DP300E rev 8.3 1 Show information... Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click the APC logo link to jump back to the previous showed slide. Click the left margin area to jump to the index (“Contents of the presentation”) From the index -links, you may jump to any other subjects. - use the APC-return logo to return to the index slide again .

Upload: brittney-carpenter

Post on 25-Dec-2015

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

1

Show information...Show information...

•Navigation links: Move the cursor across the links and wait for the “hand” symbol

•- then click left mouse key.

•Click the APC logo link to jump back to the previous showed slide.

•Click the left margin area to jump to the index (“Contents of the presentation”)

•From the index -links, you may jump to any other subjects.

• - use the APC-return logo to return to the index slide again .

Page 2: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

2

Silcon DP300ESilcon DP300EOn-lineOn-line

power protectionpower protection

APC presentationAPC presentation

DurationDuration::

Page 3: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

3

It’s a world of It’s a world of riskyrisky

businessbusiness

Page 4: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

4

... 5 minutes... 5 minutes

power down time power down time

in your company !in your company !

Imagine...Imagine...

Page 5: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

Sort

Page 6: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

• Is your business depending

on IT infrastructure?

• What is the cost of IT

downtime?

• Do you have a strategy for

securing up-time?

• Do you have a strategy for

power availability?

5 minutes 5 minutes power down timepower down time

Page 7: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

7

Application

ServersNT, UNIX, Novell etc.

File server

DP300EMainframe

Print

Web

Mail

DP100E

Gateway

Mini Computers DP10E

Windows 95 Windows NT OS/ and others

Enterprise IT InfrastructureEnterprise IT Infrastructure

Policy...Policy...Protection

of the critical

infrastructure

to ensure:

Up-time

Data safety

Availability

Efficiency

Productivity

Is this the situation…?Is this the situation…?

Page 8: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

8

Silcon DP300E SeriesSilcon DP300E Series

ContentsContents

of the of the presentationpresentation

Headlines:

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 9: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

9

Cost of down time

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 10: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

10

Fortune 1000 companies average outage across Fortune 1000 companies average outage across industries that lasts four hours costs….industries that lasts four hours costs….

Source: Find/SVP. Outages includes other than power failures

Cost of IT Power Down timeCost of IT Power Down timeCost of down time

Page 11: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

11

A typical company experiences A typical company experiences 99 outages per year, outages per year, resulting in annual losses of almost resulting in annual losses of almost

(excluding the cost of lost employee productivity). (excluding the cost of lost employee productivity).

Source: Find/SVP. Outages includes other than power failures

Cost of IT Power Down timeCost of IT Power Down time

Cost of down time

Page 12: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

12

Financial Brokerage operations

Financial Credit card operations

Media Pay-per-view

Retail Home shopping (TV)

Retail Home catalog sales

Transportation Airline reservations

Media Tele ticket sales

Transportation Package shipping

Finance ATM fees

Source: Dataquest, Perspective, Sept. 30, 1996

Average industry cost of down timeAverage industry cost of down time

$ 6,45 million

$ 2,6 million

$ 150.000

$ 113.000

$ 90.000

$ 89.500

$ 69.000

$ 28.000

$ 14.500

Cost of down time

Page 13: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

13

...97%...97% of power supply problems are coursed by of power supply problems are coursed by

power disturbances and low supply voltage.power disturbances and low supply voltage.

Source: National Power Laboratories USA

IT Power problems...IT Power problems...Cost of down time

Page 14: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

14

Did You Know?Did You Know?

Power problemsPower problems are the largest single cause of data loss,

5 times more frequent than viruses.

Power problemsPower problems are the second largest (to theft) cause of hardware loss.

Causes of data loss...Causes of data loss...

Source: Contingency Planning

Power problems are preventable...Power problems are preventable...

Cost of down time

Page 15: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

15

Industry Trends Drive Demand for...Industry Trends Drive Demand for...

Increased IT usage:

Internet Internet extranetsextranets EDIEDI E-commerceE-commerce DatabasesDatabases

7 x 24 hours up-timenetwork availability

Utility deregulation

Constant-Constant-Clean-Clean-

PowerPower

Cost of down time

Page 16: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

16

Did you realize that....Did you realize that....

Investment

“nines”

99.9%99.9% uptime per year...

means 525 minutes down time (8½ hours)

99.99%99.99% uptime per year...

means 52 minutes down time

99.999%99.999% uptime per year...

means 5 minutes down time

Cost of down time

Page 17: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

17

Users Require 7 x 24 hours Availability...Users Require 7 x 24 hours Availability...

“As businesses becomes more internationalized,

7 x 24 hours access to computer systems is a

requirement.

E-mail, group-ware, and similar types of services are

becoming business critical,

- and as a result, highly available systems are now

needed by many more organizations.”

IDC, Highly Available Systems Study

Cost of down time

Page 18: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

18

Information availability...Information availability...throughout the enterprise networkthroughout the enterprise network

Regional DatacenterRegional Datacenter Regional Datacenter

Localservers

Localservers

Localservers

Localservers

Localservers

Localservers

Localservers

Localservers

Localservers

Corporate Datacenter

Cost of down time

Page 19: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

19

Enterprise Customer NeedsEnterprise Customer Needs

No shut-down = AvailabilityNo shut-down = Availability

Mainframe class functionality, reliability, Mainframe class functionality, reliability,

availability, and fault toleranceavailability, and fault tolerance

Flexible growthFlexible growth

Round-the-clock, easy manageabilityRound-the-clock, easy manageability

Low cost of ownershipLow cost of ownership

7 x 24 hours system support7 x 24 hours system support

Operate in poor power conditionsOperate in poor power conditions

Cost of down time

Page 20: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

20

On-line 3 phase UPS systems for…On-line 3 phase UPS systems for…

Data Centers

Corporate network

- and industrial

applications

...to protect any company or organization against losing money in case of power failure at...

Lowest operation cost

Lowest installation cost

Highest performances

Cost of down time

Page 21: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

21

PerformancePerformance and and

benefitsbenefits

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 22: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

22

Silcon DP300E SeriesSilcon DP300E SeriesThe product family offers...The product family offers...

Highest efficiency

Lowest operation cost

Performance and benefits

… from 10 to 480 kVA/ kW in one unit

Cubicles for: UPS + Battery packs + isolation and combinations

“Close to perfect”

Page 23: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

23

Silcon DP300E Silcon DP300E

Up to 97% efficiency

Input power factor corrected to 1

No mains repercussions

Full rated output power available in kW

200% overload capacity

Compact and small footprint

Expandable for more Power/ Redundancy

““Close to perfect” Close to perfect” means...means...

Performance and benefits

Page 24: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

24

Silcon DP300E Silcon DP300E

Unique patented APC/Silcon technologyUnique patented APC/Silcon technology

True on-line systemTrue on-line system

No phase compensation requiredNo phase compensation required

Saves you the most money in operationSaves you the most money in operation

Lowest installation costLowest installation cost

“Close to perfect”

Performance and benefits

What more to say about Delta-Conversion…What more to say about Delta-Conversion… ?

Page 25: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

25

Silcon DP300E - power flowSilcon DP300E - power flow

Mains input

Battery

DeltaInverter

MainInverter

Regulating the delta, ± diff. in/out

1. Normal operation

2. Regulated operation

3. Battery operation

4 Recharge battery

Load

Performance and benefits

Delta-Conversion

Page 26: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

26

Repercussionscaused by UPS

Distortion free no repercussions

Mains repercussions...Mains repercussions...

Delta-Conversion Legacy double conversion

Performance and benefits

Page 27: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

27

Silcon DP300E - Silcon DP300E - Input/ output efficiencyInput/ output efficiency

The high efficiency

comes from the

unique

Delta-Conversion

Technology

97%97%

Silcon DP300ESilcon DP300E

Legacy UPS SystemsLegacy UPS Systems

% Load% Load

% Efficiency% Efficiency

Performance and benefits

Page 28: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

28

Energy lossLegacyUPS systems

High efficiencyHigh efficiency

Performance and benefits

Silcon DP300EDelta-ConversionSaves energy

Silcon DP300EDelta-Conversion

UPSUPS

Page 29: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

29

“Would you accept

0.7Power factor?”

Would you accept 0.7 of a pint?Would you accept 0.7 of a pint?

UPSUPS

Performance and benefits

UPSUPS

Page 30: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

30

Delta-ConversionDelta-ConversionOn-Line and high efficiency…?On-Line and high efficiency…?

what´s the trick…?

Performance and benefits

Page 31: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

31

The Energy Saving Trick...The Energy Saving Trick...

Double conversion

4. Floor

5. Floor

Delta Conversion

4. Floor

5. Floor

Performance and benefits

Page 32: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

32

Who makes the trick...Who makes the trick...

The APC-Delta Conversion Technology is today protected by patents.

APC is the exclusive supplier of this technology - DP300E

The technology is not likely to be available from many other UPS-suppliers for some time

Performance and benefits

Page 33: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

33

““close to perfect”close to perfect”

Silcon DP300E Series - technologySilcon DP300E Series - technology

The Delta-Conversion Technology

Performance and benefits

Page 34: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

34

UPS power factor

Headlines:

Cost of down time

Efficiency

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Fans

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Headlines:

Cost of down time

Performances and benefits

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 35: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

35

UPS - power factorUPS - power factor Input - output and loadInput - output and load

The power factor… The power factor…

Load power-factorLoad power-factor

Power factorPower factor

Considerations:Considerations:

UPS Load power factor

LO

AD

INP

UT

Input power-factorInput power-factor Output power-factorOutput power-factor

Power factor

OU

TP

UT

UPS

Page 36: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

36

Silcon DP300E - power factorSilcon DP300E - power factorInput power factor Input power factor

Load (kW)

Input power-factor is always

1 regardless of load...

This means:This means:

High efficiency

Smaller cables

Smaller fuses

No separate phase

compensation required

Lower installation cost

Input power factor

Supply

Power factor

INP

UT

UPS

Page 37: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

37

Silcon DP300E

Legacy UPS system

Silcon DP300E Input Power Factor…Silcon DP300E Input Power Factor…and the installationand the installation

Power factor

Power factor 1Power factor 1- means lower- means lowerinput current input current therefore... therefore...

smaller smaller cables and fusescables and fuses

Page 38: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

38

Silcon DP300E - Output power factorSilcon DP300E - Output power factorkVA and kW - ratings... kVA and kW - ratings...

System rated for...

Unity output power-factor

- means:

Full load capacity specified

in kWatts or kVA at unity PF

Load PF-working range:

0.8 inductive to 0.9

capacitive

Normally smaller UPS size

(compared to competitors)

when pure resistive load

Load

Power factor

OU

TP

UTUPS

Page 39: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

39

The power-factor on UPS loadsThe power-factor on UPS loadswill increase…will increase…

UPS load power-factor…UPS load power-factor…

Depending on type of load

Computer load: 0.6 to1.0 typ. 0.8 (Trend: load power factor 1)

The UPS must always be power-sizedpower-sized to supply the sum of loads in

UPS Load power factor

LO

AD

Load power-factor

Type of load

kVAkVA

Power factor

Page 40: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

40

Power sizing the UPS...Power sizing the UPS...

kVA-loadPower factor on mixed loads

Power factor

60 kVA/ kWPF =1

60 kVA/48 kW

PF = 0.8

Legacy UPS

system

?

DP300E

? 60 kVA60 kVA

UPS size = kVA load

Load 1: (8 kW / 0.8) = …..…….. 10 kVA

Load 2: (18 kW / 0.9) = ………. 20 kVA

Load 3: (30 kW / 1) = ……..…... 30 kVA

Sum of loads…... 56 kW…….……..……. Sum of loads…... 56 kW…….……..……. 60 kVA60 kVA

??70 kVA/ 56 kW

PF = 0.8

Legacy UPS system

?70kVA

UPS size = kVA/ kW load

Page 41: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

41

Power sizing the UPS...Power sizing the UPS...

kW-load

Load 1: = …………..…..….. 10 kW

Load 2: =…………..………. 20 kW

Load 3: = ………..……..….. 30 kW

Sum of loads…………………………. 60 kWSum of loads…………………………. 60 kW

Power factor

60 kVA/ kWPF =1

75 kVA/ 60 kW

PF = 0.8

Legacy UPS system

?DP300E

?75kVA

60 kW

UPS load = Loads/ 0.8

UPS load = Loads/ 1

Power factor on loads = 1

Page 42: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

42

Silcon DP300E - Silcon DP300E - Power sizing the UPSPower sizing the UPS

Power sizing the DP300E UPSPower sizing the DP300E UPS Calculate the sum of the UPS-load in kVA

Define highest phase load

Choose the DP300E having its full load output power equal to - or bigger than the load

Additional considerations..

• Overload capacity• Redundancy• …….

- see the Power Binderfor further details

Additional considerations..

• Overload capacity• Redundancy• …….

- see the Power Binderfor further details

Power factor

Page 43: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

43

Headlines:

Cost of down time

Efficiency

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Fans

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

EconomyEconomy with with

Silcon DP300ESilcon DP300E

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 44: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

44

Purchase PricePurchase Price

Installation CostsInstallation Costs

Operating CostsOperating Costs

Maintenance & RepairMaintenance & Repair

:The total Economy... The total Economy...

Economy

- for a UPS system includes:

Page 45: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

45

Mains repercussion consists of a mains current out of phase Mains repercussion consists of a mains current out of phase with the mains voltage and a distorted mains current.with the mains voltage and a distorted mains current.

Utilities demand a min. PF or require payment for the kVAhUtilities demand a min. PF or require payment for the kVAhinstead of the kWh.instead of the kWh.

Utilities demand distortion filters installed if other powerUtilities demand distortion filters installed if other powerconsumers are disturbed.consumers are disturbed.

Before comparing UPS prices it must be ensured theyBefore comparing UPS prices it must be ensured theyare equal with respect to mains repercussion:are equal with respect to mains repercussion:

Purchase PricePurchase Price

Economy

Page 46: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

46

Purchase PricePurchase Price

““To clean” the mains input current in a legacy UPSTo clean” the mains input current in a legacy UPS system with 6-pulse thyristor rectifier normally involves:system with 6-pulse thyristor rectifier normally involves:

Economy

A 12-pulse rectifier.A 12-pulse rectifier.

A harmonic filter.A harmonic filter.

A phase compensating unit.A phase compensating unit.

OPTION

OPTION

OPTION

Above might increase the Above might increase the purchase purchase

price for the UPS with up to 30%price for the UPS with up to 30%

UPS

Legacy UPSLegacy UPS

Page 47: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

47

The installation costs on the UPS mains input The installation costs on the UPS mains input side are determined by the prescribed input side are determined by the prescribed input fuse for the actual UPS.fuse for the actual UPS.

As a rule a DP300E requires an input fuse one As a rule a DP300E requires an input fuse one step smaller than a legacy UPS system without step smaller than a legacy UPS system without phase compensation. The installation costs are phase compensation. The installation costs are correspondingly lower.correspondingly lower.

High efficiency and unity power factor generally meanslower installation costs on the mains input side of the UPS:

Installation CostsInstallation Costs

Economy

Page 48: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

48

Annual cost savings with Annual cost savings with Silcon DP300ESilcon DP300E

Silcon DP300E compared to legacy UPS system…

– With harmonic filter

– Incl. cost of air conditioning

– Energy price: USD 0.18/kWh

Savings - pay back your UPS investment within 5 years

kVAkVA RatingRating

0

10000

20000

30000

40000

50000

60000

10 20 40 60 80 120 160 240 320 480

Savings USDSavings USD

USD 1472

USD 50 458

Economy

Page 49: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

49

Load power

UPS power losses

Air conditioning

Maintenance & repair

The operating costs come from:The operating costs come from:

Operating CostsOperating Costs

Economy

- Let´s focus the power loss and the savings...- Let´s focus the power loss and the savings...

Page 50: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

50

Power loss costs at 10 kVA...Power loss costs at 10 kVA...

Silcon DP310E

Period:

Efficiency:

Load:

8760 timer, 1 year

95%

100%

Air con. power 33%

Power price: USD 0.18/ kWh

UPS type: DP310E, 10kVA

Power losses = input - output power = (10/0.95)-10 = 0.53 kWCost of power loss: 0.53 x 8760 x 0,18 = USD 835

Cost of air con.: 835 x 0.33 = USD 275

Total to pay: 835 + 275 = USD 11101110

Economy

UPS power losses and air conditioning

have to be paid via the

electricity bill !

Page 51: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

51

Power loss costs at 10 kVA...Power loss costs at 10 kVA...

Legacy UPS

Period:

Efficiency:

Load:

8760 timer, 1 year

90%

100%

Air con. power 33%

Power price: USD 0.18/ kWh

UPS type: A legacy UPS, 10kVA

Power losses = input - output power = (10/0.9)-10 = 1.11 kW

Cost of power loss: 1.11 x 8760 x 0,18 = USD 1750

Cost of air con.: 1750 x 0.33 = USD 578

Total to pay: 1750 + 578 = USD 2328

A yearly saving of 2328 - 1110 = USD 1218

What about 3, 5 & 10 Years ????What about 3, 5 & 10 Years ????

Economy

The same calculation for a legacy UPS system having an efficiency of 90% results in a bill of

Page 52: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

52

Power loss costs at Power loss costs at 30 kVA30 kVA

Period:

Efficiency:

Load:

8760 timer, 1 year

96%

100%

Air con. power

33%

Power price: USD 0.18/ kWh

UPS type: DP300E, 30 kVA

8760 timer, 1 year

88%

100%

33%

USD 0.18/ kWh

A legacy UPS, 30 kVA

Legacy UPS power losses per year(30/0.88 - 30) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 8579

Silcon DP300E power losses per year(30/0.96 - 30) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 2621

Saving with DP300E = 8579 - 2621 = 5958 USD first year

Economy

Page 53: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

53

Power loss costs at Power loss costs at 160 kVA160 kVA

Period:

Efficiency:

Load:

8760 timer, 1 year

97%

100%

Air con. power 33%

Power price: USD 0.18/ kWh

UPS type: DP300E, 160 kVA

8760 timer, 1 year

91%

100%

33%

USD 0.18/ kWh

A legacy UPS, 160 kVA

Legacy UPS power losses per year(160/0.91 - 160) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 33186

Silcon DP300E power losses per year(160/0.97 - 160) kW x 8.760 hour x 0.18 USD x 1.33 air con = USD 10378

Saving with DP300E = 33186 - 10378 = 2280822808 USD first year

Economy

Page 54: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

54

DP300E rev 8.3

Saving money with DP300ESaving money with DP300ECalculating actual costsCalculating actual costs

EconomyData:

Data: Units Enter value Comments

Energy cost USD/kWh 0,17

UPS data:

UPS power size kW 480

Competitor efficiency % 91 Nominal load operation

APC-Silcon efficiency % 97 Nominal load operation

Yearly energy cost to operate: UPS Aircon. Total

Competitor USD 70696 23330 94026

APC-Silcon DP300E USD 22108 7296 29403

Yearly energy cost savings USD 48588 16034 64623

All Warner model

Competitor system efficiency levels were obtained or calculated from commercially-available documentation. Competitor efficiency levels may be lower, i.e., if harmonic filter options are added.

Page 55: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

55

DP300E rev 8.3

Saving money with DP300ESaving money with DP300ECalculate savings for a period of 10 years...Calculate savings for a period of 10 years...

Economy

Page 56: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

56

DP300EDP300E in parallel in parallel

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 57: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

57

DP300E series in parallel operation…DP300E series in parallel operation…

Parallel operationParallel operation

Parallel operation

1 2 3 4 5 6 7 8 9

- for expansion and redundancy or both.

Page 58: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

58

Expansion:Expansion:

- up to 9 units can be connected whenever you need more power.

Redundancy:Redundancy:

- to comply with strict requirements for uninterruptible operation

- oversized capacity

Expansion and RedundancyExpansion and Redundancy

Parallel operation

Page 59: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

59

Advanced Power ManagementAdvanced Power Management

Day 1

Day 2

Day 3

Parallel operation

Optimized redundancy Optimized redundancy operation by control operation by control system.system.

- only systems needed to supply the load are “active”.

- the load can be switched between the systems in a preprogrammed sequence.

Page 60: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

60

Advanced battery Advanced battery managementmanagement

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 61: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

61

Extended battery life time…!Extended battery life time…!

- by “floating voltage compensation”

- by charge voltage / battery temperature compensation

- by advanced battery monitoring, control and alarms

Typical: 2 years more life time !Typical: 2 years more life time !

Silcon DP300E battery life timeSilcon DP300E battery life time

Battery management

Page 62: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

62

Charge voltage Charge voltage

compensatedcompensatedTypical compensation level

from 2.20 to 2.36

Volts/ cell

No compensationNo compensation

Silcon DP300E battery life timeSilcon DP300E battery life time

Temperature °C

Years

Battery management

Page 63: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

63

Power ControlPower Control

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 64: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

64

Silcon DP300E - Diesel back-upSilcon DP300E - Diesel back-up

Diesel / DP300E installation:Diesel / DP300E installation:

Normal back-up time UPS: 5 to 10 minutes After 5 minutes - Diesel connects to DP300E Legacy UPS: 3-5 times over sizing Using DP300E series: no over sizing because:

– the sinusoidal input cause no distortion feed-back– no distortion of supply from tyristors– programmable soft start - step load from battery to

diesel

Power Control

Page 65: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

65

Diesels Best Friend...Diesels Best Friend...

Diesel / DP300E installationDiesel / DP300E installation

Power Control

Mains Supply

Diesel Generator

Input Panel

DP310E - DP340E

SBP Distr. Panel

Page 66: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

66

Diesels Best Friend...Diesels Best Friend...

100 kW

DIESEL

Silcon DP300E

100 kVA

No harmonicsSame size as UPS

100 kVA

DIESEL

TraditionalUPS

300 - 500 kVA

Harmonics3-5 times oversized

Power Control

Page 67: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

67

CommunicationsCommunications and and

operations operations

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 68: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

68

User interfaceUser interface

15 languages15 languages

Communications and operationsCommunications and operations

Key measurements• Utility power• Battery status• Output power• Percent of capacity

Key measurements• Utility power• Battery status• Output power• Percent of capacity

Alarms• Audible alarms for

38 different monitored

functions

Alarms• Audible alarms for

38 different monitored

functions

UPS-events logger• Time stamped events• Log is accessible from

key-pad

UPS-events logger• Time stamped events• Log is accessible from

key-pad

Communication...

Page 69: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

69

PC-software, DP-Soft CDXPC-software, DP-Soft CDX

Communications and operationsCommunications and operations

Shut-down Manager

Makes unattended safe,

automatic shut-down

of your network if battery

back-up time runs out.

Notify connected users

to make safe shut-down.

Shut-down Manager

Makes unattended safe,

automatic shut-down

of your network if battery

back-up time runs out.

Notify connected users

to make safe shut-down.

Communication...

Page 70: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

70

DP view - SNMP AdapterDP view - SNMP Adapter

Communications and operationsCommunications and operations

The SNMP Adapter

• Tools for monitoring networked UPS systems

• Links your DP300E to network (RS232)

• Monitoring your UPS from any network location

• Central control of internetworking equipment like:

Routers, servers, gateways, UPS

The SNMP Adapter

• Tools for monitoring networked UPS systems

• Links your DP300E to network (RS232)

• Monitoring your UPS from any network location

• Central control of internetworking equipment like:

Routers, servers, gateways, UPS

Communication...

Page 71: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

71

Determine the right solutionDetermine the right solution

QuestionsQuestions Do you require monitoring

Do you require shutdown

Number of Servers / Workstations

Network topology

Operating Systems

Communication...

Page 72: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

72

With the right solution...With the right solution...

Communication...

Page 73: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

73

Datasave Acrobat Reader UPSDatasave Acrobat Reader UPS DP-SOFT CDX / DP-SOFTDP-SOFT CDX / DP-SOFT

Communication...

Page 74: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

74

Orderly shutdown of one computer...Orderly shutdown of one computer...

Stand alone architectureStand alone architecture

Communication...

RS232

PC

Power

UPS

Page 75: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

75

Orderly shutdown

of one computer…

Broadcast to clients

on the network...

Stand alone architectureStand alone architecture

Communication...

Server

Client

UPS

Client

Page 76: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

76

Orderly shutdown of more Orderly shutdown of more computers...computers...

DP-SOFT CDX - Master/SlaveDP-SOFT CDX - Master/Slave

UPS Power

RS232

Network

Master

ClientsSlaves

Communication...

Page 77: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

77

UPS

Server 1 Server 2 Server 3 Server 4 Server 5 Server 6

Shutdown of more computers…Shutdown of more computers…

– For all OS supported by Soft+

– Daisy chainable

Multi-Link UnitMulti-Link Unit

Communication...

Page 78: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

78

14

NMS Application (Snap-in)

NMS

SNMP

TCP/IP

Network Driver

Console User interface NTMonitoring/Shutdown CoreDriver INI FilesUPS Proxy Sub AgentTCP/IPNetwork Driver

Console User interface NTMonitoring/Shutdown CoreDriver INI FilesUPS Proxy Sub AgentTCP/IPNetwork Driver

Monitoring your UPS Monitoring your UPS

through the network...through the network...

NMS Sub Agent for Novell, NT & OS/2NMS Sub Agent for Novell, NT & OS/2

Communication...

Page 79: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

79

NetNet workworkMonitoring your UPS Monitoring your UPS through the networkthrough the network

DP-View SNMP adapterDP-View SNMP adapter

Communication...

Page 80: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

80

Graphical user interface (GUI) for HP Graphical user interface (GUI) for HP Open View (NMS system) Open View (NMS system)

22

DP-View NavigatorDP-View Navigator

Windows 95Windows NTHP UNIX

Communication...

Page 81: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

81

DP - Dial UPSDP - Dial UPS

Monitoring your UPSMonitoring your UPS

- through the Public Telephone Network...- through the Public Telephone Network...

Control Centre

Mobile Phone Pager

DP-Dial UPS

RS232

RS232

Public TelephoneNetwork

Service Technician

LocalNetwork

Communication...

Page 82: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

82

Power AdministratorPower Administrator

Communication...

UPS Power

RS232

Relay

DP-SOFT+ DP-SOFT+ DP-SOFT+ DP-SOFT+

Local MonitoringDP-SOFT CDX

Network

NMS

Power Administrator 800

Page 83: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

83

Environment AdministratorEnvironment Administrator

Smoke Power Temp Lightning Air Conditioning Intruder Water UPS

Environment Administrator

Pager

Modem

Network ManagementStation

Communication...

Page 84: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

84

DP300E rev 8.3

Minimizing the environmental impact...Minimizing the environmental impact...

Green Power with Green Power with Silcon DP300ESilcon DP300E

Green Power with Green Power with Silcon DP300ESilcon DP300EThe green aspects...

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 85: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

85

Power consumption

Low heat dissipation

Smaller installation cost

No mains repercussions

- by highest efficiency - less CO2-pollution from your power plant

- by highest possible power factor “1” saves fan energy

- due to the high efficiency -smaller cables and fuses

- saves costly EMC filters and energy losses

Longer battery lifetime - charge-voltage relative to battery temperature

Small space requirement - compact cabinet including many features as standard

Recyclable materials - No PVC´s

Green Power with Green Power with Silcon DP300ESilcon DP300E

Green Power with Green Power with Silcon DP300ESilcon DP300E

Green Power means saving resources in…Green Power means saving resources in…

The green aspects...

Page 86: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

86

Silcon DP300E - Silcon DP300E - EfficiencyEfficiency

Highest

efficiency

…saves energy

resources

…lower CO2

emission

97%

Silcon DP300E

Legacy UPS Systems

% Load

% Efficiency

The green aspects...

Page 87: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

87

Green Power with Green Power with Silcon DP300ESilcon DP300E

Charge voltage

compensated

...less battery

resources

No compensation

Temperature °C

Years

The green aspects...

Extended battery lifetime…

Page 88: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

88

Power factor 1

...less installation

resources

…less power

dissipation

Load (kW)

Input power factor

Green Power with Green Power with Silcon DP300ESilcon DP300EThe green aspects...

Power factor - “1”Power factor - “1”

Page 89: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

89

APC Silcon Division is the APC Silcon Division is the first UPS vendor withfirst UPS vendor with

ISO 14001 CertificationISO 14001 Certification

Green Power with Green Power with Silcon DP300ESilcon DP300EThe green aspects...

DET NORSKE VERITASENVIRONMENTAL SYSTEM CERTIFICATE

Page 90: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

90

ServiceService

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 91: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

91

AGS - AGS - 7. Division in APC7. Division in APC

AAPCPC

GGLOBALLOBAL

SSERVICEERVICE

Service

Page 92: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

92

AGS policyAGS policy

Consistent high quality Consistent high quality

““on site” service” on site” service”

- world wide- world wide

Service

Page 93: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

93

AGS - program...AGS - program...

Custom designed

service solutions

Service program from

buying process to

lifecycle of your UPS

Factory Acceptance Test

FAT

Service response time:within 24 hours

Every service call is completedwith a service report

Service

Page 94: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

94

Service productsService products

Premium Power Reliability package

Essential Power Reliability package

Annual Maintenance Program

Start-Up Service

Service

Page 95: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

95

Check of the system 1 - 2 times a year

Exchange of the battery at specified intervals

Exchange of the fans at specified intervals

The maintenance and repair costs are very different

- some gambles and do nothing - if lucky they have no costs.

- Others take out a complete maintenance and repair

insurance with a yearly fee of 20 - 25% of the UPS price.

The maintenance is normally consisting of:The maintenance is normally consisting of:

Maintenance & RepairMaintenance & Repair

Service

Page 96: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

96

AccessoriesAccessories

Headlines:

Cost of down time

Efficiency

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Fans

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 97: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

97

Battery cubicles BDPBattery cubicles BDP

Modularized cubicles for housing batteriesModularized cubicles for housing batteries

Matching cubicles from Matching cubicles from

DP310E to DP380EDP310E to DP380E

Battery storage

Easy battery accessibility

Easy to install

Small foot print

Clean cabinet design

Accessories

Page 98: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

98

Galvanic isolated transformersGalvanic isolated transformers

Modularized cubicles for housing transformers

Matching cubicles Matching cubicles

for all DP300E unitsfor all DP300E units

Transformer storage for

galvanic isolation

transformers

Accessories

Page 99: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

99

Remote displayRemote display

A convenient tool for the Facility ManagerA convenient tool for the Facility Manager

Matching the whole Matching the whole

DP300E familyDP300E family

Remote surveillance of UPS

Information identical to

UPS Display

Alarm features

Surveillance tool only

Operation distance - 25m

Accessories

Page 100: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

100

Service bypass panel -SBP300EService bypass panel -SBP300E

Bypass panel for efficient Bypass panel for efficient installation and safe installation and safe

maintenancemaintenance

Safe bypass operationSafe bypass operation

Switch panel for off-line operation

Intelligent communication to DP300E eliminates fault operation

Signal lamps indicate proper operation of the panel

Accessories

Page 101: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

101

Service bypass panel - SBP300EService bypass panel - SBP300E

Configurations...Configurations...

System input System output

Parallel/ Redundant System System input System output

Single System

Accessories

Page 102: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

102

Fuse box - MCCBFuse box - MCCB

Guarding the Silcon DP300E external battery bankGuarding the Silcon DP300E external battery bank

Safe battery Safe battery

installationinstallation

Protects against electric shocks

Enhances safety with coiling

and tripping facilities

Accessories

Page 103: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

103

Technical DataTechnical Data

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 104: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

104

Silcon DP300E: 10 - 480 KVA 3-phaseSilcon DP300E: 10 - 480 KVA 3-phase

120 kVA160 kVA240 kVA320 kVA480 kVA

400V

External Batteries

60 kVA80 kVA

400V

External Batteries

10 kVA20 kVA40 kVA

400V

Built-in Batteries

Technical data

- click for 208/ 480V data

Page 105: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

105

Silcon DP300E - PerformancesSilcon DP300E - Performances version 3x380/ 400/ 415Vversion 3x380/ 400/ 415V

Output power, kW/ kVA 10

Full load output current, Amp. 14.5

Type - Type - (version 3x380/ 400/ 415V)(version 3x380/ 400/ 415V)

Max input current, Amp. 18.9

Efficiency AC to AC, 100% load, % 94.8

20

29.0

37.6

95.5

40

57.7

74.7

96.5

60

87

112

96.1

80

115

147

96.5

DP310EDP310E DP320EDP320E DP340EDP340E DP360EDP360E DP380EDP380E

Typical losses, nominal load, kW 0.5 0.9 1.5 2.4 2.9

Type - Type - ((version 3x380/ 400/ 415V)version 3x380/ 400/ 415V) DP3120EDP3120E DP3160EDP3160E DP3240EDP3240E DP3320EDP3320E DP3480EDP3480E

Output power, kW/ kVA 120

Full load output current, Amp. 173

Max input current, Amp. 219

Efficiency AC to AC, 100% load, % 95.8

160

231

293

96.3

240

346

450

96.3

320

462

582

96.8

480

693

874

96.8

Typical losses, nominal load, kW 5.3 6.2 9.2 10.6 15.9

Technical data

- click for 208/ 480V data

Page 106: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

106

Silcon DP300E - General SpecificationsSilcon DP300E - General Specifications version 3x380/ 400/ 415Vversion 3x380/ 400/ 415V

Static bypass switch Built-in

Communication Interface Built-in

GeneralGeneral Specifications - (version 3x380/ 400/ 415V)

Ambient temperature 0-40 °C (above 25 °C the battery life time is reduced)

Humidity Max 95% (non condensing)

Protection Class IP 30

Safety,CE EN50091-1

UL 1778

EN50091-2

Advanced bat. Monitoring Programmable

Auto restart Programmable

CE, Emission and Immunity

Technical data

- click for 208/ 480V data

Page 107: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

107

Silcon DP300E - Technical input dataSilcon DP300E - Technical input data version 3x380/ 400/ 415Vversion 3x380/ 400/ 415V

Input voltage 3x380/ 400/ 415

Input tolerance, mains opr. ± 15%

InputInput specifications - (version 3x380/ 400/ 415V)

Input tolerance, bypass opr. ± 10% (standard) 4, 6, 8, % prog.

Input frequency 50 Hz ± 6% (standard), 0.5-8% prog.

Input power factor > 0.97 (load 25%), >0.99 (load 100%)

Technical data

- click for 208/ 480V data

Page 108: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

108

Silcon DP300E - Technical output dataSilcon DP300E - Technical output data version 3x380/ 400/ 415Vversion 3x380/ 400/ 415V

Output voltage 3x380/ 400/ 415

Output tolerance ± 1% static, sym. load

Output specifications Output specifications - (- (version 3x380/ 400/ 415V)version 3x380/ 400/ 415V)

tolerance ± 3% static, asym. load

Voltage distortion Max 3% linear load

tolerance ± 5% 0-100% load step

Max 5% non-linear loaddistortion

Load power factor 0.9 lead to 0.8 lag

Output frequency 50 Hz (mains synchronized)

± 0.1% free funning

Overload capacity, mains opr. 200% - 60 secs., 125% - 10 min.

batt. opr. 150% - 30 secs.,

DP310E - DP 3320E bypass opr. 1000% - 500 msec.

DP3480E bypass opr. 660% - 500 msec.

Technical data

- click for 208/ 480V data

Page 109: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

109

Benchmarking 10kVA systemsBenchmarking 10kVA systems

Technical data

- click for 208/ 480V data

Product

Output power 10 kW / 10 kVA 8 kW / 12 kVA 8 kW / 12 kVA 8 kW / 12 kVA

Input voltage 208 208 208 208

Run Time (Full Load)

16 - 30 min. 7 - 18 min. 8 min. 8 - 10 min.

AC to AC efficiency 94.8% 89% 89% N/A

Power Factor 0.99 0.96 N/A 0.96

Acoustic noise 57dBA 57dBA 57dBA 57dBA

Dimensions (in)

High 55.12 28.10 36.00 62.00

Width 23.62 34.00 20.50 41.00

Depth 31.50 28.60 23.00 27.00

Weight 803 lbs. 920 lbs. 590 lbs. 702 lbs.

APCDP300E

Exide Powerware

Plus 18

MGEEPS 3000

LiebertUPStation S3

Page 110: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

110

Silcon DP300E: 10 - 500 KVA 3-phaseSilcon DP300E: 10 - 500 KVA 3-phase

100 kVA(160 kVA)(320 kVA)(500 kVA)

External Batteries

60 kVA80 kVA

External Batteries

10 kVA15 kVA20 kVA30 kVA40 kVA

Built-in Batteries

200V, 208V & 480V 200V, 208V & 480V 480V

Technical data

- bypass 208/480V technical data

Page 111: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

111

Silcon DP300E - PerformancesSilcon DP300E - Performances version 208V/ 480Vversion 208V/ 480V

Output power, kW/ kVA 10

Full load output current, Amp. 27.8

Type - (version 208V)

Max input current, Amp. 37.5

Efficiency AC to AC, 100% load, % 93.6

15

41.6

56.3

93.6

20

55.5

75.0

94.5

30

83.3

113

94.7

40

110

150

95.0

DP310E DP315E DP320E DP330E DP340E

Typical losses, nominal load, kW 0.7 1.0 1.2 1.7 2.1

Efficiency AC to AC, 50% load, % 91.9 90.0 92.0 92.1 93.8

Output power, kW/ kVA 10

Full load output current, Amp. 12

Type - (version 480V)

Max input current, Amp. 15.6

Efficiency AC to AC, 100% load, % 94.3

15

18

23.5

94.3

20

24.1

31.3

94.9

30

36.1

47.0

94.3

40

48.1

62.5

95.0

DP310E DP315E DP320E DP330E DP340E

Typical losses, nominal load, kW 0.6 0.9 1.1 1.8 2.1

Efficiency AC to AC, 50% load, % 91.3 91.5 93.3 90.8 92.9

Technical data

- bypass 208/480V technical data

Page 112: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

112

Silcon DP300E - General SpecificationsSilcon DP300E - General Specifications version 208V/ 480Vversion 208V/ 480V

Static bypass switch Built-in

Communication Interface Built-in

General Specifications (version 208V/ 480V)

Ambient temperature 32-104 °F (above 77 °F the battery life time is reduced)

Humidity Max 95% (non condensing)

Protection Class IP 30

Safety,CE EN50091-1

Safety, UL 1778

EN50091-2

Advanced bat. Monitoring Programmable

Auto restart Programmable

CE, Emission and Immunity

Backfeed protection Built-in

Technical data

- bypass 208/480V technical data

Page 113: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

113

Silcon DP300E - Technical input dataSilcon DP300E - Technical input data version 208V/ 480Vversion 208V/ 480V

Input voltage 3x208V/ 3x480V

Voltage tolerance, mains opr.

± 15%

Input specifications (version 208V/ 480V)

Voltage tolerance, bypass opr.

± 10% (standard) 4, 6, 8, % prog.

Input frequency 60 Hz ± 6% (standard), ± 0.5-8% prog.

Input power factor > 0.97 (load 25%), >0.99 (load 100%)

Technical data

- bypass 208/480V technical data

Page 114: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

114

Silcon DP300E - Technical output dataSilcon DP300E - Technical output data version 208V/ 480Vversion 208V/ 480V

Output voltage 3x208V/ 480V

Output tolerance ± 1% static, sym. load

Output specifications (version 208V/ 480V)

tolerance ± 3% static, asym. load

Voltage distortion Max 3% linear load

tolerance ± 5% 1-100% load step

Max 5% non-linear loaddistortion

Load power factor 0.9 lead to 0.8 lag

Output frequency 60 Hz (mains synchronized)

± 0.1% free funning

Overload capacity, mains opr. 200% - 60 secs., 125% - 10 min.

batt. opr. 150% - 30 secs.,

bypass opr. 125% - cont.

bypass opr. 1000% - 500 msec.

Technical data

- bypass 208/480V technical data

Page 115: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

115

DP300E rev 8.3

Benchmarking 10kVA systemsBenchmarking 10kVA systems

Product

Output power 10 kW / 10 kVA 8 kW / 12 kVA 8 kW / 12 kVA 8 kW / 12 kVA

Input voltage 208 208 208 208

Run Time (Full Load)

16 - 30 min. 7 - 18 min. 8 min. 8 - 10 min.

AC to AC efficiency 94.8% 89% 89% N/A

Power Factor 0.99 0.96 N/A 0.96

Acoustic noise 57dBA 57dBA 57dBA 57dBA

Dimensions (in)

High 55.12 28.10 36.00 62.00

Width 23.62 34.00 20.50 41.00

Depth 31.50 28.60 23.00 27.00

Weight 803 lbs. 920 lbs. 590 lbs. 702 lbs.

APCDP300E

Exide Powerware

Plus 18

MGEEPS 3000

LiebertUPStation S3

Technical data

- bypass 208/480V technical data

Page 116: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

116

Customer Customer references references

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 117: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

117

Insurance's - CodanInsurance's - Codan

Statement…

"As an Insurance company, we always rate security highly and therefore the security of the data in our computers must also be at the highest level”

Phrases from the statement:

– We protect all our business data with UPS equipment from Silcon.

– Before choosing Silcon we analysed 2 different suppliers.

– Several power-down situations has been

handled by the Silcon equipment in battery back-up mode or by controlled shut-down.

– In the end - it is a matter of finance

Codan Network - Mr. Lars M. Anker Section Leader, Denmark

Codan is one of Denmark’s biggest and best consolidated insurance companies.Codan has branches throughout the country and the concern has about 2000 employees. The Codan concern comprises banking as well as the insurance business.

Customer references

Page 118: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

118

Customer ReferenceCustomer ReferenceBankdata - DenmarkBankdata - Denmark

BankingLloyds Bank - London

Annual savings USD 140, 000.-

Bankdata, Denmark

Ove vestergaard, Managing Director,Bankdata

Mr. Julian Baarwell, Lloyds Bank Engineering Manager

Lloyds Bank - London

Installation: 2.7 megawatt of Silcon UPS supplies

“Our original calculations showed

that we would save USD 70,000 in electricity

bills every year. That wasn’t right

Page 119: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

119

HitachiSemiconductor GmbH

One of the biggest supplier of electronic components in the world.

• 330.000 employees

• 6 billion USD in turn over

Peter NikonowitchHitachi, Tyskland

Semiconductors - Semiconductors - HITACHIHITACHI

Peter Nikonowitch says…

“Quality and safety comes first”

“10 milliseconds of power down is fatal for a whole production batch.

Beside the power security we have achieved essential savings in power consumption.

The technology and the environmental aspects we have achieved with the Silcon DP300E product has also been decisive”.

Customer references

Page 120: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

120

IT ServicesIT ServicesIBM Megacentre in Portsmouth UKIBM Megacentre in Portsmouth UK

IBM chose Silcon DP300E systems

IBM´s European and Middle East/African organizationhave put their trust in the safetyof their business data in the handsof APC/Silcon-UPS.

“If you have 6 Mega watt to back-upthe efficiency of the UPS system is essential.”

Chris Hayes, UPS ConsultantIT Infrastructure Services

Installation:

6 x DP3440 in parallelCapacity: 2 x 2.64 MWAdditional: 540 kW on vital systems12 minutes back-up at a load of 6 MW2.5 MW generator back-up

“We can’t afford any drops at all”

Customer references

Page 121: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

SHELL, Danmark

“We power ensure the whole control center with the Silcon UPS systems.Most essential for us was the low heat emission - meaning lower installation and operation costs”.

SHELL refinery in Fredericia

ChemicalsChemicalsShellShell

Shell in Frederica has the most advanced control system in the world !

Customer references

Page 122: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

122

Air transportationAir transportationRDM LufthansaRDM Lufthansa

Statement…

“For RDM Lufthansa security and reliability are very important. With round-the-clock working and on-line access to RDM Lufthansa's host system in Germany, a power failure would have very serious financial consequences for the airline company”.

RDM Lufthansa, India

Customer references

“We simply can't afford to go down because of a

power cut.APC´s Silcon UPS systems gives us reliability and we

get the service we need through El-Pan, APC's

partner in India”.

Page 123: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

123

HospitalsHospitalsLänssjukhuset Ryhov HospitalLänssjukhuset Ryhov Hospital

“It is of vital importance for hospitals to have high quality and constant power supply.

Without power - it is impossible for doctors to help many of there patients - babies in incubators, patients undergoing surgery or dialysis etc.

It is obvious that we put extreme demands on our UPS supplier”

“I feel secure in having chosen Silcon and I know that each UPS system is produced with care and absolute precision

Moreover the Silcon equipment is environmentally friendly with extreme high efficiency”

Länssjukhuset Ryhov is a Swedish hospital.The 200,000 m2

hospital was opened in 1988 and today employs 3700 people.

Mr. Bengt JönssonTechnical Engineer

Customer references

Page 124: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

124

Banking Banking Bankdata - DenmarkBankdata - Denmark

Statement…“We have always maintained the policy that one power cut per year is acceptable only. But since we have recently suffered three successive power cuts, we took the decision to install our own emergency power supply”.

The project:396 batteries - 11 tons - 10 minutes back-up time4 Silcon DP300E UPS systems1 Diesel generator - takes over after 30 seconds

Ove Vestergaard, Bankdata, Managing Director, …

”We have estimated that in 1996 alone, the Silcon installation has saved us some USD 4 million worth of losses by protecting critical infrastructure against power failures”

Erik Nielsen, Bankdata’s Installation Manager says...With the Silcon equipment we have installed some of the best electrical energy transformer systems with full back-up service.Bankdata can now be added to an already impressive client list.Bankdata is a data centre for 18 banks - employing 225 people - supporting banks with modern EDP systems.

Bankdata, Denmark

Silcon Technology

Customer references

Page 125: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

125

American ExpressLloyds Bank, UKBGZ PolandQingdao City Bank, ChinaCzech National BankPekao, PolandOrel Bank, RussiaCrediplus, PortugalUBS, SwitzerlandInter-Europa Bank, HungarySlovak Stock ExchangeRaiffeisenbank, GermanyGenerali, IrelandCitibank, DenmarkChase Manhattan Bank, USADen Danske Bank, DenmarkBank of New ZealandBloomberg, JapanBCA, IndonesiaDresdner Bank, Germany

National Bank of SlovakiaBank OTP, HungaryXiosbank, GreecePacific Finance,ThailandUlster Bank, IrelandMBNA Bank, UKSBG, SwitzerlandAlliance & Leicester, UKFINIbanco, PortugalJordan Gulf BankAllied Irish Bank, IrelandParibasSydbank, DenmarkDeutsche Bank, Germany

BankingBanking

Customer references

Page 126: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

126

Tele communicationTele communicationTelia - UKTelia - UK

””APC´s Silcon products are probably going APC´s Silcon products are probably going to the front in UPS support for to the front in UPS support for telecommunications”telecommunications”

“The Silcon UPS is like having a gentle giant

hidden in your cupboard that you can pull out when ever you fancy. So we are very happy with the Silcon

product".

Mr. Paul MulvenneFacilities Manager

"The main reason for choosing Silcon UPS systems over the

competitors considered, was the electronics.

The electronics gives advantages and behaves in a much more

structured way. This meets the needs of the

Telecoms.

Customer references

Page 127: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

127

Portugal PTTNokiaFinland PTTEricsson LMTelecom EireannMotorolaMCI USATeleDanmarkSonofonFrance TelecomTelecom New ZealandT.T. Mobiles IndiaAT&TPolish TelecomSwiss PTTGlobal OneAlcatelSwissphoneTeleDanmark MobilVEW Telnet D

FujitsuBritish TelecomPolish Mobile PhoneTeletas TurkeyTelex-Exchange IndonesiaCity Telephone ChinaTaiyan PTT ChinaPTT ChinaGEC AlsthomBosch TelecomTelesystem MobilfunkTMI Telecom ItaliaTeliaDutch PTTOrange TelecomVODAphoneDeutsche TelecomPost UngarnTele NordiaTelecom Malaysia

Tele communicationsTele communicationsCustomer references

Page 128: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

128

Installation Installation

Headlines:

Cost of down time

Efficiency

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Fans

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Headlines:

Cost of down time

Efficiency

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Fans

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 129: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

129

Consider:Consider:

Size Is there enough space on the installation site? Will it go through the door? Is there free space for servicing and

operation?

Weight Will the floor carry the load? Can the lift carry the load? How can it be lifted off the pallet?

Fuses Which fuses to use in installation?

Cables What cable size to use in the installation? And where to connect to the DP300E (cable entry)?

Where to find information:

Spec SheetInstallation GuideQuick Reference

Data SheetInstallation GuideQuick Reference

Installation GuideQuick Reference

Installation GuideQuick Reference

Installation of DP300EInstallation of DP300E

Installation

Page 130: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

130

Where to find information:Where to find information:

Installation Guide Quick Reference

Please note on ordering sheet

Consider:Consider:

Heat dissipation:• Ensure correct dimensioning of the air

conditioning system

Diesel generators:• Due to the sinusoidal input current a diesel

generator of only 1.3 times the size of the DP300E can be used. (A diesel for a traditional UPS must be 3-5 times the size of the UPS)

• For very sensitive diesels the DP300E series can be programmed for soft start (diesel

modification).

Installation of DP300EInstallation of DP300E

Installation

Page 131: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

131

Consider:Parallel operation:

Parallel to increase output power. Redundancy to increase safety. Up to four standard systems can be paralleled (only parallel boards needed). With external static switch up to nine systems

can be paralleled (parallel boards and external static switch needed.

Parallel systems can have common or separate batteries.

Batteries: Configuration sheet for Johnson control

batteries are available. Battery dimensioning for special applications

has to be handled from case to case.

Where to find Where to find informationinformation::

Installation GuideAPC Tech Support

Installation GuideAPC Tech Support

Installation of DP300EInstallation of DP300E

Installation

Page 132: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

132

Review Review

Headlines:

Cost of down time

Efficiency

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Fans

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Headlines:

Cost of down time

Performances and benefits

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review

Page 133: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

133

....On-line UPS ?

....High efficiency ?

....Full kW Rating ?

....No mains repercussions ?

....Input power factor correction ??

What does it mean ?What does it mean ?

Review

Page 134: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

134

Delta-conversion UPS systems...Delta-conversion UPS systems...

Highest up-time on IT equipment

Low operation costs

Low installation costs

More protection capacity

Environmentally friendly UPS system

Silcon DP300E benefits... Silcon DP300E benefits...

Review

Page 135: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

135

Silcon DP300ESilcon DP300E Delta TechnologyDelta Technology

Silcon DP300E benefits... Silcon DP300E benefits...

“Close to perfect”

Review

Page 136: DP300E rev 8.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click

DP300E rev 8.3

136

Questions

End of End of presentationpresentation

Cost of down time

Performance and benefits

UPS power factor

Economy

Parallel operation

Advanced battery management

Power Control - “Diesels best friend”

Communication and operations

Green Power aspects

Service

Accessories

Technical data

Customer references

Installation considerations

Review