dvanced a - cota · 2019-10-24 · q.in the base bid, contractor shall provide a bid allowance of...
TRANSCRIPT
DATE:DRN:DSN:
SHEET:SCALE:
CHK:
OF 4
SEPTEMBER 23, 2019
COTANORTHLAND TRANSIT CENTER
5495 CLEVELAND AVENUEEV CHARGING STATIONS
SUBMITTAL: BID SET
REV NUMBER REV DATEREV DESCRIPTION
A DVANCEDE NGINEERINGC ONSULTANTS
Mechanical | Electrical | Plumbing | Fire Protection1405 Dublin Road Tel: (614) 486-4778Columbus, Ohio 43215 Fax: (614) 486-4082
Date:
10/23
/2019
6:48
PM
File L
ocati
on:Z
:\201
9 pro
j\19-
008-
03 C
OTA
EV C
harg
ing\C
AD\C
AD S
heets
\3 No
rthlan
d Tra
nsit C
enter
\ Las
t Edit
:Gav
inL
E-001NONE 1
M. CALDWELLG. LIMAND SCHEDULES
GENERAL INFORMATIONELECTRICAL
LINE TYPE LEGENDEXISTING TO REMAIN
UNDERGROUND CONDUITS
NEW WORK
ELECTRICAL SYMBOLSNOTE: NOT ALL SYMBOLS MAY BE USED.
20A DUPLEX RECEPTACLE WITH COVER PLATE: X=TYPE,Y"=NON-STANDARD MOUNTING HEIGHT, Z=SPECIAL DESIGNATION,(18" AFF TYPICAL)
XYZ
PANELBOARD
FUSIBLE SWITCH
PULLBOX/HANDHOLE AS INDICATED ON PLANS
NTS3 SCHEDULE - PANEL B
GENERAL NOTES:
A. ALL INSTALLATIONS SHALL COMPLY WITH ANY APPLICABLE LOCAL AND NATIONAL BUILDING CODES, ANDTHE NATIONAL ELECTRICAL CODE (NEC) 2017 EDITION.
B. COORDINATE ANY UTILITY OUTAGES WITH THE OWNER NO LESS THAN 14 CALENDAR DAYS PRIOR.
C. WHERE EXACT DIMENSIONS ARE NOT CALLED OUT, THE LOCATION OF EQUIPMENT, JUNCTION BOXES,OUTLETS, WIRE WAYS, PANELS ETC. ARE TO BE IDENTIFIED ON COORDINATION DRAWINGS FOR REVIEWACCORDING TO PROJECT GENERAL CONDITIONS.
D. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S WRITTENINSTRUCTIONS.
E. ALL INSTALLATIONS SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER. CONDUIT SHALL BEDEBURRED, CAPPED, AND TAGGED.
F. CONTRACTOR IS RESPONSIBLE FOR ALL REMOVAL AND DISPOSAL OF DEBRIS FROM THE SITERESULTING FROM ELECTRICAL CONSTRUCTION ACTIVITIES.
G. UNLESS NOTED OTHERWISE, CIRCUIT WITH TYPE THWN COPPER CONDUCTORS IN CONDUIT.LIQUID-TIGHT NON-METALLIC CONDUITS SHALL BE USED FOR FINAL CONNECTIONS TO ALL EQUIPMENT.QUANTITIES AND SIZE AS NOTED.
H. UPON COMPLETION OF WORK, ALL MATERIALS AND EQUIPMENT FURNISHED IN THIS CONTRACT SHALLBE THOROUGHLY CLEANED OF DIRT, GREASE, RUST AND OILS. PREPARE FOR FINISH PAINTING ORTOUCH-UP AS REQUIRED.
I. ALL OUTDOOR INSTALLATION SHALL BE WITH WEATHERPROOF RATED ENCLOSURES AND DEVICES (E.G.NEMA 3R, IP65 RATED).
J. PROVIDE BLANK COVERS FOR ALL BOXES WITHOUT PLATES.
K. PROVIDE WEATHER-RESISTANT SELF-ADHESIVE PRINTED LABELS DESCRIBING BOXES. LABEL SHALL BEPRINTING IN A TRUE-TYPE FONT AND SIZED FOR LEGIBILITY.
L. DRAWING REPRESENTS AN APPROXIMATION OF INITIAL CONDITIONS. ELECTRICAL CONTRACTOR SHALLFIELD VERIFY EXTENT OF THE DEMOLITION WORK PRIOR TO BID.
M. UNLESS NOTED OTHERWISE, EXISTING DEVICES ARE TO REMAIN.
N. ALL REMAINING OPENINGS IN JUNCTION BOXES OR BACK BOXES AS A RESULT OF DEMOLITION WORKSHALL BE CLOSED WITH BLANK COVERPLATES AND KNOCKOUT CLOSURES. MATCH EXISTING FINISH.
O. UNLESS NOTED OTHERWISE, ALL CONDUCTORS OF DEMOLISHED DEVICES AND EQUIPMENT THAT ARENOT INDICATED FOR REUSE SHALL BE COMPLETELY REMOVED BACK TO SOURCE.
P. PROVIDE UPDATED AND TYPEWRITTEN DIRECTORY IN PANELBOARDS WHERE WORK HAS BEENPERFORMED.
Q. IN THE BASE BID, CONTRACTOR SHALL PROVIDE A BID ALLOWANCE OF $1,000.00 FOR CUSTOM LOGO ONEV CHARGER AND UTILITY (AEP) AID-TO-CONSTRUCTION COSTS.
IN LAWN AREAS, SAVE TOP SOIL. PAVING, STREETS,DRIVES, PARKING, CURBS, FOOTINGS, GUTTERS,STEPS, SIDEWALKS AND SIMILAR SURFACES TOMATCH ORIGINAL CONDITION
12"
30" M
INIM
UM
COMPACTED GRANULAR FILL TO PAVEMENTOR SIDEWALK. OTHERWISE, SELECTEDBACKFILL TO GRADE
3"
3"
3"
3"3"
3"
CONCRETE ENCASEMENT 4000PSI.TROWEL RED COLORENDUM INTOTOP OF CONCRETE.
FINISHED GRADE
RED METAL BACKEDPOLYETHYLENE TAPE MARKED"ELECTRIC", ONE TAPE PER THREEHORIZONTAL CONDUITS
GRANULAR BACKFILL
SCHEDULE 40 PVC CONDUIT SIZE ANDQUANTITY OF CONDUITS VARIES WITHLOCATION. TRANSITION FROM PVC TO RIGIDSTEEL CONDUIT LAST 6 FEET TO MANHOLES,HANDHOLES, BUILDINGS, AND/ OREQUIPMENT.
CONDUIT SUPPORTBACKFILL NOTES:UNDER LAWN AREAS, SIDEWALK, STEPS ETC:CLEAN CLAY OR SAND WATER COMPACTED IN TWO OR MORE LAYERS.
UNDER ROADS, DRIVES, STREETS, PARKING, CURBS, GUTTERS ETC.:CLEAN SAND WATER COMPACTED IN 6" LAYERS.
NTS1 DETAIL - CONCRETE-ENCASED DUCT BANK
CAUTION ELECTRIC12"
3"
2"
3"
3"
24" M
INIM
UM
3"
2"
SAND COVER
COMPACTED GRANULAR FILLTO PAVEMENT OR SIDEWALK.OTHERWISE, SELECTEDBACKFILL TO GRADE
FINISHED GRADE
RED METAL BACKED POLYETHYLENE TAPEMARKED "ELECTRIC", OR ONE TAPE PERTHREE HORIZONTAL CONDUITS
GRANULAR BACKFILL, USE LSM-50 UNDERPAVEMENT AND WITH-IN 5'-0" OF PAVEMENT EDGE
CONDUIT SPACER
TRENCH WIDTH ASREQUIRED
SCHEDULE 40 PVC CONDUIT, SIZE AND QUANTITY OF CONDUITSVARIES WITH LOCATION. REFER TO ELECTRICAL SITE PLAN.TRANSITION FROM PVC TO RIGID STEEL CONDUIT LAST 6 FEETTO MANHOLES, HANDHOLES, BUILDINGS AND/OR EQUIPMENT.
NTS2 DETAIL - DIRECT BURIED CONDUIT1
1 ADDENDUM 2 10/24/19
1
NTS4 DETAIL - PANEL B ON BUILDING EXTERIOR
PROVIDE PANEL "B" TO SERVE EVCHARGING STATIONS. PROVIDEFEEDER (THROUGH ELECTRICMETER) FROM PANEL "A" LOCATEDIN BUILDING ELECTRICAL ROOM.REFER TO SHEET E-003 FORADDITIONAL REQUIREMENTS
PROVIDE ELECTRIC METERFOR PANEL "B".
PROVIDE WEATHER-TIGHT CONDUIT LBELBOW AND PENETRATION INTO ELECTRICALROOM FOR PANEL "B" SUB-FEED. PROVIDEWEATHER-TIGHT MECHANICAL SEAL FORWALL AT CONDUIT PENETRATION.
PROVIDE SPD TO SERVEPANELBOARD. MERSENSTXP240P10(APPROVED EQUALS: PQI,SQUARE D OR EATON)
DUAL EV CHARGING STATION WITH BOLLARDMOUNTING KIT (CHARGEPOINT). INSTALL PERMANUFACTURER'S WRITTEN INSTRUCTION.PROVIDE FACTORY AUTHORIZED STARTUPAND TRAINING FOR THE OWNER'SREPRESENTATIVE.
GRADE
UTILIZING THE BID ALLOWANCE AS DESCRIBEDON SHEET E-001, PROVIDE CUSTOM AEP ANDCOTA LOGOS ON THE EV CHARGING STATION.COORDINATE EXACT GRAPHICS WITH AEP ANDCOTA AND COORDINATE PRINTING OF THELOGOS WITH THE MANUFACTURER.
46"
30"
9" 3"
36" R
2'-6"
MIN
.
90° BEND
REINFORCE WITH 6x6-W2-9/2-9EPOXY COATED MESH
CLASS "QC1"CONCRETE
4" MIN. COMPACTEDGRANULAR FILL
TO EXISTING PULLBOX
FRONT
PULL SERVICING WIRING UP THROUGH THE CONDUIT,LEAVING APROXIMATELY 6' EXTENDING OUT OF THECONDUIT. MAKE FINAL CONNECTIONS PERMANUFACTURER'S WRITTEN INSTRUCTIONS.
CHARGING STATION,SEE DETAIL 1
BOLLARD SEE DETAIL 2
1" GALVANIZED RIGID STEEL STUB UPCONDUIT
8"4"
12"
6"
8" 8"8" 14" 8"
BOLLARD
EV CHARGING STATION
BOLLARD
PLAN VIEW
SECTION
FRONT OF CONCRETE PAD SHALLBE INSTALLED FLUSH AGAINSTCURB OF PARKING LOT
3'-0"
MIN
.3'-
0"
BOLLARD SEE DETAIL 2
PROVIDE GREEN STRIPINGINSIDE EXISTING PARKINGLOT AROUND PERIMETEROF ENTIRE SPACE WHEREEV CHARGING STATION ISPROVIDED
EV CHARGING STATION.REFER TO PLANS FOR LOCATION.
CURBSIGNAGE. SEE DETAIL 5/E-002
ELECTRICVEHICLEPARKING
ONLY
PROVIDE GREEN PAINTEDLETTERING WITHINPARKING SPACEELECTRIC
VEHICLEPARKING
ONLY
DATE:DRN:DSN:
SHEET:SCALE:
CHK:
OF 4
SEPTEMBER 23, 2019
COTANORTHLAND TRANSIT CENTER
5495 CLEVELAND AVENUEEV CHARGING STATIONS
SUBMITTAL: BID SET
REV NUMBER REV DATEREV DESCRIPTION
A DVANCEDE NGINEERINGC ONSULTANTS
Mechanical | Electrical | Plumbing | Fire Protection1405 Dublin Road Tel: (614) 486-4778Columbus, Ohio 43215 Fax: (614) 486-4082
Date:
10/23
/2019
6:39
PM
File L
ocati
on:Z
:\201
9 pro
j\19-
008-
03 C
OTA
EV C
harg
ing\C
AD\C
AD S
heets
\3 No
rthlan
d Tra
nsit C
enter
\ Las
t Edit
:Gav
inL
E-002NONE 2
S. SMITHG. LIM
DETAILSELECTRICAL
NTS1 DETAIL - EV CHARGING STATION
NTS2 DETAIL - PROTECTION BOLLARD FOR CHARGING STATIONNTS3 DETAIL - BASE PLATE/BOLLARD MOUNTING FOR CHARGING STATION
BASIS OF DESIGN: VESTIL - BOLPP-62-5.5
NTS4 DETAIL - EV CHARGING STATION PARKING SPACENTS5 DETAIL - EV CHARGING STATION SIGNAGE
BASIS OF DESIGN: myparkingsign.com, ITEM K-5507 (ENGINEER GRADE REFLECTIVE ALUMINUM)
NTS4 DETAIL - EV CHARGING STATION PARKING SPACE
NTS1 DETAIL - EV CHARGING STATION
NTS2 DETAIL - PROTECTION BOLLARD FOR CHARGING STATION
BASIS OF DESIGN: VESTIL - BOLPP-62-5.5
NTS3 DETAIL - BASE PLATE/BOLLARD MOUNTING FOR CHARGING STATION
BASIS OF DESIGN: CHARGEPOINT(CT4021-GW1-CT4000-PMGMT-CT4001-CCM-CPCLD-COMMERICAL-5-CT4000-ASSURE5-CPSUPPORT-ACTIVE)
1
1 ADDENDUM 2 10/24/19
1
33
24
2
5
4
5
4
5
6
6
B-6,8
B-2,4
B-1,3
67 (TYP.)
8
M
B
9
10
DATE:DRN:DSN:
SHEET:SCALE:
CHK:
OF 4
SEPTEMBER 23, 2019
COTANORTHLAND TRANSIT CENTER
5495 CLEVELAND AVENUEEV CHARGING STATIONS
SUBMITTAL: BID SET
REV NUMBER REV DATEREV DESCRIPTION
A DVANCEDE NGINEERINGC ONSULTANTS
Mechanical | Electrical | Plumbing | Fire Protection1405 Dublin Road Tel: (614) 486-4778Columbus, Ohio 43215 Fax: (614) 486-4082
01"=20'-0" 10' 20' 40'1 ELECTRICAL SITE PLAN
CODED NOTES:
1. APPROXIMATE LOCATION OF EXISTING ELECTRICAL/DATA ROOM.
2. PROVIDE ONE 2" UNDERGROUND CONDUIT FOR POWER TO SERVE PULLBOX. PRIORTO TRENCHING WORK, CONTRACTOR SHALL PROVIDE GROUND PENETRATING RADARSCANNING TO VERIFY THAT THERE ARE NO CONFLICTS WITH OTHER UTILITIES.
3. PROVIDE 17" X 30" X 18" UNDERGROUND PULLBOX (QUAZITE) TO SERVE EV CHARGINGSTATIONS.
4. PROVIDE 12" X 12" X 12" UNDERGROUND PULLBOX (QUAZITE) TO SERVE ELECTRICVEHICLE CHARGER FEEDERS.
5. PROVIDE ONE 2" UNDERGROUND CONDUIT VIA PULLBOXES TO EV CHARGERS.
6. APPROXIMATE LOCATION OF EV CHARGING STATION CONCRETE PAD. REFER TODETAILS ON E-002. VERIFY EXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.
7. PROVIDE #8AWG CONDUCTORS BETWEEN PULLBOX AND CHARGING STATION(TYPICAL OF 3 LOCATIONS).
8. PROVIDE CONCRETE ENCASEMENT FOR UNDERGROUND CONDUITS BENEATHDRIVEWAY.
9. PROVIDE 150A SUB-FEED (UNDER 10') WITH 2 - #1/0 AWG CONDUCTORS AND #6 AWGGROUND IN 2" RGS CONDUIT FROM EXISTING PANEL "A" IN ELECTRICAL ROOMTHROUGH UTILITY (AEP) METER TO SERVE PANEL "B". PROVIDE WALL MOUNTEDMETER BASE FOR AEP METER. COORDINATE EXACT REQUIREMENTS WITH AEP.METER SHALL BE SUPPLIED BY AEP AND INSTALLED BY THE CONTRACTOR
10. PROVIDE 150A, 240/120V, 1Ø, NEMA 3R PANELBOARD FOR EV CHARGING STATIONS.MOUNT ON WALL BY METER. ATTACH WEATHER-RESISTANT VINYL LABEL ONPANELBOARD STATING "FOR EV CHARGERS ONLY". REFER TO PANEL SCHEDULE ONSHEET E-001.
N
Date:
10/23
/2019
6:53
PM
File L
ocati
on:Z
:\201
9 pro
j\19-
008-
03 C
OTA
EV C
harg
ing\C
AD\C
AD S
heets
\3 No
rthlan
d Tra
nsit C
enter
\ Las
t Edit
:Gav
inL
E-0031" = 20'-0" 3
M. CALDWELLG. LIM
SITE PLANELECTRICAL
1
1
1 ADDENDUM 2 10/24/19
1
1
1