Transcript
Page 1: RMR Gas Insulated Switchgear Catalog

SF6 Gas insulated Switchgear RMR-24/36 Series 24kV ,. Up to 36kV,……

Technical Manual

ROCKWILL ELECTRIC CO.,LTD

Page 2: RMR Gas Insulated Switchgear Catalog

C Unit

F Unit

V Unit

++++General RMR-24/46kV is completely insulated SF6 SAFERIN(hereinafter short as SF6 Gas insulated Switchgear)This product is in conformity with the standards the GB/IEC standard and the design of a high safety combined switch cabinets.

The system of RMR-24/36kV of combined switch cabinets can be divided into three kinds of unit cabinet:

++++ 3 position cable connection unit (Cable switch unit), additional live shows and configuration of surge arresters and grounding fault component. Code C

++++3 position switch and fuse tripping system and earthing switch interlock system fuse combined electrical unit (Fuse combination unit), additional live shows and configuration of surge arresters and grounding fault component. Code F

++++3 position switch and vacuum circuit breaker combined appliances unit (Vacuum circuit breaker unit), additional current transformer, live shows and configuration of surge arresters and grounding fault component. Code V The combination of the current transformer and the microcomputer protection to constitute the basic circuit protection function. Microcomputer protection using passive protection and CT electric no need of additional PT power supply

Reference standard:

----IEC62271-200 ----IEC62271-100 ----GB3804-2004 ----GB3906-1991 ----GB16926-1997 ----GB/T11022-1999

Remark:

Fuse combined electrical follow IEC 60420

VCB unit according to IEC 62271-100/GB1984-2003

Page 3: RMR Gas Insulated Switchgear Catalog

++++Service environment a) Air temperature: ±40℃; Daily average ≤25°C b)Altitude above sea level: Maximum installation altitude: 4000m c)Wind: less than 35m/s d)Earthquake intensity: no more than 8 degrees;

++++ Main technical specifications No Item Unit Data 1 Rated voltage 24/36

Dry Power Frequency withstand voltage Wet

60/70/80/95 2

Lightning Impulse withstand Voltage (peak value)

kV

125/150/170/185/200

3 Rated Current A 630/1250/2500 4 Rated short circuit breaking current (peak) kA 20/25(V) 31.5(F) 5 Rated closed-loop breaking current A 630/1250(C) 6 Rated cable charging interrupting current A 50(C) 7 Rated line cable charging interrupting current A 10(C) Rated off circuit transformer breaking current A 16 8 Rated making current (peak) 9 Rated withstand current (peak)

50(63/80)/2.5(main switch/grounding)

10 Rated short time withstand current kA

16/20/25/31.5 11 Rated short time withstand time S 3/4 12 Mechanical life times C/F(2000)V(10,000) 13 Main busbar A 630/1250/2000/2500

++++Each Panel face, dimension & function Customized Panel View Type & functions W×D×H mm

1C=500×950×1360mm 2C=1000×950×1360mm 3C=1500×950×1360mm

Mainly for switching kiosk or cable branch box

Extra bushing=140mm

Note: Above unit is for special type using for like solar plant, wind plant cable system.

Page 4: RMR Gas Insulated Switchgear Catalog

Standard Panel View Unit C Standard Panel View Unit F Standard Panel View Unit V

500×950×1950 500(568)×950×1950 500(568)×950×1950

Note: 1, Unit V type LBS can be changed to be mounted on top for feeder cable outgoing system. 2, Unit V type incomer type with 3 nos VTs configuration width is 568mm. 3, Each unit can be connected with top busbar to be combined as Ring main unit

Standard economic type Ring main unit Combination complete common gas tank CCF

Dimension 1500×950×1950

Page 5: RMR Gas Insulated Switchgear Catalog

++++Busbar system RMR type GIS switchgear can be used for main station as main switchgear, the main busbar current up to 2500A, 40kA.. Below is different schema for range of busbar current selection on RMR type GIS switchgear.

Main busbar 2500A,40kA, Max Busbar 630/1250A ,31.5kA, Max.

Busbar Section Max. up to 2500mm2 Busbar Section Max. up to 600mm2

++++Other expanding configurations for reference Vacuum circuit breaker unit for incomer using

Fuse combination for transformer protection using

Cable switch unit

Remark: Other accessories like PT, CT, relays can be equipped by special requirement. For more question pls consult with Rockwill: [email protected]


Top Related