RECLOSER SMART. LIGHT. FLEXIBLE.
ii
The need for automated reclosers has never been greater. Unfortunately many of today’s reclosers come with penalties. They weigh too much, and that makes them difficult to install. They aren’t easy to upgrade, so you have to guess about what features to include in case you need them several years from now. What’s more, if the recloser you stock doesn’t come with superior technical support, service and built-in quality, you may find it worse than no recloser at all.
The Elastimold® Recloser addresses all of these problems, and more.
The Elastimold® Recloser is 33% lighter than typical units today, so it’s easier and less expensive to install. Modular design means Smart Grid sensors can be added quickly and simply. Our recloser is compatible with SEL® Controls, the best in the business. Elastimold® customer support, technical expertise and collaborative working relationships with customers mean that you will have the information you need, exactly when you need it.
The Recloser you want, all in one package.
Elastimold® RecloserThe New Standard in Reclosers
1
Elastimold® has been the No. 1 name in underground cable accessories for nearly 60 years and is the leading brand in underground solid dielectric switchgear.
Now, as the industry implements Smart Grid technologies, our world-class designs, engineering and quality-rated production facilities, combined with the best after-sale support and training, have been applied to the next-generation recloser.
Support and Service — Best in the BusinessElastimold® is known for uncommon candor and fast, knowledgeable, user-oriented technical support. Lead times for the Elastimold® Recloser are short — typically two weeks faster than what you expect from other suppliers. From the first day you install it, no question is too small to receive our complete technical attention. If assistance is needed, our response will be swift, and often immediate.
We offer unmatched customer service to go with world-class technical support, top warranties and training in all phases of installation and operation. Your crews will know exactly what we know about the Elastimold® Recloser.
The Elastimold ® Recloser, in either single-phase or three-phase configurations, is fully compatible with SEL® Controls.
1
2
The Elastimold® Recloser is world-class, by design. It responds to every hardware requirement that utilities want, and then some.
Smart — Our recloser is Smart Grid ready with three integral load-side voltage sensors and provision to add source-side voltage sensors, if desired. It was designed to be fully compatible with the industry’s No. 1 name in controls, Schweitzer Engineering Laboratories.
Light — The three-phase Elastimold® Recloser weighs 33% less than existing typical units. The simplicity of the mechanism design, and the compactness of the encapsulated components, contribute to making the Elastimold® Recloser easier to move and install.
Flexible — The Elastimold® Recloser is modular, so field upgrades and retrofits are easy and fast. The single phase recloser has a pole rotation mounting bracket for easier installation.
Made with Your Needs in Mind — We designed the Elastimold® Recloser only after extensive talks with electric utilities. Its characteristics, from easier-to-see open/close indicators to the many robust extra features that we consider “standard,” are there because of you.
Integrated Pole Mounting Bracket
Solid Dielectric Insulation
Current & Voltage Sensors
Manual Tripping Lever
Lifting Rings
Highly Visible 360° Indicators
Elastimold® Recloser — MVRSmart, Light, and Flexible
3
Top Silicone Sheds
Vacuum Bottle
Main Body EPDM Insulation
Solid Dielectric Diaphragm
Pull Rod Assembly / Load Side Voltage Sensor
Bottom Silicone Sheds
Magnetic Actuator
Position Indicator
Current Transformer
Side Silicone Terminal
Upper Cover
Lower Cover
Recloser Operation
The Elastimold® Molded Vacuum Recloser (MVR) operates electrically by energizing a magnetic actuator system with a completely sealed housing. Each pole contains a vacuum interrupter sealed in solid dielectric insulation for mechanical and high dielectric strength.
An open-closed position indicator provides a 360-degree view. An external manual trip assembly is located on the side; when in the down position, it maintains the recloser in a lockout position until it is manually restored. All electrical control connections are made through a sealed single-environment control cable connector on the side.
The combination of the molded vacuum recloser with microprocessor controls accurately detects a wide range of line disturbances and provides reliable, high-speed isolation for adverse conditions.
4
Single Phase
SEL-351RS Kestrel®
10/14-Pin Cable
Three Phase
SEL-351R
14-Pin Cable
Three Phase
SEL-351R FalconTM
14-Pin Cable
Three Phase
SEL-651R x 2
32-Pin Cable
Current Sensor
Pull Rod Assembly/ Load-Side Voltage Sensor
4
Smart Grid Ready
Integral CT (1000:1/500:1 flexibility) and load-side voltage sensors; with provisions to add Elastimold® source-side voltage sensors
Elastimold® Recloser — MVRFeatures and Benefits
Compatible with SEL® recloser controls• SEL-351R
• SEL-351RS Kestrel®
• SEL-351R FalconTM
• SEL-651R
Notes:
Use with the SEL-351R & SEL-351R FalconTM requires connection via MVR power module. The power module is connected to the recloser via a 6 ft., 32-pin cable.
Voltage sensors require SEL-651R x 2 control with six 8VAC LEA inputs.
Typical control settingsA range of controls are available for the Elastimold® Recloser. A typical control includes:
• Overcurrent protection — fast and delay curves
• Sensitive earth fault
• Complete metering
• Recloser wear monitor
• Loop automation
• Fault locator
• Flexible control logic and integration
• Supervisory control and data acquisition ready — multiple communications protocols
• Load profile
SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.
SMAR
T
5
Side Terminal
Top Shed
Bottom Shed
EPDM Rubber
Silicone Rubber Silicone Rubber
Silicone Rubber
Mounting Bracket
180° Repositioning
Lightweight
Internal diaphragm and silicone rubber sheds reduce weight.
Proven solid dielectric insulation
Molded EPDM main body with overlapping silicone rubber sheds for improved dielectric weatherability and UV performance.
Modular design
Optimized modular design is lightweight and maintenance free. Design is modular and allows for individual pole or shed replacement if ever required.
Pole rotation mount
The single-phase recloser has a unique pole rotation mounting bracket for easier installation and repositioning from 0 to 180 degrees.
Simplified mechanism
Translates into a lightweight device.
LIGH
TFL
EXIB
LE
15 kV 27 kV 38 kV
WEIGHTOTHERS
STANDARDELASTIMOLD®
STANDARDOTHERS
STANDARDELASTIMOLD®
STANDARDOTHERS
STANDARDELASTIMOLD®
STANDARD
Single Phase100 lb 45 kg
57 lb 25.8 kg
100 lb 45 kg
57 lb 25.8 kg
130 lb 60 kg
58 lb 26.3 kg
Three Phase333 lb 150 kg
208 lb 94.3 kg
333 lb 150 kg
208 lb 94.3 kg
430 lb 195 kg
211 lb 95.7 kg
6
Closed Indication Open Indication
15 kV 27 kV 38 kV
POLLUTION LEVELREQUIRED
CREEPELASTIMOLD®
STANDARDREQUIRED
CREEP ELASTIMOLD®
STANDARDREQUIRED
CREEP ELASTIMOLD®
STANDARD
I – Light9.8"
(248 mm)N/A
17.0" (432 mm)
N/A23.9"
(608 mm)N/A
II – Medium12.2"
(310 mm)N/A
21.3" (540 mm)
N/A30.0"
(760 mm)N/A
III – Heavy15.3"
(388 mm)N/A
26.6" (675 mm)
N/A37.4"
(950 mm)N/A
IV – Very Heavy18.9"
(481 mm)41.5"
(1054 mm)33.0"
(837 mm)41.5"
(1054 mm)46.4"
(1178 mm)51.0"
(1295 mm)
Magnetic Actuator
Close Phase Position Trip Phase Position
6
Trip Handle Normal, Closed Position Open & Locked-Out Position
INNO
VATI
VEElastimold® Recloser — MVRFeatures and Benefits
Reduced inventory items
Incorporating extra features and extended capabilities as standard can lead to less stock on your floor.
Single- and three-phase tripping capabilities
The fast and highly reliable electrically-ganged operation provides flexibility of simultaneous three-phase tripping or single-phase tripping with three-phase lockout.
The manual trip lever is mechanically linked to trip and lock out all three phases simultaneously.
Reliable long-life mechanism
The state-of-the-art design of our magnetic actuator offers over 10,000 trip and close full-load operations with no maintenance required.
Easy-to-see position indicator
360-degree position indicator view with large color-coded reflective open/closed indicators on bottom of recloser for easy visibility from ground level.
15 kV 27 kV 38 kVRATED MAX VOLTAGE
OTHERS STANDARD
ELASTIMOLD® STANDARD
OTHERS STANDARD
ELASTIMOLD® STANDARD
OTHERS STANDARD
ELASTIMOLD® STANDARD
Continuous Current 630 A 800 A 630 A 800 A 630 A 800 A
BIL 95 kV 150 kV 125 kV 150 kV 150 kV 170 kV
7
Typical Recloser Installation Detail
Arresters are recommended to provide protection against overvoltage conditions. When arresters are installed, they should be mounted on the supplied arrester brackets or as close to the recloser as practical.
Optional: 500:1 jumper cable dual ratio CTs will only be used if needing 500:1 CT ratio.
Line
Recloser
351R and 351R Falcon only; Cable Plugs Directly into Recloser on 351RS Kestrel and 651R
Utility Pole
Arresters
Recloser Control
GROU
NDCO
NTRO
L
SUPP
LY
Protective Shield around Pole Ground
Control Cable
System Neutral
PT
Pole Ground
POWER MODULE
GROUNDNEUTRAL
LINE
8
15 kV & 27 kV Single-Phase Reclosers
38 kV Single-Phase Recloser
Elastimold® Recloser — MVRDimensions — Single-Phase Reclosers
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
6.00[152,4]
1.37[34,9]
24.08[611,6]
3188D0396B
1293, EMS-26
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 1-PH, 15-27KV
1/4 D 1 of 2 3188D0396REV ECN- DESCRIPTION BY CHK. DATEA - CREATED FROM 3188C0110 RC - 09/05/14B - ADD VOLT/CURR TAGS RC JP 02/04/15
X
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT= 57 LBS. [25.8 KG.]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE: LINE TO GROUND = 41.50" [1054] LOAD TO LINE = 52.00" [1321]7) INTERRUPTER RATING = 12.5 KA8) BIL: LINE TO GND = 150KV LINE TO LINE = 150KV
OPEN/CLOSED INDICATOR
FRONT VIEW
REAR VIEW
3D VIEW
MANUAL TRIP HANDLE(SEE NOTE 4)
OPEN/CLOSED INDICATOR(SEE VIEW)
3/8-16 BOLTFOR SECURINGRECLOSER TOFRAME
NAMEPLATE
RECLOSER
MOUNTING HOLES FORUSER SUPPLIED5/8 [16] DIA. LAGOR THRU BOLT
OPEN - GREENBLACK BLACK
CLOSED - RED
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
6.00[152,4]
1.37[34,9]
24.08[611,6]
3188D0398B
1293, EMS-26
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 1-PH, 38KV
1/4 D 1 of 2 3188D0398REV ECN- DESCRIPTION BY CHK. DATEA - CREATED FROM 3188C0111 RC - 09/05/14B - ADD VOLT/CURR TAGS RC JP 02/04/15
X
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT= 58 LBS. [26.3 KG.]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE: LINE TO GROUND = 51.00" [1295] LOAD TO LINE = 60.00" [1524]7) INTERRUPTER RATING = 12.5 KA8) BIL: LINE TO GND = 170KV LINE TO LINE = 170KV
OPEN/CLOSED INDICATOR
FRONT VIEW
REAR VIEW
3D VIEW
MANUAL TRIP HANDLE(SEE NOTE 4)
OPEN/CLOSED INDICATOR(SEE VIEW)
3/8-16 BOLTFOR SECURINGRECLOSER TOFRAME
NAMEPLATE
RECLOSER
MOUNTING HOLES FORUSER SUPPLIED5/8 [16] DIA. LAGOR THRU BOLT
OPEN - GREEN BLACK BLACK CLOSED - RED
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
6.00[152,4]
1.37[34,9]
24.08[611,6]
3188D0396B
1293, EMS-26
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 1-PH, 15-27KV
1/4 D 1 of 2 3188D0396REV ECN- DESCRIPTION BY CHK. DATEA - CREATED FROM 3188C0110 RC - 09/05/14B - ADD VOLT/CURR TAGS RC JP 02/04/15
X
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT= 57 LBS. [25.8 KG.]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE: LINE TO GROUND = 41.50" [1054] LOAD TO LINE = 52.00" [1321]7) INTERRUPTER RATING = 12.5 KA8) BIL: LINE TO GND = 150KV LINE TO LINE = 150KV
OPEN/CLOSED INDICATOR
FRONT VIEW
REAR VIEW
3D VIEW
MANUAL TRIP HANDLE(SEE NOTE 4)
OPEN/CLOSED INDICATOR(SEE VIEW)
3/8-16 BOLTFOR SECURINGRECLOSER TOFRAME
NAMEPLATE
RECLOSER
MOUNTING HOLES FORUSER SUPPLIED5/8 [16] DIA. LAGOR THRU BOLT
OPEN - GREENBLACK BLACK
CLOSED - RED
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
6.00[152,4]
1.37[34,9]
24.08[611,6]
3188D0398B
1293, EMS-26
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 1-PH, 38KV
1/4 D 1 of 2 3188D0398REV ECN- DESCRIPTION BY CHK. DATEA - CREATED FROM 3188C0111 RC - 09/05/14B - ADD VOLT/CURR TAGS RC JP 02/04/15
X
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT= 58 LBS. [26.3 KG.]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE: LINE TO GROUND = 51.00" [1295] LOAD TO LINE = 60.00" [1524]7) INTERRUPTER RATING = 12.5 KA8) BIL: LINE TO GND = 170KV LINE TO LINE = 170KV
OPEN/CLOSED INDICATOR
FRONT VIEW
REAR VIEW
3D VIEW
MANUAL TRIP HANDLE(SEE NOTE 4)
OPEN/CLOSED INDICATOR(SEE VIEW)
3/8-16 BOLTFOR SECURINGRECLOSER TOFRAME
NAMEPLATE
RECLOSER
MOUNTING HOLES FORUSER SUPPLIED5/8 [16] DIA. LAGOR THRU BOLT
OPEN - GREEN BLACK BLACK CLOSED - RED
35.05[890,1]
35.05[890,1]
37.92[963,1]
36.15[918,2]
19.60[497,9]
19.60[497,8]
19.72[501]
19.72[501]
8.63[219,3]
8.63[219,3]
10.07[255,7]
10.07[255,7]
3.36[85,3]
3.36[85,3]
1.75[44,5]
1.75[44,5]
9
15 kV & 27 kV Three-Phase Reclosers
38 kV Three-Phase Recloser
Elastimold® Recloser — MVRDimensions — Three-Phase Reclosers
THIS
INFO
RM
ATIO
N IS
TRA
NS
MITTE
D S
UB
JEC
T TO TH
E FO
LLOW
ING
UN
DE
RS
TAN
DIN
G A
ND
AG
RE
EM
EN
T BY
AC
CE
PTA
NC
E O
F THIS
DO
CU
ME
NT Y
OU
AG
RE
E TH
AT A
LL RIG
HTS
TO TH
E D
RA
WIN
GS
AN
D IN
FOR
MA
TION
CO
NTA
INE
HE
RE
ON
, AS
WE
LL AS
TO TH
E S
UB
JEC
T MA
TTER
HE
RE
OF A
ND
ALL P
RO
PR
IETA
RY
AN
D N
OV
EL FE
ATU
RE
S D
ISC
LOS
ED
HE
RE
IN, A
RE
RE
SE
RV
ED
BY
THO
MA
S A
ND
BE
TTS A
ND
THA
T DE
VIC
ES
EM
BO
DY
ING
SU
CH
FEA
TUR
ES
OR
INFO
RM
ATIO
N D
ER
IVE
D FR
OM
THE
SE
DR
AW
ING
S W
ILL NO
T BE
MA
NU
FAC
TUR
ED
BY
OR
FOR
YO
U O
R D
ISC
LOS
ED
TO O
THE
RS
WITH
OU
T THE
PR
IOR
EX
PR
ES
S W
RITTE
NC
ON
SE
NT O
F THO
MA
S A
ND
BE
TTS. TH
ES
E D
RA
WIN
GS
AN
D TH
E IN
FOR
MA
TION
CO
NTA
INE
D TH
ER
EIN
AR
E A
ND
RE
MA
IN TH
E P
RO
PE
RTY
OF TH
OM
AS
AN
D B
ETTS
AN
D A
RE
NO
T TO B
E C
OP
IED
OR
RE
PR
OD
UC
ED
OR
DIS
CLO
SE
D TO
OTH
ER
S W
ITHO
UT TH
E P
RIO
R W
RITTE
N C
ON
SE
NT O
F THO
MA
S A
ND
BE
TTS A
LL DR
AW
ING
S A
ND
INFO
RM
ATIO
N TO
BE
RE
TUR
NE
D TO
THO
MA
S A
ND
BE
TTS U
PO
N D
EM
AN
D O
R U
PO
N C
OM
PLE
TION
OF P
UR
PO
SE
FOR
WH
ICH
LEN
T.
THO
MA
S &
BE
TTS, P
RO
PR
IETA
RY
RIG
HTS
DR
AW
ING
NU
MB
ER
RE
V
C
AP
PR
OV
ED
CH
EC
KE
D
DR
AW
ND
ATE
DA
TE
DA
TE
TORQUE BOLTS & NUTS TO EMS-26
UNLESS OTHERWISE SPECIFIED.
MA
TER
IAL
DR
AW
ING
TITLE
SC
ALE
DR
AW
ING
NU
MB
ER
SH
T. SIZE
SH
T. No.
NE
XT A
SS
'Y
EN
GIN
EE
RIN
G S
PE
C.
QU
ALITY
STD
.M
ATE
RIA
L STD
.
ALL DIMENSIO
NS ON THIS DW
G ARE IN UNITS AS CHECKED BELO
W
ENGLISH
METRIC
DUAL
THIRD ANGLE PRO
JECTION
Thomas & Betts
8155 TB B
OU
LEV
AR
DM
EM
PH
IS, TN
38125P
HO
NE
: (800) 888-0211, FAX
: (800) 888-0690
A M
EMBER O
F THE A
BB GRO
UP
INC
Hm
mIN
CH
mm
15.01[381,3]
1.50[38,1]
31
88
D0
39
7C
RE
VE
CN
-D
ES
CR
IPTIO
NB
YC
HK
.DA
TEA
- C
RE
ATE
D FR
OM
3188C0112
RC
JP
09/05/14
B-
UP
DA
TED
PE
R FIR
ST R
EV
IEW
RC
-10/23/14
C-
AD
D V
OLTA
GE
/CU
RR
TAG
SR
CJP
02/06/15
XR.C
AR
TELLI
09/05/14
OU
TLINE, RECLO
SER 3-PH, 15-27KV
(MVR3)
0.063D
1 of 5 3188D
0397
OP
EN
/CLO
SE
D IN
DIC
ATO
R
NO
TES
:1) D
IME
NS
ION
S IN
BR
AC
KE
TS [X
XX
] AR
E M
ILLIME
TER
S.
2) MA
XIM
UM
CA
NTILE
VE
RE
D TE
RM
INA
L PA
D LO
AD
OF 60 LB
S.
[27 KG
.] PE
R P
AD
ALLO
WA
BLE
. HO
RIZO
NTA
L CA
BLE
TEN
SIO
NS
PE
R P
HA
SE
TO B
E O
PP
OS
ITE IN
DIR
EC
TION
.3) W
EIG
HT= 208 LB
S. [94.4 K
G.]
4) STA
ND
AR
D P
OS
ITION
AS
SH
OW
N.
TRIP
PO
SITIO
N S
HO
WN
DO
TTED
.5) C
ON
NE
CTIO
N O
F THE
RE
CLO
SE
R TO
THE
DE
SIG
NA
TED
LINE
AN
D LO
AD
SID
E TE
RM
INA
LS IS
ON
LY R
EQ
UIR
ED
IF THE
RE
CLO
SE
R IS
BE
ING
US
ED
WITH
A C
ON
TRO
L C
ON
TAIN
ING
DIR
EC
TION
AL O
VE
R C
UR
RE
NT C
AP
AB
ILITY.
6) CR
EE
PA
GE
DIS
TAN
CE
: LIN
E TO
GR
OU
ND
= 41.50" [1054] LO
AD
TO G
RO
UN
D = 43.60" [1107]
LINE
TO LO
AD
= 52.17" [1320]7) IN
TER
RU
PTE
R R
ATIN
G = 12.5 K
A8) B
IL: LINE
TO G
ND
= 150KV
LINE
TO LIN
E = 150K
V
RE
AR
VIE
W
3D FR
ON
T VIE
W
CLE
AR
AN
CE
SLO
TS FO
RU
SE
R S
UP
PLIE
D3/4 [19] D
IA. LA
G O
RTH
RU
BO
LTS
GR
OU
ND
TER
MIN
AL
RE
CLO
SE
R(TY
P.)
CLO
SE
D - R
ED
BLA
CK
OP
EN
- GR
EE
NB
LAC
K
THIS
INFO
RM
ATIO
N IS
TRA
NS
MITTE
D S
UB
JEC
T TO TH
E FO
LLOW
ING
UN
DE
RS
TAN
DIN
G A
ND
AG
RE
EM
EN
T BY
AC
CE
PTA
NC
E O
F THIS
DO
CU
ME
NT Y
OU
AG
RE
E TH
AT A
LL RIG
HTS
TO TH
E D
RA
WIN
GS
AN
D IN
FOR
MA
TION
CO
NTA
INE
HE
RE
ON
, AS
WE
LL AS
TO TH
E S
UB
JEC
T MA
TTER
HE
RE
OF A
ND
ALL P
RO
PR
IETA
RY
AN
D N
OV
EL FE
ATU
RE
S D
ISC
LOS
ED
HE
RE
IN, A
RE
RE
SE
RV
ED
BY
THO
MA
S A
ND
BE
TTS A
ND
THA
T DE
VIC
ES
EM
BO
DY
ING
SU
CH
FEA
TUR
ES
OR
INFO
RM
ATIO
N D
ER
IVE
D FR
OM
THE
SE
DR
AW
ING
S W
ILL NO
T BE
MA
NU
FAC
TUR
ED
BY
OR
FOR
YO
U O
R D
ISC
LOS
ED
TO O
THE
RS
WITH
OU
T THE
PR
IOR
EX
PR
ES
S W
RITTE
NC
ON
SE
NT O
F THO
MA
S A
ND
BE
TTS. TH
ES
E D
RA
WIN
GS
AN
D TH
E IN
FOR
MA
TION
CO
NTA
INE
D TH
ER
EIN
AR
E A
ND
RE
MA
IN TH
E P
RO
PE
RTY
OF TH
OM
AS
AN
D B
ETTS
AN
D A
RE
NO
T TO B
E C
OP
IED
OR
RE
PR
OD
UC
ED
OR
DIS
CLO
SE
D TO
OTH
ER
S W
ITHO
UT TH
E P
RIO
R W
RITTE
N C
ON
SE
NT O
F THO
MA
S A
ND
BE
TTS A
LL DR
AW
ING
S A
ND
INFO
RM
ATIO
N TO
BE
RE
TUR
NE
D TO
THO
MA
S A
ND
BE
TTS U
PO
N D
EM
AN
D O
R U
PO
N C
OM
PLE
TION
OF P
UR
PO
SE
FOR
WH
ICH
LEN
T.
THO
MA
S &
BE
TTS, P
RO
PR
IETA
RY
RIG
HTS
DR
AW
ING
NU
MB
ER
RE
V
C
AP
PR
OV
ED
CH
EC
KE
D
DR
AW
ND
ATE
DA
TE
DA
TE
TORQUE BOLTS & NUTS TO EMS-26
UNLESS OTHERWISE SPECIFIED.
MA
TER
IAL
DR
AW
ING
TITLE
SC
ALE
DR
AW
ING
NU
MB
ER
SH
T. SIZE
SH
T. No.
NE
XT A
SS
'Y
EN
GIN
EE
RIN
G S
PE
C.
QU
ALITY
STD
.M
ATE
RIA
L STD
.
ALL DIMENSIO
NS ON THIS DW
G ARE IN UNITS AS CHECKED BELO
W
ENGLISH
METRIC
DUAL
THIRD ANGLE PRO
JECTION
Thomas & Betts
8155 TB B
OU
LEV
AR
DM
EM
PH
IS, TN
38125P
HO
NE
: (800) 888-0211, FAX
: (800) 888-0690
A M
EMBER O
F THE A
BB GRO
UP
INC
Hm
mIN
CH
mm
15.01[381,3]
1.50[38,1]
31
88
D0
39
9C
RE
VE
CN
-D
ES
CR
IPTIO
NB
YC
HK
.DA
TEA
- C
RE
ATE
D FR
OM
3188C0113
RC
JP
09/05/14
B-
UP
DA
TE P
ER
FIRS
T RE
VIE
WR
C-
10/23/14
C-
AD
D V
OLTA
GE
/CU
RR
TAG
SR
CJP
02/06/15
XR.C
AR
TELLI
09/05/14
OU
TLINE, RECLO
SER 3-PH, 38KV
(MVR3)
0.063D
1 of 5 3188D
0399
OP
EN
/CLO
SE
D IN
DIC
ATO
R
NO
TES
:1) D
IME
NS
ION
S IN
BR
AC
KE
TS [X
XX
] AR
E M
ILLIME
TER
S.
2) MA
XIM
UM
CA
NTILE
VE
RE
D TE
RM
INA
L PA
D LO
AD
OF 60 LB
S.
[27 KG
.] PE
R P
AD
ALLO
WA
BLE
. HO
RIZO
NTA
L CA
BLE
TEN
SIO
NS
PE
R P
HA
SE
TO B
E O
PP
OS
ITE IN
DIR
EC
TION
.3) W
EIG
HT= 211 LB
S. [95.7 K
G.]
4) STA
ND
AR
D P
OS
ITION
AS
SH
OW
N.
TRIP
PO
SITIO
N S
HO
WN
DO
TTED
.5) C
ON
NE
CTIO
N O
F THE
RE
CLO
SE
R TO
THE
DE
SIG
NA
TED
LINE
AN
D LO
AD
SID
E TE
RM
INA
LS IS
ON
LY R
EQ
UIR
ED
IF THE
RE
CLO
SE
R IS
BE
ING
US
ED
WITH
A C
ON
TRO
L C
ON
TAIN
ING
DIR
EC
TION
AL O
VE
R C
UR
RE
NT C
AP
AB
ILITY.
6) CR
EE
PA
GE
DIS
TAN
CE
: LIN
E TO
GR
OU
ND
= 51.00" [1295] LO
AD
TO G
RO
UN
D = 52.00" [1320]
LINE
TO LO
AD
= 60.56" [1538]7) IN
TER
RU
PTE
R R
ATIN
G = 12.5 K
A8) B
IL: LINE
TO G
ND
= 170KV
LINE
TO LIN
E = 170K
V
RE
AR
VIE
W
3D FR
ON
T VIE
W
CLE
AR
AN
CE
SLO
TS FO
RU
SE
R S
UP
PLIE
D3/4 [19] D
IA. LA
G O
RTH
RU
BO
LTS
RE
CLO
SE
R(TY
P)
GR
OU
ND
TER
MIN
AL
CLO
SE
D - R
ED
BLA
CK
OP
EN
- GR
EE
NB
LAC
K
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
15.01[381,3]
1.50[38,1]
3188D0397C
REV ECN- DESCRIPTION BY CHK. DATEA - CREATED FROM 3188C0112 RC JP 09/05/14
B - UPDATED PER FIRST REVIEW RC - 10/23/14
C - ADD VOLTAGE/CURR TAGS RC JP 02/06/15
X
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 3-PH, 15-27KV(MVR3)
0.063 D 1 of 5 3188D0397
OPEN/CLOSED INDICATOR
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT= 208 LBS. [94.4 KG.]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.
6) CREEPAGE DISTANCE: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320]7) INTERRUPTER RATING = 12.5 KA8) BIL: LINE TO GND = 150KV LINE TO LINE = 150KV
REAR VIEW
3D FRONT VIEW
CLEARANCE SLOTS FORUSER SUPPLIED3/4 [19] DIA. LAG ORTHRU BOLTS
GROUND TERMINAL
RECLOSER(TYP.)
CLOSED - RED BLACK
OPEN - GREEN BLACK
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
15.01[381,3]
1.50[38,1]
3188D0399C
REV ECN- DESCRIPTION BY CHK. DATEA - CREATED FROM 3188C0113 RC JP 09/05/14
B - UPDATE PER FIRST REVIEW RC - 10/23/14
C - ADD VOLTAGE/CURR TAGS RC JP 02/06/15
X
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 3-PH, 38KV(MVR3)
0.063 D 1 of 5 3188D0399
OPEN/CLOSED INDICATOR
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT= 211 LBS. [95.7 KG.]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.
6) CREEPAGE DISTANCE: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING = 12.5 KA8) BIL: LINE TO GND = 170KV LINE TO LINE = 170KV
REAR VIEW
3D FRONT VIEW
CLEARANCE SLOTS FORUSER SUPPLIED3/4 [19] DIA. LAG ORTHRU BOLTS
RECLOSER(TYP)
GROUND TERMINAL
CLOSED - RED BLACK
OPEN - GREEN BLACK
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
15.01[381,3]
1.50[38,1]
3188D0397C
REV ECN- DESCRIPTION BY CHK. DATEA - CREATED FROM 3188C0112 RC JP 09/05/14
B - UPDATED PER FIRST REVIEW RC - 10/23/14
C - ADD VOLTAGE/CURR TAGS RC JP 02/06/15
X
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 3-PH, 15-27KV(MVR3)
0.063 D 1 of 5 3188D0397
OPEN/CLOSED INDICATOR
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT= 208 LBS. [94.4 KG.]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.
6) CREEPAGE DISTANCE: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320]7) INTERRUPTER RATING = 12.5 KA8) BIL: LINE TO GND = 150KV LINE TO LINE = 150KV
REAR VIEW
3D FRONT VIEW
CLEARANCE SLOTS FORUSER SUPPLIED3/4 [19] DIA. LAG ORTHRU BOLTS
GROUND TERMINAL
RECLOSER(TYP.)
CLOSED - RED BLACK
OPEN - GREEN BLACK
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
15.01[381,3]
1.50[38,1]
3188D0399C
REV ECN- DESCRIPTION BY CHK. DATEA - CREATED FROM 3188C0113 RC JP 09/05/14
B - UPDATE PER FIRST REVIEW RC - 10/23/14
C - ADD VOLTAGE/CURR TAGS RC JP 02/06/15
X
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 3-PH, 38KV(MVR3)
0.063 D 1 of 5 3188D0399
OPEN/CLOSED INDICATOR
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT= 211 LBS. [95.7 KG.]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.
6) CREEPAGE DISTANCE: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING = 12.5 KA8) BIL: LINE TO GND = 170KV LINE TO LINE = 170KV
REAR VIEW
3D FRONT VIEW
CLEARANCE SLOTS FORUSER SUPPLIED3/4 [19] DIA. LAG ORTHRU BOLTS
RECLOSER(TYP)
GROUND TERMINAL
CLOSED - RED BLACK
OPEN - GREEN BLACK
15.50[393,7]
15.50[393,7]
24.20[614,8]
24.20[614,8]
42.56[1081]
42.56[1081]
1 6.40[416,6]
18.23[463,1]
33.72[856,6]
35.55[903]
12.95[328,9]
12.95[328,9]
19.60[497,9]
19.60[497,9]
8.81[223,7]
8.81[223,7]
1.75[44,5]
1.75[44,5]
1.75[44,5]
1.75[44,5]
35.08[891,1]
35.08[891,1]
15.50[393,7]
15.50[393,7]
10
15 kV, 27 kV, & 38 kV Triple Single Cluster Mounting Frame
Typical Pole InstallationsDimensions — Triple Single Cluster Mounting Frame
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
36.50[927,1]
1.50[38,1]
19.60[497,9]
8.63[219,3]
1.75[44,5]
1.75[44,5]
35.04[890,1]
15/27KV=36.15[918,1]
38KV=37.92 [963,1]
3188D0402C
REV ECN- DESCRIPTION BY CHK. DATEA - INITIAL RELEASE RC JP 10/22/14B - UPDATE NOTES AND TITLE RC JP 10/31/14
C - ADD VOLT/CURR TAGS RC JP 02/04/15
X
-
R.CARTELLI 10/21/14
OUTLINE, 3 MVR1'S, 15/27KV & 38KVCLUSTER MOUNTING FRAME
- 0.053 D 1 of 4 3188D0402
NOTES:1) ALL DIMENSIONS ARE FOR 15/27KV UNITS UNLESS NOTED OTHERWISE. DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT: RECLOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] FRAME: 62 LBS. [28.1 KG]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE 15-27KV: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] CREEPAGE DISTANCE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV
REAR VIEW
RIGHT SIDE VIEW
RECLOSER
LINE SIDE(SEE NOTE 5)
LOAD SIDE(SEE NOTE 5)
GROUND TERMINAL(TYP. FOR 4)
TORQUE TERMINALLUGS TO 25 FT/LBS
CLEARANCE SLOTS FORUSER SUPPLIED5/8 [16] DIA. LAG OR THRU BOLTS
POLE MOUNTING FRAMEVOLTAGE TAGS
15kV = BLACK LETTERING ON SILVER BACKROUND25kV = SILVER LETTERING ON BLUE BACKROUND
35kV = BLACK LETTERING ON YELLOW BACKROUNDSCALE 0.250
DETAIL A
OPEN - GREEN BLACK CLOSED - REDBLACK
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
36.50[927,1]
1.50[38,1]
19.60[497,9]
8.63[219,3]
1.75[44,5]
1.75[44,5]
35.04[890,1]
15/27KV=36.15[918,1]
38KV=37.92 [963,1]
3188D0402C
REV ECN- DESCRIPTION BY CHK. DATEA - INITIAL RELEASE RC JP 10/22/14B - UPDATE NOTES AND TITLE RC JP 10/31/14
C - ADD VOLT/CURR TAGS RC JP 02/04/15
X
-
R.CARTELLI 10/21/14
OUTLINE, 3 MVR1'S, 15/27KV & 38KVCLUSTER MOUNTING FRAME
- 0.053 D 1 of 4 3188D0402
NOTES:1) ALL DIMENSIONS ARE FOR 15/27KV UNITS UNLESS NOTED OTHERWISE. DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT: RECLOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] FRAME: 62 LBS. [28.1 KG]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE 15-27KV: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] CREEPAGE DISTANCE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV
REAR VIEW
RIGHT SIDE VIEW
RECLOSER
LINE SIDE(SEE NOTE 5)
LOAD SIDE(SEE NOTE 5)
GROUND TERMINAL(TYP. FOR 4)
TORQUE TERMINALLUGS TO 25 FT/LBS
CLEARANCE SLOTS FORUSER SUPPLIED5/8 [16] DIA. LAG OR THRU BOLTS
POLE MOUNTING FRAMEVOLTAGE TAGS
15kV = BLACK LETTERING ON SILVER BACKROUND25kV = SILVER LETTERING ON BLUE BACKROUND
35kV = BLACK LETTERING ON YELLOW BACKROUNDSCALE 0.250
DETAIL A
OPEN - GREEN BLACK CLOSED - REDBLACK
48.06[1220,8]
48.06[1220,8]
74.94[1903,6]
30.13[765,2]
24.58[624,3]
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
36.50[927,1]
1.50[38,1]
19.60[497,9]
8.63[219,3]
1.75[44,5]
1.75[44,5]
35.04[890,1]
15/27KV=36.15[918,1]
38KV=37.92 [963,1]
3188D0402C
REV ECN- DESCRIPTION BY CHK. DATEA - INITIAL RELEASE RC JP 10/22/14B - UPDATE NOTES AND TITLE RC JP 10/31/14
C - ADD VOLT/CURR TAGS RC JP 02/04/15
X
-
R.CARTELLI 10/21/14
OUTLINE, 3 MVR1'S, 15/27KV & 38KVCLUSTER MOUNTING FRAME
- 0.053 D 1 of 4 3188D0402
NOTES:1) ALL DIMENSIONS ARE FOR 15/27KV UNITS UNLESS NOTED OTHERWISE. DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT: RECLOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] FRAME: 62 LBS. [28.1 KG]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE 15-27KV: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] CREEPAGE DISTANCE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV
REAR VIEW
RIGHT SIDE VIEW
RECLOSER
LINE SIDE(SEE NOTE 5)
LOAD SIDE(SEE NOTE 5)
GROUND TERMINAL(TYP. FOR 4)
TORQUE TERMINALLUGS TO 25 FT/LBS
CLEARANCE SLOTS FORUSER SUPPLIED5/8 [16] DIA. LAG OR THRU BOLTS
POLE MOUNTING FRAMEVOLTAGE TAGS
15kV = BLACK LETTERING ON SILVER BACKROUND25kV = SILVER LETTERING ON BLUE BACKROUND
35kV = BLACK LETTERING ON YELLOW BACKROUNDSCALE 0.250
DETAIL A
OPEN - GREEN BLACK CLOSED - REDBLACK
58.94[1497]
37.47[951,8]
23.99[609,3]
37.47[951,8]
11
15 kV, 27 kV, & 38 kV Triple Single Pole Mounting Frame
Typical Pole InstallationsDimensions — Triple Single Pole Mounting Frame
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
3188D0404A
REV ECN- DESCRIPTION BY CHK. DATEA - CREATED RC XX 02/03/15
X
-
R.CARTELLI 02/03/15
OUTLINE THREE 1PH RECLOSERSTANDARD POLE MOUTING FRAME, 15,27 AND 38kV
- 0.059 D 1 of 4 3188D0404
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT: RECLOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] FRAME = 62 LBS. [28.1 KG]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE 15-27KV: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] CREEPAGE DISTANCE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV
OPEN/CLOSED INDICATOR
3D REAR VIEW
CLOSED - RED BLACKOPEN - GREEN BLACK
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
3188D0404A
REV ECN- DESCRIPTION BY CHK. DATEA - CREATED RC XX 02/03/15
X
-
R.CARTELLI 02/03/15
OUTLINE THREE 1PH RECLOSERSTANDARD POLE MOUTING FRAME, 15,27 AND 38kV
- 0.059 D 1 of 4 3188D0404
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT: RECLOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] FRAME = 62 LBS. [28.1 KG]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE 15-27KV: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] CREEPAGE DISTANCE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV
OPEN/CLOSED INDICATOR
3D REAR VIEW
CLOSED - RED BLACKOPEN - GREEN BLACK
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
3188D0404A
REV ECN- DESCRIPTION BY CHK. DATEA - CREATED RC XX 02/03/15
X
-
R.CARTELLI 02/03/15
OUTLINE THREE 1PH RECLOSERSTANDARD POLE MOUTING FRAME, 15,27 AND 38kV
- 0.059 D 1 of 4 3188D0404
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT: RECLOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] FRAME = 62 LBS. [28.1 KG]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE 15-27KV: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] CREEPAGE DISTANCE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV
OPEN/CLOSED INDICATOR
3D REAR VIEW
CLOSED - RED BLACKOPEN - GREEN BLACK
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
3188D0404A
REV ECN- DESCRIPTION BY CHK. DATEA - CREATED RC XX 02/03/15
X
-
R.CARTELLI 02/03/15
OUTLINE THREE 1PH RECLOSERSTANDARD POLE MOUTING FRAME, 15,27 AND 38kV
- 0.059 D 1 of 4 3188D0404
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT: RECLOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] FRAME = 62 LBS. [28.1 KG]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE 15-27KV: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] CREEPAGE DISTANCE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV
OPEN/CLOSED INDICATOR
3D REAR VIEW
CLOSED - RED BLACKOPEN - GREEN BLACK
10.07[255,7]
15/27KV = 16.40[416,7]
38KV = 18.20[562,2]
10.00 POLE[254]
48.43[1230,2]
22.16[526,8]
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
3188D0404A
REV ECN- DESCRIPTION BY CHK. DATEA - CREATED RC XX 02/03/15
X
-
R.CARTELLI 02/03/15
OUTLINE THREE 1PH RECLOSERSTANDARD POLE MOUTING FRAME, 15,27 AND 38kV
- 0.059 D 1 of 4 3188D0404
NOTES:1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.3) WEIGHT: RECLOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] FRAME = 62 LBS. [28.1 KG]4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED.5) CONNECTION OF THE RECLOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RECLOSER IS BEING USED WITH A CONTROL CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.6) CREEPAGE DISTANCE 15-27KV: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] CREEPAGE DISTANCE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538]7) INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV
OPEN/CLOSED INDICATOR
3D REAR VIEW
CLOSED - RED BLACKOPEN - GREEN BLACK
19.60[497,9]
1.75[44,5]
1.75[44,5]
8.63[219,3]
35.31[897]
22.12[561,9]
1.50[38,1]
24.69[627,1]
6.00[152,4]
18.00[457,2]
24.08[611,6]
18.00[457,2]
12
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN
CONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26
UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE
DRAWING NUMBER
SHT. SIZE SHT. No.
NEXT ASS'Y
ENGINEERING SPEC.QUALITY STD.
MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARD
MEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690A MEMBER OF THE ABB GROUP
INCHmm
INCHmm
3188D0397C
REV ECN-DESCRIPTION
BY CHK. DATESEE SHEET 1
X
R.CARTELLI 08/29/64OUTLINE, RECLOSER 3-PH, 15-27KV
(LINE AND LOAD SIDE ARRESTER FRAMES)
0.063 D 2 of 5 3188D0397
FRONT VIEW
REAR VIEW
5/8-11 BOLT/NUT
FOR MOUNTING FRAME
MOUNTING FRAME FOR
LINE ARRESTERS AND
TRANSFORMERS
5/8-11 BOLT/NUT
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
3188D0397C
REV ECN- DESCRIPTION BY CHK. DATESEE SHEET 1
X
R.CARTELLI 08/29/64
OUTLINE, RECLOSER 3-PH, 15-27KV(LINE AND LOAD SIDE ARRESTER FRAMES)
0.063 D 2 of 5 3188D0397
FRONT VIEW REAR VIEW
5/8-11 BOLT/NUTFOR MOUNTING FRAME
MOUNTING FRAME FORLINE ARRESTERS ANDTRANSFORMERS
5/8-11 BOLT/NUT
15 kV, 27 kV, & 38 kV Three-Phase Recloser
15 kV, 27 kV, & 38 kV Single-Phase Recloser
Typical Pole InstallationsDimensions — Single and Three-Phase Reclosers
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
20.48[520,1]
3188D0396B
REV ECN- DESCRIPTION BY CHK. DATESEE SHEET 1 OF 2
X
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 1-PH, 15-27KV
1/8 D 2 of 2 3188D0396
LEFT SIDE VIEW
3/8-16 BOLT/WASHERFOR MOUNTING FRAME
LOAD SIDE ARRESTER
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
20.48[520,1]
3188D0396B
REV ECN- DESCRIPTION BY CHK. DATESEE SHEET 1 OF 2
X
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 1-PH, 15-27KV
1/8 D 2 of 2 3188D0396
LEFT SIDE VIEW
3/8-16 BOLT/WASHERFOR MOUNTING FRAME
LOAD SIDE ARRESTER
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
20.48[520,1]
3188D0396B
REV ECN- DESCRIPTION BY CHK. DATESEE SHEET 1 OF 2
X
R.CARTELLI 09/05/14
OUTLINE, RECLOSER 1-PH, 15-27KV
1/8 D 2 of 2 3188D0396
LEFT SIDE VIEW
3/8-16 BOLT/WASHERFOR MOUNTING FRAME
LOAD SIDE ARRESTER
6.08[154,5]
27.50[698,4]
2.87[73]
13.75[349,2]
18.93[480,9] 8.93
[226,9]
19.37[492]
38.74[984]
THIS INFORMATION IS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINE HEREON, AS WELL AS TO THE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTENCONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBERREV
C
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPECIFIED.
MATERIAL
DRAWINGTITLE
SCALE DRAWING NUMBERSHT. SIZE SHT. No.NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
ENGLISH METRIC DUAL
THIRD ANGLE PROJECTION
Thomas & Betts8155 TB BOULEVARDMEMPHIS, TN 38125
PHONE: (800) 888-0211, FAX: (800) 888-0690
A MEMBER OF THE ABB GROUP
INCH mm INCHmm
3188D0397C
REV ECN- DESCRIPTION BY CHK. DATESEE SHEET 1
X
R.CARTELLI 08/29/64
OUTLINE, RECLOSER 3-PH, 15-27KV(LINE AND LOAD SIDE ARRESTER FRAMES)
0.063 D 2 of 5 3188D0397
FRONT VIEW REAR VIEW
5/8-11 BOLT/NUTFOR MOUNTING FRAME
MOUNTING FRAME FORLINE ARRESTERS ANDTRANSFORMERS
5/8-11 BOLT/NUT
24.48[621,7]
24.60[624,7]
9.75[247,7]
13
Electrical Characteristics
Test Data SummaryElastimold® MVRs are tested under the requirements of ANSI C37.60-2003.This table highlights the testing covered in Elastimold® Test Report # 372-17-12010.
Ratings and Specifications
DESCRIPTION 15 KV 27 KV 38 KV*Nominal System Voltage (kV RMS) 14.4 25 35Rated Maximum Voltage (kV RMS) 17.1 29.3 38Nominal Frequency (Hz) 50 or 60 50 or 60 50 or 60Phase Spacing on 3-Phase Units (Inches) 15.5 15.5 15.5BIL (kV) 150 150 170Power Frequency Withstand – Dry (kV) 50 60 70Power Frequency Withstand – Wet (kV) 45 50 60Continuous Current (A RMS) 800 800 800Eight-Hour Overload Current (A RMS) 960 960 960CT Ratio 1000/500:1 1000/500:1 1000/500:1Interrupting Current (kA RMS Symmetrical) 12.5 12.5 12.5Making Current (kA Asymmetrical Peak) 32.5 32.5 32.5Creepage Distances – Inches (Line to Ground) 41.5 41.5 51Arc-Extinction Medium Vacuum Vacuum VacuumInsulation Medium EPDM/Silicone Rubber EPDM/Silicone Rubber EPDM/Silicone RubberMechanical Operations 10,000 10,000 10,000Normal Operating Temperatures -10°C to 45°C -10°C to 45°C -10°C to 45°CNormal Operating Conditions Voltage Sensor Accuracy (Load/Line)
+/-3%/1% +/-3%/1% +/-3%/1%
Extreme Operating Temperatures -40°C to 65°C -40°C to 65°C -40°C to 65°CExtreme Operating Conditions Voltage Sensor Accuracy (Load/Line)
5%/1% 5%/1% 5%/1%
CT Accuracy Class 1 Class 1 Class 1Weight (Single-Phase/Three-Phase) 57/208 lbs. 57/208 lbs. 58/211 lbs.* Single-phase 38kV units are rated for use on grounded systems only. Three-phase 38kV units can be used for single-phase tripping on grounded systems only. For ungrounded systems, three-phase tripping is required.
C37.60-2003 STANDARD CLAUSE & DESCRIPTION
15 KV MVRCOMPLIANCE
27 KV MVRCOMPLIANCE
38 KV MVRCOMPLIANCE
6.2 Insulation (Dielectric) Tests � � �6.3 Switching Tests � � �6.4 Making Current Capability � � �6.5 Operating Duty Tests � � �6.6 Minimum Tripping Current Tests � � �6.7 Partial Discharge (Corona) Tests � � �6.10 Temperature Rise Tests � � �6.11 Time-current Tests � � �6.12 Mechanical Duty Tests � � �6.13 Surge Withstand Capability (SWC) Tests � � �Other Testing UV/Weathering Tests � � �Other Testing IEC 62217 — Salt Fog Spray Test (1,000 hr)
� � �
14
Notes:
• Single-phase reclosers function with the SEL® 351RS Kestrel control. Three-phase reclosers function with SEL® 651Rx2, SEL® 351R or SEL® 351R Falcon controls. The MVR power module must be specified when using a SEL® 351R or 351R Falcon control.
• Load-side voltage sensors are standard on all units and function with any SEL® control having at least three 8 Vac, 1M LEA inputs (LEA voltage inputs are not used with a SEL® 351R or 351R Falcon control). All units are upgradeable to source-side voltage sensing but require a SEL® 651RX2XG control with six 8 Vac, 1M LEA inputs.
Ordering Information/Ratings and SpecificationsMolded Vacuum Recloser Catalog Numbering System
Product Type
PhasesVoltage Class
FrameNumber of Control
Power TransformersControl Power Transformer
(CPT)Control Model Control Cable Length & Type
Source Side Voltage Sensing
Terminal Lugs
Line and Load Side Arrester
Brackets
Surge Arresters
Wildlife Protectors (1 per )
Position Indicator
Factory Pre-Assembled
Customer Special
Customer Special
Customer Special
Customer Special
1 2 Description 3 Description 4 Description 5 Description 6, 7 Description 8 Description 9 Description 10 Description 11 Description 12 Description 13 Description 14 Description 15 Description 16 Description 17 18 19 20
R = Recloser 1 1 = Single Phase 1 1 = 15kV 11 = Pole Mounting Frame for MVR1
XX = None
(customer-supplied)XX
XX = None (customer-supplied)
XX = Ships without control
(customer-supplied)X X = Unit ships without cable X X = None X
X = No Terminal
LugsX
X = No Arrester Brackets
X X = None X X = No Wildlife Protectors S
S = Standard (Green
Open, Red Closed)
NN = Ships as
subassembliesX X X X
33 = Three Phase
(Single Tank)2 2 = 27kV 3
3 = Pole Mounting Frame for MVR3
11 = Single Oil
Filled CPT1 = 15kV Class A A = 651R Standard A
A = 6ft, Standard (for Single-Phase only)
11 = 1 (One)
Voltage Sensor
22 = NEMA 2-hole Lug
B
B = Both Line and Load Side Arrester Brackets
AA = 3kV, 2.55kV
MCOVB
B = Both Side & Top Bushing of MVR (Vented Style)
A
A = Alternative
(Green Closed, Red
Open)
Y
Y = Ships completely assembled
and site ready
44 = Triple Single
(3 - Single)3 3 = 38kV S
S = Adjustable Height Substation Frame for 3-Phase (single-tank)
22 = Dual Oil Filled CPT (applicable to 3-phase
or triple-single)1A
1A = 7200: 120V, 1kVA, 1PRI/1SEC (Single Bushing)
B B = 651R Premium B B = 20ft, Standard 33 = 3 (Three)
Voltage Sensors
44 = NEMA 4-hole Lug
D
D = Load Side
Arrester Brackets
only
BB = 6kV, 5.1kV
MCOVC
C = Both Side & Top Bushing of MVR (Non-Vented Style)
F
F = Frame pre-assembled,
single-phase reclosers shipped
upright
CC = Standard
Cluster Mounting for Triple Single
3 3 = Single Dry Type PT AB1B = 7620: 120V, 1kVA,
1PRI/1SEC (Single Bushing)C
C = 651R AC Transfer (applicable with Dual PTs)
C C = 25ft, Standard AA = Aerial
LugE
E = Line Side
Arrester Brackets
only
CC = 9kV, 7.65kV
MCOVD
D = Both Side & Top Bushing of MVR (Vented Style) +
Protectors for PT(s) and/or Arrestors
SS = Customer
specific assembly and pre-wiring
HH = Horizontal
Mounting Frame for Triple-Single
44 = Dual Dry Type PT (applicable to 3-phase
or triple-single)1C
1C = 7960: 120V, 1kVA, 1PRI/1SEC (Single Bushing)
DD = 651R Customer
SelectedD D = 30ft, Standard S
S = Special Lug
DD= 10kV, 8.4kV
MCOVE
E = Both Side & Top Bushing of MVR, (Non-Vented Style)
+ Protectors for PT(s) and/or Arrestors
PP = Pole Mounting
for Triple Single1D
1D = 13200: 120V, 1KVA, 2PRI/2SEC (Two Bushing)
EE = 651R Customer
SpecialE E = 35ft, Standard E
E = 12kV, 10.2kV MCOV
SS = Side Bushing of MVR
(Vented Style)
VV = Vertical Mounting
for Triple Single2 = 27kV Class F F = 351R Standard F F = 40ft, Standard F
F = 15kV, 12.7kV MCOV
RR = Side Bushing of MVR
(Non-Vented Style)
F F = Custom Frame 2A2A = 13200: 120V, 1kVA,
1PRI/1SEC (Single Bushing)G G = 351R Premium G G = 45ft, Standard G
G = 18kV, 15.3kV MCOV
TT = Top Bushing of MVR
(Vented Style)
2B2B = 14400: 120V, 1kVA,
1PRI/1SEC (Single Bushing)H
H = 351R Customer Selected
H H = 50ft, Standard HH = 21kV, 17kV
MCOVU
U = Top Bushing of MVR (Non-Vented Style)
2C2C = 13200: 120V, 1KVA, 2PRI/2SEC (Two Bushing)
II = 351RS Kestrel
StandardI I = 60ft, Standard I
I = 24kV, 19.5kV MCOV
2D2D = 14400: 120V, 1kVA, 2PRI/2SEC (Two Bushing)
JJ = 351RS Kestrel
PremiumJ J = 75ft, Standard J
J = 27kV, 22kV MCOV
3 = 38kV Class KK = 351RS Kestrel Customer Selected
K K = 100ft, Standard KK = 30kV, 24.4kV
MCOV
3A3A = 19920:120V, 1kVA,
1PRI/1SEC (Single Bushing)L
L = 351R Falcon Standard
L L = 20ft, 1st 10ft armored LL = 36kV, 29kV
MCOV
4 = 4kV Class MM = 351R Falcon
PremiumM M = 25ft, 1st 10ft armored S
S = Customer Specified (manu-facturer, ratings)
4A4A = 2300:120V, 1kVA,
1PRI/1SEC (Single Bushing)N
N = 351R Falcon Customer Selected
N N = 30ft, 1st 10ft armored
4B4B = 2400:120V, 1kVA,
1PRI/1SEC (Single Bushing)O
O = Reserved for Beckwith 351 equivalent
O O = 35ft, 1st 10ft armored
Dual Primary PP = Reserved for
Beckwith 651 equivalentP P = 40ft, 1st 10ft armored
DADA = 14,400V/7200V:120V
(Dual Primary), 1kVAQ Q = 45ft, 1st 10ft armored
CS CS = Customer Specified PT R R = 50ft, 1st 10ft armored
T T = 60ft, 1st 10ft armored
U U = 75ft, 1st 10ft armored
V V = 100ft, 1st 10ft armored
W W = 20ft, full length armored
Y Y = 25ft, full length armored
Z Z = 30ft, full length armored
0 0 = 35ft, full length armored
1 1 = 40ft, full length armored
2 2 = 45ft, full length armored
3 3 = 50ft, full length armored
4 4 = 60ft, full length armored
5 5 = 75ft, 1st 10ft armored
6 6 = 100ft, full length armored
S S = Special Cable
15
ControlsControl Type 1-Phase 3-Phase
SEL® 351RS Kestrel 10/14-pin cable XSEL® 351R X 14-pin cableSEL® 651RX2 X 32-pin cable
Notes:
1. Use with the 351R or 351R Falcon control requires connection via MVR power module. The power module is connected to the recloser via a 6 ft. 32-pin cable.
2. Voltage sensors require 8 Vac, 1M LEA inputs.
SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.
Ordering Information/Ratings and SpecificationsMolded Vacuum Recloser Catalog Numbering System
Product Type
PhasesVoltage Class
FrameNumber of Control
Power TransformersControl Power Transformer
(CPT)Control Model Control Cable Length & Type
Source Side Voltage Sensing
Terminal Lugs
Line and Load Side Arrester
Brackets
Surge Arresters
Wildlife Protectors (1 per )
Position Indicator
Factory Pre-Assembled
Customer Special
Customer Special
Customer Special
Customer Special
1 2 Description 3 Description 4 Description 5 Description 6, 7 Description 8 Description 9 Description 10 Description 11 Description 12 Description 13 Description 14 Description 15 Description 16 Description 17 18 19 20
R = Recloser 1 1 = Single Phase 1 1 = 15kV 11 = Pole Mounting Frame for MVR1
XX = None
(customer-supplied)XX
XX = None (customer-supplied)
XX = Ships without control
(customer-supplied)X X = Unit ships without cable X X = None X
X = No Terminal
LugsX
X = No Arrester Brackets
X X = None X X = No Wildlife Protectors S
S = Standard (Green
Open, Red Closed)
NN = Ships as
subassembliesX X X X
33 = Three Phase
(Single Tank)2 2 = 27kV 3
3 = Pole Mounting Frame for MVR3
11 = Single Oil
Filled CPT1 = 15kV Class A A = 651R Standard A
A = 6ft, Standard (for Single-Phase only)
11 = 1 (One)
Voltage Sensor
22 = NEMA 2-hole Lug
B
B = Both Line and Load Side Arrester Brackets
AA = 3kV, 2.55kV
MCOVB
B = Both Side & Top Bushing of MVR (Vented Style)
A
A = Alternative
(Green Closed, Red
Open)
Y
Y = Ships completely assembled
and site ready
44 = Triple Single
(3 - Single)3 3 = 38kV S
S = Adjustable Height Substation Frame for 3-Phase (single-tank)
22 = Dual Oil Filled CPT (applicable to 3-phase
or triple-single)1A
1A = 7200: 120V, 1kVA, 1PRI/1SEC (Single Bushing)
B B = 651R Premium B B = 20ft, Standard 33 = 3 (Three)
Voltage Sensors
44 = NEMA 4-hole Lug
D
D = Load Side
Arrester Brackets
only
BB = 6kV, 5.1kV
MCOVC
C = Both Side & Top Bushing of MVR (Non-Vented Style)
F
F = Frame pre-assembled,
single-phase reclosers shipped
upright
CC = Standard
Cluster Mounting for Triple Single
3 3 = Single Dry Type PT AB1B = 7620: 120V, 1kVA,
1PRI/1SEC (Single Bushing)C
C = 651R AC Transfer (applicable with Dual PTs)
C C = 25ft, Standard AA = Aerial
LugE
E = Line Side
Arrester Brackets
only
CC = 9kV, 7.65kV
MCOVD
D = Both Side & Top Bushing of MVR (Vented Style) +
Protectors for PT(s) and/or Arrestors
SS = Customer
specific assembly and pre-wiring
HH = Horizontal
Mounting Frame for Triple-Single
44 = Dual Dry Type PT (applicable to 3-phase
or triple-single)1C
1C = 7960: 120V, 1kVA, 1PRI/1SEC (Single Bushing)
DD = 651R Customer
SelectedD D = 30ft, Standard S
S = Special Lug
DD= 10kV, 8.4kV
MCOVE
E = Both Side & Top Bushing of MVR, (Non-Vented Style)
+ Protectors for PT(s) and/or Arrestors
PP = Pole Mounting
for Triple Single1D
1D = 13200: 120V, 1KVA, 2PRI/2SEC (Two Bushing)
EE = 651R Customer
SpecialE E = 35ft, Standard E
E = 12kV, 10.2kV MCOV
SS = Side Bushing of MVR
(Vented Style)
VV = Vertical Mounting
for Triple Single2 = 27kV Class F F = 351R Standard F F = 40ft, Standard F
F = 15kV, 12.7kV MCOV
RR = Side Bushing of MVR
(Non-Vented Style)
F F = Custom Frame 2A2A = 13200: 120V, 1kVA,
1PRI/1SEC (Single Bushing)G G = 351R Premium G G = 45ft, Standard G
G = 18kV, 15.3kV MCOV
TT = Top Bushing of MVR
(Vented Style)
2B2B = 14400: 120V, 1kVA,
1PRI/1SEC (Single Bushing)H
H = 351R Customer Selected
H H = 50ft, Standard HH = 21kV, 17kV
MCOVU
U = Top Bushing of MVR (Non-Vented Style)
2C2C = 13200: 120V, 1KVA, 2PRI/2SEC (Two Bushing)
II = 351RS Kestrel
StandardI I = 60ft, Standard I
I = 24kV, 19.5kV MCOV
2D2D = 14400: 120V, 1kVA, 2PRI/2SEC (Two Bushing)
JJ = 351RS Kestrel
PremiumJ J = 75ft, Standard J
J = 27kV, 22kV MCOV
3 = 38kV Class KK = 351RS Kestrel Customer Selected
K K = 100ft, Standard KK = 30kV, 24.4kV
MCOV
3A3A = 19920:120V, 1kVA,
1PRI/1SEC (Single Bushing)L
L = 351R Falcon Standard
L L = 20ft, 1st 10ft armored LL = 36kV, 29kV
MCOV
4 = 4kV Class MM = 351R Falcon
PremiumM M = 25ft, 1st 10ft armored S
S = Customer Specified (manu-facturer, ratings)
4A4A = 2300:120V, 1kVA,
1PRI/1SEC (Single Bushing)N
N = 351R Falcon Customer Selected
N N = 30ft, 1st 10ft armored
4B4B = 2400:120V, 1kVA,
1PRI/1SEC (Single Bushing)O
O = Reserved for Beckwith 351 equivalent
O O = 35ft, 1st 10ft armored
Dual Primary PP = Reserved for
Beckwith 651 equivalentP P = 40ft, 1st 10ft armored
DADA = 14,400V/7200V:120V
(Dual Primary), 1kVAQ Q = 45ft, 1st 10ft armored
CS CS = Customer Specified PT R R = 50ft, 1st 10ft armored
T T = 60ft, 1st 10ft armored
U U = 75ft, 1st 10ft armored
V V = 100ft, 1st 10ft armored
W W = 20ft, full length armored
Y Y = 25ft, full length armored
Z Z = 30ft, full length armored
0 0 = 35ft, full length armored
1 1 = 40ft, full length armored
2 2 = 45ft, full length armored
3 3 = 50ft, full length armored
4 4 = 60ft, full length armored
5 5 = 75ft, 1st 10ft armored
6 6 = 100ft, full length armored
S S = Special Cable
16
Accessories
ACCESSORY NAME/DESCRIPTION PART NUMBER
Three-phase Line Side Arrester Frame 3188D0120G1
Three-phase Load Side Arrester Frame 3188D0121G2
Single-phase Line Side Arrester Frame 3188C0122G1
Single-phase Load Side Arrester Frame 3188C0123G1
Single-phase Line & Load Side Arrester Frame 3188C0474G1
Horizontal Mounting Frame 3188D0293G1
Cluster Mounting Frame 3188D0204G1
Wildlife Protector Top Bushing (one per phase) 3070A1191P1
Wildlife Protector Side Bushing (one per phase) 3070A1190P1
Source-side Voltage Sensors (one per phase) 3188C0075G1*
Substation Mounting Frame 3188D0119G1
NEMA 2-hole Terminal Lug Kit 3188B0126G1
NEMA 4-hole Pad 3180A0661P1
Aerial Lug 3070B1302P1
* Source-side voltage sensors for Triple-Single applications require different cable lengths. Contact your T&B representative for part number.
Ask Us About the Elastimold® Recloser TodayThe Elastimold® Recloser team at Thomas & Betts is eager to further demonstrate the benefits of this industry’s premier product. For additional technical information and details, call or write us today.
17
Notes
18
Visit the T&B world of electrical product solutionsVisit our web site for more information about
Thomas & Betts solutions and our newest products.
For a user-friendly catalog and competitive part
number search, application and technical support
and other useful information, go to:
www.tnb.com
Industry codes and specificationsAll Thomas & Betts products meet or exceed applicable
industry specifications or codes which are detailed in
the appropriate T&B product literature.
IEEE ANSI RUS
Please ask your Thomas & Betts sales representative for a complete catalog of quality Thomas & Betts electrical products or visit us at www.tnb.com. For customer service, call 1-800-816-7809. For technical questions, call 1-888-862-3289.
© 2016 Thomas & Betts Corporation. All rights reserved. Printed in the U.S.A. 02/16 GM7117
Thomas & Betts Corporation Electrical Division 8155 T&B Boulevard Memphis, TN 38125 901-252-5000 www.tnb.com