e0-01 · lguc office 455 2 students lguc office 454 2 rts lguc office 453 # 2 interview 425 bedroom...
TRANSCRIPT
-
DRAWING NUMBER DRAWING TITLE SCALE
E0-01 ELECTRICAL LEGEND AND DRAWING LIST N.T.S
UNIT # 1 - 1st - FLOOR ENLARGED PLANS POWER AND SYSTEMS LAYOUT
EMERGENCY POWER PANELBOARD SURFACE MOUNTED
SINGLE RECEPTACLE.
SINGLE POLE LIGHT SWITCH MOUNTED AT 1200mm A.F.F.
DUPLEX RECEPTACLE
POWER AND CONTROL
DUPLEX RECEPTACLE CEILING MOUNTED.
DIRECT CONNECTION TO EQUIPMENT
D-DATAV-VOICEO-BLANK PLATECC-CCTV CONTROLLER
WALL MOUNTED VOICE OUTLET
FIRE DETECTION & VOICE ALARM
FIRE ALARM PANEL ANNUNCIATOR
DESCRIPTIONSYMBOL
W SINGLE OR DOUBLE SURFACE MOUNTED RACEWAY.
DUPLEX RECEPTACLE-WALL MOUNTED COUNTER HEIGHT. REFER TO
CEILING MOUNTED 1'x4' RECESSED FLUORESCENT LUMINAIREON EMERGENCY CIRCUIT
CEILING MOUNTED RECESSED DOWNLIGHT
LIGHTING
CEILING MOUNTED 2'x4' RECESSED FLUORESCENT LUMINAIRE
CEILING MOUNTED 2'x4' RECESSED FLUORESCENT LUMINAIREON EMERGENCY CIRCUIT
AT
KEY SWITCH TO RELEASE
3-WAY SWITCH.
DIMMER SWITCH.
WALL MOUNTED DATA OUTLET
FIRE ALARM HORN/SPEAKER
DOOR CONTACT
ACCESS CONTROL OVERRIDEB-BUTTONK-KEYSWITCHT-TOGGLE
WALL MOUNTED VOICE AND DATA OUTLET
-ONE(1) CABLE DROP
-ONE(1) CABLE DROP. 'C' DENOTES DATA FOR CCTV CAMERA,
-ONE(1) CABLE DROP FOR EACH
CEILING MOUNTED 1'x4' RECESSED FLUORESCENT LUMINAIRE
EXIT SIGN - CEILING MOUNTEDARROW DENOTES DIRECTION
3-WAY DIMMER SWITCH.
TELECOMMUNICATIONS OUTLET ASSEMBLY
ELECTROMAGNETIC DOOR LOCK TEMPORARILY
EXIT SIGN - WALL MOUNTEDARROW DENOTES DIRECTION
CARD READER
ELECTROMAGNETIC DOOR LOCK
ELECTRIC DOOR STRIKE
ACCESS CONTROL ABBREVIATIONS
E
ER
R
RL
C
R END OF LINE RESISTOR.
FKS FIRE ALARM KEY STATION
DENOTES EXISTING FIXTURE/EQUIPMENT TO REMAIN UNCHANGED
DENOTES EXISTING FIXTURE/EQUIPMENT IN RELOCATED POSITION
DENOTES EXISTING FIXTURE/EQUIPMENT TO BE DISCONNECTED,REMOVED
DENOTES EXISTING FIXTURE/EQUIPMENT TO BE RELOCATED.
DENOTES EQUIPMENT TO BE MOUNTED AT COUNTER HEIGHT.
MOTORM
FIREMANS HAND SETFA
DR DENOTES DOOR RELEASE.
WALL MOUNTED TV CONNECTION OUTLET-ONE(1) COAX CABLE DROP
COUNTER MOUNTED VOICE AND DATA OUTLET-ONE(1) CABLE DROP FOR EACH
DESCRIPTIONSYMBOL
OCCUPANCY SENSOR CEILING/WALL MOUNTED
SECURITY CAMERA
HK DENOTES HOUSE KEEPING RECEPTACLE - CSA TYPE '5-520R'
GFI DENOTES GROUND FAULT INTERRUPT
FG DENOTES FRIDGE
V DENOTES VANDAL RESISTANT
FIRE ALARM HORN WITH STROBE
POWER AND/OR DISTRIBUTION PANELBOARD - SURFACE MOUNTEDDP - DENOTES DISTRIBUTION PANELLP - DENOTES LIGHTING AND RECEPTACLE PANEL
POWER AND/OR DISTRIBUTION PANELBOARD- RECESSED
3
D
3/D
TV
F DISCONNECT SWITCH FUSED
DISCONNECT SWITCH NON FUSIBLE
OS
CR
DL
DS
DC
H
F
DESCRIPTIONSYMBOL
DUCT SMOKE DETECTORSD
FIRE ALARM SPEAKERS
POWER AND/OR COMMUNICATIONS HARDWIRE DIRECTCONNECTION TO FURNITURE SYSTEMS
S
DUPLEX RECEPTACLE FED FROM EMERGENCY.
WDR DENOTES WASHROOM DOOR RELEASE
T T - DENOTES TAMPER RESISTANT SCREWS
T T - DENOTES TAMPER RESISTANT SCREWS
F FIRE ALARM PULL STATION
R FIRE ALARM ADDRESSABLE RELAY MODULE
BK
STRIP LIGHTING
RECEPTACLES
SWITCHES & CONTROLS
TELEPHONE AND COMMUNICATIONS
A7DUPLEX RECEPTACLE IN UNDERFLOOR/ACCESS FLOOR/TABLE TOP RECESSED BOX
ARCHITECTURAL DRAWINGS FOR DETAILS.
C
MOUNTED ABOVE CEILING AND CABLE CONCEALED.
KR
DOOR HELD OPEN DEVICED H
KEY RELEASEK
DOOR BUZZER
F/S
Y
FS
PS
M
ALARM OR SUPERVISED VALVE
FLOW SWITCH
MONITOR MODULE
PRESSURE SWITCH
SMOKE DETECTOR'V' - DENOTES VANDAL RESISTANT
HEAT DETECTOR'V' - DENOTES VANDAL RESISTANT
SS NSS ACCESS CONTROL DOOR TYPESS- DENOTES DOOR SECURED SIDENSS- DENOTES DOOR NON-SECURED SIDE
3/32" = 1'- 0"
OS
E0-02 ELECTRICAL UNIT # 1 - 1st - FLOOR REFERENCE
NL DENOTES NIGHT LIGHT
LEGEND AS APPLICABLE LEGEND AS APPLICABLE
N DENOTES NEW EQUIPMENT TO BE INSTALLED
3/32" = 1'- 0"
1/4" = 1'- 0"
1/4" = 1'- 0"UNIT # 1 - 1st - FLOOR ENLARGED PLANS POWER AND SYSTEMS LAYOUT
UNIT # 1 - 1st - FLOOR ENLARGED PLANS POWER AND SYSTEMS LAYOUT
UNIT # 1 - 1st - FLOOR ENLARGED PLANS POWER AND SYSTEMS LAYOUT
1/4" = 1'- 0"
E2-01
E2-02
E0-03 ELECTRICAL UNIT # 1 - 4th - FLOOR REFERENCE
E2-03
E2-04
E2-05
E2-06
UNIT # 1 - 4th - FLOOR ENLARGED PLANS POWER AND SYSTEMS LAYOUT
UNIT # 1 - 4th - FLOOR ENLARGED PLANS POWER AND SYSTEMS LAYOUT
1/4" = 1'- 0"
1/4" = 1'- 0"
1/4" = 1'- 0"
UNIT # 1 - 1st - FLOOR DEMOLITION PLANE8-01
E8-02 UNIT # 1 - 4th - FLOOR DEMOLITION PLAN
3/32"=1'-0"
3/32"=1'-0"
DOOR OPERATORDO
CR
IC
D
CARD READER
DOOR BELL
INTERCOM
E3-01 UNIT # 1 - 1st - FLOOR LIGHTING PLAN
E3-02 UNIT # 1 - 4th - FLOOR LIGHTING PLAN
3/32"=1'-0"
3/32"=1'-0"
UNIT # 1 - 1st - FLOOR DEMOLITION LIGHTING PLANE8-03
E8-04 UNIT # 1 - 4th - FLOOR DEMOLITION LIGHTING PLAN
3/32"=1'-0"
3/32"=1'-0"
METAL DETECTORMD
CDUPLEX RECEPTACLE CEILING MOUNTED.
PUSH BUTTON
CCT DENOTES CIRCUIT NUMBERS
XD DENOTES X NUMBER OF DATA DROPSQUAD RECEPTACLE WALL MOUNTED.
CODE WHITE PUSH BUTTON (BY OTHERS)
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E0-01 LEGEND.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:19 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
M. KUTA
M. LI
UNIT # 1 ELECTRICAL LEGEND AND DRAWING LIST
E0-01
0ISSUED FOR PERMIT / TENDER2019-12-06
-
1
E2-01
104ROOM #1SEARCH
184AWATINGPHALLO
168OFFICE
169OFFICE
176OFFICE
178OFFICE
179OFFICE
175INTERIVIEW
150(SBC and FOPS)TREATMENT RM
SHARED
112AWORK ROOM
SHARED
180OFFICE
167STAFFOFFICE
168AOFFICE
160RESEARCH
OFFICE
161OFFICE
145WORKSTATIONS
133WORKSTATIONS
126OFFICE
126APSYCHOLOFFICE
125ADMINOFFICE
124MANAGER
OFFICE
118OFFICE
184OFFICE
PHALLO LAB
184BPHALLO LAB
155ALOUNGE ROOM
STAFF /
177MANAGER
OFFICE
101LOBBY
102ROOM
SECURITY
103ROOM #2SEARCH
195ROOM
WATING
153MEETING ROOMSMALL TEAM /
129HUB
RECEPTION
119OFFICE
117OFFICE
190CORRIDOR
191CORRIDOR
128CORRIDOR
108CORRIDOR
159CORRIDOR
196CORRIDOR
197CORRIDOR
17
0C
OR
RID
OR
199CORRIDOR
194CORRIDOR
193CORRIDOR
AA27OFFICE
AA14OFFICE
AA10OFFICE
AA1CW
INTERVIEW
1634 WRKST
156W
171W
172
186ROOM
CONFERENCE
182W
183W
174ELECT106WC
107WC
109ELECT
110JAN
192 AREA
WAITING
112
115(FORCAT/SBC)GROUP ROOM
SHARED122W
121W
131INTERVIEW
132ROOMGROUP
146INTERVIEW
144INTERVIEW
144AINTERVIEW
148WC
149STORAGE
143ELECT
137STORAGE
138WC
135INTERVIEW
198
142OFFICE
141OFFICE
140INTERVIEW
139OFFICE
158AMED ROOM
112BKITCHENETTE
EXIST. SKYLIGHTBELOW (TYP.)
105 100VESTIBULE
16
2C
OR
RID
OR
1
E2-02
1
E2-03
1
E2-04
EXISTING PANEL'LP-1A-1A'
EXISTINGPANEL'LP-1A-1E'
EXISTINGFIRE ALARMANNUNCIATOR
EXISTING PANEL'LP-1A-1D'
EXISTINGPANEL'LP-1A-1B'
EXISTINGPANEL'LP-1A-1C'
3/32"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 1 FLOOR REFERENCE PLAN
E0-021
E0-02
UNIT # 1 - 1 FLOOR PLAN3/32"=1'-0"
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E0-02 - UNIT#1 - 1 FLOOR REFERENCE PLAN.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:19 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
0ISSUED FOR PERMIT / TENDER2019-12-06
-
1
E2-05
402BMD
OFFICE
402AMD
OFFICE
402WS
OFFICESHARED
408WORKSTATIONS
HOTELING
401LOUNGE
TEAM ROOM/
461MD
LGUCOFFICE
460SW
LGUCOFFICE
459OT
LGUCOFFICE
456MANAGER
LGUCOFFICE
4552 STUDENTS
LGUCOFFICE
4542 RTSLGUC
OFFICE
453# 2
INTERVIEW
425BEDROOM
SWING
426ROOM
PATIENT
427ROOM
PATIENT
428ROOM
PATIENT
432ROOM
PATIENT
433ROOM
PATIENT
434ROOM
PATIENT
435ROOM
PATIENT
440ROOM
PATIENT
439ROOM
PATIENT
438ROOM
PATIENT
458CWASHROOM
458DWASHROOM
458BWASHROOM
PATIENT
415ROOM
MEETINGFAMILY
CEXIST.
C EXIST.
CEXIST.
C EXIST.
C EXIST.
C
C
EXIST.
CEXIST.
EXIST.
EXIST.
B
A
6A41.01
490CORRIDOR
429CORRIDOR
442CORRIDOR
493CORRIDOR
495CORRIDOR
494CORRIDOR
437CWC
437DWC
437AWC
437BWC
43
6EL
EC
431BATH
430SHOWER
441COMFORT
419LOUNGE
GROUP ROOM/
418JAN
417ELEC
417VESTIBULE
UNIT ENTRY
411RECREATION
DINING /
412WC
413WC
489SERVERY
469SOILED
423CLEAN
475LOUNGE
444WC
462EXAM
PRACTIONERS/VISITING
466TUB
488TUB
467MED
450STORAGE
451INTERVIEW #1
446GREETING
447ROOM
CHARTING
448COPIER
449SECLUSION
452SHOWER
458ALAUNDRY
457AELEC
487SHOWER
480ELEC
481AWC
481BWC
481CWC
481DWC
485 ROOM
PATIENT
484 ROOM
PATIENT
483 ROOM
PATIENT
482 ROOM
PATIENT
479 ROOM
PATIENT
478 ROOM
PATIENT
477 ROOM
PATIENT
476 ROOM
PATIENT
474 ROOM
PATIENT
473 ROOM
PATIENT
472 ROOM
PATIENT
471 ROOM
PATIENT
2
E2-06
1
E2-05
EXISTING PANEL'LP-1A-4A'
EXISTINGPANEL'LP-1A-4E'
EXISTING PANEL'LP-1A-4D' EXISTING PANEL
'LP-1A-4B'
3/32"=1'-0"
M. KUTA
A.BISWAS
UNIT # 1 - 4 FLOOR REFERENCE PLAN
E0-031
E0-03
UNIT # 1 - 4 FLOOR PLAN3/32"=1'-0"
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E0-03 - UNIT#1 - 4 FLOOR REFERENCE PLAN.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:20 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
0ISSUED FOR PERMIT / TENDER2019-12-06
-
77.6 S.F. 115 S.F.
304 S.F.
85 S.F.
75 S.F.
156.8 S.F. 165 S.F.194CORRIDOR
193CORRIDOR
186ROOM
CONFERENCE
182W
183W
174ELECT
106WC
107WC
109ELECT
110JAN
192 AREA
WAITING
RECEPTION DESK
105 100VESTIBULE
ELECTRICALROOM#109
EXISTINGPANEL'LP1A-1E'
2D
2D
2D
2D 2D
8D
2D
E
4D
CR
DO
CR
DO
CR
CR
CR
CR
DH
CR
CR
E
DH
CR E
DC
COFFEE
TEA KETTLE
TOASTER
MICROWAVE
EXISTINGPANEL'LP-1A-1B'
CR
CR
DC
DL
DC
F
MD
F
DL
DC
TV
E
CONNECT TO FIREALARM SYSTEM FORFIRE ALARM INTERFACE.
CONNECT TO FIRE ALARM SYSTEMFOR FIRE ALARM INTERFACE.
DS
EE
E
ECCT.#1B-26 CCT.#1B-26
E
E
E
EE
E
CCT.#1B-24CCT.#1B-24 E
E
EECCT.#1B-22
E
E
CCT.#1B-22
EE
CCT.#1B-20
FIRE ALARMPROTECTION PANEL
CC
T.#
1B-1
6
CC
T.#
1B-1
8
CC
T.#
1B-1
6
CCT.#1B-39
CC
T.#
1B-3
8
CC
T.#
1B-3
8
CC
T.#
1B-3
8
CC
T.#
1B-1
4
CC
T.#
1B-1
4
CCT.#1B-14
CC
T.#
1B-1
4
ER
E
E
ERER
CC
T.#
1B-2
1
CCT.#1A-31
E
CCT.#1B-40
CCT.#1B-10
CCT.#1B-40
CCT.#1B-41
120V AC/12V DC (AS PERSECURITY DEVICES REQUIREMENT)TRANSFORMER ABOVE CEILINGFOR DOOR SECURITY
CCT.#1A-12
E
E-34
E-38
E-39
E-40
E-41
E
TX
CC
T.#
1A
-8
5-20R
5-20R
5-20R
5-20R
5-20R
FKSE
EEEE
E
CONNECTED TODOOR BELL ATCORRIDOR #182
D
CCT.#A-33PROVIDE LABEL INDICATINGTHE PANEL DESIGNATION
CR
E
DL
E
E
E
FFAE
E
E
F
E
E
CCT.#1D-31WATER COOLER
TV
CCT.#1D-32
CCT.#1E-21
CCT.#1E-22LOCATION TO BECONFIRMED ON SITE
E
E
EE
CCT.#1B-40
POWER SUPPLY FOR MILLWORK LIGHTREFER TO ARCHITECTURAL DRAWINGA91-01 FOR DETAILS
REFER TO DWG. E2-04
GENERAL NOTES:1. VERIFY EXACT POWER REQUIREMENTS AND RECEPTACLES TYPES FOR SPECIAL EQUIPMENT
WITH MANUFACTURE PRIOR TO INSTALLATION. PROVIDE HARD WIRED CONNECTIONS FOREQUIPMENT IN LIEU OF RECEPTACLES OR VICE-VERSA AS REQUIRED.
2. CIRCUITING IN PART DIAGRAMMATIC, INTENDED TO SHOW GROUPING AND PANELDESIGNATION.
3. WHERE WALL MOUNTED POWER OUTLETS ARE SHOWN ADJACENT TO ONE ANOTHER, THEYSHALL BE GANGED UNDER A COMMON COVER PLATE.
4. OUTLETS NOT TO BE BACK TO BACK, TO BE STAGGERED.
5. CONTRACTOR TO CO-ORDINATE WITH OTHER DISCIPLINES & OWNER REGARDING POWERREQUIREMENTS, MOUNTING HEIGHTS OF TV, IT AND SECURITY POWER SUPPLY BEFOREROUGH-IN.
6. RESPONSIBILITY OF THE CONTRACTOR TO VERIFY KITCHEN EQUIPMENT DRAWINGS AND CUTSHEETS FOR EXACT POWER REQUIREMENTS AND PROVIDE BREAKERS AND CABLINGACCORDINGLY.
7. ADD 4 (FOUR)-15A, 120V BREAKER CIRCUITS #38, 39, 40 & 41 IN THE EXISTING PANEL'LP-1A-1B' TO PROVIDE POWER SUPPLY. THE BREAKERS TO MATCH EXISTING PANEL BREAKERS.THE CABLES TO BE 2x#12 AWG + GND-21 MMC.
8. ALL VOICE / DATA TO RUN IN CONDUIT HOME RUN TO THE IT RACK IN THE IT ROOM # 109.
9. ADD 2 (TWO) 15A, 120V BREAKERS IN CIRCUITS #31 AND 32 IN THE EXISTING PANEL'LP-1A-1D' TO PROVIDE POWER SUPPLY. THE BREAKERS TO MATCH THE EXISTING BREAKERSOF THE PANEL . THE CABLES TO BE 2X#10AWG+GND-21mmC. LABEL BOTH ENDS THE CIRCUITNUMBERS C/W PANEL DESIGNATION.
10. ADD 2-15A, 120V BREAKER IN CIRCUITS #21 & 22 IN THE EXISTING EMERGENCY PANEL'LP-1A-1E' TO PROVIDE POWER SUPPLY FOR CCTV AND DOOR SECURITY CONTROL PANELS.THE BREAKERS TO MATCH EXISTING BREAKERS OF THE PANEL. THE CABLES TO BE2X#12AWG+GND-21mmC.
11. CONTRACTOR TO TRACE ALL THE CIRCUITS (NEW AND EXISTING) AND REFLECT ON THEUPDATE PANEL SCHEDULE (ALL AFFECTED PANELS). THE FINAL PANEL SCHEDULES TO BELAMINATED AND STICK TO THE INSIDE PANEL DOOR.
12. POWER AND DATA CONDUITS TO RUN ABOVE THE CEILING.
13. THE COMMUNICATION CABLES TO BE BELDEN/NORDX CAT 6.
14. CONTRACTOR TO ALLOW FOR FIRE ALARM REPROGRAMMING AND ALARM GRAPHIC TO BEUPDATED ACCORDINGLY TO SUIT BY 'TYCO' AFFILIATED CONTRACTOR ONLY. PROVIDE FORFIRE ALARM VERIFICATION TO 'ULCS537' AND DEMONSTRATION TO GTAA.
15. THE EXISTING FIRE ALARM CONTROL PANEL MANUFACTURED BY NOTIFIER.
CCTV NOTES:
1. SUPPLY, INSTALLATION & COMMISSIONING OF THE ALL SURVEILLANCE CCTV CAMERASYSTEM AND DIGITAL VIDEO RECORDER
2. FIELD REVIEW OF THE CAMERAS TO BE FIELD VARIFIED WITH THE CAMH ENGINEER OF RECORD PRIOR TO ROUGH-IN.
3. THE CCTV CAMERA TO BE A COMPLETE SYSTEM , NOT LIMITED TO CONDUITS, CABLING, DEVICES, COMPLETE CONNECTION TO CONTROL PANELS AND PROGRAMMING AS PER CAMH.
a. CCTV CAMERA (SPECIFICATION TO BE SUPPLIED BY CAMH)b.NETWORK SWITCH (SPECIFICATION TO BE SUPPLIED BY CAMH)c. PATCH PANEL (SPECIFICATION TO BE SUPPLIED BY CAMH)
4. THE CONTRACTOR TO ENGAGE EXISTING CAMH CCTV VENDER FOR FINAL CONNECTION ANDREPROGRAMMING OF THE SYSTEM.
5 THE CABLES TO BE CAT6.
6. THE DIGITAL VIDEO RECORDER TO BE TruVision Navigator 8.
7. THE CCTV SYSTEM TO BE CONNECTED VIA NETWORK TO THE MAIN SECURITY OFFICE ANDSECURITY DESK.
DOOR SECURITY NOTES:
1. SUPPLY, INSTALLATION & COMMISSIONING OF THE ALL DOOR SECURITY SYSTEMOF THIS CONTRACT.
2. FIELD REVIEW OF THE DOOR SECURITY SYSTEM TO BE FIELD VARIFIED WITH THE CAMH ENGINEER OF RECORD , PRIOR TO ROUGH-IN.
3. THE DOOR SECURITY SYSTEM CABLING, DEVICES, COMPLETE CONNECTION TO CONTROL PANELS AND PROGRAMMING AS PER CAMH.
a. TWO PORT DOOR SECURITY SYSTEMINSTALLATION UNDER THIS CONTRACT.
b.1(ONE)- TWO PORT DOOR SECURITY SYSTEM
c. PATCH PANEL (SPECIFICATION TO BE SUPPLIED BY CAMH)
4. THE CONTRCTOR TO ENGAGE EXISTING CAMH DOOR SECURITY SYSTEMCONNECTION AND REPROGRAMMING OF THE SYSTEM.
5. THE CABLES TO BE CAT6.
1/4"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 1st - FLOORPOWER AND SYSTEMS PLANS
E2-01
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E2-01 - UNIT#1 - 1 FL-PWR PLANS.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:20 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
1
E2-01
ENLARGED 1st FLOOR POWER AND SYSTEMS PLAN1/4"=1'-0"
0ISSUED FOR PERMIT / TENDER2019-12-06
-
168OFFICE
169OFFICE
167STAFFOFFICE
168AOFFICE
160RESEARCH
OFFICE
161OFFICE
159CORRIDOR
196CORRIDOR
197CORRIDOR
17
0C
OR
RID
OR
AA27OFFICE
AA14OFFICE
AA10OFFICE
AA1CW
INTERVIEW
1634 WRKST
156W
171W
172
16
2C
OR
RID
OR
EXISTINGPANEL'LP1A-1C'
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
3D
CC
T.#
1C
-20
1D
(E)+
1D E
E
E
CC
T.#
1C
-20
E
CC
T.#
1C
-22
CC
T.#
1C
-22
EE
E
E E
E
CC
T.#
1C
-22
E
E
1D
(E)+
1D
CCT.#1C-37
CCT.#1C-9
CCT.#1C-9
CCT.#1C-9CCT.#1C-9
CCT.#1C-9
E
E
E
CCT.#1C-35
CCT.#1C-35
CCT.#1C-35
CCT.#1C-35
CCT.#1C-37
1D
(E)+
1D
CCT.#1C-9
CCT.#1C-9
CCT.#1C-9
CCT.#1C-35
CCT.#1C-35
CCT.#1C-35
CCT.#1C-9
CCT.#1C-9
CCT.#1C-37
OFFICE #AA27
2D
E
CCT.#1C-7
2DCCT.#1C-7
E
NEW CCTVCAMERAS(TYPICAL)
GENERAL NOTES:1. VERIFY EXACT POWER REQUIREMENTS AND RECEPTACLES TYPES FOR SPECIAL EQUIPMENT WITH MANUFACTURE PRIOR TO INSTALLATION. PROVIDE
HARD WIRED CONNECTIONS FOR EQUIPMENT IN LIEU OF RECEPTACLES OR VICE-VERSA AS REQUIRED.
2. CIRCUITING IN PART DIAGRAMMATIC, INTENDED TO SHOW GROUPING AND PANEL DESIGNATION.
3. WHERE WALL MOUNTED POWER OUTLETS ARE SHOWN ADJACENT TO ONE ANOTHER, THEY SHALL BE GANGED UNDER A COMMON COVER PLATE.
4. OUTLETS NOT TO BE BACK TO BACK, TO BE STAGGERED.
5. CONTRACTOR TO CO-ORDINATE WITH OTHER DISCIPLINES & OWNER REGARDING POWER REQUIREMENTS, MOUNTING HEIGHTS OF TV, IT ANDSECURITY POWER SUPPLY BEFORE ROUGH-IN.
6. RESPONSIBILITY OF THE CONTRACTOR TO VERIFY KITCHEN EQUIPMENT DRAWINGS AND CUT SHEETS FOR EXACT POWER REQUIREMENTS AND PROVIDEBREAKERS AND CABLING ACCORDINGLY.
7. ADD 2 (TWO)-15A, 120V BREAKER CIRCUITS #35 & 37 IN THE EXISTING PANEL 'LP-1A-1C' TO PROVIDE POWER SUPPLY. THE BREAKERS TO MATCHEXISTING PANEL BREAKERS. THE CABLES TO BE 2x#12 AWG + GND-21 MMC.
8. CONTRACTOR TO TRACE ALL THE CIRCUITS (NEW AND EXISTING) AND REFLECT ON THE UPDATE PANEL SCHEDULE (ALL AFFECTED PANELS). THE FINALPANEL SCHEDULES TO BE LAMINATED AND STICK TO THE INSIDE PANEL DOOR.
9. ALL VOICE / DATA TO RUN IN CONDUIT HOME RUN TO THE IT RACK IN THE IT ROOM # 109.
10. POWER AND DATA CONDUITS TO RUN ABOVE THE CEILING..
11. THE COMMUNICATION CABLES TO BE BELDEN/NORDX CAT 6.
12. CONTRACTOR TO ALLOW FOR FIRE ALARM REPROGRAMMING AND ALARM GRAPHIC TO BE UPDATED ACCORDINGLY TO SUIT BY 'TYCO' AFFILIATEDCONTRACTOR ONLY. PROVIDE FOR FIRE ALARM VERIFICATION TO 'ULCS537' AND DEMONSTRATION TO GTAA.
13. THE EXISTING FIRE ALARM CONTROL PANEL MANUFACTURED BY NOTIFIER.
1/4"=1'-0"
M. KUTA
A. BISHWAS
UNIT # 1 - 1st - FLOORPOWER AND SYSTEMS PLANS
E2-02
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E2-02 - UNIT#1 - 1 FL-PWR PLANS.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:21 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
1
E2-02
ENLARGED 1st FLOOR POWER AND SYSTEMS PLAN1/4"=1'-0"
0ISSUED FOR PERMIT / TENDER2019-12-06
-
112AWORK ROOM
SHARED
126OFFICE
126APSYCHOLOFFICE
125ADMINOFFICE
124MANAGER
OFFICE
118OFFICE
129HUB
RECEPTION
EXIST.C
429 S.F.
EXISTEXIST
119OFFICE
117OFFICE
190CORRIDOR
191CORRIDOR
128CORRIDOR
109ELECT
110JAN
192 AREA
WAITING
112
115(FORCAT/SBC)GROUP ROOM
SHARED
122W
121W
131INTERVIEW
132ROOMGROUP
112BKITCHENETTE
EXIST. RADIATOR
EXIST. SKYLIGHTBELOW (TYP.)
118OFFICE
02
A91-01
2D2D2D
2D2D
1-D(E)+1D
2D
2D
2D
2D
2D
2D
EXISTINGPANEL'LP1A-1A'
2D2D
2D
2D
2D
2D
2D
TV
ELECTRICALROOM#109
EXISTINGPANEL'LP1A-1E'
CR
CR
CR
CR
CR
DH
DH
CR
CR
CR
DL
E
CR
DH
CR E
DC
IC
F
DL
DC
DC
F
D
E
E
E
E
SECURITYMONITOR(CCTV)
TV
CONNECT TO FIRE ALARM SYSTEMFOR FIRE ALARM INTERFACE.
CONNECT TO FIREALARM SYSTEM FORFIRE ALARM INTERFACE.
EXISTING DOOR HARDWARE TO BEDISMANTLED AND INSTALL BACKTO NEW DOOR FRAME.
CONNECT TO FIRE ALARM SYSTEMFOR FIRE ALARM INTERFACE.
CC
T.#
1A
-16
CC
T.#
1A
-16
CC
T.#
1A
-16
E
CC
T.#
1A
-18
CC
T.#
1A
-18
CCT.#1A-17
EE
CCT.#1A-13
CCT.#1A-13
CCT.#1A-13
CCT.#1A-17
CC
T.#
1A
-18
CC
T.#
1A
-16
CC
T.#
1A
-16
CC
T.#
1A
-18
CC
T.#
1A
-16
CCT.#1A-17
E
CCT.#1A-17
CCT.#1A-17
1-D
(E)+
1D E E
E
E
E
E
1-D
(E)+
1D E
E
E
E
E
1-D
(E)+
1D
E CC
T.#
1A
-22
CC
T.#
1A
-22 E
1-D
(E)+
1D
E
CCT.#1A-8
CCT.#1A-8
CC
T.#
1A
-8
CC
T.#
1A
-8
CCT.#1A-8
CCT.#1A-8
CCT.#1A1E-17
5-20R
E
E
CCT.#1A-10
CCT.#1A-10
CCT.#1A-10
CCT.#1A-10
CC
T.#
1A
1E-
19
CC
T.#
1A
1E-
19
CCT.#1A-12
CCT.#1A-12
CCT.#1A-29
120V AC/12V DC (AS PERSECURITY DEVICES REQUIREMENT)TRANSFORMER ABOVE CEILINGFOR DOOR SECURITY
E
INTERCOM COMPLETEW/ SPEAKERS
CONNECT TO DOORBELLAT THE RECEPTION
TX
CC
T.#
1A
-8
CCT.#A-33
DSEXISTING DOOR STRIKE TO
BE REPLACED BY HEAVYDUTY ELECTRIC STRIKE
E
DL
E E
E
E
E
E
F
CCT.#1E-21
CCT.#1E-22LOCATION TO BECONFIRMED ON SITE
REFER TO DWG. E2-01
GENERAL NOTES:1. VERIFY EXACT POWER REQUIREMENTS AND RECEPTACLES TYPES FOR SPECIAL EQUIPMENT WITH MANUFACTURE PRIOR TO
INSTALLATION. PROVIDE HARD WIRED CONNECTIONS FOR EQUIPMENT IN LIEU OF RECEPTACLES OR VICE-VERSA ASREQUIRED.
2. CIRCUITING IN PART DIAGRAMMATIC, INTENDED TO SHOW GROUPING AND PANEL DESIGNATION.
3. WHERE WALL MOUNTED POWER OUTLETS ARE SHOWN ADJACENT TO ONE ANOTHER, THEY SHALL BE GANGED UNDER ACOMMON COVER PLATE.
4. OUTLETS NOT TO BE BACK TO BACK, TO BE STAGGERED.
5. CONTRACTOR TO CO-ORDINATE WITH OTHER DISCIPLINES & OWNER REGARDING POWER REQUIREMENTS, MOUNTINGHEIGHTS OF TV, IT AND SECURITY POWER SUPPLY BEFORE ROUGH-IN.
6. RESPONSIBILITY OF THE CONTRACTOR TO VERIFY KITCHEN EQUIPMENT DRAWINGS AND CUT SHEETS FOR EXACT POWERREQUIREMENTS AND PROVIDE BREAKERS AND CABLING ACCORDINGLY.
7. ADD 1 (ONE)-15A, 120V BREAKER CIRCUIT #29 IN THE EXISTING PANEL 'LP-1A-1A' TO PROVIDE POWER SUPPLY. THEBREAKERS TO MATCH EXISTING PANEL BREAKERS. THE CABLES TO BE 2x#12 AWG + GND-21 MMC.
8. ADD 2 (TWO) -15A, 120 V BREAKER CIRCUIT #31 & 33 IN THE EXISTING PANEL 'LP-1A-1A' TO PROVIDE POWER SUPPLY FORTHE MAGNETIC DOOR DETECTOR AT #93.1 (REFER TO DWG. E2-01"). THE BREAKER TO MATCH EXISTING BREAKER OF THEPANEL. THE CABLE SIZE TO BE 2x#10 AWG + GND-21 MMC. LABEL BOTH ENDS WITH CIRCUIT NUMBER C/W PANELDESIGNATION.
9. ADD 1 (ONE) 15A, 120V BREAKER CIRCUIT #19 AND 1 (ONE) 20A, 120V BREAKER CIRCUIT #17 IN THE EXISTINGEMERGENCY PANEL 'LP-1A1E' TO PROVIDE POWER SUPPLY IN THE RECEPTION HUB #129 PRINTER AND COMPUTER. THEBREAKER TO MATCH EXISTING BREAKER OF THE PANEL. THE CABLE SIZE TO BE 2X#12AWG+GND-21mmC. LABEL BOTHENDS WITH CIRCUIT NUMBER C/W PANEL DESIGNATION.
10. CONTRACTOR SHALL PROVIDE IN TENDER FOR SUPPLY AND INSTALLATION OF TWO ADDITIONAL 15A, 120V BREAKERSC/W 250 FEET OF WIRING AND CONDUITS TO BE INSTALLED IF REQUIRED BY CONSULTANT/INSPECTOR. PROVIDE CREDITFOR UNUSED ALLOWANCE AT THE END OF THE PROJECT.
11. CONTRACTOR TO TRACE ALL THE CIRCUITS (NEW AND EXISTING) AND REFLECT ON THE UPDATE PANEL SCHEDULE (ALLAFFECTED PANELS). THE FINAL PANEL SCHEDULES TO BE LAMINATED AND STICK TO THE INSIDE PANEL DOOR.
12. ALL VOICE / DATA TO RUN IN CONDUIT HOME RUN TO THE IT RACK IN THE IT ROOM # A109.
13. POWER AND DATA CONDUITS TO RUN ABOVE THE CEILING..
14. THE COMMUNICATION CABLES TO BE BELDEN/NORDX CAT 6.
15. CONTRACTOR TO ALLOW FOR FIRE ALARM REPROGRAMMING AND ALARM GRAPHIC TO BE UPDATED ACCORDINGLY TOSUIT BY 'TYCO' AFFILIATED CONTRACTOR ONLY. PROVIDE FOR FIRE ALARM VERIFICATION TO 'ULCS537' ANDDEMONSTRATION TO GTAA.
16. THE EXISTING FIRE ALARM CONTROL PANEL MANUFACTURED BY NOTIFIER.
17. ALL DOOR HOLDERS TO BE CONNECTED WITH THE EXISTING FIRE ALARM SYSTEM FOR FIRE ALARM INTERFACE.
1/4"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 1st - FLOORPOWER AND SYSTEMS PLANS
E2-03
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E2-03 - UNIT#1 - 1 FL-PWR PLANS.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:21 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
1
E2-03
ENLARGED 1st FLOOR POWER AND SYSTEMS PLAN1/4"=1'-0"
0ISSUED FOR PERMIT / TENDER2019-12-06
-
150(SBC and FOPS)TREATMENT RM
SHARED
145WORKSTATIONS
133WORKSTATIONS
155ALOUNGE ROOM
STAFF /
139 S.F.
191 S.F.
153MEETING ROOMSMALL TEAM /
KEEP EXIST.DOOR LOCKED
4 NEW FULLSIZE LOCKERS
POWER & DATAFOR 5 STATIONS
4 NEW FULLSIZE LOCKERS
ACCESSIBLECOUNTER
LOW G.B. PARTITIONH=2'6"
NEW 3 "Z" LOCKERSW/ SLOPED TOP
2 DESKS(BY HOSPITAL)
STORAGESHELVING(BY HOSPITAL)
STORAGESHELVING(BY HOSPITAL)
P-#P-#
EXISTING TO REMAIN
LOCKED STORAGECABINET (BY HOSPITAL)
LABEL MAKER WITHSTORAGE FOR COPIERMILLWORK BENEATH
LARGE COPIER
MAIL SLOTS
108CORRIDOR
199CORRIDOR
131INTERVIEW
132ROOMGROUP
146INTERVIEW
144INTERVIEW
144AINTERVIEW
148WC
149STORAGE
143ELECT
137STORAGE
138WC
135INTERVIEW
198
142OFFICE
141OFFICE
140INTERVIEW
139OFFICE
158AMED ROOM
02
A91-01
2D
2D
2D
2D
TV
EXISTINGFIRE ALARMANNUNCIATORPANEL
2D2D2D
2D
2D
2D
2DE
2D2D2D
2D
CR
CR
E
CR
E
DH
CR E
EXISTINGPANEL'LP-1A-1D'
COFFEE
TEA KETTLE
TOASTER
MICROWAVE
DC
SECURITYMONITOR(CCTV)
DS
E
E
E
ALARM SYSTEM FIRE ALARM INT
CONNECT TFOR FIRE AL
CCT.#1A-8
CCT.#1A-8
CCT.#1A1E-17
5-20R
E
CCT.#1A-10
CCT.#1A-10
CC
T.#
1A
1E-
19
CC
T.#
1A
1E-
19
CCT.#1A-12
CC
T.#
1D
-11
CC
T.#
1D
-11
CC
T.#
1D
-11
CC
T.#
1D
-11
CC
T.#
1D
-11
CC
T.#
1D
-9
E E
CC
T.#
1D
-9
CC
T.#
1D
-11
EE
CCT.#1D-13
E
CC
T.#
1D
28
CC
T.#
1D
29
E CCT.#1D-15CCT.#1D-15
CC
T.#
1D
30
CC
T.#
1D
30
CC
T.#
1D
30E
EE
CC
T.#
1D
30
CC
T.#
1D
30
CC
T.#
1D
30
CC
T.#
1D
30
CC
T.#
1D
30
CC
T.#
1D
30
CCT.#1E-42E
CCT.#1E-42
E
E
CCT.#1E-34
CCT.#1E-38
CCT.#1E-39
CCT.#1E-40
CCT.#1E-41
E
5-20R
5-20R
5-20R
5-20R
5-20R
D
CCT.#A-33PROVIDE LABEL INDICATHE PANEL DESIGNATI
CR
E
E
L
E E
E
F
TV
CCT.#1D-32
REFER TO DWG. E2-03
REFER TO DWG. E2-01
GENERAL NOTES:1. VERIFY EXACT POWER REQUIREMENTS AND RECEPTACLES
TYPES FOR SPECIAL EQUIPMENT WITH MANUFACTURE PRIORTO INSTALLATION. PROVIDE HARD WIRED CONNECTIONS FOREQUIPMENT IN LIEU OF RECEPTACLES OR VICE-VERSA ASREQUIRED.
2. CIRCUITING IN PART DIAGRAMMATIC, INTENDED TO SHOWGROUPING AND PANEL DESIGNATION.
3. WHERE WALL MOUNTED POWER OUTLETS ARE SHOWNADJACENT TO ONE ANOTHER, THEY SHALL BE GANGEDUNDER A COMMON COVER PLATE.
4. OUTLETS NOT TO BE BACK TO BACK, TO BE STAGGERED.
5. CONTRACTOR TO CO-ORDINATE WITH OTHER DISCIPLINES &OWNER REGARDING POWER REQUIREMENTS, MOUNTINGHEIGHTS OF TV, IT AND SECURITY POWER SUPPLY BEFOREROUGH-IN.
6. RESPONSIBILITY OF THE CONTRACTOR TO VERIFY KITCHENEQUIPMENT DRAWINGS AND CUT SHEETS FOR EXACT POWERREQUIREMENTS AND PROVIDE BREAKERS AND CABLINGACCORDINGLY.
7. ADD 2 (TWO)-15A AND 1 (ONE)-20A, 120V BREAKERCIRCUITS #28 & 30 IN THE EXISTING PANEL 'LP-1A-1D', ALSOADD 6 (SIX)-20A, 120V BREAKER CIRCUIT #34, 38, 39, 40, 41AND 42 IN THE EXISTING PANEL 'LP-1A-1C' TO PROVIDEPOWER SUPPLY. THE BREAKERS TO MATCH EXISTING PANELBREAKERS. THE CABLES TO BE 2x#12 AWG + GND-21 MMC.
8. CONTRACTOR TO TRACE ALL THE CIRCUITS (NEW ANDEXISTING) AND REFLECT ON THE UPDATE PANEL SCHEDULE(ALL AFFECTED PANELS). THE FINAL PANEL SCHEDULES TO BELAMINATED AND STICK TO THE INSIDE PANEL DOOR.
9. ALL VOICE / DATA TO RUN IN CONDUIT HOME RUN TO THEIT RACK IN THE IT ROOM # 109.
10. POWER AND DATA CONDUITS TO RUN ABOVE THE CEILING..
11. THE COMMUNICATION CABLES TO BE BELDEN/NORDX CAT 6.
12. CONTRACTOR TO ALLOW FOR FIRE ALARM REPROGRAMMINGAND ALARM GRAPHIC TO BE UPDATED ACCORDINGLY TOSUIT BY 'TYCO' AFFILIATED CONTRACTOR ONLY. PROVIDEFOR FIRE ALARM VERIFICATION TO 'ULCS537' ANDDEMONSTRATION TO GTAA.
13. THE EXISTING FIRE ALARM CONTROL PANEL MANUFACTUREDBY NOTIFIER.
1/4"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 1st - FLOORPOWER AND SYSTEMS PLANS
E2-04
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E2-04 - UNIT#1 - 1 FL-PWR PLANS.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:21 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
1
E2-04
ENLARGED 1st FLOOR POWER AND SYSTEMS PLAN1/4"=1'-0"
0ISSUED FOR PERMIT / TENDER2019-12-06
-
F.D.
490CORRIDOR
429CORRIDOR
CORRIDOR
437CWC
437DWC
437AWC
437BWC
43
6EL
EC
431BATH
430SHOWER
441COMFORT
FHC
2D2D 2D2D
2D
2D
2D
2D
2D
2D
2D
E
E E
425BEDROOM
SWING
426ROOM
PATIENT
427ROOM
PATIENT
428ROOM
PATIENT
432ROOM
PATIENT
433ROOM
PATIENT
434ROOM
PATIENT
435ROOM
PATIENT
440ROOM
PATIENT
439ROOM
PATIENT
438ROOM
PATIENT
EXISTINGPANEL'LP-1A-4A'
ER
ER
ER
ER
ER
ER
ER
ER
ER ER
ER ER
ER ER
ER ER
ER ER
ER ER
ER ER
E E EE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
NOTES:
1. REPLACE THE EXISTING POWER OUTLETSWITH THE HEAVY DUTY HOSPITAL GRADERECEPTACLES AT THE SAME LOCATION.
2. PATIENT ROOMS ALL RECEPTACLES ANDSWITCHES TO BE VANDAL PROOF.
402BMD
OFFICE
402AMD
OFFICE
402WS
OFFICESHARED
408WORKSTATIONS
HOTELING
401LOUNGE
TEAM ROOM/
415ROOM
MEETINGFAMILY
105 S.F.
101 S.F.
166 S.F.
290.8 S.F.
411RECREATION
DINING /
412WC
413WC
FHCEL. P
2D
1D
(E)+
1D
2D
2D
2D
2D
SURFACE SLIMELINE TWO WAYFLOOR TRUNKING (LEGRAND 2400 SERIES)FOR POWER AND COMMUNICATION
SURFACE FLOOR BOX C/W TWODUPLEX RECEPTACLES AND TWOCOMMUNICATION OUTLETS (TYPICAL)
SURFACE FLOOR BOX C/W TWODUPLEX RECEPTACLES AND TWOCOMMUNICATION OUTLETS
SURFACE SLIMELINE TWO WAYFLOOR TRUNKING FORPOWER AND COMMUNICATION
DCD
S
CR
EXISTINGPANEL'LP-1A-4B'
2D
2D
2D
2D
2D
TV
DCD
S
CR
E
CC
T#
4B-1
6
E
E
E
CC
T#4B-1
6 E
EE
1D
(E)+
1D E
CC
T#4B-1
8
CC
T#4B-1
8
CC
T#4B-1
8
ECC
T#4B-1
8
CC
T#4B-1
8
E
E
CCT#4B-21
CCT#4B-21
CC
T#4B-2
1
CC
T#4B-2
1
CC
T#4B-2
1
CC
T#4B-2
1
CC
T#4B-1
9
CC
T#4B-1
9
CC
T#4B-1
9
CC
T#4B-1
9
CC
T#4B-1
9
CC
T#4B-1
9
CC
T#4
B-1
9
CC
T#4
B-1
9
E
E
E
E
2D
CCT#4B-21
CCT#4B-21
WiFi
E
CCT#4B-38
CC
T#
4B-3
6
CC
T#
4B-3
6
TXCCT#4B-40
120AC/12V DC (AS PER SECURITYDEVICES REQUIREMENT) TRANSFORMERABOVE CEILING FOR DOOR SECURITY
E
EE
E
EE
E
E
E
E
GENERAL NOTES:1. VERIFY EXACT POWER REQUIREMENTS AND RECEPTACLES TYPES FOR SPECIAL EQUIPMENT
WITH MANUFACTURE PRIOR TO INSTALLATION. PROVIDE HARD WIRED CONNECTIONS FOREQUIPMENT IN LIEU OF RECEPTACLES OR VICE-VERSA AS REQUIRED.
2. CIRCUITING IN PART DIAGRAMMATIC, INTENDED TO SHOW GROUPING AND PANELDESIGNATION.
3. WHERE WALL MOUNTED POWER OUTLETS ARE SHOWN ADJACENT TO ONE ANOTHER, THEYSHALL BE GANGED UNDER A COMMON COVER PLATE.
4. OUTLETS NOT TO BE BACK TO BACK, TO BE STAGGERED.
5. CONTRACTOR TO CO-ORDINATE WITH OTHER DISCIPLINES & OWNER REGARDING POWERREQUIREMENTS, MOUNTING HEIGHTS OF TV, IT AND SECURITY POWER SUPPLY BEFOREROUGH-IN.
6. RESPONSIBILITY OF THE CONTRACTOR TO VERIFY KITCHEN EQUIPMENT DRAWINGS AND CUTSHEETS FOR EXACT POWER REQUIREMENTS AND PROVIDE BREAKERS AND CABLINGACCORDINGLY.
7. ADD 3 (THREE)-15A, 120V BREAKER CIRCUITS #36, 38 & 40 IN THE EXISTING PANEL 'LP-1A-4B'TO PROVIDE POWER SUPPLY. THE BREAKERS TO MATCH EXISTING PANEL BREAKERS. THECABLES TO BE 2x#12 AWG + GND-21 MMC.
8. CONTRACTOR SHALL PROVIDE IN TENDER FOR SUPPLY AND INSTALLATION OF TWOADDITIONAL 15A, 120V BREAKER C/W 150 FEET OF WIRING AND CONDUITS TO BE INSTALLEDIF REQUIRED BY CONSULTANT / INSPECTOR. PROVIDE CREDIT FOR UNUSED ALLOWANCE ATTHE END OF THE PROJECT.
9. CONTRACTOR TO TRACE ALL THE CIRCUITS (NEW AND EXISTING) AND REFLECT ON THEUPDATE PANEL SCHEDULE (ALL AFFECTED PANELS). THE FINAL PANEL SCHEDULES TO BELAMINATED AND STICK TO THE INSIDE PANEL DOOR.
10. ALL VOICE / DATA TO RUN IN CONDUIT HOME RUN TO THE IT RACK IN THE ELECTRICALROOM # 417.
11. POWER AND DATA CONDUITS TO RUN ABOVE THE CEILING.
12. THE COMMUNICATION CABLES TO BE BELDEN/NORDX CAT 6.
1/4"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 4th FLOORENLARGED POWER AND SYSTEMS PLANS
E2-05
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E2-05 - UNIT#1 - 4 FL-PWR PLANS.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:22 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
1
E2-05
ENLARGED 4th FLOOR POWER AND SYSTEMS PLAN1/4"=1'-0"
2
E2-05
ENLARGED 4th FLOOR POWER AND SYSTEMS PLAN1/4"=1'-0"
0ISSUED FOR PERMIT / TENDER2019-12-06
-
461MD
LGUCOFFICE
460SW
LGUCOFFICE
459OT
LGUCOFFICE
456MANAGER
LGUCOFFICE
4552 STUDENTS
LGUCOFFICE
4542 RTSLGUC
OFFICE
453# 2
INTERVIEW
458CWASHROOM
458DWASHROOM
458BWASHROOM
PATIENT
NEW HW SINKIN EXIST.LOCATION
POWER & DATAFOR 2 STATIONS
OPTION 1OPTION 3
48"X24"DESK (TYP)
F.D.
F.D.
495CORRIDOR
444WC
462EXAM
PRACTIONERS/VISITING
466TUB
467MED
450STORAGE
451INTERVIEW #1
446GREETING
447ROOM
CHARTING
448COPIER
449SECLUSION
452SHOWER
458ALAUNDRY
457AELEC
2D
2D
2D
2D
E
E
E
CR
DL
2D
2D2D
2D
2D
2D
2D
EXISTING PANEL'LP-1A-4D'
CR
EXISTING CARDREADER TO BEDEMOLISHED ANDREINSTALLED
F
CC
T#
4D
-12
CC
T#
4D
-12
E
CCT#4D-28
CC
T#
4D
-12
E
CC
T#
4D
-12
CC
T#
4D
-12
CC
T#4
D-1
2
CC
T#4
D-1
2
CC
T#4
D-1
4
CC
T#4
D-1
4
2DC
CT#4D
-14
CC
T#4D
-14
E
CC
T#4D
-14
E
CC
T#4D
-14
CC
T#4D
-14
DC
E
E
E E
EE
E
E
E
CC
T#4D
-6
E E
CCT#4D-4
CCT#4D-4
CCT#4D-4
CCT#4D-4
CCT#4D-4
CCT#4D-4CCT#4D-4
CCT#4D-4
CCT#4D-6
CCT#4D-6
CCT#4D-6
CCT#4D-6
ER
E
GENERAL NOTES:1. VERIFY EXACT POWER REQUIREMENTS AND RECEPTACLES TYPES FOR SPECIAL EQUIPMENT
WITH MANUFACTURE PRIOR TO INSTALLATION. PROVIDE HARD WIRED CONNECTIONS FOREQUIPMENT IN LIEU OF RECEPTACLES OR VICE-VERSA AS REQUIRED.
2. CIRCUITING IN PART DIAGRAMMATIC, INTENDED TO SHOW GROUPING AND PANELDESIGNATION.
3. WHERE WALL MOUNTED POWER OUTLETS ARE SHOWN ADJACENT TO ONE ANOTHER, THEYSHALL BE GANGED UNDER A COMMON COVER PLATE.
4. OUTLETS NOT TO BE BACK TO BACK, TO BE STAGGERED.
5. CONTRACTOR TO CO-ORDINATE WITH OTHER DISCIPLINES & OWNER REGARDING POWERREQUIREMENTS, MOUNTING HEIGHTS OF TV, IT AND SECURITY POWER SUPPLY BEFOREROUGH-IN.
6. RESPONSIBILITY OF THE CONTRACTOR TO VERIFY KITCHEN EQUIPMENT DRAWINGS AND CUTSHEETS FOR EXACT POWER REQUIREMENTS AND PROVIDE BREAKERS AND CABLINGACCORDINGLY.
7. ADD 1 (ONE)-15A, 120V BREAKER CIRCUIT #28 IN THE EXISTING PANEL 'LP-1A-4D' TOPROVIDE POWER SUPPLY FOR THE SINK. THE BREAKERS TO MATCH EXISTING PANEL BREAKERS.THE CABLES TO BE 2x#12 AWG + GND-21 MMC.
8. CONTRACTOR SHALL PROVIDE IN TENDER FOR SUPPLY AND INSTALLATION OF TWOADDITIONAL 15A, 120V BREAKER C/W 150 FEET OF WIRING AND CONDUITS TO BE INSTALLEDIF REQUIRED BY CONSULTANT / INSPECTOR. PROVIDE CREDIT FOR UNUSED ALLOWANCE ATTHE END OF THE PROJECT.
9. CONTRACTOR TO TRACE ALL THE CIRCUITS (NEW AND EXISTING) AND REFLECT ON THEUPDATE PANEL SCHEDULE (ALL AFFECTED PANELS). THE FINAL PANEL SCHEDULES TO BELAMINATED AND STICK TO THE INSIDE PANEL DOOR.
10. ALL VOICE / DATA TO RUN IN CONDUIT HOME RUN TO THE IT RACK IN THE ELECTRICALROOM # 417.
11. POWER AND DATA CONDUITS TO RUN ABOVE THE CEILING.
12. THE COMMUNICATION CABLES TO BE BELDEN/NORDX CAT 6.
1/4"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 4th FLOORENLARGED PLANS
E2-06
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E2-06 - UNIT#1 - 4 FL-PWR PLANS.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:23 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
1
E2-06
ENLARGED 4th FLOOR PLAN1/4"=1'-0"
0ISSUED FOR PERMIT / TENDER2019-12-06
-
119OFFICE
117OFFICE
190CORRIDOR
191CORRIDOR
128CORRIDOR
108CORRIDOR
159CORRIDOR
196CORRIDOR
197CORRIDOR
170
CO
RRID
OR
199CORRIDOR
194CORRIDOR
193CORRIDOR
AA27OFFICE
AA14OFFICE
AA10OFFICE
AA1CW
INTERVIEW
1634 WRKST
156W
171W
172
186ROOM
CONFERENCE
182W
183W
174ELECT106WC
107WC
109ELECT
110JAN
192 AREA
WAITING
112
115(FORCAT/SBC)GROUP ROOM
SHARED122W
121W
131INTERVIEW
132ROOMGROUP
146INTERVIEW
144INTERVIEW
144AINTERVIEW
148WC
149STORAGE
143ELECT
137STORAGE
138WC
135INTERVIEW
198
142OFFICE
141OFFICE
140INTERVIEW
139OFFICE
158AMED ROOM
112BKITCHENETTE
RECEPTION DESK
EXIST. RADIATOR
EXIST. SKYLIGHTBELOW (TYP.)
105 100VESTIBULE
162
CO
RRID
OR
LIGHTING NOTES:1. THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH INTERIOR DESIGN DRAWINGS FOR DIMENSIONS,
MOUNTING HEIGHTS, CONSTRUCTION DETAILING, FINISHES AND COLORS.
2. RE-WORK EXISTING LIGHTING CIRCUITS AND WIRING AS REQUIRED TO ACHIEVE NEW LIGHTING LAYOUT AND NEWEMERGENCY LIGHTING LAYOUT. MAKE SURE LIGHTING IS IN THE CONTROL OF TENANT.
3. ALL EXIT SIGNS SHOWN ON THE LAYOUT ARE EXISTING UNLESS OTHERWISE INDICATED. THE EXIT SIGNS SHALL BEBRUSHED ALUMINUM GREEN RUNNING MAN STYLE WITH ARROWS AS SHOWN. CONNECT TO THE NEARESTAVAILABLE EMERGENCY POWER CIRCUIT DEDICATED FOR EXIT LIGHTS.
4. ALL LIGHT FIXTURES IN RENOVATED AREAS SHALL BE CONNECTED TO NORMAL POWER (REWIRE AS REQUIRED TOSUIT). THE LIGHTING FIXTURE OF THE GENERAL OFFICE AREA TO BE BASE BUILDING LIGHTING CONTROL SYSTEMAND IN THE ROOMS TO BE CONTROLLED BY SWITCHES SERVING THE SPACE. ALLOW FOR ALL COSTS TO BEREPROGRAMME THE BASE BUILDING LIGHTING CONTROL SYSTEM.
5. THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL LIGHTING NOT REQUIRED BY NEW LAYOUT. VISIT SITE TODETERMINED EXACT REQUIREMENTS OF DEMOLITION.
6. ELECTRICAL CONTRACTOR TO BE RESPONSIBLE FOR CEILING ALTERATIONS, CUTTING OR REPLACING ANYDAMAGED TILE.
7. ALL RECESSED FLUORESCENT FIXTURE SHALL BE CHAIN HUNG AND SUPPORTED AT LEAST TWO CORNERSDIAGONALLY FROM THE SLAB ABOVE.
8. PROVIDE TEMPORARY ELECTRICAL SERVICE (LIGHTING AND POWER) FOR THE WORK OF THIS AND OTHER TRADES.
9. WIRE LIGHT FIXTURES IN PRIVATE OFFICES AND SPACES TO NEW WALL MOUNTED OCCUPANCY SENSORS.
10. ADD 2 (TWO)-15A, 120V BREAKER CIRCUIT #32 AND #34 IN THE EXISTING PANEL 'LP-1A-1A' TO PROVIDE POWER SUPPLY. THE BREAKERS TO MATCH EXISTING PANEL BREAKERS. THE CABLES TO BE 2x#10 AWG + GND-21 MMC.
E
E
EE
E E
E E
E
E
E
E
E
EE
E E
E E
E
E
E
E
EE
EE
E E
E E
E E
L2
L2
E E E E E
E EE E E
L2 L2
E
E E
E E
E E
E
E
E E E
E
E
E
E
E
E
E
E
E
E
E
E
EE
EE
EE
EE
E E
E E
E E
E E
E E
EE
E E
E
E
EE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
L2
L2
L2 L2
D
PROVIDE POWER SUPPLYTO LUMINOUS VIRTUAL WINDOWCCT.#1A-32
POWER SUPPLY FORRECEPTION TABLECCT.#1A-34
L2
L5
L5
L5 L5
L5
L5
L5
L5
L5 L5
L5
L5
L5
L5
L5
L2L2
L2L2
L2L2
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION VOLTAGE LAMP TYPELUMEN
OUTPUTCOLOUR
TEMPDRIVER TYPE MANUFACTURER SERIES MODEL NO
L2 120V2'x4' RECESSED TROFFER, SUITABLE FOR T-BAR CEILING LED
WATTS
4000474838
L1 40000-10VDIM DRIVER
120V45"x8" TROFFER LED FIXTURES COOPER LIGHTINGLED 381544.3 FAIL SAFE HVSL8-4-LD4-1HI-4-UNV-O-EDD1-SF1
COOPER LIGHTING 24EN-LD2-45-UNV-L840-CD1-U
ALL LUMINARIES AND DRIVERS TO BE C/W CSA LABEL SUITABLE FOR USE IN CANADA.PAY FOR ALL LOCAL APPROVAL PROCESS AS REQUIRED.
METALUX0-10VDIM DRIVER
L3
L5
4' LIGHT FIXTURE FOR VALENCE LIGHTING
6"x6" SQUARE RECESSED FIXTURE
120V LED 4000251123.6 COOPER LIGHTING HVSL2-4LD4-STD-40UNV-O-EDCI-SF1FAIL SAFE0-10VDIM DRIVER
120V LED 4000200021 COOPER LIGHTING PRS6FS12D010-SM6128FS-61SMDHHALOCOMMERCIAL
0-10VDIM DRIVER
L4 2'x2' RECESSED TROFFER, SUITABLE FOR T-BAR CEILING 120V LED 4000340028.5 COOPER LIGHTING 22EN-LD2-34-UNV-CD-1UMETALUX0-10VDIM DRIVER
3/32"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 1 FLOOR LIGHTING LAYOUT
E3-011
E3-01
UNIT # 1 - 1 FLOOR CEILING PLAN3/32"=1'-0"
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E3-01 - UNIT#1 - 1 FLOOR CEILING PLAN.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:23 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
0ISSUED FOR PERMIT / TENDER2019-12-06
-
490CORRIDOR
429CORRIDOR
442CORRIDOR
493CORRIDOR
495CORRIDOR
494CORRIDOR
437CWC
437DWC
437AWC
437BWC
436
ELEC
431BATH
430SHOWER
441COMFORT
419LOUNGE
GROUP ROOM/
418JAN
417ELEC
417VESTIBULE
UNIT ENTRY
411RECREATION
DINING /
412WC
413WC
489SERVERY
469SOILED
423CLEAN
475LOUNGE
444WC
462EXAM
PRACTIONERS/VISITING
466TUB
488TUB
467MED
450STORAGE
451INTERVIEW #1
446GREETING
447ROOM
CHARTING
448COPIER
449SECLUSION
452SHOWER
458ALAUNDRY
457AELEC
487SHOWER
480ELEC
481AWC
481BWC
481CWC
481DWC
485 ROOM
PATIENT
484 ROOM
PATIENT
483 ROOM
PATIENT
482 ROOM
PATIENT
479 ROOM
PATIENT
478 ROOM
PATIENT
477 ROOM
PATIENT
476 ROOM
PATIENT
474 ROOM
PATIENT
473 ROOM
PATIENT
472 ROOM
PATIENT
471 ROOM
PATIENT
402BMD
OFFICE
402AMD
OFFICE
402WS
OFFICESHARED
408WORKSTATIONS
HOTELING
401LOUNGE
TEAM ROOM/
461MD
LGUCOFFICE
460SW
LGUCOFFICE
459OT
LGUCOFFICE
456MANAGER
LGUCOFFICE
4552 STUDENTS
LGUCOFFICE
4542 RTSLGUC
OFFICE
453# 2
INTERVIEW
425BEDROOM
SWING
426ROOM
PATIENT
427ROOM
PATIENT
428ROOM
PATIENT
432ROOM
PATIENT
433ROOM
PATIENT
434ROOM
PATIENT
435ROOM
PATIENT
440ROOM
PATIENT
439ROOM
PATIENT
438ROOM
PATIENT
458CWASHROOM
458DWASHROOM
458BWASHROOM
PATIENT
415ROOM
MEETINGFAMILY
CEXIST.
C EXIST.
CEXIST.
C EXIST.
C EXIST.
C
C
EXIST.
CEXIST.
EXIST.
EXIST.
B
A
6A41.01
OC
CO
CC
OC
CO
CC
E E
E
E
EE
E E
E E
E E
E E
L1L1
L1L1
L1L1
L1L1 E E
E E
E E
E E
E
E E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
L4
OCC OCC OCC
L2
L2
L2
L2
L2
L2
L3
L4
ER ER
ER
ER
E
E
LIGHTING NOTES:1. THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH INTERIOR DESIGN DRAWINGS FOR DIMENSIONS,
MOUNTING HEIGHTS, CONSTRUCTION DETAILING, FINISHES AND COLORS.
2. RE-WORK EXISTING LIGHTING CIRCUITS AND WIRING AS REQUIRED TO ACHIEVE NEW LIGHTING LAYOUT ANDNEW EMERGENCY LIGHTING LAYOUT. MAKE SURE LIGHTING IS IN THE CONTROL OF TENANT.
3. ALL EXIT SIGNS SHOWN ON THE LAYOUT ARE EXISTING UNLESS OTHERWISE INDICATED. THE EXIT SIGNS SHALLBE BRUSHED ALUMINUM GREEN RUNNING MAN STYLE WITH ARROWS AS SHOWN. CONNECT TO THE NEARESTAVAILABLE EMERGENCY POWER CIRCUIT DEDICATED FOR EXIT LIGHTS.
4. ALL LIGHT FIXTURES IN RENOVATED AREAS SHALL BE CONNECTED TO NORMAL POWER (REWIRE AS REQUIREDTO SUIT). THE LIGHTING FIXTURE OF THE GENERAL OFFICE AREA TO BE BASE BUILDING LIGHTING CONTROLSYSTEM AND IN THE ROOMS TO BE CONTROLLED BY SWITCHES SERVING THE SPACE. ALLOW FOR ALL COSTS TOBE REPROGRAMME THE BASE BUILDING LIGHTING CONTROL SYSTEM.
5. THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL LIGHTING NOT REQUIRED BY NEW LAYOUT. VISIT SITE TODETERMINED EXACT REQUIREMENTS OF DEMOLITION.
6. THE ELECTRICAL CONTRACTOR SHALL PROVIDE IN TENDER FOR SUPPLY AND INSTALLATION OF THREE (3)ADDITIONAL EXIT SIGNS C/W 150 FEET OF CONDUIT AND WIRING TO BE INSTALLED IF REQUESTED BYCONSULTANT OR FIRE MARSHAL ON FINAL INSPECTION. PROVIDE CREDIT FOR UNUSED ALLOWANCE AT END OFTHE PROJECT.
7. ELECTRICAL CONTRACTOR TO BE RESPONSIBLE FOR CEILING ALTERATIONS, CUTTING OR REPLACING ANYDAMAGED TILE.
8. ALL RECESSED FLUORESCENT FIXTURE SHALL BE CHAIN HUNG AND SUPPORTED AT LEAST TWO CORNERSDIAGONALLY FROM THE SLAB ABOVE.
9. PROVIDE TEMPORARY ELECTRICAL SERVICE (LIGHTING AND POWER) FOR THE WORK OF THIS AND OTHERTRADES.
10. WIRE LIGHT FIXTURES IN PRIVATE OFFICES AND SPACES TO NEW WALL MOUNTED OCCUPANCY SENSORS.
3/32"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 4 FLOOR LIGHTING LAYOUT
E3-021
E3-02
UNIT # 1 - 4 FLOOR CEILING PLAN3/32"=1'-0"
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E3-02 - UNIT#1 - 4 FLOOR CEILING PLAN.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:25 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
0ISSUED FOR PERMIT / TENDER2019-12-06
-
119OFFICE
117OFFICE
190CORRIDOR
191CORRIDOR
128CORRIDOR
108CORRIDOR
159CORRIDOR
196CORRIDOR
197CORRIDOR
17
0C
OR
RID
OR
199CORRIDOR
194CORRIDOR
193CORRIDOR
AA27OFFICE
AA14OFFICE
AA10OFFICE
AA1CW
INTERVIEW
1634 WRKST
156W
171W
172
195
186ROOM
CONFERENCE
182W
183W
174ELECT106WC
107WC
109ELECT
110JAN
192 AREA
WAITING
112
115(FORCAT/SBC)GROUP ROOM
SHARED122W
121W
129RECEPTION
FOPS
131INTERVIEW
132ROOMGROUP
146INTERVIEW
144INTERVIEW
144AINTERVIEW
148WC
149STORAGE
143ELECT
137STORAGE
138WC
135INTERVIEW
198
142OFFICE
141OFFICE
140INTERVIEW
139OFFICE
158AMED ROOM
112BKITCHENETTE
RECEPTION DESK
EXIST. RADIATOR
EXIST. SKYLIGHTBELOW (TYP.)
105 100VESTIBULE
16
2C
OR
RID
OR
E
E
R
R
RR
RR
E
E E
E
ER
R R
EEXISTING PANEL'LP-1A-1A'
E
E
E E
E E
EE
E
E
E E
EE
E E
E
R RR
R R
R
R
E
E
RR
E
R R R R
RR
RR
E
E
E
RR
R
RE
EXISTING PANEL'LP-1A-1D'
R R
R
R R
R
E
EEE
E
EXISTING PANEL'LP-1A-1C'
R
E E
E
E E
E
R
E E
E
E E
E
E
R
ER
RR
R
E
E
E
E EEE
EE E
EE E EE
EE
EEE
EE
E
EEE
EE
ER
FEER
ER
FAE
E E E
RR
EXISTING PANEL'LP-1A-1B'R
RR
RRRR R
RR RR
R
E
ER
R E
CR
E
E
E E
CR
CR
RR
CR
DL
DC
DS
EE
E
E
R
DL
DC
E
E
DL
DC
E
E
DCED
S
EE
CR E
POWER DEMOLITION NOTES:1. VISIT SITE, EXAMINE EXISTING CONDITIONS AND BECOME FAMILIAR WITH THE EXTEND OF THE NECESSARY
REMOVAL, RELOCATION, RECONNECTING, AND REROUTING OF ELECTRICAL EQUIPMENT AND WIRING ASNECESSARY FOR THE COMPLETION OF THE PROJECT.
2. REVIEW AND CONFIRM WITH THE ARCHITECT/DESIGNER'S DRAWINGS FOR THE COMPLETE EXTENT OFDEMOLITION AND ALTERATION. ALLOW FOR ALL
COST.
3. MAKE SAFE AND DISCONNECT LIGHT FIXTURES/SWITCHES, AS AND WHEN, AND TO THE EXTEND REQUIRED TOFACILITATE WITH THE DEMOLITION.
4. ENSURE THAT ALL ELECTRICAL, LIFE SAFETY SERVICES, AND SERVICES FOR EXISTING EQUIPMENT, IN AREASOUTSIDE THE AREAS OF THIS WORK, THAT ARE REQUIRED TO REMAIN IN SERVICE, SHALL DO SO.
5. RELOCATE ANY ELECTRICAL FEEDERS OR EQUIPMENT THAT ARE REQUIRED TO REMAIN IN SERVICE, THAT ARESECURED TO EXISTING WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED OR THAT ARE BURIED AND REQUIREDTO BE EXCAVATED FOR NEW WORK.
6. REMOVE AND REPLACE ANY ELECTRICAL EQUIPMENT ON WALLS OR CEILINGS THAT WILL BE DEMOLISHED ANDREBUILT.
7. WHEN DELETING AND/OR MAKING SAFE EXISTING ELECTRICAL WORK, ENSURE THAT IT INCLUDES ALL WIRINGBACK TO THE ASSOCIATED PANELBOARDS OR CONTROL PANEL.
8. DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES, SWITCHES, DEVICES, OUTLETS ETC. WHICH ARE NOT TOBE REUSED. SUCH ITEMS SHALL CARTONED AND TURN OVER TO THE OWNER AT A PLACE DESIGNATED BY THEOWNER. CUT BACK AND CAP UNUSED RACEWAY AND OUTLETS AND REMOVED UNUSED WIRING BACK TOPANELBOARD IN APPROVED MANNER.
9. PROVIDE BLANK COPPER PLATE WHERE OUTLETS ARE REMOVED FROM EXISTING WALLS TO REMAIN.
10. ALL EXISTING ELECTRICAL EQUIPMENT WHICH IS NO LONGER REQUIRED SHALL BE REMOVED AND DISPOSED OF,OFF SITE.
11. BE RESPONSIBLE AND PAY FOR ANY DAMAGE TO THE BASE BUILDING INCURRED BY WORK OF THIS DIVISION, ORREPAIR TO THE SATISFACTION OF THE CONSULTANT.
12. CARRY OUT THE WORK WITH MINIMUM OF NOISE, DUST AND DISTURBANCE.
13. ALL FIRE ALARM DEVICES SHALL REMAIN IN CEILING SPACE, UNLESS REQUIRED TO BE RELOCATED DUE TODEMOLITION & PROPOSED SCOPE OF WORK.
3/32"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 1 ST FLOOR DEMOLITION PLAN
E8-011
E8-01
UNIT # 1 - 1 FLOOR DEMOLITION PLAN3/32"=1'-0"
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E8-01 - UNIT#1 - 1 FLOOR DEMOLITION PLAN.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:26 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
0ISSUED FOR PERMIT / TENDER2019-12-06
-
F.D.
F.D.
F.D.
490CORRIDOR
429CORRIDOR
442CORRIDOR
493CORRIDOR
495CORRIDOR
494CORRIDOR
437CWC
437DWC
437AWC
437BWC
43
6EL
EC
431BATH
430SHOWER
441COMFORT
419LOUNGE
GROUP ROOM/
418JAN
417ELEC
417VESTIBULE
UNIT ENTRY
411RECREATION
DINING /
412WC
413WC
489SERVERY
469SOILED
423CLEAN
475LOUNGE
444WC
462EXAM
PRACTIONERS/VISITING
466TUB
488TUB
467MED
450STORAGE
451INTERVIEW #1
446GREETING
447ROOM
CHARTING
448COPIER
449SECLUSION
452SHOWER
458ALAUNDRY
457AELEC
487SHOWER
480ELEC
481AWC
481BWC
481CWC
481DWC
485 ROOM
PATIENT
484 ROOM
PATIENT
483 ROOM
PATIENT
482 ROOM
PATIENT
479 ROOM
PATIENT
478 ROOM
PATIENT
477 ROOM
PATIENT
476 ROOM
PATIENT
474 ROOM
PATIENT
473 ROOM
PATIENT
472 ROOM
PATIENT
471 ROOM
PATIENT
FHCEL. P
FHC
2D
2D
E
F
F
E
E EE
EEE E
EEE
LR
E
R
R
R
E
E
R
R
RE
E
RR
E
R
R
R
E
E
R
R
R
R
R
E
E FE E
EE
EEE
E
E
E E EE
EE
E E E
E
E E E E
E
E
E
E
E
EE
E
E
E
EE
E
E
E
E
E
E
E
EE
EE
EE
E
EE
E
EE
EE
E
E E
EE
FE
E
DC TX
EE
CR
E
E
DS
CR E
DCD
S
E
E
EE E
E
E
E
E
E E
E
E
WiFi EE
POWER DEMOLITION NOTES:1. VISIT SITE, EXAMINE EXISTING CONDITIONS AND BECOME FAMILIAR WITH THE EXTEND OF THE NECESSARY
REMOVAL, RELOCATION, RECONNECTING, AND REROUTING OF ELECTRICAL EQUIPMENT AND WIRING ASNECESSARY FOR THE COMPLETION OF THE PROJECT.
2. REVIEW AND CONFIRM WITH THE ARCHITECT/DESIGNER'S DRAWINGS FOR THE COMPLETE EXTENT OFDEMOLITION AND ALTERATION. ALLOW FOR ALL
COST.
3. MAKE SAFE AND DISCONNECT LIGHT FIXTURES/SWITCHES, AS AND WHEN, AND TO THE EXTEND REQUIRED TOFACILITATE WITH THE DEMOLITION.
4. ENSURE THAT ALL ELECTRICAL, LIFE SAFETY SERVICES, AND SERVICES FOR EXISTING EQUIPMENT, IN AREASOUTSIDE THE AREAS OF THIS WORK, THAT ARE REQUIRED TO REMAIN IN SERVICE, SHALL DO SO.
5. RELOCATE ANY ELECTRICAL FEEDERS OR EQUIPMENT THAT ARE REQUIRED TO REMAIN IN SERVICE, THAT ARESECURED TO EXISTING WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED OR THAT ARE BURIED AND REQUIREDTO BE EXCAVATED FOR NEW WORK.
6. REMOVE AND REPLACE ANY ELECTRICAL EQUIPMENT ON WALLS OR CEILINGS THAT WILL BE DEMOLISHED ANDREBUILT.
7. WHEN DELETING AND/OR MAKING SAFE EXISTING ELECTRICAL WORK, ENSURE THAT IT INCLUDES ALL WIRINGBACK TO THE ASSOCIATED PANELBOARDS OR CONTROL PANEL.
8. DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES, SWITCHES, DEVICES, OUTLETS ETC. WHICH ARE NOT TOBE REUSED. SUCH ITEMS SHALL CARTONED AND TURN OVER TO THE OWNER AT A PLACE DESIGNATED BY THEOWNER. CUT BACK AND CAP UNUSED RACEWAY AND OUTLETS AND REMOVED UNUSED WIRING BACK TOPANELBOARD IN APPROVED MANNER.
9. PROVIDE BLANK COPPER PLATE WHERE OUTLETS ARE REMOVED FROM EXISTING WALLS TO REMAIN.
10. ALL EXISTING ELECTRICAL EQUIPMENT WHICH IS NO LONGER REQUIRED SHALL BE REMOVED AND DISPOSED OF,OFF SITE.
11. BE RESPONSIBLE AND PAY FOR ANY DAMAGE TO THE BASE BUILDING INCURRED BY WORK OF THIS DIVISION, ORREPAIR TO THE SATISFACTION OF THE CONSULTANT.
12. CARRY OUT THE WORK WITH MINIMUM OF NOISE, DUST AND DISTURBANCE.
13. ALL FIRE ALARM DEVICES SHALL REMAIN IN CEILING SPACE, UNLESS REQUIRED TO BE RELOCATED DUE TODEMOLITION & PROPOSED SCOPE OF WORK.
3/32"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 4 FLOOR DEMOLITION PLAN
E8-021
E8-02
UNIT # 1 - 4 FLOOR DEMOLITION PLAN3/32"=1'-0"
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E8-02 - UNIT#1 - 4 FLOOR DEMOLITION PLAN.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:26 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
0ISSUED FOR PERMIT / TENDER2019-12-06
-
AR
AR
AR
S
AR
AR
S
AR
S
S
S
S
S
S
S
S
S
SS
S
AR
S
S
S
SS
S
S
S
S
S
S
119OFFICE
117OFFICE
190CORRIDOR
191CORRIDOR
128CORRIDOR
108CORRIDOR
159CORRIDOR
196CORRIDOR
197CORRIDOR
17
0C
OR
RID
OR
199CORRIDOR
194CORRIDOR
193CORRIDOR
AA27OFFICE
AA14OFFICE
AA10OFFICE
AA1CW
INTERVIEW
1634 WRKST
156W
171W
172
195
186ROOM
CONFERENCE
182W
183W
174ELECT106WC
107WC
109ELECT
110JAN
192 AREA
WAITING
112
115(FORCAT/SBC)GROUP ROOM
SHARED122W
121W
129RECEPTION
FOPS
131INTERVIEW
132ROOMGROUP
146INTERVIEW
144INTERVIEW
144AINTERVIEW
148WC
149STORAGE
143ELECT
137STORAGE
138WC
135INTERVIEW
198
142OFFICE
141OFFICE
140INTERVIEW
139OFFICE
158AMED ROOM
112BKITCHENETTE
RECEPTION DESK
EXIST. RADIATOR
EXIST. SKYLIGHTBELOW (TYP.)
105 100VESTIBULE
16
2C
OR
RID
OR
E E
E E
E E
E EE E
E E
E E
E E
E E
E
E
E
E
E E
E E
E
E E
R R
R R
E E E R E E
E E E R E E
R
R
E
E
E
E
E
E
R R
RRREEER
E E
E E
E
E E
E E
E
E
E
E E
E E
E
E
E
R R R
R R
R
R
R
R
R
R
R
R
R
R
R
E E
E E
EE
E
E
E
E
E
E
E
E
E
E E
E
EE
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
R
R
LIGHTING DEMOLITION NOTES:1. VISIT SITE, EXAMINE EXISTING CONDITIONS AND BECOME FAMILIAR WITH THE EXTEND OF THE NECESSARY
REMOVAL, RELOCATION, RECONNECTING, AND REROUTING OF ELECTRICAL EQUIPMENT AND WIRING ASNECESSARY FOR THE COMPLETION OF THE PROJECT.
2. REVIEW AND CONFIRM WITH THE ARCHITECT/DESIGNER'S DRAWINGS FOR THE COMPLETE EXTENT OFDEMOLITION AND ALTERATION. ALLOW FOR ALL
COST.
3. MAKE SAFE AND DISCONNECT LIGHT FIXTURES/SWITCHES, AS AND WHEN, AND TO THE EXTEND REQUIRED TOFACILITATE WITH THE DEMOLITION.
4. ENSURE THAT ALL ELECTRICAL, LIFE SAFETY SERVICES, AND SERVICES FOR EXISTING EQUIPMENT, IN AREASOUTSIDE THE AREAS OF THIS WORK, THAT ARE REQUIRED TO REMAIN IN SERVICE, SHALL DO SO.
5. RELOCATE ANY ELECTRICAL FEEDERS OR EQUIPMENT THAT ARE REQUIRED TO REMAIN IN SERVICE, THAT ARESECURED TO EXISTING WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED OR THAT ARE BURIED AND REQUIREDTO BE EXCAVATED FOR NEW WORK.
6. REMOVE AND REPLACE ANY ELECTRICAL EQUIPMENT ON WALLS OR CEILINGS THAT WILL BE DEMOLISHED ANDREBUILT.
7. WHEN DELETING AND/OR MAKING SAFE EXISTING ELECTRICAL WORK, ENSURE THAT IT INCLUDES ALL WIRINGBACK TO THE ASSOCIATED PANELBOARDS OR CONTROL PANEL.
8. DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES, SWITCHES, DEVICES, OUTLETS ETC. WHICH ARE NOT TOBE REUSED. SUCH ITEMS SHALL CARTONED AND TURN OVER TO THE OWNER AT A PLACE DESIGNATED BY THEOWNER. CUT BACK AND CAP UNUSED RACEWAY AND OUTLETS AND REMOVED UNUSED WIRING BACK TOPANELBOARD IN APPROVED MANNER.
9. PROVIDE BLANK COPPER PLATE WHERE OUTLETS ARE REMOVED FROM EXISTING WALLS TO REMAIN.
10. ALL EXISTING ELECTRICAL EQUIPMENT WHICH IS NO LONGER REQUIRED SHALL BE REMOVED AND DISPOSED OF,OFF SITE.
11. BE RESPONSIBLE AND PAY FOR ANY DAMAGE TO THE BASE BUILDING INCURRED BY WORK OF THIS DIVISION, ORREPAIR TO THE SATISFACTION OF THE CONSULTANT.
12. CARRY OUT THE WORK WITH MINIMUM OF NOISE, DUST AND DISTURBANCE.
13. ALL FIRE ALARM DEVICES SHALL REMAIN IN CEILING SPACE, UNLESS REQUIRED TO BE RELOCATED DUE TODEMOLITION & PROPOSED SCOPE OF WORK.
3/32"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 1 FLOOR DEMOLITION LIGHTING LAYOUT
E8-031
E8-03
UNIT # 1 - 1 FLOOR DEMOLITION CEILING PLAN3/32"=1'-0"
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E8-03 - UNIT#1 - 1 FLOOR DEMOLITION CEILING PLAN.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:27 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
0ISSUED FOR PERMIT / TENDER2019-12-06
-
F.D.
F.D.
F.D.
490CORRIDOR
429CORRIDOR
442CORRIDOR
493CORRIDOR
495CORRIDOR
494CORRIDOR
437CWC
437DWC
437AWC
437BWC
43
6EL
EC
431BATH
430SHOWER
441COMFORT
419LOUNGE
GROUP ROOM/
418JAN
417ELEC
417VESTIBULE
UNIT ENTRY
411RECREATION
DINING /
412WC
413WC
489SERVERY
469SOILED
423CLEAN
475LOUNGE
444WC
462EXAM
PRACTIONERS/VISITING
466TUB
488TUB
467MED
450STORAGE
451INTERVIEW #1
446GREETING
447ROOM
CHARTING
448COPIER
449SECLUSION
452SHOWER
458ALAUNDRY
457AELEC
487SHOWER
480ELEC
481AWC
481BWC
481CWC
481DWC
485 ROOM
PATIENT
484 ROOM
PATIENT
483 ROOM
PATIENT
482 ROOM
PATIENT
479 ROOM
PATIENT
478 ROOM
PATIENT
477 ROOM
PATIENT
476 ROOM
PATIENT
474 ROOM
PATIENT
473 ROOM
PATIENT
472 ROOM
PATIENT
471 ROOM
PATIENT
EL. P
EE
EE
EE
ER ER
ERE
E ER
E
E
ER ER
E
ER
ERE
E
E
E
E
E
E
E
E E
E E
E E
E E
E
E
E
E
E E
R R R
E E E
E
E
R
E
R
R
R
R
R
R
R
R
R
R R
R R
R
R
E
R R
R
R RR
R R
RR
R R
R R
LIGHTING DEMOLITION NOTES:1. VISIT SITE, EXAMINE EXISTING CONDITIONS AND BECOME FAMILIAR WITH THE EXTEND OF THE NECESSARY
REMOVAL, RELOCATION, RECONNECTING, AND REROUTING OF ELECTRICAL EQUIPMENT AND WIRING ASNECESSARY FOR THE COMPLETION OF THE PROJECT.
2. REVIEW AND CONFIRM WITH THE ARCHITECT/DESIGNER'S DRAWINGS FOR THE COMPLETE EXTENT OFDEMOLITION AND ALTERATION. ALLOW FOR ALL
COST.
3. MAKE SAFE AND DISCONNECT LIGHT FIXTURES/SWITCHES, AS AND WHEN, AND TO THE EXTEND REQUIRED TOFACILITATE WITH THE DEMOLITION.
4. ENSURE THAT ALL ELECTRICAL, LIFE SAFETY SERVICES, AND SERVICES FOR EXISTING EQUIPMENT, IN AREASOUTSIDE THE AREAS OF THIS WORK, THAT ARE REQUIRED TO REMAIN IN SERVICE, SHALL DO SO.
5. RELOCATE ANY ELECTRICAL FEEDERS OR EQUIPMENT THAT ARE REQUIRED TO REMAIN IN SERVICE, THAT ARESECURED TO EXISTING WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED OR THAT ARE BURIED AND REQUIREDTO BE EXCAVATED FOR NEW WORK.
6. REMOVE AND REPLACE ANY ELECTRICAL EQUIPMENT ON WALLS OR CEILINGS THAT WILL BE DEMOLISHED ANDREBUILT.
7. WHEN DELETING AND/OR MAKING SAFE EXISTING ELECTRICAL WORK, ENSURE THAT IT INCLUDES ALL WIRINGBACK TO THE ASSOCIATED PANELBOARDS OR CONTROL PANEL.
8. DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES, SWITCHES, DEVICES, OUTLETS ETC. WHICH ARE NOT TOBE REUSED. SUCH ITEMS SHALL CARTONED AND TURN OVER TO THE OWNER AT A PLACE DESIGNATED BY THEOWNER. CUT BACK AND CAP UNUSED RACEWAY AND OUTLETS AND REMOVED UNUSED WIRING BACK TOPANELBOARD IN APPROVED MANNER.
9. PROVIDE BLANK COPPER PLATE WHERE OUTLETS ARE REMOVED FROM EXISTING WALLS TO REMAIN.
10. ALL EXISTING ELECTRICAL EQUIPMENT WHICH IS NO LONGER REQUIRED SHALL BE REMOVED AND DISPOSED OF,OFF SITE.
11. BE RESPONSIBLE AND PAY FOR ANY DAMAGE TO THE BASE BUILDING INCURRED BY WORK OF THIS DIVISION, ORREPAIR TO THE SATISFACTION OF THE CONSULTANT.
12. CARRY OUT THE WORK WITH MINIMUM OF NOISE, DUST AND DISTURBANCE.
13. ALL FIRE ALARM DEVICES SHALL REMAIN IN CEILING SPACE, UNLESS REQUIRED TO BE RELOCATED DUE TODEMOLITION & PROPOSED SCOPE OF WORK.
3/32"=1'-0"
M. KUTA
A. BISWAS
UNIT # 1 - 4 FLOOR DEMOLITION LIGHTING LAYOUT
E8-041
E8-04
UNIT # 1 - 4 FLOOR DEMOLITION CEILING PLAN3/32"=1'-0"
NORR Limited
175 Bloor St. EastNorth Tower, 15th FloorToronto, ON, Canada M4W 3R8www.norr.com
An Ingenium Group Company
ISSUED FOR REV
Keyplan
NORTH:STAMP:
This drawing has been prepared solely for the useof CLIENT NAME and there are no representations ofany kind made by LEGAL COMPANY NAME to anyparty with whom LEGAL COMPANY NAME has notentered into a contract.
This drawing shall not be used for constructionpurposes until the seal appearing hereon is signedand dated by the Architect or Engineer.
Project Manager Drawn
Project Leader Checked
Client
Drawing Title
Check Scale (may be photo reduced)
Project No.
Drawing No.
Project
0 1inch 0 10mm
ONBL19-0202
DATE
PATH AND FILENAME: P:\ONBL19-0202 - CAMH - PHASE 1C RELOCATION OF DISPLA\500-DELIV\ELEC\SHEETS\E8-04 - UNIT#1 - 4 FLOOR DEMOLITION CEILING PLAN.DWG PLOTSYLE TABLE: ---- PLOT DATE: December 10, 2019 TIME: 4:27 PM
AR
CH
D -
24
"x3
6"
- 6
10
mm
x9
14
mm
(ro
unded
)
D. WITALEC
CAMHRELOCATION OF DISPLACED SERVICES OF PHASE 1C
Scale:
F. PANICI
0ISSUED FOR PERMIT / TENDER2019-12-06