ecm 517 ubbl part viii

34
PART VIII FIRE ALARMS, FIRE DETECTION, FIRE EXTINGUISHMENT AND FIRE FIGHTING ACCESS

Upload: mashithah-ahmad

Post on 08-Apr-2015

1.697 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Ecm 517 Ubbl Part Viii

PART VIII

FIRE ALARMS, FIRE DETECTION, FIRE EXTINGUISHMENT AND FIRE FIGHTING ACCESS

Page 2: Ecm 517 Ubbl Part Viii

Section 225 Detecting and extinguishing fire

Every building shall be provided with means of detecting extinguishing fire and fire alarms together with illuminated exit signs in accordance with illuminated as specified in the Tenth Schedule to these By law

Every building shall be served by at least one fire hydrant located not more than 92.5 meters from the nearest point of fire brigade access.

Depending on the size and location of the building and the provision of access for fire appliances , additional fire hydrant shall be provided as may be required by Fire Authority.

Page 3: Ecm 517 Ubbl Part Viii

Section 226 Automatic system for hazardous occupancy.

Where hazardous processes, storage or occupancy are of such character to require automatic sprinklers or other automatic extinguishing system, it shall be of a type and standard appropriate to extinguish fires in the hazardous materials stored or handled or for safety of the occupants.

Section 227 Portable extinguishes

Portable extinguishes shall be provided in accordance with the relevant codes of practice and shall be sited in prominent positions on exit routes to be visible from all directions and similar extinguishers in a building shall be of the same method of operation.

Page 4: Ecm 517 Ubbl Part Viii

228. Sprinkler ValvesSprinkler will discharges water when

the effects of a fire have been detected, such as when a predetermined temperature has been reached.

Sprinkler valves shall be located in a safe and enclosed position on the exterior wall and shall be readily accessible to the Fire Authority.

All sprinkler systems shall be electricity connected to the nearest fire station to provide immediate and automatic relay of the alarm when activated

Page 5: Ecm 517 Ubbl Part Viii

229. Means of Access and Fire Fighting in Buildings Over 18.3 Metres High.

provided with means of gaining access and fighting fire from within the building consisting of fire fighting access lobbies, fire fighting staircase, fire lifted and dry or wet riding systems.

Fire fighting access lobbies shall be provided at every floor level and shall be so located that the level distance.

A fire fighting staircase shall be provided to give direct access to each fire fighting access lobby and shall be directly accessible from outside the building at fire appliances access level.

A fire lift shall be provided to give access to each fire fighting access lobby or in the absence of a lobby to the fire fighting staircase at each floor level.

Page 6: Ecm 517 Ubbl Part Viii

230. Installation and Testing of Dry Rising System.

Main vertical pipe intended to distribute water to multiple levels of a building or structure as a component of the fire suppression systems.

Dry rising system shall be provided in every building in which the topmost floor is more that 18.3 metres but less than 30.5 metres above fire appliance access level.

A hose connection shall be provided in each fire fighting access lobby.

Dry riser shall be tested hydrostatically to withstand not less than 14 bars of pressure for two hours in the presence of the Fire Authority before acceptance.

Page 7: Ecm 517 Ubbl Part Viii

231. Installation and Testing of Wet Rising System.

Wet rising system shall be provided in which:

◦ Topmost floor more than 30.5 metres above fire appliance access level.

◦ Minimum 152.4 mm diameter and tested at a pressure 50% above the working pressure required and not less than 14 bars for at least 24 hours.

◦ Outlet comprise 63.5 mm instantaneous coupling fitted with a hose not less than 38.1 mm diameter equipped with approved typed cradle and a variable fog nozzle.

Page 8: Ecm 517 Ubbl Part Viii

Hose connection provided in each fire fighting access lobby.

◦ Provide in every staircase which extends from the ground floor level to the roof and equipped with 3-way 63.5 mm outlet above the roof line.

Stage of the wet riser not exceed 61 m, unless permitted by D.G.F.S but still not exceed 70.15 m.

Page 9: Ecm 517 Ubbl Part Viii

232. Wet or Dry Rising System for Buildings Under Construction.

Rising systems shall be installed when building reached a height above the level of the fire brigade pumping inlet with connections there to locate adjacent to a useable staircase.

Riser shall be extended to:◦ Within 2 floors of the topmost floor under

construction.◦ Where the designed height of the building

requires the installation of a wet riser system fire pumps, water storage tanks and water main connections shall be provided to serve the riser.

Page 10: Ecm 517 Ubbl Part Viii

233. Foam inlets.

Boiler rooms and storage areas below ground level where automatic extinguishing installations are not provided shall be equipped with foam inlets.

Page 11: Ecm 517 Ubbl Part Viii

234. Underground Structures And

Windowless Building

• All underground structures, windowless buildings depending on:

type of occupancy storage processes type of protection installed shall be provided with foam inlets as may be required by the Fire Authority.

Page 12: Ecm 517 Ubbl Part Viii

235. Fixed Installations

Depends on the nature of hazard process and occupancy (required by Fire Authority) total flooding system or unit protection system

Page 13: Ecm 517 Ubbl Part Viii

236. Special Hazards

Places constituting special hazards or risk due to the nature of storage, trade, occupancy or size shall be required to be protected by fixed installations, protective devices, systems and special extinguishers (required by Fire Authority)

Page 14: Ecm 517 Ubbl Part Viii

237. Fire Alarms Fire alarms – refer the Tenth Shedule to these

By-Laws. All premises and buildings with

gross floor area excluding car park storage areas exceeding 30.5 metres in

height shall be provided with a two-stage alarm

system with evacuation (continuous signal) to be given immediately in the effected section of the premises while an alert (intermittent signal) be given in adjoining section.

Provision shall be made for the general evacuation of the premises by action of a master control.

Page 15: Ecm 517 Ubbl Part Viii

238. Command & Control Centre

Every large premises or building exceeding 30.5 metres in height shall be provided with a command and control centre located on the designated floor

It shall contain a panel to monitor the public address, fire brigade communication, sprinkler, waterflow detector, fire detection and alarm systems and with a direct telephone connection to the appropriate fire station by-passing the switchboard.

Page 16: Ecm 517 Ubbl Part Viii

239. Voice Communication System

There shall be two separate approved continuously electrically supervised voice communications systems

◦a fire brigade communications system;

◦a public address system between the central control station.

Page 17: Ecm 517 Ubbl Part Viii

239. Voice Communication System (cont…)

The area involve are:-

Lifts, lift lobbies, corridors and staircases;

In every office area exceeding 92.9 square metres in area;

In each dwelling unit and hotel guest room where the fire brigade sytem may be combined with the public address system.

Page 18: Ecm 517 Ubbl Part Viii

240. Electrical Isolating Switch

Every floor or zone of any floor with a net area exceeding 929 square metres shall be provided with an electrical isolation switch located within a staircase enclosure to permit the disconnection of electrical power supply to the relevant floor or zone served.

The switch shall be of a type similar to the fireman’s switch specified in the Institution of Electrical Engineers Regulations then in force.

Page 19: Ecm 517 Ubbl Part Viii

241. Special requirements for fire

alarm systems

1. Fire detection and alarm system are design to provide warning of the outbreak of fire and allow appropriate fire fighting action to taken before the situation get out of control.

2. The design depends on:a. Type of building –UBBL Requirement,

Bomba Requirements.

b. Type of system to be installed.c. Type of fire detection system.

Page 20: Ecm 517 Ubbl Part Viii

242. Fire fighting access lobbies

Fire fighting access lobby is a protected lobby designed for firefighting access.

According to Uniform Building By-Laws (UBBL):1. Buildings in which topmost floor is more than 18.3

metres above fire appliance access level shall be provided with means of gaining access and fighting fire from within the building consisting of fire fighting access lobbies, fire fighting staircases, fire lifts and dry or wet rising systems.

2. Fire fighting lobbies shall be provided at every floor level and shall be so located that the level distance from the furthermost point of the floor does not exceed 45.75 metres.

Page 21: Ecm 517 Ubbl Part Viii

Fire fighting access lobbies shall conform to the following requirements:

1. Each lobby shall a floor area of not less than 5.57 square metres.

2. The open able area of windows or area of permanent ventilation shall be not less than 25% of the floor area of the lobby and, if ventilation is by means of open able windows, additional permanent ventilation having a free opening of 464 square centimetres shall be provided except that mechanical pressurisation may be provided as an alternative.

Page 22: Ecm 517 Ubbl Part Viii

243. Fire lifts1. In a building where the top occupied floor is

over 18.5 metres above the fire appliance access level fire lifts shall be provided.

2. The fire lifts shall be located within a separate protected shaft if it opens into a separate lobby.

3. Fire lifts shall be provided at the rate of one lift in every group of lifts which discharge into the same protected enclosure of smoke lobby containing the rising main, the fire lifts provided are located not more than 61 metres travel distance from the furthermost point of the floor.

Page 23: Ecm 517 Ubbl Part Viii

244. Standards required

According to the Uniform Building By-Laws (UBBL), all the fire fighting installations and appliance shall conform to the current edition of the following standards: Fire Hydrants BS 750:1977, BS CP 402.101:1952Hydraulic Hose Reels BS 5306 Part1: 1976Portable Extinguishers BS CP 402 Part 3: 1964Dry/ Wet Rising Mains BS 3980:1996, BS 5306: Part 1: 1076, BS 750:

1964, BS 3980: 1966Automatic Sprinklers FOC Rules 29th Edition: 1973Fire Alarm Systems FOC rules: 1973, BS CP1019: 1973, BS 3116:

Part1: 1970, BS 3116: Part4: 1974, BS 5445: Part1: 1977Fire Damper AS 1682: 1974Fire Lifts BS 2655: Pat1: Appendix ESmoke Control AS 1668: Part1: 1974

Page 24: Ecm 517 Ubbl Part Viii

245. APPROVAL OF D.G.F.S

All fire fighting installations and appliances other than those conforming to the standards listed in by-law 244 shall be of those as tested and approved by the D.G.F.S.

Plans, drawings and calculations of all fixed installations shall be submitted to the Fire Authority in a manner prescribed by the D.G.F.S. before commencement of work.

Every plan, drawing or calculation in respect of any automatic sprinklers or other fixed installations shall be submitted together with the relevant forms as prescribed in the Tenth Schedule to these By-laws.

Page 25: Ecm 517 Ubbl Part Viii

246. CERTIFICATION ON COMPLETION

When the fixed installation has been completed and final tests carried out the person submitting the plans shall certify to the Fire Authority on Form B as set out in the Tenth Schedule to these By-laws that the work has been completed and the necessary tests carried out in accordance with the current D.G.F.S. rules for various fixed installations.

Page 26: Ecm 517 Ubbl Part Viii

247. WATER STORAGE

Water storage capacity and water flow rate for fire fighting systems and installations shall be provided in accordance with the scale as set out in the Tenth Schedule to these By-laws.

Main water storage tanks within the building, other than for hose reel systems, shall be located at ground, first or second basement levels, with fire brigade pumping inlet connections accessible to fire appliances.

Storage tanks for automatic sprinkler installations where full capacity is provided without need for replenishment shall be exempted from the restrictions in their location.

Page 27: Ecm 517 Ubbl Part Viii

248 Markings on Wet Riser, etc

• Wet riser, dry riser, sprinkler and other fire installation pipes and fittings shall be painted red.

• All cabinets and areas recessed in walls for location of fire installations and extinguishers shall be clearly by identified by Fire Authority.

Page 28: Ecm 517 Ubbl Part Viii

249 Smoke and Heat VentingSmoke venting facilities shall be

provided for the safe use of exit in

◦windowless buildings, ◦underground structures and ◦large area factories

Page 29: Ecm 517 Ubbl Part Viii

250 Natural Draught Smoke Vent

Natural draught smoke venting shall utilize roof vents or vents in walls at or near the ceiling level.

Such vent shall normally be in open positions of if they are closed, they have to design the vent open automatically in the event of a fire.

Page 30: Ecm 517 Ubbl Part Viii

251. Smoke Vent To Be Adequate To Prevent Dangerous Accumulation Of

SmokeWhere smoke venting facilities are install for purpose of exit safety in accordance with the requirement of this part they shall be adequate to prevent dangerous accumulation of smoke during the period of time necessary to evacuate the area served using available exit facilities with a margin of safety to allow for unforeseen contingencies.

252.Smoke Vent To Be Openable Fire Authorities

The discharge apertures of all manual smoke vents shall be arranged as readily openable by the Fire Authorities working from the exterior.

Page 31: Ecm 517 Ubbl Part Viii

253.Emergency Power System

  1) Emergency Power System shall be provided to supply illumination and power automatically in the events of failure of the normal supply or in the events of the accident to elements of the system supplying power and illumination essential for safety to life and property.

 2) Emergency Power System Provide power

for smoke control system, illumination, fire alarm system, fire pumps, public address systems, fire lift and other emergency system.

 

Page 32: Ecm 517 Ubbl Part Viii

Cont……..3) Emergency Power System Adequate

capacity and rating for emergency operation of all equipment connected to the system including the simultaneous operation of all fire lift and one other lift. 

 4)All wiring for emergency system shall be in

metal conduit or of fire resisting mineral insulated cable, laid along area of least fire risk.

 

Page 33: Ecm 517 Ubbl Part Viii

5) Current supply shall be such that I the events of failure of the normal supply to or within the within the building or group of building concerned, the emergency power or emergency lighting, or both be available within 10 seconds of interruption of the normal supply. The supply systems for emergency purpose shall comprises one or more of the following approved types:a)Storage Batteryb) Generator Set

Page 34: Ecm 517 Ubbl Part Viii

THANK YOU…