Split Type Air Conditioners FTXM-H Series 1
Split Type
Air Conditioners
FTXM H Series
1. Power Supply ..........................................................................................2
2. Functions.................................................................................................3
3. Specifications..........................................................................................44. Dimensions .............................................................................................6
4.1 Indoor Unit................................................................................................6
4.2 Outdoor Unit .............................................................................................6
5. Wiring Diagrams......................................................................................75.1 Indoor Unit................................................................................................7
5.2 Outdoor Unit .............................................................................................7
6. Piping Diagrams......................................................................................86.1 Indoor Unit................................................................................................8
6.2 Outdoor Unit .............................................................................................8
7. Capacity Tables ......................................................................................97.1 Heat Pump ...............................................................................................9
7.2 Capacity correction factor by the length of refrigerant piping
(Reference) ............................................................................................12
8. Operation Limit......................................................................................13
9. Sound Level ..........................................................................................149.1 Measuring Location................................................................................14
9.2 Indoor Unit..............................................................................................15
9.3 Outdoor Unit ...........................................................................................16
10.Electric Characteristics..........................................................................17
11.Installation Manual ................................................................................1812.Operation Manual..................................................................................28
12.1 English....................................................................................................28
12.2 Vietnamese ............................................................................................52
13.Optional Accessories ............................................................................7613.1 Option List ..............................................................................................76
Heat Pump
FTXM20HVMV
FTXM25HVMV
FTXM35HVMV
RXM20HVMV
RXM25HVMV
RXM35HVMV
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
4/80
Power Supply EDVN041518
2 Split Type Air Conditioners FTXM-H Series
1. Power Supply
Note: Power Supply Intake; Outdoor Unit
Indoor Unit Outdoor Unit Power Supply
FTXM20HVMV RXM20HVMV1 phase, 220 - 230 - 240 V, 50 Hz1 phase, 220 - 230 V, 60 Hz
FTXM25HVMV RXM25HVMV
FTXM35HVMV RXM35HVMV
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
5/80
EDVN041518 Functions
Split Type Air Conditioners FTXM-H Series 3
2. Functions
Category Functions
FTXM
20/25/35HVMV
RXM20/25/35HVMV
Category Functions
FTXM
20/25/35HVMV
RXM20/25/35HVMV
Basic Function Inverter (with inverter power control) Health & Clean Air-purifying filter
Operation limit for cooling (CDB)10
~ 46Photocatalytic deodorising filter
Air-purifying filter with photocatalyticdeodorising function
Operation limit for heating (CWB)
1~ 20
Titanium apatite photocatalytic air-purifyingfilter (option)
PAM control
Standby electricity saving Air filter (prefilter)
Compressor Oval scroll compressor Wipe-clean flat panel
Swing compressor Washable grille
Rotary compressor MOULD PROOF operation
Reluctance DC motor Heating dry operation
ComfortableAirflow
Power-airflow flap Good-sleep cooling operation
Power-airflow dual flaps Timer WEEKLY TIMER operation
Power-airflow diffuser 24-hour ON/OFF TIMER
Wide-angle louvres NIGHT SET mode
Auto-swing (up and down) Worry Free(Reliability &Durability)
Auto-restart (after power failure)
Auto-swing (right and left) Self-diagnosis (R/C, LED)
3-D airflow Wiring error check function
COMFORT AIRFLOW operation Anti-corrosion treatment of outdoor heatexchanger
ComfortControl
Auto fan speed
Indoor unit quiet operation Flexibility Multi-split / split type compatible indoor unit
NIGHT QUIET mode (automatic) Flexible power supply correspondence
OUTDOOR UNIT QUIET operation (manual) High ceiling application INTELLIGENT EYE operation Chargeless 10 m
2-area INTELLIGENT EYE operation Either side drain (right or left)
Operation Automatic operation Power selection
Programme dry operation Facility setting (cooling at low outdoortemperature)
Fan only
LifestyleConvenience
New POWERFUL operation (non-inverter) RemoteControl
5-room centralised controller
Inverter POWERFUL operation Remote control adaptor(normal open pulse contact)
Priority-room setting
COOL / HEAT mode lock Remote control adaptor(normal open contact)
HOME LEAVE operation
ECONO operation DIII-NET compatible (adaptor)
Indoor unit ON/OFFbutton
Wireless LAN connection (option) Signal receiving sign Remote
ControllerWireless
R/C with back light Wired
Temperature display
Note: : Available
: Not available
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
6/80
Specifications EDVN041518
4 Split Type Air Conditioners FTXM-H Series
3. Specifications50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Note: The data are based on the conditions shown in the table below.
Model
Indoor Unit FTXM20HVMV FTXM25HVMV
Outdoor UnitRXM20HVMV RXM25HVMV
Cooling Heating Cooling Heating
Capacity
Rated (Min. ~ Max.)
kW 2.0 (1.0 ~ 2.6) 2.0 (1.0 ~ 2.6) 2.5 (1.0 ~ 3.4) 2.5 (1.0 ~ 3.4)
Btu/h 6,800 (3,400 ~ 8,850) 6,800 (3,400 ~ 8,850) 8,500 (3,400 ~ 11,600) 8,500 (3,400 ~ 11,600)
kcal/h 1,720 (860 ~ 2,240) 1,720 (860 ~ 2,240) 2,150 (860 ~ 2,920) 2,150 (860 ~ 2,920)
Moisture Removal L/h 1.2 1.2
Running Current (Rated) A 2.8 2.8 3.0 3.0
Power ConsumptionRated (Min. ~ Max.) W 454 (225 ~ 645) 454 (225 ~ 645) 610 (225 ~ 1,070) 610 (225 ~ 1,070)
Power Factor (Rated) % 73.7 73.7 92.4 92.4
COP (Rated) W/W 4.40 4.40 4.10 4.10
PipingConnections
Liquid mm 6.4 6.4
Gas mm 9.5 9.5
Drain mm 16.0 16.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 15 15
Max. Interunit Height Difference m 12 12
Chargeless m 10 10
Amount of Additional Charge ofRefrigerant g/m 20 20
Indoor Unit FTXM20HVMV FTXM25HVMV
Front Panel Colour Shiny Pure White Shiny Pure White
Airflow Rate
H
m/min(cfm)
9.0 (318) 9.0 (318) 9.0 (318) 9.0 (318)
M 6.7 (237) 7.6 (268) 6.7 (237) 7.6 (268)
L 4.4 (155) 6.4 (226) 4.4 (155) 6.4 (226)
SL 3.5 (124) 5.4 (191) 3.5 (124) 5.4 (191)
Fan
Type Cross Flow Fan Cross Flow Fan
Motor Output W 16 16
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof
Running Current (Rated) A 0.19 - 0.18 - 0.17 /0.19 - 0.180.19 - 0.18 - 0.17 /
0.19 - 0.180.19 - 0.18 - 0.17 /
0.19 - 0.180.19 - 0.18 - 0.17 /
0.19 - 0.18
Power Consumption (Rated) W 39 39 39 39
Power Factor (Rated) % 93.3 - 94.2 - 95.6 /93.3 - 94.293.3 - 94.2 - 95.6 /
93.3 - 94.293.3 - 94.2 - 95.6 /
93.3 - 94.293.3 - 94.2 - 95.6 /
93.3 - 94.2
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H W D) mm 283 770 203 283 770 203
Packaged Dimensions (H W D) mm 263 840 344 263 840 344
Weight (Mass) kg 8 8
Gross Weight (Gross Mass) kg 10 10
Sound PressureLevel H / M / L / SL dB(A) 39 / 34 / 28 / 25 39 / 34 / 29 / 27 40 / 35 / 29 / 25 40 / 35 / 30 / 27
Outdoor Unit RXM20HVMV RXM25HVMV
Casing Colour Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 1YC22DXD 1YC22DXD
Motor Output W 395 551
Refrigerant OilType FW68DA FW68DA
Charge L 0.275 0.275
RefrigerantType R-32 R-32
Charge kg 0.75 0.75
Airflow Rate H m/min(cfm)
27.1 (957) 27.1 (957) 27.1 (957) 27.1 (957)
Fan
Type Propeller Propeller
Motor Output W 20 20Running Current (Rated) A 2.61 2.61 2.81 2.81
Power Consumption (Rated) W 415 415 571 571
Power Factor (Rated) % 72.3 72.3 92.4 92.4
Starting Current A 2.8 3.0
Dimensions (H W D) mm 550 658 275 550 658 275
Packaged Dimensions (H W D) mm 616 788 359 616 788 359
Weight (Mass) kg 27 27
Gross Weight (Gross Mass) kg 31 31
Sound PressureLevel H dB(A) 48 48 48 48
Drawing No. 3D096417 3D096418
Conversion Formulae
kcal/h = kW 860Btu/h = kW 3412
cfm = m/min 35.3
Cooling Heating Piping LengthIndoor ; 27CDB / 19CWB
Outdoor ; 35CDB / 24CWBIndoor ; 20CDB
Outdoor ; 7CDB / 6CWB 7.5 m
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
7/80
EDVN041518 Specifications
Split Type Air Conditioners FTXM-H Series 5
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Note: The data are based on the conditions shown in the table below.
Model
Indoor Unit FTXM35HVMV
Outdoor UnitRXM35HVMV
Cooling Heating
CapacityRated (Min. ~ Max.)
kW 3.5 (1.2 ~ 3.8) 3.5 (1.2 ~ 3.8)
Btu/h 11,900 (4,100 ~ 12,950) 11,900 (4,100 ~ 12,950)
kcal/h 3,010 (1,030 ~ 3,270) 3,010 (1,030 ~ 3,270)
Moisture Removal L/h 1.2
Running Current (Rated) A 4.6 4.6Power ConsumptionRated (Min. ~ Max.) W 990 (250 ~ 1,320) 990 (250 ~ 1,320)
Power Factor (Rated) % 97.8 97.8
COP (Rated) W/W 3.54 3.54
PipingConnections
Liquid mm 6.4
Gas mm 9.5
Drain mm 16.0
Heat Insulation Both Liquid and Gas Pipes
Max. Interunit Piping Length m 15
Max. Interunit Height Difference m 12
Chargeless m 10
Amount of Additional Charge ofRefrigerant g/m 20
Indoor Unit FTXM35HVMV
Front Panel Colour Shiny Pure White
Airflow Rate
H
m/min(cfm)
9.7 (342) 9.9 (349)
M 7.1 (251) 7.9 (279)L 4.6 (162) 5.9 (208)
SL 3.6 (127) 4.8 (169)
Fan
Type Cross Flow Fan
Motor Output W 16
Speed Steps 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards
Air Filter Removable, Washable, Mildew Proof
Running Current (Rated) A 0.27 - 0.26 - 0.24 / 0.27 - 0.26 0.27 - 0.26 - 0.24 / 0.27 - 0.26
Power Consumption (Rated) W 57 57
Power Factor (Rated) % 96.0 - 95.3 - 99.0 / 96.0 - 95.3 96.0 - 95.3 - 99.0 / 96.0 - 95.3
Temperature Control Microcomputer Control
Dimensions (H W D) mm 283 770 203
Packaged Dimensions (H W D) mm 263 840 344
Weight (Mass) kg 8
Gross Weight (Gross Mass) kg 10
Sound Pressure
LevelH / M / L / SL dB(A) 41 / 36 / 30 / 26 41 / 36 / 31 / 28
Outdoor Unit RXM35HVMV
Casing Colour Ivory White
Compressor
Type Hermetically Sealed Swing Type
Model 1YC22DXD
Motor Output W 913
Refrigerant OilType FW68DA
Charge L 0.275
RefrigerantType R-32
Charge kg 0.75
Airflow Rate H m/min(cfm) 27.1 (957) 27.1 (957)
FanType Propeller
Motor Output W 20
Running Current (Rated) A 4.33 4.33
Power Consumption (Rated) W 933 933
Power Factor (Rated) % 96.2 96.2
Starting Current A 4.6Dimensions (H W D) mm 550 658 275
Packaged Dimensions (H W D) mm 616 788 359
Weight (Mass) kg 27
Gross Weight (Gross Mass) kg 31
Sound PressureLevel H dB(A) 48 48
Drawing No. 3D096419
Conversion Formulae
kcal/h = kW 860Btu/h = kW 3412
cfm = m/min 35.3
Cooling Heating Piping LengthIndoor ; 27CDB / 19CWB
Outdoor ; 35CDB / 24CWBIndoor ; 20CDB
Outdoor ; 7CDB / 6CWB 7.5 m
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
8/80
Dimensions EDVN041518
6 Split Type Air Conditioners FTXM-H Series
4. Dimensions
4.1 Indoor Unit
FTXM20/25/35HVMV
4.2 Outdoor Unit
RXM20/25/35HVMV
AIRFLOW (INDOOR)
THE MARK () SHOWS PIPING DIRECTION
REAR770
RIGHT
30MIN.
LEFT
50MIN. 50MIN.205
REQUIRED SPACE203
SIGNAL RECEIVER 283
OPERATION LAMP
TIMER LAMP
INDOOR UNIT ON/OFF SWITCHBOTTOM FLAPS
GAS PIPE 9.5 CuT
LIQUID PIPE 6.4 CuT
770SIGNAL TRANSMITTER
10154916
6
BLADE ANGLE1858
UP/DOWN (AUTOMATIC)172
HEATINGCOOLING DRY 283
41.3
55 5
163
4545 45 54.5 54
41.3
FAN RIGHT/LEFT (MANUAL) WALL HOLE FOR EMBEDDED PIPING65 HOLE
WALL HOLE65 HOLE
5STANDARD LOCATIONS OF WALL HOLES
45WIRELESS REMOTE CONTROLLER 4545(ARC433A87)
FRONT PANEL FIXING SCREWS(INSIDE)
ROOM TEMP. THERMISTOR(INSIDE)
MODEL NAMEPLATE
(THE LENGTH OF PIPE OUTSIDE
THE UNIT: ABOUT 350)
(THE LENGTH OF PIPE OUTSIDETHE UNIT: ABOUT 400)
DRAIN HOSE(CONNECTING PARTI.D. 14O.D. 16
THE HOSE LENGTH OF OUTSIDETHE UNIT IS ABOUT 450)
MANUFACTURER'S
LABEL
TERMINAL BLOCKWITH EARTHTERMINAL(INSIDE)
(SPACE FORMAINTENANCE)
(SPACE FORMAINTENANCE)
(SPACEFOR
PERFORMANCE)
INCLUDINGMOUNTING PLATE
3D093418
DRAIN OUTLET WALL HEIGHT ON AIR OUTLET SIDE= LESS THAN 1200
MINIMUM SPACE FOR AIR PASSAGE4-HOLES FOR ANCHOR BOLTS(M8 OR M10) 1
50
100
150
470 96
11379
40
300
50 5050
100
297
50
BRAND NAME LABELHANDLE MANUFACTURE'S LABEL
13.5 8 OUTDOOR AIR THERMISTOR50275 12 658
(6.4CuT)
550
168
108
155 GAS STOP VALVE(9.5CuT)
INDICATION LABEL (INDONESIA)
FOR INDONESIA MODEL ONLY
3D089153C
(I.D15.9 HOSE FOR CONNECTIONWITH DRAIN JOINT)
WIRINGINLET
SERVICEPORT
IN CASE OF REMOVINGSTOP VALVE COVER
LIQUIDSTOP VALVE
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
9/80
EDVN041518 Wiring Diagrams
Split Type Air Conditioners FTXM-H Series 7
5. Wiring Diagrams
5.1 Indoor Unit
FTXM20/25/35HVMV
5.2 Outdoor Unit
RXM20/25/35HVMV
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
10/80
Piping Diagrams EDVN041518
8 Split Type Air Conditioners FTXM-H Series
6. Piping Diagrams
6.1 Indoor Unit
FTXM20/25/35HVMV
6.2 Outdoor Unit
RXM20/25/35HVMV
INDOOR UNIT
HEAT EXCHANGER7.0CuT
4.8CuT
7.0CuT
7.0CuT
7.0CuT
CROSS FLOW FANFIELD PIPING
(6.4CuT) M
FAN MOTOR
9.5CuTFIELD PIPING
(9.5CuT)
REFRIGERANT FLOWCOOLINGHEATING
THERMISTOR
ON HEAT EXCH.
4D096261
OUTDOOR UNIT
HEAT EXCHANGER7.0CuT
7.0CuT
9.5
Cu
T
6.4CuT6.4CuT 6.4CuT 6.4CuT
M
PROPELLER FAN
ON: HEATING9.5CuT 9.5CuT
STRAINER
6.4CuT
MUFFLER4.8CuT
9.5CuT FIELD PIPING(6.4CuT)
REFRIGERANT FLOW
COMPRESSOR ACCUMULATOR 9.5CuT FIELD PIPINGCOOLING
HEATING (9.5CuT)GAS STOPVALVE
LIQUID STOP
VALVE
MOTOR OPERATED
VALVE
MUFFLER
WITHFILTER
HEATEXCHANGER
THERMISTOR
FAN
MOTOR
4-WAYVALVE
DISCHARGE PIPE
THERMISTOR
OUTDOOR TEMPERATURETHERMISTOR
3D096247
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
11/80
EDVN041518 Capacity Tables
Split Type Air Conditioners FTXM-H Series 9
7. Capacity Tables
7.1 Heat Pump
FTXM20HVMV + RXM20HVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
Heating
3D096248A
AFR 9
BF 0.13
INDOOR OUTDOOR TEMPERATURE (CDB)
EWB EDB 20 25 30 32 35 40
C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 1.97 1.77 0.35 1.88 1.73 0.38 1.79 1.69 0.42 1.83 1.71 0.43 1.77 1.69 0.45 1.68 1.64 0.48
16.0 22 2.05 1.75 0.35 1.97 1.71 0.39 1.88 1.67 0.42 1.92 1.69 0.43 1.86 1.66 0.45 1.77 1.63 0.48
18.0 25 2.14 1.87 0.35 2.05 1.84 0.39 1.96 1.80 0.42 2.01 1.82 0.43 1.95 1.80 0.45 1.86 1.76 0.49
19.0 27 2.19 2.01 0.36 2.10 1.98 0.39 2.01 1.95 0.42 2.06 1.96 0.43 2.00 1.94 0.45 1.91 1.91 0.49
22.0 30 2.32 1.96 0.36 2.23 1.93 0.39 2.14 1.90 0.43 2.19 1.92 0.44 2.14 1.90 0.46 2.05 1.87 0.49
24.0 32 2.41 1.92 0.36 2.32 1.89 0.39 2.23 1.87 0.43 2.29 1.88 0.44 2.23 1.87 0.46 2.14 1.84 0.49
AFR 9
INDOOROUTDOOR TEMPERATURE
(CDB/CWB)
EDB 2/1 7/6 11/10
C TC PI TC PI TC PI
15.0 1.31 0.36 2.07 0.44 2.25 0.46
20.0 1.26 0.36 2.00 0.45 2.18 0.47
22.0 1.24 0.37 1.97 0.46 2.15 0.47
24.0 1.22 0.37 1.94 0.46 2.13 0.4825.0 1.21 0.37 1.93 0.46 2.11 0.48
27.0 1.19 0.38 1.90 0.47 2.08 0.48
Symbols: Notes:
AFR : Airflow rate (m/min.) 1. shows nominal (rated) capacities and power input.2. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m
BF : Bypass factor
EWB : Entering wet bulb temp. (C)
EDB : Entering dry bulb temp. (C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
12/80
Capacity Tables EDVN041518
10 Split Type Air Conditioners FTXM-H Series
FTXM25HVMV + RXM25HVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
Heating
3D096249A
AFR 9
BF 0.13
INDOOR OUTDOOR TEMPERATURE (CDB)
EWB EDB 20 25 30 32 35 40
C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.46 2.00 0.47 2.35 1.95 0.52 2.23 1.90 0.56 2.28 1.92 0.58 2.21 1.89 0.60 2.10 1.83 0.65
16.0 22 2.57 1.97 0.47 2.46 1.92 0.52 2.34 1.87 0.56 2.40 1.89 0.58 2.33 1.86 0.61 2.21 1.81 0.65
18.0 25 2.68 2.09 0.48 2.57 2.04 0.52 2.46 2.00 0.57 2.51 2.02 0.58 2.44 1.99 0.61 2.33 1.94 0.66
19.0 27 2.73 2.23 0.48 2.62 2.18 0.52 2.51 2.14 0.57 2.57 2.16 0.58 2.50 2.13 0.61 2.38 2.09 0.66
22.0 30 2.90 2.16 0.48 2.79 2.12 0.53 2.68 2.08 0.57 2.74 2.10 0.59 2.67 2.08 0.61 2.56 2.04 0.66
24.0 32 3.01 2.11 0.48 2.90 2.07 0.53 2.79 2.04 0.57 2.86 2.06 0.59 2.79 2.04 0.62 2.67 2.00 0.66
AFR 9
INDOOROUTDOOR TEMPERATURE
(CDB/CWB)
EDB 2/1 7/6 11/10
C TC PI TC PI TC PI
15.0 1.31 0.36 2.59 0.60 2.81 0.62
20.0 1.26 0.36 2.50 0.61 2.73 0.63
22.0 1.24 0.37 2.47 0.62 2.69 0.64
24.0 1.22 0.37 2.43 0.62 2.66 0.64
25.0 1.21 0.37 2.41 0.62 2.64 0.64
27.0 1.19 0.38 2.38 0.63 2.61 0.65
Symbols: Notes:
AFR : Airflow rate (m/min.) 1. shows nominal (rated) capacities and power input.2. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m
BF : Bypass factor
EWB : Entering wet bulb temp. (C)
EDB : Entering dry bulb temp. (C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
13/80
EDVN041518 Capacity Tables
Split Type Air Conditioners FTXM-H Series 11
FTXM35HVMV + RXM35HVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
Heating
3D096250B
AFR 9.7
BF 0.13
INDOOR OUTDOOR TEMPERATURE (CDB)
EWB EDB 20 25 30 32 35 40
C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 3.30 2.47 0.75 3.28 2.47 0.84 3.13 2.39 0.91 3.19 2.42 0.94 3.10 2.37 0.98 2.93 2.29 1.05
16.0 22 3.60 2.50 0.77 3.44 2.43 0.84 3.28 2.35 0.92 3.36 2.39 0.94 3.26 2.34 0.98 3.10 2.27 1.06
18.0 25 3.75 2.62 0.77 3.59 2.55 0.85 3.44 2.48 0.92 3.52 2.52 0.94 3.42 2.47 0.99 3.26 2.40 1.06
19.0 27 3.83 2.76 0.77 3.67 2.69 0.85 3.51 2.63 0.92 3.60 2.66 0.95 3.50 2.62 0.99 3.34 2.56 1.06
22.0 30 4.06 2.66 0.78 3.90 2.60 0.85 3.75 2.55 0.93 3.84 2.58 0.95 3.74 2.54 1.00 3.58 2.48 1.07
24.0 32 4.21 2.59 0.79 4.06 2.54 0.86 3.90 2.49 0.93 4.00 2.52 0.96 3.90 2.49 1.00 3.74 2.43 1.07
AFR 9.9
INDOOROUTDOOR TEMPERATURE
(CDB/CWB)
EDB 2/1 7/6 11/10
C TC PI TC PI TC PI
15.0 1.43 0.39 3.62 0.97 3.94 1.00
20.0 1.37 0.40 3.50 0.99 3.82 1.02
22.0 1.35 0.41 3.45 1.00 3.77 1.03
24.0 1.33 0.41 3.40 1.01 3.72 1.04
25.0 1.32 0.41 3.38 1.01 3.70 1.04
27.0 1.30 0.42 3.33 1.02 3.65 1.05
Symbols: Notes:
AFR : Airflow rate (m/min.) 1. shows nominal (rated) capacities and power input.2. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m
BF : Bypass factor
EWB : Entering wet bulb temp. (C)
EDB : Entering dry bulb temp. (C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
14/80
Capacity Tables EDVN041518
12 Split Type Air Conditioners FTXM-H Series
7.2 Capacity correction factor by the length of refrigerant piping (Reference)The cooling capacity and the heating capacity of the unit have to be corrected in accordance with the length
of refrigerant piping the distance between the indoor unit and the outdoor unit.
Note: The graph shows the factor when additional refrigerant of the proper quantity is charged.
Capacitycorrectionfactor
100
5 10 15
90
80
(R-32)
Piping length
(%)
(m)
Range of the
refrigerantadditional
charge
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
15/80
EDVN041518 Operation Limit
Split Type Air Conditioners FTXM-H Series 13
8. Operation Limit
RXM20/25/35HVMV
Cooling Heating
50
2546
2040
15
30
Pull-downperiod
Continuousoperation
Outdoortemp.(CDB)
Outdoortemp.(CWB)
10
20
5
1
010
-5(-5CDB)
0
3023 10 202014 302810
Indoor temp. (CDB)Indoor temp. (CWB)Notes:
The graphs are basedon the following conditions. Equivalent piping length Level difference Airflow rate
Continuous
operation
7.5m0m
High3D095152A
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
16/80
Sound Level EDVN041518
14 Split Type Air Conditioners FTXM-H Series
9. Sound Level
9.1 Measuring Location
Notes: 1. Operation sound is measured in an anechoic chamber.
2. The data are based on the conditions shown in the table below.
Indoor Unit Outdoor Unit
1 m
0.8m
MICROPHONE
1 m
MICROPHONE
Cooling Heating Piping Length
Indoor ; 27CDB / 19CWB
Outdoor ; 35CDB
Indoor ; 20CDB
Outdoor ; 7CDB / 6CWB
5 m
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
17/80
EDVN041518 Sound Level
Split Type Air Conditioners FTXM-H Series 15
9.2 Indoor Unit
FTXM20HVMV
FTXM25HVMV
FTXM35HVMV
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVEBANDSOUNDPRESSURE
LEVEL
dB(0dB=0.0002
bar)
70
60
20
30
50
40
63 125
OCTAVE BAND CENTER FREQUENCY (Hz)
250 500 1000 2000 4000 8000
OVER ALL (dB )
SCALE
A( B.G.N IS ALREADY RECTIFIED )
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz)
125 250 500 1000 2000 4000 8000
OCTAVEBANDSOUNDPRESSURE
LEVEL
dB(0dB=0.0002
bar)
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL (dB )
SCALE
A( B.G.N IS ALREADY RECTIFIED )
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
COOLING HEATING
220-240/220-230V 50/60Hz 220-240/220-230V 50/60Hz
STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE
50/60Hz220-240/220-230V
(H)
39 39 29
50/60Hz220-240/220-230V
(L)
50/60Hz220-240/220-230V
(H)
50/60Hz220-240/220-230V
(L)
28
50/60Hz 220-240/220-230V (H) 50/60Hz 220-240/220-230V (H)
50/60Hz 220-240/220-230V (L)50/60Hz 220-240/220-230V (L)
HeatingCooling
3D096262
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVEBANDSOUNDPRESSURELEVEL
dB(0dB=0.0002
bar)
70
60
20
30
50
40
63 125
OCTAVE BAND CENTER FREQUENCY (Hz)
250 500 1000 2000 4000 8000
OVER ALL (dB )
SCALE
A
( B.G.N IS ALREADY RECTIFIED )
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz)
125 250 500 1000 2000 4000 8000
OCTAVEBANDSOUNDPRESSURELEVEL
dB(0dB=0.0002
bar)
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
COOLING HEATING
220-240/220-230V 50/60Hz
STANDARD EXTERNAL STATIC PRESSURE
50/60Hz 220-240/220-230V (H)
50/60Hz 220-240/220-230V (L)
Cooling
40
50/60Hz220-240/220-230V
(H)
29
50/60Hz220-240/220-230V
(L)
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL (dB )
SCALE
A
( B.G.N IS ALREADY RECTIFIED )
220-240/220-230V 50/60Hz
STANDARD EXTERNAL STATIC PRESSURE
50/60Hz 220-240/220-230V (H)
50/60Hz 220-240/220-230V (L)
Heating
40
50/60Hz220-240/220-230V
(H)
30
50/60Hz220-240/220-230V
(L)
3D096263A
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCT
AVEBANDSOUNDPRESSURELEVEL
dB(0dB=0.0002
bar)
70
60
20
30
50
40
63 125
OCTAVE BAND CENTER FREQUENCY (Hz)
250 500 1000 2000 4000 8000
OVER ALL (dB )
SCALE
A
( B.G.N IS ALREADY RECTIFIED )
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz)
125 250 500 1000 2000 4000 8000
OCT
AVEBANDSOUNDPRESSURELEVEL
dB(0dB=0.0002
bar)
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
COOLING HEATING
220-240/220-230V 50/60Hz
STANDARD EXTERNAL STATIC PRESSURE
41 30
50/60Hz 220-240/220-230V (H)
50/60Hz 220-240/220-230V (L)
Cooling
50/60Hz220-240/220-230V
(L)
50/60Hz220-240/220-230V
(H)
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL (dB )
SCALE
A
( B.G.N IS ALREADY RECTIFIED )
220-240/220-230V 50/60Hz
STANDARD EXTERNAL STATIC PRESSURE
41 31
50/60Hz 220-240/220-230V (H)
50/60Hz 220-240/220-230V (L)
Heating
50/60Hz220-240/220-230V
(L)
50/60Hz220-240/220-230V
(H)
3D096264A
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
18/80
Sound Level EDVN041518
16 Split Type Air Conditioners FTXM-H Series
9.3 Outdoor Unit
RXM20HVMV
RXM25HVMV
RXM35HVMV
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVEBANDSOUNDPRESSURE
LEVEL
dB(0dB=0.0002
bar)
70
60
20
30
50
40
63 125
OCTAVE BAND CENTER FREQUENCY (Hz)
250 500 1000 2000 4000 8000
OVER ALL (dB )
SCALE
A( B.G.N IS ALREADY RECTIFIED )
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz)
125 250 500 1000 2000 4000 8000
OCTAVEBANDSOUNDPRESSURE
LEVEL
dB(0dB=0.0002
bar)
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL (dB )
SCALE
A( B.G.N IS ALREADY RECTIFIED )
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
COOLING HEATING
220-240/220-230V 50/60Hz 220-240/220-230V 50/60Hz
50/60Hz220-240/220-230V (H)
50/60Hz220-240/220-230V (H)
4848
Cooling Heating
3D096257
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVEBANDSOUNDPRESSURELEVEL
dB(0dB=0.0002
bar)
70
60
20
30
50
40
63 125
OCTAVE BAND CENTER FREQUENCY (Hz)
250 500 1000 2000 4000 8000
OVER ALL (dB )
SCALE
A
( B.G.N IS ALREADY RECTIFIED )
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz)
125 250 500 1000 2000 4000 8000
OCTAVEBANDSOUNDPRESSURELEVEL
dB(0dB=0.0002
bar)
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL (dB )
SCALE
A
( B.G.N IS ALREADY RECTIFIED )
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
COOLING HEATING
220-240/220-230V 50/60Hz220-240/220-230V 50/60Hz
50/60Hz220-240/220-230V (H)
50/60Hz220-240/220-230V (H)
4848
Cooling Heating
3D096258
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCT
AVEBANDSOUNDPRESSURELEVEL
dB(0dB=0.0002
bar)
70
60
20
30
50
40
63 125
OCTAVE BAND CENTER FREQUENCY (Hz)
250 500 1000 2000 4000 8000
OVER ALL (dB )
SCALE
A
( B.G.N IS ALREADY RECTIFIED )
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz)
125 250 500 1000 2000 4000 8000
OCT
AVEBANDSOUNDPRESSURELEVEL
dB(0dB=0.0002
bar)
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL (dB )
SCALE
A
( B.G.N IS ALREADY RECTIFIED )
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
NC-30
NC-50
NC-20
NC-60
NC-70
NC-40
COOLING HEATING
220-240/220-230V 50/60Hz 220-240/220-230V 50/60Hz
50/60Hz220-240/220-230V (H)
50/60Hz220-240/220-230V (H)
4848
Cooling Heating
3D096259
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
19/80
EDVN041518 Electric Characteristics
Split Type Air Conditioners FTXM-H Series 17
10.Electric Characteristics
3D096254A
Indoor Unit Outdoor UnitPower Supply Compressor OFM IFM
Hz - Volts Voltage Range MCA MFA RHz RLA W FLA W FLA
FTXM20HVMV RXM20HVMV
50 Hz - 220 VMax. 50 Hz, 264 VMin. 50 Hz, 198 V
8.0 15 36
2.4
20
0.22
16
0.19
50 Hz - 230 V 2.3 0.21 0.1850 Hz - 240 V 2.2 0.20 0.17
60 Hz - 220 V Max. 60 Hz, 253 VMin. 60 Hz, 198 V
2.5 0.22 0.19
60 Hz - 230 V 2.4 0.21 0.18
FTXM25HVMV RXM25HVMV
50 Hz - 220 VMax. 50 Hz, 264 VMin. 50 Hz, 198 V
8.0 15 48
2.6
20
0.22
16
0.19
50 Hz - 230 V 2.5 0.21 0.18
50 Hz - 240 V 2.4 0.20 0.17
60 Hz - 220 V Max. 60 Hz, 253 VMin. 60 Hz, 198 V
2.7 0.22 0.19
60 Hz - 230 V 2.6 0.21 0.18
FTXM35HVMV RXM35HVMV
50 Hz - 220 VMax. 50 Hz, 264 VMin. 50 Hz, 198 V
8.0 15 74
4.2
20
0.22
16
0.27
50 Hz - 230 V 4.0 0.21 0.26
50 Hz - 240 V 3.8 0.20 0.24
60 Hz - 220 V Max. 60 Hz, 253 VMin. 60 Hz, 198 V
4.3 0.22 0.2760 Hz - 230 V 4.1 0.21 0.26
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.Indoor temp. 27CDB / 19CWBOutdoor temp. 35CDB.
2. Maximum allowable voltage variation between phases is 2%.3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leakdetector capable of handling high harmonics must be used inorder to prevent malfunctioning of the earth leak detector.)
MFA : Max. fuse amps (A)
RHz : Rated operating frequency (Hz)
RLA : Rated load amps (A)
OFM : Outdoor fan motor
IFM : Indoor fan motor
W : Fan motor rated output (W)
FLA : Full load amps (A)
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
20/80
Installation Manual EDVN041518
18 Split Type Air Conditioners FTXM-H Series
11.Installation Manual
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
21/80
EDVN041518 Installation Manual
Split Type Air Conditioners FTXM-H Series 19
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
22/80
Installation Manual EDVN041518
20 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
23/80
EDVN041518 Installation Manual
Split Type Air Conditioners FTXM-H Series 21
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
24/80
Installation Manual EDVN041518
22 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
25/80
EDVN041518 Installation Manual
Split Type Air Conditioners FTXM-H Series 23
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
26/80
Installation Manual EDVN041518
24 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
27/80
EDVN041518 Installation Manual
Split Type Air Conditioners FTXM-H Series 25
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
28/80
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
29/80
EDVN041518 Installation Manual
Split Type Air Conditioners FTXM-H Series 27
3P383016-9A
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
30/80
Operation Manual EDVN041518
28 Split Type Air Conditioners FTXM-H Series
12.Operation Manual
12.1 English
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
31/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 29
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
32/80
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
33/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 31
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
34/80
Operation Manual EDVN041518
32 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
35/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 33
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
36/80
Operation Manual EDVN041518
34 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
37/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 35
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
38/80
Operation Manual EDVN041518
36 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
39/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 37
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
40/80
Operation Manual EDVN041518
38 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
41/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 39
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
42/80
Operation Manual EDVN041518
40 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
43/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 41
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
44/80
Operation Manual EDVN041518
42 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
45/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 43
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
46/80
Operation Manual EDVN041518
44 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
47/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 45
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
48/80
Operation Manual EDVN041518
46 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
49/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 47
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
50/80
Operation Manual EDVN041518
48 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
51/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 49
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
52/80
Operation Manual EDVN041518
50 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
53/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 51
EN_3P383015-6A
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
54/80
Operation Manual EDVN041518
52 Split Type Air Conditioners FTXM-H Series
12.2 Vietnamese
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
55/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 53
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
56/80
Operation Manual EDVN041518
54 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
57/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 55
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
58/80
Operation Manual EDVN041518
56 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
59/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 57
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
60/80
Operation Manual EDVN041518
58 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
61/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 59
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
62/80
Operation Manual EDVN041518
60 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
63/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 61
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
64/80
Operation Manual EDVN041518
62 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
65/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 63
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
66/80
Operation Manual EDVN041518
64 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
67/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 65
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
68/80
Operation Manual EDVN041518
66 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
69/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 67
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
70/80
Operation Manual EDVN041518
68 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
71/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 69
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
72/80
Operation Manual EDVN041518
70 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
73/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 71
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
74/80
Operation Manual EDVN041518
72 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
75/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 73
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
76/80
Operation Manual EDVN041518
74 Split Type Air Conditioners FTXM-H Series
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
77/80
EDVN041518 Operation Manual
Split Type Air Conditioners FTXM-H Series 75
VN_3P383015-6A
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
78/80
Optional Accessories EDVN041518
76 Split Type Air Conditioners FTXM-H Series
13.Optional Accessories
13.1 Option List
13.1.1 Indoor Unit
13.1.2 Outdoor Unit
Option Name Model Name
1 Titanium apatite photocatalytic air-purifying filter (without frame) KAF970A462 Remote controller loss prevention with chain KKF917A4
Option Name Model Name
1 Air direction adjustment grille KPW937B4
2 Drain plug KKP937A4
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
79/80
-
7/26/2019 Edvn041518 - Ftxm Hvmv - r32
80/80
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Warning