Signature of The Contractor Page 1 of 14
SBI INFRA MANAGEMENT SOLUTIONS PVT.LTD.
3rd Floor, Local Head Office,Bank Street, Koti, Hyderabad- 500095
On behalf of On behalf of On behalf of Cash Management Product GOC (CMP
GOC) & Internal Audit Department(IAD) lingampally invites tenders for
ELECTRICAL WORKS RELATED TO AC & UPS OF CMP GOC & IAD, LINGAMPALLY,
HYDERABAD”
IN TWO BID SYSTEM THROUGH E-TENDER
PRICE BID
The Technical and price bid to be submitted online on M/s E-
Procurement Technologies
Ltd.websitehttps://sbi.abcprocure.com/EPROC.
E-TENDER IS INVITED FROM THE EMPANELLED CONTRACTORS OF LHO,
HYDERABAD FOR ELECTRICAL WORKS UPTO Rs. 15 lakhs ARE ELIGIBLE TO
QUOTE.
TENDER NO.: SBIIMS/29/18
Signature of The Contractor Page 2 of 14
AC & UPS WORKS OF IA AND CMP GOC WORKS
SL NO Description unit Qty Unit price Total Amount
1
Supply, installation, concelling and fixing of following items:
TPN DBs - VTPN DB, IP43, IK 09 with metal door 4 way DB model
No: 6079 13, Qty:1 DPX 160, Icu 36KA, 100A, 4 pole
MCCB model No:4200 95 Qty:1
D curve 32 Amps single pole MCB (Model No: 4087 19) Qty:12.
Complete the work as directed by the SBIIMS.
Pupose: AC DB
No 1
2
Supply, installation, concelling and fixing of following tems:
1 no of DP enclosure(Model No:6078
82) with one no of 2 pole 32A MCB(Model No 4087 45).Complete
the work as directed by the SBIIMS. Purpose: AC DB to SUb DB at
various locations inside the room
No 9
3
Supply, Installation, concelling and fixing of following items:
TPN DBs- VTPN DB, IP43 with
acrylic door, 4 way DB(model NO: 6077 25) -Qty:1
D curve 4 pole 63A MCB (Model No: 4087 94 ) Qty:1,
SPN MCB: Qty :8 . Complete the work as directed by the SBIIMS
Purpose: Raw Power DB
No 1
Signature of The Contractor Page 3 of 14
4
Supply, Installation, concelling and fixing of following items
SPN DB IP 43 IK 09 with acrylic door 12 way DB( model No:6077
22) Qty:1 63 Amps 2 pole MCB D curve(
model No: 4087 48) Qty-1 16Amps 2 pole MCB (model No:
4087 42) Qty:8 . Complete the work as directed by SBIIMS
Purpose: UPS DB
No 1
5
Supply , laying , Testing and commissioning of 16sqmm 4 core
copper armoured LT XLPE insulated PVC sheathed FRLS armoured cable
1.1 KV grade confirming to extruded
PVC Type ST2 Sheathed, 650/1100 V grade as per IS7098 (part-I)
1988. The scope of work includes civil works like excavation and back
filling. Complete the work as directed by the SBIIMS.Purpose:
panel to AC DB input
rmt 70
6
Termination of the cable with
suitable double compression gland and canopy. Complete the work as
directed by the SBIIMS
No 2
Signature of The Contractor Page 4 of 14
7
Supply , laying , Testing commissioing and termination of
4sqmm 3 core copper armoured LT XLPE insulated PVC sheathed
FRLS armoured cable 1.1 KV grade confirming to extruded PVC Type
ST2 Sheathed, 650/1100 V grade as per IS7098 (part-I) 1988. The scope
of work includes civil works like plastering andconcelling if required
etc. Comple the work as directed by
the SBIIMS Purpose: AC DB to AC individual
control to AC outdoor unit
Rmt 230
8
Termination of the cable with suitable double compression gland
and canopy. Complete the work as directed by the SBIIMS
No 18
9
Supply , laying , Testing and
commissioing of 10sqmm 4 core copper armoured LT XLPE
insulated PVC sheathed FRLS armoured cable 1.1 KV grade
confirming to extruded PVC Type ST2 Sheathed, 650/1100 V grade as
per IS7098 (part-I) 1988. The scope of work includes civil works like
excavation and backfilling and plastering if required etc..Comple
the work as directed by the SBIIMSPurpose: PANEL to UPS1 &
UPS2 and Panel to raw power DB
Rmt 230
10
Termination of the cable with
suitable double compression gland and canopy. Complete the work as
directed by the SBIIMS
No 8
Signature of The Contractor Page 5 of 14
11
Supply , laying , Testing and commissioing of 10sqmm 3 core
copper armoured LT XLPE insulated PVC sheathed FRLS
armoured cable 1.1 KV grade confirming to extruded PVC Type
ST2 Sheathed, 650/1100 V grade as per IS7098 (part-I) 1988. The scope
of work includes civil works like plastering if required etc. and also
supplying and laying of fine river
sand with shabad stones for cable protection of the cables. Comple the
work as directed by the SBIIMS Purpose: UPS o/p DB to UPS DB
inside the room
Rmt 50
12
Termination of the cable with suitable double compression gland
and canopy. Complete the work as directed by the SBIIMS
No 2
13
Supply , laying, termination and
dressing of 1.1KV XLPE PVC Insulated 10sqmm 4 core copper
flexible cable. The scope of work includes laying of cable in a suitable
metal hose flexible pipe .complete the work as directed by the SBIIMS.
Purpose: UPS Input DB to UPS i/p
Rmt 30
14
Supply , laying and dressing of
1.1KV XLPE PVC Insulated 10sqmm 3 core copper flexible
cable. The scope of work includes laying of cable in a suitable metal
hose flexible pipe .complete the work as directed by
theSBIIMS.Purpose: Ups o/p to UPS o/p DB
Rmt 30
Signature of The Contractor Page 6 of 14
15
Supply, installation and fixing of 63/100 Amps 4 pole 36KV MCCB in
a suitable metal enclosure. Complete the work as directed by
the Bank. Output of this MCCB will be connected to UPS.Complete the
work as directed by the SBIIMS. Purpose: UPS i/p DB
no 2
16
Supply, installation and fixing of 100Amps2 pole MCB in a suitable
metal enclosure. Complete the work as directed by the Bank. Output of
UPS will be connected to this MCB.
Purpose: UPS o/p DB
no 1
17
Supply, installation and fixing of 100Amps 4 pole 36KV MCCB with
suitable handle it has to be installed inside the distribution panel. The
scope of work extending to power wiring from bas bar to MCCB &
MCCB to Terminals and also supply&
fixing of suitable terminals. Complete the work as directed by
the SBIIMS. Purpose: AC, UPS, raw power i/p DB
at panel room
No 3
Signature of The Contractor Page 7 of 14
18
Providing independent earthing for sophisticated electronic equipment
with 600 mm x 600 mm x 3.5 mm thick copper plate rigidly fixed to 40
mm dia G.I. pipe of 0.3 mtr length connected with reducer providing
.GI. funnel with wiremesh as per national electric code including C.C.
Chamber of size 400 mm x 400 mm x 400 mm covered with RCC slab
filling with salt and charcoal giving
earth connection from electrode copper G.I. strip of 50 mm x 6 mm
x 200 mm length with all accessories and labour charges
complete, as per IS specifications 732/1982 (Part II) for UPS
earthing.Complete the work as directed by the SBIIMS.Purpose:
Earthing for UPS
No 2
19
Providing independent earthing for important equipment with 40 mm
dia "B" class 2.5m long G.I pipe and 19mm dia "B" class G.I pipe of 0.3
mtr. Long connected with reducer providing G.I. funnel with mesh
enclosed in C.C. Chamber of 400mm x 400 mm x 400 mm with RCC slab
cover duly providing staggered holes filling with salt and charcoal
from the bottom of the pipe giving earth connection from electrode
through G.I. strip of 50 x 6 mm x 200 mm length with all accessories
and labour charges complete, as per
IS specifications 732/1982 (part II)- for body earthing.Complete the
work as directed by the SBIIMS.
No 2
20
Supply and run of 50 mm x 6 mm G.I. strip including cost of all
accessories and labour charges etc. complete the work as directed by
the SBIIMS
rmt 10
Signature of The Contractor Page 8 of 14
21
Supply and run of 25 mm x 6 mm G.I. strip including cost of all
accessories and labour charges etc. complete the work as directed by
the SBIIMS
rmt 50
22
Supply and run of 8SWG copper bear wire including cost of all
accessories and labour charges etc. complete the work as directed by
the SBIIMS
rmt 100
23
Supply and run of 25 mm x 6 mm copper strip including cost of all
accessories and labour charges etc. complete the work as directed by
the SBIIMS
rmt 12
24
Supply, laying and termination of 25 sqmm single core copper flexible
cable in a suitable PVC conduit from neutral earth pit respective floor
DBs earthing.Complete the work as
directed by the SBIIMS.
rmt 60
TOTAL QUOTED AMOUNT FOR ELECTRICAL RELATED TO AC & UPS OF
2ND FLOOR OF IA -- PART-A
Tiolet electrical works
Signature of The Contractor Page 9 of 14
1
Supply and Concealed wiring in a stone mashonary wall for light, fan,
exhaust fan, call bell / 5A plug points with 3 runs of 1.5 Sqmm
P.V.C insulated FRLS copper conductor single core multi
standard wire in PVC conduits with 3 plate ceiling rose etc. The scope of
work including the supply of 6A modular switches / boxes & front
plates. (the light and fan point wiring shall be concealed in the wall
and replastered) the scope includes Extending existing light points
below the false ceiling with 3core
1.5 sqmm flat wire in MS flexible pipe as required and terminate the
wires with suitable lugs, complete in all respects by using approved make
& quality items and directed by SBIIMS.
no 14
2 Same as the above 3 lights
controlled by one switch.Complete the work as directed by the SBIIMS.
No 2
3 Supply & fixing of 15 watts down
lights.Complete the work as directed
by the SBIIMS.
No 8
4 Supply & fixing of 28 watts 4 feet lEDlight.Complete the work as
directed by the SBIIMS.
No 1
5 Supply & Fixing of Exhaust fan. Complete the work as directed by
the SBIIMS.
No 4
6 Supply & fixing of Hand Dryer. Basic Cost Rs.6500.00. Complete the
work as directed by the SBIIMS.
No 1
7 Supply & fixing of Occupancy
sensor. Complete the work as directed by the SBIIMS.
No 1
TOTAL QUOTED AMOUNT FOR ELECTRICAL WORKS RELATED TO WASHROOMS OF 2ND FLOOR IA- PART B
Signature of The Contractor Page 10 of 14
UPS at Ground floor works
1
Supply & Installation of 4 pole, 63Amps Manual changeover switch
with suitable enclosure switch. Complete the work as directed by
the SBIIMS.
No 2
2
Providing independent earthing for
sophisticated electronic equipment with 600 mm x 600 mm x 3.5 mm
thick copper plate rigidly fixed to 40 mm dia G.I. pipe of 0.3 mtr length
connected with reducer providing .GI. funnel with wiremesh as per
national electric code including C.C. Chamber of size 400 mm x 400 mm
x 400 mm covered with RCC slab filling with salt and charcoal giving
earth connection from electrode copper G.I. strip of 50 mm x 6 mm
x 200 mm length with all accessories and labour charges
complete, as per IS specifications
732/1982 (Part II) for UPS earthing.Complete the work as
directed by the SBIIMS.
No 2
3
Supply & Installation of 25*6 MM
copper flat.Complete the work as directed by the SBIIMS.
Rmt 20
4
Supply &laying of 25 sqmm single
core copper flexible cable.Complete
the work as directed by the SBIIMS. Rmt 15
5
Supply &laying of 25sqmm 3 core copper flexible cable and it should
be laid on a suitable metal house.Complete the work as
directed by the SBIIMS.
rmt 20
6
Supply & Installation of 63Amps 2
pole MCB with enclosure.Complete
the work as directed by the SBIIMS. No 2
TOTAL QUOTED AMOUNT FOR ELECTRICAL WORKS RELATED TO UPS AT GROUND FLOOR OF IA-- PART-C
Signature of The Contractor Page 11 of 14
CMP- GOC UPS RELATED WORKS
1
Supply , laying , Testing and
commissioning of 16 sq mm 4 core copper armoured LT XLPE insulated
PVC sheathed FRLS armoured cable 1.1 KV grade confirming to IS7098
(part-I). The scope of work clamping & dressing of cable. The
complete the work as directed by the Bank. The cable has to be run
from existing Panel & DB of ground & 2nd floor to respective panels.
Complete the work as directed by
the SBIIMS
rmt 40
2
Supply , laying and dressing of
1.1KV XLPE PVC Insulated 16 sqmm 4 core copper flexible cable
and with one run of 16 sqmm single core copper flexible cable for
earthing. The scope of work includes laying of cable in a suitable metal
hose flexible pipe The complete the work as directed by the SBIIMS
engineer.
rmt 45
3
Supply , laying and dressing of 1.1KV XLPE PVC Insulated 16
sqmm 3 core copper flexible cable. The scope of work includes laying of
cable in a suitable metal hose flexible pipe. The complete the work
as directed by the SBIIMS engineer.
No 45
4
Supply, installation and fixing of 100/63 Amps 4 pole 36KV MCCB in
a suitable metal enclosure and necessary arrangement. The
complete the work as directed by
the SBIIMS. (Output of the MCCB will be connected to UPS input).
No 3
Signature of The Contractor Page 12 of 14
5
Supply, installation and fixing of 100Amps 2 pole MCB in a suitable
metal enclosure and necessary arrangement. The complete the
work as directed by the SBIIMS.(Output of UPS will be
connected to the MCB).
No 3
6
Supply , laying , Testing and commissioning of 25 sq mm 3 core
copper armoured LT XLPE Insulated, cores laid up, PVC tape
inner sheathed for Multi core Cables, Armour (Galvanised wire for cables
with galvanised steel strip, extruded PVC Type ST2 Sheathed, 650/1100
V grade as per IS 7098 (Part 1) 1988. The scope of work includes
clamping & dressing of cable and supply & terminations (6) with
double compression glands, canopy
, lugs etc. The complete the work as directed by the SBIIMS. (the cable
has to be lay from ups of ground & first floor to respective DB).
rmt 140
7
Supply, installation and fixing of 100Amps 4 pole 36KV MCCB with
suitable extatence handle it has to be installed inside the distribution
panel. The scope of work extending to power wiring from bas bar to
MCCB & MCCB to Terminals and also supply& fixing of suitable terminals.
The complete the above work as
directed by the SBIIMS engineer. (Output of this MCCB will be
connected to UPS)
no 1
Signature of The Contractor Page 13 of 14
8
Supply, installation, Testing and Commissioning of 3 phase and
neutral 415V, 4 wire, free standing floor mounted M.V panel made out
of 14SWG MS sheet after seven tank process and painting with
epoxy powder coating. The panel shall consist of suitable rating TPN
Copper busbar arrangement (at the rating of 1.5A/ sq.mm) supported
with DMC/ SMC barriers and colour
coded with heat shrinkable sleeves. The panel shall have short circuit
withstanding capacity of minimum 36KA and consist of the following
switchgear one of 250Amp FP 36KA MCCB as incomer and output of
100Amps 4 pole 36KA MCCB-5Nos. Complete the work as directed by
the SBIIMS.
No 1
9
Providing independent earthing for sophisticated electronic equipment
with 600 mm x 600 mm x 3.5 mm thick copper plate rigidly fixed to 40
mm dia G.I. pipe of 3 mtr length connected with reducer providing GI
funnel with wiremesh as per national electric code including C.C.
Chamber of size 400 mm x 400 mm x 400 mm covered with RCC slab
filling with salt and charcoal giving earth connection from electrode
copper strip of 50 mm x 6 mm x 200 mm length with all accessories
and labour charges complete, as per
IS specifications 732/1982 (Part II) for UPS earthing.
no 2
10
Supply and run of 25 mm x 6 mm copper strip including cost of all
accessories and labour charges etc. complete the work as directed by
the SBIIMS.
rmt 12
Signature of The Contractor Page 14 of 14
11
Supply, laying and termination of 25 sqmm single core copper flexible
cable in a suitable PVC conduit from neutral earth pit respective floor
DBs earthing.Complete the work as directed by the SBIIMS.
rmt 54
TOTAL QUOTED AMOUNT FOR ELECTRICAL WORKS RELATED TO UPS OF CMP GOC- PART D
TOTAL QUOTED AMOUNT FOR ELECTRICAL RELATED TO AC & UPS OF 2ND FLOOR OF IA -- PART-A
TOTAL QUOTED AMOUNT FOR ELECTRICAL WORKS RELATED TO
WASHROOMS OF 2ND FLOOR IA- PART B
TOTAL QUOTED AMOUNT FOR ELECTRICAL WORKS RELATED TO UPS
AT GROUND FLOOR OF IA-- PART-C
TOTAL QUOTED AMOUNT FOR ELECTRICAL WORKS RELATED TO UPS OF CMP GOC- PART D
TOTAL QUOTED AMOUNT
DISCOUNTS IF ANY
GRAND TOTAL
Applicable GST as per government norms will be paid by the Bank on actual
amount.
Note: 1) successful bidder has to submit the General Arrangement drawings &
wiring diagram to the SBIIMS for approval, before proceeding to the fabrication.
2) Submit the list components to be used in panel and detailed bill of material
for approval.
3) Submit the 3 sets of Hard copies of the control & power line diagrams along
with soft copies in the form of PDF &Autocad drawings