Download - TouchWin TH Series HMI
TH series HMI User’s manual
Xinje Electronic Co., Ltd.
Preface
Thank you for buying TH series touch screen made by Xinje Electronic Co., Ltd, this manual should be read and understood before doing relative operation.
This manual will guide readers in the correct operating and maintaining TH series touch screen. Also, this manual refers to the application situations, operations, transportation, storage, set up, installation, maintaining and so on.
This manual mainly contains three parts: hardware, software, application.
下面的内容只针对 TP 系列产品。 Please read this manual very carefully before operation and please do the correct operations while paying close attention to all the safty points.The following contents only used for TP series touch screen.
Hardware Part: contain the characteristics, specifications, dimensions, installations and communication connecting of TH series.
Software Part: introduce how to use the edit software. Application Part: illustrate the examples; make users to know TH better.
This manual is fit for following personnel:
End Users Engineers Technicians
Please read the safety notes carefully before using the products.
Purpose
Personnel
Contact us
If you have any questions, please contact us use the following methods: Tel: 86 510 85129136-221 Fax: 86 510 85111290 Address: 4th Floor, Building 7, Original Industrial Park, No.100 Dicui Road,
Wuxi, Jiangsu province, China
Safety caution
Please read the manual carefully before using. Make sure your operation is correct and safety. The following contents are only aimed at TH series products. Please keep the manual properly, put in the location easy to get and read, hand the manual to the end users.
Please do not bundle power line with communication cable or let them too close,
keep at least 10cm.
Please do not install module or change the wire. Otherwise it may cause
malfunction, error action, damage or fire.
Please shut off the power when there is abnormal smell or voice in TH products.
(The short sound made by buzzer after power on is normal)
Do not strike the touch panel with a hard or sharp object, or press on the touch
panel with too much force or with pen, screw, since it may damage the touch panel
and cause damage.
Please tighten the screws when install the products to prevent from falling off.
Please transport, store, set up, install and maintain the products correctly, otherwise
the touch panel may be damaged.
Confirm the rated voltage of TH and connect correct before power on.
Please do not touch the terminals after power on to avoid electric shock.
Please do not open the cover board.
Please cut off all the power when installing or disassembling the products, or it
may cause error action and malfunction.
Please use TH touch screen in suitable environment conditions according to
instructions, otherwise it may cause accident.
Please do not use the products where there is high frequency radiate, high magnetic
field or other interferences.
DANGERS
NOTICE
Catalog Preface............................................................................................................................................... 3 Safety caution .................................................................................................................................... 4 1. Summarize .................................................................................................................................... 7
1.1 Performance characteristics ................................................................................................ 7 1.2 Work flow............................................................................................................................ 8
2. General specification..................................................................................................................... 9 2.1 TH465 ............................................................................................................................... 10 2.2 TH765 ............................................................................................................................... 11 2.3 TH865 ............................................................................................................................... 12 2.4 THA62 .............................................................................................................................. 13 2.5 THA65 .............................................................................................................................. 14
3. Hardware ..................................................................................................................................... 15 3.1 Hardware structure ............................................................................................................ 15 3.2 Dimension ......................................................................................................................... 16 3.3 Installation and using environment ................................................................................... 18
4. Interface and switch ...................................................................................................................... 1 4.1 Introduction ......................................................................................................................... 1 4.2 DIP switch ........................................................................................................................... 1 4.3 COM1/COM2 port .............................................................................................................. 2 4.4 USB-A port ......................................................................................................................... 4 4.5 USB-B port ......................................................................................................................... 5
5. Touchwin software ........................................................................................................................ 6 5.1 Preparation .......................................................................................................................... 6 5.2 The construction of Touchwin ............................................................................................. 7 5.3 Project bar ........................................................................................................................... 7
5.3.1 Screen ....................................................................................................................... 7 5.3.2 Window .................................................................................................................... 8
5.4 Menu ................................................................................................................................... 9 5.4.1 File ........................................................................................................................... 9 5.4.2 Edit ......................................................................................................................... 13 5.4.3 View ....................................................................................................................... 13 5.4.4 Part ......................................................................................................................... 14 5.4.5 Tool ........................................................................................................................ 14 5.4.6 Window .................................................................................................................. 15 5.4.7 Help ........................................................................................................................ 15
5.5 Screen editing area ............................................................................................................ 15 5.6 Tool bar ............................................................................................................................. 15
6. Make a simple project ................................................................................................................. 19 6.1 Build a new project ........................................................................................................... 19 6.2 Make a simple project ....................................................................................................... 20 6.3 Simulate offline ................................................................................................................. 22 6.4 Simulate online ................................................................................................................. 23
6.5 Download the project ........................................................................................................ 24 7. Application .................................................................................................................................. 25
7.1 Adjust the touch area ......................................................................................................... 25 7.2 Picture application............................................................................................................. 27 7.3 Debug download ............................................................................................................... 30 7.4 Data backup (Touchwin version≥2.C.3) .......................................................................... 31
7.4.1 Data export ............................................................................................................. 31 7.4.2 Import the CSV data ............................................................................................... 41
8. TH series touch screen interior objects ....................................................................................... 49 Appendix 1 TH series HMI configuration table .............................................................................. 52
1. Summarize
Xinje new touch screen TH series are based on TP series products. It not only has the language, characters editing, data display, monitor and alarm functions but also has 65536 true color LCD which can bring you brand-new vision enjoyment. It has the advantage of large capability for data duplication and friendly user interface. It provides perfect humanized solution for industrial system, make it easy to control the system. The function compare between TP and TH:
Series
Function compare
Colors Font
setting
3D
picture
library
Adjust the
touch area Animation Password
Two ports
communication
independently
USB data
download
USB data
duplication
TP 256 √ 〇 〇 √ √ √ 〇 〇
TH 65536 √ √ √ √ √ √ √ √
1.1 Performance characteristics
LCD size: 4.7”, 7”, 8”, 10.1”, 10.4”. Rich colors: 65536 TFT true color, support BMP, JPG format, display more lively. Adjust function for touch screen. Support multinational language: Chinese, English, Japanese, Korean. Define the font as you
like, support underline, italic, bold, shadow and other art words. Large picture library, with preloading mode, no delay for screen motion. Switch control, dynamic monitor and display data, bar map, real time trend map, time trend
map, XY trend map, discrete/continue column map, real time alarm, history alarm record… User-defined data collection and saving function Set user’s authority, 9 levels password protection Simulate online/offline, upload/download data, configuration function USB port inside, connect flash disk to realize data duplication function, speed 480Mbps Special USB-B port for data download, make the data transfer faster User-defined animation track design
Display
Control
Two ports communication independently, can connect two different devices at the same time Drive the panel printer directly, economical and flexible Support free format communication, user edits the driver program
1.2 Work flow
The work flow of using TH:
NOTICE:
Communication
Edit your project
Connect PC and TH, power on
Download project in TH
Connect TH with other devices
Realize communication and data transmission
Do simulate offline Simulate the TH action in the software.
Do simulate online Connect the PC with TH, simulate the action in your PC
Install edit software TouchWin
Please use Touchwin V2.C and later version to edit your TH project.
2. General specification
This chapter will introduce the specification of TH series touch screen. TH series touch screen contains TH465, TH765, TH865, THA62 and THA65.
Series TH465 TH765-M TH765-N TH865 THA65 THA62
Type TH465-MT TH765-MT TH765-NT TH865-MT THA65-MT THA62-MT TH465-UT TH765-UT TH765-NU TH865-UT THA65-UT THA62-UT TH465-ET TH765-ET TH765-NE TH865-ET THA65-ET THA62-ET
2.1 TH465
Notes: The interfaces of each type please refer to appendix 1.
Item TH465
Electrical
Input voltage DC20-DC28V Consumption current 130mA Momentary power off allowance
Less than 10ms
Withstand voltage AC1000V-10mA 1 minute ( signal and time ) Insulated impedance DC500V- about 10MΩ ( signal and time )
Interface
COM2 Support RS-232/RS422/RS485 USB1 USB-A ( accord with USB2.0 ) USB2 USB-B ( accord with USB2.0 ) Ethernet port RJ-45
Environment
Environment temperature
20-85% ( no condensation )
Operation temperature 0-50℃ Reserve temperature -20-60℃ Withstand oscillation 10-25Hz ( X, Y, Z each direction 30 minutes 2G ) Anti-jamming Voltage noise: 1000Vp-p, pulse 1us, 1 minute Surrounding air No corrosive gas Protection construction IP65
Screen specification
Use life More than 50000 hours, 24 hours running when surrounding temperature is 25 ℃
Type 65536 true colors Screen size 4.3 inch Resolution 480*272 Contrast Non-adjustable Character Chinese, English, Korean, Japanese… Character size Any size and font Touch panel 4-wire resistance mode
Memory Screen 8MB
Construction
Mounting dimension 144.0*94.0mm Exterior dimension 152.0*102.0*41.8mm Cooling method Natural air cooling
2.2 TH765
Notes: The interfaces of each type please refer to appendix 1.
Item TH765
Electrical
Input voltage DC20-DC28V Consumption current 250mA Momentary power off allowance
Less than 10ms
Withstand voltage AC1000V-10mA 1 minute ( signal and time ) Insulated impedance DC500V- about 10MΩ ( signal and time )
Interface
COM1 Support RS-232/RS-485 COM2 Support RS-232/RS422/RS485 USB1 USB-A ( accord with USB2.0 ) USB2 USB-B ( accord with USB2.0 ) Ethernet port RJ-45
Environment
Operation temperature 0-50℃ Reserve temperature -20-60℃ Environment temperature
20-85% ( no condensation )
Withstand oscillation 10-25Hz ( X, Y, Z each direction 30 minutes 2G ) Anti-jamming Voltage noise: 1000Vp-p, pulse 1us, 1 minute Surrounding air No corrosive gas Protection construction IP65
Screen specification
Type 65536 true colors Screen size 7 inch Use life More than 50000 hours, 24 hours running when surrounding
temperature is 25 ℃ Resolution 800*480 Contrast Non-adjustable Character Chinese, English, Korean, Japanese… Character size Any size and font Touch panel 4-wire resistance mode
Memory Screen 128MB
Construction
Cooling method Natural air cooling Exterior dimension 204.0*150.5*43.9mm Mounting dimension 192.0*138.5mm
2.3 TH865
Notes: The interfaces of each type please refer to appendix 1.
Item TH865
Electrical
Input voltage DC20-DC28V Consumption current 260mA Momentary power off allowance
Less than 10ms
Withstand voltage AC1000V-10mA 1 minute ( signal and time ) Insulated impedance DC500V- about 10MΩ ( signal and time )
Interface
COM1 Support RS-232/RS-485 COM2 Support RS-232/RS422/RS485 USB1 USB-A ( accord with USB2.0 ) USB2 USB-A ( accord with USB2.0 ) USB3 USB-B ( accord with USB2.0 ) Ethernet port RJ-45
Environment
Operation temperature 0-50℃ Reserve temperature -20-60℃ Environment temperature
20-85% ( no condensation )
Withstand oscillation 10-25Hz ( X, Y, Z each direction 30 minutes 2G ) Anti-jamming Voltage noise: 1000Vp-p, pulse 1us, 1 minute Surrounding air No corrosive gas Protection construction IP65
Screen specification
Type 65536 true colors Screen size 8 inch Use life More than 50000 hours, 24 hours running when surrounding
temperature is 25 ℃ Resolution 800*600 Contrast Non-adjustable Character Chinese, English, Korean, Japanese… Character size Any size and font Touch panel 4-wire resistance mode
Memory Screen 128MB
Construction
Cooling method Natural air cooling Exterior dimension 224.4*170.8*45.5mm Mounting dimension 211.4*157.8mm
2.4 THA62
Notes: The interfaces of each type please refer to appendix 1.
Item THA62
Electrical
Input voltage DC20-DC28V Consumption current 230mA Momentary power off allowance
Less than 10ms
Withstand voltage AC1000V-10mA 1 minute ( signal and time ) Insulated impedance DC500V- about 10MΩ ( signal and time )
Interface
COM1 Support RS-232/RS-485 COM2 Support RS-232/RS422/RS485 USB1 USB-A ( accord with USB2.0 ) USB2 USB-A ( accord with USB2.0 ) USB3 USB-B ( accord with USB2.0 ) Ethernet port RJ-45
Environment
Operation temperature 0-50℃ Reserve temperature -20-60℃ Environment temperature
20-85% ( no condensation )
Withstand oscillation 10-25Hz ( X, Y, Z each direction 30 minutes 2G ) Anti-jamming Voltage noise: 1000Vp-p, pulse 1us, 1 minute Surrounding air No corrosive gas Protection construction IP65
Screen specification
Type 65536 true colors Screen size 10.1 inch Use life More than 50000 hours, 24 hours running when surrounding
temperature is 25 ℃ Resolution 800*480 Contrast Non-adjustable Character Chinese, English, Korean, Japanese… Character size Any size and font Touch panel 4-wire resistance mode
Memory Screen 128MB
Construction
Cooling method Natural air cooling Exterior dimension 272.2*191.7*51.2mm Mounting dimension 260.2*179.7mm
2.5 THA65
Notes: The interfaces of each type please refer to appendix 1.
Item THA65
Electrical
Input voltage DC20-DC28V Consumption current 630mA Momentary power off allowance
Less than 10ms
Withstand voltage AC1000V-10mA 1 minute ( signal and time ) Insulated impedance DC500V- about 10MΩ ( signal and time )
Interface
COM1 Support RS-232/RS-485 COM2 Support RS-232/RS422/RS485 USB1 USB-A ( accord with USB2.0 ) USB2 USB-A ( accord with USB2.0 ) USB3 USB-B ( accord with USB2.0 ) Ethernet port RJ-45
Environment
Operation temperature 0-50℃ Reserve temperature -20-60℃ Environment temperature
20-85% ( no condensation )
Withstand oscillation 10-25Hz ( X, Y, Z each direction 30 minutes 2G ) Anti-jamming Voltage noise: 1000Vp-p, pulse 1us, 1 minute Surrounding air No corrosive gas Protection construction IP65
Screen specification
Type 65536 true colors Screen size 10.4 inch Use life More than 50000 hours, 24 hours running when surrounding
temperature is 25 ℃ Resolution 800*600 Contrast Non-adjustable Character Chinese, English, Korean, Japanese… Character size Any size and font Touch panel 4-wire resistance mode
Memory Screen 128MB
Construction
Cooling method Natural air cooling Exterior dimension 311.0*234.0*48.0mm Mounting dimension 302.0*225.0mm
3. Hardware
3.1 Hardware structure
The hardware structure of TH series touch screen includes front and back side. Take TH765-ET as an example to explain the structure.
1 2 3 4
24V 0V FG1 2 3 4
COM1 COM2
THINGET
Xinje Electronic Co.,Ltd
Touch screen
Label
Power supply
COM1 COM2
USB-B
DIP switch
RJ-45
PWR LED
USB-A
3.2 Dimension
TH465 (unit: mm)
1 2 3 4
92.0
142.0
41.8 152.0
102.0
144.0
94.0
PLC 1 2 3 4
24V 0V FG
TH765-M/TH765-N (unit: mm)
1 2 3 4
24V 0V FG1 2 3 4
COM1 COM2
MODE: TW760T
S/ N: N20081028028
THINGET
Xinje Electronic Co.,Ltd
43.97.0 204.0
150.
5
136.5
190.0
138.5
192.0
TH865 (unit: mm)
1 2 3 4
1 2 3 4
Download PLC
24V 0V FG
224.4
170.8
38.045.5
155.8
209.4 211.4
157.
8
THA62 (unit: mm)
Download PLC
24V 0V FG
1 2 3 4
272.2
191
.7
51.2
258.2
177
.7
260.2
179
.7
THA65 (unit: mm)
+24V0VFG
311.0
234.0
48.022
3.0
43.1 300.0
1234
302.0
225.0
3.3 Installation and using environment
1. Install requirements: TH has four ferric mounting racks when out of factory, there are two square holes on the up, down side of TH, use mounting rack to fix the TH with control cabinet. In order to avoid TH temperature too high after long time working, please keep 10cm space on the up/down and 5cm on the left/right side of the TH when installing.
2. Install steps
Step1 Refer to the dimension in the former chapter to open a rectangle mounting hole in the
control cabinet
Step2 Add airproof circles in the airproof slot when installing
Fixed bracket Install panel
Step3 Insert the bottom of TH into the mounting hole of control cabinet
Step4 Insert the install rack into the fix hole of TH then tighten the screw
Step5 Connect TH and PLC with communication cable
NOTICE:
3. Environment Please use TH series touch screen indoor. Do not use TH in below environment: Inflammable gas, steam, dust, fast vary temperature, high humidity (it may cause moisture inside TH). 4. Power supply requirements: TH series touch screen use DC +24V power supply only. The permitted voltage range is 20V~28V. The connection is as below: Besides, if connect high voltage or AC power supply with TH, the TH may be damaged and cause electric shock to human body. NOTE: if use the DC +24V output of PLC to drive the TH, make sure the PLC has enough current to drive the TH. 5. Maintenance and cleaning Please do not open the back cover by yourself. Please do not analyze or change TH by yourself Please cut off all the power supply while observing the TH.
The communication cable can be offered by the supplier or made by user according to the connection diagram, input +24V DC power to start working
+24V 0 V
+DC-
Caution
Maintenance
Please do not touch terminals after power on, otherwise it may cause electric shock. Do not hot plug the cable or pull the cable when communicating, it may destroy the cable. Please periodic check installation and screws to avoid falling off. Please use TH series touch screen in the certain conditions according to instructions. Keep the cleanness of touch area, in order to keep touch sensitivity. Please use clean cloths with little detergent or alcohol to clean the screen. Neutral detergent, without acid, alkali is recommended. Keep the TH away from thrill or strong corrosive gas Never use spray detergent. Avoid damage to the screen, please do not touch the screen too hard while wiping. ● Please dispose the TH as industry waste.
Clean
Caution
Disposal
Caution
4. Interface and switch
4.1 Introduction
TH series HMI ports:
Outline Name Function
1 2 3 4
1 2 3 4 DIP switch Force-download, touch area adjustment
Download COM1 RS232/RS485 communication
PLC COM2 RS232/RS485/RS422 communication
USB-A Connect to U disk
USB-B Connect USB cable to download/upload program
RJ-45 HMI remote assistance, make network between
HMI and controller, data exchange between HMIs
4.2 DIP switch
TH series has 4-bit DIP switch at the back side; they can set the function of COM1 port. Switch Switch1 Switch2 Switch3 Switch4 Function
State
ON OFF OFF OFF Undefined OFF ON OFF OFF Force-download mode of USB-B port OFF OFF ON OFF Adjust mode of touch area OFF OFF OFF ON Interior check mode ( not recommended to users)
Notes: Force-download: if the screen cannot show normally after downloading the program, please use force-download to update the system. Force-download method:
(1) Cut off the power of TH, turn ON DIP switch 2. (2) Power on TH, connect the download cable to PC to download the program. (3) Turn OFF DIP switch 2 after finishing the download, repower on the TH.
4.3 COM1/COM2 port
TH series HMI COM1/COM2 port has these functions: COM1 pins definition
12345
6789
COM2 pins definition:
12345
6789
Communication function: connect to PLC, printer, inverter, meter…
(1) Communicate with PLC TH series HMI can communicate with most of popular PLCs
Receive data
Send data
Inverter
PLC TH series HMI
Com port Other devices
Pin Name Meaning 1 NC Unused terminal 2 RXD RS232 receive 3 TXD RS232 send 4 A RS485 + signal 5 GND Signal ground 6 NC Unused terminal 7 B RS485 – signal 8 NC Unused terminal 9 NC Unused terminal
pins Name Meaning 1 TD+ RS422 send + 2 RXD RS232 receive 3 TXD RS232 send 4 A RS485 + 5 GND Signal ground 6 TD- RS422 send - 7 B RS485 - 8 RDD- RS422 receive - 9 RDD+ RS422 receive +
Please select correct PLC port (COM2) device and communication parameters:
COM2 device selection COM2 communication parameters Select the correct download port (COM1) device and communication parameters:
COM1 communication parameters COM1 device selection
Please refer to “TP series basic manual” for the details of TH communicate with PLC.
(2) Communicate with inverter TH can communicate with various brands of frequency inverters. For the brands which are not in the
Data transfer
TH series
COM port
SIEMENS PLC
Panasonic PLC
Other PLCs…
list, user can select Modbus protocol or user-defined protocol.
Please refer to “TP series basic manual” for the details of TH communicating with frequency inverter.
(3) Communicate with meters About the communication between TH and meters, users can select user-defined protocol or Modbus protocol.
Please refer to “TP series basic manual” for the details of TH communicating with meters.
4.4 USB-A port
TH series USB-A port has below functions: (accord with USB2.0) Realize backup management, data export/import, the speed can up to 480 Mbps. USB-A port definition
Connect to U-disk
COM port
TH Mitsubishi FR series inverter
Inovance MD series inverter
Bosch Rexroth Indracontrol L40
TH front side TH back side
USB-A
USB-A port
Pins Name Meaning 1 +5V +5V voltage signal 2 DATA+ Data signal + 3 DATA- Data signal - 4 -5V -5V voltage signal
4.5 USB-B port
TH has one USB-B port (accord with USB2.0), located at the back side of TH, the functions are shown as below: To download the data, the speed can up to 480Mbps. USB-B port definition:
Notes: 1. Please use shielded USB cables.
2. Please install USB driver before using. Download the driver from www.xinje.com . 3. Connect TH with PC, open Touchwin software, click to download the program.
TH back side
PC USB cable
Pins Name Meaning 1 +5V +5V voltage signal 2 DATA- Data signal - 3 DATA+ Data signal + 4 GND Ground signal
5. Touchwin software
5.1 Preparation
1. Software version: V2.C and later versions. 2. Software source: visit Xinje website www.xinje.com to obtain the software or get from the products CD. 3. OS requirements: Windows98/2000/XP/ME/7 4. Install steps:
Open setup.exe
Click “next” until show below window
Enter the information in the space: serial number is ThingetTouchWin.
click to use the software.
Click “next” to finish your installation.
5.2 The construction of Touchwin
Double click the Touchwin software, build a new project, then you can see the following screen:
a. Project bar: build, delete, copy, cut operation of the screen and window b. Screen edit area: make the project in this area c. Menu: it includes file, edit, view, tool, part, window and help. d. Element bar: it includes standard, part, panel, operate, status, zoom, draw and align. e. Status bar: it includes HMI type, PLC port device and download port device.
5.3 Project bar
5.3.1 Screen
1. build a new screen
Method 1: click in the element bar. Method 2: right click the screen in the project bar, then click insert.
Project bar Screen edit area Menu Tool bar Status bar
It shows the following window:
2. screen cut, copy and delete Select the screen in the project bar, right click and choose cut, copy or delete.
5.3.2 Window
1. build a window Right click the window/insert in the project bar. Input the window ID, name and message.
2. window cut, copy, delete Select the window in the project bar, right click to select cut, copy or delete window.
ID: the number of the screen Name: the name of the screen Message: the description of the screen
Click to modify the screen property.
5.4 Menu
5.4.1 File
The file menu is shown as the following:
1. New: Build a new file 2. Open: Open a file 3. Close: Close a file 4. Save: Save a file 5. Save as: Save a file as another name and path 6. Download: to download project into TH
7. Run-online: connect PLC and TH, Simulate online in TH software. 8. Run-offline: simulate offline , simulate the touch screen action in the software. 9. PFW set: Initialize the PFW registers when downloading the program. Step1: set the PFW register range, click “Add” to add the register in the list.
Change the range then click “Modify”, it will show below message, click ‘Yes” to confirm.
Step2: set the value in the range Double click the PFW range, it will show data setting window:
Step3: download the project into TH. Please note PFW0~PFW256 are occupied by the TH system, please select register start from PFW257. 10. Setting: (1) Para tab:
Screen: select the start screen number when TH is power on. Password: there are 9 levels passwords; the level 9 password has the highest priority. The higher level
password can be used to all the elements of lower level password. The password is used to protect the element or screen, when input the correct password, the button or screen can be used.
Screen save: to protect the LCD. After certain time, the background light will be off or jump to certain screen. Please note “close LCD” and “show screen” only can be selected one of them.
(2) Alternation tab:
Display number can select decimal or hex. Set FF: set all the data to FFFF. Reset 0: set all the data to 0.
(3)Clock tab:
(4) Panel tab:
(5) Device tab:
Change screen control: Change the screen ID according to the value of the register. Report current screen ID: The current screen ID will show in the register. For example, change screen control D0=1, TH displays No.1 screen, report current screen ID D1=1.
Export the current time to the register. For example, object D0, so the real time will save in D0~D5. D0=year, D1=month, D2=day, D3=hour, D4=minute, D5=second. Please note the export time is hex number.
The TH type you are using now. Set parameter: Modify the quantity of PFW and PSW registers.
Set the PFW register quantity Set the PSB register quantity VisPSW Num: the PSW quantity in data input, data display area. PriPSW Num: the PSW quantity in history trend map, real time trend map area. Cache num: PFW register quantity
(6) Font:
(7) Project tab:
11. Build SCADA It realizes the SCADA function in windows. Build the SCADA file, and double click it to simulate online.
Please refer to the chapter “make a project/simulate online “. 12. Last The latest files operated by the user. 13. Exit Quit the Touchwin software.
Single, host net, slave net: TH communication mode. PLC port: TH PLC port connects device type, change the communication parameters by Download port: TH download port connects device type, change the communication parameters by
Set the font of the letter in the screen.
Record the project name, author and remark.
5.4.2 Edit
1. cut, copy, paste, undo These operations are used to the elements in the screen.
2. replace
3. public unit Select one element in the screen, click public unit, this element will be added in all the screens.
4. private unit After select one element as public unit, click private unit to delete this element in other screens.
5.4.3 View
Cut, copy, paste, undo Public unit, private unit
Replace register or coil Find what: the object you want to replace Replace with: the new object Object num: the quantity you want to replace Replace in: replace the object in current screen or all the screens.
Display all the tool bars. Advance and advance2 is gray color. Only when open the advance function of software, these items can be used. All the items with tick are displayed in the software menu.
5.4.4 Part
5.4.5 Tool
Option:
The “part” is used to edit the TH project, it is the same as the tool bar in the software.
Tool menu is the same as the following tool bar.
Grid size: Move Grid: set the min pixel when moving the element. Grid radio: the grid density, the smaller the value is, the denser the grid is. Auto save: auto save the project at the time you set. Download: select the project download com port. Download all: when you want to upload the data, please select this item before you download the data into TH. Display mouse cursor: display the mouse connected to TH USB port.
5.4.6 Window
5.4.7 Help
5.5 Screen editing area
Edit the project in the screen.
5.6 Tool bar
Tool bars functions are shown as the following:
Icon Name Function
New Build a new project Open Open the file Save Save the file
Cut Cut the element
Copy Copy the element
Paste Paste the element
Undo Undo the operation
New: build a new window Cascade: show all the window in cascade mode. Tile: show all the window in tiled mode. Arrange icon: arrange all the icons again.
Show the Touchwin software version and copyright.
Zoom in, zoom out the screen:
zoom out, zoom in
show the grid in the screen.
Help Check the software version information
Text Input static text
Dynamic text Display the text according to the value of register, support 16 texts, set register value as 0~15
Variational text Display the text according to the value of register, set register value as user need
Lamp Display the ON/OFF state of switch
Button ON/OFF the bit element
Lamp button Combine the function of lamp and button
Screen jump Jump to object screen
Digital display Display the register value
Alarm display Set the upper/lower limit of register value, when exceeding the range, twinkle display
Text display Display characters in multi-registers
Digital input Input the data in the register
Text input Input characters in the register
Set data Set data and used in arithmetic
Digital keyboard Digital input keyboard
ASCII keyboard Character input keyboard
User input One input button of keyboard
Bar Display the register value in bar picture
Dynamic map Display the map according to the register value, support 16 maps, the register value is 0~15
Call window Call window according to the value in the coil or register
Window button Control the open, close of the window
Download recipe Download the recipe into object device
Upload recipe Upload the recipe into TH register
Function button Realize multi-functions with this button
Function field Similar to function button, but the trigger condition is different.
Discrete column map Display the data in discrete column map
Continue column map Display the data in continue column map
Line Draw lines
Arc Draw arc
Rectangle Draw rectangle
Ellipse Draw ellipse
Fold/polygon Draw fold and polygon
Polygon block Similar to container
Frame Draw 3D rectangle
Map Add jpg or bmp format pictures
Move animation make the movement animation of object
Rotate animation Switch the picture
Material library The picture library
Date Display the date
Clock Display the time
Buzzer Control the buzzer by the coil
LCD light control Control the background light by the coil
Scale Display the value in scale
Instrument Display the value in the meter
Valve Simulate the state of valve
Pipe Simulate the liquid state in the pipe
Pump Simulate the pump running
Auto wind Simulate the auto wind
Motor Simulate the motor running
Retort Simulate the retort running
Inverter alarm
information Display the inverter alarm information
Scroll text Display the text in scroll mode
Real time map Display the current value in curve
History data map Display the current and history value in curve
XY curve Display two curve in X, Y direction
XY curve Ex Display the value in line, point and line-point.
Time trend control Display value in certain time space
Data moving button Use with event, curve, alarm event, realize flip, confirm and clear operation
Alarm list Show the inverter alarm information in the list
Display real time event Display real time alarm information, when the alarm is free, the event will be deleted automatically
Display history event Display many alarm information and event happen time
Common grid control Display a group of register in the table
Data grid control Display a group of register in the table, support time
information table
Sample save To collect the object data, no limit for the sample quantity and time, save the data in TH registers
Sample export Save the data in TH register and export to object device as CSV format file
Align left Align left the objects
Align center Align center the objects
Align right Align right the objects
Align top Align top the objects
Align middle Align middle the objects
Align bottom Align bottom the objects
Zoom out Zoom out the screen
Zoom percent Zoom percent
Zoom in Zoom in the screen
Grid Display grid in the screen
State change Switch button state display
Dynamic picture state selection Switch dynamic picture state display
Public unit Use the unit in all the screens
Private unit Use the unit in appointed screen
New Build a new screen
Property Screen name, author, remark…
delete Delete the current screen
Simulate offline Simulate the project in the TH
Simulate online Connect PLC and TH, simulate the project in TH online
Download Download the project in the TH
Upload Upload the project from TH to PC
Debug download Debug download
6. Make a simple project
In this chapter, make a switch to control the PLC output, in order to explain how to make TH project.
NOTE:
6.1 Build a new project
(1) Open the Touchwin software.
(2) Click File/New or to build a new project. (3) Select the correct TH type and com port device type
TH type com port device type
(4) Set the com port device communication parameters according to PLC port device
Please make sure the TH type and communication device type; it is important for the project download and device communication.
(5) When download port (COM1) is not used as communication port, please select unuse download port. When use COM1 as com port, please select communication device.
(6) Finish the building process.
(7) Click to save the project in the PC.
6.2 Make a simple project
Make a button on the screen, to control the Y0 output of Xinje XC series PLC.
PLC output Y0 is ON
Lamp
Button
Lamp
Button
TH HMI
PLC COM port
Y1 Y0
PLC output Y0 is OFF
Set ON
Set OFF Y1 Y0
● Make button
(1) click , put the button on the screen. Change the object to Y0.
(2) select operate tab, change the button operate to reverse.
(3) select button tab, change the text to reverse
(4) select the color tab, change the button colors
● make the lamp
(1) click , put it on the screen, change the object to Y0.
(2) select the lamp tab, change the aspect of the lamp.
(2) select the twinkle tab, change the lamp state to stop twinkle.
(3) color and position tab are similar to the button.
6.3 Simulate offline
Do not have to download the project into the TH, you can simulate the project in the Touchwin software. It can save debug time and easy to edit.
(1) click to enter simulate offline screen.
(2) click the reverse button to see the ON/OFF switching of the lamp.
Turn off the reverse button turn on the reverse button
Thus, the simulate operation is finished.
6.4 Simulate online
By connecting the PLC and PC, it can read the data from PLC, simulate the operate of TH in touchwin software. Do not have to download the project into TH, you can control the PLC in your PC. Make sure the connection is correct between PLC and PC, the com port setting is right.
(1) connect Xinje PLC with the PC via serial port.
(2) click the to enter simulate online. It will show below message:
It means the simulate online is not registered, you only can use it for 2 hours. If you want to use it longer, please contact Xinje company to get register number. (3) click ok to enter simulate online screen. Right click the screen to show below menu:
Log: log on time and history record About: the version information of autowin Com port: the serial port number of your PC which is connected with PLC. Register: register to get user right. Exit: exit the autowin. If showing the following message, it means the connection between PLC and PC is not good, or the serial port number is wrong.
In this example, we use TH PLC port and PC serial com port3, so select PLC port com 3.
NOTE: only Xinje PLC support the simulate online function with TH.
(4) click the button to see the lamp ON/OFF.
Turn off the reverse button turn on the reverse button
When click the reverse button, the PLC output Y0 will switch ON/OFF at the same time.
6.5 Download the project
1. Install the USB driver, users can get it on www.xinje.com .
2. Connect TH USB-B port and PC with USB cable, power on the TH, click to download the project.
7. Application
7.1 Adjust the touch area
The touch area adjustment function can make the component touch more precise. The adjustment steps: Step 1: turn on the DIP switch 3, then power on the TH again, it will show the following screen:
Step2: After clicking the cross center, the adjust cross will jump to the second position. Keep on click the cross until the cross jump to the last position 5. Step 3: Please see the detailed motion:
Adjust cross
● Click the center of the adjust cross ● Turn on switch 3
OFF
ON
21 3 4 Calibrate the touch panelRepeat as the target moves around the screen
Calibrate the touch panelRepeat as the target moves around the screen
1
2
3
4
5
Step 4: When finished the adjustment, the result is as the following;
Adjustment process is end. Adjustment process is failed. Please do again.
Repeat as the target moves around the screenCalibrate the touch panel
Repeat as the target moves around the screenCalibrate the touch panel
Calibrate the touch panelRepeat as the target moves around the screen
Calibrate the touch panelRepeat as the target moves around the screen
Calibrate the touch panelRepeat as the target moves around the screen
Calibrate the touch panelRepeat as the target moves around the screen
Calibrate the touch panelRepeat as the target moves around the screen
(1)click the center of the cross (2)click the center of the cross on the top left
(3)click the center of the cross on the left bottom
(4)click the center of the cross on the right bottom
(5)click the center of the cross on the top left to finish the adjust process.
If the adjustment process is end, please turn off the power of TH, then turn off the DIP switch 3, then turn on the power again. Now you can use TH normally.
7.2 Picture application
TH series LCD are 65536 true colors, it can make your picture display more vividly. This example will make the picture moving in parallel. Step1: select the picture
Click button in the tool bar to open the material library:
Select the picture you want, then click “open” button
Step2: design the motion track
Click the button in the tool bar, drag your mouse to draw the motion track, double click the mouse to finish the drawing. Please see the drawing:
Step3: combine the picture with the motion track Drag your mouse to select the picture and the motion track, then right click the mouse, select “group”.
Step4: Simulate offline Click to simulate offline your project. You can see the picture motion track. Step5: Change the animation property Right click the picture, then select “animal prop”.
The animation property includes coordinate and control. (1) Coordinate
a. X: the position on X axis b. Y: the position on Y axis c. Escape time: the time that the photo moves from (X1,Y1) to (X2,Y2) d. Key point X,Y: the coordinate of every motion position
You can click the X, Y position and the escape time in the list and modify them. (2) Control
Enable: control the animation by bit signal. When the rising edge of the signal is coming, the
animation will be activated. Reset: control the end of the animation by bit signal. When the rising edge of the signal is coming, the
animation will end. Repeat: repeat the motion of the animation.
7.3 Debug download
TH series touch screen support debug download function. This function can be used when you are debugging your project in order to save your time. Compared with normal download function, this function has the following advantages:
Click button in the tool bar to debug download the project into your TH.
(1) This function only can be used when debugging the project. (2) The data transfer speed is faster than normal download, save time and cost.
7.4 Data backup (Touchwin version≥2.C.3)
Data backup includes the following contents:
About CSV file: The CSV file is based on Excel, the format is as the following:
To build CSV file Open Excel, input the data as the up format, then save as CSV file.
7.4.1 Data export
Export the data from TH to other device.
Step1: click function button or function field , select “export CSV data” and add it.
When using function button, please select “pressing” or “releasing” as the trigger condition.
Temperature Pressure Hydraulic pressure
Date Time
30 35 40 2009-8-10 12:10:10 40 45 50 2009-8-12 12:10:45 50 55 60 2009-8-14 12:10:23
Title
Data
Data Date Time
(1) Data collection and export, store the data of TH series HMI into U disk, produce CSV data base file. (2) Import CSV data, transfer the data of U disk to TH series HMI.
When using function field, please select the trigger condition as you need.
Step 2: Double click “export CSV data”, it shows the following window: This window includes destination, import, save and date time tab. (1) Destination tab
Length Width Height Qty
20 30 40 1232 41 37 13
Fix name file Length Width Height Qty
20 30 40 12Length Width Height Qty
32 41 37 13 Fix name and re-export title file Name add automatic: it exports a new file when collect the data each time. The new file name will increase automatically. For example, file 1 is TH001.csv, file 2 will be TH002.csv. Please see the following picture:
Device ID: set the object device number which you want to export data, “dynamic set” can connect the D register with the device ID. Path/File: the name of the CSV file Fix name: the data collected each time will be saved in the same file. Re-export title: export the title when collect the data each time Please see the following examples.
Add number after name: add the number after the file name. For example, input 001 , the file name is TH001.csv. Dynamic set: set the number in D register. For example, If D0=20, the file name is TH020, D0=23, the file name is TH023. When “add number after name” and “dynamic set” are both selected, “dynamic set” has priority. Named by date: the file name is added the date. When exporting the data several times at the same day, it will add the data title in the file automatically. For example:
(2) Data tab
● Export the data the first time on 8/18/2009
● Export the data the second time on 8/18/2009
Length Width Height Qty
20 30 40 12Length Width Height Qty
32 41 37 13
Register capacity: import register quantity Register mode: Loop: use with “real trend map”, “history data map”, “time trend control”, “sample save”… Line: export the data in the registers to CSV file. It is used to the recipe and data arrays. Add, delete, move up, move down: Add the data titles, select the export data format and type.
(3) Save tab
(4) Control tab
This tab is used to control the export. Execute status: to show if it is in exporting state via bit state. If the bit is ON, TH is exporting data. Execute result: show the export result state via the register state.
0- export failed 1- export target device does not exist 2- the memory is not enough 3- file path error 4- reading / writing file failed
Execute process: show the exporting process via register, 100 means the exporting process is succeed. (5) Date time
EXAMPLE: This chapter will introduce the data export examples in loop and line mode. <A> Data export in loop mode Purpose: collect the data via history data map, export the data to moveable device and save as CSV file. Please see the whole process:
Export the data
PSW300 value increase 10 every 1 second, use function field to realize it.
Collect data by history data map
Save the data in the registers start from PSW400
Produce CSV file
Collect object is PSW300
Process: Data collection
Data export Produce data source
Save the data in touch screen internal registers.
To add the date in the CSV file. Please select the data format and time format in the pull down menu.
Next, we will introduce the each process: (1) produce the data source: PSW300=PSW300+10 every 1 second:
Open the Touchwin software, click
Please see the TP touch screen manual for this content.
Time
● Data change every 1 second PSW300=PSW300+10 ● PSW data change process: 1 second:PSW300=0; 2 second: PSW300=10; 3 second:PSW300=20; 4 second:PSW300=30;
History data map ● Collect data in loop mode ● Data source: PSW300 ● Save object: registers start from PSW400
● Data export to the registers start from PSW400
● Produce CSV format file
Value
Function filed
Select time: 1 second
Add the arithmetic PSW300=PSW300+10
(2) data collect: use history data map to collect the data every 1 second, use PSB300 to control if it is need to collect.
Click ,add it in the screen, change the “trend source” tab.
Next, change the display tab: page data is 5, control is PSB300.
Change the save tab: save the data in the registers start from PSW400.
Add a button, to control the stop and start of the collection process. The button is related to PSB300.
Page data:5, show 5 numbers each screen Total data:10, it can collect 2 screens data Pick period: 1 second, collect the data every 1 second. Control:PSB300, control the ON/OFF of the data collection by PSB300
(2) Data export
Realize the data export function by function button. Click in the tool bar. Add it on the screen, set the button as the following:
Double click the “export CSV file” to continue the setting:
PSW300+10 every second
PSB300, to control the ON/OFF of data collection
Device ID: 1, there is one U disk device. Path/File: name the file to SJDC.csv, re-export the title.
Data tab
Save tab
Date time tab
Now the data export has been done.
Via the simulate offline, you can monitor the data change and operate the button.
Turn on the button to start the history data map
Click the button to export the data into U disk
Register capacity: 10 Register mode: loop, to correspond to the history trend map Format: decimal
Save the data in PSW400
Date time: export the date and time to the .csv file.
The operation steps: Step 1: make sure the TH is connected to object device. Step 2: click ON/OFF button to start the data collection in history data map Step 3: click the data export button, the U disk device LED starts to flickering, it means the CSV file is being produced, if the LED ends flicker, the export process has been finished. The CSV data is shown as below: <B> Data export in line mode In industry system, HMI is seemed as control and monitor terminal. It can be used to set all kinds of parameters directly. In order to check the history data, use data export function to complete the data management. In this example, using data export function to complete the parameters recording. Purpose: realize parameters setting by data input button, and data export by data export button. The process is shown as below:
Next, we will introduce how to make the project in two parts: Part 1: input the parameters Put the data input button on the screen, change the address as the following:
PSW500 PSW501 PSW502 PSW503 PSW504
● Save in CSV format file
PSW500
PSW501
PSW502
PSW503
PSW504
● Set the head address to PSW500.
Realize by data input button
Data input 1
Data input 2
Data input 3
Data input 4
Data input 5
Realize by function button/export CSV data
Data export button
About the data input button, please refer to TP series HMI manual. Part 2: about data export button
Click function button, then set as the following:
Double click the export CSV data to change the parameters: Destination tab:
Data tab:
Device ID: 1 is the U disk number Change the file name to SJDX.csv, export the data to this file.
Each group of parameters includes 5 values, export 1 group parameter each time, so the register capacity is 1. Register mode is line. Add the title, make it correspond to the parameters.
Save tab
In this example, it has not referred to date and time, so do not have to set them. The screen has been done, please see the following picture:
Run the project, and you will see the following result:
7.4.2 Import the CSV data
The purpose is to import the data from the SD card or U disk to TH register.
Step1: use function button or function field , select import CSV data function.
Set the export object to PSW500, make it the same as the data input button address.
Data input
Data export
Excel file: SJDX.csv
Step2: double click import CSV data, change the parameters as the following: (1) Source path tab
Please see the following picture: the import data when select start ID to 5 and 10.
When the start ID is 0 or 1, the import data is the first group.
Device ID: the device number of import device Dynamic set: set the device ID in D register. Import control: control the import process by M coil, when M is ON, the import process starts. Path/File: the CSV file name Fix name: the import data are from the same source file Add ID after name: set the import file name by the input value or the value in D register. Start ID: the import data head number. Dynamic set: can set the head address in D register.
When start ID is 5, import these data. When start ID is 10, import these data.
(2) Data tab
Please note the title list items must be the same as the CSV file items.
(3) Save tab
(4) Control tab
Execute status: to show if it is in importing state via bit state. If the bit is ON, TH is importing data. Execute result: show the import result state via the register state.
0- import failed 1- import target device does not exist 2- the memory is not enough 3- file path error
Register capacity: the import data group quantity Register mode: Loop: the data will be stored in the object registers in loop mode, so the original data will be covered. Line: the data import to the object register one after another. Add, delete, move up, move down, title….: Add the data title in the list, and select the data format, type, bit length,etc.
There are 4 items in the title list. There are four items in the CSV file.
The import registers address.
4- reading / writing file failed Execute process: show the importing process via register, 100 means the importing process is succeed. (5) Date time tab
Example: Purpose: import the data from object device to TH touch screen, select the import data group by input the start ID. The CSV file in the SD card is SJDR.csv.
In TH touch screen, the data store address starts from PSW400. The realize steps:
Step1: use function button or function field . Set as the following:
Add the date and time in the CSV file. Select the date and time format via the pull down menu.
Step2: build the import data group selection button.
Put a data input button on the screen----- , change the parameters:
Step3: double click “import CSV data”.
Change the object to PSW500 and be constant with the following import data dynamic appoint address.
Device ID: 1 Path/File: SJDR.csv, must be the same as the object import file. Fix name means importing from the same file. Start ID: dynamic appoint PSW500.
Import tab:
Save tab:
Control tab:
Date/time tab:
Step4: show the import data start from PSW400 in “data table” .
Register capacity: 10, it means 10 groups of data Register mode: line Add the title: there are 4 rows of data.
Object: save the data of mobile device into TH register starts from PSW400.
Because the import data has time and date, select this item.
Execute status: PSB300 to show the importing state Execute result: PSW256 to show the importing result Execute process: PSW257 to show the importing process
Change the parameters: Object tab:
Common tab:
Column tab:
The data table is finished, please see the following screen:
The object is PSW400, the same to the data import address.
Set the all records, page records as the left window.
Add the text as the left window. Set the date time item to time format.
Step5: connect the mobile device and TH, click the import data button, monitor the data in “data table”.
● When the import data No = 10, the data table is shown as up.
NO Name Length Width Height Qty Date time 0 Group 1 60 12 10 25 2009-08-10 21:10:10 1 Group 2 60 20 8 35 2009-08-10 22:10:10 2 Group 3 65 10 10 20 2009-08-10 23:10:10 3 Group 4 65 12 5 15 2009-08-10 00:10:10 4 Group 5 65 18 15 15 2009-08-10 10:10:10 5 Group 6 65 20 8 30 2009-08-10 00:10:10 6 Group 7 70 8 8 18 2009-08-10 03:10:10 7 Group 8 70 16 10 18 2009-08-10 04:10:10 8 Group 9 55 20 8 20 2009-08-10 20:10:10 9 Group 10 60 12 10 25 2009-08-10 21:10:10
NO Name Length Width Height Qty Date time 0 Group 1 40 8 10 15 2009-08-10 12:10:10 1 Group 2 40 10 10 18 2009-08-10 13:10:10 2 Group 3 40 15 10 30 2009-08-10 14:10:10 3 Group 4 45 8 6 25 2009-08-10 15:10:10 4 Group 5 45 10 8 20 2009-08-10 16:10:10 5 Group 6 50 10 8 20 2009-08-10 17:10:10 6 Group 7 55 12 10 15 2009-08-10 18:10:10 7 Group 8 55 14 10 30 2009-08-10 19:10:10 8 Group 9 55 20 8 20 2009-08-10 20:10:10 9 Group 10 60 12 10 25 2009-08-10 21:10:10
● When the import data No = 0 or 1, the data table is shown as up.
8. TH series touch screen interior objects
This chapter will introduce the interior objects of the TH. The interior objects contain PSB(bit register), PSW(word register), PFW(word register).
NOTICE 1. Only when the advanced function is opened, the special interior objects can be used. 2. PSB0~PSB255, PSW0~PSW255, PFW0~PFW255 are occupied by system. Bit register PSB
Register Function Remark PSB0 Normally closed coil PSB1 Normally open coil PSB2 Turn on during the first scan period
PSB3 100ms pulse signal O NOFF
50ms
50ms
PSB4 1s pulse signal O NOFF
500m s
500ms
PSB5 1minute pulse signal O NOFF
30s
30s
PSB6 300ms pulse signal O NO FF
150m s
150m s PSB15 Communication failure 0: successful 1: failed PSB16 Succeed to scan the screen once PSB30 First scan after download PSB31 First scan after power on PSB39 Turn off the touch screen PSB60 Level 1 password flag (1: password is opened, 0: password is closed ) PSB61 Level 2 password flag (1: password is opened, 0: password is closed ) PSB62 Level 3 password flag (1: password is opened, 0: password is closed ) PSB63 Level 4 password flag (1: password is opened, 0: password is closed ) PSB64 Level 5 password flag (1: password is opened, 0: password is closed ) PSB65 Level 6 password flag (1: password is opened, 0: password is closed ) PSB66 Level 7 password flag (1: password is opened, 0: password is closed ) PSB67 Level 8 password flag (1: password is opened, 0: password is closed ) PSB68 Level 9 password flag (1: password is opened, 0: password is closed )
Word registers PSW
Register Function Remark PSW0 Start screen No. PSW1 Current screen No.
PSW20 Screen width ( read only ) PSW21 Screen height ( read only ) PSW26 PSB amounts ( read only ) PSW27 PSW amounts ( read only ) PSW28 PFW amounts Occupy PSW28、PSW29 ( read only ) PSW30 Year ( Hex) ( read only ) PSW31 Month ( Hex) ( read only ) PSW32 Day ( Hex) ( read only ) PSW33 Hour ( Hex) ( read only ) PSW34 Minute ( Hex) ( read only ) PSW35 Second ( Hex) ( read only ) PSW36 Week ( Hex) ( read only ) PSW40 Recipe index PSW54 The device quantity PSW60 COM1 communicate successful time PSW61 COM1 communicate failure time PSW62 COM1 communicate overtime time PSW63 COM1 communicate data error time PSW64 COM1 device version PSW65 COM1 device type PSW70 COM2 communicate successful time PSW71 COM2 communicate failure time PSW72 COM2 communicate overtime time PSW73 COM2 communicate data error time PSW74 COM2 device version PSW75 COM2 device type
Word registers PFW
Register Function Remark PFW1 The screen No. after power on PFW2 Background color setting PFW10 Screen saver start time PFW11 the screen number of screen saver PFW20 COM1 baud rate 4800、9600、19200、38400、115200、187500 PFW21 COM1 data bit 7、8 PFW22 COM1 stop bit 0-1 bit, 1-1.5 bits, 2-2 bits PFW23 COM1 CRC 0-None, 1-Odd, 2-Even PFW24 COM1 station NO. PFW25 COM2 send delay Unit : ms PFW30 COM2 baud rate 4800、9600、19200、38400、115200、187500 PFW31 COM2 data bit 7、8 PFW32 COM2 stop bit 0-1 bit, 1-1.5 bits, 2-2 bits PFW33 COM2 CRC 0-None, 1-Odd, 2-Even PFW34 COM2 station NO. PFW35 COM2 send delay Unit: ms PFW60 Level 1 password PFW60、PFW61 PFW62 Level 2 password PFW62、PFW63 PFW64 Level 3 password PFW64、PFW65 PFW66 Level 4 password PFW66、PFW67
PFW68 Level 5 password PFW68、PFW69 PFW70 Level 6 password PFW70、PFW71 PFW72 Level 7 password PFW72、PFW73 PFW74 Level 8 password PFW74、PFW75 PFW76 Level 9 password PFW76、PFW77
Appendix 1 TH series HMI configuration table
Series Type LCD size
Resolution Screen capacity
COM1 COM2 RJ-45 USB-A
Download mode
TH465 TH465-MT 4.3’ 480*272 8MB - 485/42
2/232 - - USB
TH465-UT 4.3’ 480*272 8MB - 485/42
2/232 - One USB
TH465-ET 4.3’ 480*272 8MB - 485/42
2/232 One One USB
TH765-M
TH765-MT 7' 800*480 128MB 232/48
5 485/422/232 - - USB
TH765-UT 7' 800*480 128MB 232/48
5 485/422/232 - One USB
TH765-ET 7' 800*480 128MB 232/48
5 485/422/232 One One USB
TH765-N
TH765-NT 7' 800*480 128MB 232/48
5 485/422/232 - - USB
TH765-NU 7' 800*480 128MB 232/48
5 485/422/232 - One USB
TH765-NE 7' 800*480 128MB 232/48
5 485/422/232 One One USB
TH865 TH865-MT 8' 800*600 128MB 232/48
5 485/422/232 - - USB
TH865-UT 8' 800*600 128MB 232/48
5 485/422/232 - Two USB
TH865-ET 8' 800*600 128MB 232/48
5 485/422/232 One Two USB
THA62 THA62-MT 10.1' 800*480 128MB 232/48
5 485/422/232 - - USB
THA62-UT 10.1' 800*480 128MB 232/48
5 485/422/232 - Two USB
THA62-ET 10.1' 800*480 128MB 232/48
5 485/422/232 One Two USB
THA65 THA65-MT 10.4' 800*600 128MB 232/48
5 485/422/232 - - USB
THA65-UT 10.4' 800*600 128MB 232/48
5 485/422/232 - Two USB
THA65-ET 10.4' 800*600 128MB 232/48
5 485/422/232 One Two USB
Xinje Electronic Co., Ltd. 4th Floor Building 7,Orignality Industry park, Liyuan Development Zone, Wuxi City, Jiangsu Province 214072 Tel: (510)85134136 Fax: (510)85111290 www.xinje.com