Transcript
Page 1: PDFINFO G E B - 0 4 1 7 GE Molded Case Circuit Breakers ... Breakers/TEY.pdfGE Molded Case Circuit Breakers Prices and data subject to change without notice 1999 Issue 4-17 4 MOLDED

PDFINFO G E B - 0 4 1 7

GE Molded Case Circuit Breakers

4-17Prices and data subject to change without notice 1999 Issue

4M

OLD

ED C

AS

EC

IRC

UIT

BR

EAK

ERS

TEY Line Circuit Breakers15-100 amperes

277 Vac, Single-Pole250 Vdc

480Y/277 Vac, Two- and Three-Pole60/75°C Conductor Ratings

UL listed as HACR type

The TEY is a one-inch wide per pole, compact, ‘‘bolt-on’’ circuitbreaker for use on grounded 480Y/277 Vac systems. The bolt-onmounting base, shown in the accessory table below, makes theTEY suitable for varied applications as a lug-lug breaker.

UL Listed Interrupting Ratings(rms symmetrical kilo-amperes)

System Voltage 120 Vac 240 Vac 277 Vac 480Y/277 Vac 125 Vdc 250 Vdc

Single-pole 65 14 14 — 10 —Two-pole — 65 — 14 10 10Three-pole — 65 — 14 — —

Single-Pole Two-Pole Three-PoleAmpere Catalog List Catalog List Catalog ListRating Number Price Number Price Number Price

GO-135B GO-135B GO-135B

15 TEY1151 $ 72.00 TEY215 $216.00 TEY315 $316.0020 TEY1201 72.00 TEY220 216.00 TEY320 316.0030 TEY130 72.00 TEY230 216.00 TEY330 316.0040 TEY140 72.00 TEY240 216.00 TEY340 316.0050 TEY150 72.00 TEY250 216.00 TEY350 316.0060 TEY160 72.00 TEY260 216.00 TEY360 316.0070 TEY170 142.00 TEY270 352.00 TEY370 424.0080 TEY180 142.00 TEY280 352.00 TEY380 424.0090 TEY190 142.00 TEY290 352.00 TEY390 424.00

100 TEY1100 142.00 TEY2100 352.00 TEY3100 424.00

Internal Accessories For TEY(Two- and Three-Pole Breaker Only—Factory Installed Only)

Add suffix to ListAuxiliary Switch, Single-Pole Breaker Price Adder,(6A at 240 Vac, 1⁄2A at 125 Vdc, 1⁄4A at 250 Vdc Catalog Number GO-135B

‘‘A’’ switch (normally open) AS1A $148.00‘‘B’’ switch (normally closed) AS1B 148.00‘‘AB’’ switch (both) ASAB 288.00

Shunt Trip120-277 Vac control voltage ST12 358.00

Available Wire RangesCircuit Breaker (load lug) #14, #12 Cu15, 20A #12, #10 Al

30-60A #10-6 Cu#8-4 Al

70-100A #4-1 Cu#2-1/0 Al

Bolt-on Mounting Base, #14-1/0 CuCat. No. TEY3B (line lugs) #12-1/0 Al

1 Single-pole, 15 and 20 amp breakers are also UL listed as switchingduty breakers, suitable for switching 120, 240, or 277 Volts ac.

Bolt-On Mounting Base for TEY(For 1-, 2-, or 3-Pole)

Catalog ListDescription Number Price, GO-135B

Accepts one three-pole or threesingle-pole breakers. Base assembliesstack together with no loss of one poleper inch spacing.

TEY3B $31.50

Top Related