Download - Tandem Pumping

Transcript
Page 1: Tandem Pumping

Tandem Pumping

Video

Page 2: Tandem Pumping

INITIAL SIZE-UP

• When approaching the structure note the location of the FDC, Hydrant and Building Access.

Page 3: Tandem Pumping

POSITIONING APPARATUS• When spotting

the apparatus for access to the FDC ensure the hose lines will not impede access to the building and angle the apparatus to protect the operator from traffic.

Page 4: Tandem Pumping

CONNECTING TO THE FDC

• The Firefighter stretches the initial line to the FDC, connects the line and removes all caps.

Page 5: Tandem Pumping

CONNECTING TO THE FDC

• The Engineer connects the first line to the discharge and stretches the second line to the FDC.

Page 6: Tandem Pumping

SECURING THE HOSELINES• After the hoses are connected to the apparatus and the

FDC, prior to charging the lines, the Engineer straightens out the hoses to remove any kinks and keep the access to the building free of obstruction. The Engineer then secures the ends of the hose lines to the apparatus and the FDC. Any couplings will have the hoses secured within 10’ on both sides.

• A kit containing four rope loops, four tie ropes two lanyards with clips and a red 2 ½” discharge cap that has a vent hole drilled in it will be issued to each apparatus.

Page 7: Tandem Pumping

SECURING THE HOSELINES• The hoses at the pump panel are secured using a Lanyard with a loop on one end

and a clip on the other. The Lanyard is secured to the pump by wrapping it around a discharge or intake and running the clip end through the loop. It is secured to the hoses using a loop of rope placed around the hose in a hose knot and attached to the clip.

Page 8: Tandem Pumping

SECURING THE HOSELINES

• The hoses are then secured to the FDC with the Lanyard and two rope loops.

Page 9: Tandem Pumping

SECURING THE HOSELINES• If there are couplings between the pump panel and the FDC a

rope will be used to secure the hoses with 10’ on both sides of the coupling. Lay the rope under the hoses, make a round turn on each side and secure with a square knot.

Page 10: Tandem Pumping

SECURING THE HOSELINES• Once the hoses are secured the area surrounding the hoses must be

secured from access by civilians or firefighters due to the high pressures. Secure an area 25’ on each side of the hoses with Caution or Danger tape.

Page 11: Tandem Pumping

CAPPING THE INTAKE RELIEF VALVE(2006 PIERCE SHOWN)

• Prior to establishing a supply, cap the Front Suction Intake Relief Valve on 2006 Pierce and the Pump Intake Relief Valve on H&W’s. A cap equipped with a vent hole or bleeder valve must be used.

Page 12: Tandem Pumping

SUPPLY• The Third In Engine will connect to the FDC and the Fourth In

Engine will supply the Tandem Pumping Evolution through the front suction. All hose lines and connections are to be away from the Engineers.

Page 13: Tandem Pumping

SUPPLY• The Fourth In Engine establishes a supply and charges the line to the third In Engine

with the pump at idle. • The Third In Engine opens the intake and then the discharges to the FDC. Remember

to close the tank to pump valve and crack open the tank fill to bypass 30 - 50 GPM.

Page 14: Tandem Pumping

SECOND SUPPLY• If the Third In Engine must establish a supply prior to

the Fourth In Engine arrival a side suction must be used.

Page 15: Tandem Pumping

SECOND SUPPLY• When the Fourth In Engine arrives it will supply the Third In Engine.

The Third In Engineer will attach the 5” supply hose to the front suction.

Page 16: Tandem Pumping

SECOND SUPPLY• The Fourth In Engine will

connect the 5” supply for the Third In Engine to the large diameter discharge on the right side of the apparatus. Once a supply is established the line will be filled with the pump at idle.

• After the discharge valve is open inform the Engineer of the Third In Engine the supply is ready.

Page 17: Tandem Pumping

SECOND SUPPLY

• Once the supply from the Fourth In Engine is established the Third In Engine Engineer will:

• Bleed all air from the intake.• Slowly open the intake.• Close the first supply.• Confirm with the Engineer of the Fourth In Engine

they are ready for Tandem Pumping.• The Fourth In Engine Engineer will then raise the

pump pressure to 200 PSI


Top Related