Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet 1 No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore: Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected] Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies DC MACHINES : - Lap Winding Wave Winding (1) Coil Span : = = (2) Back Pitch = = (3) Commutator Pitch = 1 for Progressive winding = -1 for Retrogressive winding = for Progressive winding = - for Restrogressive winding ( Must be integer) (4) Front Pitch = +2 for Progressive winding = -2 for Retrogressive winding = - (5) Parallel Paths A = P A = 2 (6) Conductor Current = = (7) No of brushes No of brushes = A = P No of brushes = 2 S = No of commutator segments P = No of poles U = No of coil sides / No of poles = C = No of coils on the rotor A = No of armature parallel paths = Armature current Distribution factor ( ) = = = Pitch factor ( ) = *100% Armature mmf/Pole (Peak) , A = AT (Compensating Winding) = *

Upload: rt

Post on 22-Oct-2015

37 views

Category:

Documents


5 download

DESCRIPTION

pdf

TRANSCRIPT

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

1

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

DC MACHINES : -

Lap Winding Wave Winding

(1) Coil Span : =

=

(2) Back Pitch = =

(3) Commutator Pitch = 1 for Progressive winding = -1 for Retrogressive winding

=

for Progressive winding

= -

for Restrogressive winding ( Must be integer)

(4) Front Pitch = +2 for Progressive winding = -2 for Retrogressive winding

= -

(5) Parallel Paths A = P A = 2

(6) Conductor Current =

=

(7) No of brushes No of brushes = A = P No of brushes = 2

S = No of commutator segments

P = No of poles

U = No of coil sides / No of poles =

C = No of coils on the rotor

A = No of armature parallel paths

= Armature current

Distribution factor ( ) =

=

=

Pitch factor ( ) =

*100%

Armature mmf/Pole (Peak) , A =

AT (Compensating Winding) =

*

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

2

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

AT(Inter pole) = A +

Where = Flux density in inter pole airgap

= length of inter pole airgap ,

No of turns in each interpole , =

The no of compensating conductor per pole, /pole =

(

)

The Mechanical power that is converted is given by =

Where T = Induced torque

= Angular speed of the machines rotor

The resulting electric power produced =

The power balance equation of the DC Machine is =

The induced emf in the armature is =

Torque developed in Dc machine , =

Where = Flux\pole , Z = No of armature conductors , P = No of poles , N = Speed in rpm ,

A = No of armature parallel paths, rmature current

The terminal voltage of the DC generator is given by = -

The terminal voltage of the DC motor is given by = +

Speed regulation of dc machine is given by ,SR =

* 100 % =

* 100 %

Voltage regulation , VR =

* 100 %

Shunt Generator:

For a shunt generator with armature induced voltage Ea, armature current Ia and

armature resistance Ra, the terminal voltage V is:

V = Ea - IaRa

The field current I f for a field resistance R f is:

I f = V / R f

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

3

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

The armature induced voltage Ea and torque T with magnetic flux at angular

speed are:

Ea = k f = km

T = k fIa = kmIa where k f and km are design coefficients of the machine. Note that for a shunt generator: - induced voltage is proportional to speed, - torque is proportional to armature current.

The airgap power Pe for a shunt generator is:

Pe = T = EaIa = km Ia Series Generator:

For a series generator with armature induced voltage Ea, armature current Ia, armature resistance Ra and field resistance R f, the terminal voltage V is: V = Ea - ( IaRa + IaR f )= Ea - Ia(Ra + R f) The field current is equal to the armature current.

The armature induced voltage Ea and torque T with magnetic flux at angular

speed are:

Ea = k f Ia = km Ia

T = k fIa2 = kmIa

2

where k f and km are design coefficients of the machine.

Note that for a series generator: - induced voltage is proportional to both speed and armature current, - torque is proportional to the square of armature current, - armature current is inversely proportional to speed for a constant Ea

The airgap power Pe for a series generator is:

Pe = T = EaIa = km Ia2

Cumulatively compounded DC generator : - ( long shunt)

(a) = +

(b) = - ( + )

(c) =

= shunt field current

(d) The equivalent effective shunt field current for this machine is given by

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

4

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

= +

- (

)

Where = No of series field turns

= No of shunt field turns

Differentially compounded DC generator : - ( long shunt)

(a) = +

(b) = - ( + )

(c) =

= shunt field current

(d) The equivalent effective shunt field current for this machine is given by

= -

- (

)

Where = No of series field turns

= No of shunt field turns

Shunt Motor:

For a shunt motor with armature induced voltage Ea, armature current Ia and armature resistance Ra, the terminal voltage V is: V = Ea + IaRa The field current I f for a field resistance R f is: I f = V / R f

The armature induced voltage Ea and torque T with magnetic flux at angular

speed are:

Ea = k f = km

T = k fIa = kmIa where k f and km are design coefficients of the machine.

Note that for a shunt motor: - induced voltage is proportional to speed, - torque is proportional to armature current.

The airgap power Pe for a shunt motor is:

Pe = T = EaIa = km Ia

The speed of the shunt motor , =

-

T

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

5

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Where K =

Series Motor :

For a series motor with armature induced voltage Ea, armature current Ia, armature resistance Ra and field resistance R f, the terminal voltage V is: V = Ea + IaRa + IaR f = Ea + Ia(Ra + R f) The field current is equal to the armature current.

The armature induced voltage Ea and torque T with magnetic flux at angular

speed are:

Ea = k f Ia = km Ia

T = k fIa2 = kmIa

2

where k f and km are design coefficients of the machine.

Note that for a series motor: - induced voltage is proportional to both speed and armature current, - torque is proportional to the square of armature current, - armature current is inversely proportional to speed for a constant Ea

The airgap power Pe for a series motor is:

Pe = T = EaIa = km Ia2

Losses:

constant losses (P k) = Pw f + Pi o

Where, = No of load core loss

= Windage & friction loss

Variable losses ( ) = + +

where = Copper losses =

= Stray load loss = α

= Brush Contact drop = , Where = Brush voltage drop

The total machine losses , = + +

Efficiency

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

6

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

The per-unit efficiency of an electrical machine with input power Pin, output power Pout and power loss Ploss is:

= Pout / Pin = Pout / (Pout + Ploss) = (Pin - Ploss) / Pin

Rearranging the efficiency equations:

Pin = Pout + Ploss = Pout / = Ploss / (1 - )

Pout = Pin - Ploss = Pin = Ploss / (1 - )

Ploss = Pin - Pout = (1 - )Pin = (1 - )Pout /

Temperature Rise:

The resistance of copper and aluminium windings increases with temperature, and the relationship is quite linear over the normal range of operating temperatures. For a linear relationship, if the winding resistance is R1 at

temperature 1 and R2 at temperature 2, then:

R1 / (1 - 0) = R2 / (2 - 0) = (R2 - R1) / (2 - 1)

where 0 is the extrapolated temperature for zero resistance.

The ratio of resistances R2 and R1 is:

R2 / R1 = (2 - 0) / (1 - 0)

The average temperature rise of a winding under load may be estimated from

measured values of the cold winding resistance R1 at temperature 1 (usually

ambient temperature) and the hot winding resistance R2 at temperature 2, using:

= 2 - 1 = (1 - 0) (R2 - R1) / R1

Rearranging for per-unit change in resistance Rpu relative to R1:

Rpu = (R2 - R1) / R1 = (2 - 1) / (1 - 0) = / (1 - 0)

.Copper Windings:

The value of 0 for copper is - 234.5 °C, so that:

= 2 - 1 = (1 + 234.5) (R2 - R1) / R1

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

7

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

If 1 is 20 °C and is 1 degC:

Rpu = (R2 - R1) / R1 = / (1 - 0) = 1 / 254.5 = 0.00393

The temperature coefficient of resistance of copper at 20 °C is 0.00393 per degC.

Aluminium Windings:

The value of 0 for aluminium is - 228 °C, so that:

= 2 - 1 = (1 + 228) (R2 - R1) / R1

If 1 is 20 °C and is 1 degC:

Rpu = (R2 - R1) / R1 = / (1 - 0) = 1 / 248 = 0.00403

The temperature coefficient of resistance of aluminium at 20 °C is 0.00403 per degC.

Dielectric Dissipation Factor:

If an alternating voltage V of frequency f is applied across an insulation system comprising capacitance C and equivalent series loss resistance RS, then the voltage VR across RS and the voltage VC across C due to the resulting current I are: VR = IRS VC = IXC V = (VR

2 + VC2)½

The dielectric dissipation factor of the insulation system is the tangent of the

dielectric loss angle between VC and V:

tan = VR / VC = RS / XC = 2fCRS

RS = XCtan = tan / 2fC

The dielectric power loss P is related to the capacitive reactive power QC by:

P = I2RS = I2XCtan = QCtan

The power factor of the insulation system is the cosine of the phase

angle between VR and V:

cos = VR / V

so that and are related by:

+ = 90°

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

8

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

tan and cos are related by:

tan = 1 / tan = cos / sin = cos / (1 - cos2)½

so that when cos is close to zero, tan cos

TRANSFORMERS:

Gross cross sectional area = Area occupied by magnetic material + Insulation

material.

Net cross sectional area = Area occupied by only magnetic material excluding area

of insulation material.

Hence for all calculations, net cross sectional area is taken since (flux) majorly

flows in magnetic material.

Specific weight of t/f =

Stacking/iron factor :- ( ) =

is always less than 1

Gross c.s Area = = length × breadth

Net c.s Area = =

Utilization factor of transformer core =

U.F of cruciform core = 0.8 to

0.85

Flux =

=

According to faradays second law

Transformer emf equations :-

= 4.44 (1)

= 4.44 (2)

Instantaneous value

of emf in primary

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

9

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Emf per turn in =

= 4.44

Emf per turn in

= 4.44

⟹ Emf per turn on both sides of the transformer is same

Transformation ratio = K =

Turns ratio =

For an ideal two-winding transformer with primary voltage V1 applied across N1 primary turns and secondary voltage V2 appearing across N2 secondary turns: V1 / V2 = N1 / N2

The primary current I1 and secondary current I2 are related by: I1 / I2 = N2 / N1 = V2 / V1

For an ideal step-down auto-transformer with primary voltage V1 applied across (N1 + N2) primary turns and secondary voltage V2 appearing across N2 secondary turns: V1 / V2 = (N1 + N2) / N2

The primary (input) current I1 and secondary (output) current I2 are related by: I1 / I2 = N2 / (N1 + N2) = V2 / V1.

For a single-phase transformer with rated primary voltage V1, rated primary current I1, rated secondary voltage V2 and rated secondary current I2, the voltampere rating S is: S = V1I1 = V2I2

For a balanced m-phase transformer with rated primary phase voltage V1, rated primary current I1, rated secondary phase voltage V2 and rated secondary current I2, the voltampere rating S is: S = mV1I1 = mV2I2

The primary circuit impedance Z1 referred to the secondary circuit for an ideal transformer with N1 primary turns and N2 secondary turns is: Z12 = Z1(N2 / N1)

2

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

10

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

During operation of transformer :-

= constant

Equivalent ckt of t/f under N.L condition :-

No load current =

No load power = Iron losses.

Transferring from to :-

=

From to :-

No load /shunt branch.

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

11

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Total resistance ref to primary =

/

Total resistance ref to secondary =

Total Cu loss =

Or

Per unit resistance drops :-

P.U primary resistance drop =

P.U secondary resistance drop =

Total P.U resistance drop ref to =

Total P.U resistance drop ref to =

The P.U resistance drops on both sides of the t/f is same

Losses present in transformer :-

1. Cu losses in t/f:

Total Cu loss =

=

=

Rated current on

Similarly current on =

Cu losses or

. Hence there are called as variable losses.

1. Copper losses

2. Iron losses

3. Stray load losses

4. Dielectric losses

major losses

minor losses

t/f windings

t/f core cu parts

Iron parts

insulating materials.

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

12

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

P.U Full load Cu loss =

=

If VA rating of t/f is taken as base then P.U Cu loss as remaining terms are constant.

P.U Cu loss at x of FL = FL Cu loss

=

∴ P.U Resistance drop = P.U FL cu loss

% FL Cu loss = % R = % Resistance drop.

Iron (or) Core losses in t/f :-

1. Hysteresis loss :

Steinmetz formula :-

Where

= stienmetz coefficient

= max. flux density in transformer core.

f = frequency of magnetic reversal = supply freq.

v = volume of core material

x = Hysteresis coeff (or) stienmetz exponent

= 1.6 (Si or CRGo steel)

2. Eddycurrent loss:

Eddy current loss ,(

As area decreases in laminated core resistance increases as a result conductivity decreases.

Constant Supply freq

thickness of laminations.

(it is a function of )

Area under one hysteresis loop. . f . v

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

13

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

During operation of transformer :-

Case (i) :-

= constant, = const.

Case (ii) :-

constant, const.

P.U iron loss :-

P.U iron loss =

As VA rating is choosen as base then the P.U iron loss are also constant at all load conditions.

To find out constant losses :-

= Losses in t/f under no load condition

= Iron losses + Dielectric loss + no load primary loss ( )

Constant losses =

Where , = LV winding resistance.

To find out variable losses :-

= Loss in t/f under S.C condition

Const.

When = const.

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

14

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

= F.L Cu loss + stray load losses (Cu and Iron) + Iron losses in both wdgs

Variable losses = Iron losses corresponding to

O.C test :-

rated

S.C test :-

∴ Variable losses =

Under the assumption that small amount of iron losses corresponds to and stray load

losses are neglected the wattmeter reading in S.C test can be approximately taken as F.L

Cu losses in the transformer.

F.L Cu loss

Efficiency :-

=

=

O.C test S.C test

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

15

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Transformer efficiency =

Efficiency = =

Total losses in transformer =

output

Condition for maximum effieciency is, Cu losses = Iron losses

Total losses at = 2

%load at which maximum efficiency occurs % x =

*100 %=

*100 %

KVA corresponding to = F.L KVA

Voltage drop in t/f at a Specific load p.f =

% Voltage regulation =

100

=

P.U resistance P.U reactance

% Regulation = × 100

Condition for max. regulation :-

% regulation = (% R) cos

= 0

Tan

lagging

At maximum regulation

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

16

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

=

Value of maximum regulation :-

% Regulation = (% R) cos

At max. regulation cos

Sin

max. % regulation = (% R)

=

=

max. % regn = % Z

= % of rated voltage required to produce rated short ckt current

.

Condition for zero regulation :-

If the voltage regulation in the t/f is zero, the t/f voltages are maintained at their nominal

values even under load condition

% Regn = (% R) cos

For zero regulation occurs at leading p.f’s

(% R) cos sin = 0

Tan

leading.

At zero regulation condition :

Regulation at x of FL = x [% R cos X sin ]

= x × F.L regn

Regulation at U.P.F:-

Regulation at UPF = % R

= % F.L Cu loss

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

17

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Scott Connection:

= 0.866

= 0.577

= 0.866 0.577 = 0.289

= 0.577 0.289

= 2 : 1

If a neutral pt is located on 3 side, such that, voltage between any terminal to that neutral

point is 0.577 then such neutral point divides the primary of teaser transformer in the ratio

of 2 : 1

Location of neutral point from top = 0.866

Location of neutral point from bottom = 0.866

Operation of Scott Connection with 2 balanced load at UPF :-

Teaser t/f :-

Let

Main t/f

86.6%

0.289

2

:

1

M

N

0.866 0.577

A

B

C

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

18

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Let

Capacity of Scott Connection :-

↙ ↓

Vol. rating of 1 – t/f Current rating of 1 – t/f

Utilization factor =

=

= 0.866

Utilization factor of Scott connection with 2 identical 1 – t/f’s is 86.6%

AUTO TRANSFORMER:

Primary applied voltage, = Secondary voltage referred to primary + primary leakage impedance

drop + secondary leakage impedance drop ref. to primary.

K of auto transformer =

I/P KVA =

= 1 –

= 1 – K

∴ (KVA) induction = (1 – K) i/p KVA

(KVA) conduction = I/p KVA –

I/p KVA

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

19

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Wt. of conductor in section AB of auto t/f

Wt of conductor in section BC of auto t/f

∴ Total wt. of conductor in auto t/f is

Total wt. of conductor in 2 wdg transformer

= 1 –

= 1 – K

Wt. of conductor in auto t/f = (1 – K) (wt. of conductor in 2 wdg t/f)

Thus saving of conductor material if auto – t/f is used} = K × {conductor wt in 2 wdg transformer.

.

SYNCHRONOUS MACHINES:

Principle of operation :-

Whenever a conductor cuts the magnetic flux, an emf is induced in that conductor”

Faraday’s law of electromagnetic induction.

Coil span () :- It is the distance between two sides of the coil. It is expressed in terms of

degrees, pole pitch, no. of slots / pole etc

Pole pitch :- It is the distance between two identical points on two adjacent poles.

Pole pitch is always 180° e = slots / pole.

Slot pitch or slot angle :- (T)Slot angle is the angle for each slot.

For a machine with ‘P’ poles and ‘s’ no. of slots, the slot angle = γ =

γ =

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

20

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Pitch factor or coil span factor or chording factor :- ( )

=

=

Pitch factor for harmonic i.e,

chording angle to eliminate harmonics (α)=

coil spam to eliminate harmonics ,() = 180

Distribution factor | spread factor | belt factor | breadth factor(kd) :-

=

=

Kd =

γ

γ

The distribution factor for uniformly distributed winding is

For harmonic, =

γ

γ

To eliminate harmonics ,phase spread (mγ) =

Generally, KVA rating, power output kd and (induce emf) .

=

= 1.15

= cos /2

=

=

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

21

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

= 1.06

= 1.5

1.414

Speed of space harmonics of order (6k ± 1) is

where = synchronous speed =

The order of slot harmonics is

where S = no. of slots , P = no. of poles

Slot harmonics can be eliminated by skewing the armature slots and fractional slot winding.

The angle of skew = = γ (slot angle)

= 2 harmonic pole pitches

= 1 slot pitch.

Distribution factor for slot harmonics,

Is

γ

γ

i.e., same that of fundamental

Pith factor for slot harmonics,

=

The synchronous speed Ns and synchronous angular speed s of a machine with p pole pairs running on a supply of frequency fs are:

s = 2fs / p

Slip S =

Where

= synchronous speed

The magnitude of voltage induced in a given stator phase is =

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

22

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Where K = constant

The output power Pm for a load torque Tm is:

Pm = sTm

The rated load torque TM for a rated output power PM is:

TM = PM / s = PM p/ 2fs = 120PM / 2Ns

Synchronous Generator:

For a synchronous generator with stator induced voltage Es, stator current Is and synchronous impedance Zs, the terminal voltage V is:

V = E - IsZs = Es - Is(Rs + jXs)

where Rs is the stator resistance and Xs is the synchronous reactance

E =

+ lag p.f

leading p.f.

Synchronous Motor:

For a synchronous motor with stator induced voltage Es, stator current Is and synchronous impedance Zs, the terminal voltage V is:

V = Es + IsZs = Es + Is(Rs + jXs) where Rs is the stator resistance and Xs is the synchronous reactance

Voltage regulation :

% regulation =

100

E – V =

∴ % regulation =

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

23

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

=

100

∴ regulation

∴ As increases, voltages regulation increases.

Condition for zero | min. voltage regulation is, Cos (θ + ) =

Condition for max. Voltage regulation is, = θ

Short circuit ratio (SCR) =

SCR

Voltage regulation Armature reaction

∴ SCR

∴ Small value of SCR represent poor regulation.

But reluctance Air gap

Armature reaction

∴ SCR

Airgap length

∴ machine size SCR.

Cost SCR

Power =

P

SCR

Air gap length SCR

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

24

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

∴ Large value of SCR represent more power output.

Synchronizing power coefficient or stability factor is given as

=

=

is a measure of stability

∴ stability

But

SCR

Stability SCR Air gap length

When the stator mmf is aligned with the d – axis of field poles then flux perpole is set up

and the effective reactance offered by the alternator is .

= Direct axis reactance

When the stator mmf is aligned with the q – axis of field poles then flux per pole is set up

and the effective reactance offered by the alternator is .

=

= Quadrature axis reactance

Cylindrical rotor Synchronous machine ,

The per phase power delivered to the infinite bus is given by P =

sin δ

Salient pole synchronous machine ,

The per phase power delivered to the infinite bus is given by

P =

δ

δ

Power SCR

∴ Stability SCR

∴ Stability Air gap length

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

25

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Condition for max. power:-

For cylindrical rotor machine :-

At constant and , the condition for max. power is obtained by putting

= 0

= 0

Cos δ = 0

δ = 90

Hence maximum power occurs at δ = 90

For salient – pole synchronous machine :-

= 0

= 0

Cos δ =

The value of load angle is seed to be less than 90°.

∴ max. power occurs at δ < 90

Synchronizing power = . ∆ δ.

=

.

Synchronizing torque =

.

Power flow in Alternator :-

Complex power = S = P + jQ = V

Where Active power flow (P) =

;

Reactive power flow (Q) =

;

Condition for max. power output :-

P =

= 0 for max power condition

ie – δ = 0

θ =

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

26

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

If = 0; = δ = 90 ; then max power is given by

SYNCHRONOUS MOTORS:

Speed regulation =

=

= 0%

Slip S =

= 0%

The speed can be controlled by varying the frequency

ratio control is preferred for rated torque operation

Power flow in synchronous motor is given by

complex power i/p s = p + jQ = V

where P = Resl power flow , Q = Reactive power flow

:

:

If = 0 ;

Condition for max power :-

= 0 0 +

Sin ( + δ) = 0 = sin 180

=

cos θ

=

Q =

8 0

P =

Q =

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

27

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Expression for mechanical power developed :-

Mechanical power developed = = active component +

Condition for max. mechanical power developed :-

δ

δ = 0

Sin ( – δ) = 0 = sin 0

δ =

This is the expression for the mechanical power developed interms of load angle and the

internal machine angle , for constant voltage and constant E i.e., excitation

Gross Torque =

=

synchronous speed in r.p.m

∴ Tg =

Condition for excitation when motor develops :-

For max power developed is

= 0

Condition for excitation when motor develops is

The corresponding value of max. power is

=

Power flow in synchronous motors :-

Tg =

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

28

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

For leading p.f

tan δ =

The mechanical power developed per phase is given by,

s

δ

δ

INDUCTION MACHINES:

The power flow diagram of 3 – induction motor is

The slip of induction machine is (S) =

Mechanical power

developed,

Rotor i/p power

= airgap power

Power i/p to stator

from mains

Power of

rotor shaft

Windage

loss

Friction loss

at bearings

and sliprings

of (if any)

Rotor core loss

(negligible for

small slips)

Rotor

R

loss

Stator

core

loss

Stator

R

loss

(input)

Stator

copper loss

3

Mechanical power

developed in armature

= 3 . cos

( ± )

+ ve lead

–ve for lag

=

2 π Ns

60.

output

Friction

and Iron

losses

=

2π Ns

60

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

29

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

=

Where is synchronous speed in rpm

is synchronous speed in rps

= S

∴ Rotor frequency,

For an induction machine with rotor resistance Rr and locked rotor leakage reactance Xr, the rotor impedance Zr at slip s is:Zr = Rr + jsXr The stator circuit equivalent impedance Zrf for a rotor / stator frequency ratio s is: Zrf = Rrs / s + jXrs

For an induction motor with synchronous angular speed s running at angular speed m and slip s, the airgap transfer power Pt, rotor copper loss Pr and gross output power Pm for a gross output torque Tm are related by:

Pt = sTm = Pr / s = Pm / (1 - s) Pr = sPt = sPm / (1 - s)

Pm = mTm = (1 - s)Pt The power ratios are: Pt : Pr : Pm = 1 : s : (1 - s)

The gross motor efficiency m (neglecting stator and mechanical losses) is:

m = Pm / Pt = 1 - s

Rotor emf, Current Power :- At stand still, the relative speed between rotating magnetic field and rotor conductors is

synchronous speed ; under this condition let the per phase generated emf in rotor circuit

be .

∴ = 4.44

= 4.44

= Rotor winding factor

But during running conditions the frequency of the rotor becomes, running with speed

S

∴ Emf under running conditions is

E =

= S

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

30

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Rotor leakage reactance = 2 (Rotor frequency)

(Rotor leakage Inductance)

∴ Rotor leakage reactance at stand still = 2

=

Rotor leakage reactance at any slips = 2

Rotor leakage impedance at stand still

=

At any slip s, rotor

Per phase rotor current at stand still

=

Per phase rotor current at any slip s is given by

The rotor current lags the rotor voltage by rotor power factor angle given by

Per phase power input to rotor is

=

= s

=

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

31

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

`

=

=

is the power transferred from stator to rotor across the air gap. There fore is called air

gap power

=

= (Rotor ohmic loss) + Internal mechanical power developed in rotor ( )

= S

∴ =

Rotor ohmic loss =

= S

Internal (or gross) torque developed per phase is given by

Electromagnetic torque can also be expressed as

Power available at the shaft can be obtained from as follows.

Output or shaft power, Mechanical losses

Mechanical losses implies frication and windage losses

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

32

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Rotor ohmic loss – Friction and windage losses

= Net mechanical power output or net power output

Output or shaft torque

If the stator input is known. Then air gap power is given by

stator power input – stator loss – stator core loss.

Ratio of Rotor input power, rotor copper losses and gross mechanical output is

:

:

∴ Rotor copper losses = S × Rotor input

Gross mechanical output =(1 – S) × Rotor input.

Rotor copper losses = (Gross Mechanical output) ×

Efficiency of the rotor is approximately

Equal to

=

= 1 – S

= 1

=

Total torque is

m is the number of stator phases.

Torque equation can be written as

rotor input per phase.

Thus the slip at which maximum torque occurs is given by

Substituting the value of maximum slip in the torque equation, gives maximum torque

1 : S : (1 – S)

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

33

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

If stator parameters are neglected then applying maximum transfer theorem to then

=

Slip corresponding to maximum torque is

(Breakdown slip)

is the stalling speed at the maximum torque

Starting torque:- At starting, slip S = 1.00, starting torque is given by

Test =

Motor torque in terms of :

The torque expression of an induction motor can also be expressed in terms of maximum

torque and dimension less ratio

. In order to get a simple and approximate

expression, stator resistance , or the stator equivalent resistance , is neglected.

Since r1 or Re is neglected

The slip at which maximum torque occurs is

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

34

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Power slip characteristics :-

The total internal mechanical power developed is

Maximum power transfer theorem is invoked again to obtain maximum value of internal

mechanical power developed. Since per phase is the power delivered to

, internal

mechanical power developed is maximum, when

In order to get maximum power ,substitute

, in place of

in power equation

In order to get maximum power output from an induction generator, the rotor must be deiven

at a speed given by

Losses and efficiency :- There are three cases in iron losses.

Case (i) : If the ratio of voltage to frequency is constant and flux is also constant then

Iron loss = Hysteresis loss + eddy current loss

Given

is constant. As

is constant

∴ and

Case (ii) : If the ratio of voltage to frequency is not constant and flux is also not constant

≠ const

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

35

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Case (iii) : If frequency is constant and voltage is variable then

=

Short circuit current with normal voltage applied to stator is

I = short circuit current with normal voltage

= short circuit current with voltage .

Power factor on short circuit is found from

As is approximately equal to full load copper losses

The blocked rotor impedance is

∴ Blocked rotor reactance =

Efficiency of Induction machines :-

Generally efficiency =

∴ Efficiency of Induction motor =

∴ Efficiency of Induction generator =

Squirrel cage rotor:

Stator Cu loss = 3

I =

Cos =

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

36

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

∴ Rotor Cu loss =

Wound rotor

Direct – on line (across the line) starting :-

The relation between starting torque and full load torque is

=

The above equation valids of rotor resistance remains constant.

Where

Per phase short – circuit current at stand still (or at starting) is,

Where

Here shunt branch parameters of equivalent circuit are neglected.

Therefore, for direct switching,

.

Stator resistor (or reactor) starting :-

Since per phase voltage is reduced to xv, the per phase starting current is given by

As be fore

=

In an induction motor, torque

Institute of Engineering Studies (IES,Bangalore) Electrical Machines Formula Sheet

37

No.1 Training center for GATE/IES/JTO/PSUs in Bangalore @ Malleshwaram & Jayanagar of Bangalore:

Ph: 0 99003 99699/ 0 97419 00225 / 080-32552008 Email : [email protected]

Site: www.onlineIES.com Google+: www.gplus.to/onlineies FB: www.facebook.com/onlineies

Auto transformer starting :-

Per phase starting current from the supply mains is

Star – delta method of starting :

=

∴ star delta starter also reduces the starting torque to one – third of that produced by direct switching

in delta.

With star – delta starter, a motor behaves as if it were started by an auto transformer starter with x =

= 0.58 i.e with 58% tapping.

=

=