The SattScope Operator Panels are a range of operator interface terminals that are ideally suited to replace discrete components, push buttons and display instruments in many applications.
The functionality of the OPs is naturally progressive. Upgrades can be
easily undertaken as many of the OPs have the same physical dimensions and panel cutout.
All the OPs use the same Windows-based configuration program, allowing for quick and easy set-up and installation. It’s easy to use the
pre-defined objects that are supplied with the OPs and reduce the programming time for your application. Contained in the configuration software are a wide variety of bitmap examples containing pictures of push-buttons, sliders, bars, meters, sensors....
Operator Panels
SattScope
a
/
/
t
e
Operator PanelUsed for configura-tion only
Printer optionUnique “one hole fixing”
PLC
PLC
Host comms option
Operator Interfaces -Terminals for IndustryThe operator interface products of the SattScope Operator Panel range are designed to provide high quality humanmachine interfaces (HMIs) for PLCs and other types of industrial control systems.
They have rugged plastic or metal enclosures validated to NEMA/IP/FCCCE standards.
The OP typically comprises a slim enclosure mounting, an LCD screen thais monochrome, and a membrane keypad. Some of the models in the rangoffer resistive-touch overlays for the display, further enhancing the customized options offered by the product.
The OP run-time software offers a wide range of facilities from simple text displays on the entry level “SattScope K” model, to trends, bar charts, and dynamic bitmaps on the more powerfumodels.
All the OPs can be tailored to better suit the user requirements by implementing the configurable “soft keys”. Here, there is a potential for ove600 application specific keys on the entry level systems and even more on the more advanced units.
Using the OPs with touch sensitive screens delivers even greater flexibilitywith up to 48 touch sensitive areas on the smaller OP units.
l
r
,
Configuration SoftwareAll the OPs are configured off-line from the PC based software tool WinCfg. WinCfg functions under Windows 3.11,Windows 95/98 and Windows NT.
Configuring an OP is quick and easyand there is the benefit of a common development environment for all models in the SattScope Operator Panrange. This will effectively reduce the “time of implementation” when designing the application solutions.
Having selected the database type fothe target OP (SattScope K, J+, H, 240or 320T) the software automatically structures the screen display and run-time facilities to match the target system.
Once configured it is a simple matterto download the database to the targetOP system through the PC’s serial portNow the SattScope Operator Panels isready to go on-line.
f
n
le.
e
Run-Time SoftwareAll the OPs support certain standard functions which are considered essential for a quality MMI product thatis able to deliver an effective operator interface.
CommunicationsThe OPs support both read and write functions for a wide variety of control equipment protocols from the on-boardserial port.
Analogue and Digital PointsIt is possible to scale raw analogue datand convert it into plant engineering units. Digital point identity information, tag names and alarm limits are fully supported.
Alarm ManagerChecks for alarms on analogue and digital values can be managed to maintain a log of active alarms and supports operator acknowledgement oalarms.
OverviewOverview pages display pre-configuredgroups of Operator Panel or PLC data ieasily understood tabular form.
Text Page DisplayDisplays of static and dynamic text on up to 100 user defined pages is possib
Multiple font sizes are supported to enhance important or critical data. Up to512 dynamic elements per page may bconfigured.
,
el
r T
.
g e
et
Soft KeysEither 6 or 8 user defined keys may beconfigured on each text page dependinon the OP model. The keys may changpage, write to the PLC or perform otheroperator interface tasks.
ProtocolsAll the OPs are supplied as standard with a full suite of serial protocols for which there is no charge.
The serial protocols, currently available in the OP library, are providedwith the configuration software. During configuration, a protocol will be selected, and is downloaded to the targsystem.
All the protocols are read/write in order to allow the operator to view dataand send new information and instructions to the control device. Although the control device is typically a PLC, this is not always the case. A number of protocols are provided for other types of control devices, such asI/O systems, or three term controllers.
Interfacing to SattBus requires an adapter.
s
,
Operator PanelsThe OPs offer a new and exciting departure from the normal operator interface devices. All of the models in the OP range are rich in features normally found only on larger, more expensive devices, such as, printer ports, alarm handling, clocks, single hole cutout fixing and IP65/Nema 4/12rating.
SattScope KThe SattScope K is the “entry level” - text only - model in the OP range of MMI devices. The use of advanced design and manufacturing technologiehas enabled the SattScope K to be equipped with high functionality firmware at very low cost.
The operator interface comprises a high resolution pixel based display anda simple membrane keypad with tactilefeedback.
The panel cut-out and depth requirements are compatible with the more sophisticated models J+ and 240Tthereby simplifying the process of future upgrades.
● Flash program and data storage, no battery backup needed
● Six configurable function keys plus numeric and control keys
● Dynamic and static display of text in multiple font sizes
● Alarm management● 600 user configurable keys● Clock set from the PLC
SattScope HThe SattScope H OP (in a rugged metal enclosure for use in arduous industrial conditions) offers a clean, bright screen of unparalleled display quality with crisp images of superior definition. The hexadecimal keypad incorporates 8 user-defined function keys.
● NEC V40 processor● 512 kbytes of flash memory for
program and data storage● 640 x 200 dot matrix monochrome
display ● Metal enclosure● Display bitmaps● Print function● Real time clock
SattScope J+The SattScope J+ extends OP functionality from a simple text display to a more powerful interface. This is achieved through the use of trends, bar charts and bitmaps, while still maintaining the same ease of use.
It is manufactured to the same frame size as the SattScope K, providing a simple upgrade path from it.
The monochrome LCD screen offers a 256 x 64 pixel display area, with 8 lines of text of 42 characters, in variable font size.
● Display data as bar graphs, either vertically or horizontally
● Display data as graphical trends● Display text in sizes configurable by
the users● Alarm manager● Display bitmaps● Print function● Real time clock
e
a
.
SattScope 240TThe SattScope 240T incorporates all thtried and tested functionality of the OPrange with a larger, brighter display overlaid with a touch-sensitive system for direct screen interaction.
The normal LCD display of the OP range has been replaced by a CCFT-backlight transmissive model, increasing the display size to 240 x 128pixels and incorporating a resistive-touch display window.
This has enabled the development of touch membrane overlaid on the muchsimplified keypad, from which all but the essential keys have been removedThe resistive touch area of the display window has been divided into 8 horizontal rows and 6 vertical columnsto give 48 touch points each 16 pixels high and 40 pixels wide.
● 256 kbytes of flash memory for program and data storage
● Pop-up numeric/application keypad● Real time trending, bar charts and
bitmaps
ABB Automation center in Malmö, Sweden: +46 40 222000, Fax: +46 40 219539, Internet: www.automation.alfalaval.com. TELEPHONE: ARGENTINA: Buenos Aires: +54 1 229 5500/5560, AUSTRIA: Vienna: +43 160109/9105, BELGIUM:Brussels: +32 2 7186471, BRAZIL: Osasco: +55 11 7084 8220, CANADA: Scarborough: +1 416 2996101, CHILE: Santiago: +56 2 2335366, DENMARK: Copenhagen: +45 44 848844, Silkeborg: +45 86 822811, ESTONIA: Tallinn:+372 6 711800, FINLAND: Helsinki: +358 10 222000, FRANCE: Le Blanc-Mesnil: +33 1 55815200, GERMANY: Munich: +49 89 840000, Glinde: +49 40 727409, Haan: +49 2129 94130, HUNGARY: Budapest: +36 1 4635270, INDIA: Pune:+91 212 797721, IRELAND: Dublin: +353 1 4573399, ITALY: Monza: +39 3624951, LATVIA: Riga: +371 7 828508, LITHUANIA: Vilnius: +370 2 233566, MEXICO: Mexico City: +52 5 3986162, NETHERLANDS: Etten-Leur: +31 76 5086200,NORWAY: Oslo: +47 64 835200, PERU: Lima: +51 1 2248801, POLAND: Warzaw: +48 22 6581020, ROMANIA: Bucharest: +40 1 3370615, RUSSIA: Moscow: +7 095 2322593, SINGAPORE: +65 776 5711, SLOVAK REPUBLIC: Bratislava:+421 7 5254473, SPAIN: Madrid: +34 1 3790741, SWEDEN: Malmö : +46 40 222000, Gislaved : +46 371 80151, Göteborg: +46 31 7276950, Jönköping : +46 36 175030, Karlskoga: +46 586 39330, Stockholm: +46 8 53066100, Sundsvall:+46 60 129380, Västerås : +46 21 810135, SWITZERLAND: Kloten: +41 1 8046600, UNITED KINGDOM: Northwich: + 44 1606 49935, USA: Kenosha: +1 414 9429310, Warminster: +1 215 9578980, Greenwood : +1 317 8894626.
Specifications subject to change without notice. Printed in Sweden. © 1999 ABB Satt AB.
0000
0. A
E A
nder
sson
Gra
fiska
AB
. Prin
ted
in S
wed
en 1
999.
Technical Data
*All current models can display up to 100 text pages, the size of text being configurable.
Windows, Windows 95 and Windows NT are registered trademarks of Microsoft Corporation.
Hardware SattScope K SattScope J+ SattScope H SattScope 240TStandard Processor NEC V20 NEC V40 NEC V20
Display Type LCD-EL Backlight LCD-CCFT Backlight
Display Area (pixels) 256 x 64 pixels 640 x 200 pixels 240 x 128 pixels
Display Area (Height x Width)
35 x 124 mm1.38 x 4.88 inches
79 x 211 mm3.12 x 8.31 inches
64 x 119 mm2.50 x 4.70 inches
Touch Display No Yes, 48 regions
Database Memory 64 kbytes
LEDs 4 LEDs - Power, Status, Receive and Transmit
Keypad - Audible Touch Membrane Keypad - 22 keys 30 Membrane keys 10 Membrane keys
Protection Rating IP65 (NEMA4 x 4/12 UL CE)
Real-time Clock Set from PLC Yes
Function Keys 6 programmable keys 8 programmable keys
Memory Type 256 kbytes Flash 512 kbytes Flash 256 kbytes Flash
Serial Ports 1 (RS232) 2 (RS232)
Printer Port No Yes
Power Supply 9 V DC–35 V DC (24 V rms)
Power Drain 9 V DC–370 mA / 35 V DC–95 mA9 V DC–780 mA /35 V DC–200 mA
9 V DC–450 mA /35 V DC–185 mA
Overall Dimensions(Height x Width x Depth)
188 x 208 x 51 mm7.4 x 8.2 x 1.8 inches
267.4 x 311 x 51 mm10.53 x 12.24 x 2 inches
188 x 208 x 51 mm7.4 x 8.2 x 2 inches
Cutout Dimensions(Height x Width)
177 x 197 mm7.0 x 7.8 inches
243.4 x 287mm9.6 x 11.3 inches
177 x 197 mm7.0 x 7.8 inches
Weight 795 grams / 1.75 pounds 3.85 kg / 8.5 pounds 795 grams / 1.75 pounds
Environmental Operating Temp.: ±0° to +40°C, Storage Temp.: -20° to +60°C. Vibration 2 G from 81 to 1000 Hz
Humidity 5 to 85% non-condensing
Approvals Designed to comply with Part 15 of the FCC Regulations, EN5022 and CE status
Software SattScope K SattScope J+ SattScope H SattScope 240TAlarm Processing Yes
Windows Configurator Yes
Comms Blocks 100 Blocks 250 Blocks 100 Blocks
Analog Points 250 Points
Digital Points 200 Points 500 Points 200 Points
User Bits 1000 Bits
Registers 500 Registers
Text – Default Size * 8 rows x 42 characters 14 rows x 80 characters
14 rows x 40 characters
Bar Graphs No Yes
Bit Maps No Yes
Trending No Yes
Host Communications No Yes
Password Can be configured to protect access to Off-line Utilities and Drive Outs
Protocols More than 80 alternative communication protocols for a variety of makes of control system accompany the panels. Only SattBus involves an optional cost.
493-
1079
-11
9903
Ver
. 3-1