    EDVN041518

    - Heat Pump -

    Split Type Air Conditioners

    FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    2/80

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    3/80

    EDVN041518

    Split Type Air Conditioners FTXM-H Series 1

    Split Type

    Air Conditioners

    FTXM H Series

    1. Power Supply ..........................................................................................2

    2. Functions.................................................................................................3

    3. Specifications..........................................................................................44. Dimensions .............................................................................................6

    4.1 Indoor Unit................................................................................................6

    4.2 Outdoor Unit .............................................................................................6

    5. Wiring Diagrams......................................................................................75.1 Indoor Unit................................................................................................7

    5.2 Outdoor Unit .............................................................................................7

    6. Piping Diagrams......................................................................................86.1 Indoor Unit................................................................................................8

    6.2 Outdoor Unit .............................................................................................8

    7. Capacity Tables ......................................................................................97.1 Heat Pump ...............................................................................................9

    7.2 Capacity correction factor by the length of refrigerant piping

    (Reference) ............................................................................................12

    8. Operation Limit......................................................................................13

    9. Sound Level ..........................................................................................149.1 Measuring Location................................................................................14

    9.2 Indoor Unit..............................................................................................15

    9.3 Outdoor Unit ...........................................................................................16

    10.Electric Characteristics..........................................................................17

    11.Installation Manual ................................................................................1812.Operation Manual..................................................................................28

    12.1 English....................................................................................................28

    12.2 Vietnamese ............................................................................................52

    13.Optional Accessories ............................................................................7613.1 Option List ..............................................................................................76

    Heat Pump

    FTXM20HVMV

    FTXM25HVMV

    FTXM35HVMV

    RXM20HVMV

    RXM25HVMV

    RXM35HVMV

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    4/80

    Power Supply EDVN041518

    2 Split Type Air Conditioners FTXM-H Series

    1. Power Supply

    Note: Power Supply Intake; Outdoor Unit

    Indoor Unit Outdoor Unit Power Supply

    FTXM20HVMV RXM20HVMV1 phase, 220 - 230 - 240 V, 50 Hz1 phase, 220 - 230 V, 60 Hz

    FTXM25HVMV RXM25HVMV

    FTXM35HVMV RXM35HVMV

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    5/80

    EDVN041518 Functions

    Split Type Air Conditioners FTXM-H Series 3

    2. Functions

    Category Functions

    FTXM

    20/25/35HVMV

    RXM20/25/35HVMV

    Category Functions

    FTXM

    20/25/35HVMV

    RXM20/25/35HVMV

    Basic Function Inverter (with inverter power control) Health & Clean Air-purifying filter

    Operation limit for cooling (CDB)10

    ~ 46Photocatalytic deodorising filter

    Air-purifying filter with photocatalyticdeodorising function

    Operation limit for heating (CWB)

    1~ 20

    Titanium apatite photocatalytic air-purifyingfilter (option)

    PAM control

    Standby electricity saving Air filter (prefilter)

    Compressor Oval scroll compressor Wipe-clean flat panel

    Swing compressor Washable grille

    Rotary compressor MOULD PROOF operation

    Reluctance DC motor Heating dry operation

    ComfortableAirflow

    Power-airflow flap Good-sleep cooling operation

    Power-airflow dual flaps Timer WEEKLY TIMER operation

    Power-airflow diffuser 24-hour ON/OFF TIMER

    Wide-angle louvres NIGHT SET mode

    Auto-swing (up and down) Worry Free(Reliability &Durability)

    Auto-restart (after power failure)

    Auto-swing (right and left) Self-diagnosis (R/C, LED)

    3-D airflow Wiring error check function

    COMFORT AIRFLOW operation Anti-corrosion treatment of outdoor heatexchanger

    ComfortControl

    Auto fan speed

    Indoor unit quiet operation Flexibility Multi-split / split type compatible indoor unit

    NIGHT QUIET mode (automatic) Flexible power supply correspondence

    OUTDOOR UNIT QUIET operation (manual) High ceiling application INTELLIGENT EYE operation Chargeless 10 m

    2-area INTELLIGENT EYE operation Either side drain (right or left)

    Operation Automatic operation Power selection

    Programme dry operation Facility setting (cooling at low outdoortemperature)

    Fan only

    LifestyleConvenience

    New POWERFUL operation (non-inverter) RemoteControl

    5-room centralised controller

    Inverter POWERFUL operation Remote control adaptor(normal open pulse contact)

    Priority-room setting

    COOL / HEAT mode lock Remote control adaptor(normal open contact)

    HOME LEAVE operation

    ECONO operation DIII-NET compatible (adaptor)

    Indoor unit ON/OFFbutton

    Wireless LAN connection (option) Signal receiving sign Remote

    ControllerWireless

    R/C with back light Wired

    Temperature display

    Note: : Available

    : Not available

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    6/80

    Specifications EDVN041518

    4 Split Type Air Conditioners FTXM-H Series

    3. Specifications50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V

    Note: The data are based on the conditions shown in the table below.

    Model

    Indoor Unit FTXM20HVMV FTXM25HVMV

    Outdoor UnitRXM20HVMV RXM25HVMV

    Cooling Heating Cooling Heating

    Capacity

    Rated (Min. ~ Max.)

    kW 2.0 (1.0 ~ 2.6) 2.0 (1.0 ~ 2.6) 2.5 (1.0 ~ 3.4) 2.5 (1.0 ~ 3.4)

    Btu/h 6,800 (3,400 ~ 8,850) 6,800 (3,400 ~ 8,850) 8,500 (3,400 ~ 11,600) 8,500 (3,400 ~ 11,600)

    kcal/h 1,720 (860 ~ 2,240) 1,720 (860 ~ 2,240) 2,150 (860 ~ 2,920) 2,150 (860 ~ 2,920)

    Moisture Removal L/h 1.2 1.2

    Running Current (Rated) A 2.8 2.8 3.0 3.0

    Power ConsumptionRated (Min. ~ Max.) W 454 (225 ~ 645) 454 (225 ~ 645) 610 (225 ~ 1,070) 610 (225 ~ 1,070)

    Power Factor (Rated) % 73.7 73.7 92.4 92.4

    COP (Rated) W/W 4.40 4.40 4.10 4.10

    PipingConnections

    Liquid mm 6.4 6.4

    Gas mm 9.5 9.5

    Drain mm 16.0 16.0

    Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes

    Max. Interunit Piping Length m 15 15

    Max. Interunit Height Difference m 12 12

    Chargeless m 10 10

    Amount of Additional Charge ofRefrigerant g/m 20 20

    Indoor Unit FTXM20HVMV FTXM25HVMV

    Front Panel Colour Shiny Pure White Shiny Pure White

    Airflow Rate

    H

    m/min(cfm)

    9.0 (318) 9.0 (318) 9.0 (318) 9.0 (318)

    M 6.7 (237) 7.6 (268) 6.7 (237) 7.6 (268)

    L 4.4 (155) 6.4 (226) 4.4 (155) 6.4 (226)

    SL 3.5 (124) 5.4 (191) 3.5 (124) 5.4 (191)

    Fan

    Type Cross Flow Fan Cross Flow Fan

    Motor Output W 16 16

    Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto

    Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards

    Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof

    Running Current (Rated) A 0.19 - 0.18 - 0.17 /0.19 - 0.180.19 - 0.18 - 0.17 /

    0.19 - 0.180.19 - 0.18 - 0.17 /

    0.19 - 0.180.19 - 0.18 - 0.17 /

    0.19 - 0.18

    Power Consumption (Rated) W 39 39 39 39

    Power Factor (Rated) % 93.3 - 94.2 - 95.6 /93.3 - 94.293.3 - 94.2 - 95.6 /

    93.3 - 94.293.3 - 94.2 - 95.6 /

    93.3 - 94.293.3 - 94.2 - 95.6 /

    93.3 - 94.2

    Temperature Control Microcomputer Control Microcomputer Control

    Dimensions (H W D) mm 283 770 203 283 770 203

    Packaged Dimensions (H W D) mm 263 840 344 263 840 344

    Weight (Mass) kg 8 8

    Gross Weight (Gross Mass) kg 10 10

    Sound PressureLevel H / M / L / SL dB(A) 39 / 34 / 28 / 25 39 / 34 / 29 / 27 40 / 35 / 29 / 25 40 / 35 / 30 / 27

    Outdoor Unit RXM20HVMV RXM25HVMV

    Casing Colour Ivory White Ivory White

    Compressor

    Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type

    Model 1YC22DXD 1YC22DXD

    Motor Output W 395 551

    Refrigerant OilType FW68DA FW68DA

    Charge L 0.275 0.275

    RefrigerantType R-32 R-32

    Charge kg 0.75 0.75

    Airflow Rate H m/min(cfm)

    27.1 (957) 27.1 (957) 27.1 (957) 27.1 (957)

    Fan

    Type Propeller Propeller

    Motor Output W 20 20Running Current (Rated) A 2.61 2.61 2.81 2.81

    Power Consumption (Rated) W 415 415 571 571

    Power Factor (Rated) % 72.3 72.3 92.4 92.4

    Starting Current A 2.8 3.0

    Dimensions (H W D) mm 550 658 275 550 658 275

    Packaged Dimensions (H W D) mm 616 788 359 616 788 359

    Weight (Mass) kg 27 27

    Gross Weight (Gross Mass) kg 31 31

    Sound PressureLevel H dB(A) 48 48 48 48

    Drawing No. 3D096417 3D096418

    Conversion Formulae

    kcal/h = kW 860Btu/h = kW 3412

    cfm = m/min 35.3

    Cooling Heating Piping LengthIndoor ; 27CDB / 19CWB

    Outdoor ; 35CDB / 24CWBIndoor ; 20CDB

    Outdoor ; 7CDB / 6CWB 7.5 m

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    7/80

    EDVN041518 Specifications

    Split Type Air Conditioners FTXM-H Series 5

    50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V

    Note: The data are based on the conditions shown in the table below.

    Model

    Indoor Unit FTXM35HVMV

    Outdoor UnitRXM35HVMV

    Cooling Heating

    CapacityRated (Min. ~ Max.)

    kW 3.5 (1.2 ~ 3.8) 3.5 (1.2 ~ 3.8)

    Btu/h 11,900 (4,100 ~ 12,950) 11,900 (4,100 ~ 12,950)

    kcal/h 3,010 (1,030 ~ 3,270) 3,010 (1,030 ~ 3,270)

    Moisture Removal L/h 1.2

    Running Current (Rated) A 4.6 4.6Power ConsumptionRated (Min. ~ Max.) W 990 (250 ~ 1,320) 990 (250 ~ 1,320)

    Power Factor (Rated) % 97.8 97.8

    COP (Rated) W/W 3.54 3.54

    PipingConnections

    Liquid mm 6.4

    Gas mm 9.5

    Drain mm 16.0

    Heat Insulation Both Liquid and Gas Pipes

    Max. Interunit Piping Length m 15

    Max. Interunit Height Difference m 12

    Chargeless m 10

    Amount of Additional Charge ofRefrigerant g/m 20

    Indoor Unit FTXM35HVMV

    Front Panel Colour Shiny Pure White

    Airflow Rate

    H

    m/min(cfm)

    9.7 (342) 9.9 (349)

    M 7.1 (251) 7.9 (279)L 4.6 (162) 5.9 (208)

    SL 3.6 (127) 4.8 (169)

    Fan

    Type Cross Flow Fan

    Motor Output W 16

    Speed Steps 5 Steps, Quiet, Auto

    Air Direction Control Right, Left, Horizontal, Downwards

    Air Filter Removable, Washable, Mildew Proof

    Running Current (Rated) A 0.27 - 0.26 - 0.24 / 0.27 - 0.26 0.27 - 0.26 - 0.24 / 0.27 - 0.26

    Power Consumption (Rated) W 57 57

    Power Factor (Rated) % 96.0 - 95.3 - 99.0 / 96.0 - 95.3 96.0 - 95.3 - 99.0 / 96.0 - 95.3

    Temperature Control Microcomputer Control

    Dimensions (H W D) mm 283 770 203

    Packaged Dimensions (H W D) mm 263 840 344

    Weight (Mass) kg 8

    Gross Weight (Gross Mass) kg 10

    Sound Pressure

    LevelH / M / L / SL dB(A) 41 / 36 / 30 / 26 41 / 36 / 31 / 28

    Outdoor Unit RXM35HVMV

    Casing Colour Ivory White

    Compressor

    Type Hermetically Sealed Swing Type

    Model 1YC22DXD

    Motor Output W 913

    Refrigerant OilType FW68DA

    Charge L 0.275

    RefrigerantType R-32

    Charge kg 0.75

    Airflow Rate H m/min(cfm) 27.1 (957) 27.1 (957)

    FanType Propeller

    Motor Output W 20

    Running Current (Rated) A 4.33 4.33

    Power Consumption (Rated) W 933 933

    Power Factor (Rated) % 96.2 96.2

    Starting Current A 4.6Dimensions (H W D) mm 550 658 275

    Packaged Dimensions (H W D) mm 616 788 359

    Weight (Mass) kg 27

    Gross Weight (Gross Mass) kg 31

    Sound PressureLevel H dB(A) 48 48

    Drawing No. 3D096419

    Conversion Formulae

    kcal/h = kW 860Btu/h = kW 3412

    cfm = m/min 35.3

    Cooling Heating Piping LengthIndoor ; 27CDB / 19CWB

    Outdoor ; 35CDB / 24CWBIndoor ; 20CDB

    Outdoor ; 7CDB / 6CWB 7.5 m

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    8/80

    Dimensions EDVN041518

    6 Split Type Air Conditioners FTXM-H Series

    4. Dimensions

    4.1 Indoor Unit

    FTXM20/25/35HVMV

    4.2 Outdoor Unit

    RXM20/25/35HVMV

    AIRFLOW (INDOOR)

    THE MARK () SHOWS PIPING DIRECTION

    REAR770

    RIGHT

    30MIN.

    LEFT

    50MIN. 50MIN.205

    REQUIRED SPACE203

    SIGNAL RECEIVER 283

    OPERATION LAMP

    TIMER LAMP

    INDOOR UNIT ON/OFF SWITCHBOTTOM FLAPS

    GAS PIPE 9.5 CuT

    LIQUID PIPE 6.4 CuT

    770SIGNAL TRANSMITTER

    10154916

    6

    BLADE ANGLE1858

    UP/DOWN (AUTOMATIC)172

    HEATINGCOOLING DRY 283

    41.3

    55 5

    163

    4545 45 54.5 54

    41.3

    FAN RIGHT/LEFT (MANUAL) WALL HOLE FOR EMBEDDED PIPING65 HOLE

    WALL HOLE65 HOLE

    5STANDARD LOCATIONS OF WALL HOLES

    45WIRELESS REMOTE CONTROLLER 4545(ARC433A87)

    FRONT PANEL FIXING SCREWS(INSIDE)

    ROOM TEMP. THERMISTOR(INSIDE)

    MODEL NAMEPLATE

    (THE LENGTH OF PIPE OUTSIDE

    THE UNIT: ABOUT 350)

    (THE LENGTH OF PIPE OUTSIDETHE UNIT: ABOUT 400)

    DRAIN HOSE(CONNECTING PARTI.D. 14O.D. 16

    THE HOSE LENGTH OF OUTSIDETHE UNIT IS ABOUT 450)

    MANUFACTURER'S

    LABEL

    TERMINAL BLOCKWITH EARTHTERMINAL(INSIDE)

    (SPACE FORMAINTENANCE)

    (SPACE FORMAINTENANCE)

    (SPACEFOR

    PERFORMANCE)

    INCLUDINGMOUNTING PLATE

    3D093418

    DRAIN OUTLET WALL HEIGHT ON AIR OUTLET SIDE= LESS THAN 1200

    MINIMUM SPACE FOR AIR PASSAGE4-HOLES FOR ANCHOR BOLTS(M8 OR M10) 1

    50

    100

    150

    470 96

    11379

    40

    300

    50 5050

    100

    297

    50

    BRAND NAME LABELHANDLE MANUFACTURE'S LABEL

    13.5 8 OUTDOOR AIR THERMISTOR50275 12 658

    (6.4CuT)

    550

    168

    108

    155 GAS STOP VALVE(9.5CuT)

    INDICATION LABEL (INDONESIA)

    FOR INDONESIA MODEL ONLY

    3D089153C

    (I.D15.9 HOSE FOR CONNECTIONWITH DRAIN JOINT)

    WIRINGINLET

    SERVICEPORT

    IN CASE OF REMOVINGSTOP VALVE COVER

    LIQUIDSTOP VALVE

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    9/80

    EDVN041518 Wiring Diagrams

    Split Type Air Conditioners FTXM-H Series 7

    5. Wiring Diagrams

    5.1 Indoor Unit

    FTXM20/25/35HVMV

    5.2 Outdoor Unit

    RXM20/25/35HVMV

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    10/80

    Piping Diagrams EDVN041518

    8 Split Type Air Conditioners FTXM-H Series

    6. Piping Diagrams

    6.1 Indoor Unit

    FTXM20/25/35HVMV

    6.2 Outdoor Unit

    RXM20/25/35HVMV

    INDOOR UNIT

    HEAT EXCHANGER7.0CuT

    4.8CuT

    7.0CuT

    7.0CuT

    7.0CuT

    CROSS FLOW FANFIELD PIPING

    (6.4CuT) M

    FAN MOTOR

    9.5CuTFIELD PIPING

    (9.5CuT)

    REFRIGERANT FLOWCOOLINGHEATING

    THERMISTOR

    ON HEAT EXCH.

    4D096261

    OUTDOOR UNIT

    HEAT EXCHANGER7.0CuT

    7.0CuT

    9.5

    Cu

    T

    6.4CuT6.4CuT 6.4CuT 6.4CuT

    M

    PROPELLER FAN

    ON: HEATING9.5CuT 9.5CuT

    STRAINER

    6.4CuT

    MUFFLER4.8CuT

    9.5CuT FIELD PIPING(6.4CuT)

    REFRIGERANT FLOW

    COMPRESSOR ACCUMULATOR 9.5CuT FIELD PIPINGCOOLING

    HEATING (9.5CuT)GAS STOPVALVE

    LIQUID STOP

    VALVE

    MOTOR OPERATED

    VALVE

    MUFFLER

    WITHFILTER

    HEATEXCHANGER

    THERMISTOR

    FAN

    MOTOR

    4-WAYVALVE

    DISCHARGE PIPE

    THERMISTOR

    OUTDOOR TEMPERATURETHERMISTOR

    3D096247

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    11/80

    EDVN041518 Capacity Tables

    Split Type Air Conditioners FTXM-H Series 9

    7. Capacity Tables

    7.1 Heat Pump

    FTXM20HVMV + RXM20HVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)

    Cooling

    Heating

    3D096248A

    AFR 9

    BF 0.13

    INDOOR OUTDOOR TEMPERATURE (CDB)

    EWB EDB 20 25 30 32 35 40

    C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14.0 20 1.97 1.77 0.35 1.88 1.73 0.38 1.79 1.69 0.42 1.83 1.71 0.43 1.77 1.69 0.45 1.68 1.64 0.48

    16.0 22 2.05 1.75 0.35 1.97 1.71 0.39 1.88 1.67 0.42 1.92 1.69 0.43 1.86 1.66 0.45 1.77 1.63 0.48

    18.0 25 2.14 1.87 0.35 2.05 1.84 0.39 1.96 1.80 0.42 2.01 1.82 0.43 1.95 1.80 0.45 1.86 1.76 0.49

    19.0 27 2.19 2.01 0.36 2.10 1.98 0.39 2.01 1.95 0.42 2.06 1.96 0.43 2.00 1.94 0.45 1.91 1.91 0.49

    22.0 30 2.32 1.96 0.36 2.23 1.93 0.39 2.14 1.90 0.43 2.19 1.92 0.44 2.14 1.90 0.46 2.05 1.87 0.49

    24.0 32 2.41 1.92 0.36 2.32 1.89 0.39 2.23 1.87 0.43 2.29 1.88 0.44 2.23 1.87 0.46 2.14 1.84 0.49

    AFR 9

    INDOOROUTDOOR TEMPERATURE

    (CDB/CWB)

    EDB 2/1 7/6 11/10

    C TC PI TC PI TC PI

    15.0 1.31 0.36 2.07 0.44 2.25 0.46

    20.0 1.26 0.36 2.00 0.45 2.18 0.47

    22.0 1.24 0.37 1.97 0.46 2.15 0.47

    24.0 1.22 0.37 1.94 0.46 2.13 0.4825.0 1.21 0.37 1.93 0.46 2.11 0.48

    27.0 1.19 0.38 1.90 0.47 2.08 0.48

    Symbols: Notes:

    AFR : Airflow rate (m/min.) 1. shows nominal (rated) capacities and power input.2. TC, PI and SHC must be calculated by interpolation using the figures in the

    above tables. (Figures out of the tables should not be used for calculation.)3. Capacities are based on the following conditions.

    Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

    BF : Bypass factor

    EWB : Entering wet bulb temp. (C)

    EDB : Entering dry bulb temp. (C)

    TC : Total capacity (kW)

    SHC : Sensible heat capacity (kW)

    PI : Power input (kW)

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    12/80

    Capacity Tables EDVN041518

    10 Split Type Air Conditioners FTXM-H Series

    FTXM25HVMV + RXM25HVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)

    Cooling

    Heating

    3D096249A

    AFR 9

    BF 0.13

    INDOOR OUTDOOR TEMPERATURE (CDB)

    EWB EDB 20 25 30 32 35 40

    C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14.0 20 2.46 2.00 0.47 2.35 1.95 0.52 2.23 1.90 0.56 2.28 1.92 0.58 2.21 1.89 0.60 2.10 1.83 0.65

    16.0 22 2.57 1.97 0.47 2.46 1.92 0.52 2.34 1.87 0.56 2.40 1.89 0.58 2.33 1.86 0.61 2.21 1.81 0.65

    18.0 25 2.68 2.09 0.48 2.57 2.04 0.52 2.46 2.00 0.57 2.51 2.02 0.58 2.44 1.99 0.61 2.33 1.94 0.66

    19.0 27 2.73 2.23 0.48 2.62 2.18 0.52 2.51 2.14 0.57 2.57 2.16 0.58 2.50 2.13 0.61 2.38 2.09 0.66

    22.0 30 2.90 2.16 0.48 2.79 2.12 0.53 2.68 2.08 0.57 2.74 2.10 0.59 2.67 2.08 0.61 2.56 2.04 0.66

    24.0 32 3.01 2.11 0.48 2.90 2.07 0.53 2.79 2.04 0.57 2.86 2.06 0.59 2.79 2.04 0.62 2.67 2.00 0.66

    AFR 9

    INDOOROUTDOOR TEMPERATURE

    (CDB/CWB)

    EDB 2/1 7/6 11/10

    C TC PI TC PI TC PI

    15.0 1.31 0.36 2.59 0.60 2.81 0.62

    20.0 1.26 0.36 2.50 0.61 2.73 0.63

    22.0 1.24 0.37 2.47 0.62 2.69 0.64

    24.0 1.22 0.37 2.43 0.62 2.66 0.64

    25.0 1.21 0.37 2.41 0.62 2.64 0.64

    27.0 1.19 0.38 2.38 0.63 2.61 0.65

    Symbols: Notes:

    AFR : Airflow rate (m/min.) 1. shows nominal (rated) capacities and power input.2. TC, PI and SHC must be calculated by interpolation using the figures in the

    above tables. (Figures out of the tables should not be used for calculation.)3. Capacities are based on the following conditions.

    Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

    BF : Bypass factor

    EWB : Entering wet bulb temp. (C)

    EDB : Entering dry bulb temp. (C)

    TC : Total capacity (kW)

    SHC : Sensible heat capacity (kW)

    PI : Power input (kW)

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    13/80

    EDVN041518 Capacity Tables

    Split Type Air Conditioners FTXM-H Series 11

    FTXM35HVMV + RXM35HVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)

    Cooling

    Heating

    3D096250B

    AFR 9.7

    BF 0.13

    INDOOR OUTDOOR TEMPERATURE (CDB)

    EWB EDB 20 25 30 32 35 40

    C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14.0 20 3.30 2.47 0.75 3.28 2.47 0.84 3.13 2.39 0.91 3.19 2.42 0.94 3.10 2.37 0.98 2.93 2.29 1.05

    16.0 22 3.60 2.50 0.77 3.44 2.43 0.84 3.28 2.35 0.92 3.36 2.39 0.94 3.26 2.34 0.98 3.10 2.27 1.06

    18.0 25 3.75 2.62 0.77 3.59 2.55 0.85 3.44 2.48 0.92 3.52 2.52 0.94 3.42 2.47 0.99 3.26 2.40 1.06

    19.0 27 3.83 2.76 0.77 3.67 2.69 0.85 3.51 2.63 0.92 3.60 2.66 0.95 3.50 2.62 0.99 3.34 2.56 1.06

    22.0 30 4.06 2.66 0.78 3.90 2.60 0.85 3.75 2.55 0.93 3.84 2.58 0.95 3.74 2.54 1.00 3.58 2.48 1.07

    24.0 32 4.21 2.59 0.79 4.06 2.54 0.86 3.90 2.49 0.93 4.00 2.52 0.96 3.90 2.49 1.00 3.74 2.43 1.07

    AFR 9.9

    INDOOROUTDOOR TEMPERATURE

    (CDB/CWB)

    EDB 2/1 7/6 11/10

    C TC PI TC PI TC PI

    15.0 1.43 0.39 3.62 0.97 3.94 1.00

    20.0 1.37 0.40 3.50 0.99 3.82 1.02

    22.0 1.35 0.41 3.45 1.00 3.77 1.03

    24.0 1.33 0.41 3.40 1.01 3.72 1.04

    25.0 1.32 0.41 3.38 1.01 3.70 1.04

    27.0 1.30 0.42 3.33 1.02 3.65 1.05

    Symbols: Notes:

    AFR : Airflow rate (m/min.) 1. shows nominal (rated) capacities and power input.2. TC, PI and SHC must be calculated by interpolation using the figures in the

    above tables. (Figures out of the tables should not be used for calculation.)3. Capacities are based on the following conditions.

    Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

    BF : Bypass factor

    EWB : Entering wet bulb temp. (C)

    EDB : Entering dry bulb temp. (C)

    TC : Total capacity (kW)

    SHC : Sensible heat capacity (kW)

    PI : Power input (kW)

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    14/80

    Capacity Tables EDVN041518

    12 Split Type Air Conditioners FTXM-H Series

    7.2 Capacity correction factor by the length of refrigerant piping (Reference)The cooling capacity and the heating capacity of the unit have to be corrected in accordance with the length

    of refrigerant piping the distance between the indoor unit and the outdoor unit.

    Note: The graph shows the factor when additional refrigerant of the proper quantity is charged.

    Capacitycorrectionfactor

    100

    5 10 15

    90

    80

    (R-32)

    Piping length

    (%)

    (m)

    Range of the

    refrigerantadditional

    charge

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    15/80

    EDVN041518 Operation Limit

    Split Type Air Conditioners FTXM-H Series 13

    8. Operation Limit

    RXM20/25/35HVMV

    Cooling Heating

    50

    2546

    2040

    15

    30

    Pull-downperiod

    Continuousoperation

    Outdoortemp.(CDB)

    Outdoortemp.(CWB)

    10

    20

    5

    1

    010

    -5(-5CDB)

    0

    3023 10 202014 302810

    Indoor temp. (CDB)Indoor temp. (CWB)Notes:

    The graphs are basedon the following conditions. Equivalent piping length Level difference Airflow rate

    Continuous

    operation

    7.5m0m

    High3D095152A

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    16/80

    Sound Level EDVN041518

    14 Split Type Air Conditioners FTXM-H Series

    9. Sound Level

    9.1 Measuring Location

    Notes: 1. Operation sound is measured in an anechoic chamber.

    2. The data are based on the conditions shown in the table below.

    Indoor Unit Outdoor Unit

    1 m

    0.8m

    MICROPHONE

    1 m

    MICROPHONE

    Cooling Heating Piping Length

    Indoor ; 27CDB / 19CWB

    Outdoor ; 35CDB

    Indoor ; 20CDB

    Outdoor ; 7CDB / 6CWB

    5 m

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    17/80

    EDVN041518 Sound Level

    Split Type Air Conditioners FTXM-H Series 15

    9.2 Indoor Unit

    FTXM20HVMV

    FTXM25HVMV

    FTXM35HVMV

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OCTAVEBANDSOUNDPRESSURE

    LEVEL

    dB(0dB=0.0002

    bar)

    70

    60

    20

    30

    50

    40

    63 125

    OCTAVE BAND CENTER FREQUENCY (Hz)

    250 500 1000 2000 4000 8000

    OVER ALL (dB )

    SCALE

    A( B.G.N IS ALREADY RECTIFIED )

    70

    60

    20

    30

    50

    40

    63

    OCTAVE BAND CENTER FREQUENCY (Hz)

    125 250 500 1000 2000 4000 8000

    OCTAVEBANDSOUNDPRESSURE

    LEVEL

    dB(0dB=0.0002

    bar)

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OVER ALL (dB )

    SCALE

    A( B.G.N IS ALREADY RECTIFIED )

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    COOLING HEATING

    220-240/220-230V 50/60Hz 220-240/220-230V 50/60Hz

    STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE

    50/60Hz220-240/220-230V

    (H)

    39 39 29

    50/60Hz220-240/220-230V

    (L)

    50/60Hz220-240/220-230V

    (H)

    50/60Hz220-240/220-230V

    (L)

    28

    50/60Hz 220-240/220-230V (H) 50/60Hz 220-240/220-230V (H)

    50/60Hz 220-240/220-230V (L)50/60Hz 220-240/220-230V (L)

    HeatingCooling

    3D096262

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    70

    60

    20

    30

    50

    40

    63 125

    OCTAVE BAND CENTER FREQUENCY (Hz)

    250 500 1000 2000 4000 8000

    OVER ALL (dB )

    SCALE

    A

    ( B.G.N IS ALREADY RECTIFIED )

    70

    60

    20

    30

    50

    40

    63

    OCTAVE BAND CENTER FREQUENCY (Hz)

    125 250 500 1000 2000 4000 8000

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    COOLING HEATING

    220-240/220-230V 50/60Hz

    STANDARD EXTERNAL STATIC PRESSURE

    50/60Hz 220-240/220-230V (H)

    50/60Hz 220-240/220-230V (L)

    Cooling

    40

    50/60Hz220-240/220-230V

    (H)

    29

    50/60Hz220-240/220-230V

    (L)

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OVER ALL (dB )

    SCALE

    A

    ( B.G.N IS ALREADY RECTIFIED )

    220-240/220-230V 50/60Hz

    STANDARD EXTERNAL STATIC PRESSURE

    50/60Hz 220-240/220-230V (H)

    50/60Hz 220-240/220-230V (L)

    Heating

    40

    50/60Hz220-240/220-230V

    (H)

    30

    50/60Hz220-240/220-230V

    (L)

    3D096263A

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OCT

    AVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    70

    60

    20

    30

    50

    40

    63 125

    OCTAVE BAND CENTER FREQUENCY (Hz)

    250 500 1000 2000 4000 8000

    OVER ALL (dB )

    SCALE

    A

    ( B.G.N IS ALREADY RECTIFIED )

    70

    60

    20

    30

    50

    40

    63

    OCTAVE BAND CENTER FREQUENCY (Hz)

    125 250 500 1000 2000 4000 8000

    OCT

    AVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    COOLING HEATING

    220-240/220-230V 50/60Hz

    STANDARD EXTERNAL STATIC PRESSURE

    41 30

    50/60Hz 220-240/220-230V (H)

    50/60Hz 220-240/220-230V (L)

    Cooling

    50/60Hz220-240/220-230V

    (L)

    50/60Hz220-240/220-230V

    (H)

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OVER ALL (dB )

    SCALE

    A

    ( B.G.N IS ALREADY RECTIFIED )

    220-240/220-230V 50/60Hz

    STANDARD EXTERNAL STATIC PRESSURE

    41 31

    50/60Hz 220-240/220-230V (H)

    50/60Hz 220-240/220-230V (L)

    Heating

    50/60Hz220-240/220-230V

    (L)

    50/60Hz220-240/220-230V

    (H)

    3D096264A

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    18/80

    Sound Level EDVN041518

    16 Split Type Air Conditioners FTXM-H Series

    9.3 Outdoor Unit

    RXM20HVMV

    RXM25HVMV

    RXM35HVMV

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OCTAVEBANDSOUNDPRESSURE

    LEVEL

    dB(0dB=0.0002

    bar)

    70

    60

    20

    30

    50

    40

    63 125

    OCTAVE BAND CENTER FREQUENCY (Hz)

    250 500 1000 2000 4000 8000

    OVER ALL (dB )

    SCALE

    A( B.G.N IS ALREADY RECTIFIED )

    70

    60

    20

    30

    50

    40

    63

    OCTAVE BAND CENTER FREQUENCY (Hz)

    125 250 500 1000 2000 4000 8000

    OCTAVEBANDSOUNDPRESSURE

    LEVEL

    dB(0dB=0.0002

    bar)

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OVER ALL (dB )

    SCALE

    A( B.G.N IS ALREADY RECTIFIED )

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    COOLING HEATING

    220-240/220-230V 50/60Hz 220-240/220-230V 50/60Hz

    50/60Hz220-240/220-230V (H)

    50/60Hz220-240/220-230V (H)

    4848

    Cooling Heating

    3D096257

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    70

    60

    20

    30

    50

    40

    63 125

    OCTAVE BAND CENTER FREQUENCY (Hz)

    250 500 1000 2000 4000 8000

    OVER ALL (dB )

    SCALE

    A

    ( B.G.N IS ALREADY RECTIFIED )

    70

    60

    20

    30

    50

    40

    63

    OCTAVE BAND CENTER FREQUENCY (Hz)

    125 250 500 1000 2000 4000 8000

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OVER ALL (dB )

    SCALE

    A

    ( B.G.N IS ALREADY RECTIFIED )

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    COOLING HEATING

    220-240/220-230V 50/60Hz220-240/220-230V 50/60Hz

    50/60Hz220-240/220-230V (H)

    50/60Hz220-240/220-230V (H)

    4848

    Cooling Heating

    3D096258

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OCT

    AVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    70

    60

    20

    30

    50

    40

    63 125

    OCTAVE BAND CENTER FREQUENCY (Hz)

    250 500 1000 2000 4000 8000

    OVER ALL (dB )

    SCALE

    A

    ( B.G.N IS ALREADY RECTIFIED )

    70

    60

    20

    30

    50

    40

    63

    OCTAVE BAND CENTER FREQUENCY (Hz)

    125 250 500 1000 2000 4000 8000

    OCT

    AVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    POWER SOURCE

    JIS STANDARD

    OPERATING CONDITIONS

    OVER ALL (dB )

    SCALE

    A

    ( B.G.N IS ALREADY RECTIFIED )

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    NC-30

    NC-50

    NC-20

    NC-60

    NC-70

    NC-40

    COOLING HEATING

    220-240/220-230V 50/60Hz 220-240/220-230V 50/60Hz

    50/60Hz220-240/220-230V (H)

    50/60Hz220-240/220-230V (H)

    4848

    Cooling Heating

    3D096259

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    19/80

    EDVN041518 Electric Characteristics

    Split Type Air Conditioners FTXM-H Series 17

    10.Electric Characteristics

    3D096254A

    Indoor Unit Outdoor UnitPower Supply Compressor OFM IFM

    Hz - Volts Voltage Range MCA MFA RHz RLA W FLA W FLA

    FTXM20HVMV RXM20HVMV

    50 Hz - 220 VMax. 50 Hz, 264 VMin. 50 Hz, 198 V

    8.0 15 36

    2.4

    20

    0.22

    16

    0.19

    50 Hz - 230 V 2.3 0.21 0.1850 Hz - 240 V 2.2 0.20 0.17

    60 Hz - 220 V Max. 60 Hz, 253 VMin. 60 Hz, 198 V

    2.5 0.22 0.19

    60 Hz - 230 V 2.4 0.21 0.18

    FTXM25HVMV RXM25HVMV

    50 Hz - 220 VMax. 50 Hz, 264 VMin. 50 Hz, 198 V

    8.0 15 48

    2.6

    20

    0.22

    16

    0.19

    50 Hz - 230 V 2.5 0.21 0.18

    50 Hz - 240 V 2.4 0.20 0.17

    60 Hz - 220 V Max. 60 Hz, 253 VMin. 60 Hz, 198 V

    2.7 0.22 0.19

    60 Hz - 230 V 2.6 0.21 0.18

    FTXM35HVMV RXM35HVMV

    50 Hz - 220 VMax. 50 Hz, 264 VMin. 50 Hz, 198 V

    8.0 15 74

    4.2

    20

    0.22

    16

    0.27

    50 Hz - 230 V 4.0 0.21 0.26

    50 Hz - 240 V 3.8 0.20 0.24

    60 Hz - 220 V Max. 60 Hz, 253 VMin. 60 Hz, 198 V

    4.3 0.22 0.2760 Hz - 230 V 4.1 0.21 0.26

    Symbols: Notes:

    MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.Indoor temp. 27CDB / 19CWBOutdoor temp. 35CDB.

    2. Maximum allowable voltage variation between phases is 2%.3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. Be sure to install an earth leak detector.

    (This unit uses an inverter, which means that an earth leakdetector capable of handling high harmonics must be used inorder to prevent malfunctioning of the earth leak detector.)

    MFA : Max. fuse amps (A)

    RHz : Rated operating frequency (Hz)

    RLA : Rated load amps (A)

    OFM : Outdoor fan motor

    IFM : Indoor fan motor

    W : Fan motor rated output (W)

    FLA : Full load amps (A)

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    20/80

    Installation Manual EDVN041518

    18 Split Type Air Conditioners FTXM-H Series

    11.Installation Manual

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    21/80

    EDVN041518 Installation Manual

    Split Type Air Conditioners FTXM-H Series 19

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    22/80

    Installation Manual EDVN041518

    20 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    23/80

    EDVN041518 Installation Manual

    Split Type Air Conditioners FTXM-H Series 21

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    24/80

    Installation Manual EDVN041518

    22 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    25/80

    EDVN041518 Installation Manual

    Split Type Air Conditioners FTXM-H Series 23

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    26/80

    Installation Manual EDVN041518

    24 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    27/80

    EDVN041518 Installation Manual

    Split Type Air Conditioners FTXM-H Series 25

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    28/80

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    29/80

    EDVN041518 Installation Manual

    Split Type Air Conditioners FTXM-H Series 27

    3P383016-9A

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    30/80

    Operation Manual EDVN041518

    28 Split Type Air Conditioners FTXM-H Series

    12.Operation Manual

    12.1 English

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    31/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 29

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    32/80

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    33/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 31

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    34/80

    Operation Manual EDVN041518

    32 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    35/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 33

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    36/80

    Operation Manual EDVN041518

    34 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    37/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 35

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    38/80

    Operation Manual EDVN041518

    36 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    39/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 37

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    40/80

    Operation Manual EDVN041518

    38 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    41/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 39

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    42/80

    Operation Manual EDVN041518

    40 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    43/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 41

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    44/80

    Operation Manual EDVN041518

    42 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    45/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 43

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    46/80

    Operation Manual EDVN041518

    44 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    47/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 45

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    48/80

    Operation Manual EDVN041518

    46 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    49/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 47

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    50/80

    Operation Manual EDVN041518

    48 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    51/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 49

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    52/80

    Operation Manual EDVN041518

    50 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    53/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 51

    EN_3P383015-6A

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    54/80

    Operation Manual EDVN041518

    52 Split Type Air Conditioners FTXM-H Series

    12.2 Vietnamese

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    55/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 53

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    56/80

    Operation Manual EDVN041518

    54 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    57/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 55

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    58/80

    Operation Manual EDVN041518

    56 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    59/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 57

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    60/80

    Operation Manual EDVN041518

    58 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    61/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 59

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    62/80

    Operation Manual EDVN041518

    60 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    63/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 61

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    64/80

    Operation Manual EDVN041518

    62 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    65/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 63

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    66/80

    Operation Manual EDVN041518

    64 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    67/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 65

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    68/80

    Operation Manual EDVN041518

    66 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    69/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 67

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    70/80

    Operation Manual EDVN041518

    68 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    71/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 69

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    72/80

    Operation Manual EDVN041518

    70 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    73/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 71

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    74/80

    Operation Manual EDVN041518

    72 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    75/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 73

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    76/80

    Operation Manual EDVN041518

    74 Split Type Air Conditioners FTXM-H Series

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    77/80

    EDVN041518 Operation Manual

    Split Type Air Conditioners FTXM-H Series 75

    VN_3P383015-6A

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    78/80

    Optional Accessories EDVN041518

    76 Split Type Air Conditioners FTXM-H Series

    13.Optional Accessories

    13.1 Option List

    13.1.1 Indoor Unit

    13.1.2 Outdoor Unit

    Option Name Model Name

    1 Titanium apatite photocatalytic air-purifying filter (without frame) KAF970A462 Remote controller loss prevention with chain KKF917A4

    Option Name Model Name

    1 Air direction adjustment grille KPW937B4

    2 Drain plug KKP937A4

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    79/80

  • 7/26/2019 Edvn041518 - Ftxm Hvmv - r32

    80/80

    Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.

    Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

    Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or

    contractor to install those parts and accessories. Use of unauthorised parts and accessories or

    improper installation of parts and accessories can result in water or refrigerant leakage, electrical

    shock, fire or explosion.

    Read the user's manual carefully before using this product. The user's manual provides important

    safety instructions and warnings. Be sure to follow these instructions and warnings.

    1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.