Panel Bus I/O Modules Product Data
Copyright © 2016 Honeywell GmbH All Rights Reserved EN0Z-0979GE51 R0316
3.4
GENERAL The CentraLine Panel Bus I/O Modules communicate via the Panel Bus. The pluggable CentraLine Panel Bus I/O modules consist of a terminal socket and a removable electronic module, allowing the socket to be mounted and wired before the electronic module is installed. All such electronic modules can be swapped out without disrupting the power and bus connec-tions: Simply unplug the “old” and insert the “new” module.
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet. Disconnect the power supply before you start to install
the control system. More than one disconnect switch may be required to de-energize the system.
Do not reconnect the power supply until you have completed the installation.
Unused terminals must be closed (by completely screwing in the terminal screws), thus preventing the accidental touching of “live” parts.
The mixed CentraLine Panel Bus I/O modules offer a mix of 34 inputs and outputs in a compact housing. Software updates, configuration, and commissioning are all done automatically by the controller for all Panel Bus I/O Modules. The Panel Bus I/O Modules are addressed manually by adjusting their HEX switches. The Panel Bus I/O Modules may be used with any CPU supporting Panel Bus communication (e.g., the LION, EAGLE, etc.).
FEATURES Plug-and-play functionality for easy maintenance.
Pluggable Panel Bus I/O modules can be exchanged without rewiring. Further, the separate installation of terminal sockets and electronic modules lower risk of damage and theft in the construction phase.
Fast wiring with state-of-the-art push-in terminals (screw-type terminals also available) and bridge connectors.
Wide range of sensors supported (NTC20kΩ, NTC10kΩ, PT1000-1/-2, Johnson A99 PTC, NI1000TK5000, PT3000, Balco500, 0/2…10 V, 0/4…20 mA). NOTE: The mixed Panel Bus I/O modules CLIOP830 and CLIOP831 feature inputs suitable for signals from NTC20kΩ sensors and 0/2…10 V, 0/4…20 mA, only!
Binary input LEDs of the pluggable CentraLine Panel Bus I/O Modules can be configured for status display (off / yellow) or alarm display (green / red) per channel. NOTE: The mixed I/O modules CLIOP830 and CLIOP831 feature only non-configurable binary input LEDs!
Configurable safety position for outputs, in case of loss of communication with the controller.
Max. wiring flexibility due to optional accessories like auxiliary terminals, manual disconnectors, and cross-connectors.
Can be mounted in small installation housings
Flexible mix of Panel Bus I/O modules covering all your application requirements.
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 2
OVERVIEW
CLIOP821A CLIOP822A
CLIOPR822A
CLIOP823A CLIOP824A
CLIOPR824A CLIOPR825A
1 2 3 4 5 6 7 8 9 10 11 12
B1 B2 B3 B4 B5 B6
B12
12
6
B11
11
5
B10
10
4
B9
9
3
B8
8
2
B7
7
1
DI
Binary Inputs
G1 G2
41 42
GND Analog Outputs
AI2 AI3 AI4
14 15 16
AI1
17 18 19 20
13
Analog Inputs
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
21
25 26 27 28
22 23 24
DO
24V Relays
NO1 NO2 NO3 NO4 NO5 NO6
CO1 CO2 CO3 CO4 CO5 CO6
35
29 30 31 32 33 34
36 37 38 39 40
1 2 3 4 5 6Install. Instr.MU1B-0473GE51
!
AI5 AI6 AI7 AI8
CentraLine
CLIOP830A
XS821-22XSU821-22CONTROLLER
XS823XSU823
XS824-25XSU824-25
PANELBUS MODULES
pluggableANALOG OUTPUT
pluggableANALOG INPUT
pluggableBINARY INPUT
pluggableFLOATINGOUTPUT
MIXED I/Os(with integrated socket)
pluggableRELAY OUTPUT
Panel Bus
1 2 3 4 5 6 7 8 9 10 11 12
B1 B2 B3 B4 B5 B6
B12
12
6
B11
11
5
B10
10
4
B9
9
3
B8
8
2
B7
7
1
DI
Binary Inputs
G1 G2
41 42
GND Analog Outputs
AI2 AI3 AI4
14 15 16
AI1
17 18 19 20
13
Analog Inputs
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
21
25 26 27 28
22 23 24
DO
24V Relays
NO1 NO2 NO3 NO4 NO5 NO6
CO1 CO2 CO3 CO4 CO5 CO6
35
29 30 31 32 33 34
36 37 38 39 40
1 2 3 4 5 6Install. Instr.MU1B-0473GE51
!
AI5 AI6 AI7 AI8
CentraLine
CLIOP830ACLIOP831A
CLIOP831A
Fig. 1. Overview of CentraLine Panel Bus I/O Modules
Table 1. Overview of CentraLine Panel Bus I/O Modules
order number description Pluggable Panel Bus I/O Modules CLIOP821 Pluggable Panel Bus Analog Input Module (with 8 analog inputs) CLIOP822 Pluggable Panel Bus Analog Output Module (with 8 analog outputs) CLIOPR822 Pluggable Panel Bus Analog Output Module (with 8 analog outputs and manual overrides) CLIOP823 Pluggable Panel Bus Binary Input Module (with 12 binary inputs) CLIOP824 Pluggable Panel Bus Relay Output Module (with 6 relay outputs) CLIOPR824 Pluggable Panel Bus Relay Output Module (with 6 relay outputs and manual overrides) CLIOPR825 Pluggable Panel Bus Floating Output Module (with 3 floating outputs and manual overrides)
Mixed Panel Bus I/O Modules with integrated socket CLIOP830 Mixed Panel Bus I/O Module (with 8 AIs, 8 AOs, 12 BIs, and 6 ROs); housing fits to LION Controller housing CLIOP831 Mixed Panel Bus I/O Module (with 8 AIs, 8 AOs, 12 BIs, and 6 ROs); housing fits to EAGLE Controller housing
Terminal Sockets (not needed for the mixed I/O modules CLIOP830 and CLIOP831) XS821-22 Push-in terminal socket for pluggable AI/AO modules (incl. bridge connector, swivel label) XSU821-22 Screw-type terminal socket for pluggable AI/AO modules (incl. bridge connector, swivel label) XS823 Push-in terminal socket for pluggable BI modules (incl. bridge connector, swivel label) XSU823 Screw-type terminal socket for pluggable BI modules (incl. bridge connector, swivel label)
XS824-25 Push-in terminal socket for pluggable relay/floating output modules (incl. bridge connector, cross connector, swivel label)
XSU824-25 Screw-type terminal socket for pluggable relay/floating output modules (incl. bridge connector, cross connector, swivel label)
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 3
Table 2. Overview of auxiliary parts and spare parts
order number description
XS812
Manual Disconnector Module for AI/AO/BI Modules (for manual disconnection of individual signals; useful during start-up). Plugged between Terminal Socket and Electronic Module. For pluggable I/O modules, only.
XS812RO
Manual Disconnector Module for Relay Output Modules (for manual disconnection of individual signals; useful during start-up). Plugged between Terminal Socket and Electronic Module. Not suitable for line voltage. For pluggable I/O modules, only.
XS814
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two groups with seven internally-connected push-in terminals. For pluggable I/O modules, only.
XS830A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block consists of two groups of nine internally-connected push-in terminals. For CLIOP830 and CLIOP831, only.
XS831A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8
Ten Auxiliary Terminal Blocks (for connection of 0…20 mA signals). Each terminal block supports up to 8 current inputs. For CLIOP830 and CLIOP831, only.
XS815
20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in the Terminal Socket package. For pluggable I/O modules, only.
XS816
10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package / in the mixed Panel Bus I/O module packages.
XAL10
10 Swivel Labels (for attaching the application-specific label printed with CARE). One Swivel Label is included in the Terminal Socket package.
XAL11
10 Swivel Label Holders for Mixed I/O modules. One Swivel Label Holder is included in each mixed I/O module package. For mixed I/O modules, only.
NOTE: All CentraLine Panel Bus I/O Modules are protected against short circuit, 24 VAC +20% and 30 VDC
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 4
Table 3. Pluggable Panel Bus I/O Module specifications
Module Analog Input Analog Output Binary Input Relay Output Floating Output
CLIOP821 CLIOP822, CLIOPR822 CLIOP823 CLIOP824, CLIOPR824 CLIOPR825 no. of I/Os 8 analog inputs 8 analog outputs 12 binary inputs
requiring a gold contact or open collector
6 relay outputs 3 floating outputs
charac-teristic
Linear Graph, 0..10 Vdc with pull-up, 0(2)…10 Vdc without pull-up NTC20kΩ (-50…+150 °C, default) NTC10kΩ (-30…+100 °C) PT1000-1 (-50…150 °C) PT1000-2 (0…400 °C) Johnson A99 (-40…+120 °C) NI1000TK5000 (-30…+130 °C) PT3000 (-50…150 °C) BALCO500 (-30…120 °C) Also configurable as: binary inputs Linear graph (0…10 V with
pull-up) Features: 16-bit resolution configurable offset per input auxiliary voltage: 10 Vdc, Imax =
5 mA
0…11 Vdc / 1 mA, 8-bit resolution (default) Also configurable as: floating outputs or binary outputs (0 V / 10 V) Features: 8-bit resolution Safety position
(remain, 0%, 50%, 100%) red LED per output light intensity follows
output level in auto Version with manual override (R): 1 potentiometer per
output auto feedback signal
(mode + value) blinking in manual
override position
static binary input, (default: dry contact) Also configurable as: totalizers (20 Hz) Features: 1 LED per input Color mode can
be set per input to OFF/yellow or green/red using CARE ON: < 1.6 kΩ to
GND or < 2.5 V to GND, OFF: > 90 kΩ to GND or > 4 V to GND
relay outputs (default) Features: Changeover relays Voltage: 19…250 Vac,
1…29 Vdc, P>50 mW max. total current:
12 A current per relay:
N.O.: 4(4) A (AC) or 4(1) A (DC), N.C.: 2(1) A (AC) or 4(1) A (DC) Safety position
(remain, 0%, 100%) yellow LED per output Version with manual override (R): 1 switch per output auto feedback signal
(mode + value) blinking in manual
override position
floating outputs Features: 2 relays per
floating output Voltage:
19…250 Vac, 1…29 Vdc, P>50 mW max. total current:
12 A current per relay:
N.O.: 4(4) A (AC) or 4(1) A (DC), N.C.: 2(1) A (AC) or 4(1) A (DC) 1 potentiometer per
floating output 2 LEDs per output:
green: relay 1 closed, red: relay 2 closed blinking in manual
override position auto feedback
signal (mode + value)
Manual Overrides as per EN ISO 16484-2:2004 The manual override switches and potentiometers of the output modules (…R822, …R824, and CLIOPR825) support direct operation as per EN ISO 16484-2:2004, section 5.4.3 "Local Priority Override/Indicating Units." Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the corresponding output LED will blink continuously, and the output module will send a feedback signal with the status "manual override" and the given override position to the controller (which will then also store this information in its alarm memory). NOTE: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
manual override switches and/or potentiometers.
Table 4. Mixed CentraLine Panel Bus I/O module specifications (CLIOP830 and CLIOP831)
Analog Inputs Analog Outputs Binary Inputs Relay Outputs Number: 8 Configurable types: NTC20kΩ (-30…+110 °C)
(default) Linear Graph 0..10 Vdc with pull-up 0(2)…10 Vdc without pull-up Also configurable as: binary inputs (static, dry
contact, only) Features: 10-bit resolution configurable offset per input
Number: 8 Configurable types: 0…11 Vdc / 1 mA (default) Also configurable as: binary outputs (0 V / 10 V) Features: 10-bit resolution (default) Safety position (remain, 0%,
50%, 100%)
Number: 12 (requiring a gold contact or open collector) Configurable types: Static binary inputs (default:
static, dry contact) ON: < 1.6 kΩ to GND or
< 2.5 V to GND, OFF: > 90 kΩ to GND or > 4 V to GND
Also configurable as: totalizers (15 Hz) Features: 1 yellow LED per input
Number: 6 Configurable types: Relay outputs (default) Features: Voltage: 24 VAC/DC,
P>50 mW max. total current: 3 A
(AC/DC) current per relay: 500 mA normally-open contacts: P >
50 mW, voltage: 24 V (AC/DC) 1 yellow LED per output
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 5
GENERAL FEATURES
PRESS PR
ESS PR
ESS PRES
S
1 2 3 Honeywell
AUTO
0
!
A A A100
S1 S221
0F E DCB
98
76543
A
71 COM a
72 COM b
73 24V~
74 24V 0~
21
22
23
14 4424 5434 64 25
13
12
11 31
32
33
41
42
43
51
52
53
61
62
61
62
6363
1 2 3 4 5 6 7 8 Honeywell
AUTO
0
!
A A A A A A A A100
S1 S221
0F EDCB
98
76543
A
21
9
GND GND
AI/AOVAUX
10 11 12 13 14 15 16 17 18 25 26
22 1 2 3 4 5 6 7 8
1 2 3 4 5 6 Honeywell
--1--0--AUTO
!
S1 S221
0F E DCB
98
76543
A
21
22
23
14 4424 5434 64 25
13
12
11 31
32
33
41
42
43
51
52
53
61
62
61
62
6363
1 2 3 4 5 6 7 8 Honeywell
!
21
9
GND GND
AI/AOVAUX
10 11 12 13 14 15 16 17 18 25 26
22 1 2 3 4 5 6 7 8
GND
BI
13 14 15 16 17 18 19 20 21 22 23 24 25 26
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12 Honeywell
!
S1 S221
0F EDCB
98
76543
A
71 COM a
72 COM b
73 24V~
74 24V 0~
PRESS PR
ESS
1:ABCDFERTAQWESDERT1
2:ABCDFERTAQWESDERT2
3:ABCDFERTAQWESDERT3
4:ABCDFERTAQWESDERT4
5:ABCDFERTAQWESDERT5
6:ABCDFERTAQWESDERT6
7:ABCDFERTAQWESDERT7
8:ABCDFERTAQWESDERT8
3 42
6 7
571 COM a
72 COM b
73 24V~
74 24V 0~
1
Fig. 2. CentraLine Panel Bus I/O Modules on DIN rails
Legend 1 Controller (e.g., LION, EAGLE, HAWK, etc.) 2 Cable (power, Panel Bus) connection from controller to
Panel Bus I/O Modules 3 Swivel label holder 4 Cable connection between Panel Bus I/O Modules on
separate DIN rails 5 Bridge connectors between Panel Bus I/O Modules on
same DIN rail 6 Stopper (from 3rd-party supplier) 7 Auxiliary terminal packages
LEDs Each CentraLine Panel Bus I/O Module is equipped with: one green power LED one yellow service LED
Overvoltage Protection All inputs and outputs are protected against 24 Vac and 40 Vdc overvoltage as well as against short-circuiting.
Service LED Each Panel Bus I/O Module is equipped with a yellow service LED (status: yellow/OFF) for easy diagnosis of failures.
Microprocessor Each Panel Bus I/O Module is equipped with its own microprocessor.
Addressing Addressing is performed using the HEX switch.
System Constraints
Table 5. System constraints
Max. no. of I/O modules (any combination) per controller
depends upon controller type
Max. no. of I/O modules per row 10
Max. current (F1) 4 A
Max. current (F2) 12 A
Max. current (F3) 12 A
Max. current (F4) (mixed I/O modules, only)
3 A
Max. row length 3 m
Max. distance between rows 40 m
Min. cross-section of GND (terminal 9) (protected by F2)
1.5 mm2
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 6
Analog Input Module
1
2 3
Fig. 3. CLIOP821 Panel Bus AI Module (shown with
terminal socket) Legend 1 Hex switch S2 2 Service LED 3 Power LED The pluggable CentraLine Panel Bus Analog Input Module, with 8 analog inputs, is installed with the XS821-22 or XSU821-22 Terminal Socket. Accessory disconnector module: XS812 (see also Table 2 on page 3).
24.9 kOHM
RTD
10 VDC
AI
GND
Fig. 4. Analog input low impedance (input circuit for
PT1000, Johnson A99 PTC, Balco500, PT3000, NI1000TK5000, slow binary input)
199.9 kOHMVi
AI
GND
Fig. 5. Analog input high impedance (input circuit for
voltage input for active sensors)
199.9 kOHM(8.9 VDC IFCONNECTIONINTERRUPTED)
Vi
AI
GND
24.9 kOHM
10 VDC
Fig. 6. Analog input impedance setpoint (input circuit for
NTC10kΩ, NTC20kΩ, wall module setpoint)
71 75
72 76
73 77
74
21
9
VAUX
GND GND GND GND GND GND GND GND GND GND
VAUX
22
10
1
11
AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
2
12
3
13
4
14
5
15
6
16
7
17
8
18 25 26
78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
Fig. 7. CentraLine Panel Bus Analog Input Module
(schematic)
Features 0…10 Vdc, 2…10 Vdc without pull-up 0…10 Vdc with pull-up (linear graph, e.g. used for wall
module connection) 0/4…20 mA, needs 499 Ω resistor in parallel NTC20kΩ (-50…+150 °C, default) NTC10kΩ (-30…+100 °C) PT1000-1 (-50…+150 °C) PT1000-2 (0…+400 °C) NI1000TK5000 (-30…+130 °C) PT3000 (-50…+150 °C) BALCO500 (-30…+120 °C) Binary input 16-bit resolution Configurable offset per input Auxiliary voltage: 10 Vdc, IMAX = 5 mA Sensor failure detection See also section "Sensor Characteristics" on pg. 24.
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 7
OPT. AUX. TERMINAL MODULE XS814
A1 A2 A3 A4 A5 A6 A7 B1 B
CLIOP821 ANALOG INPUT MODULE
74
21
9 925
GND GNDGND GNDGNDGNDGNDGND GND GND GND GND
22
10 1026
1
11
AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
2
12
3
13
4
14
5
15
6
16
7
17
8
18
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
VAUX VAUX
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
ACTIVE SENSOR1: 24V POWER2: 0...10 VDC SIGNAL3: GND (24V 0)
~
~
AUX. VOLTAGE + POT.1: SIGNAL2: GND3: 10 VDC AUX.
2 23 31 1
F1
F2
CLIOP...
(24 VAC)EXTERNALGROUND
REQUIRED TOPOWER
EXTERNALDEVICES
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 8. CLIOP821 Panel Bus AI Module, wiring example 1: Active sensor and potentiometer
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 8
DRY CONTACT1: SIGNAL2: GND
CLIOP821 ANALOG INPUT MODULE
CLIOP... CLIOP...
74
21
9 925
GND GNDGND GNDGNDGNDGNDGND GND GND GNDGND
22
10 1026
1
11
AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
2
12
3
13
4
14
5
15
6
16
7
17
8
18
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
VAUX VAUX
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
2 22 1 11
DRYCONTACT TEMP. SENSOR
(NTC20k or Pt1000)
0(4)...20 mA1: IN2: OUT
7824V~0
77
76
75
24V~
COMB
COMA
EXTERNAL 499 OHMRESISTOR WITHTWIN WIRE-END
FERRULESREQUIRED.
EXTERNALDC POWER
SUPPLY
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 9. CLIOP821 Panel Bus AI Module, wiring example 2: Passive sensor and 0 (4) … 20 mA signal
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 9
Analog Output Modules
4 53
2
1
Fig. 10. CLIOPR822 Panel Bus AO Module (shown with
terminal socket) Legend 1 Hex switch S2 2 Manual overrides 3 Status LEDs 4 Service LED 5 Power LED The pluggable CentraLine Panel Bus Analog Output Modules, with 8 analog outputs, are available in the following models: CLIOP822 Panel Bus Analog Output Module (without
manual overrides) CLIOPR822 Panel Bus Analog Output Module (with
manual overrides) They are installed with the XS821-22 or XSU821-22 Terminal Socket.
Accessory disconnector module: XS812 (see also Table 2 on page 3).
71 75
72 76
73 77
74
21
9
GND GND GND GND GND GND GND GND GND GND
22
10
1
11
AO1NC NC AO2 AO3 AO4 AO5 AO6 AO7 AO8
2
12
3
13
4
14
5
15
6
16
7
17
8
18 25 26
78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
Fig. 11. CentraLine Panel Bus Analog Output Modules
(schematic)
Features 0…11 Vdc, +/-1 mA Floating actuator (requires MCD3) Binary output (0 V / 10 V) red LED per output (brightness according to signal level) Optional versions with manual override potentiometers
(Auto, 0…100%; LED flashes in override mode) Feedback on manual override signal 8-bit resolution Configurable safety position for outputs in case of
communication problems (remain, 0%, 50%, 100%)
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 10
CLIOP822 ANALOG OUTPUT MODULE
CLIOP...
OPT. AUX. TERMINAL MODULE XS814
74
925
GND GND
1026
A1 A2 A3 A4 A5 A6 A7 B1
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
2 31
F1
F2
21
NC NC22 1
AO1AO2AO3AO4AO5AO6AO7AO8
2 3 4 5 6 7 8
M
9
GND GND GNDGNDGNDGND GND GND GNDGND
10 11 12 13 14 15 16 17 18
24V DRIVE WITH0...10 VDC SIGNAL1: 24V POWER2: GND (24V 0)3: 0...10 VDC SIGNAL
~
~~
B
XS814
A1 A
(24 VAC)EXT. GROUND
REQUIREDTO POWER
EXT. DEVICES
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 12. CLIOP822 Panel Bus AO Module, wiring example 1: Actuator
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 11
CLIOP822 ANALOG OUTPUT MODULE
CLIOP...
OPT. AUX. TERMINAL MODULE XS814
74
925
GND GND
1026
A1 A2 A3 A4 A5 A6 A7 B1
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
2
2
3
3L N
1
1
F1
F2
21
NC NC22 1
AO1AO2AO3AO4AO5AO6AO7AO8
2 3 4 5 6 7 8
M
M
2 1
M
9
GND GND GNDGNDGNDGND GND GND GND GND
10 11 12 13 14 15 16 17 18
11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8
MCD 3
K1 K2 K3
24V DRIVE WITH0...10 VDC SIGNAL1: 24V POWER2: GND (24V 0)3: 0...10 VDC SIGNAL
~
~~
B
XS814
A1 A
(24 VAC)
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
EXT. GROUNDREQUIREDTO POWER
EXT. DEVICES
Fig. 13. CLIOP822 Panel Bus AO Module, wiring example 2: Relay Module MCD 3
The relay module facilitates the control of peripheral devices with high load via the analog outputs. Input terminal 17 of MCD3 controls changeover contact K3. Relay terminal 18 of MCD3 controls the N.O. contacts (floating outputs) K1, K2.
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 12
CLIOP822 ANALOG OUTPUT MODULE
CLIOP...
OPT. AUX. TERMINAL MODULE XS814
74
925
GND GND
1026
A1 A2 A3 A4 A5 A6 A7 B1
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
2 31
F1
F2
21
NC NC22 1
AO1AO2AO3AO4AO5AO6AO7AO8
2 3 4 5 6 7 8
M
9
GND GND GNDGNDGNDGND GND GND GNDGND
10 11 12 13 14 15 16 17 18
24V DRIVE WITH0...10 VDC SIGNAL1: 24V POWER2: GND (24V 0)3: 0...10 VDC SIGNAL
~
~~
B
XS814
A1
(24 VAC)
11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8
MCE 3
K1 K2 K3
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
EXT. GROUNDREQUIREDTO POWER
EXT. DEVICES
Fig. 14. CLIOP822 Panel Bus AO Module, wiring example 3: Relay Module MCE 3
The relay module facilitates the control of peripheral devices with high load via the analog outputs. Input terminal 16 of MCE3 controls the N.O. contact K3. Input terminal 17 of MCE3 controls the changeover contact K2. Input terminal 18 of MCE3 controls the changeover contact K1.
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 13
Binary Input Module
3 42
1
Fig. 15. CLIOP823 Panel Bus BI Module (shown with
XS823 terminal socket) Legend 1 Hex switch S2 2 Status LEDs 3 Service LED 4 Power LED The pluggable CentraLine Panel Bus Binary Input Module, with 12 binary inputs, is installed with the XS823 or XSU823 Terminal Socket. Accessory disconnector module: XS812 (see also Table 2 on page 3).
FASTTOTALIZER
DRY CONTACT4 ... 40 VDC = OPEN0 ... 2 VDC = CLOSED
150 kOHM
10 kOHM
18 VDC (NOT STABILIZED)
+V
BI
GND
Fig. 16. Configuration of a binary input as a fast totalizer
71 75
72 76
73 77
74
GND GND GND GND GND GND GND GND GND GND GND GND
1
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12
2 3
13
4
14
5
15
6
16
7
17
8 9 10 11 12
18 19 20 21 22 23 24 25 26
78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
Fig. 17. CentraLine Panel Bus Binary Input Modules
(schematic)
Features Static binary input (dry contact) Totalizer for up to 20 Hz LEDs per binary input supporting alarm display mode
(red/green) or status mode (off/yellow). Color mode of each LED can be set to OFF/yellow or
green/red in CARE.
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 14
DRY CONTACT1: SIGNAL2: GND
TOTALIZER1: SIGNAL2: GND
CLIOP823 BINARY INPUT MODULE
CLIOP...
74
25
GNDGND GNDGND GND GND GND GND GNDGND GND GND
26
1
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9BI10 BI11BI12
2 3
13
4
14
5
15
6
16
7
17
8 9 10 11 12
18 19 20 21 22 23 24
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
21
DRYCONTACT
F1
21
TOTALIZERMIN. 25 ms
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F1
LEGEND:
THICK LINES
MAX. 4 A
Fig. 18. CLIOP823 Panel Bus BI Module, wiring example: Dry contact and totalizer
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 15
Relay Output Modules
1
4 53
2
Fig. 19. CLIOPR824 Panel Bus Relay Output Module
(shown with terminal socket) Legend 1 Hex switch S2 2 Manual overrides 3 Status LEDs 4 Service LED 5 Power LED The pluggable CentraLine Panel Bus Relay Output Modules, with 6 relay outputs, are available in the following versions: CLIOP824 Panel Bus Relay Output Module (without
manual overrides) CLIOPR824 Panel Bus Relay Output Module (with manual
overrides) They are installed with the XS824-25 or XSU824-25 Terminal Socket. Accessory disconnector module: XS812-RO (see also Table 2 on page 3).
REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED)
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
25
71 75
72 76
73 77
74 78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
RELAY BLOCK 1 RELAY BLOCK 2
Fig. 20. CentraLine Panel Bus Relay Output Modules
(schematic)
Features - Cross-Connecter - 1 yellow LED per output - Optional versions with manual override switches (Auto, 0,
1; LED flashes in override mode) - Feedback on manual override signal - Configurable safety position for outputs in case of
communications problems (remain, OFF, ON) - Permissible Load per Relay Output Module (Total)
Max. load (fuse F3): 19…250 Vac: 12 A 1…24 Vdc: 12 A resistive, 3 A inductive
- Permissible Load per Normally-Open Contact: Max. load:
19…250 Vac: 4 A resistive or inductive 1…24 Vdc: 4 A resistive, 1 A inductive
Min. load: P > 50 mW - Permissible Load per Normally-Closed Contact:
Max. load: 19…250 Vac: 2 A resistive, 1 A inductive 1…24 Vdc: 2 A resistive, 1 A inductive
Min. load: P > 50 mW
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 16
OPTIONAL AUX. TERMINAL PACKAGE XS814
POWER SUPPLY230 VAC
NL
B1 B2 B3 B4 B5 B6 B7A1 A2 A3 A4 A5 A6 A7
CLIOP...
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
74 24V~0
73
72
71
24V~
COMB
COMA
CLIOP824 RELAY OUTPUT MODULE
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
25
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
FIELD DEVICE1: 230 V (N)2: 230 V (L)
FIELD DEVICE1: 230 V (N)2: 230 V (L)
1 2
M230 V
1 2
M230 V
F1
F3
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F32
DASHED LINES
THIN LINES
F3
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
CROSS CONNECTOR XS815 (FACTORY-MOUNTED)
Fig. 21. CLIOP824 Panel Bus RO Module, wiring example 1: Both relay blocks with line voltage
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 17
POWER SUPPLY230 VAC
CROSS CONNECTOR XS815 (FACTORY-MOUNTED)
NL
CLIOP...
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
74 24V~0
73
72
71
24V~
COMB
COMA
CLIOP824 RELAY OUTPUT MODULE
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
25
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
FIELD DEVICE1: 230 V (N)2: 230 V (L)
FIELD DEVICE1: 230 V (N)2: 230 V (L)
1 2
M230 V
1 2
M230 V
F1
FIELD DEVICE1: 230 V (N)2: 230 V (L)
1 2
M230 V
OPTIONAL AUX. TERMINAL PACKAGE XS814
B1 B2 B3 B4 B5 B6 B7A1 A2 A3 A4 A5 A6 A7
F3
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F32
DASHED LINES
THIN LINES
F3
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 22. CLIOP824 Panel Bus RO Module, wiring example 2: Relay blocks with low and line voltage
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 18
Floating Output Module
4 53
2
1
Fig. 23. CLIOPR825 Panel Bus Floating Output Module
(shown with terminal socket) Legend 1 Hex switch S2 2 Manual overrides 3 Status LEDs 4 Service LED 5 Power LED The pluggable CLIOPR825 Panel Bus Floating Output Module, with manual overrides and 3 floating outputs, is installed with the XS824-25 or XSU824-25 Terminal Socket. Accessory disconnector module: XS812-RO (see also Table 2 on page 3).
REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED)
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
25
71 75
72 76
73 77
74 78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
ACTUATOR 1 ACTUATOR 2 ACTUATOR 3
Fig. 24. CentraLine Panel Bus Floating Output Module
(schematic)
Features - Cross-Connecter - 1 red LED (opening) and 1 green LED (closing) per
floating output - Manual override potentiometers (Auto, 0%...100%; LED
flashes in override mode) - Feedback on manual override signal - Configurable safety position for outputs in case of
communication problems (remain, 0%, 50%, 100%) - Permissible Load per Floating Output Module (Total)
Max. load (fuse F3): 19…250 Vac: 12 A 1…24 Vdc: 12 A resistive, 3 A inductive
- Permissible Load per Normally-Open Contact: Max. load:
19…250 Vac: 4 A resistive or inductive 1…24 Vdc: 4 A resistive, 1 A inductive
Min. load: P > 50 mW - Permissible Load per Normally-Closed Contact:
Max. load: 19…250 Vac: 2 A resistive, 1 A inductive 1…24 Vdc: 2 A resistive, 1 A inductive
Min. load: P > 50 mW
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 19
FLOATING ACTUAOR WITH 230VAC(REQUIRES TWO RELAYS)1: 2: 3: N
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
CON CON CON CON CON CON14 24 34 44 54 64
CLIOP...
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
74 24V~0
73
72
71
24V~
COMB
COMA
CLIOPR825 FLOATING OUTPUT MODULEF1
25
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
POWER SUPPLY230 VAC
NL 23 1
M
F3
OPTIONAL AUX. TERMINAL PACKAGE XS814
B1 B2 B3 B4 B5 B6 B7A1 A2 A3 A4 A5 A6 A7
CROSS CONNECTOR XS815 (FACTORY-MOUNTED)
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F32
DASHED LINES
THIN LINES
F3
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 25. CLIOPR825 Panel Bus FO Module, wiring example: Floating actuator
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 20
Mixed I/O Modules CLIOP830 CLIOP831
Fig. 26. Mixed Panel Bus Modules
The CLIOP830 and CLIOP831 mixed Panel Bus I/O modules feature 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs. The CLIOP830 is equipped with push-in terminals, while the CLIOP831 features screw-type terminals. Both feature an integrated terminal socket and electronic module and come complete with one bridge connector and one swivel label. The CLIOP830 can be equipped with up to two rows of (XS830 and/or XS831) auxiliary terminal blocks on the top and/or bottom. The CLIOP831 can be equipped with up to two rows of (XS830 and/or XS831) auxiliary terminal blocks on the top, only.
AI5
AI1 AI2 AI3 AI4 41
G1 G2
42
17
13 14 15 16
18 19 20
AI6 AI7 AI8 AO525
21 22 23 24
26 27 28 35
29 30 31 32 33 34
36 37 38 39 40
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
1 2 3 4 5 6
25 26 27 28 35 36 37 38 39 40
1 21 22 23 24 29 30 31 32 33 342 3 4 5 6 13 14 15 16 41 42
7 8 9 10 11 12 17 18 19 20
Analog Inputs Analog OutputsGND
DO!
CLIOP830A12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T500706AX0001-XFU830A
Made in Germany0532
8
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B93
24V Relays
2
1 0
F E
D C B
9 8
7
6 5 4 3
A
40External
24V for relay 1...5
24V
J1 J2 J3 J4 J5
71 75
76
77
78
COM a
COM b
24V~
24V~0
COM a
COM b
24V~
24V~0
72
73
74 S2
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8
B7
B1 B2 B3 B4 B5 B6
B8 B9 B10 B11 B12
DI
Binary Inputs
Install. Instr.EN1B-0375GE51
7
1 2 3 4 5 6
8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
1 2
4
Fig. 27. CLIOP830 mixed Panel Bus I/O module, shown with 4 optional aux. terminal blocks (top view)
1 2 3 4 5 6 7 8 9 10 11 12
B1 B2 B3 B4 B5 B6
B12
12
6
B11
11
5
B10
10
4
B9
9
3
B8
8
2
B7
7
1
BI
Binary Inputs
G1 G2
41 42
GND Analog Outputs
AI2 AI3 AI4
14 15 16
AI1
AI5 AI6 AI7 AI8
17 18 19 20
13
Analog Inputs
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
21
25 26 27 28
22 23 24
BO
24V Relays
NO1 NO2 NO3 NO4 NO5 NO6
IN1 IN2 IN3 IN4 IN5 IN6
35
29 30 31 32 33 34
36 37 38 39 40
1 2 3 4 5 6 !
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B91
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B93
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B92
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B84
40External
24V FOR RELAY 1...5
24V
J1 J2 J3 J4 J5
71 COM a
COM b
24V~
24V~0
72
73
74
75
76
77
78
COM a
COM b
24V~
24V~0
Fig. 28. CLIOP831 mixed Panel Bus I/O module, shown
with 4 optional aux. terminal blocks (top view)
Features - 1 yellow LED per output - Configurable safety position for outputs in case of com-
munications problems (remain in last position, OFF, ON)
Table 6. Permissible loads of Mixed Panel Bus I/O Modules
max. load min. load
per module (total for all relay contacts)
24 VDC/VAC 3 A resistive or inductive, cos φ ≥ 0.6, no capacitive load, protected by fuse F4
–
per nor-mally open contact
24 VDC/VAC, 0.5 A resistive or inductive, cos φ ≥ 0.6, no capacitive load
>50 mW, 0.05 A res./ind.,cos φ ≥ 0.6
199.9 kOHMVi
AI
GND
Fig. 29. Analog input high impedance (input circuit for
voltage input for active sensors)
199.9 kOHM(8.9 VDC IFCONNECTIONINTERRUPTED)
Vi
AI
GND
24.9 kOHM
10 VDC
Fig. 30. Analog input impedance setpoint (input circuit
for NTC10kΩ, NTC20kΩ, wall module setpoint)
FASTTOTALIZER
DRY CONTACT16 ... 22 VDC = OPEN 0 ... 2 VDC = CLOSED
150 kOHM
10 kOHM
18 VDC (NOT STABILIZED)
+V
BI
GND
Fig. 31. Configuration of a binary input as a fast totalizer
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 21
CLIOP830 Mixed I/O Module
2 21
DRYCONTACT1: GND2: SIGNAL
DRYCONTACT1: GND2: SIGNAL
21 1
ACTIVESENSOR1: GND (24V 0)2: 24V POWER3: 0...10 VDC
~~
23 31
0...10 VDC 0...10 VDCM
1 2
M
1 2
XS830 OPT. AUX. TERM. MODULE XS830
F1
F4
1 2
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
41 42
B10 B11 B12 AI5
AI1
AI6
AI2
AI7
AI3
AI8
AI4
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
IN1
NO1
IN2
NO2
IN3
NO3
IN4
NO4
IN5
NO5
IN6
NO6
B7 B8 B9
7 8 9 10 11 12 17
13
18
14
19
15
20
16
25
21
26
22
27
23
28
24
35
29
36
30
37
31
38
32
39
33
40
34
B1 B2 B3 B4 B5 B6
1 2 3 4 5 6
G1 G2
A7 A7B7 B7A8 A8B8 B8A9 A9B9 B9A1 A1B1 B1A2 A2B2 B2A3 A3B3 B3A4 A4B4 B4A5 A5B5 B5A6 A6B6 B6
TOTALIZER1: GND2: SIGNAL
NTC20kOHMSENSOR1: GND2: SIGNAL
24V
1: GND (24V 0)2: 24V POWER3: 0...10 VDC
~ DRIVE with0...10V SIGNAL
~~
DCA1: 24V 02: 24V
~~
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F2, F42
THIN LINES
F4
F1 F2LEGEND:
THICK LINES
MAX. 3 A
MAX. 4 A MAX. 12 A
F2
(GND 24 VAC)
BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS
(24 VAC)(GND)
Fig. 32. CLIOP830 mixed Panel Bus I/O Module, wiring example: Actuators
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 22
ACTIVESENSOR1: GND (24V 0)2: 24V POWER3: 4...20 mA
~~
CLIOP831 Mixed I/O Module
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
A7 A7B7 B7A8 A8B8 B8A9 A9B9 B9A1 A1B1 B1A2 A2B2 B2A3 A3B3 B3A4 A4B4 B4A5 A5B5 B5A6 A6B6 B6
A4 A8B4 B8G1 G2A1 A5B1 B5A2 A6B2 B6A3 A7B3 B7
OPT. AUX. TERM. MODULE XS830 OPT. AUX. TERM. MODULE XS830
OPT. AUX. TERM. MODULE XS831
F2
F1
4...20 mA
1 2 3
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F22
THIN LINES
F1 F2LEGEND:
THICK LINES
MAX. 4 A MAX. 12 A
BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS
41 42
B10 B11 B12 AI5
AI1
AI6
AI2
AI7
AI3
AI8
AI4
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
IN1
NO1
IN2
NO2
IN3
NO3
IN4
NO4
IN5
NO5
IN6
NO6
B7 B8 B9
7 8 9 10 11 12 17
13
18
14
19
15
20
16
25
21
26
22
27
23
28
24
35
29
36
30
37
31
38
32
39
33
40
34
B1 B2 B3 B4 B5 B6
1 2 3 4 5 6
G1 G2
Fig. 33. CLIOP831 mixed Panel Bus I/O Module, wiring example: Current inputs
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 23
Approvals, Certifications, and Standards Approvals and Certifications
CE-approved Conforms to EN 60730-1 and EN 60730-2-9 Investigated according to United States Standard
UL916 (USL-listed) as well as according to Canadian National Standard(s) C22.2 (CNL-listed)
Classification according to EN60730-1 Environmental conditions: For use in home (residential,
commercial, and light-industrial) environments
Pollution degree: Class 2 Protection against shock: Class II Software class: Class A Overvoltage category: II
Classification according to EN60529 (Degree of Protection Provided by Enclosures) Classification: IP20
Ambient Environmental Limits Operating temperature: 0 … +50 °C at 5…93% r.H. Storage temperature: -20 … +70 °C at 5…93% r.H. Humidity: 5 … 93% r.h. non-condensing
Current Requirement and Heat Dissipation The Panel Bus I/O Modules are equipped with highly-efficient switching power supplies which provide for relatively uniform power consumption over a wide range of supply voltages (see Table 7). The specific heat dissipation inside the modules amounts to less than 2 W for all models.
Table 7. Current requirements of CentraLine Panel Bus I/O Modules
devices powered supply voltage
24 Vac 24 Vdc
CLIOP821 130 mA 80 mA
CLIOP822, CLIOPR822 150 mA 90 mA
CLIOP823, CLIOL823 180 mA 130 mA
CLIOP824, CLIOPR824, CLIOPR825 140 mA 80 mA
CLIOP830, CLIOP831 200 mA 95 mA
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 24
Mechanical Housing dimensions (H x W x D) The pluggable CentraLine I/O Modules (mounted on Terminal Sockets) all have the dimensions: 110 X 90 X 93 mm (see also Fig. 34 on page 25). The CLIOP830 mixed Panel Bus I/O module has the dimensions: 216 X 110 X 93 mm (see also Fig. 35 on page 25). The CLIOP831 mixed Panel Bus I/O module has the dimensions: 216 X 110 X 61 mm (see also Fig. 36 on page 26).
Housing Material Plastic, flame-retardant
Mounting Methods DIN-rail mounting (e.g. in control cabinet).
Calculated Lifetime of Weakest Components MTBF 13.7 years (under typical operating conditions)
Sensor Characteristics The following sensor characteristics do not include failures due to: sensor failures; wiring resistance or wiring failures; misreadings due to a meter connected to measure
resistance or voltage at the input. For more-detailed values, see section "Appendix 3: Sensor Characteristics" of the CentraLine I/O Modules – Installation & Commissioning Instructions (EN1Z-0973GE51).
Table 8. BALCO 500
Temp. [°C] Resistance [] Terminal voltage [V]
-20.0 415 0.164
0.0 453 0.179
20.0 493 0.194
40.0 535 0.210
60.0 579 0.227
80.0 625 0.245
100.0 673 0.263
120.0 724 0.283
Table 9. NTC 20 kOhm
Temp. [°C] Resistance [k Terminal voltage [V]
-20.0 221.0 8.08
0.0 70.2 6.76
20.0 25.3 4.75
40.0 10.2 2.81
60.0 4.52 1.51
80.0 2.17 0.792
100.0 1.11 0.425
120.0 0.61 0.238
Table 10. Pt 1000
Temp. [°C] Resistance [ Terminal voltage [V]
-20.0 922 0.357
0.0 1000 0.386
20.0 1078 0.415
40.0 1155 0.443
60.0 1232 0.471
80.0 1309 0.499
100.0 1385 0.527
120.0 1461 0.554
Table 11. Ni1000TK5000
Temp. [°C] Resistance [Ω] Terminal voltage [V]
-20.0 913.5 0.354
0.0 1000.0 0.386
20.0 1090.7 0.420
40.0 1185.7 0.455
60.0 1285.4 0.491
80.0 1390.1 0.529
100.0 1500.0 0.568
120.0 1615.4 0.609
Table 12. NTC 10 kOhm
Temp. [°C] Resistance [k Terminal voltage [V]
-20.0 97.073 7.241
0.0 32.650 5.299
20.0 12.490 3.207
40.0 5.327 1.724
60.0 2.488 0.898
80.0 1.258 0.478
100.0 0.680 0.265
Table 13. Pt 3000
Temp. [°C] Resistance [k Terminal voltage [V]
-20.0 3.090 1.104
0.0 3.266 1.160
20.0 3.440 1.214
40.0 3.613 1.267
60.0 3.784 1.319
80.0 3.954 1.370
100.0 4.122 1.420
120.0 4.289 1.469
PANEL BUS I/O MODULES – PRODUCT DATA
EN0Z-0979GE51 R0316 25
Dimensions
LOCK
89.5 94.1
51.5
45
83 67.5
14
110
XS814 Aux. Terminal Package (optional)
2830.6
SWIVEL LABEL HOLDER
38
SCREW-TYPETERMINALS
Fig. 34. CentraLine Panel Bus I/O Modules (example shows Manual Overrides), incl. Terminal Socket, outside
dimensions (in mm)
92.5
51.5
45
69
100
CLE
AR
AN
CE
15
110
28
SWIVEL LABEL HOLDER
B7
B1 B2 B3 B4 B5 B6
7
1 2 3 4 5 6
8 9 10 11 12
B8 B9 B10 B11 B12 AI5
AI1 AI2 AI3 AI4 41
G1 G2
42
17
13 14 15 16
18 19 20
AI6 AI7 AI8 AO525
21 22 23 24
26 27 28 35
29 30 31 32 33 34
36 37 38 39 40
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
1 12 23 34 45 56 67
25 26 27 28 35 36 37 38 39 40
1 21 22 23 24 29 30 31 32 33 342
8 9
3
10
4
11
5
12
6 13 14 15 16 41 42
7 8 9 10 11 12 17 18 19 20
DI
Binary Inputs Analog Inputs Analog Outputs 24V RelaysGND
S2
DO!
Install. Instr.EN1B-0375GE51
CLIOP830A12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T500706AX0001-XFU830A
Made in Germany0532
8
2
1 0
F
E
D C B
9 8
7
6 5 4 3
A
40External
24V for relay 1...5
24V
J1 J2 J3 J4 J5
71 75
76
77
78
COM a
COM b
24V~
24V~0
COM a
COM b
24V~
24V~0
72
73
74
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9A
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9B
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9C
216
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8D
D = XS831 Aux. Terminal Package (optional)A, B, and C = XS830 Aux. Terminal Packages (optional)
Fig. 35. CLIOP830 mixed Panel Bus I/O module (shown with 4 auxiliary terminal packages), dimensions (in mm)
PANEL BUS I/O MODULES – PRODUCT DATA
Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
CentraLine Honeywell GmbH Böblinger Strasse 17 71101 Schönaich, Germany Phone +49 (0) 7031 637 845 Fax +49 (0) 7031 637 740 [email protected] www.centraline.com
Subject to change without notice EN0Z-0979GE51 R0316
216 54.444
61.1
110
1 2 3 4 5 6 7 8 9 10 11 12
B1 B2 B3 B4 B5 B6
B12
12
6
B11
11
5
B10
10
4
B9
9
3
B8
8
2
B7
7
1
BI
Binary Inputs
G1 G2
41 42
GND Analog Outputs
AI2 AI3 AI4
14 15 16
AI1
AI5 AI6 AI7 AI8
17 18 19 20
13
Analog Inputs
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
21
25 26 27 28
22 23 24
BO
24V Relays
NO1 NO2 NO3 NO4 NO5 NO6
IN1 IN2 IN3 IN4 IN5 IN6
35
29 30 31 32 33 34
36 37 38 39 40
1 2 3 4 5 6 !
40External
24V FOR RELAY 1...5
24V
J1 J2 J3 J4 J5
71 COM a
COM b
24V~
24V~0
72
73
74
75
76
77
78
COM a
COM b
24V~
24V~0
Fig. 36. CLIOP831 mixed Panel Bus I/O module, dimensions (in mm)