ecodesign directive for hvac chillers and heat pumps

16
Ecodesign Directive for HVAC Chillers and Heat Pumps YORK Commitment: A European View

Upload: others

Post on 04-Oct-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Ecodesign Directive for HVAC Chillers and Heat Pumps

Ecodesign Directive for HVAC Chillers and Heat Pumps

YORK Commitment: A European View

Page 2: Ecodesign Directive for HVAC Chillers and Heat Pumps

At Johnson Controls, we have been dedicated to protecting the environment since our invention of the electric thermostat in 1885, which provided a fundamental shift in the energy efficiency of buildings. Now, all over the world, our products and services empower customers and communities to consume less energy and conserve resources.

This commitment is in line with the targets of the European climate and energy package for the future.

Page 3: Ecodesign Directive for HVAC Chillers and Heat Pumps

03 YORK Commitment: A European View | 2020

EU Energy and Climate Policy ContextThe European 2050 Vision towards a low carbon economy is targeting reduction of 80/95% of the Green-house gas emissions by looking at the reduction of the 3 following parameters and comparing to the values of 1990.

EU Energy efficiency improvement targets strongly influence the HVAC market

Buildings are the largest consumers of energy today, and HVAC systems account for a significant portion of a building’s energy consumption. This is why the HVAC industry is a focus of European Environmental Policies. The F-Gas regulation addresses direct emissions while EPBD, EcoDesign and RES are directives focused on indirect greenhouse gas emissions by improving the efficiency of the HVAC systems and the buildings.

31%

40%

29%

Buildings

Transport

Industry10% Water Heating

18% Lighting

37% HVAC

15% IT Equipment

21% Other

Indirect emissions from power generation:

over 95% of greenhouse gas emissions

Direct emissions from refrigerant releases:less than 5% of total greenhouse gas emissions

1990 2000 2010 2020 2030 2040 2050

Primary Energy consumption -20% -27%Green-house effect gas emissions -20% -40% -80/95%Use of renewable energies +20% +27%

205020302020

Page 4: Ecodesign Directive for HVAC Chillers and Heat Pumps

04

The Regulatory Response

What is Ecodesign Directive?

As stated on the previous graph, building energy consumption is ~40% of the overall total in Europe and the HVAC system consumes more than a third of the building energy total. So, as an estimate, the HVAC industry is responsible of 15% of the overall European energy consumption, That makes it a key driver to achieve the 2020, 2030 and 2050 targets. There are four main legislations focused on the HVAC industry:

Ecodesign Directive is a framework that regulates the environmental impact of all products using energy (excluding products in the transport sector). Application of Ecodesign Directive for Chillers and Heat Pumps is enforced through regulations specific to various products and operating ranges. Once a regulation is published and active, products affected must comply with the minimum efficiency performance, sound emissions, etc., to receive a CE mark.

As the word Ecodesign stands for, this regulation focuses on the design of the machine and implies taking into account all the environmental impacts of a product right from the earliest stage of design. It’s proven that around 80% of the environmental impact is determined at the design stage while the other 20% is related to the operation. Ecodesign is forcing manufacturers to renew the product range and create new and more efficient designs.

RES2009

• Renewable Energy Sources Directive (2009/28/EC)

• Recognize heat pumps as renewable source, if technology meets minimum efficiency requirements

Driving growth for Heat Pumps

EPBD2010

• Energy Performance of Buildings Directive (2010/31/EU)

• Establish inspection schemes for heating and air-conditioning systems

Driving Efficiency in Buildings, leading, for example, to more efficient chillers, as well as increasing the number of controls (OEM) and with higher complexity.

FGAS2014

• F-Gas regulation (517/2014)

• Phase down for HFCs used in HVAC (Chillers). Baseline 2015, -79% by 2030

Driving low GWP based product offering

Ecodesign2009

• Eco-Design Directive (2009/125/EC)

• Ban for products below minimum seasonal energy efficiency levels (no CE mark)

Driving efficiency requirements focus on part load efficiency, requiring better controls

YORK Commitment: A European View | 2020

Page 5: Ecodesign Directive for HVAC Chillers and Heat Pumps

Ecodesign has changed the way we speak

Which products are affected by Ecodesign?

05 YORK Commitment: A European View | 2020

The European Union has developed two directives (Ecodesign Directive 2009/125/EC and Energy Labeling Directive 2010/30/EC) to address the environmental impact of all Energy related Products (ErP) beginning at the earliest stages of design. The Ecodesign directive affects all types of Energy related Products (ErP) such as TVs, washing machines, lights and, of course, also HVAC products and components. Energy related Products (ErP) are grouped into “Lots” that, once they are published, they become mandatory CE regulations. There are three Ecodesign Lots (already approved regulations) that directly impact HVAC products.

Each of the three regulations set the MEPS or Minimum Efficiency Performance Standards for the product category and those are implemented in 2 steps (Tiers), as shown in the table below.

According to the below chart, a same chiller model can be applied to different regulations and/or different temperature levels. When the application is known, the machine should comply with the requirements defined by Ecodesign for this specific application. If a product meets the requirements of any category, it is enough to get the CE mark as the model can be used at the different applications.

Former full efficiency ratios at full load like EER and COP are being used less and less. Even the former seasonal efficiency ratio ESEER has been replaced. Ecodesign MEPS are the current key indicators used for all HVAC product and compliance is mandatory to have the CE marking. The Eurovent organization is already using Ecodesign MEPS at the different certification programs and not using their former ESEER values anymore.

ECO

DES

IGN

EU F

ram

ewor

k Di

rect

ive

2009

/ 12

5 / E

CSe

ts t

he G

ener

al R

ules

Regulation Scope MEPS 2015 2016 2017 2018 2019 2020 2021

Reg 2016/2281(former ENER Lot 21)

Comfort Chillers SEER ηs,cT1

Jan18T2

Jan21High Temperature Process Chillers SEPRHT

Reg 2015/1095(former ENTR Lot 1) Medium Temperature Process Chillers SEPRMT

T1Jul16

T2Jul18

Reg 813/2013(former ENER Lot 1) Heat Pumps SCOP ηs,h T1

Oct15T2

Oct17

Calculations according to Transitional Methods that indicates the Harmonized EN standards to use (EN14511, EN14825 mainly).

SEPR Is the new performance indicator for chillers in industrial process cooling applications.

SEER Is the new performance indicator for chillers in comfort cooling applications.

SCOP Is the new performance indicator for space heating applications.

Etas (ηs):Ecodesign introduces a new performance indicator for seasonal primary energy efficiency that allows product efficiency comparison with different energy sources.

SEPREER

COP

ESEER

SEER ηs,c

SCOP ηs,h

BEFORE Ecodesign AFTER Ecodesign

* No YORK Chillers apply to Low Temperature Process regulation

SEPR SEER ηs,c

Low Temp. (LT)-25°C brine

Air-cooled andwater-cooled

Medium Temp. (MT) -8°C brine

Air-cooled andwater-cooled

High Temp. (HT)+7°C water

Heat Pump Low Temp. (LT) +35°C

Air-cooled andwater-cooled

Air-cooled andwater-cooled

Comfort Low Temp. (LT) +7°C

Comfort Medium Temp. (MT) +18°C

Heat Pump Med. Temp. (MT) +52°C

Air-cooled andwater-cooled

Air-cooled andwater-cooled

Air-cooled andwater-cooled

*

REGULATION 2015/1095

Process Chillers Comfort A/C Chillers Heat Pumps

REGULATION 2016/2281 REGULATION 813/2013

SCOP ηs,h

Page 6: Ecodesign Directive for HVAC Chillers and Heat Pumps

06

Comfort CoolingRegulation 2016/2281

YORK Commitment: A European View | 2020

SEER

Ecodesign regulation 2016/2281 affects Comfort Cooling Chillers with rated cooling capacity below 2,000 kW with a leaving chilled water temperature equal to or higher than 2°C. It’s divided into two sub-categories (low and medium T) based on the chiller water temperature. The MEPS that apply in each of the two Tiers are the same independently of the T sub-category used. Manufacturers must provide a technical data sheet, called Product Fiche, with the equipment to detail the application(s) in compliance.

Calculation methodAn important point that must be specified on the manufacturers rating report is the calculation method regarding the water flow and outlet temperature. According to the regulation there are four possible methods.

Comfort Chillers used at low temperatureChillers that provide water to fan coil or air handling units using 12 to 7°C as entering and leaving temperatures for the efficiency calculation.

Comfort Chillers used at medium temperatureChillers that provide water, for instance to cooling floors or chilled beams, using 23 to 18°C as entering and leaving temperatures for the efficiency calculation.

SEER - Seasonal Energy Efficiency Ratio

Ecodesign regulation introduces new Minimum Energy Performance Standards for Comfort Cooling Chillers (SEER) that it’s the ratio between the annual cooling demand and the annual electrical input energy over the entire cooling season.

SEER is calculated using standard EN14825, which takes the following into account:• Seasonal efficiency while the unit is operating (SEERon). It considers all the energy consumptions during ON mode (compressor, fans, auxiliaries) and takes also into account the heat exchanger pressure drops.

• Electrical consumption when the compressor is not running: crankcase heater, standby or OFF mode

SEER is a better performance indicators for cooling than former ESEER, as it takes into account temperature bins and hours based on weather data from a reference city (Strasbourg) and for a comfort cooling application.

• Variable Outlet increases the leaving water temperature at partial load. This reduces the lift required by the chiller, reducing energy use significantly. To provide this rating, chillers must be capable of automatic water temperature reset based on outdoor ambient temperature. With this capability, even projects without advanced building control systems can benefit. Variable Outlet Temperature (VO) is only available for chillers at low temperature, while those at medium temperature use a Fixed Outlet Temperature (FO) of 18°C.

• Variable Flow reduces energy use at part load through reduced waterside pressure drop and water pump power input. Variable Speed Pumps must be fitted to the system to benefit from this savings.

• It is important to note that efficiencies can vary hugely depending on the temperatures and the method of calculation.

• It is crucial to check the chilled water conditions used to determine the SEER when comparing the seasonal energy efficiency of chillers.

FW/FO = Fixed Water Flow, Fixed Outlet TemperatureFW/VO = Fixed Water Flow, Variable Outlet Temperature

VW/FO = Variable Water Flow, Fixed Outlet TemperatureVW/VO = Variable Water Flow, Variable Outlet Temperature

ηs,c

According to the standard EN14825 the number of operating hours for a comfort chiller is 2602h (only 29.7% of the total year hours).

0 0

50 20

100 40

150 60

200 80

250 100

15°

Num

ber

of o

pera

ting

hour

s at

sp

ecifi

c am

bien

t te

mpe

ratu

res

Uni

t lo

ad (%

)

Outdoor temperature (°C)

27°21° 33°18° 30°24° 36°16° 28°22° 34°19° 31°25° 37°17° 29° 39°23° 35°20° 32°26° 38°

Unit runs 73% of the time

Unit runs 26% of the time

1% of the time

D C B A

450

400

350

300

250

200

150

100

50

0-20

Ambient temperature [°C]

Bin hours Process Chillers (SEPR) Bin hours Comfort Chiller (SEER)

BIN

hou

rs p

er y

ear

-10-15 -5 0 5 10 15 20 25 30 35

Page 7: Ecodesign Directive for HVAC Chillers and Heat Pumps

07 YORK Commitment: A European View | 2020

Efficiency requirements set by REGULATION 2016/2281 Comfort Cooling

Regulation 2016/2281 sets seasonal energy efficiency in ηs,c. This value expresses SEER in terms of primary energy and makes it possible to compare the energy efficiency of units using different energy sources. In Europe, on average 2.5 kW of primary energy is required to generate 1kW of electricity and therefore the next formulas and values are used for the conversion.

Design points for Comfort Cooling

The regulation requires calculating the part load efficiencies at A, B, C, D rating points as per below table. For the rest of the temperatures covered by the regulation, the values are calculated using an interpolation and extrapolation process. Each point is weigthed by the BIN hours defined by the standard. Please refer to the calculation example for a better understanding (page 14).

No cooling efficiency requirement is defined by Ecodesign for heat pumps (regulation 813/2011) or for medium temperature industrial or for process chillers (regulation 2015/1095).

ƞs,c(%) =1/CC x SEER-∑Fi

CC – Conversion Coefficient

European average coefficient that represents the amount of primary energy required to obtain electricity. CC is defined by the regulation with a constant value of 2,5.

∑Fi – Correction Factors

Air-cooled chillers ∑Fi = 3%

Water-cooled chillers ∑Fi = 8%

COMFORT CHILLERSTIER 1 (Jan 2018) TIER 2 (Jan 2021)

ηs,c % SEER ηs,c % SEER

Air cooled < 400 kW 149 3.80 161 4.10

Air cooled 400 to 2000 kW 161 4.10 179 4.55

Water cooled < 400 kW 196 5.10 200 5.20

Water cooled 400 to 1500 kW 227 5.88 252 6.50

Water cooled 1500 to 2000 kW 245 6.33 272 7.00

Air to water comfort chillers

Rating Point

Load %

Outdoor air dry bulb temperatures (°C)

Fan coil application inlet/outlet water temperatures Cooling floor application inlet/outlet water temperatures (°C)

Fixed outlet water temperature (°C)

Variable outlet water temperature (°C)

A 100 35 12 / 7 12 / 7 23 / 18

B 74 30 (*) / 7 (*) / 8.5 (*) / 18

C 47 25 (*) / 7 (*) / 10 (*) / 18

D 21 20 (*) / 7 (*) / 11.5 (*) / 18

Water to water comfort chillers

Rating Point

Load %

Temp. (°C)

Cooling tower or water loop application inlet/outlet temp. (°C)

Ground coupled application

(water or brine) inlet/outlet temp. (°C)

Fan coil application inlet/outlet water temperatures Cooling floor application

inlet/outlet water temperatures (°C)Fixed outlet water

temperature (°C)Variable outlet water

temperature (°C)

A 100 35 30 / 35 10 / 15 12 / 7 12 / 7 23 / 18

B 74 30 26 / (*) 10 / (*) (*) / 7 (*) / 8.5 (*) / 18

C 47 25 22 / (*) 10 / (*) (*) / 7 (*) / 10 (*) / 18

D (**) 21 20 18 / (*) 10 / (*) (*) / 7 (*) / 11.5 (*) / 18

(*) Temperatures dependent on water flow rate as determined at standard rating conditions.(**) Entering condenser water decreases to 18°C at partial load. Together with Variable Outlet reset to 11.5°C, the chiller can operate at very low lift for outstanding energy efficiency. Only the most advanced chillers can operate at this condition today. If this condition cannot be achieved, Ecodesign standard permits rating at highest leaving evaporator water temperature possible, typically 8-10°C (depending on technology).

Page 8: Ecodesign Directive for HVAC Chillers and Heat Pumps

Medium TemperatureRegulation 2015/1095

High TemperatureRegulation 2016/2281

Ecodesign regulation 2016/2281 also applies to High Temperature Process Chillers with rated cooling capacity below 2,000 kW for industrial process applications. High temperature process chillers are capable of delivering leaving water temperatures of between 2°C and 12°C. For water leaving temperatures above 12°C there is no minimum efficiency requirement set by the regulation.

In addition regulation 2015/1095 affects any capacity Process Chillers operating at design capacity that can generate outlet fluid temperature of -8°C (Medium Temperature) or -25°C (Low Temperature - Out of scope of this guide). There is no limitation in terms of cooling capacity of the chiller so, unlike the High Temperature Process regulation, in this case it applies to chillers above 2,000 kW.

Calculation method

Rating report provided by the manufacturer must specify the calculation method regarding the water flow.SEPR is measuring the efficiency of a chiller applied to a process where normally the requested temperature is fixed among the year.Therefore in that case there are only two possible methods.

SEPR - Seasonal Energy Performance Ratio

Ecodesign regulation 2016/2281 and 2015/1095 introduces a new indicator called Seasonal Energy Performance Ratio (SEPR), which is the ratio of annual cooling demand to annual electrical energy consumption.

SEPR is calculated from an average climate reference with ambient temperature ranging from -19°C up to 38°C, and with corresponding operating hours at each temperature bin.

For Process cooling the operating load ranges from 100% down to 80%.

• Variable Flow reduces energy use at part load through reduced waterside pressure drop. Variable Speed Pumps must be fitted to the system to benefit from this savings.

• It is important to note that efficiencies can vary hugely depending on the temperatures and the method of calculation.

• It is crucial to check the chilled water conditions used to determine the SEPR when comparing the seasonal energy efficiency of chillers.

FW/FO = Fixed Water Flow, Fixed Outlet Temperature VW/FO = Variable Water Flow, Fixed Outlet Temperature

SEPRMT

SEPRHT

08 YORK Commitment: A European View | 2020

Note that SEPR is focused on high loads (typical of process cooling applications) and covers the complete 8760 hours of the year.

0 0

50

20100

300

40150

350

60

200

400

80

250

450

100

-19°

Num

ber

of o

pera

ting

hour

s at

sp

ecifi

c am

bien

t te

mpe

ratu

res

Uni

t lo

ad (%

)

Outdoor temp. (°C)

5°-7° 17°-13° 11°-1° 23° 33°-17° 7°-5° 19°-11° 13°1° 25° 35°-15° 9° 29°-3° 21° 31°-9° 15°3° 27° 37° 39°

Unit runs 71% of the time

Unit runs 28% of the time

<1% of the time

D C B A

450

400

350

300

250

200

150

100

50

0-20

Ambient temperature [°C]

Bin hours Process Chillers (SEPR) Bin hours Comfort Chiller (SEER)

BIN

hou

rs p

er y

ear

-10-15 -5 0 5 10 15 20 25 30 35 37

Process Chillers

Page 9: Ecodesign Directive for HVAC Chillers and Heat Pumps

Efficiency requirements set by REGULATION 2016/2281 High Temperature Process Chillers

Regulation 2016/2281 sets minimum efficiency levels for positive leaving water temperature chillers (high temperature chillers) rated up to 2,000 kW used in industrial process cooling applications.There is no SEPRHT requirement for chillers and heat pumps that apply to other regulations.

Efficiency requirements set by REGULATION 2015/1095 Medium Temperature Process Chillers

Regulation 2015/1095 sets minimum efficiency levels for chillers with negative leaving water temperature used in industrial process cooling applications. Medium temperature process chillers are defined as units capable of operating at -8°C leaving temperature.Chillers that applies to this regulation (SEPRMT) are excluded to the other Ecodesign regulations (like 2016/2281)

MEDIUM TEMPERATURE PROCESS CHILLERSTIER 1 (Jul 2016) TIER 2 (Jul 2018)

SEPRMT (GWP > 150) SEPRMT (GWP < 150) SEPRMT (GWP > 150) SEPRMT (GWP < 150)

Air cooled < 300 kW 2.24 2.02 2.58 2.32

Air cooled > 300 kW 2.80 2.52 3.22 2.90

Water cooled < 300 kW 2.86 2.57 3.29 2.96

Water cooled > 300 kW 3.80 3.42 4.37 3.93

HIGH TEMPERATURE PROCESS CHILLERSTIER 1 (Jan 2018) TIER 2 (Jan 2021)

SEPRHT (12/7°C) SEPRHT (12/7°C)

Air cooled < 400 kW 4.50 5.00

Air cooled 400 to 2000 kW 5.00 5.50

Water cooled < 400 kW 6.50 7.00

Water cooled 400 to 1500 kW 7.50 8.00

Water cooled 1500 to 2000 kW 8.00 8.50

Part load conditions for SEPR calculation for air-cooled and water-cooled high temperature process chillers

Rating point

Part load ratio %

Air-cooled Water-cooled Evaporator inlet/outlet water temperature (°C)Inlet air temperature (°C) Water inlet/outlet temperature (°C)

A 100 35 30 / 35 12 / 7

B 93 25 23 / (*) (*) / 7

C 87 15 16 / (*) (*) / 7

D (***) 80 5 9 / (*) (*) / 7

Part load conditions for SEPR calculation for air-cooled and water-cooled medium temperature process chillers

Rating point

Air-cooled Water-cooled Air-cooled Water-cooledEvaporator inlet/outlet water temperature (°C)Part load ratio % Part load ratio % Outdoor air inlet

temperature (°C)Water inlet

temperature (°C)

A 100 100 35 30 -2 (**) / -8 (30% EG)

B 93 95 25 25 -2 / -8 (30% EG)

C 87 86 15 15 -2 / -8 (30% EG)

D (***) 80 80 5 9 -2 / -8 (30% EG)

(*) Temperatures dependent on water flow rate as determined at standard rating conditions.(**) Inlet temperature can vary based on allowed flow and ΔT.(***) Entering condenser water decreases to 9°C at partial load and the chiller can operate at very low lift for outstanding energy efficiency. Only the most advanced chillers can operate at this condition today. If this condition cannot be achieved, Ecodesign standard permits rating at lowest entering condenser water temperature possible, typically 18°C (depending on technology).

09 YORK Commitment: A European View | 2020

Design points for Process Chillers

The regulation requires to calculate the part load efficiencies at A, B, C, D rating points as per below table. For the rest of the temperatures covered by the regulation, the values are calculated using an interpolation and extrapolation process. Each point is weighted by the BIN hours defined by the standard. The calculation process is similar to the comfort one so you might refer to the calculation example for a better understanding (page 14).

Note: SEPRMT for chillers charged with refrigerant gas with GWP < 150 can lower the MEPS value by a maximum of 10%.

Page 10: Ecodesign Directive for HVAC Chillers and Heat Pumps

10 YORK Commitment: A European View | 2020

SCOP- Seasonal Coefficient of Performance

Ecodesign regulation 813/2013 introduces a new indicator called Seasonal Coefficient of Performance (SCOP), which is the ratio between the annual heating demand and the annual electrical input energy over the entire heating season.

SCOP is calculated using standard EN14825, which takes the following into account:• Seasonal efficiency while the compressor is running (SCOPon)• Electrical consumption when the compressor is not running: crankcase heater, standby or OFF mode• Backup heater required to achieve the defined heating design load

SCOP takes into account the energy efficiency achieved at each outdoor temperature of an average climate weighted by the number of BIN hours for each of those temperatures. The standard divides Europe in three climate zones, selecting a reference city for each of them and adopting its temperature profile. The “Average” temperature profile is mandatory and corresponds to Strasbourg. There is no cooling efficiency requirement (neither comfort nor process) for heat pumps affected by regulation 813/2103.

Published regulation 813/2013 affects all Heat Pumps (both air and water cooled) with a rated heating output below 400 kW (measured at -10°C ambient)

It relates to units used for space heating application that supply hot water and covers two sub-categories based on the leaving water temperature: low temperature and medium temperature.

Low temperature heat pump means a heat pump space heater that is specifically designed for low-temperature application, and that cannot deliver heating water with an outlet temperature of 52°C at an inlet dry (wet) bulb temperature of -7°C (-8°C) in the reference design conditions for average climate.

Low temperature application means an application where the heat pump space heater delivers its declared capacity for heating at an indoor heat exchanger outlet temperature of 35°C.

Medium temperature application means an application where the heat pump space heater or heat pump combination heater delivers its declared capacity for heating at an indoor heat exchanger outlet temperature of 55°C.

Calculation methodAn important point that must be specified on the manufacturers rating report is the calculation method regarding the water flow and outlet temperature. According regulation there are four possible methods.

• Variable Outlet decreases the leaving water temperature at partial load. This reduces the lift required by the heat pump, reducing energy use significantly. To provide this rating, chillers must be capable of automatic water temperature reset based on outdoor ambient temperature. With this capability, even projects without advanced building control systems can benefit.

• Variable Flow reduces energy use at part load through reduced waterside pressure drop. Variable Speed Pumps must be fitted to the system to benefit from this savings.

• It is important to note that efficiencies can vary hugely depending on the temperatures and the method of calculation.

• It is crucial to check the water conditions used to determine the SCOP when comparing the seasonal energy efficiency of different heat pumps.

FW/FO = Fixed Water Flow, Fixed Outlet TemperatureFW/VO = Fixed Water Flow, Variable Outlet Temperature

VW/FO = Variable Water Flow, Fixed Outlet TemperatureVW/VO = Variable Water Flow, Variable Outlet Temperature

SCOP ηs,h

For the “Average” temperature profile

*Tdesign, h = Reference design temperature = -10°C.

* TOL = Temperature operating limit is the lowest outdoor temperature at which the heat pump can work. Maximum = -7°C.

** Tbiv = ’bivalent temperature’ means the outdoor temperature declared by the manufacturer at which the heat pump exactly meets the heating demand. Maximum = +2°C.

The number of operating hours for a heat pump covered by SCOP is 4910h (56% ot the total year hours).

0

20

40

60

80

100

Num

ber

of o

pera

ting

hour

s at

sp

ecifi

c am

bien

t te

mpe

ratu

res

Uni

t lo

ad (%

)

Outdoor temperature (°C)

Unit runs 75% of the time

Unit runs 23% of the time

2% of the time

ATOL B C D400

350

300

250

200

150

100

50

0

-12 -11 -9-10 -8 -7 -6 -4-5 -3 -2 -1 10 2 3 4 5 6 7 8 9 1110 12 13 14 15

Tbiv* **

Heat PumpsRegulation 813/2013

Page 11: Ecodesign Directive for HVAC Chillers and Heat Pumps

11 YORK Commitment: A European View | 2020

Efficiency requirements set by REGULATION 813/2013 – Heat Pumps

Regulation 813/2013 sets seasonal energy efficiency in ηs,h. This value expresses SCOP in terms of primary energy and it makes it possible to compare the energy efficiency of units using different energy sources.

Energy Labelling Regulation 811/2013

Heat Pumps with capacities below 70 kW are classified by the European Energy Labelling regulation 811/2013 with the objective to inform to the end-user about which is the efficiency level of the heat pump adquired.

ƞs,h(%) =1/CC x SCOP-∑Fi

CC – Conversion Coefficient

European average coefficient that represents the amount of primary energy required to obtain electricity. CC is defined by the regulation with a constant value of 2,5.

∑Fi – Correction Factors

Air source heat pumps ∑Fi = 3%

Water source heat pumps ∑Fi = 8%

Low Temperature Heat Pumps (35°C)TIER 1 (Oct 2015) TIER 2 (Oct 2017)

ηs,h % SCOP ηs,h % SCOP

Air to water low temperature heat pumps < 400 115 2.95 125 3.20

Water to water low temperature heat pumps < 400 115 3.08 125 3.33

Medium Temperature Heat Pumps (55°C)TIER 1 (Oct 2015) TIER 2 (Oct 2017)

ηs,h % SCOP ηs,h % SCOP

Air to water medium temperature heat pumps < 400 100 2.57 110 2.82

Water to water medium temperature heat pumps < 400 100 2.7 110 2.95

Air to water heat pumps

Rating point

Part load ratio %

Outdoor heat exchanger Indoor heat exchanger low temperature Indoor heat exchanger medium temperature

Outdoor air temperature (°C) Fixed outlet water temperatures (°C)

Variable outlet water temperatures (°C)

Fixed outlet water temperatures (°C)

Variable outlet water temperatures (°C)

A 88 -7 (*) / 35 (*) / 34 (*) / 55 (*) / 52

B 54 2 (*) / 35 (*) / 30 (*) / 55 (*) / 42

C 35 7 (*) / 35 (*) / 27 (*) / 55 (*) / 36

D 15 12 (*) / 35 (*) / 24 (*) / 55 (*) / 30

Water to water heat pumps

Rating point

Part load ratio %

Outdoor heat exchanger Indoor heat exchanger low temperature Indoor heat exchanger medium temperature

Inlet/outlet water temperatures (°C) Fixed outlet water temperatures (°C)

Variable outlet water temperatures (°C)

Fixed outlet water temperatures (°C)

Variable outlet water temperatures (°C)

A 88 10 / (**) (*) / 35 (*) / 34 (*) / 55 (*) / 52

B 54 10 / (**) (*) / 35 (*) / 30 (*) / 55 (*) / 42

C 35 10 / (**) (*) / 35 (*) / 27 (*) / 55 (*) / 36

D 15 10 / (**) (*) / 35 (*) / 24 (*) / 55 (*) / 30

Note: The above part load conditions for determining the declared capacity and the declared COP are given in the EN14825 standard.(*) With the water flow rate as determined at the standard rating conditions given in EN 14511-2 at 30/35 for units with a fixed flow rate, and with a fixed delta T of 5°C for units with a variable flow rate.(**) With the water flow rate as determined at the standard rating conditions given in EN 14511-2 at 30/35 for units with a fixed flow rate or with a fixed delta T of 3°C for units with a variable flow rate.

A++

A+

A B C D E F G

35 °C

dB

kW

kW

kW

2015 811/2013

A+

YORK YVAG012RSE30-0AM

7

69

Design points Heat Pumps (for “Average” Temperature Profile)

The regulation requires to calculate the part load efficiencies at A, B, C, D rating points as per below table. For the rest of the temperatures covered by the regulation, the values are calculated using an interpolation and extrapolation process. Each point is weighted by the BIN hours defined by the standard. The calculation process is similar to the comfort one so you might refer to the calculation example for a better understanding (page 14).

Page 12: Ecodesign Directive for HVAC Chillers and Heat Pumps

12 YORK Commitment: A European View | 2020

Product InformationOnce the manufacturer has certified that a specific chiller (or heat pump) meets the corresponding Ecodesign directive, it’s mandatory to provide to installers and end users the following information:

· Declaration of Conformity (DoC) including Ecodesign Directive and applied regulation

· Technical Data Sheet (also called Product Fiche) that summarizes the values used for the MEPS efficiency calculation (ηs,c, SEPR or ηs,h)

Declaration of Conformity Example

Manufacturer:

Assembly model / type: Air-cooled Chiller (Heat Pump) Standard Unit

Assembly Serial No:

Pressure Equipment Directive 2014/68/EU

Machinery Directive 2006/42/EC

EN ISO 12100:2010

EN 378-2:2016

EN 61000-6-2:2005/AC:2005

EN 61000-6-4:2007+A1:2011

EN 14825:2016*

EN 60204-1:2006 +A1:2009+AC:2010

EMC Directive 2014/30/EU

EcoDesign Directive 2009/125/EC

Manufacturers EU Declaration of Conformity

We hereby certify and declare under our sole responsibility that the assembly detailed below:

Conforms with the essential reqiurements of the following relevant EU Directives:

The following applicable harmonised standards have been used in the conformity assesment:

* Chiller application as per Eco-Design Directive 2009/125/EC Implementing Regulation EU 2016/2281, EU 2015/1095 and EU 813/2013. EU 813/2013 is only for heat pump.

And the assembly complies with the essentential requirements and provisions of the above mentioned relevant EU Directives:

Page 13: Ecodesign Directive for HVAC Chillers and Heat Pumps

Technical Data Sheet (Product Fiche) example

Compliance

Manufacturers are to provide to installers and end users instruction and access to a website that makes available (for free) a new “Technical Data Sheet” document summarizing the values used for the efficiency (ηs,c , SEPR or ηs,h) calculation.

Below is an example of the “Technical Data Sheet” as it appears in regulation 2016/2281:

All YORK products on the EU market comply with applicable Ecodesign regulations. In many cases YORK products offer significantly better energy efficiency than required by regulation, resulting in an attractively low cost of operation and lighter environmental footprint.

Information requirements for comfort chillers

Model(s): Information to identify the model(s) to which the information relates.

Outdoor side heat exchanger of chiller: (select which: air or water/brine)

Indoor side heat exchanger chiller: (default: water)

Type: compressor driven vapour compression or sorption process

If applicable: driver of compressor: (electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine)

Item Symbol Value Unit Item Symbol Value Unit

Rated cooling capacity

Prated,c x,x kWSeasonal space cooling

energy efficiencyȠs,c x,x %

Declared cooling capacity for part load at given outdoor temperature TiDeclared energy efficiency ratio or gas utilisation efficiency/auxiliary

energy factor for part load at given outdoor temperature Ti

Tj = + 35°C Pdc x,x kW Tj = + 35°CEERd or

GUEc,bin/AEFc,binx,x %

Tj = + 30°C Pdc x,x kW Tj = + 30°CEERd or

GUEc,bin/AEFc,binx,x %

Tj = + 25°C Pdc x,x kW Tj = + 25°CEERd or

GUEc,bin/AEFc,binx,x %

Tj = + 20°C Pdc x,x kW Tj = + 20°CEERd or

GUEc,bin/AEFc,binx,x %

Degradation coefficient for chillers (*)

Cdc x,x -

Power consumption in modes other than "active mode"

Off mode POFF x,xxx kW Crankcase heater mode PCK x,xxx kW

Thermostat off mode PTO x,xxx kW Standby mode PSB x,xxx kW

Other items

Capacity control fixed / staged / variableFor air-to-water comfort chillers: air flow rate, outdoor measured

- x m3/h

Sound power level, outdoor LWA x,x/x,x dB For air-to-water comfort chillers: air flow rate, outdoor measured

- x m3/hEmissions of nitrogen oxides (if applicable)

NOx (**) xmg/kWh

input GCV

GWP of the refrigerantkg CO2 eq

(100 years)

Standard rating conditions used: (low temperature application/medium temperature application)

Contact details Name and address of the manufacturer or of its authorised representative

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0.9.(**) From 26 September 2018

General Information: Unit name, Air/Water cooled, type compressor

Mode “On” information: Capacity, efficiency at different temperatures for partial load points A,B,C and D

Mode “Off” information: Power input Auxiliaries (crankcase heater, stand-by mode, etc)

Other information: Sound, GWP, flow rates, application: • Floor heating/fancoils• Fancoils/Chilled beams

13 YORK Commitment: A European View | 2020

Page 14: Ecodesign Directive for HVAC Chillers and Heat Pumps

14 YORK Commitment: A European View | 2020

EXPLANATION: • Define the temperature category that our chiller will work (Low 12/7°C or Medium 23/18°C)• Define calculation method: FW/FO, FW/VO, VW/FO, VW /VO• Get Efficiencies at the four points A, B, C, D• Get the consumptions of the unit when it’s OFF: Psb, Pck, Poff, Pto

EXAMPLE • Inverter Screw Air Cooled Chiller working at low temp (12/7°C) and water method FW/VO• Part Load (A, B, C, D) efficiencies shown at the below table

Pto = Psb = Pck = Poff = 0.75 kW

Example of calculation of ECODESIGN comfort ŋs,c in 5 steps

Get all the Technical Data

Sheet Information

1

Air Water (Variable Outlet)

Reference condition

Ambient T(°C)

Entering T(°C)

Leaving T(°C)

Part Load(%)

Net Cooling Capacity (kW)

Net Power Input (kW)

Net EER(%)

A 35 12 7 100 664.48 234.80 2.83 EERA

B 30 12 8.5 74 491.07 128.89 3.81 EERB

C 25 12 10 47 311 65.47 4.75 EERC

D 20 12 11.5 21 137.59 22.48 6.12 EERD

EXPLANATION: • Interpolate and extrapolate A, B, C, D values for the different ambient temperatures and weighten with the BIN hours defined by the Standards EN14825

• For units with staged compressor control, the part load efficiency at the different points is obtained directly by interpolation and extrapolation process (it’s the case of this example as unit is using inverter screw technology).

• For units with fixed speed compressor, a degradation factor must be applied to calculate the part load efficiencies along the different ambient temperatures.

EERbin = EERd x [CR / (Cdc x CR + (1 - Cdc))] where CR is Capacity Ratio and the degradation of coefficient Cdc is 0.9 when it’s not determined by a test.

• Get the SEER of the unit when it’s operating also called SEERON

j Tj (°C) hj Part Load (%) Cooling Demand (Ph) EER(PL) Ph*Tj (Ph*Tj ) / EER(PL)15 0%16 0% 0

1 17 205 6% 42.53 6.12 8717.98 1424.512 18 227 12% 77.08 6.12 17497.09 2859.003 19 225 17% 111.63 6.12 25117.34 4104.14

D 4 20 225 21% 137.59 6.12 30957.75 5058.465 21 216 27% 180.74 5.57 39039.53 7003.866 22 215 32% 215.29 5.38 46287.68 8606.867 23 218 38% 249.84 5.18 54466.10 10510.638 24 197 43% 284.40 4.99 56026.30 11236.72

C 9 25 178 47% 311.00 4.75 55358.00 11654.3210 26 158 53% 353.50 4.59 55853.53 12157.9311 27 137 58% 388.06 4.40 53163.72 12088.1612 28 109 64% 422.61 4.20 46064.41 10962.5013 29 88 69% 457.16 4.01 40230.28 10042.51

B 14 30 63 74% 491.07 3.81 30937.41 8120.0615 31 39 79% 526.27 3.61 20524.46 5679.1516 32 31 84% 560.82 3.42 17385.45 5086.4417 33 24 90% 595.37 3.22 14288.98 4434.8218 34 17 95% 629.93 3.03 10708.76 3538.92

A 19 35 13 100% 664.48 2.83 8638.24 3052.3820 36 9 100% 664.48 2.83 5980.32 2113.1921 37 4 100% 664.48 2.83 2657.92 939.1922 38 3 100% 664.48 2.83 1993.44 704.4023 39 1 100% 664.48 2.83 664.48 234.8024 40 0 100% 664.48 2.83 0.00 0.00

Total 642559.15 141612.92

SEERon 4.54

EXTRAPOLATED VALUES, Below point D (20°C) unit works at EERD

EXTRAPOLATED VALUES, Above point A (35°C) unit works at EERA

INTERPOLATED VALUES, Below point D (20°C) and point C (25°C) temperatures part load efficiencies are calculated using interpolation

INTERPOLATED VALUES, Below point C (25°C) and point B (30°C) temperatures part load efficiencies are calculated using interpolation

INTERPOLATED VALUES, Below point B (30°C) and point A (35°C) temperatures part load efficiencies are calculated using interpolation

BIN hours, “ON”calculation

2

0 0

50 20

100 40

150 60

200 80

250 100

15°

Num

ber

of o

pera

ting

hour

s at

sp

ecifi

c am

bien

t te

mpe

ratu

res

Uni

t lo

ad (%

)

Outdoor temperature (°C)

27°21° 33°18° 30°24° 36°16° 28°22° 34°19° 31°25° 37°17° 29° 39°23° 35°20° 32°26° 38°

Unit runs 73% of the time

Unit runs 26% of the time

1% of the time

D C B A450

400

350

300

250

200

150

100

50

0-20

Ambient temperature [°C]

Bin hours Process Chillers (SEPR) Bin hours Comfort Chiller (SEER)

BIN

hou

rs p

er y

ear

-10-15 -5 0 5 10 15 20 25 30 35

Page 15: Ecodesign Directive for HVAC Chillers and Heat Pumps

15 YORK Commitment: A European View | 2020

EXPLANATION: • Consider all the electrical consumption when the compressor is not running: crankcase heater, standby or OFF mode• Convert in this way the SEERON in the SEER value (SEER < SEERON)• SEER is the ratio between the anual cooling demand (Qc) and the anual electrical input energy over the entire cooling season (Qce)

EXPLANATION: • Conversion of the SEER into ŋs,c• This value expresses SEER in terms of primary energy and it makes it possible to compare the energy efficiency of units using different energy sources

EXPLANATION: • Apply the MEPS defined by the regulation according to the type of unit and capacity

EXAMPLE • After applying the following formulas SEERON = 4.53 becomes SEER = 4.38 as the energy consumption when unit is OFF has taken into account

EXAMPLE • After applying the following formula SEER=4.38 becomes ŋs,c = 172.2%

In our example:

SEER = 4.38Air Cooled -> F(i) = 3%

EXAMPLE • It’s an Air Cooled unit with a cooling capacity of 664 kW so that means that the result ŋs,c = 172.2% passes Tier 1 but not Tier 2

Auxiliaries, all time calculation

Apply Correction Factors

Check that the unit meets

Ecodesign requirements

3

4

5

COMFORT CHILLERSTIER 1 (Jan 2018) TIER 2 (Jan 2021)

ηs cool % SEER 12/7° or 23/18° ηs cool % SEER 12/7° or 23/18°

Air cooled < 400 kW 149 3.80 161 4.10

Air cooled 400 to 2000 kW 161 4.10 179 4.55

Water cooled < 400 kW 196 4.98 200 5.08

Water cooled 400 to 1500 kW 227 5.75 252 6.38

Water cooled 1500 to 2000 kW 245 6.20 272 6.88

SEER = QC / QCE

QC = PDESIGNC x HCE

PTO = PSB = PCK = POFF = 0.75 kWElectrical consumptions when the unit is not operating. Information from the Technical Data Sheet.

HCE = 600 h, HTO = 659 h, HSB = 1377 h, HCK = 2036 h, HOFF = 0 hAmount of hours established by normative EN14825 for the auxiliary consumptions.

PDESIGNC = 664.48 kWInformation from the Technical Data Sheet. It matches with point A cooling capacity (full load).

SEER = 398.688 kW / 91.065 kW = 4.38

ŋS,C = [(1 / 2.5) * 4.38*100] - 3% = 172.2%

. SEER – ∑F(i)ŋS,C =

QCE = + HTO x PTO + HSB x PSB + HCK x PCK + HOFF x POFFSEERon

QC

1CC

CC = Conversion coefficient (2.5 by regulation)

F(i) = Correction factors (3% AC. 8% WC)

Page 16: Ecodesign Directive for HVAC Chillers and Heat Pumps

© 2020 Johnson Controls. All Rights Reserved.

Johnson Controls reserves the right, in line with continuing research and development,

to amend or change specifications without notice. YORK® is a registered trademark of

Johnson Controls, Inc. in the United States and other countries.

About Johnson Controls

Johnson Controls is a global leader creating a safe, comfortable and sustainable world. Our 105,000 employees create intelligent buildings, efficient energy solutions and integrated infrastructure that work seamlessly together to deliver on the promise of smart cities and communities in 150 countries. Our commitment to sustainability dates back to our roots in 1885, with the invention of the first electric room thermostat. We are committed to helping our customers win everywhere, every day and creating greater value for all of our stakeholders through our strategic focus on buildings.

For additional information, please visit www.johnsoncontrols.co.uk