Reliable Power Solutions
UPS Catalog
Kehua Group --------------------------------------------------------------------------------------------------------02
Applications / Qualifications ---------------------------------------------------------------------------------------03
Products● Online Transformerless UPSKR11 Plus Series (1-10kVA)---------------------------------------------------------------------------------------04 KR11-J Plus Rack Series (1-3kVA)--------------------------------------------------------------------------------06KR11-J Rack/Tower Series (6-10kVA)----------------------------------------------------------------------------08KR-RM Rack/Tower series (1-3kVA)------------------------------------------------------------------------------10KR31 Series (10-20kVA)--------------------------------------------------------------------------------------------12 KR33 Series (10-200kVA)------------------------------------------------------------------------------------------14 KR33 BM Series (300-600kVA)------------------------------------------------------------------------------------16MR33 Series Modular UPS (25-600kVA)-------------------------------------------------------------------------18
● Online Transformer-based UPSFR-UK11 Series (1-15kVA)-----------------------------------------------------------------------------------------20 FR-UK31 Series (10-50kVA)---------------------------------------------------------------------------------------22 FR-UK33 Series (10-600kVA)--------------------------------------------------------------------------------------24KR11 T Series (1-10kVA)--------------------------------------------------------------------------------------------26KR33 T Series (300-600kVA) -------------------------------------------------------------------------------------28
● Low voltage UPSKR11 UL Series (1-5kVA)------------------------------------------------------------------------------------------30KR11A-J Rack/Tower Series (1-5kVA)---------------------------------------------------------------------------32KR33A Series (10-30kVA)------------------------------------------------------------------------------------------34FR-UK33A Series (10-200kVA)------------------------------------------------------------------------------------36MR33A Series Modular UPS (10-260kVA)-----------------------------------------------------------------------38
● Line Interactive UPSKI Series (1-5kVA) -------------------------------------------------------------------------------------------------40Mini-guard Series (500-2000VA)----------------------------------------------------------------------------------41
● Lithium Battery UPSLi UPS Series (500-3000VA)--------------------------------------------------------------------------------------42Li UPS-A Series (500-3000VA)-----------------------------------------------------------------------------------44
● DC UPSZL Series 240VDC Power System---------------------------------------------------------------------------------46
● Telecom InverterDJN-K Series 48Vdc Inverter (1-5kVA) ---------------------------------------------------------------------------48DJN P Series 48Vdc Modular Inverter (3-12kVA)----------------------------------------------------------------49
● Static Transfer SwitchRACK ATS (1 phase rack automatic transfer switch 10-32A/2-6kVA)-----------------------------------------50STS System (63-400A)---------------------------------------------------------------------------------------------51
Awarded as global top 500 company in renewable energy industry
The solar system application achieved over 4.5GW
Cultivated the military industry and nuclear power protection business
Awarded as one of Top 5 of China Inverter enterprises
Introduced MES systems,awarded as most promising mid-size company by <Forbes>
Introduced PLM systems
Successfully publish the modular data center
ntroduced CRM systems
Set up 30,000M2 Xiamen new factory
Set up 80,000M2 Jiaomei factory
Introduced ERP systems for processing management.
Kehua officially went public and listed on the Shenzhen Stock Exchange
Recognized as “UPS Well-known Trademark” by government
Passed Ohsas18001 authentication
Set up 70,000M2 production base
Complied with RoHS requirement
Passed ISO14001 authentication
Implemented 6sigma management system
Set up EMC test center
Developed no-master-slave parallel UPS and won the national patent
Transformed into private enterprise
Exported UPS to Japan, America etc.
Passed ISO9001 authentication
Company established
2016
2015
2014
2013
2012
2011
2010
2009
2008
2006
2005
2002
2001
2000
1999
1997
1995
1988
HISTORY
KEHUA TECH - POWER SOLUTION SPECIALIST
Listed on ShenzhenStock Exchange
Zhangzhou factory Shenzhen factory Xiamen factory Jiaomei factory
Telecom Industry Finance Traffic Data Center Electric Power
Medical Device
Kehua Group
Renewable Energy
Critical Power
With high reputation and good service in power electronics f ield, Kehua has participated and
undertaken many power projects for key events, such as 2016 G20 Summit, the 16th Asian Games,
2010 Shanghai EXPO, Angolan Luanda Stadium (for 2010 African Cup football games), 2008 Beijing
Olympic Games, the Golden Tax Project…
Being a qualif ied high-end UPS manufacturer, Kehua passed ISO9001 authentication in 1995,
ISO14001 in 2005 and OHSAS18001 in 2008. With years’ efforts in extending global market, UPS with
CE, CB, UL,TUV, KC, SONCAP certificates are available to meet different market requirements.
Xiamen Kehua Hengsheng Co., Ltd. is a leading provider in mainland China, founded in 1988 and
headquartered in Xiamen. KEHUA has the R & D, manufacturing, sales and service base with a
facility of more than 180,000 square meters, 5 manufacture bases and emplys over 3,000 people.
The Group's mission is to achieve sustained development of reliable power solution for the future of
green world. KEHUA officially went public on Shenzhen Stock Exchange on Jan 13th of 2010, Stock
NO.: 002335.
KEHUA owns 29 years experience of specializing in power industry and solid R&D strength: 3 R&D
centers with over 700 expert engineers including 3 national experts, 1 EMC test center and 1 UL
witness Test Data Program.
Being a qualified high-end power equipment manufacturer, Kehua passed ISO 9001 authentication
in 1995, ISO 14001 in 2005 and OHSAS18001 in 2008. Products also have approval of UL, CE, TUV,
SAA and CQC certification.
KEHUA is a integrated power solution provider in Critical Power, Renewable Energy, Data Center for
customers of various industry. KEHUA provides complete range of power equipments, professional
and comprehensive power services and solutions: All IGBT UPS up to 600KVA, Online double
conversion UPS from 1KVA to 1200KVA, Line-interactive UPS, Lithium battery UPS, Outdoor UPS,
Telecom inverter, rectifier, EPS, STS, etc.
The company insists on market-orientation and innovation, KEHUA keeps satisfying its users with
intelligent, custom-made products and solutions to meet diverse demands of power.
0504
Specification:
Main Features:
Application:
Online Transformerless UPS
MODELKR1000+/KR1000L+
KR2000+/KR2000L+
KR3000+/KR3000L+
KR6000+/KR6000L+
KR1110S+/KR1110+
Input
Voltage (Vac) 120~295 80~275
Frequency (Hz) 50/60± 10% (50/60Hz auto-sensing)
Power Factor ≥0.99
THDi <5%
Output
Capacity (VA) 1000 2000 3000 6000 10000
AC/AC Efficiency (Max.)92%
(94.2%optional)
93%
(94.6%optional)
94%(94.2% optional)
95% 95%
Power Factor 0.9 (1.0 optional)
Voltage (Vac) 208/220/230/240±1%(selectable on display panel)
Frequency (Hz) 50/60±0.2% (battery mode)
THDvTHD < 2% (linear load );
THD < 5% (nonlinear load )THD < 1% (linear load );
THD < 4% (nonlinear load )
Transfer Time (ms) 0
Battery
Voltage (Vdc) 24/36 48/72 72/96 192/192~240 192/192~240
BATT Type2×9Ah 12V/
External4×9Ah 12V/
External6×9Ah 12V/
External
16×7Ah 12V/External 16~20 units
settable
16×9Ah 12V/External 16~20 units
settable
Charger Current (A) Max. 1/4 1/4 1/4 1~8 (adjustable) 1~8 (adjustable)
Other
Communication InterfaceRS232, EPO, USB (slot)
(SNMP, RS485+dry contact are optional in slot)
LCD DisplayAC input & output voltage, frequency, Load level, Battery level, Temperature;
AC mode, Battery mode, Bypass mode, and Fault
Alarm Low battery, abnormal AC input, UPS failure, etc.
Protection Low battery, overload, short-circuit and over temperature, etc.
Noise (dB) <50 <55
Working Temperature (℃) -5 ~ 40
Relative Humidity 0 ~ 95%, No condensation
Dimension (W×D×H) mm 145×360×225 190×400×330 230×502×553/190×422×337
Weight (kg) 9.2/4.5 17.7/8.5 22.9/9.2 54.5/10.9 56.2/12.5
● Full digital control technology
● Low THDi: <5%
● Input power factor up to 0.996
● Output power factor up to 1.0
● AC/AC efficiency up to 95%
● Perfect LCD display panel
● High power density design
● Intelligent RS232+USB+EPO communication port
● ECO function
● SNMP or RS485+ dry contact (optional)
● Data center
● Point-of-sale
● Network device
● Commercial facility
● Precision instrument
KR11 Plus Series (1-10kVA)
KR11-J Plus Series (1-10 kVA)
0706
Specification:
Main Features:
Application:
Online Transformer-based UPS
0706
MODEL KR1000-J+ KR1000L-J+ KR2000-J+ KR2000L-J+ KR3000-J+ KR3000L-J+
Input
Voltage (Vac) 120-295
Frequency (Hz) 50/60± 10% (50/60Hz auto-sensing)
Power Factor ≥0.99
THDi <5%
Output
Capacity (VA) 1000 2000 3000
AC/AC Efficiency 92% 93% 94%
Power Factor 0.9 (1.0 optional)
Voltage (Vac) 208/220/230/240±1% (settable on display panel)
Frequency (Hz) 50/60±0.2 (battery mode)
THDv THD < 3% (linear load ); THD < 5% (nonlinear load )
Transfer Time (ms) 0
Overload 101%~115% for 1 min, 116%~133% for 1 s, above 134% for 200ms
Battery
Voltage (Vdc) 24 36 48 72 72 96
BATT Type 2×9Ah12V External 4×9Ah12V External 6×9Ah12V External
Charger Current(A)Max. 1 4 1 4 1 4
Other
Communication Interface RS232+USB+EPO (RS485, Dry contact and SNMP adapter are optional)
Display LCD
Alarm Low battery, abnormal AC input, UPS failure, etc.
Protection Low battery, overload, short-circuit and over temperature, etc.
Noise (dB) < 50 < 55
Working Temperature (℃) -5 ~ 40
Relative Humidity 0 ~ 95%, No condensation
Dimension (W×D×H) (mm) 438×420×2U438×420×2U(UPS)
+ 438×420×2U(Battery pack)
438×420×2U438×420×2U(UPS)
+ 438×420×2U(Battery pack)
438×420×2U
Weight (kg) 11.5 7 8+14 9.9 8.5+20 10
● Full digital control technology
● Three level inverter technology
● High AC/AC efficiency up to 94%
● Low THDi: < 5%
● High input power factor up to 0.996
● High output power factor up to 1.0
● Intelligent RS232+USB+EPO communication port
● ECO function
● Perfect LCD display panel
● Programmable rear panel
● Full options for communication and monitoring
● SNMP or RS485 dry contact (optional)
● External battery bank, Rack kits (optional)
● Online double conversion
● 19" rack device
● Computer room
● Data center
● Point-of-sale
● Router
● Hub and network device
● Commercial facility
● Precision instrument
KR11-J Plus Rack Series (1-3kVA)
KR11-J Plus Rack Series (1-3 kVA)
0908
Specification:
Main Features:
Application:
Online Transformerless UPS
MODEL KR6000-J/ KR6000L-J KR1110S-J/KR1110-J
INPUT
Voltage (Vac) 120~275 (L1, L2, G)
Frequency (Hz) 50/60Hz±5% (50/60Hz ±10% settings)
Power Factor >0.99
OUTPUT
Capacity (VA) 6000 10000
Power Factor 0.8 (0.9 optional)
Voltage (Vac) 220/230/240±2%
Frequency (Hz) 50/60±0.2%(battery mode)
Waveform Pure sine wave THD < 3% (linear load )
Transfer Time (ms) 0
Overload
105%~129% for 10minutes, 130~150% for 1 minute,
above150% for 1 second.
BATTERY
Voltage (Vdc) 192
BATT Type 16×7Ah12V/External
Charger Current(A)Max 1.5 (2A is optional)
OTHER
Communication Interface RS232+USB+EPO( Dry contact, SNMP are optional)
Display LCD display parameters of UPS
Alarm Low battery, abnormal AC input, UPS failure, etc
Protection Low battery, overload, short-circuit and over temperature, etc
Noise (dB) < 60
Working Temperature(℃) 0 ~ 40
Relative Humidity 0 ~ 95%, No condensation
Dimension (W×D×H)(mm) 440×550×3U(UPS)+ 440×550×3U(Battery pack)/ 440×550×3U(UPS)
Weight (kg) 18+48/18 19+48 /19
● Online double conversion
● Rack and tower convertible
● High input power factor
● Wide input voltage range
● Compact and light weight
● High reliability and performance
● Low THDi≤5%
● With ECO function
● Intelligent RS232+USB+EPO communication port
● Full protection function & Automatic bypass
● UPS management software (optional)
● SNMP or dry contact (optional)
● External battery bank, rack kits (optional)
● 19" rack device
● Computer room
● Data center
● Point-of-sale
● Router
● Hub and network device
● Commercial facility
● Precision instrument
KR11-J Rack/Tower Series (6-10kVA)
KR11-J Rack/Tower Series (6-10kVA)
1110
Specification:
Main Features:
Application:
Online Transformerless UPS
1110
MODEL KR1000-RM KR2000-RM KR3000-RM
INPUT
Voltage (Vac) 120-295
Frequency (Hz) 50/60± 10% (50/60Hz auto-sensing)
Power Factor ≥0.99
THDi <5%
OUTPUT
Capacity(VA) 1000 2000 3000
AC/AC Efficiency Max. 91.1% 92.5% 93.5%
Power Factor 0.9 (1 optional)
Voltage (Vac) 208/220/230/240±1%(settable)
Frequency(Hz) 50/60±0.2(battery mode)
THDvTHD < 3% (linear load );
THD < 5% (nonlinear load )
ECO mode YES
Transfer Time (ms) 0
Overload 101%~115% for 1 min, 116%~133% for 1 s, above 134% for 200ms
BATTERY
Voltage(Vdc) 36 48 72
BATT Type 3×7Ah12V 4×9Ah12V 6×9Ah12V
Charging Current(A)Max. 1
OTHER
Communication InterfaceRS232+USB+EPO
(DB9 dry contact and SNMP adapter are optional)
*Output outlet 4×IEC320 C13 6×IEC320 C13 + 1×IEC320 C19
Display Blue screen LCD
Alarm Low battery, abnormal AC input, UPS failure, etc.
Protection Low battery, overload, short-circuit and over temperature, etc.
Noise (dB) < 50 < 55
Working Temperature 0 ~ 40℃
Relative Humidity 0 ~ 95%, No condensation
Dimension
(W×D×H) (mm) 438×420×87(2U) 438×570×87(2U)
Weight (kg) 13.2 19.9 24.8
● Hot-swappable battery design
● User-friendly and easy-shift LCD display
● Full digital control technology
● Three level inverter technology
● High AC/AC efficiency up to 93.5%
● Low THDi: < 5%
● High input power factor up to 0.996
● High output power factor up to 1.0
● Intelligent RS232+USB+EPO communication port
● Perfect LCD display panel
● Programmable rear panel
● Full options for communication and monitoring
● Selectable output sockets
● SNMP or dry contact (Optional)
● External battery pack (Optional)
● Programmable power management outlet (Optional)
● 19" rack device
● Computer room
● Data center
● Point-of-sale
● Router
● Hub and network device
● Commercial facility
● Precision instrument
KR-RM Rack/Tower Series(1-3kVA)
KR-RM Rack/Tower Series (1-3kVA)
Online Transformerless UPS
Specification:
Main Features:
Application:
1312
MODEL KR3110S/KR3110 KR3115 KR3120
INPUT
Voltage (Vac) 380/400/415±25%(-45% in half load)
Frequency (Hz) 50/60 ±10%
Power Factor ≥0.98
Phase 3φ4W+PE
THDi ≤5%
Bypass Voltage (Vac) 180-260
OUTPUT
Capacity (kVA) 10 15 20
Power Factor 0.8 (0.9 optional)
Voltage (Vac) 220/230/240 ±1%
Frequency (Hz) 50/60±0.2%(battery mode)
Waveform Pure sine wave THD <3% (linear load)
Overload 105%~125% load for 10 mins,126%~150% load for 1 min, above150% load for 1 second
Transfer Time (ms) 0
Efficiency 90%(linear load) 91%(linear load)
Crest Factor 3:1
BATTERY
BATT Voltage(Vdc) 192
BATT Type 16×7Ah 12V/External External
Charger Current(A)Max 1/5 5
OTHER
Maintenance Bypass Switch Standard
Communication Interface RS232+USB+EPO (SNMP adapter, Dry contact are optional)
Display LCD Display indicates frequency, voltage, load, battery voltage, etc. LED indicates running status
Alarm Low battery, abnormal AC input, Overload, UPS failure
Protection Low battery, overload, short-circuit, UPS failure, and input over/low voltage
Noise (dB) <60
Working Temperature(℃) 0 ~ 40
Relative Humidity 0 ~ 95%, No condensation
Dimension (W×D×H) (mm)Standard/Long backup
255×565×700/255×565×500 255×565×585
Weight (kg) Standard/ Long backup 71/27 37 37
● Online double conversion
● High reliability DSP control
● Advanced PFC technology
● Wide input voltage range
● DC cold start function
● Intelligent fan speed control
● Full protection function
● Advanced battery charging management
● Intelligent RS232+USB+EPO communication port
● SNMP adapter or dry contact (optional)
● Advanced no-master-slave parallel technology (optional)
● 1P/1P or 3P/1P is suitable without additional setting (15kVA
and 20kVA only)
● IT device
● Data center
● Precision instrument
● Intelligent equipment
KR31 Series(10-20kVA)
KR31 Series (10-20kVA)
Specification:
1514
Main Features:
Application:
Online Transformerless UPS
1514
MODELKR3310S/KR3310
KR3320S/KR3320
KR3330S/KR3330
KR3340 KR3360 KR3380 KR33100 KR33120 KR33160 KR33200
INPUT
Voltage (Vac) 380/400/415(138~485 L-L)380/400/415(209~ 475
L-L)
Frequency (Hz) 40~70 50/60 ±10%
Bypass Voltage (Vac) 380/400/415: -20%~+15% 380/400/415: -30%~+20%
Power Factor ≥0.99
Phase 3φ4W+PE
OUTPUT
Capacity (kVA) 10 20 30 40 60 80 100 120 160 200
Power Factor 1 0.9
Voltage (Vac)L-N: 220/230/240±1%
L-L: 380/400/415±1%
Frequency (Hz) 50/60±0.2%(Battery mode)
Phase 3φ4W+PE
Unbalance 3-phasevoltage stabilization with
full load≤2%
Waveform Pure sine wave, THD<1% at linear Pure sine wave, THD<3%
at linear
Transfer Time (ms) 0
Efficiency ≥95% ≥94%
Overload 115% load for 60 minutes, 130% load for 10 minutes, 150% load for 1 minute130% for 10 mins, 150% for
10 seconds, above 150% for 200ms
BATTERY
Battery Voltage (Vdc) ±180~±240480
(400-522 settable)
BATT Type32×7Ah
12V/External
40×7Ah 12V/
External
40×7Ah 12V/
External
64×7Ah 12V/
ExternalExternal
Charging Current (A) 1-10 settable 5-10 settable
5-20 settable
5-20settable 5-30 settable 10-60 settable
OTHER
CommunicationInterface
RS485 MODBUS, dry contact
(SNMP adapter optional) RS485,dry contact (Modbus and SNMP adapter are optional)
Display Touch screen+LED
Alarm AC input abnormal, low battery, overload, failure
Protection Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage
Noise(dB) <65 <67
Working Temperature
(℃)0~40
Relative Humidity 0 ~ 95%, No condensation
Dimension (W×D×H)(mm) 450×850×1400/320×850×800 320×850×900 450×850×1400 1200×800×1800
Weight (kg) 237/110 254/110 304/110 110 180 206 239 239 730 760
● Online double conversion
● Fully DSP control
● Advanced 3-level technology, high input power factor
● IGBT rectifier
● High reliability and performance
● Wide input voltage range
● DC cold start function
● Advanced battery charging management
● Frequency converter function (10-120kVA)
● Small footprint design
● Intelligent fan speed control
● ECO mode and EPO function
● Full protection function
● Intelligent RS485 Communication Port
● Dry contact, maintenance bypass
● SNMP adapter (optional)
● Advanced no-master-slave parallel technology (optional)
● Intelligent battery monitor system - MMBM (optional)
● Computer room
● Data center
● Precision instrument
● Commercial facility
● Intelligent equipment
KR33 Series(10-200kVA)
KR33 Series (10-200kVA)
320×850×800
Online Transformerless UPS
Specification:
Main Features:
Application:
1716
Model KR33300BM KR33400BM KR33500BM KR33600BM
Input
Voltage(Vac) 380/400/415
Voltage range -40% ~ +25%
Input wiring 3Ph+N+PE
Rated frequency (Hz) 50/60
Frequency range ±5% / ±10%
PF 0.99
THDi ≤3%
Bypass
Input Voltage (Vac) 380/400/415
Voltage range -25% ~ +20%
Frequency range ±5% / ±10%
Output
Capacity (kVA) 300 400 500 600
Output voltage 380/400/415Vac±1%
Frequency (Hz) 50/60±0.1
Output PF 0.9 (1.0 optional)
THDv <0.5%(linear load), ≤5%(nonlinear load)
Efficiency 97%
Output wiring 3Ph+N+PE
Overload ≤130%, 10min; ≤150%, 1min
Dynamic response time (ms) 20
Dynamic response range ≤5%
Battery
Voltage (Vdc) 480(12V battery from 32 to 44 cells settable)
Charging Current (A) 20-100
Other
Operating temperature (℃) -5~40
Storage temperature (℃) -25~55
Noise(dB) <75
Communication Dry contact,MODBUS,SNMP(optional)
Dimension (W×D×H)(mm) 1400×800×1800 1400×800×1800 1600×900×1800 1600×900×1800
Weight (kg) 950 1000 1200 1300
● Three level technology
● DSP digital control technology
● Efficiency up to 97%
● Support 8 units in parallel, single /parallel system compatible
● Low THDi: ≤3%
● PCB boards feature with anti-corrosion paint coating
● Intelligent fans control
● Self-aging function
● Large-size touch screen with LED indicators
● Computer room
● Data center
● Precision instrument
● Commercial facility
● Intelligent equipment
KR33 BM Series(300-600kVA)
KR33 BM Series (300-600kVA)
Online Transformerless UPS
Specification:
Main Features:
Application:
1918
MODEL MR33125 MR33200 MR33320 MR33480 MR33600
Power Module MR3325-J MR3340-J
INPUT
Rated Voltage (Vac) 380/400/415
Voltage Range (Vac) 138~485
Input Frequency (Hz) 40~70
Bypass Voltage Range (Vac) -15% (-20%/-30% optional) ~+15%(+10% /+20% optional)
Power Factor ≥0.99
THDi <3%
Phase 3Φ4W+PE
Battery Voltage (Vdc) ±192 (±180~ ±240 settable)
Charging Current (A) 10 Maximum (single module)
OUTPUT
Capacity(kVA) 125/125 200/200 320/320 480/480 600/600
Power Factor 1
Phase 3Φ4W+PE
Waveform sine wave
Voltage (Vac) L-L:380,400,415±1%
Frequency (Hz) 50/60± 0.2% (battery mode)
Three Phase Difference ≤2 degrees
Waveform Distortion ≤ 3% (linear load)
Static Bypass Transfer Time 0
System Efficiency 96%
Parallel Mode Advanced no-master-slave parallel technology, N+1 redundancy
Overload Capacity105-115% load for 60 minutes, 116%-130% load for 10 minutes,
131%-150% load for 1minute
OTHERS
Approvals CE (EN62040-2, IEC62040-1)
Operating Temperature(℃) 0~40
Storage Temperature(℃) -40~7
Relative Humidity 0%~95% (no condensing )
Communication Function RS485, dry contact(SNMP optional)
Noise (dB) < 65 < 70
Power Module(kVA) 25 40
Power Module Dimension
(W×D×H) mm500x700x130
Power Module Weight (kg) 32 33
Dimension (W×D×H) (mm) 600x900x1400 600×860×2000 1200×860×2000 1800×860×2000
Weight (kg) 347 412 527 854 1250
● Hot-swappable design
● High efficiency up to 96%
● Dual system control card and bypass unit power
● Battery cold start function
● Intelligent fan control and redundant design
● Parallel expansion up to 4 units
● Advanced power module sleep mode
● Allow 100% three phase unbalance load
● Frequency converter function(60Hz to 50Hz or 50Hz to 60Hz)
● Self-aging test function
● EPO and ECO function
● Intelligent battery management
● Fault Trace Management(FTM)
● Programmable dry contacts
● Intelligent fan control and redundant design
● Data center
● Telecom system
● Computer room
● Financial system
● Precision instrument
● Intelligent equipment
MR33 Series Modular UPS(25-600kVA)
Main Features:
Specification:
Application:
Online Transformer-based UPS
2120
MODEL FR-UK10L FR-UK20L FR-UK30LFR-UK50/FR-UK50L
FR-UK60/FR-UK60L
FR-UK1110S/FR-UK1110
FR-UK1115S/FR-UK1115
INPUT
Voltage (Vac) 220/230/240V MODEL:165-275 110/120V MODEL: 85~137
Frequency (Hz) 50/ 60±5% (50/60Hz settable)
Phase Single phase three wires
OUTPUT
Capacity(VA) 1000 2000 3000 5000 6000 10000 15000
Power Factor 0.8 ( 0.9 optional )
Voltage range(Vac) 220/230/240±2% or 110/120±2%
Frequency (Hz) 50 / 60 ±0.5%(battery mode)
Waveform Pure Sine wave,THD<3% ( Linear load )
Transfer Time(ms) 0
Overload 125% load for 60 seconds , 150% load for 1 second
BATTERY
Voltage (Vdc) 48 96 192
BATT Type4×7Ah 12V/
External8×7Ah 12V/
External8×7Ah 12V/
External16×7Ah 12V/
External16×7Ah 12V/
External32x7Ah 12V/
External48x7Ah 12V/
External
Charger Current(A)Max
1/4.5 1/4.5 1/4.5 1/8.0 2/6 (12 option) 3/4.5
OTHER
CommunicationInterface
RS232,dry contact (USB and SNMP adapter are optional)
Display LCD display input voltage, output voltage, load capacity, battery voltage, etc., LED indicates running status
Alarm Overload, abnormal AC input, low battery
Protection Low battery, overload, over temperature, short circuit, output over voltage, output low voltage
Noise (dB) ≤55 ≤58
Working Temperature 0~40℃
Relative humidity 0~95%(no condensation)
Dimension (W×D×H)(mm)
230×610×470 230x635x690/230×610×470400x800x1180/300x610x530
400x800x1180
Weight (kg) Standard/ Long backup
31.5 43.5 53 79/44 82/45 308/65 353/158
● Online double conversion
● IGBT inverter and output isolation transformer
● Wide input voltage range
● Full protection function
● High reliability and performance
● Intelligent RS232/RS485&DB9 dry contact
communication port
● Management software(optional)
● External battery bank(optional)
● SNMP adapter or USB(optional)
● IT device
● Data center
● Commercial facility
● Telecommunication
● Industry
FR-UK11 Series(1-15kVA)
FR-UK11 Series (1-15 kVA)
Main Features:
Specification:
Application:
Online Transformer-based UPS
2322
MODEL FR-UK3110 FR-UK3115 FR-UK3120 FR-UK3130 FR-UK3140 FR-UK3150
INPUT
Voltage(Vac) 380/400/415±25%
Rectified Frequency(Hz) 45~65 40~65
SYNC Frequency(Hz) 50/60±10%(±5%optional) 50/60±5%
Phase Three phase in single phase out (L1,L2,L3,N,G)
OUTPUT
Capacity (kVA) 10 15 20 30 40 50
Power Factor 0.8 (0.9 optional)
Voltage (V) 220/230/240±1%
Frequency(Hz) 50/60±0.2% 50/60±0.5% (Battery mode)
Waveform Pure sine wave THD <3% (linear load)
Overload125% load for 1 minute, 150% load
for 1 second125% load for 1 minute, 150% load for 20 seconds
BATTERY
Voltage (Vdc) 192 348
BATT Type External
Charger Current(A)Max
6(12 optional) 10~20 settable
OTHER
Maintenance Bypass Switch
Optional Standard
Communication Interface RS232/RS485 and dry contact (SNMP adapter are optional)
Display LCD Display indicates frequency, voltage, load, battery voltage, etc.LED indicates running status
Alarm Low battery, abnormal AC input, overload, UPS failure
Protection Low battery, overload, output over voltage, short-circuit, over temperature
Noise (dB) <60 <65
Working Temperature 0 ~ 40℃
Relative Humidity 0 ~ 95%, No condensation
Dimension (W×D×H)(mm)
30×780×720 400×800×1180
Weight (kg) Standard/ Long backup
230/130 320/160 205 230 270 300
● Online double conversion
● IGBT inverter and output isolation transformer
● Wide input voltage range
● High reliability DSP control
● DC cold start function
● Full protection function
● Intelligent RS232/RS485 & DB9 dry contact communication port
● SNMP adapter(optional)
● Advanced no-master-slave parallel technology (optional)
● Intelligent battery monitor system-MMBM(optional)
● Computer room
● Data center
● Precision instrument
● Intelligent equipment
● Industrial application
FR-UK31 Series(10-50kVA)
FR-UK31 Series (10-50kVA)
Specification:
2524
Main Features:
Application:
Online Transformer-based UPS
2524
MODELFR-UK
3310 FR-UK
3320 FR-UK
3330 FR-UK
3340FR-UK
3360FR-UK
3380FR-UK33100
FR-UK 33120
FR-UK33160
FR-UK 33200
FR-UK 33250
FR-UK 33300
FR-UK 33400
FR-UK 33500-
12P
FR-UK 33600-
12P
INPUT
Voltage(Vac) 380/400/415±25%
RectifierFrequency(Hz)
40~70
SYNC Frequency
Tracking(Hz)50/60±10%(±5% settable)
Phase 3φ4W+PE
OUTPUT
Capacity (KVA) 10 20 30 40 60 80 100 120 160 200 250 300 400 500 600
Power Factor 0.9
Phase 3φ4W+PE
Voltage (Vac) L-N:220/230/240±1%, L-L:380/400/415±1%,
Frequency(Hz) 50/60±0.2 (battery mode)
Waveform Pure sine wave, THD≤2% (linear load)
3 Phases 100% Load Unbalance Voltage Stability
≤2%,allow 100% unbalance
Overload 125% load for 10mins, 150% load for 1 min
BATTERY
Voltage (Vdc) 348 (360 settable) 384(348/360/372 settable)
BATT Type External
ChargingCurrent(A)
10~40A settable 10-100A settable
OTHERS
Maintenance Bypass
Yes
CommunicationInterface
RS485/MODBUS / dry contacts (SNMP is optional) RS232/RS485 /Dry contacts(SNMP is optional)
Display Touch screen + LED
Alarm Overload, abnormal AC input, low battery, UPS failure,etc.
Protection Low battery, overload, over temperature, short circuit, output over voltage, output low voltage, etc.
Noise (dB) < 65 < 70
WorkingTemperature
0 ~ 40℃
Relative Humidity
0 ~ 95%, No condensation
Dimension (W×D×H)(mm)
500×600×1180 500×800×1600 700×800×1800 1400x1000x1850 1600×1000×1850 3000×1000×1850
Weight(kg) 230 260 300 400 450 520 600 650 825 1280 1568 1830 2050 4500
● Online double conversion
● IGBT inverter and output isolation transformer
● Wide input voltage range
● 3 phases UPS allow 100% unbalance load
● Fully DSP control, high reliability and performance
● DC cold start function (Optional)
● Advanced battery charging management
● Intelligent fan speed control
● HMI-touch screen display
● ECO mode and EPO function.
● ECO-mode with 98% efficiency
● 10,000 events logs
● Battery self-test function
● Intelligent RS232/RS485,DB9 dry contact communication port
● 10-30kVA models with wheels
● MODBUS &SNMP adapter(optional)
● Advanced no-master-slave parallel technology (optional)
● Intelligent battery monitor system-MMBM(optional)
● 12 Pulse rectifier(optional)
● Bypass isolation transformer(optional)
● Computer room
● Data center
● Precision instrument
● Intelligent equipment
● Industrial application
FR-UK33 Series(10-600kVA)
FR-UK33 Series (10-600 kVA)
Main Features:
Specification:
Application:
Online Transformer-based UPS
2726
MODELKR1000T/KR1000TL
KR2000T/KR2000TL
KR3000T/KR3000TL
KR6000T/KR6000TL
KR1110T
INPUT
Voltage (Vac) 120~295 120~275
Frequency (Hz) 50/60±10%/5% (50/60Hz settable)
Power Factor ≥0.99
OUTPUT
Capacity (VA) 1000 2000 3000 6000 10000
Power Factor 0.8
Voltage (Vac) 208/220/230/240±2% or 110/120±3%
Frequency (Hz) 50/60±0.2% (battery mode)
Waveform Pure sine wave THD < 3% (linear load )
Transfer Time (ms) 0
Overload105%~129% for 60 seconds, 130%~150% for 30 seconds, above 150% for 300ms
105%~129% for 10minutes,130~150% for 1 minute,above150% for 1 second.
BATTERY
Voltage(Vdc) 36 72 96 192
BATT Type 3×7Ah 12V/External 6×7Ah 12V/External 8×7Ah 12V/External 16×7Ah 12V/External
Charger Current(A)Max 1/5 1/5 1/5 1/6
OTHER
Communication InterfaceRS232
(Dry contact, USB and SNMP adapter are optional)RS232+USB+EPO
(Dry contact, SNMP are optional)
Display LCD & LED display
Alarm Low battery, abnormal AC input, UPS failure
Protection Low battery, overload, short-circuit and over temperature
Noise (dB) < 55 < 60
Working Temperature(℃) 0 ~ 40
Relative Humidity 0 ~ 95%, No condensation
Dimension (W×D×H)(mm)Standard/ Long backup
156×530×220 198×630×347 255×650×790
Weight (kg) Standard/ Long backup
20/12 38/27 42/28 147/105 107
● Output isolation transformer
● Online double conversion
● High input power factor
● Wide input voltage range
● Full protection function
● Automatic bypass
● High reliability and performance
● THDi≤5%
● Dual Output 208V/120V voltage
● Intelligent RS232 communication port
● EPO function
● UPS management software (optional)
● SNMP or USB or dry contact (optional)
● Manual bypass switch (optional)
● External battery bank (optional)
● Data center
● Point-of-sale
● Router
● Hub and other network device
● Commercial facility
● Precision instrument
KR11 T Series(1-10kVA)
KR11 T Series (1-10 kVA)
Main Features:
Specification:
Application:
Online Transformer-based UPS
2928
MODEL KR33300T KR33400T KR33500T KR33600T
Input
Rated voltage(Vac) 380/400/415( settable)
REC voltage range(Vac) 228~475
Bypass voltage range ±20%
Bypass frequency sync(Hz) 50/60±5%(±10% optional)
Battery voltage(Vdc) 480V(384V~504V, 32~42pcs 12V battery settable)
Charging mode Equalized and float Charging
Charging current(A) 20~100
PF ≥0.999
THDi ≤2%(full load)
Output
Capacity (kVA) 300 400 500 600
Voltage(Vac) 380/400/415Vac±1%
Frequency(Hz) 50/60±0.02%(Battery mode)
Output PF 0.9
THDV (Linear load) ≤0.5%
THDV (Non linear load) ≤2%; (RCD output PF=0.8,≤6%)
Crest factor 3:1
Voltage Transient range (Hz) ±5%
100% load system efficiency 95%
Power consume without load 4.785kw (INV); 2.736kw(ECO) 5.745kw (INV) 4.34kw(ECO)
Frequency sync range (Hz) 45~55/54~66
Inverter overload 130% 10min; 150% 1min;
Inverter short circuit current-limiting (A) 1150 1600 1900 2300
Bypass overload 130% long time;150% 10min;
Transfer time(AC to DC) (ms) 0
ECO/normal mode transfer time (ms) ≤10
Other
Maintenance bypass Yes
Display Touch screen+ LED
Communication port RS232/485, dry contact (SNMP, MODBUS optional)
DC start function Optional
Noise(dB) 72 75
Working temperature(℃) -5~40
Storage temperature(℃) -20~55
Humidity 0~95%
IP IP20
Approvals EN62040-2:2006
Dimension(W×D×H)(mm) 1600X1000X1800 2200X1000X1800
Weight(kg) 1400 1700 2300 2400
● Isolation output transformer
● Online double conversion
● High input power factor
● Wide input voltage range
● Full protection function
● Automatic bypass
● High reliability and performance
● THDi≤5%
● Dual Output 208V/120V voltage
● Intelligent RS232 communication port
● EPO function
● UPS management software (optional)
● SNMP or USB or dry contact (optional)
● Manual bypass switch (optional)
● External battery bank (optional)
● Data center
● Point-of-sale
● Router
● Hub and other network device
● Commercial facility
● Precision instrument
KR33T Series(300-600kVA)
KR33T Series (300-600 kVA)
Main Features:
Specification:
Application:
Low Voltage UPS
3130
MODEL KR1000A/KR1000AL KR2000A/ KR2000AL KR3000A/ KR3000ALKR5000A/
KR5000AL
INPUT
Voltage (Vac) 80~148 83~138
Frequency (Hz) 50/60Hz±5%
Power Factor >0.99
OUTPUT
Capacity (VA) 1000 2000 3000 5000
Power Factor 0.8
Voltage (Vac) 110/115/120±2%
Frequency (Hz) 50/60±0.2% (battery mode)
Waveform Pure sine wave THD < 3% (linear load )
Transfer Time (ms) 0
Overload105%~129% for 60 seconds, 130%~150% for 30 seconds
above 150% for 300ms
105%-129% load for 10 minutes 130%-149% load for 1 minute above 150% load for 1 second
BATTERY
Voltage(Vdc) 36 72 96
Internal BATT Type 3×7Ah 12V/External 6×7Ah 12V/External 8×7Ah 12V/External
Charger Current(A)Max 1/5
OTHER
Communication Interface RS232 (USB or Dry contact or SNMP adapter is optional)
Display LCD display parameters of UPS
Alarm Low battery, abnormal AC input, UPS failure
Protection Low battery, overload, short-circuit and over temperature
Noise (dB) < 45 < 60
Working Temperature 0 ~ 40℃
Relative Humidity 0 ~ 95%, No condensation
Dimension (W×D×H)(mm) 156×400×220 198×490×347 255×565×700/255×565×500
Weight (kg) 13/7 28/16 34/17 70/24
● Online double conversion
● High input power factor
● Wide input voltage range
● Full protection function
● Automatic bypass
● High reliability and performance
● Intelligent RS232 communication port
● EPO for 5kVA
● Manual bypass switch optional for 5kVA
● UPS management software (optional)
● SNMP or USB or dry contact (optional)
● External battery bank (optional)
● Data center
● Point-of-sale
● Router
● Hub and other network device
● Commercial facility
● Precision instrument
KR11 UL Series(1-5kVA)
KR11 UL Series (1-5 kVA)
Main Features:
Specification:
Application:
Low Voltage UPS
3332
INPUT DC
FUSE 250V/10A
AC INPUT
SIGNAL RS232 RS232 �S�
SN
P
N��A��������
�
RS232
AC UTPUT 10A
MODEL KR1000A-J/KR1000AL-J KR2000A-J/ KR2000AL-J KR3000A-J/ KR3000AL-J KR5000A-J/ KR5000AL-J
INPUT
Voltage (Vac) 80~148 60~138
Frequency (Hz) 50/60± 5% (50/60Hz ± 10% settable)
Power Factor ≥0.99
OUTPUT
Capacity (VA) 1000 2000 3000 5000
Power Factor 0.8
Voltage (Vac) 110/120±2%
Frequency (Hz) 50/60±0.2% (battery mode)
Waveform Sine wave, THD<3% at linear load
Transfer Time (ms) 0
Overload 105%~129% for 60 seconds, 130%~150% for 30 seconds, above 150% for 300ms105%~125% for 10minutes, 125~150% for 1 minute, above150% for 1 second.
BATTERY
Voltage (Vdc) 36 72 96 96
BATT Type 3×7Ah 12V/External 6×7Ah 12V/External 8×7Ah 12V/External 16×7Ah 12V/External
Charger Current(A)Max 1/5 1/4 1/4 1/3
OTHER
Communication Interface RS232 (Dry contact, USB or SNMP adapter is optional)RS232+USB+EPO
(Dry contact or SNMP are optional)
Display LED indicates the status of UPS LCD & LED display
Alarm Low battery, abnormal AC input, UPS failure
Protection Low battery, overload, short-circuit and over temperature
Working Temperature 0~40℃
Relative Humidity 0~95%,No condensation
Dimension (W×D×H)(mm) Standard/Long backup
440×500×2U440×500×2U(UPS)+ 440×500×2U(Battery pack)/
440×500×2U(UPS)
440×550×3U(UPS)+ 440×550×3U(Battery
pack)/ 440×550×3U(UPS)
Weight(kg) Standard/long backup
14/7 10+22/12 11+28/13 18+48/18
● Online double conversion
● Rack and tower convertible
● High input power factor
● Wide input voltage range
● Compact and light weight
● High reliability and performance
● Full protection function & automatic bypass
● Intelligent RS232 communication port
● 5kVA UPS has ECO&EPO function
● UPS management software (optional)
● SNMP, USB, dry contact (optional)
● External battery bank, Tower housing, rack kits (optional)
● 19" rack device
● Computer room
● Data center
● Point-of-sale
● Router
● Hub and network device
● Commercial facility
● Precision instrument
KRA-J Rack/TowerSeries(1-5kVA)
KRA-J Rack/Tower Series (1-5kVA)
Main Features:
Specification:
Application:
Low Voltage UPS
3534
MODEL KR3310A/KR3310AS KR3320A/KR3320AS KR3330A/KR3330AS
INPUT
Nominal voltage (Vac) 110/115/120 (L-N)
Voltage range (Vac) 83~138V full load, 73~83V 75% load, 60~73V 50% load
Rectifier frequency (Hz) 50/60±5% (±10% optional)
Bypass voltage range (Vac) 110+15%(+20% optional)/-25%
Power factor (PF) >0.99
THDI <3%
Phase 3φ4W+PE
Battery External/16pcs x 12AH 12V External/32pcs x 12AH 12V External/48pcs x 12AH 12V
Battery voltage (Vdc) 192
Charging current (A) 6
OUTPUT
Capacity (kVA) 10 20 30
Power factor (PF) 0.9
Phase 3φ4W
Waveform Pure sine wave
Voltage(Vac) 110/115/120 (L-N)
Frequency(Hz) 50/60±0.2% (battery mode)
Waveform distortion THD≤3%
Static bypasstransfer time(ms)
0
System efficiency ≥93%
Parallel mode Advanced no-master-slave parallel technology, N+1 redundancy
Overload capacity 106-130% load for 1min ; 150% load for 10s (to bypass)
OTHERS
Maintenance bypass Yes
DC cold start function Yes
Display Touch screen+LED
Communication function RS232/RS485 ,dry contact,SNMP (optional)
Approvals Meet standard EN 62040-2: 2006
Noise(dB) <65
Dimension (WxDxH) (mm) 500×800×1500
● Online double conversion
● DSP and full digital control
● No-master-slave N+1 parallel technology
● International IGBT power modules
● Internal maintenance bypass
● PCB boards feature with anti-corrosion paint coating
● Manual bypass maintenance design
● DC startup function
● Allow 100% three phase unbalance load
● EPO function
● Intelligent battery management
● Intelligent network supervising
● Intelligent fans control
● Computer room
● Data center
● Precision instrument
● Commercial facility
● Intelligent equipment
KR33A Series(10-30kVA)
KR33A Series (10-30 kVA)
Main Features:
Specification:
Application:
Low Voltage UPS
3736
MODELFR-UK
3310A/FR-UK3310AS
FR-UK3320A/FR-UK3320AS
FR-UK3330A/FR-UK3330AS
FR-UK3340A
FR-UK3350A
FR-UK3360A
FR-UK3380A
FR-UK 33100A
FR-UK33120A
FR-UK33160A
FR-UK 33200A
INPUT
Voltage(Vac) 208/220 ±20% (±25% optional)
RectifierFrequency(Hz)
40~70
SYNC Frequency Tracking(Hz)
50/60±10%(±5% optional)
Phase 3φ4W+PE
OUTPUT
Capacity (kVA) 10 20 30 40 50 60 80 100 120 160 200
Power Factor 0.8 (0.9 optional)
Phase 3φ4W+PE
Voltage (Vac) L-N:120/127±1%, L-L:208/220±1%,
Frequency(Hz) 50/60±0.5% (battery mode)
Waveform Pure sine wave, THD≤3% (linear load)
3 Phases 100% Load Unbalance Voltage
Stability≤2%,allow 100% unbalance
Overload 105% load for 60mins, 125% load for 10 mins, 150% load for 1 min.
BATTERY
Voltage (Vdc) 192 348 (360 setting)
BATT Type External /Max 7Ah 12V 64pcs External
Charger Current(A)Max
10~40 settable
Battery Self-testing Automatically alarm and estimate battery status in battery abnormal status
OTHER
Maintenance Bypass
Yes
CommunicationInterface
MODBUS/RS485 and dry contact (RS232 and SNMP adapter are optional)
Display LCD Display indicates frequency, voltage, load, battery voltage, etc. LED indicates running status
Alarm Overload, abnormal AC input, low battery, UPS failure
Protection Low battery, overload, over temperature, short circuit, output over voltage, output low voltage
Noise (dB) <65
WorkingTemperature
0 ~ 40℃
Relative Humidity 0 ~ 95%, No condensation
Dimension(W×D×H)(mm)
500×800×1180/500×800×1600
800×800×1600 1400×1000×18501600×1000
×2000
Weight(Kg) 300/500 325/530 340/540 590 620 670 970 1000 1200 1450 1700
● Online double conversion
● IGBT inverter and output isolation transformer
● Wide input voltage range
● 3 phases UPS allow 100% unbalance load
● Fully DSP control, high reliability and performance
● DC cold start function
● Advanced battery charging management
● Intelligent fan speed control
● ECO mode and EPO function.
● Intelligent RS232/RS485 communication port
● MODBUS & SNMP adapter (optional)
● Advanced no-master-slave parallel technology (optional)
● Intelligent battery monitor system - MMBM (optional)
● Bypass isolation transformer (optional)
● Computer room
● Data center
● Precision instrument
● Intelligent equipment
● Industrial application
FR-UK33A Series(10-200kVA)
FR-UK33A Series (10-200A)FR-UK33A Series (10-200A)
Main Features:
Specification:
Application:
Low Voltage UPS
3938
MODEL MR3360AS/MR3360A MR33100A MR33160A MR33240A
Maximum Capacity 60kVA 100kVA 160kVA 240kVA
POWER MODULE
Power Module MR3320A-J
INPUT
Configuration 3 phase 4 wires + ground
Nominal voltage(Vac) 190/208/220 (L-L)
Voltage Range(Vac) 156~260 (L-L)
Frequency Range 50/60Hz ± 10%
PF ≥0.99
THDi ≤3%
Batteries(Vdc) ±192 Vdc (±180,±240V settable)
OUTPUT
PF 0.9(1.0 optional)
Frequency Range 50/60Hz±0.2% at battery mode
Voltage Stability(Vac) 190/208/220±1%(static) 190/208/220 ±2% (load 0~100%)
Transient Recovery Time (ms) 20(loads 0~100%)
Overload 125% loads for 10 minutes, 150% loads for 1 minute
Transfer Time (ms) 0
Efficiency ≥95%(AC-AC)
BATTERY
Battery Type 128×9 AH/12V/External External
OTHER
Communication Interface Dry contact, RS232/RS485
SNMP Adapter(optional) Yes
Display Touch screen + LED
Working Temperature(℃) -5~40
Relative Humidity ≤95% No condensation
Protection Degree IP20
Approvals CE (EN 62040-2, IEC 62040-1)
Noise (dB) ≤60 ≤65
Power Module
Dimension(W×D×H) (mm)500×700×130
Power module weight (kg) 32
Cabinet Size (W×D×H)(mm)600×1050×2000/600×900×1400 600×860×2000 1200×860×2000
● Online double conversion
● DSP digital control
● N+X parallel redundancy UPS
● ECO+EPO function
● Internal maintenance bypass
● PCB boards feature with anti-corrosion paint coating
● Module communication ring connection redundancy design
● Advanced power module dormancy technology
● DC startup function
● 3 level inverter technology
● Allow 100% three phase unbalance load
● Intelligent battery management
● Flexible network management
● Frequency converter function (60Hz to 50Hz or 50Hz
to 60Hz)
● Self-aging test function
● Data center
● Telecom system
● Computer room
● Financial system
● Precision instrument
● Intelligent equipment
MR33A Series Modular UPS(20-240kVA)
MR33A Series Modular UPS (20-260 kVA)
Line Interactive UPS Line Interactive UPS
4140
MODEL KI1000 KI1000L KI2000 KI2000L KI3000 KI3000L KI5000L
INPUT
Voltage (Vac) 150-300
Frequency (Hz) 50/60 ± 5% (50/60Hz settings)
OUTPUT
Capacity (VA/W) 1000/700 2000/1400 3000/2100 5000/3500
Voltage (Vac) 220/230/240±2% (battery mode)
Frequency (Hz) 50 /60± 0.1% (battery mode)
Waveform Pure sine wave, THD < 3%
Transfer time Typical 4ms (Synchronous switch-over)Typical
8ms
Overload Utility mode: 150% for 5 minutes, above 200% for 3 seconds
Battery mode: 120% for 30 seconds, above 150% for 1 second
BATTERY
Voltage (Vdc) 24 48 72 48
BATT type 2×7Ah 12V External 4×7Ah 12V External 6×7Ah 12V External External
Charger Current(A)Max
1 10 1 10 1 10 30
OTHER
CommunicationInterface
RS232. (Dry contact, USB and SNMP adapter are optional)
Display LED or LCD display operation status of UPS
Alarm Low battery, abnormal AC input, UPS failure
Protection Low battery, overload, short-circuit and over temperature
Dimension (W×D×H)(mm)
156×450×220 198×525×347 255×590×500
Weight (kg) 16 13 35 26 44 30 48
MODEL UPS500UPS700/UPS700L
UPS1000/UPS1000L
UPS1600/UPS1600L
UPS2000/UPS2000L
SUPS700 SUPS1200
INPUT
Voltage(Vac) 140~280 / 90~145 190~265
Frequency (Hz) 50/60 ± 10%
OUTPUT
Power (VA/W) 500/300 700/420 1000/600 1600/960 2000/1200 700/420 1200/720
Voltage (Vac) 220/230±10% ;110/120±10% (on battery mode)220/230±10%
(on battery mode)
Frequency (Hz)Synchronizing with input AC while it is normal, and 50±0.5% or 60 ± 0. 5% on
battery mode
Transfer timeTypical 6ms, including detection time and switching time (Synchronous switch-
over)
Waveform Square wave Pure sine wave
BATTERY
Voltage (Vdc) 12 12 12/24 36 36/48 24 24
BATT type 1×7Ah1×7Ah/
External2×7Ah/
External3×7Ah/
External3×9Ah/ External
2×7Ah
Charger Current(A)Max
1 1/8 1/6 1/5 1/5 1
OTHER
Communication Interface
RS232, RJ11 / RJ45 (USB and SNMP adapter are optional)
RS232 (USB,SNMP adapter are optional)
DisplayLCD display shows status of AC input, inverter, low battery, overload and battery capacity, or LED indicators show status of AC input, inverter, low
battery, overload
Dimension (W×D×H)(mm)
90×325×165/120×380×220
120×380×220
156×450×220 122×380×170
Weight (kg) 6 6.5/8 11.5/9.5 17/13 18.5/15 8 9
● Digital technology
● Intelligent battery charger
● Reliable online interactive design,with output transformer
● Intelligent regulation system on utility power voltage
● Fully functional protection
● Intelligent RS232 communication port
● UPS management software (optional)
● External SNMP or USB or dry contactor (optional)
● External battery bank (optional)
● Advanced digital control technology
● Streamline design
● Comprehensive net equipment protection
● Green idea environmental design
● Flexible and practical cold start function
● Wide voltage range for intellectual regulating (SMART AVR)
● Intelligent power management (optional)
KI Series (1-5kVA) Mini-guard Series (500-2000VA)
Specification:
Main Features:
Application:
Lithium Battery UPS
4342
MODEL UPS500Li-S UPS1000 Li-S UPS500Li UPS1000Li UPS2000Li UPS3000Li
INTPUT
Voltage (Vac) 220/230 ± 20%
Input frequency (Hz) 50/60 ± 10%
OUTPUT
Power Factor 0.7(0.8 optional)
AC Voltage (Vac) 220/230±3%(on battery mode) 220/230±2%(on battery mode)
Frequency (Hz) 50/60 ± 0. 5%
Transfer Time (ms) <10
Waveform Pure Sine Wave
BATTERY
Voltage (Vdc) 24 48
BATT Type10Ah BATT pack
with BMS20Ah BATT pack
with BMSExternal
Charger Current(A)Max 1 4 8
OTHER
Communication Interface RS232 and dry contact (SNMP is optional)
Display LED indicators show status of AC input, inverter, low/high battery, fault;
Dimension (W×D×H) (mm) 440×500×2U 440×320×1U 440×500×2U
Weight (kg) 14 16 6 13
● Double outputs: AC output and 48V DC output (long backup
time model)
● Pure sine wave output
● Low broadband noise current
● Advanced digital control technique
● Comprehensive equipment protection
● Special Lithium battery charger
● DC cold start and automatic start at low voltage recover
● Intelligent power management (optional)
● External charger (optional)
● IT Device
● Data Center
● Telecom system
● Automatic Device
● Precision Instrument
Li UPS series is rack-mount UPS combined with Lithium batteries.
it is ideal for IT device, telecommunication system, data center,
automatic device and those require high quality power protection,
supplying reliable power guarantee for your loads. Customization
products are available for special requirement.
Compared with lead acid battery, the lithium batteries have many
advantages such as higher reliability, longer cycling lifetime,
smaller size and better environmental protection.
Li UPS Series(500-3000VA)
Li UPS Series (500-3000VA)
Specification:
Main Features:
Application:
Lithium Battery UPS
4544
MODEL UPS500Li-A UPS1000Li-A UPS2000Li-A UPS3000Li-A
INTPUT
Voltage (Vac) 100/110/120 ± 15%
Input frequency (Hz) 50/60 ± 10%
OUTPUT
Power Factor 0.7 (0.8 optional)
AC Voltage (Vac) 100/110/120±2% (on battery mode)
Frequency (Hz) 50/60 ± 0. 5%
Transfer Time (ms) <10
Waveform Pure Sine Wave
BATTERY
Voltage (Vdc) 48
BATT Type External
Charger Current(A)Max 4 8
OTHER
Communication Interface RS232 and dry contact (SNMP is optional)
Display LED indicators show status of AC input, inverter, low/high battery, fault;
Dimension (W×D×H) (mm) 440×400×1U 440×500×2U
Weight(kg) 5.5 11.2
● Double outputs: AC output and 48V DC output
● Pure sine wave output
● Low broadband noise current
● Advanced digital control technique
● Comprehensive equipment protection
● Special Lithium battery charger
● DC cold start and automatic start at low voltage recover
● Intelligent power management (optional)
● External charger (optional)
● IT Device
● Data Center
● Telecom system
● Automatic Device
● Precision Instrument
Li UPS-A series is rack-mount UPS combined with Lithium
batteries, featuring low AC output voltage such as 100/110/120Vac.
it is ideal for IT device, telecommunication system, data center,
automatic device and those require high quality power protection,
supplying reliable power guarantee for your loads. Customization
products are available for special requirement.
Compared with lead acid battery, the lithium batteries have many
advantages such as higher reliability, longer cycling lifetime,
smaller size and better environmental protection.
Li UPS-A Series(500-3000VA)
Li UPS-A Series (500-3000VA)
Specification:
Main Features:
Application:
DC UPS
4746
MODEL ZL304-G400 ZL304-G600 ZL304-G800 ZL304-G1200 ZL304-G1600
INPUT
Ratecl Voltage (Vac) 260~530(>304Vac 100% load)
THDu ≤5%
THDi ≤3%(100% load ), ≤5%(50% load )
PF ≥0.99
Frequency (Hz) 40-66
Wires 3 phase 3 wires+ground
Applicable battery capacity 100AH~2000AH
OUTPUT
Voltage (Vdc) 240/360
Voltage (Vdc) 180~300 adjustable
Current(A) 400 600 800 1200 1600
Current limit rated current×(20% ~110% )
Voltage regulation ≤±0.2%
Current regulation ≤±1.0%
Ripple ≤±0.13%
Efficiency ≥95%
Parallel performance ≤±1%
Charger Boost and floating (manually and automatically)
OTHER
Insulation monitor DC BUS and DC circuit
Insulation resistor (MΩ) ≥10
Insulation grade Output to ground, input to ground, input to output with 2.5kVAC, no arc in 1 minute
Alarm Battery fault, insulation fault, AC fault, output fault, modular fault, system modular
IP grade IP20
Display LCD
Noise(dB) ≤60dB
ProtectionAC over voltage, sag, DC output over voltage, protection for input phase missing, over load protection, DC
output over current protection, protection for short circuit, over temperature protection
Cooling Fans (speed adjustable)
Dimension (W×D×H) (mm) 800×800×2000 2000×600×2000 2600×600×2000 3200×600×2000
Weight (kg) 400 660 920 1080 1360
● Intelligent DSP control
● Touch screen interface
● Modular N+1 design for easy expansion
● Hot-swappable modules ensure quick and online maintenance
● Intelligent alternately working modules
● PFC technology for high power factor 0.99 and low THDi ≤5%
● DC power application with high efficiency ≥95%
● Flexible communication management: CAN bus and RS485 port
● Voltage/current/capacity is adjustable (Optional)
● Multiple monitor modules are available (Optional)
● IDC data center
● Mobile communication data center
● Banks
● 3G, 4G base station
● Other equipments with 240VDC power source
ZLSeries 240VDC Power System
Telecom Inverter Telecom Inverter
4948
MODEL DJN1000-K DJN1500-K DJN2000-K DJN3000-K DJN5000-K
INPUT
Voltage (Vdc) 40-60
OUTPUT
Capacity (VA) 1000 1500 2000 3000 5000
Power Factor 0.7 (0.8 optional)
Voltage (Vac) 110/220/230±2%
Waveform Sine wave, THD<3%
Frequency (Hz) 50/60±0.5%
OTHER
Panel Display LED indicators show status of inverter’s operation
Protection Low battery, over voltage, overload, short-circuit and over temperature.
Communication
Interfacedry contact dry contact
dry contact+RS232
dry contact+RS232
dry contact + RS232
Dimension(WxDxH) (mm)
440×286×1U 440×360×1U 440×350×2U 440×350×2U 440×440×3U
Weight (kg) 5 6 10 10 14
MODEL DJN3000-P / DJN-S12
INPUT
Voltage (Vdc) 43-60
OUTPUT
Capacity (VA) 3000 (N+X)
Power Factor 0.7(0.8 optional)
Voltage (Vac) 110/220/230±2%
Waveform Sine wave, THD<3%
Frequency (Hz) 50/60±1%
OTHER
Panel Display LED indicators show status of inverter’s operation
Protection Low battery, over voltage, overload, short-circuit and over temperature.
Communication
Interfacedry contact + RS232 (system)
Dimension
(WxDxH) (mm)435×358×2U / 445×335×10U
Weight (kg) 8.5/15
● Compliant with communication standard of AC and DC power supply system
● High performance SPWM inversion technology
● Perfect protection
● Low DC current noise
● Compliant with communication standard of AC and DC power supply system
● High performance SPWM inversion technology
● Perfect protection
● Low DC current noise
DJN series inverters adapt to telecom systems with 48VDC power supply, adopting
high efficiency SPWM inversion technology. DJN series inverter can be connected to
teleprinter, telegraph terminal, wireless paging equipment, data switching exchange, local
exchange, microwave communication equipment, program controlled exchange charging
system, fax machine and all kinds of AC instrument, computer equipment and various
communication equipment. Meanwhile, DJN-K Series inverter "on ECO mode" can be
used for air conditioner, such as 3KVA for 1.5P and 5KVA inverter for 3P air conditioner.
DJN-P inverters adopting rack imbed design so as to be more slinky and tide ,easy to
install 3+1 parallel system for high MPBF, adapt to telecom systems with 48VDC power
supply, adopting high efficiency SPWM inversion technology. DJN-P inverter can be
connected to teleprinter, telegraph terminal, wireless paging equipment, data switching
exchange, local exchange, microwave communication equipment, program controlled
exchange charging system, fax machine and all kinds of AC instrument, computer
equipment and various communication equipment.
DJN-P series parallelable inverter powers,3+1 for redundancy system,being able to
supply high-performance uninterrupted AC power for various precision instruments
DJN-K Series48 Vdc Inverter (1-5kVA)
DJN-P Series48 Vdc Modular Inverter(3-12kVA)
Static Transfer Switch Static Transfer Switch
5150
MODEL KTS010 KTS032
Input voltage(Vac) 110/220±25%
Input frequency(Hz) 50/60Hz±6Hz
Rated output capacity 110V 1kVA/0.7kW 3kVA/2.1kW
Rated output capacity 220V 2kVA/1.4kW 6kVA/4.2kW
Overload 125%, not limited; 150%≥60S
Output voltage(Vac) 110/220±25%
Transfer time (ms) 6-10
Dimension(mm)(W×D×H) 440×286×1U
Weight(kg) 4
MODEL STS33063 STS33100 STS33160 STS33250 STS33400
INPUT
Input way 3φ+N+PE or 3φ+PE
Rated voltage 190/208/220/380/400V/415Vac
Rated frequency 50/60Hz
Input voltage range ±15%
Input frequency range ±10%
OUTPUT
Transfer time (ms) 4ms
Current rating3 phases, 63A per phase
3 phases, 100A per
phase
3 phases, 160A per
phase
3 phases, 250A per
phase
3 phases, 400A per
phase
Overload capacity <150% With load for long time
150%~170% ,15 minutes ; >170% 1.5 seconds
Efficiency(100%linear load) 98%
OTHER
Noise (dB) <55
Protection level IP20
EMC Complies with CE(EN / IEC 62040-2)
Safety and regulatory Complies with CE(EN / IEC 62040-1)
Dimensions(mm)(W×D×H) 600×800×1600
Weight(kg) 125 135 142 146 152
Communication RS485
● Isolated dual AC input
● Accurate synchronization
● Flexible control panel location (Front or Rear);
● It ensures the high MTBF and the system reliability of Inverter system or UPS system
● Strong adaptability for input power
● Accurate synchronized detection system
● Human machine interface--Lovely touch screen
● Your choice for main input power source
● Perfect protection function
● Remote monitor via RS485
STS is applied for various important power supply environments,such as computer
systems, working and fire fighting in buildings,hospitals, malls, hotels, highway, tunnels,
subway, light rail, airport,electric power system, finance, telecommunication and so on.
RACK ATS(1 phase rack automatic transfer switch10-32A/2-6kVA)
STS System(63-400A)
Xiamen Kehua Hengsheng Co., Ltd.
Add: No. 457, Malong Road, Torch High-Tech
Industrial Zone, Xiamen Fujian 361006 China
Tel: +86-592-5160516
Fax: +86-592-5162166
Email: [email protected]
www.kehua.com
Copyright © Xiamen Kehua Hengsheng Co., Ltd 2017. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means
without prior written consent of Kehua Hengsheng Co., Ltd.
General Disclaimer
The information in this document may contain predictive statements including, without
limitation, statements regarding the future financial and operating results, future product
portfolio, new technology, etc. There are a number of factors that could cause actual results
and developments to differ materially from those expressed or implied in the predictive
statements. Therefore. such information is provided for reference purpose only and
constitutes neither an offer or an acceptance. Kehua may change the information at any time
without notice.Version No.: 20170825-01-500
Reliable • Flexible • Responsible