SWPU SERIES
DUCTEDCEILING
MOUNTED
WATER-COOLEDPACKAGED
AIR-CONDITIONERS
SLIMLINE
Smar tw ise I nnovat ions...Towards Green, Qual i t y & Rel iabi l i t y Solut ions
Smartech Sales & Services Sdn. Bhd.(829707-K)
No.15, Jalan PJS 1/27, (Jalan Petaling Utama 6), Petaling Utama, Batu 7,
Off Jalan Klang Lama, 46000 Petaling Jaya, Selangor.
T: 603-7782 2788 / 7783 7288 F: 603-7782 3788
W: www.smart-hvac.com.my
Specifications in this catalogue are subject to change without notice in order that SMARTECH may bring the latest innovations to their customer.
SWPU0110
-
7/30/2019 Ducted Unit
2/8
-
7/30/2019 Ducted Unit
3/8
INTRODUCTION
DUCTED CEILING MOUNTED WATER-COOLEDPACKAGE AIR-CONDITIONERS
The Smartech SlimLine Water-cooled Packaged air-conditioners ranging incapacity from 20,000 Btu/hr to 260,000 Btu/hr, offers Architects, Design Engineers,Developers and building owners a versatile, flexible and economical type ofair-conditioning system for use in office buildings, factories, hospitals supermarkets,shopping malls, etc; instead of the higher cost Central Chilled water Air-conditioningsystem, utilizing Chillers, Cooling towers, Air-handling units and Fancoils. Comparedwith air-cooled split or packaged air-conditioners, the water-cooled packagedair-conditioners offer approximately 30% savings in operating cost.
2
The Ducted Ceiling Mounted SlimLine water-cooled packaged air-conditionerssaves valuable floor space when compared with floor mounted water-cooledpackaged air-conditioners.
The Smartech SlimLine SWPUs with its rigid double-wall casing construction, highefficiency hermetic rotary or scroll compressors, cleanable shell & tubes condensers,hydrophillic coated aluminium fins evaporator coil, direct-drive or belt-driven blowerfans, balanced port design thermal expansion valves, factory prepiped and leaktested thick wall copper refrigerant pipings, factory prewired electrical and controlpanel, etc; are designed and manufactured to ensure efficient , reliable, low noiseand low vibration performance within the ceiling space.
NOMENCLATURE
SWPU 200T DDC P
Smartech Water-CooledPackaged Unit
Model Size
Twin Compressors
-
P R-407c Green Refrigerant
DDC-Ducted Direct Drive Motor,Ceiling Mounted
DBC-Ducted Belt Drive Motor,Ceiling Mounted
R-22 Refrigerant
DIMENSIONAL DATASWPU 200T (DBC)
SWPU 260T (DBC)
13
Note: All dimension are in inches. Unless otherwise specified.
Note: All dimension are in inches. Unless otherwise specified.
1
2
3 3
CONDENSATEDRAIN 3/4" MPT
CONDENSERINLET/OUTLET
CONN J
MOTOR
HANGINGLUGS5/8" HOLES
CONDENSER
BLOWERFAN
COOLINGCOIL
FILTERRACK
2" DUCTCOLLAR
COMPRESSOR
ELECTRICALPANEL
89
18 17
18
243
3021
243
18
7
25
3021
2
31318
60
1718182016
8221
21
HANGINGLUGS5/8" HOLES
CONDENSER
BLOWERFAN
MOTOR
CONDENSATEDRAIN 3/4" MPT
CONDENSERINLET/OUTLET
CONN J
COMPRESSOR
ELECTRICALPANEL
COOLINGCOIL
FILTERRACK
2" DUCTCOLLAR
2
1825
21
31318
60
2
30
7 21
432
43
18
18 13
74
3021
1813 18 13
67321 32
1
-
7/30/2019 Ducted Unit
4/8
3
FEATURES
The casing cabinetry consists of a rigid framework constructed fromheavy gauge welded steel channels, held rigidly together by double-wallpanels and supports;
A. Casing
The double wall panels, with sandwiched polyurethane insulation betweenthe walls are held tightly to the framework to form a rigid casing whichreduces noise breakout from within the unit;
Selected double-wall panels near the Blower fan are insulated with 1/3lbs density fiberglass and internally lined with perforated GI liner to absorbnoise generated by the fan;
With double-wall construction, it is easy to clean the inner surfaces toreduce risk of dirt and bacteria contamination;
There is no erosion of internal insulation material which can contaminatethe air-stream. The double-wall construction SWPU is ideal for cleanroom applications, such as hospital, electronic factories, food processing andpharmaceutical factories;
Casing panels are aesthetically coated with oven-baked polyester paint toprovide excellent finish and good corrosion resistance;
Removable access panels are provided for ease of access to critical partsand components for service and repairs.
B. Hermetic Rotary Compr essor (Size 21 to Size 32)
Hermetic motor of single phase permanent split capacitor type, refrigerantcooled. Motor fitted with internal thermal protection;
Compressor with internal suspension system and externally mounted onrubber grommets to eliminate vibration and ensure quiet operation;
Compressor fitted with suction accumulator to protect against liquid sluggingat start-up
The hermetic Rotary compressor design has high efficiency, low noise andproven reliability.
C. Scroll Compressors (from size 38 to 260)
Scroll hermetic type operating at 2950 rpm (50Hz);High efficiency (high EER), low noise and proven high reliability;
No contact scroll design and suction gas cooled motor ensure long servicelife;
With internal line break motor protector or solid state motor protector;Unit with twin compressors and dual refrigerant circuits, besides providingfor system redundancy, reduces current inrush during start-ups and bycycling on/off of two compressors to match building load, less energy isbeing used when room load requires lesser cooling capacity.
Consists of outer carbon steel shell with internal bundle of copper finnedtubes;
Water travels within the copper finned tubes while hot discharge gas envelopesthe outer finned surface of the copper tubes before condensing to liquid;
D. Cleanable Shell & Tube Condenser
Each condenser is built with integral sub-cooling chamber to maximizesystem efficiency;
Each condenser is provided with a fusible plug which meltswhen temperature reaches 175F, releases system refr igerantgas and avoids explosion in case of fire;
Complete condenser is leak and pressure tested on bothwater and refrigerant sides prior to assembly.
DIMENSIONAL DATASWPU 164T (DBC)
SWPU 195 (DBC)
3 48 3
24
11
1614
49
HANGINGLUGS5/8" HOLES
CONDENSER
BLOWERFAN
MOTOR
CONDENSATEDRAIN 3/4"MPT
CONDENSERINLET/OUTLET
CONN J
28
55
1314
14
ELECTRICALPANEL
COMPRESSOR
497
12 13 3
28
14
33
25
COOLINGCOIL
43
41
41
41
41
167
167 2
1
2" DUCTCOLLAR
Note: All dimension are in inches. Unless otherwise specified.
Note: All dimension are in inches. Unless otherwise specified.
FILTERRACK
12
ELECTRICALPANEL
COMPRESSOR 18 13
30
74
18
2
21
43
21
2 43
18
2" DUCTCOLLAR
21
7
3025
31312
54
21
3 67 21
3
13 12 18 13
CONDENSATEDRAIN 3/4" MPT
CONDENSERINLET/OUTLET
CONN J
HANGINGLUGS5/8" HOLES
CONDENSER
BLOWERFAN
2
3
141
-
7/30/2019 Ducted Unit
5/8
4
FEATURES contd
E. Evaporator Coil
Constructed from staggered rows of copper tubes mechanicallyexpanded into die formed aluminium fins;The aluminium fins are precoated with low surface tensionsubstance which speeds up the drainage of condensate,eliminates moisture carry-over, maintain the aluminium finssurface dry and clean, and prevent mould formation. The coatingalso improves the corrosion resistance of the aluminium fins andprevents oxidation of the aluminium surface, thus maintaininggood heat rejection.
Coils are leak and pressure tested to 450 psig when immersedin water;Complete coil is internally evacuated, dehydrated prior to assembly.
F. Direct-Drive Blower-Motor Assembly (Size 21 to Size 58)
Blower of galvanized steel construction, DWDI forward curve bladesdesign, statically and dynamically balanced;
Direct Drive motor resiliently mounted on blower inlet to assuresmooth and vibration free performance;
Single Phase permanent split capacitor motor with permanentlylubricated ball-bearing;Motor provided with thermal overload protection.
G. Blower Fan & Drive Package for Ducted Belt Drive units(Size 72 to Size 260)
Fan is of Centrifugal forward curved design, with double inletdouble width, AMCA certified, suitable for Class II operation;
Pillow block heavy duty bearings to ensure long operating life;Single large diameter fan is used, to reduce noise level,eliminates the need for common transition piece and prevent airunbalance;Complete fan-motor & drive package assembly is resiliently isolatedfrom unit casing by either rubber or spring vibration isolators;
All fan wheels are statically and dynamically balanced to ISO1940and AMCA-204-G2.5 Standard;Optional non-overloading backward airfoil fan can be providednon-loading.
H. Control and Safety Protection
Balanced port thermal expansion valve is provided for eachrefrigerant circuit to control liquid refrigerant flow while maintainingadequate suction superheat, over a wide variation of condensinghead pressures;High-low pressure cut-out to protect compressor against highdischarge pressure and low refrigerant charge;
Liquid line filter drier to ensure system dryness and prevent acidformation.
I. Filters
Side loading filter rack, 1 filters is provided.
J. Optional Accessories
Factory prewired starters and control panel including single ormulti-steps thermostat and indicating lights;1 prefilters and 15 bag filters section;Mixing Box section with fresh air and return air dampers;Suction stop valves, discharge stop valves and liquid stop valvesfor each circuit;R407c refrigerant
DIMENSIONAL DATASWPU 100 & 130 (DBC)
SWPU 150 & 165 (DBC)
11
3 48 3
24
11
1614
49
HANGINGLUGS5/8" HOLES
CONDENSER
BLOWERFAN
MOTOR
CONDENSATEDRAIN 3/4" MPT
CONDENSERINLET/OUTLET
CONN J
28
55
1314
14
ELECTRICALPANEL
COMPRESSOR
497
12 13 3
28
14
33
25
COOLINGCOIL
43
41
41
41
41
167
167 2
1
2" DUCTCOLLAR
Note: All dimension are in inches. Unless otherwise specified.
Note: All dimension are in inches. Unless otherwise specified.
FILTERRACK
COMPRESSOR
ELECTRICALPANEL
30
63
16
16
14 3
21
167
COOLINGCOIL
2" DUCTCOLLAR
FILTERRACK
52
12 13 32
1625
30
3 7
21
21
167
HANGINGLUGS5/8" HOLES
CONDENSER
BLOWERFAN
MOTOR
CONDENSATEDRAIN 3/4" MPT
CONDENSERINLET/OUTLET
CONNJ
27
10
1816 14
-
7/30/2019 Ducted Unit
6/8
5
Notes:
MODELSTANDARDCAPACITY
MBH
kWINPUT
AI R ON EVA P. WAT ER TEM PER AT URE OF F C ON DE NS ER - F
STANDARDCFM
WBTEMP.
F
80 95 110
TOTALMBH
SENSMBH
kWTOTALMBH
SENSMBH
kWTOTALMBH
SENSMBH
kW
SWPU 21DDC
21.0 1.28 660
72 23.67 12.64 1.22 22.27 11.85 1.31 20.13 10.76 1.37
67 23.53 16.73 1.16 21.00 15.56 1.28 19.90 14.80 1.34
62 20.56 20.60 1.16 19.00 19.00 1.25 18.16 18.20 1.31
57 18.17 18.17 1.13 16.80 16.80 1.25 15.97 15.97 1.31
SWPU 24DDC
24.0 1.65 800
72 27.01 14.36 1.57 25.45 13.52 1.69 22.97 12.23 1.76
67 25.75 19.09 1.50 24.00 17.79 1.65 22.74 16.80 1.72
62 23.50 23.50 1.50 21.71 21.71 1.61 20.76 20.76 1.68
57 20.76 20.76 1.46 19.20 19.20 1.61 18.25 18.25 1.68
SWPU 28DDC
28.0 2.08 930
72 31.51 16.76 1.98 29.69 15.78 2.13 26.80 14.27 2.22
67 30.04 22.27 1.89 28.00 20.76 2.08 26.53 19.69 2.18
62 27.42 27.42 1.89 25.33 25.33 2.03 24.22 24.22 2.13
57 24.22 24.22 1.84 22.40 22.40 2.03 21.29 21.29 2.13
SWPU 32DDC
32.0 2.38 1060
72 36.01 19.15 2.27 33.93 18.03 2.43 30.63 16.30 2.54
67 34.34 25.45 2.16 32.00 23.72 2.38 30.32 22.50 2.49
62 31.34 31.34 2.16 28.95 28.95 2.33 27.68 27.68 2.43
57 27.68 27.68 2.11 25.60 25.60 2.33 24.33 24.30 2.43
SWPU 38DDC
38.0 2.52 1260
72 42.77 22.73 2.41 40.29 21.41 2.58 36.37 19.36 2.70
67 40.78 30.21 2.29 38.00 28.16 2.52 36.01 26.72 2.64
62 37.21 37.21 2.29 34.38 34.38 2.46 32.87 32.87 2.58
57 32.88 32.88 2.23 30.40 30.40 2.46 28.89 28.89 2.58
SWPU 48DDC
48.0 2.70 1600
72 53.39 28.72 2.58 50.89 27.04 2.76 45.94 24.45 2.88
67 51.51 38.17 2.45 48.00 35.58 2.70 45.49 33.75 2.82
62 47.01 47.01 2.45 43.43 43.43 2.63 41.52 41.52 2.76
57 41.52 41.49 2.38 38.40 38.40 2.63 36.49 36.49 2.76
SWPU 58DDC
58.0 6.50 1900
72 65.27 34.71 6.20 61.50 32.69 6.65 55.51 29.95 6.94
67 62.24 46.12 5.91 58.00 42.99 6.50 54.97 40.78 6.79
62 56.80 56.80 5.92 52.48 52.48 6.35 50.17 50.17 6.66
57 50.17 50.17 5.76 46.40 46.40 6.35 44.10 44.10 6.66
SWPU 72DBC
72.0 3.70 2400
72 80.90 43.10 3.50 76.30 40.50 3.80 68.90 36.60 3.90
67 77.30 57.30 3.40 72.00 53.40 3.70 68.20 50.60 3.90
62 70.60 70.60 3.40 65.10 65.10 3.60 62.20 62.20 3.80
57 62.20 62.20 3.40 57.60 57.60 3.60 54.70 54.70 3.80
SWPU 82DBC
82.0 4.20 2500
72 92.30 44.80 4.00 86.90 41.90 4.30 75.50 39.80 4.40
67 88.00 57.10 3.80 82.00 54.90 4.20 77.70 53.30 4.30
62 80.30 68.60 3.80 74.20 66.10 4.10 70.90 64.30 4.30
57 70.90 70.90 3.70 65.60 65.60 4.10 62.30 62.30 4.30
PERFORMANCE TABLE
1) Total MBH - Rating are gross capacities. For net c apacities, deduct evaporator blower motor heat.2) Sensible MBH - Capacities are based on 80F (26.6C) air on evaporator.3) kW - Compressor kW input
DIMENSIONAL DATASWPU 21 - 58 (DDC)
SWPU 72 - 82 (DBC)
10
Note: All dimension are in inches. Unless otherwise specified.
Note: All dimension are in inches. Unless otherwise specified.
4 45 4
49
24
10
15 1441
53
24
1114
3
41
4114
167
12 13 3
24
497
41
14
3167
21 FILTER
RACK
COOLINGCOIL
2" DUCTCOLLAR
ELECTRICALPANEL
COMPRESSOR
CONDENSATEDRAIN 3/4" MPT
CONDENSERINLET/OUTLET
CONN J
HANGINGLUGS5/8" HOLES
CONDENSER
BLOWERFAN
MOTOR
CONDENSERINLET/OUTLETCONN J
CONDENSATEDRAIN 3/4" MPT
ACCESSPANEL
G E
AB
H
F
C
K
FILTERRACK
COOLINGCOIL
10
3
3721 16
7
DIRECTDRIVE
MOTOR
ACCESSPANEL
4 NOS.HANGING
LUGS5/8" HOLES
COMPRESSOR
ELECTRICALPANEL
2" DUCTCOLLAR
ACCESSPANEL
L M
N
6
3
D5
MODEL A B C D E F G H J K L M N
SWPU 21DDC 43 27 21 26 10 11 8 10 7 12 15
SWPU 24DDC 43 27 21 32 10 11 8 10 7 12 15
SWPU 28DDC 43 27 23 36 9 10 8 1 12 7 12 15
SWPU 32DDC 43 27 23 36 9 10 8 1 12 7 12 15
SWPU 38DDC 43 27 23 36 11 10 8 1 12 7 12 17
SWPU 48DDC 58 27 24 52 11 10 10 12 10 16 17
SWPU 58DDC 58 27 24 52 11 10 10 12 10 16 17
38
38
38
38
38
38
38
18
18
34
34
34
3166
3166
3916
3169
3169
3169
3169
34
34
141
141
-
7/30/2019 Ducted Unit
7/8
PERFORMANCE TABLE
MODELSTANDARDCAPACITY
MBH
kWINPUT
AIR ON EVAP. WATER TEMPERATURE OFF CONDENSER - F
STANDARDCFM
WBTEMP.
F
80 95 110
TOTALMBH
SENSMBH
kWTOTALMBH
SENSMBH
kWTOTALMBH
SENSMBH
kW
SWPU100DBC
100.0 5.20 3200
72 112.50 60.00 4.90 106.00 56.40 5.30 95.70 53.30 5.50
67 107.30 79.80 4.70 100.00 74.50 5.20 94.80 70.50 5.40
62 98.00 97.30 4.70 91.70 91.20 5.00 86.50 86.50 5.30
57 86.60 86.60 4.60 80.10 80.10 5.00 76.00 76.00 5.30
SWPU130DBC
130.0 6.70 4000
72 146.30 78.40 6.40 137.80 73.80 6.90 130.00 69.60 7.20
67 139.50 103.60 6.10 130.00 96.50 6.70 123.10 91.40 7.00
62 127.30 126.20 6.10 119.20 118.20 6.60 112.40 112.40 6.90
57 112.40 112.40 6.00 104.30 104.30 6.60 98.80 98.80 6.90
SWPU150DBC
150.0 7.60 4500
72 168.80 79.60 7.30 159.00 74.90 7.80 150.00 70.70 8.20
67 161.00 105.00 6.90 150.00 97.90 7.60 142.00 92.70 7.90
62 146.90 128.00 6.90 137.50 119.80 7.50 129.70 114.00 7.80
57 129.70 114.00 6.80 120.30 105.70 7.50 114.00 100.10 7.80
SWPU164TDBC
164.0 8.40 5200
72 184.30 105.30 8.00 173.70 99.10 8.60 163.90 93.30 8.90
67 175.90 142.60 7.80 164.00 132.90 8.40 155.50 126.00 8.80
62 160.50 160.50 7.70 150.40 150.40 8.20 141.80 141.80 8.60
57 141.70 141.70 7.40 131.10 131.10 8.20 124.60 124.60 8.60
SWPU165DBC
165.0 8.60 5200
72 185.50 105.90 8.20 174.80 99.70 8.80 164.90 93.90 9.10
67 177.00 143.50 8.00 165.00 133.70 8.60 156.40 126.80 9.00
62 161.50 161.50 7.90 151.30 151.30 8.40 142.60 142.60 8.80
57 142.60 142.60 7.60 131.90 131.90 8.40 125.40 125.40 8.80
SWPU195DBC
195.0 10.00 6000
72 219.30 86.70 9.60 206.70 110.00 10.30 195.00 103.70 10.60
67 209.20 154.10 9.10 195.00 143.60 10.00 184.80 136.10 10.40
62 190.90 187.40 9.10 178.70 175.50 9.70 168.60 168.60 10.30
57 167.90 167.90 8.90 156.30 156.30 9.70 148.20 148.20 10.30
SWPU200TDBC
200.0 10.40 6000
72 226.20 131.40 9.90 213.20 123.90 10.80 200.00 116.20 11.10
67 212.20 175.30 9.40 200.00 165.30 10.40 187.80 155.20 10.90
62 196.00 196.00 9.40 185.80 185.80 10.00 161.80 161.80 10.70
57 177.80 177.80 9.20 157.60 157.60 10.00 154.50 154.50 10.70
SWPU260TDBC
260.0 13.40 7200
72 292.50 154.40 12.80 275.50 145.40 13.90 259.90 137.20 14.20
67 275.80 202.40 12.20 260.00 190.80 13.40 246.40 180.90 14.00
62 254.40 239.40 12.20 237.40 237.40 13.00 224.80 224.80 13.90
57 231.00 231.00 12.00 208.40 208.40 13.00 197.50 197.50 13.90
Notes: 1) Total MBH - Rating are gross capacities. For net capacities, deduct evapor ator blower motor heat.2) Sensible MBH - Capacities are based on 80F (26.6C) air on evaporator.3) kW - Compressor kW input.
6
SWPU 195 DBC
CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5400 745 2.17 868 2.74 983 3.32 1104 4.04 1229 4.89
6000 791 2.79 905 3.40 1012 4.03 1115 4.70 1225 5.53
6600 839 3.52 946 4.19 1047 4.89 1140 5.57 1235 6.34
7200 887 4.38 988 5.10 1082 5.84 1173 6.60 1258 7.36
SWPU 260T DBC
CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6500 792 3.17 903 3.81 1006 4.50 1103 5.17 1198 5.91
7200 850 4.12 949 4.81 1045 5.54 1137 6.30 1224 7.05
7900 997 5.99 1089 6.78 1174 7.58 1258 8.43
8600 1048 7.34 1133 8.20 1215 9.06 1293 9.96
SWPU 200T DBC
CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5400 745 2.17 868 2.74 983 3.32 1104 4.04 1229 4.89
6000 791 2.79 905 3.40 1012 4.03 1115 4.70 1225 5.53
6600 839 3.52 946 4.19 1047 4.89 1140 5.57 1235 6.34
7200 887 4.38 988 5.10 1082 5.84 1173 6.60 1258 7.36
9
BLOWER PERFORMANCE TABLE contd
% of NominalAir Flowrates
Total CapacitySensibleCapacity
80% 0.960 0.900
90% 0.980 0.950
100% 1.000 1.000
110% 1.015 1.045
120% 1.025 1.090
Correction FactorsA) VARIATION in Air Flowrates
Altitude abovesea level - ft
Total CapacitySensibleCapacity
0 1.00 1.00
2000 0.99 0.93
4000 0.97 0.88
6000 0.95 0.82
8000 0.93 0.76
B) VARIATION in Altitude above SEA LEVEL
Dry Bulb FWET BULB F
57 F 62 F 67 F 72 F
75 F 0.84 0.81 0.78 0.74
80 F 1.00 1.00 1.00 1.00
85 F 1.16 1.21 1.21 1.26
C) VARIATION in Dry Bulb Temperature on Sensible Capacity
If after applying the correction factor, thecalculated sensible capacity exceeds totalcooling capacity, than the sensible capacitymust be adjusted to be equal the totalcooling capacity.
Note:
-
7/30/2019 Ducted Unit
8/8
MODEL BLOWER MODEL
Air flowrates (cfms) vs External Available Static Pressure WG
0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 1.00"
SWPU 21 DDCKDD 8/8,4P 165W
870 830 730 660 510 435 N.A. N.A.
(Alternative)KDD 8/84P 180W
N.A. 880 810 730 605 480 N.A. N.A.
SWPU 24 DDCKDD 8/84P 180W
980 910 860 780 670 555 N.A. N.A.
SWPU 28DDC KDD 9/7T4P 245W
1060 1050 1040 970 910 870 850 N.A.
SWPU 32 DDCKDD 9/7, Hi.
4P 245W1280 1270 1240 1210 1150 1100 1060 N.A.
(Alternative)KDD 9/7, Med.
4P 245W1130 1115 1095 1070 1010 940 N.A. N.A.
SWPU 38 DDCKDD 9/9T, Hi.
4P 350W1420 1390 1360 1320 1280 1200 1130 N.A.
SWPU 48 DDCKDD 9/9, Med.
4P 550W1700 1690 1680 1670 1650 1600 1560 1470
SWPU 58 DDCKDD 9/9, Hi.
4P 550W2120 2110 2090 2060 2020 1980 1860 1810
BLOWER PERFORMANCE TABLE
Note:1. Internal losses allowed for wet coils and 1" filters.
SWPU 72 DBC
CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1800 958 0.56 1193 0.82 1433 1.15
2250 1029 0.86 1245 1.17 1431 1.48 1618 1.85 1811 2.31
2500 1071 1.07 1274 1.40 1456 1.74 1620 2.09 1788 2.52
2750 1129 1.34 1316 1.69 1492 2.07 1649 2.44 1798 2.83
SWPU 82 DBC
CFM 0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WGRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2250 983 0.81 1205 1.10 1395 1.42 1580 1.77 1773 2.21
2500 1050 1.05 1254 1.37 1439 1.72 1604 2.05 1771 2.48
2750 1099 1.29 1286 1.64 1465 2.00 1625 2.39 1774 2.77
3000 1155 1.58 1328 1.95 1498 2.35 1656 2.77 1799 3.17
7
SWPU 100 DBC
CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2800 861 0.94 1040 1.26 1203 1.62 1391 2.11 1578 2.67
3200 934 1.30 1095 1.65 1246 2.04 1388 2.46 1552 3.01
3600 991 1.69 1141 2.09 1279 2.50 1412 2.94 1537 3.41
4000 1052 2.16 1192 2.62 1322 3.06 1445 3.52 1564 4.01
SWPU 130 DBC
CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3600 939 1.56 1094 1.96 1235 2.36 1371 2.79 1497 3.25
4000 1012 2.05 1156 2.50 1289 2.94 1413 3.40 1534 3.88
4400 1072 2.59 1207 3.07 1332 3.56 1449 4.05 1562 4.55
4800 1138 3.25 1264 3.76 1382 4.28 1494 4.83 1600 5.36
SWPU 150 DBC
CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4000 850 1.72 1006 2.21 1156 2.79 1302 3.44 1441 4.17
4500 901 2.24 1046 2.78 1178 3.38 1313 4.04 1442 4.77
5000 957 2.87 1088 3.46 1214 4.09 1333 4.78 1454 5.50
5500 1017 3.62 1136 4.28 1255 4.94 1366 5.65 1474 6.42
8
SWPU 164T DBC
CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4400 869 2.05 1017 2.58 1153 3.17 1291 3.81 1423 4.52
4900 925 2.64 1058 3.22 1187 3.84 1308 4.51 1432 5.22
5400 984 3.36 1105 4.00 1226 4.64 1339 5.34 1449 6.09
5900 1043 4.20 1154 4.87 1266 5.58 1376 6.30 1477 7.07
SWPU 165 DBC
CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4800 894 2.43 1030 3.01 1162 3.60 1286 4.27 1412 4.97
5200 945 2.99 1070 3.60 1196 4.23 1312 4.91 1427 5.64
5600 998 3.64 1115 4.28 1233 4.95 1345 5.65 1451 6.40
6000 1050 4.36 1160 5.03 1270 5.76 1379 6.48 1480 7.25
BLOWER PERFORMANCE TABLE contd