Transcript
Page 1: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING/STEAM DISTRIBUTION 02695/15521Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes2695 DIRECT BURIAL PIPING PERMA-PIPE

or Approved EqualGalva-Guard STEAM and

CONDENSATEFor steam pipe 4" and smaller specify steam and condensate in common conduit

2695 DIRECT BURIAL PIPING PERMA-PIPEor Approved Equal

DUALGUARD 250 CONDENSATE BELOW 225F for replacement of existing condensate only

2695 IDENTIFICATION ALLEN SYSTEMSor Approved Equal

LINE MARKER

2695 LINK SEAL LINK SEALor Approved Equal

MODEL-T FOUNDATION /WALL PENETRATION

High temp

December 2006

Page 2: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING/ UTILITIES TUNNEL 02300Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes02300/15521 EXPANSION JOINT ATS

or approved equalTHERMAL PACK TP2F

EXPANSION JOINTSTEAM

02300/15521 EXPANSION JOINT ATSor approved equal

THERMAL PACK TP2F EXPANSION JOINT

CONDENSATE

02300/15521 LINK SEAL LINK SEALor Approved Equal

MODEL T TUNNEL/WALL PENETRATIONS

High Temp

02300/15521 SLIDE GUIDES ATSor approved equal

LOW FRICTION GRAPHITE GUIDE

SLIDE GUIDES

December 2006

Page 3: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

Colorado School of Mines Campus Standards

PLUMBING MATERIALS AND METHODS 15050Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15050 Ball Valves Apollo

MilwaukeeBronze body, full port made in USA), (Comply with MSSSP110

Butterfly Valves DeZurikKeystoneMilwaukee

NibcoVictaulic

Comply with MSSSP67

NonLubricated Eccentric Plug Valves

DeZurikKeystone

Lubricated Plug Valves NordstromPowell

WalworthGas Cocks (AGA, CGA, UL):

CraneHammond

PeterHealy

Alternate: Milwaukee "Butterball" valves

U.L., F.M. Approved or Listed Valves

DemcoGEM

GrinnellJomar

KennedyKeystoneMissionMuellerNibcoPratt

Victaulic

Plumbing Standards(Rev. 10/23/2009) 15000-1

Page 4: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING/ MECHANICAL INSULATION 15250Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15250 FIBERGLASS/PLASTIC

FITTINGSOWENS CORNINGor approved equal

DCW,RD,DHW,DWH,UL,CDW,

15250 FIBERGLASS/PLASTIC FITTINGS

OWENS CORNINGor approved equal

PLUMBING VALVES AND FITTINGS

15250 FIBERGLASS/PLASTIC FITTINGS

OWENS CORNINGor approved equal

HEATING SYSTEM PIPING

15250 FIBERGLASS/PLASTIC FITTINGS

OWENS CORNINGor approved equal

CHILLING SYSTEMS

15250 ALUMINUM JACKET POLYGAURD ALUMIGARD 60

or Approved Equal

CHILLING SYSTEMS

15250 SARCO PTC PUMP REMOVABLE JACKET

SARCO or approved equal

CONDENSATE PUMP

15250 ATS EXPANSION JOINT REMOVABLE JACKET

ATSor approved equal

EX JOINTS

December 2006

Page 5: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING/FIRE PROTECTION 15300Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15300 FIRE HEADS VIKING ALL Or match existing

15300 Sprinkler Heads VIKING ALLMust be from current year supply.

No old stock that is un-used.

15300 Pipe Dutile lorn Underground

15300 PipeSch 40 2" and below

ASTM A53Above Ground sprinkler

stand pipe Corrosion resistance 1.00 or greater

15300 PipeSch 10 2 1/2" and Larger ASTM A53

Above Ground sprinkler stand pipe Corrosion resistance 1.00 or greater

15300 PipeGalvanized Sch 40 2" and below ASTM A53 Drains

15300 Pipe

Galvanized Sch 10 2 1/2" and below ASTM

A53 Drains

15300 Fittings 2" and smaller cast class 125 Threaded Above Ground

15300 Fittings

2" 2 1/2" and larger Groved Victolic ASTM

A536 Above Ground

15300 Gate Valves2" and under thrd rising

stern Above Ground

15300 Gate Valves2 1/2" and larger flanged

or grooved Above Ground

15300 Check ValvesVIKING / VICTAULIC 2

1/2" and over

15300 Butterfly and Ball Valves VICTAULIC

15300Fire Protection Specialty

Valves VIKING

15300Fire Department

Connection POTTER

15300 Fire Protection Specialty POTTER

15300Inspectors Test and

Main Drain VIKING

15300 Double Check Valve FEBCO Owner Approved

15300 Preaction VIKING

15300 Air Compressors VIKING / GAST

15300 Alarm / Flow / Tamper VICTAULIC / POTTER

15300

Riser Assemblies VIKING ALL

15300

Surger restorators VIKING ALL OVER 100# PSI

15300

BAR JOIST HANGER VIKING ALL OVER 100# PSI

15300

SAMMYS VERTICAL AND SIDEWINDER

VIKING WOOD

15300

EXPANSION TANK WILKINGS ANTI-FREEZE

15300

ADJUSTABLE PRESSURE RELIEF

WATTS ALL

15300

HANGERS, CLAMPS FASTNERS

VIKINGTOLCO

ALL

15300

Anti-Freeze propylene glycol

INHIBITED DOW FROTS PROPYLENE

GLYCOL

ANTI-FREEZE

December 2006

Page 6: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

15300 FIRE CAULK HILTI ALL

15300OSY. SUPERVISORY

SWITCHSYSTEM SENSOR PSPI PLUG-IN TYPE OS&Y USE ON ALL OS&Y

December 2006

Page 7: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING PIPING 15410Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15410 ACID WASTE PIPING

AND FITTINGSSPEARS

or approved equalLAB WASTE DWV INSIDE AND OUTSIDE BLDG

15410 CAST IRON SOIL PIPE TYLERor approved equal

BLDG DWV, ROOF DRAINS

INSIDE BUILDING

15410 CAST IRON SOIL PIPE BELL/SPIGOT

TYLERor approved equal

BURIED SEWER LINES INSIDE BUILDING

15410 DI WATER PIPING AND FITTINGS

SPEARSor approved equal

LXT OR PVC ASK USER DI WATER INSIDE BUILDING

15410 NO-HUB BANDS BLDG DWV, ROOF INSIDE BUILDING 15410 PIPE DOPE RECTORSEAL TPLUS2 ALL PIPING THREADS Sole Source15410 SDR35 BURIED BUILDING

SEWER LINES OUTSIDE BUILDING

15410 TEFLON TAPE ALL PIPING THREADS Sole Source15410 TYPE K COPPER BURIED WATER LINES

OVER 2"OUTSIDE BUILDING

15410 TYPE L COPPER CANFIELD "100% DHW, DCW,DWV,CA INSIDE BUILDING 15410 VALVES APOLLO CONBRACO

USA MADEor approved equal

77CLF 140 or 77CLF 240 DCW,DHW,CA INSIDE BLDG

15410 VALVES APOLLO CONBRACO USA MADE

78-100/200 DRAINS 70-100 1/4" GAUGES

DRAIN VALVES GAUGE ISOLATION

INSIDE BLDG - sole source

15410 WATER MAIN VALVE AMERICAN VALVEor approved equal

BURIED WATER LINES OVER 2"

OUTSIDE BUILDING

15410 WATER PIPE FITTINGS OVER 2" DUCTILE IRON

TYLERor approved equal

BURIED WATER LINES OVER 2"

OUTSIDE BUILDINGS

15410 WATER PIPE OVER 2" DUCTILE IRON

PACIFIC STATESor approved Equal

BURIED WATER LINES OVER 2"

OUTSIDE BUILDING

15410 COMM. KITCHEN WASTE PIPING

SPEARSor approved equal

December 2006

Page 8: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING SPECIALTIES 15430Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15430 BACKFLOW FEBCO ANY BFP BLDG MAIN Sole Source15430 BOILER DRAINS APOLLO CONBRACO 31-900 INSIDE MECH ROOM Sole Source15430 DOUBLE CHECK FEBCO ANY BFP FIRE Sole Source15430 Floor Sinks

Planter DrainsDeck DrainsGarage DrainsTrench DrainsRoof DrainsDownspout NozzlesStorm Drain Exp. JointsCleanout FittingsSanitary Vent TerminalAir Gap Fittings

JosamJ.R.Smith

WadeZurn

15430 PVB FEBCO 765 BFP IRRIGATION Sole Source15430 Scald Protection Skal-Gard

BrocarTruebro

or acceptable equal

Trap-WrapLav-Guard

15430 SHOCK ARRESTERS ZURNWATTS

or approved equal

Z1700SS SERIES

BATHROOM GROUPS

15430 SILL COCKS WOODFORD 67 AND B67 OUTSIDE HOSE Sole Source15430 SPVB WATTS 008QT OR008QTS FUME HOODS Sole Source15430 TRAP PRIMERS SLOAN

or approved equalVBF72A ALL PPP prime rite

15430

Trench Drains

J-MarkMaclear MFrg. Co.Neenah Foundry

Heavy Duty C.I. Grate and Frame

15430 VALVES APOLLO CONBRACO 77CLF140 or77CLF240 DCW,DHW,CA Sole Source15430 VALVES APOLLO CONBRACO 78-100/200 DRAINS 70-

100 1/4" GAUGESGAUGES/ DRAINS Sole Source;

Keystone fig. 222 2-1/2” and over. a. 2-1/2” through 4” locking hand lever b. Over 4” gear driven hand wheel operator. c. Stainless steel ball

15430 WATER METER BUILDING WATER PER CITY OF GOLDEN15430 WATER PRV WATTS

or approved equalALL

December 2006

Page 9: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING/FIXTURES 15440Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15440 1/4 TURN STOPS BRASSCRAFT 1/4 TURN CP FIXTURE SHUTOFF OR EQUAL

15440 17 GAUGE TRAPS SINKS CP WITH BRASS NUTS

15440 BATH TUB CRANE 2716NS RH 2717NS LH USE POPUP WAST AND OVERFLOW

15440 DRINKING FOUNTAINS HAWS MODEL 1109 INSIDE BLDG

15440 EMERGENCY EYE WASH

HAWS

15440 FAUCETS Kohler Triton K7825-K-CP Kitchen

FAUCETS - COMM. KITCHEN

WATERSAVER WITH CERAMIC CARTRIDGES

15440 FLUSH VALVE PHOTO EYES

SLOAN EBV-89A-M RESTROOMS WC AND URINALS

15440 FLUSH VALVES SLOAN SLOAN ROYAL 110-YB with SV-37-A diaphram

RESTROOMS WATER CLOSETS 1.6GPF

15440 FLUSH VALVES SLOAN SLOAN ROYAL 180 with SV-43-A diaphram

RESTROOMS URINALS 1.0 GPM

15440 GARBAGE DISPOSALS INSINKERATOR

15440 GRID STRAINERS STAINLESS STEEL

15440 KITCHEN SINK FAUCETS

KOHLER K-7827-K-CP HANDLES K-16010-5

LUNCH ROOMS NO SUBSTITUTIONS

15440 LABORATORY FAUCETS

WATER SAVER FAUCET COMPANY

LABS WITH GOOSE NECK VB

15440 LAV CARRIER ZURN Z-1231 RESTROOMS OR EQUAL

15440 LAVATORIES AMERICAN STANDARD

AQUALYN0476.028

COUNTERTOP DECK MOUNT; WHITE

15440 LAVATORIES AMERICAN STANDARD

LUCERNE0355.012

DORM ROOMS WHITE WALL HUNG

15540 LAVATORY FAUCET KOHLER K-7401-5A-CP DORM ROOMS15440 LAVATORY FAUCETS KOHLER K-7404-5A-CP PUBLIC RESTROOMS15440 LAVATORY FAUCETS

ADA KOHLER K 7305-5A-CP PUBLIC RESTROOMS

ADA

15440 MOP SINK BASIN FIAT MSB 2424 JANITOR CLOSET WHITE, ST.ST. WALL GUARD. ST. ST. RIM GUARD

15440 MOP SINK FAUCET KOHLER K-8906-RP JANITOR CLOSET

15440 SHOWER BASES BradleyFiatFl t15440 SHOWER EQUIP. Bradley Bradley

15440 SHOWER HEAD SUNCRAFT S-188 S188 TUB AND SHOWERS

15440 SHOWER VALVES POWERS MODEL PB413 SHOWERS AND BATHS

NO SUBSTITUTIONS

15440 STAINLESS STEEL SINKS

BRADLEY, ELKAY, JUST

SINKS 18 GAUGE 302/304/316

15440 URINAL CARRIER ZURN Z-1222 RESTROOMS OR EQUAL

15440 URINALS AMERICAN STANDARD

WASHBROOK 6590.001 RESTROOMS WHITE

15440 WATER CLOSET CARRIER

ZURN Z-12## RESTROOMS OR EQUAL

15440 WATER CLOSET TANK TYPE

AMERICAN STANDARD

CADET PRO 215AA.004 RESTROOMS WC-1 ADA

December 2006

Page 10: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

15440 WATER CLOSETS AMERICAN STANDARD

AFWALL2257.001/047007-0070A

RESTROOMS WHITE WALL HUNG

15440 WATER COOLERS ELKAY HAC8FS-Q ADA INSIDE BLDG Infrared sensing actuation not acceptable

15440 WATER MIXING VALVES

LEONARD MODEL 170-LF or 270 ALL HAND SINKS

15440 WATER MIXING VALVES

LEONARD MODLE TM-2020B-LF-DT-IT

EIM DOM. HOT WATER

December 2006

Page 11: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING EQUIPMENT 15450Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15450 STEAM WATER

HEATERSMaxi-therm BY ENGINEER DHW

15450 DOMESTIC HOT TACO 0012-SF4 DHWR sole source

15450 SUMP PUMPS - ELEVATOR

DAYTON GRAINGER #3BB79 ELEVATOR 1/2 hp

15450 SUMP PUMPS - GROUND WATER

DAYTONZOLLER

GROUND WATER

15450 WATER PUMP CONTROLLER

SEEWATER INC. OSS20* ELEVATOR Specific model number depends on pumping differntial and plug.

15450 SEWER EJECTORS WEILFEDERAL

or approved equal

SEWER EJECTORS

15450 AIR COMPRESSORS Ingersoll RandQuincy

Atlas CopcoGardner-Denver

Worthington

December 2006

Page 12: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING SPECIAL EQUIPMENT SYSTEMS 15460Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15460 ACID ENFIELD BY ENGINEER LABS15460 AUTOMATIC WATER CULLIGAN BY ENGINEER BY USER15460 DEIONIZER CULLIGAN BY ENGINEER BY USER15460 FILTER EQUIPMENT AMF

CUNOCULLIGAN

BY ENGINEER BY USER

15460 REVERSE OSMOSIS CULLIGANOSMONICS INC.

BY ENGINEER BY USER

15460 TYPE L COPPER DWV,DW15460 TUBULAR BRASS FIXTURES KITCHEN,

LABCP/17 GAUGE

15460 STOPS BRASSCRAFT 1/4 TURN FIXTURES KITCHEN, LAB

ALL BRASS

15460 SUPPLY TUBES FIXTURES KITCHEN, LAB

CP COPPER

15460 GAS PIPE A-53 FIXTURES KITCHEN, LAB

15460 GAS FLEX CONNECTORS

THERMO TECH. CO. FIXTURES KITCHEN, LAB

or approved equal

15460 SOLENOID VALVES ASCO FIXTURES KITCHEN, LAB

GAS AND WATER RATED; or approved equal

15460 TRAPS LABORATORY EQUIPMENT

POLYPROPYLENE IF ACID WASTE SYSTEM;

December 2006

Page 13: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING /NATURAL GAS SYSTEMS 15485Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15485 PIPING ASTM A120 SCH 40 INSIDE BUILDING 1/2" THROUGH 1 1/2"15485 PIPING ASTM A53 TYPES

GRADE B SCH 40INSIDE BUILDING 2" AND OVER

15485 FITTINGS MALLEABLE IRON INSIDE BUILDING 1/2" THROUGH 1 1/2"15485 FITTINGS BUTT WELD ASTMA234 INSIDE BUILDING 2" AND OVER15485 FLANGES 150# RF BW WN ANSI

B16.5 AND ASTM A105INSIDE BUILDING 2" AND OVER

15485 GAS SOLENOID ASCO INSIDE BUILDING LISTED; 15485 GAS VALVE CABINETS CROKER PER ENGINEER INSIDE BUILDING 15485 FLEX CONNECTORS THERMO TECH.

PRODUCTSor approved equal

Corrugated type 304 stainless steel flexible pipe with stainless steel braid and heavy flexible armor shield.

15485 PIPE DOPE RECTORSEAL TPLUS 2 ALL THREADED FITTINGS; sole source

15485 Quick Coupler Hanson Manufacturing Co

Gas Mate One way quick coupler with gas rating in cubic feet per hour equal to equivalent gas appliance rating.

December 2006

Page 14: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

PLUMBING HYDRONIC PIPING AND SPECIALTIES 15511Specification

Section # ItemAcceptable

Manufacturers Model # Usage Notes15511 Air Separators Spirovent

AmtrolArmstrong

Bell and GossettTaco

15511 Compression Tanks Diaphragm Tanks AmtrolExtrolB & G

Tested and stamped in accordance with Section 8D of

ANSI/ASTME15511 FITTINGS MECHANICAL VICTAULIC Mechanical rooms and tunnel

onlyPer CSM Engineering

15511 Fittings-Pump Suction ArmstrongAurora

Bell and GossetPeerless

TacoWeinman

Fitting to match specified pump

15511 Flow Indicator Switches McDonnell and MillerMueller

15511 Flow Measuring and Balancing Devices

Flow DesignGriswoldNexuxNibco

Presco

FlowsetQuickset

Globe style w/isolation valve

Manual Balancing All specified balancing valves shall have test ports on one side of of the valve.

15511 Inhibited Glycol Dow Chemical Co. Propylene Glycol with inhibitors only

15511 PIPING TYPE L COPPER 2" AND UNDER INSIDE BUILDING

15511 PIPING ASTM A53 SCH 40 2 1/2" AND OVER INSIDE BUILDING

15511 PIPING ATSor approved equal

Review w/CSM Engineering DIRECT BURIAL UNDER 4" CW

15511 PIPING ATSor approved equal

HDPE DIRECT BURIAL OVER 6" CW

15511 RELIEF VALVES KUNKLEWATTS

Bronze body, teflon seat; st. stl stem and springs; automatic, direct pressure actuated, capacities ASTM certified and labeled.

Per CSM Engineering

15511 Strainers AW CashBoylstonHoffman

ITTKeckleyMueller

15511 Strainers - Basket HaywardTate Andale

OxfordEaton

Duplex quick-opening covrs, st. stl. Baskets, single-handle or hand-wheel valve operation

15511 VALVES APOLLOCONBRACO

70-14# AND 7024# SERIES ISOLATION / BRANCH LINES 2" AND UNDER

sole source

15511 VALVES APOLLOCONBRACO

78-14# SERIES DRAINS sole source

15511 VALVES KEYSTONEor approved equal

FIG. 222 EPDM 2 1/2" AND OVER GEAR OPERATOR ON ALL VALVES 6" AND ABOVE; or approved equal

15511 VALVES Combination Pump Discharge

ArmstorngBell and Gossett

15511 Water Meters OniconSeametricsFlowmetrics

Chilled Water

15511 WATERWAYS BETWEEN COPPER AND BI

15511 Ball Valves ApolloMilwaukee

Bronze body, full port made in USA), (Comply with MSSSP110

15511

Butterfly Valves

DeZurikKeystone

MilwaukeeNibco

Victaulic

Comply with MSSSP67

15511

Non-Lubricated Eccentric Plug Valves

DeZurikKeystoneMilliken

December 2006

Page 15: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

15511

Lubricated Plug Valves

NordstromPowell

Walworth

15511

Gas Cocks (AGA, CGA, UL):

CraneHammond

PeterHealy

Alternate: Milwaukee "Butterball" valvesJomar Ball values

15511

U.L., F.M. Approved or Listed Valves

DemcoGEM

GrinnellJomar

KennedyKeystoneMissionMuellerNibcoPratt

Victaulic

15511

Stop and Drain Valves

HammondPrier

UnitedBrass

15511

Bronze Pressure rated Valves

Crane Hammond Milwaukee

Nibco Powell

Stockham Comply with MSSSP8015511

Iron Body Pressurerated Valves

Crane Kennedy

Lunkenheimer Milwaukee

Mueller Powell

Stockham Walworth Comply with MSSSP70

15511 Stationary Pressure gages CrosbyDwyerTrerice

U.S. GaugeWeksler

15511 Stationary Thermometers TrericeU.S. Gauge

Weksler15511 Temperature and Pressure

Test PlugsFairfax

Peterson Equipment (Pete's Plug)

Trerice15511 Pipe Hangers, supports and

GuidesBLine

GrinnellMichiganP.H.D.Tolco

15511 Dielectric Pipe Fittings and Isolators

Perfection Corporation: Dielectric Waterway,

Flow Design Available from Keystone and Victaulic distributors

December 2006

Page 16: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

Specification Section # Item

Acceptable Manufacturers Model # Usage Notes

15521 AIR VENTS SPIRAX/ SARCO

15521 ANTI-SEIZE Jet Lube Nikal COPPER ALL FLANGE BOLTS 2000 DEG. F METAL BASED; 15521 BLANKETS/ JACKETS PER MANUFACTURE

15521 BOLTS GRADE 8 All Flanges15521 CHECK VALVES DURABLA

or approved equal MODEL SCV 750 CWP /

500 WSPTRAP ASSEMBLES 2"

AND BELOWALL; or approved equal

15521 CONDENSATE METER ORION F-3500 IF NO PUMP INSTALLED

15521 CONDENSATE PUMP SARCO New Installs only; provide 5 year warranty

15521 CYCLE COUNTERS MOUNTAIN STATES ENGENDERING

PUDURE INTERMENTS CONDENSATE PUMPS sole source; With Pumps

15521 DHW HEAT EXCHANGERS

PATTERSON KELLY RETROFIT

15521 DHW HEAT EXCHANGERS

MAXI THERM NEW INSTALL

15521 FITTINGS THREADED MALLEABLE IRON 300# STEAM AND COND.15521 FITTINGS WELDED BW A234 RATED FOR

2000 PSIGSTEAM AND COND. TO MATCH ADJOINING WALL

THICKNESS

15521 FLANGE GASKETS FLEXITALLICor approved equal

SPIRAL WOUND 304 ST ST PINK AND YELLOW

STEAM AND COND. STEEL GAUGE RING;

15521 FLANGES ASTM A181 RF BW WN STEAM AND COND. 300# ON HIGH PRESSURE15521 FLANGES ASTM A181 RF BW WN STEAM AND COND. 150# ON LOW PRESSURE15521 GAUGES WINTERS LF

or approved equal4" DRY GAUGE WITH

1/4" MPT CONNECTIONRATED FOR STEAM

WITH STAINLESS STEEL INTERNALS

WITHIN 20% OF OPERATING PRESSURE

15521 PIPE DOPE + TEFLON RECTORSEAL TPLUS2 ALL THREADED sole sourceCHECK VALVES DURABLA

or approved equalMODEL WLC CI/BR

WAFER BODY 2 1/2" AND ABOVE

CONDENSATE ALL

15521 GLOBE VALVES BONNEY FORGEDANVILVOGT

CLASS 800 FORGED STEEL A105

BI-PASS RISING STEM

15521 RADIATOR CONTROL POWERS POWERMITE STEAM PNEUMATIC FM X MU; sole source15521 STEAM SAFETY'S KUNKLE PER ENGINEER STEAM SYSTEM15521 STRAINERS KECKLEY

SARCOARMSTRONG

250# CAST IRON Y-TYPE FLANGES OVER 2

1/2"

STEAM SYSTEM THREADED FITTING FOR BLOW DOWN

15521 STRAINERS KECKLEYSARCO

ARMSTRONG

250# CAST IRON Y TYPE THREADED

UNDER 2"

STEAM SYSTEM THREADED FITTING FOR BLOW DOWN

15521 EXPANSION JOINTS ADVANCED THERMAL SYSTEMS

d l

TP2F STEAM AND CONDENSATE

FLANGED

15521 TRAPS HOFFMAN 17C / 8C RADIATOR sole source15521 TRAPS SPIRAX

SARCOIB DRIP sole source

15521 TRAPS SPIRAXSARCO

FT / FTI COILS, EXCHANGERS sole source

15521 CONDENSATE PUMPS SPIRAXSARCO

PTC WHERE CONDENSATE NEEDS

PUMPED

sole source

15521 PIPING ASTM A53 GRADE B SEAMLESS SCH 80

2" AND SMALLER

15521 PIPING ASTM A53 GRADE B SEAMLESS SCH 40

2 1/2" AND LARGER STEAM ONLY

15521 PIPING ASTM A53 GRADE B SEAMLESS SCH 80

2 1/2" AND LARGER CONDENSATE ONLY

15521 SIGHT GLASSES APOLLOor approved equal

20-204-00 CONDENSATE PUMPS

15521 SLIDE GUIDES PER MANUFACTURE

15521 STEAM REGULATORS LESLIE GPKP STEAM PRV STATION sole source

PLUMBING STEAM AND CONDENSATE PIPING SPECIALTIES 15521

December 2006

Page 17: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

15521 STEAM REGULATORS FISHER PREFERRED 92B OR 92C STEAM PRV STATION WITH PILOT OPERATOR; sole 15521 STEAM VACUUM

BREAKERSSPIRAX SARCO

15521 STEAM TRAPS SPIRAX SARCO FTI OR FT, B1H F&T FOR HX AND COILS , B1H FOR LOW

STEAM TRAPS WATSON MCDANIEL WD700s TD FOR EOM DRIPS AND FLASH TRAPS

15521 VALVES KEYSTONE K LOCK LUGGED STEAM AND COND. OVER 2 1/2" LINE SIZE

BELOW 25 PSI; sole source

15521 VALVES VANESSA QTF STEAM OVER 21/2" ABOVE 25 PSI; sole source15521 VALVES APOLLO 83-30#-64 INLINE STEAM ABOVE 25 PSI; sole source15521 VALVES APOLLO 70-14#-64 INLINE STEAM AND

CONDENSATEBELOW 25 PSI; sole source

15521 VALVES APOLLO 78-14#-64 STRAINERS ALL; sole source15521 WALL PENETRATION

SEALSLINKSEAL

or approved equalMODEL T

December 2006

Page 18: PLUMBING/STEAM DISTRIBUTION 02695/15521 · 2019-08-31 · Planter Drains Deck Drains Garage Drains Trench Drains Roof Drains Downspout Nozzles Storm Drain Exp. Joints Cleanout Fittings

Colorado School of Mines Campus Standards

Specification Section # ItemAcceptable

Manufacturers Model # Usage Notes15548 Water Treatment Chemicals Industrial Division, Ashland

Specialty Chemical Company

Chemical Feed Pumps LMIWater meters Certified LMI

BadgerSeametrics

Conductivity Meters LMI DC4500-111A or approved equivalent

WATER TREATMENT

Plumbing Standards(Rev. 10/23/2009) 15000-1


Top Related