Colour Coding to Pipelines (Ground Colour and Colour Bands)
Giving a base or ground colour to pipelines based on fluid flowing, the line identification is
done. Further colour bands are provided accordingly. The base/ground colour gives the
basic nature of the flowing fluid (i.e. water, air, gases etc.).
Typically ground colours are provided on the full pipe section or minimum 300 mm length
portion or by attaching the label.
Ground colour Fluid flow inside the pipe
Green Water
Sky Blue Air
ellow Gases
Aluminum Steam
Over and above the base colour or ground colour to the pipeline, colour bands are provided
to differentiate and identify the application of the basic fluid.
Example:
(1)Fluid:Water
GroundColourCode:Green
Cooling water: Sea green (ground colour) and application is for cooling hence a furthercolour band of French blue is provided.
(2) Fluid: Air
Ground colour code: Sky blue
Plant air: Sky blue (ground colour) and application is for supplying the plant air hence a
further colour band of silver grey is provided.
Colour Bands
As stated earlier, colour bands in single or double over the ground colour on the pipeline,
and the ground colour on the entire or partial length of the pipeline is provided. These
colour bands are provided at suitable locations such as:
At the beginning and termination points
8/12/2019 Pipeline Marking
http://slidepdf.com/reader/full/pipeline-marking 2/4
For yard piping around 50 to 60 m distances
At change in flow direction points and flow diversion locations.
At locations where the pipe enters the building or exits from the building
Typical Practices Followed for the Provision of Ground Colour
and Colour Bands on the Pipelines(1) If colour bands are provided over the ground colour, then the ground colour should extend on
both sides of the colour bands.
(2) When double colour bands exist on the pipeline, then a proportional width of 4:1 to the next
colour band is provided.
(3) Minimum colour band width to be 25 mm.
(4) Generally below 80 NB piping width of the colour band is 25 mm.
(5) For piping 100 NB to 150 NB width of the colour band is 50 mm.
(6) Valves and piping accessories to be painted with the same colour as that of the pipe groundcolour.
(7) For insulated pipes, non-ferrous pipes, S.S. pipe ground colour to be given for minimum 1.5
m length.
(8) For uninsulated piping above 100 Degree C, generally colour bands are not provided (only
ground color Aluminum). If bands are to be provided then they should be of Teflon tape.
8/12/2019 Pipeline Marking
http://slidepdf.com/reader/full/pipeline-marking 3/4
(9) Flow direction, arrows to be marked at suitable intervals along the line. Line carrying
fluid, the fluid name should be written in the white box on the ground colour provided for
the line.
Arrow sizes, dimensions differ w.r.t. company standards.
Example:
Below 200 NB line arrow dimensions are given below.
Lettering size for fluid name is also based on the pipe diameter
Examples:
100 NB Pipe ---------------Legend Size is 30 mm
50 NB Pipe -----------------Legend Size is 25 mm
200 NB Pipe ---------------Legend Size is 50 mm
(10) Visibility of Marking: It should be such that the operator can see if it is at the normal height.
If lines are above the operator's head (may be along the roof, or side wall or through the rack),then the lettering is to be done below or towards the bottom side of the pipe.
8/12/2019 Pipeline Marking
http://slidepdf.com/reader/full/pipeline-marking 4/4
(11) Lighting provided in the plant should not affect the colour and shades in terms of visibility
particularly at night.
(12) For closed circuit lines other than direction ‘F' for “Flow” and ‘R' for “Return” to be writtenfor better understanding.
(13) Lines carrying hazardous materials have a panel of colour with dots, strips, crosses are
marked based on the practices.
Hence, finally uniformity for color coding on pipelines will lead to better safety, less human
errors