Rhode Island Convention Center • Providence, Rhode Island
Refrigerant Additive and Coil Coating Case Studies
Session: HVAC Technologies
Michael Bowers, PE, LEED Green AssociateAmec Foster Wheeler
August 10, 2016
Energy Exchange: Federal Sustainability for the Next Decade
Session Outline
2
1. Identify Reasons for DX Efficiency Degradation2. Testing Methods3. HVAC Armor Test Results4. IceCOLD Test Results5. Combined Test Results6. Summary
Energy Exchange: Federal Sustainability for the Next Decade
Objective
3
Direct‐expansion (DX) equipment begins to degrade shortly after installation. This study documents the efficiency gains of two
products that claim to increase the performance of DX equipment by tackling two major causes of degradation.
Condenser coil fin oxidation/degradation
Reduces oil fouling in refrigerant lines
Energy Exchange: Federal Sustainability for the Next Decade4
Efficiency of a System
EER, COP, EI, SEER, kW/ton…
Energy Exchange: Federal Sustainability for the Next Decade5
Testing Methods
Energy Exchange: Federal Sustainability for the Next Decade
• Field Diagnostics’ HVAC Service Assistant– Instantaneous diagnostic equipment– Compares the pressures and temperatures of the refrigeration cycle against generic compressor data
– Calculates efficiency index (EI) EI =
6
Testing Method – HVAC Service Assistant (EI)
Pros• Ease of use• Instantaneous calculations• Comprehensive data
analysis• EI is normalized for
ambient temperature
Cons• Single‐point data• Non‐industry standard
efficiency rating (EI)
Energy Exchange: Federal Sustainability for the Next Decade
• HVAC Armor testing method– Calculating change in enthalpy across the condenser– Data loggers obtain 20‐30 minutes of data
• Analyzed data is chosen based on finding a stable set of data in the temperature/pressure
– Data is corrected for ambient temperature
– COP =
7
Testing Method – COP Data Logging
Pros• 20‐30 minutes of data
obtained• COP calculated before and
after implementation
Cons• Total system efficiency
based on assumptions of fully functioning system
• COP varies greatly during system operation
Energy Exchange: Federal Sustainability for the Next Decade8
Testing Method – Compressor Amp Draw
Pros• Actual current draw• Full week of data to
analyze before and after implementation
Cons• Low sample size yields
unreliable data when corrected for ambient temperature
• Cannot account for changes in occupant behavior
• IceCOLD testing method– Amp‐draw was logged and analyzed– Data loggers obtained one week of data for baseline and one week of data for post‐implementation data
– Data is corrected for ambient temperature using cooling degree days (CDD)
Energy Exchange: Federal Sustainability for the Next Decade
• Total of 14 DX units were tested at various test sites in North Central Florida (12 units of valid data)
• Each individual circuit analyzed• Performance analyzed using three different methods
9
Test Overview
Energy Exchange: Federal Sustainability for the Next Decade10
Test Limitations
Imperfect equipment with imperfect data
Variables• Behavioral changes• Changes in thermostat setpoints• Voltage
Corrective Measures• Analyzed data with similar CDD• Eliminated data that were clear anomalies
Energy Exchange: Federal Sustainability for the Next Decade11
Energy Exchange: Federal Sustainability for the Next Decade
What is HVAC Armor?
12
• Inorganic coating for DX coil protection and rejuvenation
• Restores coil to original state• Prevents corrosion• ~1 mil coating allows for maximum heat
transfer and condenser coil airflow • Advertises 13% energy savings
Energy Exchange: Federal Sustainability for the Next Decade13
Installation – HVAC Armor
Condenser coil is cleaned, combed, and coated with HVAC Armor
Energy Exchange: Federal Sustainability for the Next Decade14
Testing Results – HVAC Armor
Percent Increase in EfficiencyTag Tons Pre‐EI
CU‐2 7.5 73CU‐5 15 111CU‐6 5 82CU‐7 10 78CU‐8 10 86RTU‐3 6 103RTU‐4 10 95RTU‐6 5 98
ton‐weighted average
Unit in worst condition yielded the highest efficiency gains
HVAC Armor % Increase
39%15.9%‐3.8%‐9.7%‐3.4%25%11%15.2%10.5%
EI% Increase
5%2%2%1%1%‐6%0%4%1.2%
Energy Exchange: Federal Sustainability for the Next Decade15
Energy Savings – HVAC Armor
Savings estimated using Trane Trace 700™ modeling software
• One of the tested buildings was modeled and calibrated to utility bills
• Cost estimates provided by HVAC Armor• Electrical cost assumed to be $0.12/kWh
Payback varies for each unit, but can be maximized if unit is
properly screened for application
Tag Tons
CU‐2 7.5CU‐5 15CU‐6 5CU‐7 10CU‐8 10RTU‐3 6RTU‐4 10RTU‐6 5
ton‐weighted average
*Paybacks must be analyzed against expected remaining life expectancy of the unit
HVAC Armor % Increase Payback
39% 0.74 15.9% 1.53‐3.8% ‐‐9.7% ‐‐3.4% ‐25% 1.0411% 2.1515.2% 1.5910.5% 2.50
EI% Increase Payback
5% 4.152% 13.372% 9.581% 19.871% 22.37‐6% ‐0% ‐4% 6.401.2% 23.56
Energy Exchange: Federal Sustainability for the Next Decade16
Energy Exchange: Federal Sustainability for the Next Decade
What is IceCOLD?
17
• Synthetic catalyst that reduces oil fouling in refrigerant lines
• Restores system to original capacity• Keeps system lubricated and prevents future
oil fouling• Advertises a 10% reduction in HVAC energy
consumption (average 15‐23%)
Energy Exchange: Federal Sustainability for the Next Decade18
Installation ‐ IceCOLD
Refrigerant levels are measured* to calculate
correct amount of IceCOLD to add to system.
*Refrigerant levels were not modified as a part of this study
Energy Exchange: Federal Sustainability for the Next Decade19
Testing Results – IceCOLD
Amp Draw (Amp‐hr/day/CDD)Analyzed by IceCOLD
Tag Tonnage Pre‐EI
RTU‐1 10 97RTU‐2 10 95RTU‐3 6 79RTU‐5 15 81CU‐2 7.5 74CU‐4 15 91CU‐5 15 113
ton‐weighted average
IceCOLD % SavingsAmp‐hr/day/CDD
4.1%14.4%20.0%4.9%29.5%8.6%9.4%11.1%
EI% Increase
0%3%30%‐4%‐1%‐3%‐5%0.2%
Energy Exchange: Federal Sustainability for the Next Decade20
Combined Effect
Energy Exchange: Federal Sustainability for the Next Decade21
The combined system effect on the application of both products was analyzed for 28.5 tons of equipment.
Combined Effect
While efficiency gains can be realized by implementing both HVAC Armor and IceCOLD, the savings do not appear to compound on top of one another.
Majority of the energy savings will be realized after the first product implementation
74%
26%
Total Achieved Savings
First Product Second Product
Energy Exchange: Federal Sustainability for the Next Decade22
What does all this mean?
Energy Exchange: Federal Sustainability for the Next Decade23
Summary
• Increases efficiency of unit• Simple payback increases
substantially when you consider potential cost avoidance
• Energy savings confirmed for a small population of tested units
• Not cost‐effective to apply both products to a single unit• Screening of units is recommended prior to product
installation
Energy Exchange: Federal Sustainability for the Next Decade
Thank you for your time!
24