Our journey to date has taken 25 years in the field of design, manufacture and installation of water leak detection and environmental monitoring systems.

With the wealth of knowledge gained, J.A.M. can guide you through the design process, manufacture the products and carry out the installation to the exacting timescales of the contracting process and program. We +Arill also support the product and Client with after sales service and preventative maintenance contracts for years to come.

J.A.M. Limited have also been involved with the design, supply, installation & commissioning of electric trace heating systems for a number of years, and have supplied equipment to a vast array of end users and Clients. Although originally taken on board as a supplementary product to our range of environmental monitoring systems, we rapidly gained the reputation of a professional, reliable and cost-effective supplier of trace heating in its own right.

We feel the products within this brochure offer the most cost-effective solutions to current building services requirements and would encourage you to visit our website: www.jam.uk.corn to see our systems in action.

I have taken the step of releasing my personal e-mail address for anyone to contact me with comments or suggestions.

Paul Goodacre Managing Director

[email protected]

Page 3: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Contents

Leakigense

mcitdargl&P'ji

Typical Applications 1

System Introduction 2

Which System is Best for You?

Aqualarm i-Zone

System Design Guide .3 Control Panels Specification and Data............................................................S Detectors 7 'F' Gas Legislation 10 Zoned key Components 11

LeakSense2i

System Design Guide 13 Specification and Data 15 Locating Key Components 17

Aqualarm One Touch

System Design Guide 19 Specification and Data 21 Key Components 24

Networking Systems 25

Universal Detectors 28

Trace Heating 29

Agents and Distributors 32

Our Credentials 33

Page 4: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Typical Applications

Computer Suites LT./Sender Rooms Dealer Floors Data Centres Hotels Kitchen/Toilet & Vending Areas Hospitals (rv1Pli Plant Rooms) Leisure Complexes Supermarkets Listed Buildings Museums Art Galleries Archive Facilities

Sample of aCLialanTl Installations

Bank of England - London CitiGroup- Canary Wharf Barclays Trust- Dubai HSU( - Dubai Credit Suisse - London Microsoft - LondonMeading Dresdner Kleinwort - London 13.T.Centre - London Department of Education - Runcorn Department of Transport - London Hertfordshire Constabulary HQ Greater Manchester Police Global Switch - London, Australia & Hong Kong Natural History Museum - London Science Museum - London Victoria & Albert Museum - London RAF Benson • Oxford Postal Heritage - London Chastleton House • Oxford Marlborough House London Asda Stores - .Glasgow Whittington Hospital - London Leeds University - Leeds DHL - Prague Police Headquarters - Hong Kong

T BANK

1

Page 5: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

System Introduction

aTILalarin

These produce are our latest Zoned range of systems using art addressable method for irrstaliation. Each system will be easier to install with less interconnecting cable used. The control panels can simultaneously monitor our water, oil, refrigerant gas, temperature and humidity detectors The control panels are available as an i-Zone 5, capable of monitoring up to 5 detectors, or as an i-Zone 10/25 capable of monitoring between 10 and 25 detectors. Multiple i-Zane systems tan be networked together. monitored by an 'Aqualarm' One-Touch system master control panel.

LeakAense2i rem, rem LC.101.19r1U.71

A stand alone system capable of monitoring up to 1500rn of cable and able to display the meterage reading relating to the point of contact that water has made with the detection cable with an accuracy of .1- 1 metre. This system dS0 has the added advantage of displaying a meterage reading of any open circuits caused by damage with the same accuracy.

Now also available as a ZLM-500 zoned locating module. a simplified version to allow a network of these units to monitor multiple areas, all connected back to either a 'master' i-Zone panel which will display the alarm conditions and meterage reading of each ZLM•500, or connected to an 'Aqualarrn' One-Touch system that can also display graphic maps of the alarm locations.

amiare.,1044' This is the most comprehensive system we have produced to date We have designed this system to be netvvorked to multiple 'Aqualarm' control panels as well as being able to function as a stand alone control panel. All system functions are displayed on a 12 inch colour touch screen monitor. Powered by a PC based operating system, using Windowste, protocol, all operating manuals, service information and as installed system maps can be stored for future reference.

This system can monitor all 'Aqu alarm' control panels and the full range of 'Aqual arm dctcctors, to deliver the complete package.

2

Page 6: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Connection to arr/SwiaVolt•Ire.e corMaS. R5-46

Mote

CLI1 Flow CI lin Recommended one everyaS metres or

where required WL/1 %Naming Labels.

Recommended one

every 5 metres.

CD-i€ 1,2, S and 1Cm

ZEOL

Interconnecting

wiring to I-Zone Control Panel

CDRE-24 STDI-24

Interconnecting -wiring to i Zone

COMM.! Panel

nne System Design Guide: Perimeter and Footprint Protection

beneath access flooring, using zoned system

Drip Trays

3

Page 7: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Cormerticl to BUS via Volt-free contacts. I15 185

Conduit containing inKreonnOttinG wir6

StorageTank

Iriteroonn,actingwiring to control panel

11,11:4-24

Interconnecting wiring i-Zung

control panel

Otani an! 4I IiQlerel Tray

PrpeWCel<

Interconnecting wiring to i-baneconliol panel

FLI-24

Boiler/Plant Room Application using Detecting Cable and Point Detection

i•Zone Cararol Panel

Nom

CD-K detecting cable 1711.11St lse lostalled on the

outside of lagged pipework

CD-1s held In place by I) ktt cableties.

Fuel Oils/Non-Conductive Liquids

Va Ivo

Float Detector Used in sump/tank applications

Overflow Detector Used in overflow pipework

interccnrecrng wiring ltp E-Zone control panel

4

Page 8: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

ENVFROIRM€NrAL IliONITORN4 SY STE hl •

Control Panel Mode i-Zone 5

The i-Zone Control Panel shall be wall mounted and be of a mild steel construction and powder coated. It will be capable of monitoring the full range of 'Aqua!arm' detectors for water, fuel oils, chemicals, temperature, humidity and refrigerant gases. The control panel is an addressable system capable of monitoring 5 detectors/ addresse5 SiMki taneously

The default detector identification is 70110 -Zone2` etc, however these can be programmed to display customers requirements, up to 24 characters per zone i.e. 'Zone 1 - Room 5 2nd Floor'. This has to be carried out at time of manufacturing.

The control panel can store a 100-alarm event history log into non-volatile memory_ During normal operation, the Green LCD screen will display the current time date together with SYSTEM CLEAR status.

The i-Zone 5 Control Panel can also be linked to a maximum of 5 ZLNI-500 modules, resulting in a single system, monitoring 2500 metres of detecting cable, and in the condition of an alarm, will display a rneterage reading accurate to 14- 1 metre to the point of water contact with cable.

The control panel will be provided with a TEST button, MUTE button and the facility to view the 100-event history log. In an aiarm state, the LCD will display the activated detector identification and a 97db (at 1 metre} audible alarm will sound.

For remote signalling, the control panel will be supplied as standard with the following outputs: RS42,5, Common Alarm, Network Failure, Mains Fail, Rattery Fail A Service Required.

For safety, the control panel is fitted with a key operated door lock and 'power off' door switch.

Main Features 114mm x 64mm Back-lit Green LCD Screen displayl ng:

Current Tirr)e Si Data, System status, Alarm status & available Button functions. Power 'On'. Power Support System ',On'. Service.

System will monitor 5 detectors/addresses or 21.M1.0-500's, simultaneously, Last 100 Event Memory_ Alarm Siren 97db IQ 1m. Alarm horn 'Mute', 'Test' & another functions displayed or LCD when required, Lockable mild steel cabinet. Powder Coated RAL7035. Door interlock safety switch. Mains Fail Battery Back Up. ill Hours)

Outputs P.S4B5

Volt -free outputs Common Alarm. Network Fall. Mains Fail. flattery Fa Service.

Mains Voltage Ra rigs 120 or 240 volts A.C, 02 50 or 60 Hz.

Normal Operating Voltage 24 volts D.C. internally supplied

Operating Temperature Range 0 to 50 deg.C,

A pprovals B5 EN ISO 14001 and ISO 9001: 1994. EMC Directive 89i3361EEC, CE Marked.

Cabinet Dimensions Height 330mm Width 255 mm Depth BSmm

5

Page 9: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Control Panel Model i-Zone 10125

The i-Zone Control Panel shall be wall mounted and be of a mild steel construction and powder coated It will be capable of monitoring the full range of 'Aqua I arm' detectors for water, fuel oils, chemicals, temperature, humidity and refrigerant gases. The control panel is an addressable system capable of monitoring 10-25 detectors addresses simultaneously.

The default detector identification is 'Zoner, 'Zone2' etc, however these can be programmed to display customers requirements, up to 24 characters per zone i.e. 'Zone I - Room 5 2nd Floor', This has to Oe carried out at time of manufacturing,

The control panel can store a 100-alarm event history log into rion-volatile memory_ D Wring normal operation, the Blue LCD screen will display the current time & date together with SYSTEM CLEAR status.

The i-Zone 10-25 Control Panel can also be linked to a maximum of 10-25 ZLM-500 modules, resulting in a single system. monitoring between 5000 and 12500 metres of detecting cable, and in the condition of an alarm, will display a mete rage reading accurate to 41- 1 metre to the point of water contact with cable.

The control panel will be provided with a TEST button, MUTE button and the facility to view the 100-event history log. In an alarm state, the LCD will display the activated detector identification and a 97db at 1 metret audible alarm will sound.

For remote signalling. the control panel will be supplied as standar d with the following outputs: 8S485., Common Alarm, Network Failure, Mains Fail, Battery Fail & Service Required.

For safety, the control panel is fitted with a key operated door lack and 'power oft' door switch,

Main Features 114mm x 54rrim Back-lit Blue LCD Screen displaying:

Current Time & Cate, System status, Alarm status & available Button functions_ Power 'On', Power Support System 'On'. Service.

System will monitor 10-25 detectors or addresses or ZLM-590's., simultaneously. Last 100 Event Memory. Alarm Siren 97db 6:Jt 1m. Alarm ham 'Mute', 'Test' & all other functions displayed on LCD when required, Lockable mild steel cabinet. Powder Coated FiAL7435. Door interlock safely switch. Mains Fail Battery Back Up. (4 Hours)

Outputs

RS485

Volt free outputs Common Alarm Network rail. Mains Fail. Battery Fail. Servi.ce

Mains Voltage Range 120 or 240 volts A,C 5.1=I or 60 H2.

Normal Operating Voltage 24 volts D.C. internally supplied.

Operating Temperature Range G. to 50 deg C.

Ap provals. as DI ISO 14091 and ISO 9001: 1994. EMC Directive 3g/336/EEC, CE Marked.

Cabinet Dimensions Height 330rrum Width 255mrn Depth 35mrit

6

Page 10: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Detector Model STDi-24

The STDi-24 Point of Use Water Detector shall comprise of TWO components, the detector

module and the point detector, connected together via a lm jumper cable. Roth the Detector

• Module and the Point Detector shall be manufactured from STAREX General ABS (SD-0150)

plastic. The Detector Module shall house the electronic circuitry and the Point Detector shall house the gold plated detection pins.

The jumper cable shall be connected to the top of the Point Detector via a 3-pin plug and socket_ A stabilising bar shall be supplied as a means of fixing the Point Detector to the floor surface.

Conductive fluid touching the two detection pins simultaneously will cause the detector to enter an alarm condition. Alarm status and monitoring is via a network, using a CAN bus system.

Normal Operating Voltage 24 volts d.c,

Quiescent Current <10mA, per detector.

Alarm Current 0DrnA per detector

Detector oscillator frequency LrkFix

Voltage at detection cable outlet 2 volts e.c.

Recommended interconnecting cable core 0_51nre) screened Twisted Pair tt 120 ohms,

Line-out voltage drop 1.5mVim

Approvals B5 EN l$C 9001:1994, EMC Directive 89/336dEEC CE Marked.

Detector Model CDBi-24

The 'Aqualarm' CORi-24 Zone Detector Module shall comprise a purpose -moulded ABS box, housing the electronic circuitry. At one end of the Module a locking fine socket is fitted to enable connection of the detecting cable. The other end is fitted with a gland for connection to the PCB. A red Alarm LED shall he incorporated in the top of the module.

The red LED will glow to indicate an alarm condition. Alarm status and monitoring is via a network, using a CAN bus system.

Normal Operating Voltage 74 volts

Quiescent Current <10mA. per detector.

Alarm Current <100mA, per deteceer.

Detector oscillator frequency 6k -lr

Voltage at detection cable outlet 2 volts a.c.

Recommended interconnecting cable A cure D.StrenA screened Twisted Pair Q5l 170 ohms,

Line-out voltage drop 1.SmWrn

Approvals BS EN ISO 9001:1994, EMC Directive 69/336/EEC CE Marked.

Detecting Cable Model CD-X

The 'Aeualarm" water leak Detecting Cable shall comprise two flat tinned copper braids separated and protected by hlelegaine self extinguishing nylon 65 sleeves. This type of configuration gives protection to the sensing cores against duet and other types of conductive contamination and mechanical damage. The cable is available in modular lengths of 1, 2, 5 and 10m. Each cable is pre-terminated with a male and female locking line plug and socket. The Detecting Cable can be used on the i-Zone system (for use with CDEli-24) and LeakSense Systems .

Installation Method

Where protection Is required born a liquid leaking from pipework, the Detecting Cable should be secured to the underside of the pipework by cable ties after all vapour seal or thermal protection has been carried out or secured to the floor slab immediately below the pipework with suitable dips or ties.

Where protection is required from a liquid leaking from eceepment, i.e. water cooled computers, chiller plant, air conditioning units etc., the Detecting Cable should be secured to the floor stab around the equipment.

Voltage at Cable Not greater than 2 volts d.c.

Overall cliarnetre of cable Bmm,

Maximum Detecting Cable length Zoned System! 50rn not including interconnecting cable). LeakSense System: 150Drn iincluding leader/jumper cable). ZLM-500, 500m (including leaderjumper cable),

Operating temperature range +1 deg C +85 dog C.

Construction Self extinguishing Polyrnide 6.6 rnonohlaments to ISO 3n5 with sensing cores of flat tinned copper braid.

Colour Grey/blue

Approvals BS EN ISO 9001:1594. EMC Directive 89/33DEEC CE Marked.

7

Page 11: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Detector Model FLi-24

The FLi-24 Liquid Level Detector shall comprise of TWO components. the detector module and the float switch, connected together via a lm jumper cable. Roth the Detector Module and the float switch shall be manufactured in high STAREX General A05 (SD-0150) plastic. The glass filled nylon float switch will be held in place by a sprung clip, secured to the wall at the level desired for the alarm to be activated

The red LED on the detector module %fulll glow to indicate the alarm has activated. Alarm status and monitoring is via a network, using a CAN bus system.

Normal Operating Voltage 24 volts d.c.

Quiescent Current <10mA. per detector.

Alarm Current i00rnA. per detector.

Detector oscillator frequency 6kHa

Voltage to float switch. 2 volts a e

Float switch type

'make on rise or fall.

Recommended interconnecting cable 4 core Li_Smir2 screened Twisted Pair ti2/ k2Clohms

Line-out voltage drop 1,5mV/m

Approvals BS El ISO 9001:1994, EMC Directive 69836/EEC CE Marked.

Detector Model IRDI-24

The IRDi-24 Point of Use Oil Detector shall comprise of TWO components, the detector module and the Point of Use Detector, connected

together via a 1 rn jumper cable. Roth

the Detector Module and the Point of Use Detector shall be manufactured from STAREX General ABS (SD-01S0) plastic, The Detector Module shall

house the electronic circuitry and the Point of Use Detector shall house the Infra-Bed transrnitterireceiver, which shall extend from the bottom of the detector lts height above the reflective sensing area shall be set between 3-5rrm. A reflective area (50mrn dia.) must be painted on the -Floor with paint capable of reflecting light. (e.g. standard white gloss paint) The top of the Point of Use Detector shall be fitted with a sensitivity pot for calibrating the Intro-Red focal point, The jumper cable shall be connected to the top of the Point of Use Detector via a 3-pin plug and socket, A stabilising bar shall be supplied as a means of fixing the Point of Use Detector to the floor surface A red LED will glow to indicate the detection of a substance.

Alarm status and monitoring is via a network, using a CAN bus system.

Normal Operating Voltage 24 volts d.C,

Quiescent Current <10rrIA. per derecriar.

Alarm Current <100mA. per detector.

Detector oscillator frequency 6kH7

Infra-Red probe type Gallium arsenide

Recommended interconnecting cable 4 core acSrnrw' screened Twisted Pair r 120 ohms,

Line-out voltage drop 1,5mWrin

Approvals ES EN ISO 9001:199.1r EMC Directive 8.9/3364EC CE Marked_

Detector Model OFDi-24

The 'Aqualarm' OFD1-24 Overflow Detector shall comprise a STAREX General ABS box (SD-0150) housing the electronic circuitry. The bottom of the ABS box is fitted with a 3/4" BSP threaded connector with two stain I ess ste el sensing probes extending from the end. The connector should be inserted into a 'tee' to enable the probes to sense any water passing through the main over-flow pipe. A red LED shall also be incorporated and will glow to indicate the detection of water. Alarm monitoring and status is via a network, using a CAN bus system.

Normal Operating Voltage 24 valks d

Quiescent Current <I0mA. per detector.

Alarm Current <100mA. per detector.

Detector oscillator frequency 61.cRt

Voltage at probes 2 volts a.c.

Recommended interconnecting cable 4 corer:0.5mm' screened Twisted Pair 43 120 ohms,

Line-out voltage drop 1.5rriVN

Approvals ES EN ISO 9001;1994, EMC Directive 891325/EEC CE Marked.

8

Page 12: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Detector Model IlDi-24

The 'Aqualarmr 1-1De24 Humidity Detector shall Comprise a STAREX General ABS bok -31D-0150) housing the electronic circuitry to detect changes in the level of 'Tumidity and give an alarm signal should the humidity drop below the low level set point, or exceed any of the two high /eve! set points.

Levels can be set between 30% and 100% and are entered via the Control Panel. A red LED shall also be incorporated and will glow to i ndliC ate the detection of a change in humidity outside of the Set levels. Alarm monitoring and status i5 vie a network, using a CAN bus system,

Normal Operating Voltage 24 volts

Quiescent Current <100mA per detector

Alarm Current -4100MA. per detector.

Humidity range 30 • 100%.

Recommended interconnecting cable core 0.5men2 screened Tv,d5led Pair CP 120 ohms..

Line-out voltage drop 1.571V/m

Approvals BS EN ISO 9001:1904, EMC Directive 39/33EdEEC CE Marked.

Detector Model TDi-24

The 'Agualarrre TIDi-24 Temperature Detector shall comprise a STAREX General ABS box (SD. 0150) housing the electronic -circuitry to detect changes in temperature and give an alarm signal should the temperature drop below the low temperature set point, or exceed any of the two high temperature set points_

The "set points' are entered via the Control Panel. A red LED shall also be incorporated and will glow to indicate the detection of a temperature outside of the set points. Alarm monitoring and status is via a network, using a CAN bus system.

Normal Operating Voltage 24 volts d.c. 1111111) Quiescent Current io2OrriA. per detector,

Test/Alarm Current <15OrnA. per detector.

Temperature range 10 • 100 deg. C.

Recommended interconnecting cable 4 core 0.5mm1 screened Twisted Pair itt 120 ohms.

Line-out voltage drop I .5.rnVfm

Approvals B5 EN ISO g001:1934. EMC Directive 8E/336/EEC CE Marked.

Detector Model RGi-xx-24

The 'Agualarrn' RGiocx-24 shall comprise a STAREX General ABS box (51)-C150) housing the electronic circuitry to detect the presence of the nominated refrigerant gas. The alarm threshold can be adjusted via the control panel. A red LED shall also be incorporated and will glow to indicate the detection of refrigerant gas above the set level.

The Detector can detect the following refrigerant gases. (There are a sample of most commonly used, but others are available) R-17, Ft-22, R125, R-134a, R-401 a, 11-401b, R-401c, R-402a, R-4026, R. 403a, R-403b, R-407a, R-407b, R-407c, R 502, Ft-507, R-410a.

Alarm status and monitoring is via a network, using a CAN bus system.

Normal Operating Voltage 24 volts d.c. Quiescent Current <180mA. per detector.

TestJAlarm Current <350mA_ per detector.

Operating temperature range 10 - 100 deg.0

Refrigerant gases se nsed See hit

Recommended interconnecting cable 4 core 0.5rnm? screened Twisted Pair @ 120 ohms.

Line-out voltage drop I.SmVirn

Approvals BS EN ISO 9001:1994, EMC Directive 89/336/EEC CE Marked.

9

Page 13: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

F-Gas Regulation No. 842/2006 Prevention and Detection of Leaks

The European IUniona5 F--.a5 Regulation No. 842/2006 became law on 4th July 2006, and many of the requirements came into force on 4th July 2C07.

F-Cases include all HFC refrigerants such as R134A. and mixtures containing F-Gases such as R407C. R410.0, and 11404A.

if you own equipment containing HFC refrigerants in stationary equipment, you now have new legak obligations under the F-.2 as Regulations.

Below are sections of the requirement that relate to leak prevention and detection.

F-iGas Requirement Date of Effect

Row to implement the requirement

Further Information

Operators of equipment must prevent leakage, ensure leak che:ks are carried out and carryout any necessary repairs 45 soon as possible. Proper refrigerant recovery must alSO he in place_

04.01.2007 1) Works to be carried out by qualified personnel {current requirement Is City & Guilds lon or CITD only). 2) Follow a standard leak check procedure Set by the Commission

www.defra.gov.uki corporate/consult/ f-gasiindex.htm

Opefa tors must ensure systems are checked for leaks: 1) At least annually If more than 3kg charge- 2) At I test once every 6 months if over 30kg. If an automatic leak detection system is installed. they only need to check every 12 months, 3) Automatic leak detection systems MUST be installed on applications with 3.00kg or more, and these systems should be checked every 6 months. If a leak is detected and repaired, further check must be carried out on the repair within 1 month to ensure the repair has been effective.

04.07.2007 11 Personnel Qualified to the levels set out by the Commission can only carry out the checks. 2) install a n automatic leak detection system that meets the requirement set by the Commission {see definition below)

www.dti.gov.uki in novationisustainabilityl fgasesepage28$139/html

Definition of Leak Detection System

Leak Detection System • This meansa calibrated mechanical, electrical or electronic device for detecting leakage of flourinated greenhouse gases, which, on detection, alerts the operator.

You con download the lull Regulation at www.dti.gov.0 kfinnovationfsustain a bi lity/fgasestp age28889intml

10

Page 14: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

i-Zone • Monitor up to 5 detectors • battery back-up internal • Volt-free contact • Mild Mei construction IP54 • Powder coated RAL 7035 Code- 6019

4

I-Zone 1025 • Monitor between 5-23 detectors • Battery back-up internal • Volt-free contact • Mild steer construction IP54 • Powder coated RAL 7035 Code: 10 Zane. 6020 15 Zone: 6021 20 Zone: 6022 25 Zone: 6023

4s.

5TDi-24

OFDi-24 Point of use Detector. Overflow Detector. Coder 6026

Code: 6030

CDIN-24 Zone Module. Code: 6027

IRDi-24 Point of use Infra Red Detector. Code. 6029

RGI-xx-24 Refrigerant Leak Detector. Code: 6031

' .0*

I 'It

TDi-24 2 Stage Temperature Detector. Code:6032

Remote Alarm Panels

Optional Extras

IZ/FIV1-1 Semi-flush Mount Frame for Control Panels. Mild Steel finished in RAL 7035 Grey powder coat. Code: 6025

(I:Zone i-Zone Key Cum ponents

Detectors

CD-x Water Detecting Cables

Detecting Cable complete with maleffe male connections. CD-1 7 metre Code: 6004 CD-2 2 metre Code. 6005 CD-5 5 metre Code: 6006 CD-1U 10 metre Code: 6001

74r1716":

12-EOL End of Line Resistor Plug. Code:6036

CL.! CL/1-100 Floor Clips. Bag of 10. Code: 5015 gag of 100, Code: 6016 rhOthever dips are serf-adheAre barked the use pea suitaf'e adf&shreigiLre is rerwrorrrerded.

Okir

VILF1-10 f WL/1 100 Warning Labels. Bag of 10. Rag of 100

FLI-24 Float Detector. Code: 6023

HDi-24 Humidity Detector. Code: 6033

Code: 5719 Code; 5720

All are 12v powered by Main Control Panel and are complete with 97db alarm. Specified Remote Alarm Panels can also be made to order to 61.1 it specific building Interiors_

PC-I • SB-1 RP -1 Single Channel Code: 6045 Protection Cover for Stabilising Par for RP-2 Two Channel Cede: 6046 Point of Use Detectors. Point of Use Detectors. RP-3 Three Charrne I Code: 6047 Code: 6035 Code: 6034

11

Page 15: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Connection to EMS via Volt-koa contacts, R5,485. RS-232

Nate

ail Flom Clips. Recommended one Every OS metres or

where requited. van WArnirg Lobo's. Recommended rare

every 5 metres.

Telecom 1,quipment Racks

Connection to RMS. via Volt -Free fantods, RS-485 RS-232

(4'

Telecom Equipment Racks

C1734 Z 5 arid 1 Oirn

L5-ECIL

System Design Guide: Perimeter and Footprint Protection beneath access flooring, using location system

Serpentine Layout beneath access flooring, using location system

13

Page 16: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Canne€tion to EMS.via Unit-free contacts, 1,[5-4S5 RS-212 co Fi9orciio5.

Ittcoromencled ant every 0.5 metre or wliererequired. Mil Warning Labels RecornmerKied one tyely S memos.

Note

6.5rUC SO IOW lave" 5.108)

ern ferr

Conneetlan to 5M5 via Volt-free .ranraeti,

1,15.-4S5 85.232

Note

Lifr Jumper Cables reywatglInN

arm and flisnr1

14

Drip Trays !-Itien,421 High Level to Low Level

Multi Area/Floor Option 1 See page 25 for Networking Options

Page 17: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

EINVIRONIJEHTM. MONITORING Sysrely

vt_ 11:24 V 23106/152

Control Panel Mode LS-2i

The LeakSense Control Panel shall be wall mounted and be of a mild steel construction and powder coated with a 6 line format 114rrim x fp-Imm Blue LCD screen.

When connected to a single phase mains supply the Control panel shall generate Pulsed Echo Radar signals, which shall be transmitted along the entire length of the Leader/Jumper and Detecting Cables. Any change in the characteristics of the table is compared to pro-programmed limits and dependent on the type of change the LCD will display an Alarm and the Alarm Horn will sound.

The LCD screen will, during normal operation display the current Time and date, and the words 'SYSTEM CLEAR' h will also display the functions available of the soft touch buttons located each side of the LCD together with a pulsing Heart denoting that the system is connected to a healthy Mains Power Supply.

In an Alarm state the LCD will display current Time & Date, a meterage reading giving the location of the Alarm and the Alarm state. i,e. Water Detected' ar 'Open Circuit'. The Alarm Horn will also sound. It will also display the functions available of the soft touch Buttons and at the touch of a button, produce an 'Alarm' Verification Graph (This will show the wave form of the actual alarm).

'Clean' Signal contacts for 'Water Detected', "Open Circultr, 'Mains Fail', 'Battery Fail', and 'Service', together with RS-232 and RS-4 outputs are fitted as standard for remote signalling.

For safety the Control Panel is fitted with a key operated lock and 'Power Oft door switch.

On completion of the installation, a system location map will be prepared and encapsulated to enable easy identification of the Alarm location.

Main features 114rtorn x 64min LCD Screen displaying:- Current Time & Date, System status, Alarm status & available Dutton functions,

over 'On'. Power Support System ',On'. Service.

System will monitor 15X metres of cable, Last 100 Event Memory_ Alarm Siren 97db It lm. Alarm hom 'Mute'. 'Test' and all other functions displayed on LCD when required. Lockable mild steel cabinet. Powder Coated PAL7035. Door interlock safety 9.viten. Mains Fail Battery Back Up. (4 hours)

Outputs RS-232

Volt free outputs Water Detected. Open Circuit. Mains Fail. Battery Fail and Service.

Resolution + or - I metre.

Mains Voltage Range 120 or 240 volts A.C. 12 50 or 6D Hz_

Normal Operating Voltage 24 volts D.C. internally supplied

Operating Temperature Range to 50 deg E

Approvals BS EN ISO 140131 and ISO 9001: 1994. EMC Directive S9/335,EEC. CE Marked

Cabinet Dimensions Height 330mm Width 255 MITI

Depth 8Sn-1m

15

Page 18: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Zoned Locating Module Model ZLM-500 Leefftenjai

The 'Aquala rm' Zoned Locating Module shall be wall mounted and be of a mild steel construction. painted and powder coated.

The Zone Locating Module shall generate Pulsed Echo Radar signals, which shall be transmitted along the entire length of the Leader/Jumper and Detecting Cables. Any change in the characteristics of the cable, whether water detected or open circuit, occurs, these are compared to pre-programmed limits and when the limits are exceeded, an alarm signal providing the meterage reading accurate to +I- 1 metre, will be sent to the designated 'Aqualarm• master control panel

The LM-500 is capable of monitoring up to 500m 0-F combined Leader/Jumper end D eteeti or cables.

Power to the alvl-500 is generated via the 'Aqualarrn' CAN network.

A local, volt free alarm contact is available within the Zuvi-500. Other alarm contacts will be available from the designated "Aqualarrn' master control panel.

The FLM-500 can only be used within a network designed system connected to either an i-Zone control panel or One-Touch system to monitor and display the relevant alarms and information.

Main features Operating Temperature CAN BUS Technology. 0- 5C1 de9 C System will monitor 504m of combined cable. Door 'Power Off' Interlock Switch. Approvals 'Power On' LED. BS EN ISO 9001: 1994 Key Operated Cabinet Lock, EMC Directive 89/336/EEC Alarm Relay Output. EC Marked. Network Fail Relay Output. Powder Coated PAL7035, Cabinet Dimensions

Heigh( 150mrr Outputs Width 200rnru $-232 Depth 135rnm

RS-48S

Resolution ti• 1 metre.

Power Supply 24 volts via 'Aqualarrn' CAN network.

Normal Operating Voltage 24 volt D C. internally supplied.

Cabinet Rating IP 54.

16

Page 19: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Floor CI ips CL/1-10 Bag of 10. Code: 6015 CL/1-100 Bag of 100. Code: 6016 Ih4lsoy9h dice Aft ArloCkhesNle Wald the we of a .witaiYe adhesivelpikre Is recommended

Warning Labels WM -10 Bag of 10

Code- 5719 WL11-100 Bag of 100

Code: 5 720

Optional Extras

L5 frii1B-1 Replacement Mapping Cock: 6018

1VFM-1 Semi-flush Mount Frame for 1_52i only. woe Steel finished in RAL 7035 Grey powder coal. Code: 6025

Key Components LeaktenSe 5%-zwurlec.agampimen

Control Panel Model 15-21 .• 230v AC • Mild Steel enclosure IP54 • Powder coated RAL 7035 • Surface or semi-flush mount (Frame Optional) • To Monitor 1500m of cable • RS 232 and RS 485 volt-free outputs • Battery beck-up fitted interna/ly Code: 5000

2LM-500 ▪ Mild Stec! enclosure- IP54

• Powder coated RAL 7035 i• To Monitor SOem of cable

Powered via network Code 501/

Key Components

Leader Cable L5/LC3.5 3.5 metre LS/LC7 7 metre

Code: 6002 Code: 6003

L5-EOL End of Lire Resistor Plug. Code 6017

CD-x Water Detecting Cables

Detecting Cable complete with male/female connections.

CD-1 1 metre Code: 6004 CP-2 2 metre Code: 6005 CD-5 5 metre Code: 6006 CD-10 10 metre Code: 6007

LS-JC Jumper Cables

Jumper Cable complete with ma1tifemale connections. Longer lengths of Jumper Cable can be ordered.

LSIJC5 5 metre Code: 6009 L5f1C10 10 metre Code: 6010 LSLICZO 20 metre Code: 6011

Remote Alarm Panels

All are 12v powered by Main Control Panel and are complete with 91dB alarm. Specified Remote Alarm Panels can aim Ise made to order to suit specific building interiors.

RP-1 Single Channel Code: 6045 RP-2 Two Channel Code: 6046 RP-3 Three Channel Code: 6047

17

Page 20: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

J.A.M. Limited has taken the field of environmental monitoring to a new level with theacelaplo,..d. system.

Combining the latest addressable CAN 2US technology for monitoring and displaying information of alarms/alarm conditions within the running protocol of a MS Windows0 program.

Specification Summary

• 12 inch touch screen LCD full colour VGA monitor • Capable of monitoring up to GS0 zonesiaddresses,

including water, refrigerant gas, fuel oils, high temperature and humidity

• Detailed layout maps electronically stored and easily retrieved to show alarm condition and location

• Alarm history logged for future reference • Mend alone system or easily integrated with El.MS

systems

Typical Applications

• Computer suites • IT environments • Dealer floors • Electronic offices • Hotels • Hospitals • Leisure Complexes * Supermarkets • Listed Buildings • Museums • Art Galleries • Archive Facilities

RG1 Ref! igerant Sensor

ZLM.St1.0 Zoned Locating Module

APM•25 Area Power Module

TDI•24 Temperature Sensor

IR D1.24 Oil Leak Detecte Point Sensor

19

MCILiderone, Envftonmental Monitoring System

Page 21: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

MICILIMIErM ,1044.011" "Va.

CON1MUNICATIONSil_T_ SUITE

1111116: RECEPTION/SECURITY

CP41.1000 Central Processing Unit

STD1.24 /41)1.24 (Dar Detecting Cable Humidity Sensor Point oP usc. Lietc-ctoi

Tifuld Touch Screen Monitor Desk bp or W.211 Monitor

20

Page 22: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

aw9karm Central Processing Unit Model CPU 1000

The 'Aqualarm One Touch' Central Processing Unit shall be wall or floor mounted and be of a mild steel construction, painted and powder coated.

The CPU-1000 combines the latest addressable CAN BUS technology for monitoring and displaying information of alarms I alarm conditions within the running protocol of a Windows 0 program. It will be capable of monitoring up to 25 detectors from the full 'Agu alarm' range including water, refrigerant gas, fuel oils, temperature and humidity as well as up to 25 i-Zone Control Panels or APM-25 Area Power Modules resulting in a combined monitoring power of up to 65C detectors.

The CPU-1000 can also monitor up lo 23 LS-2i LeakSense Control Panels or ZLM-300 Zone Locating Modules, to create a fully comprehensive Locating System.

When alarm conditions are raised, they will be displayed On the TSM-1 Touch Screen Monitor, with the use of detailed layout maps for the area(s) being protected. Alarm history is stared an the unit's own internal hard disk drive for future perusal.

Operating Instructions, Commissioning, Maintenance and Service logs are all stored electronically on the system for ease of retrieval and use.

The system is supplied with 5 volt free outputs, and a R5-485 output to relay alarm conditions to other controls such as Building Management Systems.

As the CPLI-1000 is essentially a PC based product we strongly recommend the power supply is either connected directly to the building UPS system or an after market proprietry unit which is purchased to support the system should the mains be interrupted or tail.

Main Features CAN BUS Technology Alarm Horn 57db 0 lir Alarm Horn Mute Facility Door 'Power DI' Interlock Switch Circuit Continuity Alarm 'Mains On' LED 'Battery On' LED Reset Facility Key Operated Cabinet Lock Alarm Relay Output Mains Fail Relay Output Network Failure Output Service OLle Output 1S485 Output Power Support System Parallel Printer connection

Power Supply 120-240 volts, single phase 50Hz fused 5 Amp_

Normal Operating Voltage 24v do internally Supplied.

Cabinet Rating IP 54

Voltage to Detector 24 volts dc.

Quiescent Current 1.2 Amp 24e de.

Operating Temperature U SE; deg C

Approvals BS EN iSO 9001:1994 EMC Directive 89/336.1 EC CE Marked,

22

Page 23: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

a9ualarm Area Processing Module Model APM-25

gniNs Gm

40

The 'Aqualairon' One Touch Area Processing F Power Module shall be wall mounted and be of a mild steel construction, painted and powder coated.

The APV-25 combines the latest addressable CAN SUS technology for monitoring informat ion of alarms/alarm conditions within the running protocol of a Windows lb program. It will be capable of monitoring the full range of 'Aqualarrn detectors including water, refrigerant gas, fuel oils, temperature and humidity as well as other devices capable of producing a volt free alarm output

The APM-25 is capable of monitoring 25 zones f addresses. This unit must be used in conjunction with the CPU-1050 Central Processing Unit.

When alarm conditions are raised, they will be relayed to the CPU-IC00, which in turn will display them on the TSM-1 Touch Screen Monitor, with the use of detailed layout maps for the area (s) being protected.

For remote signalling, the control panel will be supplied as standard with the following outputs: RS485, Common Alarm, Network Failure, Mains Fail ti Service Required.

Main Features CAN BUS Technology Door 'Power Of Interlock. Switch 'Mains On' LED Key Operated Cabinet Lock Alarm Relay Output Mains Fail Relay Output Network Failure Relay Output Foyer Support System

Rower Supply 120-240 volts, single phase SOFIr fused 5 Artip.

Normal Operating Voltage 24v dc Internally Supplied.

Cabinet Rating IP 54

Voltage to Detector 24 volts dc

Quiescent Current 1.2 Amp@ 24v dc.

Operating Temperature 41 50 deg C.

Approvals BS EN ISO 9001:1954 [MC Directive 69/33StEEC CE Merited_

23

Page 24: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

41".4■1114

T5M-1 Touch Screen Monitor Desk Top or Wall Mounted Code: 6038

-----____ —

CPU-11100 Central Processing Unit

pjer 6038

Ada&

ASV-25 Arcs Power Module Code: 6039

CDB1.24 Zone Module, Code: 60.2

1131:11-24 Point of use Infra Red Detector. Cc kle: 6029

a9ualarn Aqua!arm One Touch Key Components 00,

Detectors

CD-x Water Detecting Cables

STD1-24 OFIN-24 Point of use Detector. Overflow Detector. Code: 6026 Code: 6030

Detecting Cable complete with maleffemale connections. CD-I 1 metre Code: 6004 CD-Z 2 metre Code. 6005 CD-5 5 metre Code: 6006 CD-10 10 metre Code: 6007

R Gi-xx-24 Refrigerant Leak Detector. Code: 6031

1Di-24 2 Stags Temperature Detector. Code. 6032

far

IZ-EOL End of Line Resistor Plug. Code: 6036

CL11-10 1 CU1-100 Floor Clips. Bag of 10. Code: 6015 Bag of 100. Code: 6016 AI hough dips are zed-adhesive backed die Else of a giIabre adhesivefghle h recomirpeodesi.

4-

INI11-10 i VVIA-100 FLi-24

14D1-24

Warning Labels. Float Detector, Humidity Detector, Rag of 10. Code: 5719 Code. 602e

Code: 6033

Bag of 100. Code: 5720

Optional Extras

PC-T 513-1 Protection Cover far Stabilising Bar for Point of Use Detectors. Pfldrrt of Use Detectors. Code: 6035 Code: 6034

24

Page 25: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Networking Options LeakSense Locating Systems

Stage

A Oral L7' SOW -64 and detecting cable can he rrionhamd by each am-sin Module

_ 2nd Floor

CiN Net workllnk 710i1,51111

bstua CCONCill Module

i-7rno 7S rrsnftr5113and

aht-srm Vp to 25 LL1/21.5a, Modules Zona tocadon can de netstiurNal on a single modula

ZLM-50C1 connected to i-Zone Control Panel, showing -floor and rneterage reading

i-Zone display C1)-K DiteCtlIN CWt.

3rd Floor

nianoTp !,our rter and anew.

112!, Fi _

lo ENS via Volt Free Cordacti and PS 485

25 Control Pared

it:ss ntrAla

ZLIA-SDO 2nd Floor Mel

Liquid detected

Stage 2

1_5-2i Control Panels connected to i-Zone Control Panel, showing theterage reading an local panel and floor & meter age reading on 1-Zone display.

A total of 1509re or Ilimpsensing

and detecting cable carlbeincritccaau hyaach LS2I C.iirrai Parr!

dq

Remote Sounder

and Rmcran

1st Flppr

Jolt:, 25 Leo1.6ense Syrwtern3 can be net worked an a single One Touch Panel

water

Dote:clod at :250M

',77.11111...To ULM'S via Volt Free Contacts and RS 485

11:56 MS108

Lee k•Son5n LS-2i 2nd Floor 250m

Liquid DetdOted

El

Page 26: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

ZLM-500 connected to One-Touch System, Showing floor and rneterage reading together with graphic map of effected area.

IJ X Drnly Wag table

Up L. mXim Ur LOrnbinard nonrsensi rig and detection cad e per ZLY-SONSI odule

2nd Nam

Srd Fl

Filename/ Link ei husno 'tune Location Mackie

ref

Water Leak Detected_ 2n1 Firm 250iel Male East nel&E

TSIka. Tooth SL. ern Montt. runner will:. 0.12-1001 Faatessing Unit

..e,'''''''''''''''''' --- ToUMSvia VoFt FreeConiacts and F5 A85

7] ]d-301: Zane We tin. MOLL' E.

LiplitiS Ti-SrtrUeleddarr-s can he redworked on a single One loud, Control Panel

Stage 4

LS-2i Control Panels connected to Dne-Touclr System, showing rneterage reading OR local panel and floor, meterage reading and graphic map or One.Teurh System,

314 Ficxy A total of 150E1m pt Non-sensing and itable canhernorsliurrd olorsliur by ealth LS2iCtrotpul Powl

2nd plow ii

Water Cele:21A

a9 7S Om

Cary 2Terte.rni k Link

Up co 25 LeartSense Syswins Carl tee net...eked Ors aSITigie Oni-louttiCkarkrai Panel

ip X Deirc Port; rt,ahlir

_EA

LS-2. Contici Panel

111( •

%mom Ind Ent c•-■

Coned Anvil

LS-2J Control Panel

1111116

_ •

Skidisir Look Maki; 2nd Floe( 255m WI* FeatToilel

11%1.1 Traireh Sonora, Jel mare sonneiteri In COLI-10012 F rooming Unit

isk Flear

Stag e 3

ilk

To ELMS via Vali Free Eaintacts and PS .tISS

Page 27: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Networking Options Zoned Systems

remontalont 11.71-14

Oates tot

LI kr-scro module- an-el cipici 500m el Cr-x Deina_tion Cable

To EngSvia

Volt Peetorgacts arm:KG-16S

Stage 1

APIv1-25 Modules connected to a One-Touch System, showing floor, meterage reading and graphic map.

A marl-num al 75 detector; At any unii.34 tombinalion can be c caninected . Flunldlly i peed' And 75

Detector

it

CDF11.24 01:1-4 Water "Detection Cable

Outer 25 APM•25 Modules can he newer:aced on a single Ore !ouch Control Panel

ieff'.. R31-24 Refrigerant Gas Oates: or I

APM-751 Module

• clOi-24 Point detector

A.191 Floor gag ,

_10

APh1-2-5

msdkkle

ARM Link

,10.0; 111 — 15C iimr

1.

Wien l task Eictortert 2nd 1109i Male Talot • mar I

ISM. I touch 5treenMonitor crnnerhselThCP1.1-1{1011

Processing !Arc

APIA-25 Module

Stage 2

Upto}51-7oneCeetrat Panel; cent* nelonokedon a tingle One I ourh Control Panel Coolly!

PIMA

_ REA-111, Nefhile.11f11rElkt lifl.PefEd

511}i-7d Pnirt n a;;;410;

_ 3rd Flow

i-Zone Control Panels connected to One-Touch) System. showing alarm condition on local panel and floor, zone and graphic map or One-Touch SW-ern.

kneikril 4.7ber coricrol Parbrl

A rriaximura of 25 detectors of ary ,r>04 relinhinatiesn rsnb rcrinweloal

aumidity 7M rcrnr

Wel De.lectod Zara One zild.F7cle rr

Mahe Link LLISI-24 N■ 4_17-x

WE[Ef USIK.:1011 table

water Leo* Omura:, ]rid Flour Male Toler - Zonal

Control Panel 71 M•SPO ncoduteand up nr rn-n rim wind CINr•

at

tilt-24rerripereltafe 01411fC:CIN

111 picOr

.1J _

• -..

PIM•1 Touch 5 creen Monitor rrrirnwE had I ri rPi egn Pro, rzeincp Unit

co

Yen Free-Coe Tads, and I:15 485

la-

Came

27

Page 28: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

IJDH-24 UDF-24 IFloat Detector. Humidity Detector.

mciLralarrn Universal Detectors

JAM offer a range of detectors that can be linked directly onto other control systems, i.e. BMS systems, AC controls or any control system that can provide a 24v power supply {ac or tic) and receive a volt free signal in the condition of alarm, which we categorise under 'Universal Detectors'.

The Universal Detectors do not require an "Aqua!arm' control panel to monitor them.

All the detectors that are shown within this product guide are available in this format. The alarm volt free signal can be raised in either a Normally Open {h1.0.} or Normally Closed (N.C.) condition.

Detectors

CD-x Water Detecting Cables

UDP-211. UDOF-24 Point of use Detector. Overflow Detector.

Detecting Cable complete with maleffernale connections.

F

CD-1 CD-2 CD-5 CD-10

1 metre 2 metre 5 metre 10 metre

Code: 6004 Code' 6005 Code' 6005 Code. 6007

UDC-24 UDR-24 gene tvladule. Refrigerarrt Leak

Detector.

The model numbers for the Universal Version of each detectors are as follows:

U D111-24 UDT-24 Point of use Infra Red 2 Stage Temperature Detector. Detector.

Detector Description Model Number

Point of usawaterdetector UDP-241 Cable zone detector module UDC-.241 Detection cable CD-x Infra-Red detector {oil or diesel) UDIN-24 Float detector U0P-24 Overflow detector UOOF-24 Refrigerant gas detector UDR-24 Temperature detector UDT-24 Humidity detector UGH-24

26

Page 29: Drum Heaters, IBC Heaters, Drager Gas Detectors, ASCO Solenoid … · 2013. 1. 15. · Our journey to date has taken 25 years in the field of design, manufacture and installation

Air - siia—Pe

J.A.M. Limited is an 1509001 & 14001 registered company.

Technology

All our electronics and components are Rol-1S Compliant in line with current legislation. Our PCB's are multi-layered and are PTH manufactured to meet UL Standards. All our finished products are Cr marked.

Environment

Our Credentials

As pa rt of the government's WEEE Directive, J.A.M. Limited are registered for the safe disposal of electronic component waste, which is recycled. Using this procedure allows us to offer disposal of any redundant systems to our clientfenct users.

J.A.M. Limited ensures that any of our metal enclosures that are either damaged or do not meet our production standards, are returned to our fabricator for recycling,