HVAC PROJECT DETAILS
Building type: Commercial building
Location: Bangalore, India
Floors: Ground floor + 16 floors
Area: 3,00,000 sf
Cooling load: 352 TR
Occupancy: 3,584 people
Operating Schedule: 5 Days / Week
Air distribution system: VAV Single Duct
-
TYPICAL FLOOR PLAN
-
3D VIEW OF BUILDING
-
HEAT LOAD REPORT
-
AIR DISTRIBUTION DESIGN
-
AIR DISTRIBUTION SYSTEM
Floor mounted AHU is selected to distribute air
Comfort condition 77F And 50% RH
ADP is 54F And 8,000 CFM
Chilled water inlet 8C And outlet is 15C
VCD are placed at beginning of each Duct
Backward curved Aerofoil blade Centrifugal fan is selected
for AHU
Inline centrifugal fan is selected for Exhaust air
MERV 8 Filter is selected for AHU
-
DUCT PRESSURE DROP ANALYSIS Pressure drop is due to bends and head
Static pressure in critical path is 29 Pa & 52 Pa
Based on Static pressure in critical path AHU fan is selected
-
CHILLER PLANT DESIGN
Total building cooling load 352 TR
Water cooled screw chillers 2 quantities
175TR+175TR
Cooling tower Approach is 3C And Range is 4C to
8C
-
ELECTRICAL SYSTEM
Ladder type cable trays are used
-
SECTIONAL VIEW
Lighting fixture Sprinkler
Diffuser False Ceiling
True Ceiling
-
PLUMBING
1:100 Slope for sanitary pipes
Sanitary pipe connection should be 45
-
CO-ORDINATION OF ALL FLOORS
-
FIRE FIGHTING Fire fighting system is designed as per NBC
standards for commercial building
Pipes are sized based on No of sprinklers
-
INTERFERENCE CHECK Interference Report Project File: F:\HVAC REVIT PROJECT\floor project\RUDRA _Mechanical
Project.rvt
Created: Friday, May 27, 2016 4:06:49 PM
Last Update:
-
CLASH DETECTION & SOLUTION
Clash in between
supply duct and cable
tray.
Clash is solved by
moving supply duct
Clash in between
column and supply duct.
Clash is solved by
moving supply duct
-
ANNOTATION Labels are created to annotate duct size, flow
rate and BOD
Diffusers are tagged with neck size and CFM
-
CREATING FAMILY (AHU)
-
A1 DRAFT SHEET
-
BILL OF QUANTITY
-