tanks used for the storage of hazardous substances are required to comply with a Standard specified in Schedule 8, Clause 8 of the Hazardous Substances (Dangerous Goods and Scheduled Toxic Substances) Transfer Notice 2004 (as amended) or a code of practice approved under this clause. As at the time of publication, this Standard was not approved under this clause.
1.1.2 Exclusions
This Standard does not apply to the design of: (a) Dams;(b) Hydraulic tunnels;(c) Precast concrete pipes (pressure or non-pressure);(d) Fibre-impregnated concrete that does not comply with the design requirements and
procedures of NZS 3101;(e) Bins or silos for storage of dry bulk materials;(f) Pressure vessels.
NEW ZEALAND STANDARDDESIGN Of CONCRETE STRUCTURES fOR THE STORAGE Of LIqUIDS
NZS 3106:2009
10
1.2 NEW ZEALAND bUILDING LEGISLATION
1.2.1 Building Act and Code
Liquid retaining structures are buildings in terms of the Building Act 2004 and must therefore meet all the relevant performance requirements of the New Zealand Building Act and Code.
1.2.2 Verificationmethod
It is intended that this Standard will be cited as part of a Verification Method to be used in conjunction with other cited Standards to achieve compliance with the Building Code.
C1.2.2 Non-specific terms
Provisions in this Standard that are in non-specific or unquantified terms will not form part of the Verification Method. Non-specific terms include, but are not limited to, special studies, manufacturer’s advice and references to methods that are appropriate, adequate, suitable, relevant, satisfactory, acceptable, applicable, or the like.
1.3 INTERpRETATION
1.3.1 'Shall'and'should'
In this Standard the word ‘shall’ indicates a requirement that is to be adopted in order to comply with the Standard. The word ‘should’ indicates practices which are advised or recommended.
1.3.2 Clause cross-references
Cross-references to other clauses or clause subdivisions within this Standard quote the number only, for example: ‘… is given by 6.2 (a)’.
1.3.3 Commentary
Clauses prefixed by C, printed in italic type and shaded are intended as comments on the corresponding mandatory clauses. The commentary to this Standard, NZS 3106, does not contain requirements essential for compliance with this Standard but summarises technical background, offers explanations, and suggests approaches which satisfy the intent of the Standard.
1.4 AppENDICES
The terms ‘Normative’ and ‘Informative’ have been used in this Standard to define the application of the Appendix to which they apply. A ‘Normative’ Appendix is an integral part of a Standard while an ‘Informative’ Appendix is only for information and guidance.
1.5 DESIGN AND CONSTRUCTION
Unless otherwise specified in this Standard, all concrete design and construction shall be in accordance with NZS 3101 and NZS 3109.
NZS 3106:2009
11
C1.5 Design data
It is recommended that the following design data should be shown in the drawings:
(a) Reference number and date of issue of applicable design Standards;
(b) Tightness class;
(c) Live loads used in design;
(d) Exposure classification for durability;
(e) Class and, where appropriate, grade designation of concrete;
(f) Grade and type of reinforcement and tendons.
NZS 3106:2009
12
2 DEFINITIONS AND AbbREVIATIONS
2.1 DEFINITIONS
For the purposes of this Standard the following definitions shall apply:
Ambienttemperature Nominal temperature of the liquid to be stored
Anchorage The means by which prestress force is permanently transferred to the concrete. Also, the method of ensuring that reinforcing bars and fixings acting in tension or compression are tied into a concrete member
Beam A member subjected primarily to loads and forces producing flexure
Capacitydesign In the capacity design of structures subjected to earthquake forces, regions of members of the primary lateral force-resisting system are chosen and suitably designed and detailed for energy dissipation under severe deformations. All other structural members are then provided with sufficient strength so that the chosen means of energy dissipation can be maintained
Column An element subjected primarily to compressive axial loads
Component A physically distinguishable part of a structure such as a wall, beam, column, slab or connection
Concrete A mixture of Portland cement or any other hydraulic cement, sand, coarse aggregate, and water
Construction joint An intentional joint in concrete work detailed to ensure monolithic behavior at both the serviceability and ultimate limit states
Convectivemode The liquid in the upper portion of the tank vibrates with a long period sloshing motion and is referred to as the convective mode
Creepstrain Relates to the deformation over a period of time under constant load
Ductility The ability of a structure to sustain its load carrying capacity and dissipate energy when it is subjected to cyclic inelastic displacements during an earthquake
NZS 3106:2009
13
Endanchorage Length of reinforcement, or a mechanical anchor, or a hook, or combination thereof, required to develop stress in the reinforcement; mechanical device to transmit prestressing force to concrete in a post-tensioned member
fatigue load Load representing repeated stress cycles on the component
Force,earthquake Forces assumed to simulate earthquake effects
Hydrostaticpressure The lateral pressure exerted by liquid when it is at rest
Impulsivemode A portion of the liquid in the tank moves rigidly with the tank and is referred to as the impulsive mode
Load dead The weight of all permanent components of a structure, including permanently fixed plant and fittings
Load, design Combinations of loads and forces used in design as set out in AS/NZS 1170.0 and NZS 1170.5 or other referenced loading Standard for the applicable limit state. In seismic design for the ultimate limit state, the design load may be either the ultimate limit state forces or the forces resulting from the capacity design procedure depending on the case being considered
Monolithicconcrete Reinforced concrete cast with no joints other than construction joints
Overstrength The overstrength value takes into account factors that may contribute to strength, such as higher than specified strengths of the steel and concrete, steel strain hardening, confinement of concrete, and additional reinforcement placed for construction and otherwise unaccounted for in calculations
Precast concrete A concrete element cast-in other than its final position in the structure
Prestressed concrete Concrete in which internal stresses of such magnitude and distribution have been introduced that the stresses resulting from loads are counteracted to some extent to ensure the required strength and serviceability are maintained
Pre-tensioning A method of prestressing in which the tendons are tensioned before the concrete is placed
Progressive failure Failure progressing from initial stage of damage, such as
NZS 3106:2009
14
cracking, to final state of reaching the ultimate strength of any component within the system, which often occurs in interactive fashion
Reinforced concrete Concrete containing steel reinforcement, and designed and detailed so that the two materials act together in resisting loads and forces
Restrained concrete Concrete with restrained boundary conditions not allowing free shrinkage
Serviceabilitylimit The state that corresponds to conditions beyond which specified state service criteria for a structure or structural element are no longer met
Settlement Permanent downward displacement of the foundation
Slenderness ratio Ratio of the effective length of column to its least radius of gyration of its cross section
Stability The ability of a member to maintain its structural function when deformed
Strength, The crushing resistance of cylindrical specimens of concrete, compressive of prepared, cured and tested in accordance with the Standard concrete procedures prescribed in sections 3, 4 and 6 of NZS 3112: Part 2. This is normally denoted by the general symbol f´c
Strength,design The nominal strength multiplied by the appropriate strength reduction factor
Strength,lower That yield stress below which fewer than 5% of results fall when characteristicyield obtained in a properly conducted test programme. Refer to ofnon-prestressed AS/NZS 4671reinforcement
Strength, nominal The theoretical strength of a member section, calculated using the section dimensions as detailed and the lower characteristic reinforcement strengths as defined in this Standard and the specified compressive strength of concrete
Strength,over See Overstrength
Strength,probable The theoretical strength of a member section calculated using the expected mean material strengths as defined in this Standard.
NZS 3106:2009
15
Strengthreduction A factor used to multiply the nominal strength to obtain the factor design strength
Strength,specified A singular value of strength, normally at age 28 days unless compressiveof stated otherwise, denoted by the symbol f´c, which classifies concrete a concrete as to its strength class for purposes of design and construction. It is that level of compressive strength which meets the production Standards required by section 6 of NZS 3109
Strength,upper That maximum tensile strength below which greater than 95% characteristicbreaking of the results fall when obtained in a properly conducted test strengthofnon- programme prestressed reinforcement
Structural A term used to denote an element or elements which provide resistance to loads and forces acting on a structure
Structuraladequacy The ability of a member to maintain its structural function when exposed to fire
Structuralductility A numerical assessment of the ability of a structure to sustain factor cyclic inelastic displacements
Structuralperformance A factor which is used in the derivation of design earthquake factor forces in accordance with AS/NZS 1170.0 and NZS 1170.5 or other referenced loading Standard and 2.6.2.2 of NZS 3101 – Part 1
Surchargeloads Loads on the surface of the backfill of the tank wall which induces additional pressure on the wall
Tendon A steel element such as wire, cable, bar, rod, or strand which when tensioned imparts a prestress to a concrete member
Transfer Act of transferring stress in prestressing tendons from jacks or pre-tensioning bed to a concrete member
Ultimatelimitstate The state at which the design strength or ductility capacity of the structure is exceeded, when it cannot maintain equilibrium and becomes unstable
Wall Means a structural wall, a vertical thin member, usually planar, which because of its position, strength, shape, and stiffness, contributes to the rigidity and strength of a structure
C2.1 Definitions
NZS 3101 provides further guidance on definitions.
NZS 3106:2009
16
2.2 AbbREVIATIONS
For the purposes of this Standard the following abbreviations shall apply:NZBC New Zealand Building CodeNZSEE New Zealand Society for Earthquake EngineeringSLS Serviceability limit stateULS Ultimate limit state
2.3 NOTATION
2.3.1 Quantitysymboldefinition
The following notations are used in this Standard.
NOTE – Appendix B uses separate notations that are not included in 2.3.1.
Ac,eff effective concrete area
As cross-sectional area of reinforcement
a radius of a circular tank
b one half of the width of a rectangular tank, perpendicular to the direction being considered
C thermal stress coefficient from appropriate table
C(T )elastic site hazard spectrum for horizontal loading for the site subsoil type, and the relevant mode
Cd(Tc) horizontal design action for the first convective mode
Cd(T ) horizontal design action coefficient for mode i
Cd(TI) horizontal design action coefficient for the first impulsive mode
Ch(T ) spectral shape factor for the site subsoil type and the relevant mode, from NZS 1170.5
Ct creep factor
cs wave impact coefficient
D overall depth of a concrete cross section
d distance from the extreme compression fibre to the centroid of tension reinforcement
db nominal diameter of a bar, wire, or tendon
dmax maximum vertical displacement of the convective sloshing wave from the at-rest level of the liquid
E modulus of elasticity
Ec modulus of elasticity of concrete
Es modulus of elasticity of reinforcing steel MPa
Es1 earthquake load for serviceability limit state 1 (SLS1)
Es2 earthquake load for serviceability limit state 2 (SLS2)
Eu ultimate earthquake load
e base of natural logarithms (approximately 2.71828)
Fe earth pressure load
Fgw ground water load
F the equivalent static horizontal seismic force at a wall level
NZS 3106:2009
17
F p liquid pressure load
FP forces or stresses resulting from prestress
FR horizontal earthquake force from tank roof
Fsh forces or stresses resulting from shrinkage
Fsw forces or stresses resulting from swelling
FT forces or stresses resulting from temperature variation
f c characteristic compressive cylinder strength of concrete at 28 days
fcp compressive strength of concrete at transfer
fct.3 direct tensile strength of the concrete at three days
f equivalent static horizontal force per unit length at a wall level
f n thermal stress on the inside face of wall
fot thermal stress on the outside face of wall
fs tensile stress in non-tensioned reinforcing steel
fsr residual compression stress in reinforcement
ft principal tension stress
ft0 principal tension stress at wall centreline
fy yield strength of the reinforcement
G permanent action (self-weight or ‘dead action’)
H height of the tank wall to the surface level of the liquid
He height of the tank wall to the surface level of the soil
hc height of the centre of gravity of the convective weight
h’c equivalent height at which the convective weight is placed to give the total overturning moment arising from pressures on both the walls and base
hD hydrostatic head
hI height of the centre of gravity of the impulsive weight
h’I equivalent height from at which the impulsive weight is placed to give the total overturning moment arising from pressures on both walls and base
hR height of the centre of gravity of the roof
hW height of the centre of gravity of the wall
Icr cracked moment of inertia
Ig uncracked moment of inertia
kf(μ, )correction factor for NZS 1170.5 elastic site hazard spectrum to account for ductility and level of damping
LI Langelier Saturation Index
l
one half of the length of a rectangular tank in the direction being considered
M design moment action for ULS
MT moment due to thermal stress
MW total overturning moment acting at the level of the base of the wall immediately above the floor slab, from the hydrodynamic loads on the walls ➤
NZS 3106:2009
18
M′W total overturning moment acting on the floor slab, from the hydrodynamic loads on the floor and the walls
NT axial force due to thermal stress
N(T ,D) near fault factor, from NZS 1170.5
pb bouyancy pressure
pr pressure on roof due to convective wave
Q imposed load (due to occupancy and use, ‘live’ load) in accordance with AS/NZS 1170.1
Qv membrane shear force
qv shear force flow
Rreturn period factor for the relevant limit state and tank importance level and design life, from NZS 1170.5
RFreduction factor that accounts for the reduced section rigidity that accompanies concrete cracking
SFACT shape factor used for determining thermal stress coefficients (Appendix D)
Sp structural performance factor, to be taken as 1.0
Suultimate value of various loads appropriate for particular combinations in accordance with AS/NZS 1170.0
t thickness of the wall, roof or floor
TC period of vibration of the fundamental convective mode
T period of vibration of appropriate mode of response
TI period of vibration of the fundamental impulsive mode
u wave particle velocity
V shear force
VH total horizontal shear force at base of tank
VH horizontal seismic base shear associated with mode i (impulsive, convective, and so on)
VR horizontal earthquake force from roof
v shear stress
WC equivalent convective weight of the liquid contents
W equivalent weight of tank and liquid contents for the particular mode of vibration considered
WI equivalent impulsive weight of the liquid contents
WL total weight of the liquid contents
WR weight of the tank roof
WW weight of the tank walls
wbc equivalent convective unit weight at base of the wall
wb equivalent unit weight (impulsive or convective) at the base of the wall
wbI equivalent impulsive unit weight at the base of the wall
w equivalent unit weight on the tank wall of liquid contents for the impulsive or convective mode of vibration
wk mean crack width
wtc equivalent convective unit weight at the surface of the liquid
NZS 3106:2009
19
wt equivalent unit weight (impulsive or convective) at the surface of the liquid
wtI equivalent impulsive unit weight at the surface of the liquid
xm n concrete compression zone depth
Z seismic zone hazard factor, from NZS 1170.5
α1, α2 effective concrete area parameters
αC linear coefficient of thermal expansion of the concrete
∆σs increase in tendon stress once decompression occurs in a partially prestressed member
εs shrinkage or swelling strain
εsh shrinkage strain
εsw swelling strain
μ displacement ductility factor for impulsive modes
π ratio of the circumference of a circle to its diameter
δ angle to the earthquake direction
γe unit weight of soil
γl
unit weight of liquid
Ψc combination factor for imposed loads in accordance with AS/NZS 1170.0
Ψl
factor for determining quasi-permanent values (long-term) of loads in accordance with AS/NZS 1170.0
ξ damping level appropriate to mode of response
θ temperature change in tank wall
θA average temperature change in tank wall
θD differential temperature change in tank wall
θT total temperature change in tank wall
ρ ratio of tension reinforcement area to concrete area
ρm n minimum ratio of tension reinforcement area to concrete area
ρp ratio of total reinforcement area to effective concrete area
ρpm n minimum ratio of total reinforcement area to effective concrete area
NZS 3106:2009
20
3 GENERAL DESIGN REQUIREMENTS
3.1 DESIGN METhoDS
Tank design loads and load combinations are specified in section 4 and design methods for the serviceability limit state, the ultimate limit state and durability are specified in sections 5, 6, and 7 respectively.
The design should take account of the conditions of edge restraint at wall junctions with floor and roof.
C3.1
Serviceability rather than ultimate limit state considerations will commonly govern the design of liquid retaining structures.
All connections of wall with floor and roof exert some measure of restraint that affects wall design. Particular attention should be given to the translation and rotation restraint, the extent of which varies depending on the type of joint: fixed, hinged or free. Actual details may exhibit properties of one or more types at different stages of construction. Design calculations are generally based on the assumption that joints are either fully fixed or completely unrestrained against rotation and/or displacement. In reality such things as friction, soil movement and foundation deformation result in an intermediate degree of the implications of which may need to be assessed.
3.2 SUppoRT STRUcTURES
Support structures for elevated tanks shall be designed to the requirements of AS/NZS 1170.0 together with the appropriate design code for the material to be used.
3.3 TANkS SToRING poTAbLE wATER
Roofs and screens shall be provided to potable water tanks to prevent contamination and the entry of vermin.
3.4 pIpEwoRk
Pipework in the close vicinity of, attached to or located adjacent to the liquid retaining structure shall be designed to withstand applied actions including settlement of the tank, earthquake induced ground deformations, seismic forces and hydrodynamic seismic forces.
NZS 3106:2009
21
3.5 FREEbOARD
Provisions shall be made to accommodate the maximum wave oscillation generated by earthquake acceleration.
C3.5
The amount of freeboard required for design will vary. Where overtopping is tolerable no freeboard provision is necessary. Where loss of liquid must be prevented (for example, tanks for the storage of toxic liquids), or where overtopping may result in scouring of the foundation materials or cause damage to pipes and/or roof, then provisions should be made by:
(a) Freeboard allowance; and/or
(b) Designing the roof structure to resist the resulting uplift pressures.
The consequences of overtopping of the walls or damage to the roof under uplift pressure are unlikely to be as significant as damage to the walls and are unlikely to result in significant loss of liquid. Consideration may be given to using a lower seismic return period factor when checking overtopping or roof pressure than used for the design of the tank walls.
NZS 3106:2009
22
4 LOADS AND LOAD COMbINATIONS
4.1 GENERAL
The design of structures and members for stability, strength and serviceability shall take account of the load and load combinations for strength in accordance with AS/NZS 1170.0 and of the action effects directly arising from the loads and other actions included in this section.
C4.1
There are two broad types of loading: that resulting from the application of forces and that resulting from the application of deformation (strain). In a tank the force loading is exemplified by contained fluid pressure; the strain induced loads are temperature, shrinkage, and swelling.
4.2 LOADS AND OThER ACTIONS
4.2.1 Liquidpressure
The pressure from liquid at maximum overflow level based on the liquid specific gravity at the design temperature plus any internal vapour pressure above the liquid level.
C4.2.1
Overflow systems usually require a surcharge to initiate operation. In most cases the surcharge is small and can safely be ignored, that is, the overflow level is taken as the inlet level of the overflow pipe. Where the surcharge is likely to be large, the additional head should be included as a design load.
4.2.2 Earthpressure
The lateral pressure from earth backfill, symmetrical or asymmetrical. Net lateral loads, including those caused by unequal backfill, shall be determined by rational methods of soil mechanics based on foundation and soils investigations. Surcharge loads on backfilled surfaces shall be considered.
4.2.3 Temperature
The walls and roofs of tanks shall be designed for the action effect arising from differential temperature gradients through the member.
For tanks containing liquids at ambient temperature and subject to direct solar radiation, the design temperature gradients considered shall include the following cases:(a) For roofs: (i) A ±20 °C variation from the mean temperature, and (ii) The temperature criteria given in table 1.
C4.2.3(a)
Temperature stresses on the roof are in general small and of little significance unless the roof is cast monolithically with the wall. However roof support details should make provision for temperature-induced displacements.
NZS 3106:2009
28
4.4 NON-SyMMETRIC LOADS FOR CIRCULAR TANkS
For thin walled circular tanks (t/a < 0.03) non-symmetrical loads (such as temperature loads and hydrodynamic seismic pressures) may be considered to be rotationally symmetric and equal to the value at the section under consideration.
C4.4
Ambient thermal loads and hydrodynamic seismic pressures are not rotationally symmetric, but vary continually around the tank’s perimeter. Analyses have shown that this variation is generally low enough for stresses at any given section to depend only on the local temperature or pressure distribution.
4.5 LOAD COMbINATIONS FOR SERVICEAbILITy LIMIT STATE
The following combinations of actions for the serviceability limit states shall be considered: (a) Group A (long term) loads:
Wall: G + Fe + Fgw+ FP + (Fsh or 0.5Fsw) .............................(1)
G + F p + FP + 0.5Fsw ..................................................(2)
G + F p + Fe +Fgw+ FP + 0.5Fsw ..................................(3)
Roof: G + FP + Fsh ................................................................(4)
(b) Group B (short term) loads: Wall, tank full: G + F p + Fe +Fgw + FP + FT + 0.7Fsw .........................(5)
G + F p + Fe + Fgw + FP + (Es1 or Es2) .........................(6)
Wall, tank empty: G + Fe + Fgw + FP + FT + (0.7Fsh or 0.35Fsw) .............(7)
Roof: G + Q + FP + FT ...........................................................(8)
G + Fp + FT + (0.7Fsh or 0.7Fsw) .................................(9)
If a worse effect is obtained by the omission of one or more of the transient actions then this effect shall be taken into account.
NZS 3106:2009
29
C4.5
Transient loads that should be omitted, if beneficial, are shrinkage (Fsh ), swelling (Fsw ),
temperature (FT ) and groundwater (Fgw ).
The prestress force may vary between FPmax and FPm n, the maximum and minimum due to in-time losses respectively. To ensure that the more adverse condition is
incorporated in design, both FPmax and FPm n should be considered in the load combinations.
(a) Group A loads. Group A load cases are permanent loads plus variable loads of long duration; or permanent loads plus frequently repetitive loads. Shrinkage is a long duration load. Swelling can be either short or long duration; this is accounted for in the load factor. Load case (1) equally applies for shrinkage and swelling; shrinkage applies when the tank is empty prior to filling, swelling applies when the tank is emptied for maintenance. For buried tanks it is necessary to consider the possibility of test loading prior to backfilling (load case (2)).
(b) Group B loads. Group B load cases are permanent loads plus infrequent combinations of transient loads. Load case (7) applies equally to shrinkage and swelling; shrinkage – tank empty prior to filling, swelling – tank empty for maintenance. The earthquake load for AS/NZS 1170.0 serviceability limit state 1
(Es1) or limit state 2 (Es2) should be applied depending on the importance level of the structure. It is considered to be overly conservative to combine the very short duration earthquake serviceability loads with other transient loads.
4.6 LOAD COMbINATIONS FOR ULTIMATE LIMIT STATE
The following combinations for the ultimate limit states shall be considered:
Wall 1.2G + 1.2F p .........................................................................(10)
1.2G + 1.5 Fe + 1.5 Fgw ......................................................... (11)
1.2G + 1.2 F p + 1.5Fe + 1.5 Fgw ...........................................(12)
G + Eu + F p ...........................................................................(13)
G + Eu + F p + Fe + Fgw .........................................................(14)
Roof 1.35G .....................................................................................(15)
1.2G + 1.5Q ...........................................................................(16)
1.2G + 1.5Ψl
Q .......................................................................(17)
G + Eu + ΨcQ .........................................................................(18)
1.2G + Su + ΨcQ ...................................................................(19)
Wind loads shall be considered for lightweight roofs.
C4.6
The strain induced loads: temperature, shrinkage, swelling, and prestress, will not significantly affect the ultimate strength of a structure and hence do not need to be considered at the ultimate limit state.
NZS 3106:2009
31
For intermediate values of hD/t, linear interpolation between 0.2 mm and 0.05 mm may be used.
The extent of cracking shall be controlled by limiting the tensile stress in the reinforcing steel in accordance with 5.2 of this Standard.
C5.1.1
It should be noted that all concrete will permit the passage of small quantities of liquids and gases by diffusion.
The tightness classes of the walls and floor in the same tank may be different.
The permissible crack width for tightness class 1 is related to the pressure gradient across the section. Limitation of the crack widths to these values should result in the effective sealing of the cracks by autogenous healing within a relatively short time. It should be noted that concrete containing supplementary cementitious materials, for example fly ash, may take longer to heal due to slower rate of hydration and a smaller crack width may therefore be required to achieve the required tightness class.
5.1.2 Minimumcompressionzonedepth
To provide adequate assurance for structures of tightness classes 2 or 3 that cracks do not pass through the full width of a section, the design value of the depth of the compression zone should be at least xm n calculated for the Group A (long term) combination of actions. Where a section is subjected to alternate actions, cracks should be considered to pass through the full thickness of the section unless it can be shown that some part of the section thickness will always remain in compression. This thickness of concrete in compression should normally be at least xm n under all appropriate combinations of actions. The action effects may be calculated on the assumption of linear elastic material behaviour. The resulting stresses in a section should be calculated assuming that concrete in tension is neglected.
The recommended value for xm n is the lesser of 50 mm or 0.2t where t is the element thickness.
5.1.3 Movementjoints
Movement joints shall be provided as necessary to ensure that design assumptions are realised. Provision shall be made for displacement and rotation without loss of contents.
C5.1.3
A movement joint is a specially formed joint intended to accommodate relative movement between adjoining parts of a structure, special provision being made for maintaining the watertightness of the joint. Movement joints may be of the following types:
(a) Contraction joint. This is a movement joint which has a deliberate discontinuity but no initial gap between the concrete on both sides of the joint. The joint is intended to permit contraction of the concrete.
A distinction should be made between a complete contraction joint, in which both the concrete and reinforcement are interrupted, and a partial contraction joint, in which only the concrete is interrupted while the reinforcement is continued through the joint. ➤
NZS 3106:2009
33
5.2 REINFORCED CONCRETE
5.2.1 Controlofcracking
The structure shall be designed so that maximum calculated crack widths from early-age thermal strains or the imposed loads and actions specified in section 4, meet the requirements for leak control and durability.
C5.2.1
It has not been normal practice to add early-age thermal crack widths to those arising from structural loading, with no reported detriment to performance (CIRIA C660).
The early-age crack control provisions in this section are for fully restrained concrete with normal mix designs. The extent of cracking and amount of crack-control reinforcement can be reduced by removing or reducing restraints, limiting the temperature rise due to hydration of the cement and other methods. Guidelines are given in CIRIA C660.
5.2.2 Effectivereinforcementratio
The effective reinforcement ratio shall be calculated using the following equation:
ρp = As/Ac,eff ...................................................................................................... (Eq.5.1)
where Ac,eff is the effective concrete area as shown in figure 2 (α2= 0.5D, but not greater than 250 mm, except for the surface of the slab that is in contact with the ground, then not greater than 100 mm.)
Figure 2 – Effective concrete area
5.2.3 Minimumreinforcementratioforcontrolofearly-agethermalcracks
The minimum reinforcement ratio shall be determined from:
....................................................................................................(Eq.5.2)
Where
ρpm n = minimum reinforcement ratio
fct.3 = direct tensile strength of concrete at three days
fy = yield strength of the reinforcement
NZS 3106:2009
34
C5.2.3
This minimum reinforcement is required to control crack spacing and hence crack widths, by preventing the yielding of the reinforcement when early-age thermal cracks form.
fct.3 is the mean value of the tensile strength of the concrete at the time when the cracks may first be expected to occur. The values are given by the relationship from 3.1.2 of BS EN1992-1-1. Estimated values are set out in table C5.2.3:
Table C5.2.3 – Mean tensile strength of concrete at three days
Concrete strength
f´c (MPa)
20 25 30 35 40 45 50 55 60
fct.3 (MPa) 1.32 1.53 1.73 1.92 2.10 2.27 2.44 2.52 2.61
5.2.4 Reinforcementratiosforcontrolofearly-agethermalcracks
The reinforcement ratio for 0.05 mm, 0.1 mm, 0.15 mm, and 0.2 mm mean crack widths are given in table 4.
Table 4 – Reinforcement ratio for fully restrained concrete
db(mm) ρpmin(%)
0.05 mm 0.10 mm 0.15 mm 0.20 mm
<12 2.0 0.78 0.48 0.35
16 2.7 1.0 0.64 0.47
20 3.4 1.3 0.80 0.58
25 4.2 1.6 1.0 0.73
32 5.4 2.1 1.3 0.93
C5.2.4
The reinforcement ratios in table 4 are for fully restrained concrete calculated in accordance with the method given in Appendix B. Refer to CIRIA C660 for other restraint conditions.
5.2.5 Crackingfromimposedloadsandactions
The size of cracks shall be controlled by limiting the tensile stress in the reinforcing steel (fs) under the most severe combination of service loads as follows:
For Group A (long term) loads fs shall be limited so that calculated crack widths meets the liquid tightness class requirements, and the requirements for durability (see section 7).
For Group B (short term) loads except combinations including ES2 ........... fs < 240 MPa
For Group B (short term) load combinations including ES2 ......................... fs < 0.9fy
NZS 3106:2009
35
Provisions for the design of reinforcement to control cracking are given in Appendix B.
Limiting stresses in steel reinforcement calculated in accordance with Appendix B for a range of mean crack widths are given in table 5 and table 6.
Table 5 – Limiting stresses in steel reinforcement where compression zone depth complies with 5.1.1
db(mm)fs(MPa)
0.2 mm 0.3 mm 0.4 mm<12 180 270 34016 150 230 30520 130 200 26525 115 170 22532 95 140 190
NOTE – The steel stress should not exceed 0.8 fy
Table 6 – Limiting stresses in steel reinforcement where compression zone depth is less than 5.1.1
db(mm)fs(MPa)
0.05 mm 0.10 mm 0.15 mm 0.20 mm<12 27 53 80 10516 21 43 64 8520 18 35 53 7025 15 30 45 6032 12 24 36 48
C5.2.5
The limiting steel stresses given in table 5 and table 6 have been calculated in accordance with the method given in Appendix B. The reinforcement was assumed to be in two equal layers and at 50 mm cover. The values in the tables should be conservative for reasonable section thicknesses and reinforcement contents, but may be unconservative for high reinforcement contents or cover exceeding 50 mm. As an alternative to limiting the steel stress to the value given in the tables, crack widths may be calculated directly using the method in Appendix B.
Larger crack widths are allowed for the Group B (short term) loads.
5.2.6 Stiffnessofcrackedsection
Strain induced forces (such as thermal and shrinkage) in the walls of circular reservoirs may be calculated on the basis of an uncracked section and reduced by a factor RF representing the local reduction in stiffness resulting from cracking in each direction.
A more rigorous approach, including an analysis of the cracked section stiffness and/or finite element analysis may be used and may be less conservative than the use of RF.
NZS 3106:2009
36
Figure3–Reductionofstiffnessofdoublyreinforcedwalloncracking(including tensionstiffeningeffect)
C5.2.6
Although curvatures caused by strain induced loads (temperature and shrinkage) are insignificant as a proportion of the ultimate deformation, they may be large compared to elastic loadings at design load level. Hence, although temperature or shrinkage will not significantly affect the ultimate capacity of the tank, they may severely bear on the serviceability of the structure.
Increasing temperature or shrinkage subject the concrete to increasing stresses until the cracking strength of the section is reached. Further increase in stress is accompanied by a decrease in section rigidity as the crack propagates. A point is eventually reached where the crack propagation stops because the section reaches a rigidity capable of resisting the stress without further deformation. This stress is somewhat less than that calculated assuming an uncracked section and can be assessed simply, and with sufficient accuracy, by factoring the uncracked section moments and axial forces
by a reduction coefficient RF representing the reduction in stiffness with cracking.
This reduction factor is given by the ratio of the cracked moment of inertia Icr to the
uncracked moment of inertia Ig adjusted for tension stiffening in the concrete. Values
of RF are plotted in figure 3 for a range of wall thickness and steel ratios.
The Icr values used in tabulating RF ignore the presence of axial forces. This omission is necessary to maintain simplicity, however the resulting errors are expected to be small and on the conservative side. Specifically, axial tension would further reduce section stiffness with a corresponding decrease in thermal and/or shrinkage stresses. Axial compression on the other hand increases section stiffness with a corresponding increase in stresses. However, unless allowable compressive stresses are exceeded in the concrete, this load case is unlikely to result in an adverse service condition. Refer to Vitharana and Priestley (1998 and 1999) for further discussion on the effect of cracking on thermal loading.
NZS 3106:2009
37
The ratio Icr/Ig depends on wall thickness and reinforcement content. Because these parameters, the latter in particular, may vary with wall height, it may be necessary to
calculate RF values for each critical section of the wall, that is, where there is a change of wall thickness or steel content.
Tension stiffening significantly increases the stiffness above that calculated at a crack. Limited experimental and theoretical evidence for slabs indicates that the stiffening effect decreases with increasing reinforcement content ρ, and with increasing moment level (after cracking). Approximate maximum figures are 100 % increase at ρ = 0.005 and 30% increase at ρ = 0.02. Because of its significance, tension stiffening has been
included in the derivation of the RF values.
5.3 pRESTRESSED CONCRETE
5.3.1 General
All prestressing tendons shall be bonded.
C5.3.1
In the case of circular prestressed tanks, care needs to be taken to avoid the possibility of local failures due to the tendons breaking out through the inside cover. In general, this will be avoided if the theoretical centroid of the horizontal cables lies in the outer half of the wall.
The diameter of a duct within a wall should generally not exceed 0.25. times the wall thickness. The prestressing force on a wall should be distributed as evenly as possible. Anchorages or buttresses should be so arranged as to reduce the possibilities of uneven force distribution unless specific measures are taken to take the effects into account.
5.3.2 Analysis
In addition to the requirements of section 4, the analysis shall take account of the full effects of prestressing including secondary effects and time-dependent creep effects. Analysis shall be carried out for the following load conditions and combinations:(a) Conditions at any stage of prestress;(b) Group A load combination that comprises predominantly long-term loads;(c) Group B load combination that includes the short-term transient loads.
5.3.3 Limitingconcretestressesforserviceability
Except as permitted by 5.3.5 and for load combinations that include ES2, stresses shall be calculated on the basis of uncracked sections, and shall remain within the limits specified in table 7.
For Group B (short term) load combinations including ES2, fs < 0.9fy
NZS 3106:2009
42
C5.3.6
Tanks constructed with wound tendons which are stressed by drawing the tendon through a die are subject to variable prestress due to variations in wire diameter as supplied and to wear of the die. Such a method will not consistently meet the requirement for uniform prestress.
The protection of the prestressing wires is crucial to the satisfactory long term performance of the tank. Poorly placed shotcrete coatings can have voids along the wires due to a shadow effect. Such voids can collect and transmit water leading to corrosion and early failure of the tank.
Good construction practice for the application of shotcrete is described in ACI 344R-70.
NZS 3106:2009
46
7 DESIGN FOR DURAbILITyDurability shall be allowed for in design by determining the exposure classification and, for that exposure classification, complying with the appropriate requirements for:(a) Concrete quality and curing;(b) Cementitious binder composition;(c) Cover;(d) Chemical content restrictions;(e) Alkali silica reaction precautions;(f) Protection of fixings;
all in accordance with NZS 3101 for a 50-year or 100-year design life.
Exposure classification shall be determined from table 8 and NZS 3101.
C7
For liquids having a detrimental effect on concrete, appropriate special precautions may include the provision of linings impervious to the liquid to be contained. Particular attention should be paid to any joints in the lining which must remain impervious for the life of the structure, for much damage can occur before a leak is detected.
The air space below roof soffits is often at 100% humidity and the slab is exposed to severely corrosive conditions. Thus the roof slab should be designed with the same crack control philosophy as for the rest of the structure.
NZS 3106:2009
48
AppENDIX A – EARThQUAkE ACTIONS(Normative)
A1 GENERAL
The structure shall be designed for the forces resulting from earthquake accelerations of equivalent hydrodynamic mass, structure mass and external mass responding with the structure.
The equivalent hydrodynamic mass comprises two components:(1) The impulsive mass representing the portion of the contents accelerating with the
tank, and (2) The convective mass representing the portion of the contents oscillating in the
tank.
CA1
The forces on a tank under earthquake motion are a combination of hydrostatic water pressure, tank wall and roof inertia forces, and hydrodynamic forces resulting from the interaction of the tank structure with the liquid contents.
The hydrodynamic effects can most conveniently be included by adding to the structure mass, ‘equivalent masses’ to represent the effects of the contents on the dynamic response of the structure. This equivalent mass approach has been adopted in this Standard. Reference should be made to the New Zealand Society for Earthquake Engineering (NZSEE), Seismic design of storage tanks for more detail on the seismic response of tanks and the derivation of the procedures specified in this Standard.
A2 EARThQUAkE ACTIONS
A2.1 Baseshear
The horizontal seismic shear acting at the base of the tank, associated with a particular mode of vibration, shall be calculated from the expression:
VH = Cd(T )W
where Cd(T ) = C(T )kf (μ,ξ )Sp
C(T ) = Ch(T ) ZRN(T ,D)
and VH = horizontal base shear associated with mode i (impulsive, convective, and so on).
W = equivalent weight of tank and contents responding in particular mode of vibration considered. (NOTE – weight is used rather than mass for consistency with NZS 1170.5.)
Cd(T ) = horizontal design action coefficient for mode i.
C(T ) = elastic site hazard spectrum for horizontal loading for the site subsoil type, and the relevant mode.
NZS 3106:2009
52
A2.2.2Convectivemodes
The period of the convective modes shall be determined from figure A3.
FigureA3–Dimensionlessperiodforfundamentalsloshingmodel
A2.3 Equivalenthydrodynamicweights
The total equivalent impulsive weight, WI and the total equivalent convective weight WC, and their respective heights to centres of gravity hI and hC shall be calculated from figure A4.
NZS 3106:2009
53
FigureA4–Equivalentweightsofimpulsiveandconvectivecontents(circular andrectangulartanks)
A2.4 Verticaldistributionofequivalentweights
Analysis of the earthquake response of the tank shall be based on distributions of the impulsive and convective equivalent weight that vary linearly from wt at the surface of the liquid to wb at the base,
where
and
NZS 3106:2009
54
FigureA5–Equivalentweightdistribution
CA2.4
Vertical equivalent weight distributions are of the form shown by the ‘exact’ curves in figure A5. The equivalent linear distributions, although a simplification of the actual distribution, are sufficiently accurate for design purposes, and form the basis of the
equations for wt and wb . Note that 50% of the total weight W is assigned to each side of the tank.
A2.5 Convectivewaveheight
The maximum vertical displacement dmax of the convective sloshing wave from the at-rest level of the liquid shall be given by:
dmax = 0.84aCd(TC) for circular tanks
and dmax = l Cd(TC) for rectangular tanks
where a = radius of tank
l = one half of length of rectangular tank in direction being considered
Cd(TC) = the convective mode Cd as defined in A2 and based on:
μ = 1.0
ξ = 0.5%
NZS 3106:2009
56
A3 STRUCTURAL ANALySIS
A3.1 Methodsofanalysis
A structural analysis to determine the action effects shall be carried out in accordance with one of the methods specified in NZS 1170.5.
CA3.1
Normally the equivalent static method would be used, but the modal response spectrum and the numerical integration time history methods could also be used.
The formulation of the equivalent impulsive weights in Appendix A is based on a rigid wall tank. However analyses have shown (for example, Veletsos and Shivakumar (1997)) that the equivalent mass representing the interaction of a rigid structure can be used to account for the hydrodynamic effects for all modes of non-rigid structures to an acceptable degree of accuracy.
A3.2 Combinedactions
The combined impulsive and convective action effects shall be taken as the square root of the sum of the squares of the separate effects.
CA3.2
The periods of the inertia and convective responses are generally widely separated, the impulsive period being much shorter than the convective period. When responses are widely separated, near-simultaneous occurrence of peak values could occur. However the convective response takes much longer to build up than the impulsive response, consequently the impulsive component is likely to be subsiding by the time the convective component reaches its peak. It is thus recommended that the combined impulsive and convective responses be taken as the square root of the sum of the squares of the separate components.
A3.3 Equivalentstaticmethod:horizontalactions
A3.3.1 Horizontalseismicshear
The total horizontal seismic shear VH acting at the base of the tank is:
.......................... (Eq.A1)
where Cd(TI) and Cd(TC) are the impulsive and convective seismic coefficients respectively as defined in section A2.
WI and WC are the total equivalent impulsive and convective weights respectively as defined in section A2.
WW and WR are the tank wall and roof weights respectively.
NZS 3106:2009
58
A3.3.3 Horizontaldistributionofhydrodynamicforces
In the absence of a more rigorous analysis which takes into account the exact and complex horizontal variations in hydrodynamic pressures, analysis of the earthquake response of the tank shall be based on circumferential/horizontal distributions of the impulsive and convective forces f per unit length of wall as shown in figure A6,
where f = 2F /πa for circular tanks
f = F /2b for rectangular tanks
FigureA6–Horizontalforcedistribution
CA3.3.3
Circumferential force distribution can be represented by a sinusoidal variation for a
circular tank where f is the peak force per unit length.
The horizontal force distribution for a rectangular tank is uniform.
A3.3.4 Seismicactionsonwalls
The effect of the individual actions on the tank walls (hoop forces, membrane forces, bending moments and shear forces) shall be computed from structural analysis models or from Standard design charts.
The individual effects shall be combined in accordance with A3.2.
For thin walled circular tanks (t/a < 0.03), the non-rotationally symmetric hydrodynamic loads may be considered to be rotationally symmetric and equal to the value at the section under consideration.
NZS 3106:2009
59
CA3.3.4
Hydrodynamic forces on circular tanks are not rotationally symmetric but vary continually around the tank’s perimeter (see figure A6). Analyses have shown that this variation is generally small enough for stresses at any given section to depend only on the local force distribution. This significantly simplifies the analysis of the effect of these non-symmetric forces.
A3.3.5 Overturningmomentabovefloorslab
The total overturning moment acting at the level of the base of the wall immediately above the floor slab shall be determined by:
.................(Eq.A2)
where hC = height to the centre of gravity of the convective weight from figure 4
hI = height to the centre of gravity of the impulsive weight from figure 4
hW = height to centre of gravity of the wall
hR = height to centre of gravity of roof
CA3.3.5
This moment, with ordinary beam theory, can be used to calculate the axial force at the base of the wall and hence on the wall footing.
A3.3.6 Overturningmomentonfloorslab
The total overturning moment acting on the floor slab from the hydrodynamic loads on the floor and the walls shall be determined by:
......... (Eq.A3)
where h'I = the equivalent height from figure A7 at which the impulsive weight is placed to give the total overturning moment arising from pressures on both the walls and base.
h'C = the equivalent height from figure A7 at which the convective weight is placed to give the total overturning moment arising from pressures on both the walls and base.
NZS 3106:2009
60
FigureA7–Equivalentheightsofimpulsiveandconvectiveweightsfor overturning(circularandrectangulartanks)
CA3.3.6
Moment M'w can be used to calculate the bearing pressures on the ground beneath the floor slab.
A3.4 Verticalseismicactions
Vertical seismic actions shall be considered to act concurrently with horizontal seismic actions. The combined horizontal and vertical action effects shall be taken as the square root of the sum of the squares of the separate effects.
CA3.4.
The effect of vertical ground motion is to alter the internal pressure exerted by the contained liquid; an upward acceleration of the tank will cause an increase in pressure. The incremental stresses caused by a vertical acceleration are identical in distribution to those produced by the static liquid load while their magnitudes are some proportion thereof. For example, an upward earthquake acceleration of 0.25 g produces incremental stresses whose magnitude is 25% of the static liquid containment stresses.
The peak horizontal and vertical seismic effects are combined by their root mean square to account for the reduced probability of their concurrence.
NZS 3106:2009
61
A3.5 Waterpressureonroof
If the freeboard is less than the height of the convective waves, then hydrodynamic pressures will be generated on the roof.
The total pressure on the roof will be the result of both wave impact and a varying buoyancy that results from the wave peak running up the roof slope. The total pressure is given by:
pr = pb + cs u2 γl
/2g
where pb = buoyancy pressure
cs = wave impact coefficient
u = wave particle velocity
The roof shall be designed to withstand water pressures due to the convective sloshing waves, and an approximate graphical method of evaluating pb is shown in Figure A8. An upper bound to cs is about 5.0 and the approximate maximum value of u can be obtained from:
u = 2π dmax/TC
FigureA8–Approximatemethodforestimatingbuoyancypressureonroof
NZS 3106:2009
62
AppENDIX b – DESIGN OF REINFORCEMENT TO CONTROL CRACkING(Normative)
NOTE – Appendix B has been adopted from BS EN 1992-1-1. All notation in Appendix B is separate from the 2.3 notation list.
b1 CALCULATION OF CRACk WIDThS
B1.1
The crack width, wk may be calculated from equation (B1):
wk = Sr,max (εsm – εcm) ...................................................................................... (Eq.B1)
Where
Sr,max is the maximum crack spacingεsm is the mean strain in the reinforcement under the relevant combination of loads, including the effect of imposed deformation and taking into account the effects of tension stiffening. Only the additional tensile strain beyond the state of zero strain of the concrete at the same level is consideredεcm is the mean strain in the concrete between cracks
B1.2
εsm – εcm may be calculated from the expression:
........................................... (Eq.B2)
whereσs is the stress in the tension reinforcement assuming a cracked section. For pretensioned members, σs may be replaced by ∆ σp the stress variation in prestressing tendons from the state of zero strain of the concrete at the same level
αe is the ratio Es / Ecm
f ct,eff is the mean value of the tensile strength of the concrete effective at the time when the cracks may first be expected to occur:
f ct,eff = f ctm (or lower if cracking is expected earlier than 28 days) refer to table B2
ρp,eff (As + ξ12 Ap’) / Ac,eff ........................................................................ (Eq.B3)
As is the area of reinforcing steel
Ap’ is the area of pre or post-tensioned tendons within
Ac,eff is the effective area of concrete in tension surrounding the reinforcement or prestressing tendons of depth hc,ef , where hc,ef is the lesser of 2.5(h-d), (h-x/3) or h/2 (see figure B1)
NZS 3106:2009
63
ξ1 is the adjusted ratio of bond strength taking into account the different diameters of prestressing and reinforcing steel
if only prestressing steel is used to control cracking, 1
ξ ratio of bond strength of prestressing and reinforcing steel, according to table B1
φs largest bar diameter of reinforcing steel
φp equivalent diameter of tendon
φp = 1.6 for bundles, where Ap is area of prestressing tendon or tendons
φp = 1.75 φw re single 7 wire strands where φw re is the wire diameter
φp = 1.20 φw re single 3 wire strands where φw re is the wire diameter
kt is a factor dependent on the duration of the load
kt = 0.6 for short term loading, and 0.4 for long term loading
Table B1 – Ratio of bond strength
Prestressing steel ξPre-tensioned Bonded,post-tensioned
≤C50/60 ≥C70/85Smooth bars and wires Not applicable 0.3 0.15Strands 0.6 0.5 0.25Indented wires 0.7 0.6 0.3Ribbed bars 0.8 0.7 0.35NOTE – For intermediate values between C50/60 and C70/85 interpolation may be used.
NZS 3106:2009
64
figure B1 – Effective tension area
Table B2 – Strength and deformation characteristics for concrete
f´c 25 30 35 40 45 50 55 60 70 80
fcm33 38 43 48 53 58 63 68 78 88
fctm2.6 2.9 3.2 3.5 3.8 4.1 4.2 4.4 4.6 4.8
Ecm31 33 34 35 36 37 38 39 41 42
f´c is the characteristic compressive cylinder strength of concrete at 28 days.
fcm is the mean value of concrete cylinder compressive strength
fctm is the mean value of axial tensile strength
Ecm is the secant modulus of elasticity
B1.3
In situations where bonded reinforcement is fixed at reasonably close centres within the tension zone (spacing ≤ 5(c + φ / 2), the maximum final crack spacing may be calculated from equation B4 (see figure B2).
NZS 3106:2009
65
FigureB2–Crackwidth,w,atconcretesurfacerelativetodistancefrombar
Sr,max = k3c + k1k2k4φ / ρp,eff ............................................................................ (Eq.B4)
where
φ is the bar diameter. Where a mixture of bar diameters is used in a section, an equivalent diameter, φeq , should be used. For a section with n1 bars of diameter φ1 and n2 bars of diameter φ2, the following expression should be used:
...................................................................... (Eq.B5)
c is the cover to the longitudinal reinforcement
k1 is a coefficient which takes account of the bond properties of the bonded reinforcement: = 0.8 for high bond bars
= 1.6 for bars with an effectively plain surface (for example, prestressing tendons)
k2 = is a coefficient which takes account of the distribution of strain:
= 0.5 for bending
= 1.0 for pure tension
NZS 3106:2009
66
For cases of eccentric tension or for local areas, intermediate values of k2 should be used which may be calculated from the relation:
k2 = (ε1 + ε2 ) / 2 ε1 ............................................................................................ (Eq.B6)
Where
ε1 is the greater and ε2 is the lesser tensile strain at the boundaries of the section considered, assessed on the basis of a cracked section
k3 = 3.4
k4 = 0.425
Where the spacing of the bonded reinforcement exceeds ≤ 5(c + φ / 2) (see Figure B2) or where there is no bonded reinforcement within the tension zone, an upper bound to the crack width may be found by assuming a maximum crack spacing:
Sr,max = 1.3 (h – x) ............................................................................................. (Eq.B7)
B1.4
Where the angle between the axes of principal stress and the direction of the reinforcement, for members reinforced in two orthogonal directions, is significant (>15°), then the crack spacing may be calculated from the following expression:
................................................................. (Eq.B8)
whereθ is the angle between the reinforcement in the y direction and the direction of the principal tensile stress
Sr,max,y Sr,max,z are the crack spacings calculated in the y and z directions respectively,
according to B1.3.
NZS 3106:2009
67
AppENDIX C – TESTING(Informative)
C1 GENERAL
Inspection and testing for safety, serviceability and durability should be carried out on completion of construction.
NOTE – Inspections should be carried out at regular intervals (maximum five years) during the service life of the structure.
C2 TESTING FOR LIQUID TIGhTNESS
At an appropriate time after completion of construction, the structure or section thereof as considered necessary should be tested for liquid-tightness in accordance with C3 and C4.
C3 TESTING OF LIQUID RETAINING STRUCTURES
For a test of liquid retention, a structure should be cleaned and initially filled with the specified liquid (usually water) at a uniform rate generally not greater than 2 m in 24 h.
Structures should not be backfilled unless specified.
When first filled, the liquid level should be maintained by the addition of further liquid for a stabilizing period of 7 days while absorption and autogenic healing takes place. After the stabilizing period, the level of the liquid surface shall be recorded at 24 h intervals, for a test period of 7 days. During this 7-day test period, the total permissible drop in level, after allowing for evaporation and rainfall (if the test is made for an uncovered structure) shall not exceed 1/500th of the average water depth of the full tank or 10 mm, whichever is less.
If at the end of the 7 days, the structure does not satisfy the condition of the test, and the daily drop in water level is decreasing, the period of test may be extended for a further 7 days and if the specified limit is not exceeded, the test may be considered satisfactory.
Notwithstanding the satisfactory completion of the test, any evidence of seepage of the liquid to the outside faces of the liquid-retaining walls or intensified underdrain flow should be assessed against the liquid tightness requirements of section 5. Any necessary remedial treatment of the concrete to the cracks or joints should, where practicable, be carried out from the liquid face. When a remedial lining is applied to inhibit leakage at a crack it shall have adequate flexibility and have no reaction with the stored liquid.
Where the structure fails to satisfy the 7-day test then, after completion of the remedial work, it should be refilled and a further 7-day test undertaken in accordance with this clause.
NZS 3106:2009
68
C4 TESTING OF ROOFS
Where applicable, the roofs of liquid-retaining structures should be watertight and should, where practicable, be tested on completion by flooding the roof with water to a minimum depth of 25 mm for a period of 24 h or longer if so specified. Where it is not possible, to contain 25 mm depth of water, because of roof falls or otherwise, a hose or sprinkler system should provide a sheet flow of water over the entire area of the roof for a period of not less than 6 hours. In either case, the roof shall be considered satisfactory if no leaks or damp patches show on the soffit. Where the structure fails to satisfy either of these tests, then after the completion of the remedial work it should be retested in accordance with this clause. The roof covering, if any, should be completed as soon as possible after satisfactory testing.
NZS 3106:2009
69
AppENDIX D – ThERMAL STRESS COEFFICIENTS
(Normative)
D1 GENERAL
D1.1
This Appendix gives tables of values of vertical and hoop thermal stress coefficients in the wall of a cylindrical tank at different heights in the wall and for different shape factors, where the shape factor is defined by:
SFACT = H2 / 2a.t
D1.2
Tables are given for three thermal conditions as set out in D2, D3 and D4, and for three base conditions: Table D1: Pinned-base condition Table D2: Fixed-base condition Table D3: Sliding-base condition.
D1.3
The stresses given in this Appendix apply to an uncracked wall. Where the wall is designed on the basis of a cracked-section analysis, the forces and moments implied by the stresses may be reduced to reflect the reduced stiffness resulting from cracks, in accordance with C4.2.3.
D2 AVERAGE TEMpERATURE ChANGE
Uniform temperature change of θATables assume θA is a temperature increase Reverse sign for temperature decrease.
D3 DIFFERENTIAL TEMpERATURE ChANGE
Differential temperature change of ±θD (see figure D1).The total gradient through wall = 2θDTables assume outside hotter than inside. Reverse sign for inside hotter than outside.
FigureD1–Differentialtemperaturechange
NZS 3106:2009
70
D4 TOTAL TEMpERATURE ChANGE
Temperature variation on outside surface only = θT (see figure D2).Tables assume outside hotter than inside. Reverse sign for outside colder than inside.
FigureD2–Totaltemperaturechange
D5 STRESSES
Thermal stress is given by:
f = C.Ec αc θ
where C = Thermal coefficient from appropriate table
Ec = Modulus of elasticity of the concrete
αc = Linear coefficient of thermal expansion of the concrete
θ = θA, θD or θT appropriate.
The sign convention used in the tables is tension positive. Vertical stress is given for the inside surface. Reverse the sign for the outside surface.
NZS 3106:2009
71
Table D1 – Thermal stress coefficients – Pinned-base condition
(a) Vertical thermal stress – Average temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.000 -0.022 -0.079 -0.175 -0.274 -0.379 -0.478 -0.526 -0.492 -0.348 0.0003.000 0.000 -0.014 -0.065 -0.144 -0.227 -0.331 -0.457 -0.547 -0.551 -0.400 0.0004.000 0.000 -0.005 -0.034 -0.077 -0.158 -0.274 -0.398 -0.523 -0.566 -0.442 0.0005.000 0.000 0.000 -0.006 -0.036 -0.096 -0.204 -0.342 -0.480 -0.564 -0.468 0.0006.000 0.000 0.000 0.000 -0.014 -0.058 -0.137 -0.281 -0.446 -0.562 -0.490 0.0008.000 0.000 0.000 0.000 0.019 0.000 -0.067 -0.192 -0.365 -0.547 -0.518 0.000
10.000 0.000 0.000 0.000 0.024 0.012 -0.024 -0.132 -0.300 -0.516 -0.540 0.00012.000 0.000 0.000 0.000 0.014 0.029 0.000 -0.072 -0.245 -0.461 -0.562 0.00014.000 0.000 0.000 0.000 0.017 0.017 0.017 0.000 -0.202 -0.437 -0.554 0.00016.000 0.000 0.000 0.000 0.000 0.019 0.038 0.077 -0.154 -0.422 -0.557 0.000
(b) Vertical thermal stress – Differential temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.000 0.072 0.234 0.417 0.592 0.697 0.728 0.665 0.531 0.306 0.0323.000 0.000 0.109 0.346 0.605 0.832 0.969 1.007 0.921 0.727 0.425 0.0524.000 0.000 0.139 0.428 0.733 0.978 1.129 1.165 1.066 0.838 0.484 0.0415.000 0.000 0.165 0.494 0.825 1.080 1.226 1.255 1.153 0.910 0.522 0.0276.000 0.000 0.189 0.549 0.895 1.143 1.282 1.305 1.203 0.756 0.551 0.0168.000 0.000 0.233 0.644 0.991 1.218 1.335 1.327 1.260 1.028 0.603 0.002
10.000 0.000 0.277 0.725 1.060 1.251 1.335 1.349 1.286 1.082 0.653 -0.00112.000 0.000 0.320 0.797 1.116 1.266 1.321 1.335 1.297 1.125 0.702 -0.00214.000 0.000 0.359 0.891 1.159 1.272 1.304 1.319 1.302 1.161 0.745 -0.00116.000 0.000 0.397 0.916 1.191 1.274 1.287 1.301 1.304 1.187 0.786 -0.001
(c) Hoop thermal stress, inside – Average temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.205 0.156 0.107 0.141 -0.038 -0.134 -0.267 -0.426 -0.609 -0.812 -1.0003.000 0.074 0.076 0.069 0.049 0.008 -0.054 -0.163 -0.319 -0.524 -0.762 -1.0004.000 0.017 0.036 0.047 0.053 0.040 -0.004 -0.093 -0.341 -0.455 -0.723 -1.0005.000 -0.008 0.014 0.034 0.050 0.052 0.025 -0.045 -0.180 -0.399 -0.690 -1.0006.000 -1.011 0.003 0.023 0.040 0.053 0.041 -0.012 -0.137 -0.354 -0.661 -1.0008.000 -0.015 -0.004 0.008 0.027 0.043 0.052 0.026 -0.069 -0.277 -0.607 -1.000
10.000 -0.008 -0.005 0.000 0.015 0.030 0.048 0.042 -0.024 -0.215 -0.564 -1.00012.000 -0.002 -0.003 -0.003 0.005 0.022 0.041 0.051 0.006 -0.163 -0.524 -1.00014.000 0.000 -0.002 -0.003 0.002 0.011 0.034 0.059 0.025 -0.127 -0.487 -1.00016.000 0.002 0.000 -0.002 -0.001 0.006 0.028 0.064 0.036 -0.100 -0.557 -1.000 ➤
NZS 3106:2009
72
Table D1 – Thermal stress coefficients – Pinned-base condition (continued)
(d) Hoop thermal stress, outside – Average temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.205 0.164 0.135 0.205 0.060 0.002 -0.095 -0.236 -0.431 -0686 -1.0003.000 0.074 0.082 0.093 0.101 0.090 0.066 0.001 -0.123 -0.326 -0.618 -1.0004.000 0.017 0.038 0.059 0.081 0.098 0.094 0.051 -0.053 -0.251 -0.565 -1.0005.000 -0.008 0.014 0.036 0.062 0.086 0.099 0.079 -0.008 -0.195 -0.522 -1.0006.000 -1.011 0.003 0.023 0.046 0.073 0.091 0.090 0.023 0.152 -0.485 -1.0008.000 -0.015 -0.004 0.008 0.021 0.043 0.076 0.096 0.063 -0.081 -0.421 -1.000
10.000 -0.008 -0.005 0.000 0.007 0.026 0.056 0.090 0.084 -0.029 -0.370 -1.00012.000 -0.002 -0.003 -0.003 -0.001 0.012 0.041 0.077 0.094 0.003 -0.322 -1.00014.000 0.000 -0.002 -0.003 -0.004 0.005 0.028 0.059 0.097 0.031 -0.287 -1.00016.000 0.002 0.000 -0.002 -0.001 -0.000 0.014 0.036 0.092 0.052 -0.357 -1.000
(e) Hoop thermal stress, inside – Differential temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.273 0.647 0.947 1.177 1.343 1.446 1.494 1.487 1.420 1.289 1.0763.000 0.247 0.676 1.002 1.229 1.379 1.464 1.504 1.493 1.427 1.285 1.0374.000 0.260 0.777 1.053 1.061 1.382 1.448 1.477 1.472 1.418 1.281 1.0135.000 0.276 0.815 1.098 1.282 1.376 1.420 1.442 1.446 1.410 1.283 1.0026.000 0.290 0.816 1.136 1.297 1.364 1.389 1.407 1.420 1.402 1.291 0.9978.000 0.304 0.884 1.195 1.314 1.336 1.336 1.321 1.378 1.392 1.307 0.996
10.000 0.310 0.938 1.238 1.322 1.313 1.294 1.304 1.347 1.387 1.325 0.99712.000 0.310 0.982 1.269 1.324 1.293 1.263 1.272 1.323 1.382 1.342 0.99914.000 0.309 1.019 1.292 1.322 1.277 1.243 1.251 1.305 1.376 1.353 1.00016.000 0.309 1.050 1.307 1.317 1.264 1.230 1.236 1.291 1.367 1.361 1.000
(f) Hoop thermal stress, outside – Differential temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 -1.728 -1.380 -1.138 -0.974 -0.871 -0.806 -0.769 -0.753 -0.772 -0.822 -0.9363.000 -1.753 -1.364 -1.123 -0.990 -0.821 -0.885 -0.859 -0.840 -0.835 -0.869 -0.9834.000 -1.741 -1.274 -1.102 -1.004 -0.971 -0.959 -0.943 -0.912 -0.885 -0.894 -1.0025.000 -1.725 -1.245 -1.081 -1.015 -1.014 -1.022 -1.010 -0.970 -0.919 -0.906 -1.0086.000 -1.711 -1.253 -1.062 -1.026 -1.049 -1.073 -1.064 -1.014 -0.943 -0.909 -1.0098.000 -1.696 -1.200 -1.037 -1.043 -1.103 -1.145 -1.111 -1.077 -0.979 -0.911 -1.006
10.000 -1.691 -1.162 -1.024 -1.061 -1.138 -1.188 -1.182 -1.116 -1.003 -0.911 -1.00312.000 -1.691 -1.134 -1.018 -1.079 -1.164 -1.213 -1.209 -1.144 -1.024 -0.912 -1.00114.000 -1.691 -1.111 -1.019 -1.096 -1.182 -1.227 -1.224 -1.164 -1.043 -0.916 -1.00016.000 -1.692 -1.093 -1.023 -1.113 -1.196 -1.235 -1.233 -1.179 -1.061 -0.922 -1.000
NZS 3106:2009
73
(g) Vertical thermal stress – Total effects
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.000 0.025 0.078 0.121 0.159 0.159 0.125 0.070 0.019 -0.021 0.0163.000 0.000 0.047 0.141 0.231 0.303 0.319 0.275 0.187 0.088 0.012 0.0264.000 0.000 0.067 0.197 0.328 0.410 0.427 0.383 0.272 0.136 0.021 0.0215.000 0.000 0.082 0.244 0.394 0.492 0.511 0.457 0.336 0.173 0.027 0.0136.000 0.000 0.095 0.274 0.441 0.543 0.573 0.512 0.378 0.197 0.031 0.0088.000 0.000 0.117 0.322 0.505 0.609 0.634 0.582 0.448 0.241 0.042 0.001
10.000 0.000 0.138 0.362 0.542 0.631 0.655 0.609 0.493 0.283 0.056 -0.00112.000 0.000 0.160 0.398 0.565 0.648 0.661 0.631 0.526 0.332 0.070 -0.00114.000 0.000 0.179 0.431 0.588 0.645 0.660 0.659 0.550 0.362 0.096 -0.00116.000 0.000 0.198 0.458 0.595 0.646 0.663 0.689 0.575 0.382 0.114 -0.001
(h) Hoop thermal stress, inside – Total effects
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.239 0.401 0.527 0.659 0.652 0.656 0.613 0.531 0.406 0.239 0.0383.000 0.161 0.376 0.536 0.639 0.694 0.705 0.670 0.587 0.452 0.261 0.0184.000 0.139 0.407 0.550 0.657 0.711 0.722 0.692 0.616 0.481 0.279 0.0075.000 0.134 0.414 0.566 0.666 0.714 0.723 0.699 0.633 0.506 0.296 0.0016.000 0.139 0.410 0.580 0.669 0.708 0.715 0.698 0.641 0.524 0.315 -0.0018.000 0.156 0.440 0.602 0.671 0.390 0.694 0.674 0.655 0.557 0.350 -0.002
10.000 0.151 0.467 0.619 0.668 0.672 0.671 0.673 0.662 0.586 0.380 -0.00112.000 0.154 0.490 0.633 0.664 0.658 0.652 0.662 0.665 0.610 0.409 -0.00114.000 0.155 0.508 0.644 0.662 0.644 0.639 0.655 0.665 0.625 0.433 0.00016.000 0.155 0.525 0.653 0.658 0.635 0.629 0.650 0.664 0.634 0.402 0.000
(i) Hoop thermal stress, outside – Total effects
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 -0.761 +0.608 -0.501 -0.385 -0.405 -0.402 -0432 -0.495 -0.602 -0.754 -0.9683.000 -0.840 -0.641 -0.515 -0.445 -0.416 -0.410 0.429 -0.481 -0.580 -0.743 -0.9924.000 -0.862 -0.618 -0.521 -0.461 -0.437 -0.432 -0.446 -0.483 -0.568 -0.729 -1.0015.000 -0.866 -0.616 -0.522 -0.476 -0.464 -0.462 -0.466 -0.489 -0.557 -0.714 -1.0046.000 -0861 -0625 -0.520 -0.490 -0.488 -0.491 -0.487 -0.495 -0.547 -0.697 -0.0058.000 -0.856 -0.602 -0.515 -0.511 -0.530 -0.534 -0.508 -0.507 -0.530 -0.666 -1.003
10.000 -0.850 -0.584 -0.512 -0.527 -0.556 -0.566 -0.546 -0.516 -0.516 -0.640 -1.00112.000 -0.846 -0.568 -0.511 -0.540 -0.576 -0.586 -0.566 -0.525 -0.510 -0.617 -1.00014.000 -0.846 -0.557 -0.511 -0.550 -0.589 -0.600 -0.583 -0.533 -0.508 -0.601 -1.00016.000 -0.845 -0.547 -0.513 -0.557 -0.598 -0.610 -0.598 -0.544 -0.504 -0.639 -1.000
Table D1 – Thermal stress coefficients – Pinned-base condition (continued)
NZS 3106:2009
74
Table D2 – Thermal stress coefficients – Fixed-base condition
(a) Vertical thermal stress – Average temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.000 -0.024 -0.086 -0.158 -0.211 -0.214 -0.142 -0.046 0.401 0.934 1.7263.000 0.000 -0.025 -0.094 -0.184 -0.266 -0.328 -0.299 -0.151 0.191 0.803 1.7394.000 0.000 -0.019 -0.072 -0.158 -0.250 -0.326 -0.360 -0.254 0.062 0.696 1.7525.000 0.000 -0.012 -0.048 -0.114 -0.210 -0.306 -0.366 -0.312 -0.042 0.606 1.7586.000 0.000 -0.007 -0.029 -0.079 -0.158 -0.259 -0.353 -0.346 -0.122 0.526 1.7428.000 0.000 0.000 -0.010 -0.029 -0.077 -0.173 -0.298 -0.365 -0.230 0.380 1.766
10.000 0.000 0.000 0.012 0.000 -0.024 -0.108 -0.252 -0.360 -0.312 0.264 1.78412.000 0.000 0.000 0.000 0.014 0.000 -0.058 -0.202 -0.346 -0.317 0.173 1.77114.000 0.000 0.000 0.000 0.000 0.000 -0.034 -0.168 -0.302 -0.353 0.118 1.76416.000 0.000 0.000 0.000 0.000 0.000 -0.019 -0.115 -0.230 -0.384 0.096 1.747
(b) Vertical thermal stress – Differential temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.000 0.070 0.232 0.432 0.633 0.814 0.964 1.080 1.164 1.219 1.2523.000 0.000 0.100 0.320 0.569 0.797 0.981 1.113 1.198 1.247 1.269 1.2724.000 0.000 0.129 0.397 0.680 0.916 1.087 1.193 1.249 1.270 1.271 1.2615.000 0.000 0.156 0.465 0.770 1.005 1.157 1.237 1.269 1.271 1.261 1.2476.000 0.000 0.183 0.527 0.847 1.072 1.203 1.260 1.272 1.264 1.249 1.2368.000 0.000 0.232 0.633 0.964 1.164 1.252 1.272 1.263 1.246 1.234 1.222
10.000 0.000 0.277 0.722 1.049 1.216 1.270 1.268 1.248 1.232 1.222 1.21912.000 0.000 0.320 0.797 1.113 1.247 1.272 1.257 1.237 1.224 1.219 1.21814.000 0.000 0.359 0.861 1.159 1.263 1.269 1.247 1.229 1.220 1.218 1.21916.000 0.000 0.397 0.916 1.193 1.270 1.261 1.238 1.224 1.218 1.218 1.219
(c) Hoop thermal stress, inside – Average temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.253 0.140 0.025 -0.100 -0.232 -0.371 -0.511 -0.647 -0.742 -0.777 -0.6893.000 0.160 0.107 0.044 -0.035 -0.136 -0.263 -0.408 -0.568 -0.708 -0.774 -0.6874.000 0.085 0.070 0.044 0.000 -0.048 -0.172 -0.319 -0.493 -0.667 -0.770 -0.6855.000 0.037 0.042 0.038 0.021 -0.023 -0.106 -0.241 -0.427 -0.629 -0.763 -0.6846.000 0.010 0.023 0.033 0.031 0.005 -0.061 -0.185 -0.368 -0.592 -0.756 -0.6868.000 -0.011 0.005 0.020 0.031 0.030 -0.005 -0.101 -0.278 -0.522 -0.742 -0.682
10.000 -0.011 -0.002 0.012 0.023 0.035 0.021 -0.049 -0.206 -0.465 -0.726 -0.68212.000 -0.006 -0.003 0.003 0.017 0.031 0.033 -0.014 -0.151 -0.405 -0.707 -0.68114.000 -0.003 -0.002 0.000 0.007 0.022 0.034 0.005 -0.105 -0.359 -0.685 -0.68216.000 0.000 -0.001 -0.001 0.003 0.018 0.029 0.019 -0.066 -0.319 -0.662 -0.686
NZS 3106:2009
75
(d) Hoop thermal stress, outside – Average temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.253 0.148 0.057 -0.042 -0.156 -0.295 -0.461 -0.663 -0.886 -1.113 -1.3113.000 0.160 0.117 0.078 0.031 -0.040 -0.145 -0.300 -0.514 -0.776 -1.064 -1.3134.000 0.085 0.076 0.070 0.058 0.042 -0.054 -0.139 -0.401 -0.689 -1.020 -1.3155.000 0.037 0.046 0.056 0.063 0.053 0.004 -0.100 -0.315 -0.613 -0.981 -1.3166.000 0.010 0.025 0.043 0.059 0.063 0.033 -0.057 -0.244 -0.548 -0.946 -1.3148.000 -0.011 0.005 0.024 0.041 0.058 0.057 0.007 -0.146 -0.440 -0.880 -1.318
10.000 -0.011 -0.002 0.008 0.023 0.043 0.059 0.041 -0.076 -0.353 -0.822 -1.31812.000 -0.006 -0.003 0.003 0.011 0.031 0.053 0.058 -0.027 -0.291 -0.769 -1.31914.000 -0.003 -0.002 0.000 0.007 0.022 0.046 0.065 0.003 -0.231 -0.727 -1.31816.000 0.000 -0.001 -0.001 0.003 0.012 0.035 0.061 0.016 -0.181 -0.696 -1.314
(e) Hoop thermal stress, inside – Differential temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.308 0.635 0.891 1.077 1.203 1.279 1.318 1.331 1.327 1.313 1.2953.000 0.308 0.699 0.983 1.168 1.273 1.321 1.331 1.320 1.299 1.277 1.2564.000 0.308 0.750 1.050 1.225 1.308 1.331 1.321 1.297 1.271 1.249 1.2335.000 0.307 0.792 1.101 1.263 1.324 1.328 1.305 1.276 1.250 1.233 1.2226.000 0.308 0.829 1.142 1.289 1.331 1.319 1.288 1.258 1.236 1.223 1.2178.000 0.308 0.891 1.203 1.318 1.327 1.295 1.260 1.235 1.221 1.216 1.215
10.000 0.308 0.941 1.244 1.329 1.314 1.274 1.241 1.222 1.216 1.215 1.21712.000 0.308 0.983 1.273 1.331 1.299 1.256 1.228 1.217 1.215 1.217 1.21914.000 0.308 1.019 1.294 1.327 1.284 1.243 1.221 1.215 1.216 1.218 1.22016.000 0.308 1.050 1.308 1.321 1.271 1.233 1.218 1.215 1.217 1.219 1.220
(f) Hoop thermal stress, outside – Differential temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 -1.693 -1.391 -1.194 -1.079 -1.026 -1.015 -1.030 -1.059 -1.093 -1.126 -1.1563.000 -1.693 -1.338 -1.133 -1.038 -1.015 -1.033 -1.070 -1.112 -1.151 -1.181 -1.2034.000 -1.693 -1.297 -1.094 -1.020 -1.023 -1.061 -1.109 -1.153 -1.187 -1.209 -1.2225.000 -1.693 -1.265 -1.067 -1.015 -1.038 -1.089 -1.141 -1.182 -1.208 -1.222 -1.2286.000 -1.693 -1.237 -1.048 -1.016 -1.056 -1.115 -1.166 -1.201 -1.220 -1.228 -1.2298.000 -1.693 -1.193 -1.026 -1.030 -1.093 -1.156 -1.199 -1.221 -1.228 -1.228 -1.226
10.000 -1.693 -1.160 -1.017 -1.049 -1.124 -1.184 -1.216 -1.228 -1.228 -1.225 -1.22312.000 -1.693 -1.133 -1.015 -1.070 -1.150 -1.203 -1.225 -1.229 -1.226 -1.223 -1.22114.000 -1.693 -1.111 -1.017 -1.091 -1.171 -1.215 -1.228 -1.228 -1.224 -1.221 -1.22016.000 -1.693 -1.094 -1.023 -1.109 -1.187 -1.222 -1.229 -1.226 -1.222 -1.220 -1.220
Table D2 – Thermal stress coefficients – Fixed-base condition (continued)
➤
NZS 3106:2009
76
(g) Vertical thermal stress – Total effects
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.000 0.023 0.073 0.137 0.211 0.300 0.411 0.563 0.782 1.076 1.4893.000 0.000 0.037 0.113 0.192 0.265 0.327 0.407 0.523 0.719 1.036 1.5064.000 0.000 0.055 0.162 0.261 0.333 0.380 0.417 0.497 0.666 0.984 1.5075.000 0.000 0.072 0.208 0.328 0.398 0.425 0.436 0.478 0.615 0.934 1.5026.000 0.000 0.088 0.249 0.384 0.457 0.472 0.454 0.463 0.571 0.887 1.4898.000 0.000 0.116 0.312 0.468 0.544 0.539 0.437 0.449 0.508 0.497 1.494
10.000 0.000 0.138 0.367 0.525 0.596 0.581 0.508 0.444 0.460 0.743 1.49112.000 0.000 0.160 0.398 0.564 0.623 0.607 0.528 0.446 0.453 0.696 1.49414.000 0.000 0.179 0.431 0.580 0.631 0.618 0.539 0.463 0.434 0.668 1.49116.000 0.000 0.198 0.458 0.597 0.645 0.621 0.562 0.497 0.417 0.657 1.483
(h) Hoop thermal stress, inside – Total effects
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.280 0.387 0.458 0.489 0.485 0.454 0.403 0.342 0.292 0.268 0.3033.000 0.234 0.403 0.513 0.566 0.568 0.529 0.462 0.376 0.296 0.251 0.2854.000 0.196 0.410 0.547 0.613 0.630 0.580 0.501 0.402 0.302 0.240 0.2745.000 0.172 0.417 0.570 0.642 0.651 0.611 0.532 0.424 0.311 0.235 0.2696.000 0.159 0.426 0.583 0.660 0.668 0.629 0.552 0.445 0.322 0.233 0.2658.000 0.148 0.448 0.611 0.674 0.679 0.645 0.580 0.478 0.349 0.237 0.267
10.000 0.148 0.469 0.628 0.676 0.674 0.647 0.596 0.508 0.375 0.244 0.26712.000 0.151 0.490 0.638 0.674 0.665 0.644 0.607 0.533 0.405 0.255 0.26914.000 0.152 0.508 0.647 0.667 0.653 0.638 0.613 0.555 0.429 0.267 0.26916.000 0.154 0.524 0.653 0.662 0.645 0.631 0.618 0.574 0.449 0.279 0.267
(i) Hoop thermal stress, outside – Total effects
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 -0.720 -0.621 -0.569 -0.561 -0.591 -0.655 -0.745 -0.861 0.990 -1.120 -1.2333.000 -0.767 -0.611 -0.528 -0.503 -0.527 -0.589 -0.695 -0.813 -0.963 -1.122 -1.2584.000 -0.804 -0.610 -0.512 -0.481 -0.490 -0.558 -0.649 -0.777 -0.938 -1.115 -1.2695.000 -0.828 -0.609 -0.506 -0.476 -0.493 -0.543 -0.625 -0.748 -0.911 -1.102 -1.2726.000 -0.842 -0.606 -0.502 -0.479 -0.497 -0.541 -0.612 -0.722 -0.884 -1.087 -1.2718.000 -0.852 -0.594 -0.501 -0.494 -0.518 -0.549 -0.596 -0.684 -0.834 -1.054 -1.272
10.000 -0.852 -0.581 -0.504 -0.513 -0.541 -0.562 -0.588 -0.652 -0.791 -0.023 -1.27012.000 -0.850 -0.568 -0.506 -0.529 -0.560 -0.575 -0.583 -0.628 -0.759 -0.996 -1.27014.000 -0.848 -0.557 -0.509 -0.542 -0.574 -0.584 -0.581 -0.612 -0.728 -0.974 -1.26916.000 -0.847 -0.547 -0.512 -0.553 -0.588 -0.593 -0.584 -0.605 -0.701 -0.958 -1.267
Table D2 – Thermal stress coefficients – Fixed-base condition (continued)
NZS 3106:2009
77
Table D3 – Thermal stress coefficients – Sliding-base condition
(a) Vertical thermal stress – Average temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0003.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0004.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0005.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0006.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0008.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00012.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00014.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00016.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
(b) Vertical thermal stress – Differential temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.032 0.068 0.176 0.292 0.377 0.407 0.377 0.292 0.176 0.068 0.0323.000 0.052 0.149 0.346 0.547 0.689 0.742 0.689 0.547 0.346 0.149 0.0524.000 0.041 0.181 0.447 0.709 0.889 0.954 0.889 0.709 0.447 0.181 0.0415.000 0.027 0.198 0.516 0.819 1.022 1.093 1.022 0.819 0.516 0.198 0.0276.000 0.016 0.212 0.571 0.899 1.113 1.186 1.113 0.899 0.571 0.212 0.0168.000 0.002 0.243 0.659 1.007 1.216 1.283 1.216 1.007 0.659 0.243 0.002
10.000 -0.001 0.279 0.734 1.077 1.264 1.320 1.264 1.077 0.734 0.279 -0.00112.000 -0.002 0.318 0.800 1.130 1.283 1.325 1.283 1.130 0.800 0.318 -0.00214.000 -0.001 0.356 0.861 1.168 1.290 1.318 1.290 1.168 0.861 0.356 -0.00116.000 -0.001 0.394 0.914 1.197 1.288 1.303 1.288 1.197 0.914 0.394 -0.001
(c) Hoop thermal stress, inside – Average temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0003.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0004.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0005.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0006.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0008.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00012.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00014.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00016.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
➤
NZS 3106:2009
78
(d) Hoop thermal stress, outside – Average temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0003.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0004.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0005.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0006.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0008.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00012.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00014.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00016.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
(e) Hoop thermal stress, inside – Differential temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.383 0.729 0.997 1.188 1.301 1.338 1.301 1.188 0.997 0.729 0.3833.000 0.344 0.755 1.062 1.268 1.384 1.422 1.384 1.268 1.062 0.755 0.3444.000 0.321 0.779 1.101 1.302 1.409 1.442 1.409 1.302 1.101 0.779 0.3215.000 0.309 0.805 1.132 1.319 1.409 1.435 1.409 1.319 1.132 0.805 0.3096.000 0.304 0.832 1.158 1.327 1.399 1.417 1.399 1.327 1.158 0.832 0.3048.000 0.303 0.887 1.204 1.332 1.367 1.371 1.367 1.332 1.204 0.887 0.303
10.000 0.305 0.936 1.240 1.332 1.335 1.327 1.335 1.332 1.240 0.936 0.30512.000 0.306 0.980 1.268 1.328 1.308 1.292 1.308 1.328 1.268 0.980 0.30614.000 0.307 1.017 1.290 1.323 1.286 1.266 1.286 1.323 1.290 1.017 0.30716.000 0.308 1.049 1.305 1.316 1.269 1.246 1.269 1.316 1.305 1.049 0.308
(f) Hoop thermal stress, outside – Differential temperature change
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 -1.629 -1.297 -1.067 -0.918 -0.836 -0.809 -0.836 -0.918 -1.067 -1.297 -1.6293.000 -1.676 -1.299 -1.064 -0.930 -0.865 -0.846 -0.865 -0.930 -1.064 -1.299 -1.6764.000 -1.695 -1.287 -1.061 -0.954 -0.912 -0.902 -0.912 -0.954 -1.061 -1.287 -1.6955.000 -1.701 -1.267 -1.055 -0.977 -0.960 -0.959 -0.960 -0.977 -1.055 -1.267 -1.7016.000 -1.702 -1.245 -1.048 -0.977 -1.003 -1.011 -1.003 -0.977 -1.048 -1.245 -1.7028.000 -1.699 -1.202 -1.034 -1.031 -1.072 -1.092 -1.072 -1.031 -1.034 -1.202 -1.699
10.000 -1.696 -1.165 -1.025 -1.057 -1.121 -1.149 -1.121 -1.057 -1.025 -1.165 -1.69612.000 -1.694 -1.136 -1.021 -1.079 -1.155 -1.186 -1.155 -1.079 -1.021 -1.136 -1.69414.000 -1.693 -1.112 -1.021 -1.098 -1.179 -1.209 -1.179 -1.098 -1.021 -1.112 -1.69316.000 -1.693 -1.094 -1.025 -1.115 -1.196 -1.223 -1.196 -1.115 -1.025 -1.094 -1.693
Table D3 – Thermal stress coefficients – Sliding-base condition (continued)
NZS 3106:2009
79
(g) Vertical thermal stress – Total effects
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.016 0.034 0.088 0.146 0.188 0.204 0.188 0.146 0.088 0.034 0.0163.000 0.026 0.074 0.173 0.273 0.345 0.371 0.345 0.273 0.173 0.074 0.0264.000 0.021 0.090 0.223 0.354 0.445 0.477 0.445 0.354 0.223 0.090 0.0215.000 0.013 0.099 0.258 0.409 0.511 0.547 0.511 0.409 0.258 0.099 0.0136.000 0.008 0.106 0.285 0.450 0.556 0.593 0.556 0.450 0.285 0.106 0.0088.000 0.001 0.121 0.329 0.503 0.608 0.642 0.608 0.503 0.329 0.121 0.001
10.000 -0.001 0.140 0.367 0.539 0.632 0.660 0.632 0.539 0.367 0.140 -0.00112.000 -0.001 0.159 0.400 0.565 0.642 0.662 0.642 0.565 0.400 0.159 -0.00114.000 -0.001 0.178 0.431 0.584 0.645 0.659 0.645 0.584 0.431 0.178 -0.00116.000 -0.001 0.197 0.457 0.598 0.644 0.651 0.644 0.598 0.457 0.197 -0.001
(h) Hoop thermal stress, inside – Total effects
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 0.191 0.364 0.499 0.594 0.650 0.669 0.650 0.594 0.499 0.364 0.1913.000 0.172 0.378 0.531 0.634 0.692 0.711 0.692 0.634 0.531 0.378 0.1724.000 0.160 0.390 0.550 0.651 0.705 0.721 0.705 0.651 0.550 0.390 0.1605.000 0.155 0.402 0.566 0.659 0.705 0.718 0.705 0.659 0.566 0.402 0.1556.000 0.152 0.416 0.579 0.664 0.699 0.709 0.699 0.664 0.579 0.416 0.1528.000 0.151 0.443 0.602 0.666 0.683 0.685 0.683 0.666 0.602 0.443 0.151
10.000 0.152 0.468 0.620 0.666 0.667 0.664 0.667 0.666 0.620 0.468 0.15212.000 0.153 0.490 0.634 0.664 0.654 0.646 0.654 0.664 0.634 0.490 0.15314.000 0.154 0.508 0.645 0.661 0.643 0.633 0.643 0.661 0.645 0.508 0.15416.000 0.154 0.524 0.653 0.658 0.634 0.623 0.634 0.658 0.653 0.524 0.154
(i) Hoop thermal stress, outside – Total effects
SfACT TOP 0.1H 0.2H 0.3H 0.4H 0.5H 0.6H 0.7H 0.8H 0.9H BTM
2.000 -0.815 -0.648 -0.533 -0.459 -0.418 -0.405 -0.418 -0.459 -0.533 -0.648 -0.8153.000 -0.838 -0.649 -0.532 -0.465 -0.432 -0.423 -0.432 -0.465 -0.532 -0.649 -0.8384.000 -0.848 -0.643 -0.530 -0.477 -0.456 -0.451 -0.456 -0.477 -0.530 -0.643 -0.8485.000 -0.851 -0.633 -0.527 -0.488 -0.480 -0.479 -0.480 -0.488 -0.527 -0.633 -0.8516.000 -0.851 -0.622 -0.524 -0.499 -0.501 -0.505 -0.501 -0.499 -0.524 -0.622 -0.8518.000 -0.849 -0.601 -0.517 -0.515 -0.536 -0.546 -0.536 -0.515 -0.517 -0.601 -0.849
10.000 -0.848 -0.583 -0.513 -0.529 -0.560 -0.574 -0.560 -0.529 -0.513 -0.583 -0.84812.000 -0.847 -0.568 -0.510 -0.540 -0.578 -0.593 -0.578 -0.540 -0.510 -0.568 -0.84714.000 -0.847 -0.556 -0.511 -0.549 -0.590 -0.605 -0.590 -0.549 -0.511 -0.556 -0.84716.000 -0.846 -0.547 -0.512 -0.558 -0.598 -0.612 -0.598 -0.558 -0.512 -0.547 -0.846
Table D3 – Thermal stress coefficients – Sliding-base condition (continued)
NOTES
NZS 3106:2009
© 2009 StaNDaRDS CoUNCil
Approved by the Standards Council on 24 July 2009 to be a New Zealand Standard pursuant to the provisions of section 10 of the Standards Act 1988.
First published: 29 July 2009
The following Standards New Zealand references relate to this Standard:
Project No. P 3106Draft for comment No. DZ 3106Typeset by: Standards New ZealandPrinted by: The Colour Guy